Lennox Y3760 User Manual

INSTALLATION & USER MANUAL
HC Digital Automatic Humidistat (Y3760)
506808-01 3/2016 Supersedes 6/2011
picture goes here
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
NOTICE
The humidistat must be installed in accordance with all local and national standards.
Installation, adjustments, alterations, service and maintenance must be performed by a qualified ser vice technician.
Product Description
The HC Digital Automatic Humidistat is a programmable control for HCSteam residential humidifiers. While the HC Digital Automatic Humidistat may be used for control of other humidification or dehumidification appliances, its op erating modes are designed for modulating control of the HCSteam electrode steam humidifiers.
When properly installed and configured, the HC Digital Au tomatic Humidistat will use information from the environ ment including Relative Humidity, Outdoor Temperature and Home Construction to determine the Ideal Humidity and the Optimum Humidifier Output.
Table of Contents
Product Description 1............................
Installation 2....................................
Electrical connections: 3.........................
User Interface and Modes 5......................
Configuration (Setting DIP Switches, Parameters,
Auto humidity control, Sensor calibration) 6.........
Functions 7....................................
Parameters 8..................................
Alarms and Signals 8...........................
Technical Specifications and Wiring 9.............
Replacement Parts 9............................
The HC Digital Automatic Humidistat includes an Indoor Temperature Sensor, Indoor Humidity Sensor and Control Unit. A separate Outdoor Sensor is supplied.
Humidistat Dimensions
°C/°F
°C/°F
Set
Set
Prg
Prg
5 1/4” (135 mm)
1-1/2”
(36 mm)
3 1/2” (86 mm)
Disposal
The product is made from metal and plastic parts. All parts must be disposed of accord ing to the local standards on waste disposal.
Page 1
Installation
1. Open the product by detaching the front from the mounting base, as shown in figure 1:
D Remove the screw holding the locking tab in place
(detail A).
D Slide the plastic tab back as shown to remove it
from the base (detail B).
D Press the tab on the front with the flat-head screw
driver into the slit in the middle on the bottom of the case (detail C) while lifting the front panel upwards (detail D).
°C/ F
Set
Prg
detail A
detail B
detail C
the connection and control cables from the relay cables. The diagrams are shown under Electrical Con nections (Page 3).
NOTICE
Make sure all connections are complete before re connecting the flat cable and front part of the humi distat.
For the purposes of electrical safety, once the con troller has been installed, replace the plastic locking tab in the humidistat base.
Table 1. Connections and DIP switches
Connector Function
J1 Not used
J2 Not used
Flat front-rear The flat front-rear connection cable must be re
connected in the position defined by the plastic part to ensure correct polarity.
DIP switches For configuring humidification/dehumidification
modes.
detail D
Figure 1. Opening the humidistat
2. Disconnect the flat front-rear connector cable from the front panel.
3. Fasten the humidistat base to the wall using the screws supplied.
4. Access the terminal block by squeezing the clips on the terminal cover.
5. Make the necessary connections and run the wires through the hole in the middle of the base. Separate
Dipswitches
J1 (NOT USED)
FLAT Front−Rear
J2 (NOT USED)
506808-01 06/11
Page 2
Electrical connections
Connect the HC Digital Automatic Humidistat to HCSteam Humidifier for Modulating Operation
IMPORTANT - Be sure the connections are made as de scribed in the following and as shown in figure 2.
1. Connect HCSteam Humidifier terminal 24V to HC Dig ital Automatic Humidistat terminal 6-G.
2. Connect HCSteam Humidifier terminal GND to HC Digital Automatic Humidistat terminal 5-G0.
3. Connect HCSteam Humidifier terminal IN to HC Digital Automatic Humidistat terminal 7-AOUT.
NOTES -
S Modulating operation requires that the signal type be
changed at the HCSteam Humidifier. See HCSteam Humidifier Installation Instruction Manual 506746-01.
S Verify DIP switch settings per figure 2.
DIP Switch
settings
HCSteam
Y3760
ON
OFF
OFF
ON
1 2 3 4
ON DP
Connect the HC Digital Automatic Humidistat to HCSteam Humidifier for ON-OFF Operation
IMPORTANT - Be sure the connections are made as de scribed in the following and as shown in figure 3.
1. Connect HCSteam Humidifier terminal 24V to HC Dig ital Automatic Humidistat terminal 6-G.
2. Connect HCSteam Humidifier terminal GND to HC Digital Automatic Humidistat terminal 5-G0.
3. Connect HCSteam Humidifier terminal GND to HC Digital Automatic Humidistat terminal 1.
4. Connect HCSteam Humidifier terminal IN to HC Digital Automatic Humidistat terminal 2.
Connect HCSteam Humidifier terminals 24V and GND to HC Digital Automatic Humidistat terminals 6-G and 5-G0 respectively. Do not reverse these connections. Connect HC Digital Automatic Humidistat terminal 1 and 2 to HCSteam terminal GND and IN respectively. Do not re verse these connections (see figure 3).
NOTES -
S HCSteam humidifiers are configured for On-OFF op
eration from the factory. See HCSteam Humidifier Installation Instruction Manual 506746-01.
S Verify Dip Switch Settings per figure 3.
DIP Switch
HCSteam
settings
Y3760
ON
OFF
OFF
1 2 3 4
ON
ON DP
Outdoor Temp.
Sensor (if used)
Figure 2. Connect for Modulating Operation
Outdoor Temp.
Sensor (if used)
Figure 3. Connect for ON-OFF Operation
Page 3
HC SERIES
Placement of Remote Outdoor Temperature Sensor
S
Outdoor temperature sensor should not be mounted on the south side of the house or in direct sunlight.
S Outdoor temperature sensor may not be located clos
er than 4 feet to exhaust vents, dryer vents, etc.
S If outdoor temperature sensor is mounted in fresh air
intake duct, make sure the probe is no further than 1 foot from outside wall.
Table 2. Outdoor Sensor Temperature / Resistance Range
S Make sure wiring for outdoor temperature sensor is
not close to other wires particularly high voltage.
S Outdoor temperature sensor must be at least 6” above
expected snow line.
S Maximum conductor length of the Outdoor Tempera
ture Sensor is 100 feet (30m) of standard thermostat cable (twisted pair not required).
S Connect Outdoor Temperature Sensor to terminals #8
and #9.
Temperature
ºF (ºC)
-40.0 (-40) 196 188 181.1 41.0 (5) 22.5 22.1 21.7
-29.2 (-34) 142 137 131.8 50.0 (10) 18.2 18 17.7
-20.2 (-29) 109 106 102.2 60.8 (16) 14.3 14.1 13.9
-9.4 (-23) 80.7 78.3 75.93 69.8 (21) 11.8 11.6 11.6
-0.4 (-18) 63.3 61.5 59.81 80.6 (27) 9.38 9.28 9.18
10.4 (-12) 47.7 46.5 45.31 100.4 (38) 6.33 6.24 6.15
19.4 (-7) 37.9 37.1 36.2 122.0 (50) 4.24 4.16 4.08
30.2 (-1) 30 28.5 27.89 136.4 (58) 3.28 3.2 3.1
Maximum Standard Minimum Maximum Standard Minimum
Resistance Value (KOHM)
Temperature
ºF (ºC)
Resistance Value (KOHM)
506808-01 06/11
Page 4
User Interface and Modes
Display and buttons
Figure 4 below shows the humidistat with its control but tons and its display, along with a key of what each of the symbols represent. Table 3 describes how the buttons op erate.
side
programming
buttons
LCD display
immediately
change the current
set point
1 3 42
5
6
7
91011
Key:
1. LARGE field - Displays the temperature/humidity.
2. Displays setting for active value on the large display.
3. Night mode symbol. If off = daytime mode.
4. Lock mode. The parameter is not accessible.
5. Active time bands.
6. Outside/inside/maximum/minimum temperature symbol.
7. Displays setting for active value on the small display.
8. Auto operating mode.
9. SMALL field - Displays the temperature/humidity.
10. Dehum. (dehumidify) / humid. (humidify) operation. When the ramp symbol is on, the corresponding mode is active.
11. HEAT COOL INDICATORS (NOT USED)
8
Figure 4. Humidistat display and buttons
Table 3. Humidistat buttons description
On/Off .
Selects the temperature display mode, degrees Celsius or Fahr enheit. Whenever pressed switches the temperature units.
Used to display and where necessary change, using the UP and DOWN buttons, the set point displayed in the SMALL field. If held for more than 5 seconds, accesses the parameters menu.
To scroll the various parameters use UP and DOWN. To edit them, press the SET button a second time and to exit the param eters menu press the PRG button. Access to the parameters is protected by password if parameter PS is enabled.
Change mode manually: activates the opposite function (and the corresponding set point) to the current (night if day or day if night), for the set time. To change or reset the timer use the UP and DOWN buttons to increase or decrease the time. Press a second time to exit and return to the main menu. If sleep mode is already active, pressing the button shows the time remaining on the timer.
E.g.: if the humidistat is in Night mode (moon symbol on) from time band, pressing this button activates daytime mode (moon symbol off ) for the set time.
Accesses the menu for setting the clock, the time bands, and the default value of the timer. When first pressed, displays the cur rent time (RTC); to display the other parameters, use the UP and DOWN arrows. To set a new value, press SET when displaying the desired parameter and change the value using the UP and DOWN buttons. Press a second time to exit and return to the main menu.
Accesses the menu for displaying the temperature: current, maximum and minimum outside (from instrument power on), inside and outside. To display the various temperatures, press the button repeatedly. Their meaning is displayed in the box with the home symbol.
Also displays the value of the analogue output when “Out” is shown in the SMALL field.
From the main menu increases the value of the set point dis played in the LARGE field. In the other menus displays the vari ables or the parameters, or alternatively sets the value after having pressed SET.
From the main menu decreases the value of the set point dis played in the LARGE field. In the other menus displays the vari ables or the parameters, or alternatively sets the value after having pressed SET
The values displayed in the LARGE and SMALL fields (shown in figure 4) depend on the setting of parameter dyS as shown in table 4.
Table 4. dyS parameter values
dyS LARGE field (1) SMALL field (9)
1 humidity humidity set point
2 humidity set point humidity
3 humidity set point
4 humidity
Page 5
HC SERIES
Configuration
NOTICE
Before closing the cover, the mode must be selected using the dip switches.
Important: Setting the dip switches incorrectly will cause the humidistat to malfunction.
Table 5. Setting humidistat control type
DIP switch positions
1 2 3 4
ON OFF OFF ON Humidifier Control (default)
ON OFF OFF OFF Dehumidifier Control
Setting parameter
The parameters for all operating modes also feature a de fault value. These values can be restored by running the “Factory set” operation. See the table of parameters for details of the default values and settings.
S SET POINT: depending on the operating mode, differ
ent set points are used. To set these, access (SET but ton – press and hold for 5 seconds) the mode for set ting the parameters and set the corresponding values.
For the current mode only, the value can be accessed directly using UP, DOWN or set, UP, DOWN (for the SMALL field).
With the desired parameter displayed, use the UP/ DOWN buttons, then press SET - the parameter starts flashing. Edit the value using the UP/DOWN buttons and then press SET. To exit the menu, press the PRG button again.
S Clock, TIME BANDS Prg/(clock): Press the corre
sponding button to display and if necessary set the de fault duration of the change mode timer, display or set the RTC clock and set the Day and Night time bands. Initially, at least the set point for humidity control need to be checked/set:
– Humidification set point (def. 30.0 % RH) – Dehumidification set point (def. 70.0 % RH)
Humidistat is
set for:
rtC clock hh:mm -
SLP manual changeover duration def. 8 hours
dAy start day band def. 08:00
nIt start night band def. 20:00
S To disable the time bands function, set parameter rtC
off : – Select parameter rtC using PRG/CLOCK and set
the value using the DOWN button.
– When reaching 00:00 using the DOWN button the
function will be off.
When parameter rtC is set to off the operating mode is al ways daytime, and consequently only the daytime set points are used, the night settings are only used when the NIGHT button is pressed, manually changing mode.
Auto humidity control
In addition to the modes featured by the control algorithms, the humidity can be controlled automatically, based on the reading of the outside temperature sensor. The aim of this type of control is to simplify the setting of the HC Digital Automatic Humidistat, changing the humidity control ac cording to the outside environmental conditions and there fore minimize the discomfort of the user when moving into/ out of the air-conditioned environment This operating mode is selected by setting parameter AUt (see table 7).
S According to the level set using the up/down buttons,
with a value from 1H to 7H, a different humidity set point trend is defined. To disable this operating mode, in the parameters menu set the value of AUt = 0. AUTO mode for the humidification control is only pos sible if the outside temperature sensor is installed.
– AUTO mode for the humidification control is only
possible if the outside temperature sensor is installed.
Sensor Calibration
To make up for any errors due to the length of the cables or the sensors connected, the controller features two param eters for calibrating the values read by the sensors. The CAL parameters are also shown in table 7.
Table 7. Auto humidity and calibration parameters
Code Description of the parameter Range Default
Table 6. Operating mode defaults
AUt
CAL+ Int
CAL+ ESt
CAL+ HUn
Humidity set point level compensated according to the outside temperature.
If humidity control is featured, the ambient humidity is controlled with an auto matic set point, defined from 1H to 7H using the buttons, as specified in Table 8. If set to OFF, the mode is disabled.
Setting one of the levels shown in the table, the controller independently sets a humidity set point in relation to the outside temperature measurement
Inside temperature calibration, digital sensor or NTC (within a max. of ± 10°C) -10 to 10 0.0 °C
Outside temperature calibration, NTC sensor (within a max. of ± 10°C) -10 to 10 0.0 °C
Digital humidity sensor calibration(within a max. of ± 15°rH) Within a maximum of ± 15% rH
OFF
1H to 7H
-15 to 15 0.0 %rH
OFF
Unit of measure
506808-01 06/11
Page 6
Table 8. Humidity set point according to the setting of AUt (outside temperature in degrees)
AUt
Level
1H
2H
3H
4H
5H
6H
7H
-9.4°F
(-23°C)
10% 10% 10% 10% 15% 20% 25% 30%
10% 10% 10% 15% 20% 25% 30% 35%
10% 10% 15% 20% 25% 30% 35% 40%
10% 15% 20% 25% 30% 35% 40% 45%
10% 20% 25% 30% 35% 40% 45% 45%
10% 25% 30% 35% 40% 45% 45% 45%
10% 30% 35% 40% 45% 45% 45% 45%
-9.4 to 1.4°F
(-23 to -17°C)
1.4 to 10.4 °F (-17 to -12°C)
10.4 to 21.2°F (-12 to -6°C)
Functions
General
This section describes the humidity control modes avail able. The control modes are based on parameters, divided into two levels (see figure 5):
S Level 1, basic: main settings, always required;
S Level 2, advanced: used to customize the features of
the controller.
IMPORTANT - Some parameters included in the ad vanced level, are forced to take on default values in the ba sic level or are linked to other parameters in the basic level. This especially applies to the control differentials. In each operating mode, the links between the various basic and advanced levels are specified.
S if level 1 is active, the level 2 parameters are not used
but rather replaced by the default values or by the link value with the level 1 parameters;
S the level 2 parameters are effectively used when level
2 is activated.
Humidity control
This type of control is used to send a start signal to a hu midifier or dehumidifier. The modulating output can only be used for humidification control. Examples of using of the analog output:
S for proportional humidity control of HCSteam humidifi
ers;
S as an additional step to the relay for humidity control.
(See the DIP switch settings in table 5, Page 6.)
Below
21.2 to 30.2°F (-6 to -1°C)
LEVEL = 1
DIP 4 = ON DIP 4 = OFF
10 V
30.2 to 39.2°F (-1 to 4°C)
Output Output
R2
39.2 to 50°F (4 to 10°C)
50°F
(10°C)
R2
Above
0 V
dFH
Humidification setpoint Dehumidification setpoint
LEVEL = 2
DIP 4 = ON DIP 4 = OFF
10 V
R2 R2
0 V
dFH
dFH
dSA
Humidification setpoint Dehumidification setpoint
Output Output
% H.R
Figure 5. Level functions
Table 9. Humidity control indicators & defaults
Code Description Default Level
Humidification set point 50.0 % rH 1
Dehumidification set point 70.0 % rH 1
dFH Humidification differential 5.0 % rH 1
dFd Dehumidification differential 5.0 % rH 1
dFd% U.R
dFd
% U.R
% H.R
Page 7
HC SERIES
Parameters
code parameter range default
Humidification set point. 10 to 70 50.0 % rH
Dehumidification set point. 10 to 70 70.0 % rH
unit of
measure
note
dFH
dFd Dehumidification differential activating relay. 1 to 20 5.0 % rH
SFH Humidification/dehumidification status in day and night mode. Acti
AUt Humidity set point automatically compensated by outside tempera
CAL+Int Inside temperature calibration, digital sensor or NTC.
CAL+ESt Outside temperature calibration, NTC sensor.
CAL+HUn Digital humidity sensor calibration.
Humidity differential for activating analog output and relay. 1 to 20 5.0 % rH
vates or deactivates humidification or dehumidification control (based on DIP 4) with the time bands. The parameter can have the following three values:
0 Time bands disabled. The humidification/dehumidification control is
always active, if featured, and is configured in relation to dip4.
1 Time bands enabled. When switching to the daytime band, humidifica
tion/dehumidification control (depends on dip4) is activated. When switching to the night band, humidification/dehumidification control (depends on dip4) is deactivated.
2 Time bands enabled. When switching to the daytime band, humidifica
tion/dehumidification control (depends on dip4) is deactivated. When switching to the night band, humidification/dehumidification control (depends on dip4) is activated.
ture. If humidity control is featured, the ambient humidity is controlled with an automatic set point, defined from 1H to 7H using the buttons, as specified in the corresponding table (see Page 6). If set to OFF the mode is disabled. Setting one of the levels in the table, the controller independently sets a humidity set point in relation to the outside temperature.
Within a maximum of ± 10 °C.
Within a maximum of ± 10 °C.
Within a maximum of ± 15% rH.
0 to 2 0
OFF
1H to 7H
-10 to 10 0.0 °C
-10 to 10 0.0 °C
-15 to 15 0.0 % rH
OFF
LE Parameter access level. Levels of access that control parameters for the
active mode:
1 Basic access: only the essential parameters for correct operation.
2 Advanced access: used to set all the parameters for the selected con
trol mode.
Unt Temperature display mode. Sets the temperature display mode, in de
grees Fahrenheit or Centigrade. Unlike direct selection using the button, if changing the temperature display mode using parameter Unt, this be comes the default display mode when switching the instrument on.
1, 2 1
°C, °F °C
Alarms and Signals
code on large field display
EE system/memory error manual by
Eth temperature+humidity sensor fault automatic stops all outputs and disables the calculation of the dewpoint
E1 built-in NTC temperature sensor fault automatic stops all outputs
E2 remote temperature sensor fault automatic tops compensation if active, and control on average if enabled
Ert RTC alarm automatic
ALE external alarm from digital input automatic signal-only alarm from external contact (humidifier)
Note: When the value is not shown in the SMALL or LARGE field, three dashes “---“ are displayed.
description reset effect
stops all outputs removing power
506808-01 06/11
Page 8
Technical Specifications
General
Power supply 24 Vac +10 to -15%, 50/60Hz, 1 VA
22 to 35 Vdc, 0.5W
Class 2 safety power supply
2
Min. cable cross-section 20 AWG (0.5 mm
Power supply compatible with HCSteam Humidifier (G – G0)
Operating temperature 0 to 60°C 32 to 140°F, 10 to 90% rH not-condensing
Storage temperature -20 to 70°C -4 to 158°F, 10 to 90% rH not-condensing
Precision of inside temperature measurement ± 1°C from 0 to 60°C, ± 2°C from 32 to 140°F
Precision of outside temperature measurement ± 1.5°C from 0 to 40°C ± 2.0°C from -40 to 0°C and 40 to 80°C
± 3°F from 32 to 104°F ± 4°F from -40 to 32°F and 104 to 176°F
0 to 10 V analog output, not isolated, for proportional control
Relay approval 1 AMP @ 24 Vac
Precision of humidity measurement range 10 to 90% ± 3% rH at 25°C, 77°F
Dimensions 5.3x3.4x1.4” (135x86x36 mm)
precision ±5%
max load 5 kΩ, max current 2 mA
± 5% rH 0 to 60°C, 32 to 140°F
Wiring
Digital input Non-isolated version:direct connection of the voltage-free contact; contact closing
Outside temperature sensor connection with standard sensor (10K 25°C β=3435):
Digital input connection Maximum length: 33' (10 m), min. cable cross-section 20 AWG (0.5 mm2).
Analog output connection Maximum length: 33' (10 m), min. cable cross-section 20 AWG (0.5 mm2).
Relay output connections: Maximum length 100' (30 m), cable cross-section from 16 to 13 AWG (1.5 to 2.5
UL specifications for connections:
Warning: All the connections, except for the relays, must be connected to very low voltage circuits with reinforced insulation.
current: 3 to 5 mA.
Maximum length: 100' (30 m), min. cable cross-section 20 AWG (0.5 mm2).
2
mm
), class 2 reinforced insulation from the instrument.
Use copper wires approved for a temperature of 75°C.
Minimum cross-section AWG 22-14 rigid or flexible.
To tighten the terminals, apply a torque of 7 Lb/In for the black terminals (SAU RO).
To use the instrument in compliance with UL-873, a load with a maximum voltage 24 Vac, class 2, can be connected to the relay output.
).
Replacement Parts
Outdoor Temperature Sensor Cat. No. Y4103 Contact your local Lennox dealer to order replacement parts. For the Lennox dealer nearest you, dial 1-800-9-Lennox. Visit
us at http://www.Lennox.com
Page 9
HC SERIES
+070220641 Rel. 1.0 - June 2011
506808-01 06/11
Page 10
Loading...