Lennox XP16-024-230-01, XP16-024-230-05, XP16-024-230-03, XP16-036-230-01, XP16-024-230-04 Unit Information

...
Corp. 0626−L5
Service Literature
Revised October 21, 2010
XP16 (HFC−410A) SERIES UNITS
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
XP16
TABLE OF CONTENTS
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Typical Serial Number Identification 2. . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 7. . . . . . . . .
Recovering Refrigerant from System 9. . . . . . . . . . . . .
Unit Placement 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 12. . . . . . . . . . . . . . . . .
New or Replacement Line Set 14. . . . . . . . . . . . . . . . . .
Brazing Connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Line Set and Indoor Coil 19. . . . . . . . . . . . . . .
Installing Indoor Metering Device 20. . . . . . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 21. . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 22. . . . . . . . . . . . .
Electrical 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Units Void of Charge 24. . . . . . . . . . . . . . . . . .
Unit Start−Up 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Wiring Diagram and Sequence of
Operations 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checklists 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The XP16 is a high efficiency residential split−system two−stage heat pump unit, which features a scroll compressor and HFC−410A refrigerant. XP16 units are available in 2, 3, 4 and 5 tons. tons. XP16 units are rated for 230 volts only. Applications where supply voltage is less requires a hard start kit. The series is designed for use with an indoor unit with an expansion valve approved for HFC−410A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
Page 1
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
2006 Lennox Industries Inc.
Model Number Identification
Refrigerant Type
X = HFC−410A
Unit Type
P = Heat Pump
P 16 036
X 5
Nominal Cooling Capacity
230
Minor Revision Number
Voltage
230 = 208/230V−1ph−60hz
024 = 2 tons
Series
036 = 3 tons 048 = 4 tons 060 = 5 tons
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008 09 = 2009 10 = 2010
19 09 C
05716
5 (or 6) Digit Unique Number
Month Code
A = January B = February C = March
Specifications
Unit Outdoor Fan
Model Number
XP16−024−230−01 74 9 lbs. 9 oz. 3 18
XP16−024−230−03 74 7 lbs. 13 oz. 3 18
XP16−024−230−04 74 7 lbs. 13 oz. 3 18
XP16−024−230−05 74 8 lbs. 13 oz. 3 18
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
Unit Outdoor Fan
Model Number
XP16−036−230−01 76 12 lbs. 8 oz. 4 22
XP16−036−230−02 76 12 lbs. 8 oz. 4 22
XP16−036−230−03 76 10 lbs. 4 oz. 4 22
XP16−036−230−04 76 10 lbs. 4 oz. 4 22
XP16−036−230−05 76 10 lbs. 9 oz. 4 22
Model Number
XP16−048−230−01 76 15 lbs. 7 oz. 4 22
XP16−048−230−02 76 15 lbs. 7 oz. 4 22
XP16−048−230−03 76 15 lbs. 7 oz. 4 22
XP16−048−230−04 76 15 lbs. 7 oz. 4 22
XP16−048−230−05 76 11 lbs. 12 oz. 3 26
Model Number
XP16−060−230−01 78 13 lbs. 8 oz. 3 26
XP16−060−230−02 78 13 lbs. 8 oz. 3 26
XP16−060−230−03 78 11 lbs. 7 oz. 3 26
XP16−060−230−04 78 11 lbs. 7 oz. 3 26
XP16−060−230−05 78 12 lbs. 15 oz. 3 26
1
Tested according to AHRI Standard 270−2008 test conditions.
2
Refrigerant charge sufficient for 15 feet length of refrigerant lines.
Sound Rating Number
Sound Rating Number
Sound Rating Number
(dB)
(dB)
(dB)
1
1
1
Factory Refrigerant
Unit Outdoor Fan
Factory Refrigerant
Unit Outdoor Fan
Factory Refrigerant
Charge
Charge
Charge
2
2
2
Number of Blades Diameter − inches.
Number of Blades Diameter − inches.
Number of Blades Diameter − inches.
Page 2
XP16
Electrical Data
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Maximum
XP16−024−230−01 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−03 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−04 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−05 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
Unit Compressor Condenser Fan
Model Number
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Maximum
XP16−036−230−01 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−02 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−03 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−04 35 22.0 16.67 82.0 1/6 PSC 825 1.1 1.87
XP16−036−230−05 35 22.5 16.67 82.0 1/4 PSC 825 1.7 3.1
Locked
Rotor Amps
(LRA)
Motor
HP
208/230V−60 Hz−1 Ph
Locked
Rotor Amps (LRA)
Motor
HP
Motor
Type
Motor Type
Nominal
RPM
Nominal
RPM
Full Load
Amps (FLA)
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
Locked Rotor
Amps (LRA)
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Locked
Rotor Amps (LRA)
Motor
HP
Motor Type
Nominal
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XP16−048−230−01 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−02 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−03 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−04 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−05 45 28.2 21.15 96.0 1/3 PSC 825 1.8 2.9
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Locked
Rotor Amps (LRA)
Motor
HP
Motor Type
Nominal
3
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XP16−060−230−01 55 33.9 25.64 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−02 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−03 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−04 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
700
XP16−060−230−05 60 35.1 25.87 118.0 1/3 VS
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
3
PSC = permanent split capacitor motor (single speed); VS = variable speed.
(1st Stage)
820
(2nd Stage)
2.8 N/A
XP16
Page 3
Unit Dimensions − Inches (mm)
A
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
C
9−1/2 (241)
8−1/4 (210)
4−3/4"
(121)
UNIT SUPPORT FEET
B
TOP VIEW
D
E
F
G
XP16−036 to −060 BASE WITH LEGS
K
J
H
UNIT SUPPORT
FEET
8−1/2 (216)
8−3/4 (222)
SIDE VIEW
5−1/2 (140)
13−1/2
(343)
XP16−024 BASE SECTION
4−1/2"
(108)
Model Number A B C D E F G H J K
XP16−024−01,
−02, −03, −04
31 (889) 27 (686) 28 (711)
XP16−024−05 35 (889) 27 (686) 28 (711)
XP16−036−01,
−02, −03, −04
35 (889) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−036−05 39 (991) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−048−01,
−02, −03, −04
XP16−048−05 35 (889) 35−1/2 (902)
XP16−060−01,
−02, −03, −04
XP16−060−05 45 (1143 35−1/2 (902)
45 (1143) 30−1/2 (775) 35 (889)) 16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
39 (991) 35−1/2 (902)
39−1/2 (1003)
39−1/2 (1003)
39−1/2 (1003)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
Page 4
XP16
Typical Unit Parts Arrangement
CAPACITOR (LOCATION OF CAPACITOR VARIES.)
DEFROST CONTROL (A108)
GROUND
LUG
CONTACTOR
(K−1)
AMBIENT TEMPERATURE SENSOR (RT13)
DISCHARGE LINE SENSOR (RT28)
REVERSING VALVE
REVERSING VALVE SOLENOID
TRUE SUCTION PORT
HIGH PRESSURE SWITCH (S4)
COMPRESSOR
CHECK
EXPANSION VALVE
FOR COIL SENSOR (RT21) LOCATION
SEE FIGURE 2.
XP16
LOW PRESSURE SWITCH (S87)
EXPANSION VALVE SENSING BULB
LIQUID VALVE AND GAUGE PORT / LIQUID LINE CONNECTIONS
Figure 1. Typical Parts Arrangements
Page 5
CRANKCASE HEATER THERMOSTAT (S40)
VAPOR VALVE AND GAUGE
PORT / SUCTION LINE
CONNECTIONS
LIQUID LINE BI−FLOW FILTER DRIER
XP16−024
COIL SENSOR −THIRD HAIRPIN DOWN FROM THE TOP ON INSIDE ROW.
XP16−036
COIL SENSOR − NINTH HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−048
COIL SENSOR − EIGHT HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−060
COIL SENSOR − SIXTH HAIRPIN UP FROM THE BOTTOM
ON INSIDE ROW.
XP16−024
COIL SENSOR 7 tubes up from bottom (7−1/2")
XP16−036
COIL SENSOR 17 tubes up from bottom (17−1/2")
XP16−060
COIL SENSOR 12 tubes up from bottom (11−1/2")
XP16−048
COIL SENSOR 13 tubes up from bottom (12−1/2")
(XP16−XXX−230−05)
(XP16−XXX−230−01 through 04)
CLIP COIL TEMPERATURE SENSOR FROM THE DEFROST BOARD ON THE RETURN BEND SHOWN.
Figure 2. Coil Sensor (RT21) Locations
Page 6
XP16
WARNING
IMPORTANT
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 3 provides information on how to access and operating both angle and ball service valves.
XP16
Page 7
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CORE
TO OUTDOOR UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
roate stem counterclockwise 90°. To close rotate stem clock­wise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
STEM CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
WHEN SERVICE VALV E IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
D With torque wrench: Finger tighten and
torque cap per table 1.
D Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
D With Torque Wrench: Finger tighten and
then torque cap per table 1.
D Without Torque Wrench: Finger
tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
9
10
9
10
8
12
11
8
7
6
12
11
7
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
3
4
5
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball Service Valves
Page 8
XP16
Recovering Refrigerant from System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
1
switch or main fuse box/breaker panel.
MAIN FUSE BOX/BREAKER PANEL
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing HCFC−22 refrigerant using one of the following procedures:
3
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil vol-
umes, and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit
D Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. D Compressor can stop pumping due to tripped internal pressure relief valve. D Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing HCFC−22 system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor
unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve. D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
:
to go into a vacuum.
Figure 4. Refrigerant Recovery
XP16
Page 9
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
12 (305)
6 (152)
36 (914)
ACCESS PANEL
CONTROL PANEL
ACCESS
LOCATION
30 (762)
LINE SET CONNECTIONS
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
Figure 5. Installation Clearances
NOTES:
D Clearance to one of the other three
sides must be 36 inches (914mm).
D Clearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 5 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
D Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
D When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 6, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 6, detail B.
NOTE  If necessary for stability, anchor unit to slab as described in figure 6, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 6, detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
Page 10
XP16
DETAIL A
Install unit away from windows.
 Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.
 Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
DETAIL C
Elevated Slab Mounting
using Feet Extenders
LEG DETAIL
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
BASE
GROUND LEVEL
STABILIZING UNIT ON UNEVEN SURFACES
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
#10 1−1/4" LONG HEX HD SCREW
Concrete slab  use two plastic anchors (hole drill 1/4")
Wood or plastic slab  no plastic anchor (hole drill 1/8")
DETAIL E
Stabilizing bracket (18 gauge metal  2" (50.8mm) width; height as required); bend to form right angle as exampled below.
 Slab Side Mounting
REQUIRED)
AND FLAT WASHER
 Deck Top Mounting
MINIMUM ONE
PER SIDE
COIL
BASE PAN
CORNER POST
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.
SAME FASTENERS AS SLAB SIDE MOUNTING.
FOR EXTRA
STABILITY
Figure 6. Placement, Slab Mounting and Stabilizing Unit
XP16
Page 11
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
With unit positioned at installation site, perform the following
1. Remove two side louvered panels to expose the unit
2. Install the brackets as illustrated in figure 6, detail D or
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
:
base.
E using conventional practices.
Removing and Installing Panels
IMPORTANT
Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
IMPORTANT
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Page 12
XP16
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly.
2. Hold the panel firmly throughout this procedure. Rotate bot-
tom corner of panel away from hinged corner post until low­er three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as pos­sible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as il­lustrated in detail A and C; then upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
IMPORTANT ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
SCREW
LIP
DETAIL A
DETAIL B
ANGLE MAY BE TOO EXTREME
HOLES
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
HOLD DOOR FIRMLY TO THE HINGED
PANEL
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
PREFERRED ANGLE FOR INSTALLATION
Figure 7. Removing and Installing Panels
XP16
Page 13
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 16.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page
19).
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.
Table 2. Refrigerant Line Set  Inches (mm)
Model
−018
−024
−030
−036
−042
−048
−060
Valve Field Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liqui d Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to communicate the following information:
D Model (XP16) and size of unit (e.g. −036).
D Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
D Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
WARNING
Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must
be added, it must be a Polyol Ester oil.
Page 14
XP16
Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL STUD
NON−CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping materi­al or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
XP16
ROOF RAFTER
Figure 8. Line Set Installation
Page 15
Brazing Connections
Use the procedures outline in figures 9 and 10 for brazing line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture − Check the high and low pressures before applying heat.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
IMPORTANT
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could re­sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
Page 16
XP16
Loading...
+ 35 hidden pages