Lennox ZHA036, ZHA048, ZHA060 Installation Instructions Manual

Litho U.S.A.
2015
INSTALLATION INSTRUCTIONS
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser vice must be performed by a licensed professional HVAC installer or equivalent or service agency.
Danger of sharp metallic edges. Can cause injury. Take care and wear protective clothing when servicing unit to avoid accidental contact with sharp edges.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table Of Contents
Dimensions Page 2.................................
Shipping and Packing List Page 3....................
General Page 3....................................
Requirements Page 3...............................
Unit Support Page 4................................
Duct Connection Page 4............................
ZHA036 (3 TON) ZHB036 (3 TON) ZHA048 (4 TON) ZHB048 (4 TON) ZHA060 (5 TON) ZHB060 (5 TON)
HEAT PUMP PACKAGED UNITS
507111-02 2/2015 Supersedes 507111-01
Rigging Unit For Lifting Page 4.......................
Horizontal Air Discharge Page 5......................
Condensate Drains Page 5..........................
Electrical Connections Page 6.......................
Blower Operation and Adjustments Page 7............
Start-Up Page 16....................................
Defrost Control Board Page 22........................
Service Page 23....................................
ZH 036, 048, 060 PARTS ARRANGEMENT
CONTROL
PANEL
OUTDOOR
COIL FAN
COMPRESSOR
OUTDOOR
COIL
SIDE POWER
ENTRY
EVAPORATOR
COIL
BLOWER
MOTOR
BLOWER
HOUSING
ELECTRIC HEAT
(OPTIONAL)
TB2 UNIT
TERMINAL
STRIP
UNIT FUSE
BOTTOM POWER
ENTRY
ZH 036, 048, 060, DIMENSIONS in (mm)
Holes required for Optional Bottom Power Entry Kit
BOTTOM POWER ENTRY
Conduit Fittings (Provided in Kit)
A B C
Threaded
1/2
1/2 3/4
Wire
Use
ACC.
24V
POWER
47-1/4 (1200) BASE
Hole Diameter
Required in
Unit Base (Max.)
7/8 (23)
7/8 (23)
1-1/8 (29)
16-1/8
(410)
13-5/8
(346)
11-1/8
(283)
24-9/16
(624)
BOTTOM RETURN
AIR OPENING
A B C
BOTTOM
POWER
ENTRY
(See Table)
75-7/8 (1927)
12-1/8
(308)
TOP VIEW (Base)
25-5/8
(651)
BOTTOM
SUPPLY
OPENING
AIR
5-1/8 (130)
17-3/4
(451)
5-3/4
(146)
5-1/8 (130)
10-7/8
(276)
29
(737)
45-1/4 (1149)
44-7/8 (1140) ZH 060
ZHB036, 048
36-7/8 (937) ZHA036, 046
1
(25)
47-1/4 (1200)
(25)
BASE
POWER
ENTRY
1
(25)
Either
side
3-1/2
(89)
1
END VIEW
ZH 036, 048, 060
LIFTING HOLES
(For rigging)
73-3/4 (1873)
FRONT VIEW
Page 2
3-1/2 (89)
TYP.
11-7/8
(302)
5-3/4 (146)
6-1/2 (165)
CONDENSATE
OUTLET
HORIZONTAL
SUPPLY
17-3/8
(441)
27
(686)
31
(787)
END VIEW
6-1/4 (159)
RETURN
HORIZONTAL
5-9/16
(141)
8-3/8
(213)
10-7/8
(276)
25-3/4
(654)
5-3/4 (146)
Shipping and Packing List
Package 1 of 1 contains:
1 - Assembled unit
Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation.
Availability of units and options varies by brand.
Requirements
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil, causing the rubber to swell. Bubbles in the rubber roofing material can cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
The National Electric Code (ANSI/NFPA No. 70-1984) is available from:
National Fire Protection Association 1 Batterymarch Park PO Box 9101 Quincy, MA 02269-9101
The ZH unit is CSA certified as a heat pump with cooling and with or without auxiliary electric heat for non-residential use only at the clearances to combustible materials as listed on the unit nameplate and in figure 1.
Installation of ZH heat pumps must conform with standards in National Fire Protection Association (NFPA) “Standard for Installation of Air Conditioning and Ventilating Systems NFPA No. 90A,” “Standard for Installation of Residence Type Warm Air Heating and Air conditioning Systems NFPA No. 90B,” local municipal building codes and manufacturer's installation instructions.
UNIT CLEARANCES
HORIZONTAL
OUTDOOR AIR HOOD
C
D
A
OUTDOOR AIR HOOD
B
Installation of CSA certified units must also conform with current standard C273.5 “Installation Requirements for Heat Pumps” and applicable local codes. Authorities having jurisdiction should be consulted before installation.
Use of this unit as a construction heater or air conditioner is not recommended during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
If this unit has been used for heating or cooling of buildings or structures under construction, the following conditions must be met or the warranty will be void:
A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or cooling is not allowed.
A pre-filter must be installed at the entry to the return
air duct.
The return air duct must be provided and sealed to
the unit.
FIGURE 1
1
Unit
Clearance
Service
Clearance
Minimum Opera
tion Clearance36(914)36(914)
*Clearance is 60 in. (1524mm) in horizontal air flow applications. Note - Entire perimeter of unit base requires support when elevated above mounting surface.
1
Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation.
A
in.(mm)Bin.(mm
36
(914)36(914)
C
in.(mm)Din.(mm)
)
36*
(914)36(914)
36*
(914)36(914)
To p
Clearance
Unob
structed
Unob
structed
Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
Air filters must be replaced and pre-filter must be
removed upon construction completion.
The unit components, duct system, air filters and
evaporator coil must be thoroughly cleaned following final construction clean-up.
The unit operating conditions (including airflow,
cooling operation, and heating operation) must be verified according to these installation instructions.
Page 3
507111-02 2/2015
WARNING
Electric shock hazard and danger of explosion. Can cause injury, death or product or property damage. Turn off electrical power to unit before performing any maintenance or servicing operations on the unit.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent ing of refrigerant (CFC's and HCFC's) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incar ceration may be levied for non-compliance.
Unit Support
NOTE - Securely fasten roof frame to roof per local codes.
NOTE-When installing unit on a combustible surface for downflow discharge applications, the Z1CURB roof mounting frame is required.
B - Horizontal Discharge Applications
1- Specified installation clearances must be maintained
when installing units. Refer to figure 1.
2- Top of support slab should be at least 4” (102mm)
above the finished grade and located so no run-off water from higher ground can collect around the unit.
3- Units require support along all four sides of unit base.
Supports must be constructed of steel or suitably treated wood materials.
Duct Connection
All exterior ducts, joints, and openings in roof or building walls must be insulated and weatherproofed with flashing and sealing compounds in accordance with applicable codes. Any duct passing through an unconditioned space must be insulated.
ZH 036, 048, 060 units are installed on Z1CURB frames.
A - Downflow Discharge Application
Roof Mounting with Z1CURB
1- The Z1CURB roof mounting frame must be installed,
flashed and sealed in accordance with the instructions provided with the frame.
2- The Z1CURB roof mounting frame should be square
and level to 1/16” per linear foot (5mm per linear meter) in any direction.
3- Duct must be attached to the roof mounting frame
and not to the unit; supply and return plenums must be installed before setting the unit.
Installer's Roof Mounting Frame
Many types of roof frames can be used to install the unit, depending upon different roof structures. Items to keep in mind when using the building frame or supports are:
1- The unit base is fully enclosed and not insulated, so
an enclosed, insulated frame is required.
2- The frames or supports must be constructed with
non-combustible materials and should be square and level to 1/16” per linear foot (5mm per linear meter) in any direction.
3- Frame or supports must be high enough to prevent
any form of moisture from entering unit. Recommended minimum frame height is 14” (356mm).
4- Duct must be attached to the roof mounting frame
and not to the unit. Supply and return plenums must be installed before setting the unit.
5- Units require support along all four sides of unit base.
Supports must be constructed of steel or suitably treated wood materials.
ZH 036, 048, 060
Page 4
!
CAUTION
In downflow applications, do not drill or punch holes in base of unit. Leaking in roof may occur if unit base is punctured.
Rigging Unit For Lifting
1- Connect rigging to the unit base using both holes in
each corner. See figure 2.
2- All panels must be in place for rigging.
3- Place field‐provided H‐style pick in place just above
top edge of unit. Frame must be of adequate strength and length. (H-style pick prevents damage to unit.)
UNIT
ZH
*Maximum weight with all available installed accessories.
CAUTION: DO NOT
WALK ON UNIT.
WEIGHT*
LBS. KG.
664 301
Lifting Point Should
Be Directly Above Center Of Gravity.
FIGURE 2
Horizontal Air Discharge
Unit is shipped with panels covering the horizontal supply and return air openings. See figure 3.
UNIT SUPPLY AND RETURN AIR OPENINGS
HORIZONTAL
HORIZONTAL
SUPPLY AIR
OPENING
RETURN AIR
OPENING
4- Install return air duct on the intake air side of the
horizontal economizer. See figure 5.
5- Horizontal economizer and return air duct must be
field-supported.
HORIZONTAL RETURN AIR DUCTWORK
WITH ECONOMIZER
HOOD
PROVIDED
WITH
ECONOMIZER
This opening not used
in horizontal applica
tions with economizer
OPTIONAL
HORIZONTAL
ECONOMIZER
UNIT
DOWNFLOW
SUPPLY AIR
OPENING
DOWNFLOW
RETURN AIR
OPENING
FIGURE 3
1- Remove horizontal covers and place a bead of silicone
sealant on the underside of the duct cover flanges. See figure 4.
2- Position covers over downflow openings. Secure
covers with self-drilling screws in at least two places on each cover. Drill through duct cover side into flange of base pan.
3- Place a bead of silicone between insulation and duct
cover to seal in insulation edges. Let silicone dry before running gas or electric heat.
Units Equipped With An Optional Horizontal Economizer
1- Install the horizontal supply air cover over the down
flow supply air opening as described above.
2- Leave the horizontal return air cover in place.
3- Locate the extra horizontal return cover that is
included with the horizontal economizer kit. Install as described in previous section.
INSTALL DUCT COVERS - SIDE VIEW
APPLY SILICONE
SEALANT TO
FLANGES
NOT TO
SCALE
FLANGE AND UNIT INSULATION
DUCT COVER
FLANGES
UNIT BASE
FLANGES
APPLY SILICONE SEALANT
BETWEEN DUCT COVER
INSULATION
HORIZONTAL
SUPPLY AIR DUCT
(FIELD-PROVIDED)
HORIZONTAL RETURN AIR DUCT (FIELD-PROVIDED)
FIGURE 5
Condensate Drains
Make drain connection to the drain coupling provided on unit.
Note - The drain pan is made with a glass reinforced engineered plastic capable of withstanding typical joint torque but can be damaged with excessive force. Tighten pipe nipple hand tight and turn an additional quarter turn.
A trap must be installed between drain connection and an open vent for proper condensate removal. See figure 6. It is sometimes acceptable to drain condensate onto the roof or grade; however, a tee should be fitted to the trap to direct condensate downward. The condensate line must be vented. Check local codes concerning condensate disposal. Refer to pages 1 and 2 for condensate drain location.
CONDENSATE SIDE DRAIN CONNECTION
CAULK AROUND CONDENSATE COUPLING
NOTE - Allow clearance to open doors when installing condensate piping.
Minimum Pitch 1” (25 mm) per 10' (3 m) of line
OPEN VENT
UNIT
MOUNTING
FRAME
FIGURE 4
FIGURE 6
Page 5
507111-02 2/2015
Electrical Connections
POWER SUPPLY
Do not apply power or close disconnect switch until installation is complete. Refer to start-up directions. Refer closely to unit wiring diagram.
Refer to unit nameplate for minimum circuit ampacity and maximum fuse size.
1- Units are factory-wired for 240, 460, or 575 volt supply.
For 208V supply
from the 208V terminal on the control transformer. Move the wire from the transformer 240V terminal to the 208V terminal. Place the insulated terminal cover on the unused 240V terminal.
2- Route power through the side or bottom power
entry area. For bottom power entry, a bottom power entry kit must be used. Connect power wiring to K1/K3 contactors in control box. See figure 7. On units equipped with electric heat, route power wiring to TB2; see parts arrangement for location. See unit wiring diagram.
, remove the insulated terminal cover
POWER WIRING
IMPORTANT - Unless field thermostat wires are rated for maximum unit voltage, they must be routed away from line voltage wiring.
B - Control Wiring
1- Route thermostat cable or wires from subbase to
control panel (refer to unit dimensions to locate bottom and side power entry).
Use18 AWG wire for all applications using remotely installed electro-mechanical and electronic thermostats.
2- Install thermostat assembly in accordance with
instructions provided with thermostat.
3- Connect thermostat wiring to low voltage leads in
control box. Wire as shown in figure 8 for electro-mechanical and electronic thermostats. If using other temperature control devices or energy management systems see instructions and wiring diagram provided by manufacturer.
IMPORTANT-Terminal connections at the wall plate or subbase must be made securely. Loose control wire connections may allow unit to operate but not with proper response to room demand.
Y, G, J, M
VOLT ONLY
K1
CONNECT FIELD-
SUPPLIED WIRING
TO K1/K3
K3
FIGURE 7
CONTROL WIRING
A - Thermostat Location
Room thermostat mounts vertically on a standard 2” X 4” handy box or on any non-conductive flat surface.
Locate thermostat approximately 5 feet (1524 mm) above the floor in an area with good air circulation at average temperature. Avoid locating the room thermostat where it might be affected by:
-drafts or dead spots behind doors and in corners
-hot or cold air from ducts
-radiant heat from sun or appliances
-concealed pipes and chimneys
ZH 036, 048, 060
Page 6
24 VOLT FIELD WIRING WITH ELECTRONIC AND
ELECTRO-MECHANICAL THERMOSTATS
UNIT CONTROL AREA
A2 THERMOSTAT
Note - On electro-mechanical thermo stats set anticipator at 0.1 amps.
TO CMC1; DO NOT
REMOVE FACTORY
INSTALLED WIRES
NOT ALL TERMINALS
ARE FOUND ON ALL
THERMOSTATS
Jumper terminals R and OC when thermostat has no night setback terminals.
FIGURE 8
Blower Operation and Adjustments
Units are equipped with belt drive blowers; available drive varies by model.
Blower performance data is based on static pressure readings taken in locations shown in figure 9.
Note - Static pressure readings can vary if not taken where shown.
IMPORTANT
Three phase scroll compressors must be phased sequentially for correct compressor and blower rotation. Follow “COOLING START-UP” section of installation instructions to ensure proper compres sor and blower operation.
A - Blower Operation
Initiate blower demand at thermostat according to instructions provided with thermostat. Unit will cycle on thermostat demand. The following steps apply to applications using a typical electro-mechanical thermostat.
1- Set thermostat or temperature control device fan
switch to AUTO or ON. With fan switch in ON position, blower will operate continuously. With fan switch in AUTO position, the blower will cycle with demand.
2- Blower and entire unit will be off when thermostat or
temperature control device system switch is in OFF position.
B - Determining Unit CFM
1- The following measurements must be made with air
filters in place.
2- With all access panels in place, measure static
pressure external to unit (from supply to return).
3- Measure the indoor blower wheel RPM.
4- Referring to pages 9-14, use static pressure and
RPM readings to determine unit CFM. Use option/accessory air resistance table on page 15 when installing units with any of the options or accessories listed. Refer to table 3 for minimum airflow when electric heat is installed.
5- The blower RPM can be adjusted at the motor pulley.
Loosen Allen screw and turn adjustable pulley clockwise to increase CFM. Turn counterclockwise to decrease CFM. See figure 10. Do not exceed minimum and maximum number of pulley turns as shown in table 1.
TABLE 1
MINIMUM AND MAXIMUM PULLEY ADJUSTMENT
Belt Min. Turns Open Maxi. Turns Open
A Section No minimum 5
C - Blower Belt Adjustment
Maximum life and wear can be obtained from belts only if proper pulley alignment and belt tension are maintained. Tension new belts after a 24-48 hour period of operation. This will allow belt to stretch and seat grooves. Make sure blower and motor pulley are aligned as shown in figure 11.
INSTALLATIONS WITH DUCTWORK
ROOFTOP UNIT
READING LOCATION
SUPPLY
MAIN
RE
TURN
OFF OF MAIN RUN
DUCT RUN
LOCATION OF STATIC PRESSURE READINGS
INSTALLATIONS WITH CEILING DIFFUSERS
ROOFTOP UNIT
RETURN AIR
SUPPLY
FIRST BRANCH
SUPPLY AIR
READING
LOCATION
SUPPLY AIR
READING
LOCATION
DIFFUSER
FIGURE 9
Page 7
RETURN AIR
READING
RE
TURN
LOCATION
507111-02 2/2015
BLOWER ASSEMBLY
TO INCREASE BELT TENSION
1-Loosen four bolts securing motor base to mounting frame.
2-Slide the motor downward to tighten the belt.
3-Tighten four bolts on motor base.
LOOSEN FOUR BOLTS
AND SLIDE BLOWER MOTOR DOWNWARD
SIDE VIEW
TO TIGHTEN BELT
MOTOR
TO INCREASE CFM
LOOSEN ALLEN SCREW &
TURN PULLEY CLOCKWISE
ALLEN
SCREW
PULLEY
TO DECREASE CFM
TURN PULLEY
COUNTERCLOCKWISE
FIGURE 10
PULLEY ALIGNMENT
ALIGNED
MOTOR
PULLEY
BELT
NOT ALIGNED
BLOWER
PULLEY
FIGURE 11
1- Loosen four bolts securing motor base to mounting
frame. See figure 10.
2- Apply perpendicular force to center of span (X) with
enough pressure to deflect belt 1/64” for every inch of span length or 1.5mm per 100mm of span length.
Example: Deflection distance of a 40” span would be 40/64” or 5/8”.
Example: Deflection distance of a 400mm span would be 6mm.
3- Measure belt deflection force. For a used belt, the
deflection force should be 5 lbs. (35kPa). A new belt deflection force should be 7 lbs. (48kPa).
A force below these values indicates an undertensioned belt. A force above these values indicates an overtensioned belt.
MEASURE BELT TENSION
2- To increase belt tension -
Slide blower motor downward to tighten the belt. This increases the distance between the blower motor and the blower housing.
To loosen belt tension -
Slide blower motor upward to loosen the belt. This decreases the distance between the blower motor and the blower housing.
3- Tighten four bolts securing motor base to the
mounting frame.
D - Check Belt Tension
Overtensioning belts shortens belt and bearing life. Check belt tension as follows:
1- Measure span length X. See figure 12.
ZH 036, 048, 060
FORCE
DEFLECTION 1/64” PER INCH OF SPAN
OR 1.5mm PER 100mm OF SPAN
FIGURE 12
E-Field-Furnished Blower Drives
For field-furnished blower drives, use pages 9-14 to determine BHP and RPM required. Reference page 15 for additional air resistance and drive kit numbers. See table 2 for drive component manufacturer's numbers.
Page 8
Loading...
+ 16 hidden pages