Lennox XP16-024-230-01, XP16-024-230-05, XP16-024-230-03, XP16-036-230-01, XP16-024-230-04 Unit Information

...
Page 1
Corp. 0626−L5
Service Literature
Revised October 21, 2010
XP16 (HFC−410A) SERIES UNITS
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
XP16
TABLE OF CONTENTS
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Typical Serial Number Identification 2. . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 7. . . . . . . . .
Recovering Refrigerant from System 9. . . . . . . . . . . . .
Unit Placement 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 12. . . . . . . . . . . . . . . . .
New or Replacement Line Set 14. . . . . . . . . . . . . . . . . .
Brazing Connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Line Set and Indoor Coil 19. . . . . . . . . . . . . . .
Installing Indoor Metering Device 20. . . . . . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 21. . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 22. . . . . . . . . . . . .
Electrical 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Units Void of Charge 24. . . . . . . . . . . . . . . . . .
Unit Start−Up 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Wiring Diagram and Sequence of
Operations 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checklists 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The XP16 is a high efficiency residential split−system two−stage heat pump unit, which features a scroll compressor and HFC−410A refrigerant. XP16 units are available in 2, 3, 4 and 5 tons. tons. XP16 units are rated for 230 volts only. Applications where supply voltage is less requires a hard start kit. The series is designed for use with an indoor unit with an expansion valve approved for HFC−410A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
Page 1
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
2006 Lennox Industries Inc.
Page 2
Model Number Identification
Refrigerant Type
X = HFC−410A
Unit Type
P = Heat Pump
P 16 036
X 5
Nominal Cooling Capacity
230
Minor Revision Number
Voltage
230 = 208/230V−1ph−60hz
024 = 2 tons
Series
036 = 3 tons 048 = 4 tons 060 = 5 tons
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008 09 = 2009 10 = 2010
19 09 C
05716
5 (or 6) Digit Unique Number
Month Code
A = January B = February C = March
Specifications
Unit Outdoor Fan
Model Number
XP16−024−230−01 74 9 lbs. 9 oz. 3 18
XP16−024−230−03 74 7 lbs. 13 oz. 3 18
XP16−024−230−04 74 7 lbs. 13 oz. 3 18
XP16−024−230−05 74 8 lbs. 13 oz. 3 18
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
Unit Outdoor Fan
Model Number
XP16−036−230−01 76 12 lbs. 8 oz. 4 22
XP16−036−230−02 76 12 lbs. 8 oz. 4 22
XP16−036−230−03 76 10 lbs. 4 oz. 4 22
XP16−036−230−04 76 10 lbs. 4 oz. 4 22
XP16−036−230−05 76 10 lbs. 9 oz. 4 22
Model Number
XP16−048−230−01 76 15 lbs. 7 oz. 4 22
XP16−048−230−02 76 15 lbs. 7 oz. 4 22
XP16−048−230−03 76 15 lbs. 7 oz. 4 22
XP16−048−230−04 76 15 lbs. 7 oz. 4 22
XP16−048−230−05 76 11 lbs. 12 oz. 3 26
Model Number
XP16−060−230−01 78 13 lbs. 8 oz. 3 26
XP16−060−230−02 78 13 lbs. 8 oz. 3 26
XP16−060−230−03 78 11 lbs. 7 oz. 3 26
XP16−060−230−04 78 11 lbs. 7 oz. 3 26
XP16−060−230−05 78 12 lbs. 15 oz. 3 26
1
Tested according to AHRI Standard 270−2008 test conditions.
2
Refrigerant charge sufficient for 15 feet length of refrigerant lines.
Sound Rating Number
Sound Rating Number
Sound Rating Number
(dB)
(dB)
(dB)
1
1
1
Factory Refrigerant
Unit Outdoor Fan
Factory Refrigerant
Unit Outdoor Fan
Factory Refrigerant
Charge
Charge
Charge
2
2
2
Number of Blades Diameter − inches.
Number of Blades Diameter − inches.
Number of Blades Diameter − inches.
Page 2
XP16
Page 3
Electrical Data
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Maximum
XP16−024−230−01 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−03 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−04 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
XP16−024−230−05 20 14.0 10.25 52.0 1/10 PSC 1075 0.7 1.4
Unit Compressor Condenser Fan
Model Number
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Maximum
XP16−036−230−01 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−02 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−03 35 22.0 16.67 82.0 1/6 PSC 825 1.1 2.1
XP16−036−230−04 35 22.0 16.67 82.0 1/6 PSC 825 1.1 1.87
XP16−036−230−05 35 22.5 16.67 82.0 1/4 PSC 825 1.7 3.1
Locked
Rotor Amps
(LRA)
Motor
HP
208/230V−60 Hz−1 Ph
Locked
Rotor Amps (LRA)
Motor
HP
Motor
Type
Motor Type
Nominal
RPM
Nominal
RPM
Full Load
Amps (FLA)
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
Locked Rotor
Amps (LRA)
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Locked
Rotor Amps (LRA)
Motor
HP
Motor Type
Nominal
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XP16−048−230−01 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−02 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−03 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−04 45 28.2 21.15 96.0 1/4 PSC 825 1.7 3.1
XP16−048−230−05 45 28.2 21.15 96.0 1/3 PSC 825 1.8 2.9
208/230V−60 Hz−1 Ph
Unit Compressor Condenser Fan
Model Number
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated Load
Amps (RLA)
2
Locked
Rotor Amps (LRA)
Motor
HP
Motor Type
Nominal
3
RPM
Full Load
Amps (FLA)
Locked Rotor
Amps (LRA)
XP16−060−230−01 55 33.9 25.64 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−02 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−03 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
XP16−060−230−04 60 33.9 25.87 118.0 1/3 PSC 825 1.8 2.9
700
XP16−060−230−05 60 35.1 25.87 118.0 1/3 VS
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
3
PSC = permanent split capacitor motor (single speed); VS = variable speed.
(1st Stage)
820
(2nd Stage)
2.8 N/A
XP16
Page 3
Page 4
Unit Dimensions − Inches (mm)
A
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
C
9−1/2 (241)
8−1/4 (210)
4−3/4"
(121)
UNIT SUPPORT FEET
B
TOP VIEW
D
E
F
G
XP16−036 to −060 BASE WITH LEGS
K
J
H
UNIT SUPPORT
FEET
8−1/2 (216)
8−3/4 (222)
SIDE VIEW
5−1/2 (140)
13−1/2
(343)
XP16−024 BASE SECTION
4−1/2"
(108)
Model Number A B C D E F G H J K
XP16−024−01,
−02, −03, −04
31 (889) 27 (686) 28 (711)
XP16−024−05 35 (889) 27 (686) 28 (711)
XP16−036−01,
−02, −03, −04
35 (889) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−036−05 39 (991) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−048−01,
−02, −03, −04
XP16−048−05 35 (889) 35−1/2 (902)
XP16−060−01,
−02, −03, −04
XP16−060−05 45 (1143 35−1/2 (902)
45 (1143) 30−1/2 (775) 35 (889)) 16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
39 (991) 35−1/2 (902)
39−1/2 (1003)
39−1/2 (1003)
39−1/2 (1003)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
Page 4
XP16
Page 5
Typical Unit Parts Arrangement
CAPACITOR (LOCATION OF CAPACITOR VARIES.)
DEFROST CONTROL (A108)
GROUND
LUG
CONTACTOR
(K−1)
AMBIENT TEMPERATURE SENSOR (RT13)
DISCHARGE LINE SENSOR (RT28)
REVERSING VALVE
REVERSING VALVE SOLENOID
TRUE SUCTION PORT
HIGH PRESSURE SWITCH (S4)
COMPRESSOR
CHECK
EXPANSION VALVE
FOR COIL SENSOR (RT21) LOCATION
SEE FIGURE 2.
XP16
LOW PRESSURE SWITCH (S87)
EXPANSION VALVE SENSING BULB
LIQUID VALVE AND GAUGE PORT / LIQUID LINE CONNECTIONS
Figure 1. Typical Parts Arrangements
Page 5
CRANKCASE HEATER THERMOSTAT (S40)
VAPOR VALVE AND GAUGE
PORT / SUCTION LINE
CONNECTIONS
LIQUID LINE BI−FLOW FILTER DRIER
Page 6
XP16−024
COIL SENSOR −THIRD HAIRPIN DOWN FROM THE TOP ON INSIDE ROW.
XP16−036
COIL SENSOR − NINTH HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−048
COIL SENSOR − EIGHT HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−060
COIL SENSOR − SIXTH HAIRPIN UP FROM THE BOTTOM
ON INSIDE ROW.
XP16−024
COIL SENSOR 7 tubes up from bottom (7−1/2")
XP16−036
COIL SENSOR 17 tubes up from bottom (17−1/2")
XP16−060
COIL SENSOR 12 tubes up from bottom (11−1/2")
XP16−048
COIL SENSOR 13 tubes up from bottom (12−1/2")
(XP16−XXX−230−05)
(XP16−XXX−230−01 through 04)
CLIP COIL TEMPERATURE SENSOR FROM THE DEFROST BOARD ON THE RETURN BEND SHOWN.
Figure 2. Coil Sensor (RT21) Locations
Page 6
XP16
Page 7
WARNING
IMPORTANT
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 3 provides information on how to access and operating both angle and ball service valves.
XP16
Page 7
Page 8
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CORE
TO OUTDOOR UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
roate stem counterclockwise 90°. To close rotate stem clock­wise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
STEM CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
WHEN SERVICE VALV E IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
D With torque wrench: Finger tighten and
torque cap per table 1.
D Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
D With Torque Wrench: Finger tighten and
then torque cap per table 1.
D Without Torque Wrench: Finger
tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
9
10
9
10
8
12
11
8
7
6
12
11
7
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
3
4
5
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball Service Valves
Page 8
XP16
Page 9
Recovering Refrigerant from System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
1
switch or main fuse box/breaker panel.
MAIN FUSE BOX/BREAKER PANEL
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing HCFC−22 refrigerant using one of the following procedures:
3
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil vol-
umes, and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit
D Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. D Compressor can stop pumping due to tripped internal pressure relief valve. D Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing HCFC−22 system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor
unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve. D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
:
to go into a vacuum.
Figure 4. Refrigerant Recovery
XP16
Page 9
Page 10
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
12 (305)
6 (152)
36 (914)
ACCESS PANEL
CONTROL PANEL
ACCESS
LOCATION
30 (762)
LINE SET CONNECTIONS
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
Figure 5. Installation Clearances
NOTES:
D Clearance to one of the other three
sides must be 36 inches (914mm).
D Clearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 5 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
D Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
D When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 6, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 6, detail B.
NOTE  If necessary for stability, anchor unit to slab as described in figure 6, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 6, detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
Page 10
XP16
Page 11
DETAIL A
Install unit away from windows.
 Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.
 Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
DETAIL C
Elevated Slab Mounting
using Feet Extenders
LEG DETAIL
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
BASE
GROUND LEVEL
STABILIZING UNIT ON UNEVEN SURFACES
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
#10 1−1/4" LONG HEX HD SCREW
Concrete slab  use two plastic anchors (hole drill 1/4")
Wood or plastic slab  no plastic anchor (hole drill 1/8")
DETAIL E
Stabilizing bracket (18 gauge metal  2" (50.8mm) width; height as required); bend to form right angle as exampled below.
 Slab Side Mounting
REQUIRED)
AND FLAT WASHER
 Deck Top Mounting
MINIMUM ONE
PER SIDE
COIL
BASE PAN
CORNER POST
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.
SAME FASTENERS AS SLAB SIDE MOUNTING.
FOR EXTRA
STABILITY
Figure 6. Placement, Slab Mounting and Stabilizing Unit
XP16
Page 11
Page 12
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
With unit positioned at installation site, perform the following
1. Remove two side louvered panels to expose the unit
2. Install the brackets as illustrated in figure 6, detail D or
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
:
base.
E using conventional practices.
Removing and Installing Panels
IMPORTANT
Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
IMPORTANT
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Page 12
XP16
Page 13
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly.
2. Hold the panel firmly throughout this procedure. Rotate bot-
tom corner of panel away from hinged corner post until low­er three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as pos­sible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as il­lustrated in detail A and C; then upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
IMPORTANT ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
SCREW
LIP
DETAIL A
DETAIL B
ANGLE MAY BE TOO EXTREME
HOLES
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
HOLD DOOR FIRMLY TO THE HINGED
PANEL
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
PREFERRED ANGLE FOR INSTALLATION
Figure 7. Removing and Installing Panels
XP16
Page 13
Page 14
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 16.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page
19).
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.
Table 2. Refrigerant Line Set  Inches (mm)
Model
−018
−024
−030
−036
−042
−048
−060
Valve Field Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liqui d Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to communicate the following information:
D Model (XP16) and size of unit (e.g. −036).
D Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
D Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
WARNING
Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must
be added, it must be a Polyol Ester oil.
Page 14
XP16
Page 15
Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL STUD
NON−CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping materi­al or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
XP16
ROOF RAFTER
Figure 8. Line Set Installation
Page 15
Page 16
Brazing Connections
Use the procedures outline in figures 9 and 10 for brazing line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture − Check the high and low pressures before applying heat.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
IMPORTANT
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could re­sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
Page 16
XP16
Page 17
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT CORE
LIQUID LINE SERVICE
VALV E
SERVICE
PORT CORE
SERVICE PORT CAP
SUCTION / VAPOR LINE
SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.
A Connect gauge set low pressure side to
liquid line service valve (service port).
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
ATTACH
GAUGES
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
LOW
HIGH
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
XP16
Figure 9. Brazing Procedures
Page 17
Page 18
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve
5
and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
BRAZE LINE SET
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water
6
saturated cloths must remain water saturated throughout the brazing and cool−down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT  Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed joint. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER SATURATED CLOTH
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a water
saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step in preparing the unit.
SUCTION / VAPOR LINE
SERVICE VALVE
WATER SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 10. Brazing Procedures (continued)
Page 18
XP16
Page 19
Flushing Line Set and Indoor Coil
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
D Remove and discard fixed orifice, valve stem assembly if present and
Teflon
E Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
washer as illustrated above.
®
SEAL
FIXED ORIFICE
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE (UNCASED
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INV ERTED HCFC−22 CYLINDER CONTAINS CLE AN HCFC−22 TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
VAPOR
LIQUID
D
RECOVERY
CYLINDER
A Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
B HCFC−22 gauge set (low side) to the liquid line valve. C HCFC−22 gauge set center port to inlet on the recovery machine with
an empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
OUTDOOR
B
NEW
UNIT
OPENED
C
RECOVERY MACHINE
MANIFOLD
LOW
TANK RETURN
INLET
DISCHARGE
GAUGE
HIGH
CLOSED
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
LINE
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
G Remove and discard check expansion valve and the two Teflon
rings.
H Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line
B
set and indoor unit coil.
B Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
®
XP16
Figure 11. Installing Indoor Expansion Valve
Page 19
Page 20
Installing Indoor Metering Device
This outdoor unit is designed for use in systems that use check expansion valve metering devices at the indoor coil.
See the Lennox XP16 Engineering Handbook for approved expansion valve kit match−ups. The expansion valve unit can be installed internal or external to the indoor coil. In
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
A Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
B Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
CHECK
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
LIQUID LINE
BRASS NUT
®
RING
SENSING
LINE
LIQUID LINE
SENSING BULB INSTALLATION
applications where an uncased coil is being installed in a field−provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit.
A Remove the field−provided fitting that temporary
reconnected the liquid line to the indoor unit’s distributor assembly.
B Install one of the provided Teflon
®
rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the
®
Teflon
ring with refrigerant oil.
C Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.
D Place the remaining Teflon
end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon
®
washer around the other
®
ring with
refrigerant oil.
E Attach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and screws provided.
NOTE  Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the expansion valve to
the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
1/2 Turn
10
9
8
10
9
8
12
11
7
6
1/8 Turn
12
11
7
6
1
2
3
4
5
1
2
3
4
5
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
VAPOR LINE
12
BULB
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
Figure 12. Installing Indoor Expansion Valve
Page 20
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
XP16
Page 21
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
CONNECT GAUGE SET
A Connect an HFC−410A manifold gauge set high pressure
1
hose to the vapor valve service port.
NOTE  Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of
HFC−410A refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
Leak Test Line Set and Indoor Coil
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
A
2
XP16
TO VAPOR
SERVICE VALVE
NITROGEN
HFC−410A
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the
valve on the HFC−410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A.
[A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a
leak detector.
F After leak testing disconnect gauges from service ports.
Figure 13. Leak Test
Page 21
Page 22
Evacuating Line Set and Indoor Coil
CONNECT GAUGE SET
NOTE  Remove cores from service valves (if not already done).
1
A
Connect low side of manifold gauge set with 1/4 SAE in−line tee to vapor line service valve
B
Connect high side of manifold gauge set to liquid line service valve
C
Connect micron gauge available connector on the 1/4 SAE in−line tee.
D
Connect the vacuum pump (with vacuum gauge) to the center port of
NITROGEN
the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
LOW
MANIFOLD
D
EVACUATE THE SYSTEM
A Open both manifold valves and start the vacuum pump.
2
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
D Close manifold gauge valves D Close valve on vacuum pump D Turn off vacuum pump D Disconnect manifold gauge center port hose from vacuum pump D Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. D Open manifold gauge valves to break the vacuum in the line set and indoor unit. D Close manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
RECOMMEND
MINIMUM 3/8" HOSE
HIGH
D Close manifold gauge valves. D Shut off HFC−410A cylinder. D Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
D Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
Figure 14. Evacuating System
Page 22
10
9
8
1/6 TURN
12
11
7
6
1
2
3
4
5
XP16
Page 23
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
UNIT LOW VOLTAGE CONNECTIONS
3
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control panel.
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
XP16
A
D
B
C
TERMINAL STRIP
Page 23
A Run 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie. C Make 24VAC control wire connections defrost control terminal
strip.
D Tighten wire tie to security 24V control wiring.
NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.
NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
Page 24
Servicing Units Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedure outlined on page
21.
2. Evacuate the system using procedure outlined on page
22.
3. Use nitrogen to break the vacuum and install a new filter
drier in the system.
4. Evacuate the system again using procedure outlined on
page 22.
5. Weigh in refrigerant using procedure outlined in figure
18.
6. Monitor the system to determine the amount of moisture
remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the
compressor will fail in the future.
Unit Start−Up
2. Inspect all factory− and field−installed wiring for loose
connections.
3. After evacuation is complete, open both the liquid and
vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in
table 1.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power
to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
8. Check system for sufficient refrigerant by using the
procedures listed under System Charge.
IMPORTANT
1. Rotate fan to check for binding.
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
REFRIGERANT TANK
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
INSIDE OUTDOOR UNIT
TEMPERATURE
D
SENSOR
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
MANIFOLD GAUGE SET
LOW
HIGH
OUTDOOR UNIT
A
C
TO LIQUID
LINE SERVICE
VALV E
TEMPERATURE SENSOR
(LIQUID LINE)
A Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
B Connect the manifold gauge set’s low pressure side to the true suction port. See figure 1 for approximate location of the true suction port.
C Connect the manifold gauge set’s high pressure side to the liquid line service port.
D Position temperature sensor on liquid line near liquid line service port.
Figure 15. Gauge Set Setup and Connections
Page 24
XP16
Page 25
CHARGING INFORMATION FOR MODEL XP16−XXX−230−01 AND XP16−XXX−230−02
Unit Charging Sticker − 401193S, dated 02/06
If the system is low on charge, follow the appropriate procedure outlined below. Charging should be done with unit operating in the cooling mode, if possible.
Charge Using The Weigh−in MethodOutdoor
Temperature < 65ºF (18ºC( If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been repaired.
1. Recover the refrigerant from the unit.
2. Conduct a leak check, then evacuate as previously
outlined.
3. Weigh in the unit nameplate charge. If weighing facilities
are not available or if you are charging the unit during warm weather, follow one of the other procedures outlined below.
Charge Using The Subcooling MethodOutdoor
Temperature < 65ºF (18ºC) When the outdoor ambient temperature is below 65ºF
(18ºC), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 325−375 psig (2240−2585 kPa) range. See figure 16.
Block coil one side at a time with cardboard/plastic until proper testing pressures are reached.
CARDBOARD OR PLASTIC SHEET
Figure 16. Blocking Outdoor Coil
1. With manifold gauge hose still on the liquid service port
and unit operating stably, use a digital thermometer to record the liquid line temperature. At the same time, record the liquid line pressure reading.
2. Use a temperature/pressure chart for HFC−410A to
determine the saturation temperature for the liquid line pressure reading.
3. Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine subcooling. (Saturation temperature − Liquid line
temperature = Subcooling)
4. Compare subcooling values with those in table 1; if
subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant.
Charge Using Normal Operating Pressures/Approach Method
>
65ºF (18ºC)
When outdoor ambient temperature is above 65_F (18_C), use approach charge method. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital
thermometer.
2. Attach high pressure gauge set; operate unit for several
minutes; allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in
table 3. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
Use the same digital thermometer to check both outdoor ambient temperature and liquid line temperature. Verify the unit charge using the approach method.
4. The difference between the ambient and liquid
temperatures should match values given in table 2. If values do not agree with the those in table 2, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Outdoor Temperature
Using the Normal Operating Pressures Table
Use table 3 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (see Charging/Checking Charge section). Minor variations in normal operating pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
XP16
Page 25
Page 26
Table 3 − Indoor Units Matchups and Subcooling Charge Levels (XP16−XXX−230−05)
XP16 Model −024 −036 −048 −060
Charging Temperatures and Pressures
Table 1 − Subcooling Values
Saturation Temperature minus Liquid Line Temperature °F (ºC) + 1ºF (0.5ºC)
Temp. °F (°C)
Table 2 − Approach Values
Liquid Line Temperature minus Outdoor Ambient Temperature ºF (ºC) + 1ºF (0.5ºC)
Temp. °F (°C)
Table 3 − Normal Operating Pressures (Liq. +10 & Vap. +5 psig) ** Temp. °F
(°C)*
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Cooling − First Stage (Low Capacity) 65 (18.3) 232 146 225 144 235 144 225 138 75 (23.9) 264 148 261 147 268 145 264 141 85 (29.4) 307 149 302 149 310 147 305 142 95 (35.0) 353 151 349 151 356 148 352 146 105 (40.6) 403 153 397 153 407 150 405 148 115 (46.1) 460 155 461 157 466 152 459 150 Cooling − Second Stage (High Capacity) 65 (18.3) 240 143 239 139 244 140 241 134 75 (23.9) 279 145 278 141 283 141 280 136 85 (29.4) 322 147 322 143 326 144 324 137 95 (35.0) 371 149 367 146 374 147 373 138 105 (40.6) 423 151 426 148 427 148 425 142 115 (46.1) 485 154 489 151 491 151 486 146
Heating − First Stage (Low Capacity) 40 (4.4) 337 93 328 98 369 75 351 63 50 (10) 322 117 333 118 366 114 335 92 Heating − Second Stage (High Capacity) 20 (−7.0) 279 62 296 62 311 58 308 59 30 (−1.0) 288 76 309 75 334 72 323 70 40 (4.4) 302 93 322 92 354 89 318 69 50 (10) 306 112 336 113 381 108 329 82
* Outdoor Coil Entering Air Temp. F (C)
** These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
8 (4.4)
7 (3.9)
9 (5) 8 (4.4)
8 (4.4) 9 (5) 8 (4.4) 8 (4.4)
Page 26
XP16
Page 27
CHARGING INFORMATION FOR MODEL XP16−XXX−230−03, XP16−XXX−230−04 and XP16−XXX−230−05
ADDING OR REMOVING REFRIGERANT
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22.
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (
DT) process using the
illustration in Figure 17.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
AIRFLOW
INDOOR COIL
Temperature of air entering indoor coil ºF
A
Wet−bulb ºF
D Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
D Measuring voltage supplied to the unit, D Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
Dry−bulb
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
DRY
BULB
C
53º
T
19º
Drop
air flow
air flow
B
A
72º
B
64º
DRY BULB
WET BULB
All temperatures are expressed in ºF
INDOOR COIL
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. Determine the desired DT  Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the inter­secting value of A and B in the table (see triangle).
2. Find temperature drop across coil  Measure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustment  If the difference between the measured T is within +
3º, no adjustment is needed. See example below:
) = A minus C.
Drop
and the desired DT (T
Drop
Drop
DT)
Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
T
53º 19 – 15 = 4 Increase the airflow 58º 14 – 15 = −1 (within +3º range) no change 62º 10 – 15 = −5 Decrease the airflow
DT = ºF ACTION
Drop
Changing air flow affects all temperatures; recheck tem­peratures to confirm that the temperature drop and DT are within +
3º.
4. Adjust the fan speed  See indoor unit instructions to increase/decrease fan speed.
Figure 17. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart Formula
XP16
Page 27
Page 28
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for verifying
refrigerant charge.
WEIGH IN
CHARGING METHOD
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount specified on
nameplate
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Adjust amount. for variation
in line set length listed on
line set length table below.
+
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Additional charge
specified per indoor unit
match−ups
+
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Total charge
=
Figure 18. Using HFC−410A Weigh In Method
Page 28
XP16
Page 29
SUBCOOLING
CHARGING METHOD
1. Check the airflow as illustrated in figure 17 to be sure the indoor airflow is as required.
(Make any air flow adjustments before continuing with the following procedure.)
SATº LIQº – SCº =
USE
COOLING
MODE
60ºF
(15ºC)
USE
HEATING
MODE
2. Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge.
3. Connect gauge set.
4. Check liquid and vapor line pressures. Compare pressures with either heat or cooling
mode normal operating pressures in the Normal Operating Pressures Tables, Second Stage  High Capacity.
NOTE
The reference table is a general guide. Expect minor pressure variations.
Significant differences may mean improper charge or other system problem.
5. Set thermostat for heat/cool demand, depending on mode being used:
USING COOLING MODE  When the outdoor ambient temperature is 60°F (15°C) and
above. Target subcooling values (second stage − high capacity) in the Normal Operating Pressures Tables are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC) which should call for second−stage (high capacity) cooling. When pressures have stabilized, continue with Step 6.
USING HEATING MODE  When the outdoor ambient temperature is below 60°F (15°C).
Target subcooling values (second−stage − high capacity) in the Normal Operating Pressures Tables are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC) which should call for second−stage (high capacity) heating. When pressures have stabilized, continue with Step 6.
6. Read the liquid line temperature; record in the LIQº space.
7. Read the liquid line pressure; then find its corresponding temperature in the temper-
ature/ pressure chart listed in table 2 and record it in the SATº space.
8. Subtract LIQº temperature from SATº temperature to determine subcooling; record
it in SCº space.
9. Compare SCº results with tables under Indoor unit match ups, being sure to note
any additional charge for line set and/or match−up.
10. If subcooling value is greater than shown in tables under indoor unit matchups for
the applicable unit, remove refrigerant; if less than shown, add refrigerant.
11. If refrigerant is added or removed, repeat steps 5 through 6 to verify charge.
12. Disconnect gauge set and re−install both the liquid and suction service valve caps.
Figure 19. Using HFC−410A Subcooling Method  Second Stage (High Capacity)
XP16
Page 29
Page 30
CHARGING INFORMATION FOR MODEL XP16−XXX−230−03
Unit Charging Sticker − 401233S, dated 01/08
Table 4 − Indoor Units Matchups and Subcooling Charge Levels (XP16−XXX−230−05)
INDOOR HEAT MATCH UPS PUMP
XP16–024
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
lb oz
INDOOR HEAT MATCH UPS PUMP
XP16–036
CBX26UH–018 20 8 1 5 CH23–51 17 7 0 13 CH23–68 15 13 0 7
CBX26UH–024 20 8 1 5 CH23–65 12 8 1 10 CB27UH−048 17 7 0 0
CB27UH−024 12 6 0 12 CBX26UH–030 25 8 1 14 CB27UH−060 17 7 0 0
CB27UH−030 13 9 1 12 CBX26UH–036 25 8 1 14 CB30U–51, –65 17 7 0 0
CB30U–21/26 12 6 0 12 CB27UH−036 17 8 2 4 CBX32M–048, –060 17 7 0 0
CB30U–31 13 9 1 12 CB27UH−042 17 8 2 4 CBX32MV–068 16 10 0 3
CBX32M–018/024 12 6 0 12 CB30U–31 17 6 0 0 CH33–60D–2F 18 4 0 2
CBX32M–030 13 9 1 12 CB30U–41/46 17 8 2 4 CH33–62D–2F 15 10 0 4
CBX32MV–024/030 13 9 1 12 CBX32M–030 17 6 0 0 CR33–60 40 4 0 2
CBX32MV–036 12 9 0 10 CBX32M–036 17 8 2 4 CX34–60D–6F 18 4 0 2
CH33–25B 17 4 0 0 CBX32MV–024/030 17 6 0 0 CX34–62D–6F 16 8 0 2
CH33–36A–2F 12 6 0 10 CBX32MV–036 17 8 2 4
CH33–36B–2F 17 4 0 0 C33–44C 17 8 1 14 CH23–68 13 14 3 3
CH33–36C–2F 12 7 1 2 CH33–42B–2F 17 7 0 13 CH23–65 18 2 0 0
CR33–24A/B–F 20 4 0 0 CH33–44/48B–2F 12 8 1 8 CBX26UH–060 13 14 3 5
CR33–30/36A/B/C–F 20 8 1 6 CH33–48C–2F 10 8 1 6 CB27UH−060 13 10 2 1
CR33–48 21 9 0 3 CH33–43B 9 10 1 6 CBX32M–060 13 10 2 1
CX34–25A/B–6F 12 6 0 12 CH33–49C 9 10 1 6 CBX32MV–068 13 12 2 9
CX34–31A/B–6F 20 9 1 12 CR33–48B/C–F 25 8 2 0 CH33–60D–2F 15 6 1 3
CX34–36A/B/C–6F 17 5 0 5 CR33–50/60C–F 25 9 0 14 CH33–62D–2F 13 12 2 10
CX34–38A/B–6F Serial
No# before 6007K
CX34–38A/B–6F Serial
No# 6007K and after
31 7 0 8
10 8 0 11
CX34–38A/B–6F Serial No#
before 6007K
CX34–38A/B–6F Serial No#
6007K and after
CX34–19 18 4 0 1 CX34–43B/C–6F 10 8 1 6 CX34–49C–6F 13 9 1 14
CX34–60D 9 9 0 14 CX34–60D–6F 15 6 1 3
**Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
lb oz
INDOOR HEAT MATCH UPS PUMP
XP16–048
XP16XP16–060
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
lb oz
lb oz
31 7 1 5 CR33–50/60C–F 30 6 1 3
10 8 1 12 CR33–60D–F 30 6 1 3
CX34–62C–6F 13 11 2 6
CX34–62D–6F 13 11 2 5
Page 30
XP16
Page 31
Table 1 − Normal Operating Pressures (Liquid +10 & Suction +5 psig) (XP16−XXX−230−03)
048−060
*Temperature
of the air
entering the
outdoor coil.
Cooling
First Stage
(Low Capacity)
Cooling
Second Stage
(High
Capacity)
Heating
First Stage
(Low Capacity)
Heating
Second Stage
(High Capac-
ity)
Model −024 −036
°F (°C)* Liquid Line Pressure/Vapor Line Pressure
65 (18) 232 / 146 225 / 144 235 / 144 225 / 138
75 (24) 264 / 148 261 / 147 268 / 145 264 / 141
85 (29) 307 / 149 302 / 149 310 / 147 305 / 142
95 (35) 353 / 151 349 / 151 356 / 148 352 / 146
105 (41) 403 / 153 397 / 153 407 / 150 405 / 148
115 (45) 460 / 155 461 / 157 466 / 152 459 / 150
65 (18) 240 / 143 239 / 139 244 / 140 241 / 134
75 (24) 279 / 145 278 / 141 283 / 141 280 / 136
85 (29) 322 / 147 322 / 143 326 / 144 324 / 137
95 (35) 371 / 149 367 / 146 374 / 147 373 / 138
105 (41) 423 / 151 426 / 148 427 / 148 425 / 142
115 (45) 485 / 154 489 / 151 491 / 151 486 / 146
50 (10) 322 / 117 333 / 11 8 366 / 114 335 / 92
40 (4.5) 337 / 93 328 / 98 369 / 75 351 / 63
50 (10) 306 / 112 336 / 11 3 381 / 108 329 / 82
40 (4.5) 302 / 93 322 / 92 354 / 89 318 / 69
30 (−1) 288 / 76 309 / 75 334 / 72 323 / 70
20 (−7) 279 / 62 296 / 62 311 / 58 308 / 59
XP16
Page 31
Page 32
CHARGING INFORMATION FOR MODEL XP16−XXX−230−04
Unit Charging Sticker − 580094−01, dated 05/09
Table 2 − Indoor Units Matchups and Subcooling Charge Levels (XP16−XXX−230−05)
Target
INDOOR HEAT MATCHUP PUMP
XP16–024
Subcooling
Heat
5ºF
+
Cool
1ºF
+
*Add
charge
lb oz
INDOOR HEAT MATCHUP PUMP
XP16–036
CB30U–21/26 12 6 0 12 C33–44C 17 8 1 14 CB27UH−048 17 7 0 0
CB30U–31 13 9 1 12 CB27UH−036 17 8 2 4 CB27UH−060 17 7 0 0
CBX26UH–018 20 8 1 5 CB27UH−042 17 8 2 4 CB30U–51, –65 17 7 0 0
CBX26UH–024 20 8 1 5 CB30U–31 17 6 0 0
CB27UH−024 12 6 0 12 CB30U–41/46 17 8 2 4
CB27UH−030 13 9 1 12 CBX26UH–030 25 8 1 14 CBX32MV–068 16 10 0 3
CBX32M–018/024 12 6 0 12 CBX26UH–036 25 8 1 14 CH23–68 15 13 0 7
CBX32M–030 13 9 1 12 CBX32M–030 17 6 0 0 CH33–60D–2F 18 4 0 2
CBX32MV–024/030 13 9 1 12 CBX32M–036 17 8 2 4 CH33–62D–2F 15 10 0 4
CBX32MV–036 12 9 0 10 CBX32MV–024/030 17 6 0 0 CR33–60 40 4 0 2
CBX40UHV–024,
−030
CBX40UHV–036 12 9 0 10
CH33–25B 17 4 0 0
13 9 1 12 CBX32MV–036 17 8 2 4 CX34–60D–6F 18 4 0 2
CBX40UHV–024,
−030
CBX40UHV–036,
−042
CH33–36A–2F 12 6 0 10 CH23–51 17 7 0 13 CB27UH−060 13 10 2 1
CH33–36B–2F 17 4 0 0 CH23–65 12 8 1 10 CBX26UH–060 13 14 3 5
CH33–36C–2F 12 7 1 2 CH33–42B–2F 17 7 0 13 CBX32M–060 13 10 2 1
CR33–24A/B–F 20 4 0 0 CH33–44/48B–2F 12 8 1 8 CBX32MV–060 13 10 2 1
CR33–30/36A/B/C–F 20 8 1 6 CH33–48C–2F 10 8 1 6 CBX32MV–068 13 12 2 9
CR33–48 21 9 0 3 CH33–43B 9 10 1 6 CH23–68 13 14 3 3
CX34–25A/B–6F 12 6 0 12 CH33–49C 9 10 1 6 CH23–65 18 2 0 0
CX34–31A/B–6F 20 9 1 12 CR33–48B/C–F 25 8 2 0 CH33–60D–2F 15 6 1 3
CX34–36A/B/C–6F 17 5 0 5 CR33–50/60C–F 25 9 0 14 CH33–62D–2F 13 12 2 10
CX34–38A/B–6F SN be-
fore 6007K
CX34–38A/B–6F SN
6007K and after
31 7 0 8
10 8 0 11
CX34–38A/B–6F SN be-
fore 6007K
CX34–38A/B–6F SN
6007K and after
CX34–19 18 4 0 1 CX34–43B/C–6F 10 8 1 6 CX34–49C–6F 13 9 1 14
SN indicates coil serial number. CX34–60D 9 9 0 14 CX34–60D–6F 15 6 1 3
*Amount of charge required in additional to charge shown on unit nameplate. (Remem­ber to consider lin
e set length difference.)
Target
Subcooling
Heat
5ºF
+
Cool
1ºF
+
*Add
charge
lb oz
INDOOR HEAT MATCHUP PUMP
XP16–048
CBX32M–048, –060
CBX32MV–048, –060
Target
Subcooling
Heat
5ºF
+
Cool +
1ºF
*Add
charge
lb oz
17 7 0 0
17 7 0 0
17 6 0 0 CX34–62D–6F 16 8 0 2
17 8 2 4 XP16–060 lb oz
31 7 1 5 CR33–50/60C–F 30 6 1 3
10 8 1 12 CR33–60D–F 30 6 1 3
CX34–62C–6F 13 11 2 6
CX34–62D–6F 13 11 2 5
Page 32
XP16
Page 33
Table 1 − HFC−410A Normal Operating Pressures (Liquid +10 & Suction +5 psig) (XP16−XXX−230−04)
036
*Temperature
of the air
entering the
outdoor coil.
Cooling
First Stage
(Low Capacity)
Cooling
Second Stage
(High
Capacity)
Heating
First Stage
(Low Capacity)
Heating
Second Stage
(High Capac-
ity)
Model −024
°F (°C)* Liquid Line Pressure/Vapor Line Pressure
65 (18) 232 / 146 225 / 144 235 / 144 225 / 138
75 (24) 264 / 148 261 / 147 268 / 145 264 / 141
85 (29) 307 / 149 302 / 149 310 / 147 305 / 142
95 (35) 353 / 151 349 / 151 356 / 148 352 / 146
105 (41) 403 / 153 397 / 153 407 / 150 405 / 148
115 (45) 460 / 155 461 / 157 466 / 152 459 / 150
65 (18) 240 / 143 239 / 139 244 / 140 241 / 134
75 (24) 279 / 145 278 / 141 283 / 141 280 / 136
85 (29) 322 / 147 322 / 143 326 / 144 324 / 137
95 (35) 371 / 149 367 / 146 374 / 147 373 / 138
105 (41) 423 / 151 426 / 148 427 / 148 425 / 142
115 (45) 485 / 154 489 / 151 491 / 151 486 / 146
50 (10) 333 / 116 318 / 11 6 354 / 115 365/ 113
40 (4.5) 314 / 88 304 / 89 324 / 92 341 / 89
50 (10) 346 / 109 333 / 11 0 370 / 110 369 / 107
40 (4.5) 321 / 89 314 / 88 345 / 92 348 / 86
30 (−1) 303 / 74 303 / 77 322 / 70 335 / 73
20 (−7) 286 / 59 289 / 63 305 / 61 318 / 59
−048 −060
XP16
Page 33
Page 34
CHARGING INFORMATION FOR MODEL XP16−XXX−230−05
Unit Charging Sticker − 580275−01, dated 12/09
Table 2 − Indoor Units Matchups and Subcooling Charge Levels (XP16−XXX−230−05)
Target
INDOOR HEAT MATCHUP PUMP
Subcooling
Heat
5ºF
+
Cool
1ºF
+
*Add charge
INDOOR HEAT MATCHUP PUMP
XP16−024 CBX40UHV−042 24 11 3 0 CH33−60D 13 8 0 0
CBX26UH−024 45 6 0 15 CBX40UHV−048 24 11 3 0 CH33−62D 11 9 1 4
CBX27UH−024−2 30
CBX27UH−030−2 30
CBX32MV−024/0 30
20 7 0 9 CH33−43B 13 10 2 7 CR33−50/60C 15 7 0 10
17 7 1 3 CH33−48C 37 11 2 11 CR33−60D 16 7 0 10
20 7 0 9 CH33−43C 37 11 2 11 CX34−60D 14 8 1 0
CBX32MV−036 17 7 1 3 CR33−48B/C 49 7 0 9 CX34−62D 9 9 1 6
CBX40UHV−024 17 7 1 3 CX34−43B/C 29 9 2 11 CX34−62C 8 9 1 9
CBX40UHV−030 17 7 1 3 CX34−50/60C 29 9 2 11 XP16−060
CBX40UHV−036 17 7 1 3 XP16−048 CBX26UH−060 20 9 4 13
CH33−31B 31 8 1 12 CBX26UH−048 10 8 1 4
CR33−30/36A/B/C 45 4 0 0 CBX27UH−048 19 9 1 4 CBX32M−060 17 6 1 12
CX34−31A/B 24 7 1 11 CBX27UH−060 13 14 3 3 CBX32MV−060 17 6 1 12
CX34−38A/B 18 8 1 10 CBX32M−048 19 9 1 4 CBX32MV−068 15 7 2 1
XP16−036 CBX32M−060 14 9 1 11 CBX40UHV−060 17 6 1 12
CBX26UH−036 50 5 0 0 CBX32MV−048 19 9 1 4 CH23−68 37 9 2 10
CBX27UH−036−2 30
CBX27UH−042−2 30
22 7 0 9 CBX32MV−060 14 9 1 11 CH33−50/60C 33 8 1 0
24 11 3 0 CBX32MV−068 9 8 1 11 CH33−62D 16 7 1 4
CBX32M−036 22 7 0 9 CBX40UHV−048 19 9 1 4 CR33−50/60C 24 7 0 0
CBX32MV−036 22 7 0 9 CBX40UHV−060 14 9 1 11 CR33−60D 24 7 0 0
CBX32MV−048 24 11 3 0 CH23−68 24 10 1 12 CX34−62C 21 9 2 16
CBX40UHV−030 22 7 0 9 CH33−49C 19 9 2 5 CX34−62D 13 7 1 4
CBX40UHV−036 22 7 0 9 CH33−50/60C 19 9 2 5
Target
Subcooling
Heat
5ºF
+
Cool
1ºF
+
*Add charge
Target
INDOOR HEAT MATCHUP PUMP
CBX27UH−060−2 30
Subcooling
Heat
5ºF
+
Cool
1ºF
+
*Add charge
10 6 2 3
*Amount of charge required in additional to charge shown on unit nameplate. (Remem­ber to consider lin
e set length difference.)
Page 34
XP16
Page 35
Table 1 − HFC−410A Normal Operating Pressures (Liquid +10 & Suction +5 psig) (XP16−XXX−230−05)
First Stage (Low Capac-
ity) Pressure
Second Stage (High Ca-
pacity) Pressure
First Stage (Low Capac-
ity) Pressure
Second Stage (High Ca-
pacity) Pressure
Size −024 −036 −048 −060
Model XP16 Only XP16 and SPB*H4
F (C) Liq Vap Liq Vap Liq Va p Liq Vap
Normal Operating Pressures − Cooling
65 (18.3) 226 144 220 141 224 143 230 137
75 (23.9) 260 145 254 144 259 143 267 139
85 (29.4) 301 148 295 148 302 147 311 141
95 (35.0) 346 151 340 150 346 149 357 144
105 (40.6) 396 153 389 153 396 152 398 147
115 (46.1) 451 156 444 156 450 155 453 149
65 (18.3) 241 140 232 129 238 138 232 131
75 (23.9) 279 142 269 136 278 140 276 133
85 (29.4) 321 144 312 140 321 142 320 136
95 (35.0) 369 146 346 142 372 144 367 138
105 (40.6) 421 148 409 145 424 147 421 141
115 (46.1) 480 151 465 148 481 149 479 144
Normal Operating Pressures − Heating
50 (10) 312 112 350 11 5 336 11 4 385 108
60 (15.5) 330 130 372 136 363 135 414 126
20 (−7.0) 299 64 321 61 289 57 332 59
30 (−1.0) 312 79 347 74 294 69 349 67
40 (4.4) 325 93 367 90 321 80 361 75
50 (10) 344 110 387 11 0 341 11 0 383 85
60 (15.5) 358 128 395 131 361 128 425 122
XP16
Page 35
Page 36
Table 2. HFC−410A Temperature (°F) −
Pressure (Psig)
°F
Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
SECOND−STAGE OPERATION
If the board receives a call for second−stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized.
If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage compressor solenoid output will be energized without the Y2 input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used.
The board de−energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason.
THERMOSTAT OPERATION
Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
FILTER DRIER
The unit is equipped with a large−capacity bi−flow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant.
Page 36
XP16
Page 37
Defrost System
DEFROST SYSTEM DESCRIPTION
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR
PLUG IN
(COIL &
AMBIENT
SENSORS)
DELAY
PINS
REVERSING
VALV E
PRESSURE
SWITCH
CIRCUIT
CONNECTIONS
Note − Component locations vary by board manufacturer.
Figure 20. Defrost Control Board
The demand defrost controller measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates when the defrost system starts and after each system defrost cycle. The defrost control board components are shown in figure 20.
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE − The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
DEFROST BOARD PRESSURE SWITCH CONNECTIONS
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the defrost board on the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS)When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions:
D During the defrost cycle and 90 seconds after the
termination of defrost
D When the average ambient sensor temperature is below
15° F (−9°C)
D For 90 seconds following the start up of the compressor D During test mode
LOW AMBIENT THERMOSTAT PINS
DIAGNOSTIC LEDS
24V TERMINAL STRIP CONNECTIONS
High Pressure Switch (HI−PS)When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike.
DEFROST BOARD PRESSURE SWITCH SETTINGS High Pressure (auto reset) − trip at 590 psig, reset at 418.
Low Pressure (auto reset) − trip at 25 psig; reset at 40. PRESSURE SWITCH 5−STRIKE LOCKOUT
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
UNIT TEMPERATURE SENSORS
Sensors connect to the defrost board through a field-replaceable harness assembly that plugs into the board as illustrated in figure 20. Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Sensor resistance values can be checked by ohming across pins shown in table
3.
Table 3. Sensor Temperature /Resistance Range
Temperature
Sensor
Outdoor −35 (−37) to 120 (48) 280,000 to 3750 3 & 4
Coil −35 (−37) to 120 (48) 280,000 to 3750 5 & 6
Discharge (if applicable)
Note: Sensor resistance increases as sensed temperature decreases.
Range °F (°C)
24 (−4) to 350 (176) 41,000 to 103 1 & 2
Resistance values range (ohms)
Pins/W ire Color
(Black)
(Brown )
(Yel­low)
Figure 21 shows how the resistance varies as the temperature changes for both type of sensors.
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not
within the range shown in table 3, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
Ambient SensorThe ambient sensor considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
XP16
Page 37
Page 38
100
TEMPERATURE (ºF)
5750
90
80
70
60
50
40
30
20
10
7450
9275
11775
15425
19975
26200
34375
46275
62700
0
10000 30000 50000 70000 90000
RESISTANCE (OHMS)
85300
Figure 21. Temperature/Resistance Chart
(Ambient and Coil Sensors)
200
300
225
250
280
275
325
260
375
425
240
220
200
180
160
TEMPERATURE (ºF)
140
120
100
500
600
700
825
1000
1175
1400
1700
2025
2500
1000 2000 50004000 60003000
RESISTANCE (OHMS)
3000
3750
4650
5825
Figure 22. Temperature/Resistance Chart
(Discharge Sensor)
Coil SensorThe coil temperature sensor considers
outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
High Discharge Line SensorIf the discharge line temperature exceeds a temperature of 285°F (140°C) during compressor operation, the board will de−energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti−short cycle delay has been satisfied. This sensor has two fault and lockout codes:
1. If the board recognizes five high discharge line
temperature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. Code on board is Discharge Line Temperature Fault and Lockout.
2. If the board recognizes five temperature sensor range
faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before
checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After five faults, the board will lockout. Code on board is Discharge Sensor Fault and Lockout.
The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" refrigerant discharge line.
NOTE − Within a single room thermostat demand, if 5−strikes occur, the board will lockout the unit. Defrost board 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between 1 to 2 seconds to reset the board.
Defrost Temperature Termination Shunt (Jumper) PinsThe defrost board selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If temperature shunt is not installed, default termination temperature is 90°F (32°C).
DELAY MODE
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins.
OPERATIONAL DESCRIPTION
The defrost control board has three basic operational modes: normal, defrost, and calibration.
D Normal ModeThe demand defrost board monitors
the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
D Calibration ModeThe board is considered
uncalibrated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
D Defrost ModeThe following paragraphs provide a
detailed description of the defrost system operation.
D Test Mode See Figure 23.
Each test pin shorting will result in one test event. For each TEST the shunt (jumper) must be removed for at least one second and reapplied. Refer to flow chart (figure 23) for TEST operation.
Note: The Y1 input must be active (ON) and the O room thermostat terminal into board must be inactive.
DETAILED DEFROST SYSTEM OPERATION
The demand defrost control board initiates a defrost cycle based on either frost detection or time.
Frost DetectionIf the compressor runs longer than 30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated.
Page 38
XP16
Page 39
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.
TimeIf six hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
ActuationWhen the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 30 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system temperatures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control or after six hours of heating mode compressor run time has been logged since the last defrost cycle.
TerminationThe defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 30 minutes of run time.
XP16
Page 39
Page 40
TEST
Placing the jumper on the field test pins (E33) allows the technician to:
D Clear short cycle lockout D Clear five−strike fault lockout D Cycle the unit in and out of defrost mode D Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 34 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor fault exist, unit will go into DEFROST MODE. If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE  Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 34 minutes.
Figure 23. Test Mode
Page 40
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
XP16
Page 41
DEFROST BOARD DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 4.
Table 4. Defrost Control Board Diagnostic LEDs
DS2 Green
OFF OFF Power problem No power (24V) to board terminals R and
DS1 Red
Condition/Code Possible Cause(s) Solution
1
Check control transformer power (24V).
C or board failure.
2
If power is available to board and LED(s) do not light, replace board.
Simultaneous SLOW Flash
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
ON ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24VAC power to board. If code does not
Normal operation Unit operating normally or in standby
mode.
5−minute anti−short cycle delay Initial power up, safety trip, end of room
thermostat demand.
Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will revert to time/temper-
ature defrost operation. (System will still heat or cool).
Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform demand
or time/temperature defrost operation. (System will still heat or cool).
clear, replace board.
None required.
None required (Jumper TEST pins to override)
Table 5. Defrost Control Board Diagnostic Fault and Lockout Codes
DS2 Green
(Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
OFF SLOW
OFF ON
SLOW Flash
ON OFF
DS1 Red
Flash
OFF High Pressure Fault
Condition/Code Possible Cause(s) Solution
Low Pressure Fault
Low Pressure LOCKOUT
High Pressure LOCKOUT
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or incorrect operation of metering device.
4
Incorrect or improper sensor location or connection to system.
1
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and subcooling temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.
SLOW Flash
FAST Flash
OFF Fast
Fast Flash
ON Discharge Line Temperature
ON Discharge Line Temperature
Flash
OFF Discharge Sensor
XP16
Fault
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 285ºF (140ºC) during compressor operation, the board will de−energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).
LOCKOUT
Discharge Sensor Fault The board detects open sensor or out of temperature sensor range. This fault is detected by allowing
the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout.
LOCKOUT
Page 41
Page 42
OUTDOOR FAN MOTOR
XP16−XXX−230−01 through 05, except
XP16−060−230−05)
All units use single−phase PSC fan motors which require a r un capacitor. In all units, the condenser fan is controlled by the compressor contactor.
ELECTRICAL DATA tables in this manual show specifications for condenser fans used in XP16’s.
Access to the condenser fan motor on all units is gained by removing the four screws securing the fan assembly. See figure 24. The grill fan assembly can be removed from the cabinet as one piece.The condenser fan motor is removed from the fan guard by removing the four nuts found on top of the grill.
REMOVE SCREWS
The controller uses sensing devices to know what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in sequence, the rotor shaft turns the blower.
RED
YELLOW
BLACK
RED
BLUE
motor
control module
Figure 26. Variable Speed Fan Motor (XP16−060−230−05
only)
BLOWER MOTOR COMPONENTS
STATOR (WINDINGS)
BEARING
OUTPUT SHAFT
REMOVE SCREWS
Figure 24. Removing Fan Grille
NUTS (4)
ALIGN FAN HUB FLUSH WITH END OF SHAFT
Figure 25. Aligning Fan Hub
XP16−060−230−05 Only
The variable speed condenser fan motor (figure 26) used in all units is a three-phase, electronically controlled d.c. brushless motor (controller converts single phase a.c. to three phase D.C.), with a permanent-magnet-type rotor, manufactured by GE. Because this motor has a permanent magnet rotor it does not need brushes like conventional D.C. motors. The motors consist of a control module and motor. Internal components are shown in figure 26. The stator windings are split into three poles which are electrically connected to the controller. This arrangement allows motor windings to be turned on and off in sequence by the controller.
The controller is primarily an A. C. to D. C. converter. Converted D. C. power is used to drive the motor. The controller contains a microprocessor which monitors varying conditions inside the motor (such as motor workload).
ROTOR
Figure 27. Fan Motor Components
Internal Operation
The condenser fan motor is a variable speed motor with RPM settings at 700 (Y1) and 820 (Y2). The variation in speed is accomplished each time the controller switches a stator winding (figure 27) on and off, it is called a pulse." The length of time each pulse stays on is called the pulse width." By varying the pulse width the controller varies motor speed (called pulse-width modulation"). This allows for precise control of motor speed and allows the motor to compensate for varying load conditions as sensed by the controller. In this case, the controller monitors the static workload on the motor and varies motor rpm in order to maintain constant airflow (cfm).
Motor rpm is continually adjusted internally to maintain constant static pressure against the fan blade. The controller monitors the static work load on the motor and motor amp-draw to determine the amount of rpm adjustment. Blower rpm is adjusted internally to maintain a constant cfm. The amount of adjustment is determined by the incremental taps which are used and the amount of motor loading sensed internally. The motor constantly adjusts rpm to maintain a specified cfm.
Initial Power Up
When line voltage is applied to the motor, there will be a large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC filter capacitors inside the controller. If the disconnect switch is bounced when the disconnect is closed, the disconnect contacts may become welded. Try not to bounce the disconnect switch when applying power to the unit.
Page 42
XP16
Page 43
The DC filter capacitors inside the controller are connected electrically to the speed tap wires. The capacitors take approximately 5 minutes to discharge when the disconnect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempting to service motor.
DANGER
Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before attempting to ser­vice motor. Failure to wait may cause personal injury or death.
3. Initiate a second stage call for cool. Check for 24 volts
between the fan motor YELLOW wire and fan motor BLACK wire, then check for 24 volts between the fan motor BLUE wire and fan motor BLACK.
4. Repeat steps 1 and 2 with a HEAT call.
1st Stage (low capacity − 700 rpm)
RED
B4
RED
YELLOW
BLUE
BLACK
common
Y1
Y2
240V
240V
24V
0V
24V
Motor Start-Up
At start-up, the motor may gently rock back and forth for a moment. This is normal. During this time the electronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called soft-start"). The motor may take as long as 10-15 seconds to reach full speed. If the motor does not reach 200 rpm within 13 seconds, the motor shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a frozen bearing or blocked fan blade. The motor may attempt to start eight times. If the motor does not start after the eighth try, the controller locks out. Reset controller by momentarily turning off power to unit.
Troubleshooting
If first or second stage thermostat call for cool is present and the variable speed condenser fan motor does not energize, check voltage at the breaker box. If voltage is present perfrom the following steps and refer to figure 28.
1. Check for 240 volts between the compressor RED
wires.
2. nitiate a first stage call for cool. Check for 24 volts
between the fan motor YELLOW wire and fan motor BLACK wire.
2nd Stage (High capacity − 820 rpm)
B4
RED
RED
YELLOW
BLUE
BLACK
common
Y2
Y1
240V
240V
24V
24V
24V
Figure 28. Speed Taps for PSC Fan Motors
Replacement
Flush mounting indicates to mount it at the end of the shaft so that the bottom of the fan blade hub is flush with the end of the motor shaft. Dimension A would be 0 (flush). Torque set screw between 137 − 150 in. lbs (approximately 1/8th turn using a standard socket and wrench).
Table 6. Mounting on Shaft
XP16 UNIT "A" DIM. + 1/8"
−024, −036 3/4" (19mm)
−048, −060 Flush
−060* 1−7/8" (47.5mm)
*XP16−060−230−05 only
XP16
MOTOR
FAN BLADE HUB (BOTTOM)
MOTOR SHAFT
Figure 29. Fan Blade Mounting Position on Motor Shaft
Page 43
A
1/8 TURN
12
11
10
9
8
1
2
3
4
5
7
6
0
Page 44
TWO−STAGE MODULATION COMPRESSOR CHECKS
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning proper to correctly perform compressor modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).
Use this checklist on page to verify part-load and full-load capacity operation of two-stage modulation compressors.
TOOLS REQUIRED
D Refrigeration gauge set D Digital volt/amp meter D Electronic temperature thermometer D On-off toggle switch
PROCEDURE
NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).
1. Turn main power OFF to outdoor unit.
2. Adjust room thermostat set point 5ºF above the room
temperature.
3. Remove control access panel. Install refrigeration
gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch OFF and install switch in series with
Y2 wire from room thermostat.
5. Cycle main power ON.
6. Allow pressures and temperatures to stabilize before
taking measurements (may take up to 10 minutes).
7. Record all of the readings for the Y1 demand.
8. Close switch to energize Y2 demand. Verify power is
going to compressor solenoid.
9. Allow pressures and temperatures to stabilize before
taking measurements (may take up to 10 minutes).
10. Record all of the readings with the Y1 and Y2 demand.
11. If temperatures and pressures change in the direction
noted in Two−Stage Modulation Compressor Field Operational Checklist on page , the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary).
12. After testing is complete, return unit to original set up.
Maintenance
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Page 44
XP16
Page 45
Outdoor Unit
1. Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No
further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and clean
if necessary.
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
D Outdoor Coil  The outdoor coil may be flushed with a
water hose.
D Outdoor Coil (Sea Coast)  Moist air in ocean locations
can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and permanently
sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper
tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
XP16
Page 45
Page 46
Unit Wiring Diagrams and Sequence of Operations
Figure 30. Unit Wiring Diagram (All Sizes)  XP16XXX23001 through 04)
Page 46
XP16
Page 47
Figure 31. Unit Wiring Diagram (−024, −036 and −048 Sizes)  XP16XXX23005
XP16
Page 47
Page 48
Figure 32. Unit Wiring Diagram (−060 Size Only)  XP16XXX23005
Page 48
XP16
Page 49
Sequence of Operation XP16−024/060
Cooling
A – First Stage Low Capacity
Transformer from indoor unit supplies 24VAC power to the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling demand initiates at Y1 in the thermostat.
2 − The defrost board checks for open low or high−pressure
switches and proper coil, ambient and discharge sensor readings.
D If checks show no issues, the defrost board sends
24 volts through Y1 OUT signal to the K1 compressor contactor coil.
D XP16−060−05 only − defrost board sends 24 volts
through Y1 OUT signal to the yellow wire to the outdoor fan motor.
HARD START KIT IF USED − Compressor begins start up. Relay K31 remains closed during start up and capacitor C7 remains in the circuit. As compressor speeds up K31 is energized, de−energizing capacitor C7.
3− K1−1 N.O. closes energizing compressor B1 and
outdoor fan motor B4.
4− Solenoid L34 is NOT energized.
D The slider ring remains open limiting compressor
to low capacity.
D XP16−060−05 only − The 24 volt input on the
yellow wire to the outdoor fan motor will allow it to run on low speed.
B – Second Stage High Capacity
5− Second stage thermostat demand goes through Y2 on
the defrost board and energizes rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34 unloader solenoid.
D L34 then closes the slider ring, allowing the
compressor to operate at high capacity.
D XP16−060−05 only − The 24 volt input to the
yellow and blue wires of the outdoor fan will provide high speed operation.
Heating
A – Low Capacity
1− Internal wiring de−energizes terminal O by heating mode
selection, de−energizing the reversing valve. Heating demand initiates at Y1 in the thermostat.
2 − The defrost board checks for open low or high−pressure
switches and proper coil, ambient and discharge sensor readings.
D If checks show no issues, the defrost board sends
24 volts through Y1 OUT signal to the K1 compressor contactor coil.
D XP16−060−05 only − defrost board sends 24 volts
through Y1 OUT signal to the yellow wire to the outdoor fan motor.
HARD START KIT IF USED − Compressor begins start up. Relay K31 remains closed during start up and capacitor C7 remains in the circuit. As compressor speeds up K31 is energized, de−energizing capacitor C7.
3− K1−1 closes, energizing the compressor and outdoor fan
motor.
4− Solenoid L34 is NOT energized. The slider ring remains
open limiting compressor to low capacity.
B – High Capacity (Ambient temperature above defrost board Y2 lock−in temperature)
1− Room thermostat in heating mode. Room thermostat
outputs Y1 and Y2 (if applicable to that room thermostat) signal to the defrost board in the heat pump and to the indoor unit.
2− The defrost board checks for open low or high−pressure
switches and proper coil, ambient and discharge sensor readings.
D If checks show no issues, the defrost board sends
24 volts through Y1 OUT signal to the K1 compressor contactor coil.
D XP16−060−05 only − defrost board sends 24 volts
through Y1 OUT signal to the yellow wire to the outdoor fan motor.
3 − The defrost board sends:
D 24 volts through Y2 OUT to the L34 compressor
solenoid plug.
D XP16−060−05 only − 24 volts through Y2 OUT to
the blue wire to the outdoor fan motor.
The 2− wire compressor solenoid plug converts the 24volt AC outputs to a 24volt DC signal input to the L34 internal high capacity solenoid valve in the compressor.
4 − K1−1 closes, energizing the compressor and outdoor fan
motor through the normally closed fan relay contacts on the defrost board.
D The compressor runs high capacity.
D XP16−060−05 only − The 24 volt input to the The
compressor runs high capacity yellow and blue wires of the outdoor fan will provide high speed operation.
XP16
Page 49
Page 50
B – High Capacity (Ambient temperature below defrost board Y2 lock−in temperature)
1 − Room thermostat in heating mode. Room thermostat
outputs Y1 signal to the defrost board in the heat pump and to the indoor unit.
2 − The defrost board checks for open low or high−pressure
switches and proper coil, ambient and discharge sensor readings.
D If checks show no issues, the defrost board sends
24 volts through Y1 OUT signal to the K1 compressor contactor coil.
D XP16−060−05 only − defrost board sends 24 volts
through Y1 OUT signal to the yellow wire to the outdoor fan motor.
3 − The defrost board Y2 locks in
D 24 volts through Y2 OUT to the L34 compressor
sends:
solenoid plug.
D XP16−060−05 only − 24 volts through Y2 OUT to
the blue wire to the outdoor fan motor.
The plug converts the 24volt AC outputs to a 24volt DC signal input to the L34 internal high capacity solenoid valve in the compressor.
4 − K1−1 closes, energizing the compressor and outdoor fan
motor through the normally closed fan relay contacts on the defrost board.
D The compressor runs on high capacity.
D XP16−060−05 only − The 24 volt input to the
yellow and blue wires of the outdoor fan will provide high speed operation.
Defrost Mode
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1" (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination temperature, the defrost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default termination temperature will be 90°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by time and the coil temperature did not remain above 35°F (2°C) for 4 minutes the control will go to the 30−minute Time/Temperature mode.
Page 50
XP16
Page 51
Checklists
Two−Stage Modulation Compressors Field Operational Checklist
Expected results during Y2
Unit Readings Y1 − First-Stage
COMPRESSOR
Voltage Same Amperage Higher
OUTDOOR UNIT FAN MOTOR
Amperage Same or Higher
TEMPERATURE
Ambient Same Outdoor Coil Discharge Air Higher Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower
PRESSURES
Suction (Vapor) Lower Liquid Higher
demand (Toggle switch On)
XP16 Start−Up and Performance
Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial
Notes:
Y2 − Second-Stage
START UP CHECKS
Refrigerant Type: 1st Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts 2nd Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts Outdoor Unit Fan Full Load Amps Actual Amps: 1st Stage 2nd Stage
COOLING MODE
Suction Pressure: 1st Stage: 2nd Stage:
Liquid Pressure: 1st Stage: 2nd Stage:
Supply Air Temperature: 1st Stage: 2nd Stage:
Temperature: Ambient: Return Air:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcool­ing and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A) minus
Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A) minus
Supply Air Temperature (B)
A
A
A
B
B
B
SUBCOOLING
=
APPROACH
=
COIL TEMP DROP
=
XP16
Page 51
Loading...