Improper installation, adjustment, alteration,
service or maintenance can cause property damage,
personal injury or loss of life. Installation and
service must be performed by a qualified installer or
service agency.
CAUTION
Physical contact with metal edges and corners
while applying excessive force or rapid motion can
result in personal injury. Be aware of, and use
caution when working near these areas during
installation or while servicing this equipment.
This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook.
Coils previously charged with HCFC−22 must be
flushed.
The Lennox XP15 outdoor units use HFC−410A
refrigerant. This unit must be installed with a matching
indoor coil and line set as outlined in the Lennox
Engineering Handbook. XP15 series outdoor units are
designed for use in check expansion valve (CTXV)
systems only, and are not designed to be used with other
refrigerant flow control devices. The Lennox Engineering
Handbook lists compatible indoor CTXV kits which are
ordered separately.
IMPORTANT
Shipping and Packing List
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFCs, HCFCs AND HFCs) as
of July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for
noncompliance.
06/09505,328M
Page 1
*2P0609**P505328M*
1 − Assembled XP15 outdoor unit
1 − Bushing (for low voltage wiring)
2 − Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Page 2
Unit Dimensions −− Inches (mm)
UNIT SUPPORT
FEET
16−7/8
(429)
8−3/4
(222)
3−1/8
(79)
BASE WITH ELONGATED LEGS
39−1/2
(1003)
DISCHARGE AIR
SIDE VIEWACCESS VIEW
3−3/4 (95)
30−3/4
(781)
ELECTRICAL INLETS
VAPOR LINE
INLET
LIQUID LINE
INLET
DEFROST CONTROL
OPERATION MONITOR
26−7/8
(683)
4−5/8
(117)
VAPOR VALVE AND
DISCHARGE LINE
REVERSING VALVE
37 (940)
[−024 thru −042]
47 (1194)
[−048 and −060]
4−7/16
(113)
18−1/2
(470)
8 (203)
1 (25)
CONTACTOR
SYSTEM
GAUGE PORT
VAPOR LINE
FILTER DRIER
XP15 Parts Arrangement
35−1/2
(902)
OUTDOOR FAN
RUN CAPACITOR
COMPRESSOR
COMPRESSOR
SOUND DOME
COMPRESSOR
TERMINAL PLUG
LOW PRESSURE
SWITCH
HIGH PRESSURE
SWITCH
WARNING
This product and/or the indoor unit it is matched
with may contain fiberglass wool.
Disturbing the insulation during installation,
maintenance, or repair will expose you to fiberglass
wool dust. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California
to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
505328M 06/09
General Information
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure
caps and fasteners are appropriately tightened. Table 1
lists torque values for typical service and repair items.
Table 1. Torque Requirements
PartRecommended Torque
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
Page 2
Page 3
USING MANIFOLD GAUGE SETS
HFC−410A refrigerant manifold gauge sets must be
capable of handling higher system operating pressures.
The gauge set shall be rated for use with pressures of 0 −
800 psig on the high side, and a low side of 30 inches of
vacuum (Hg) to 250 psig, which retards when opened to
500 psig. Gauge hoses must be rated for use up to 800 psig
of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
IMPORTANT
Only use Allen wrenches of sufficient hardness
(50Rc − Rockwell Harness Scale minimum). Fully
insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9
ft−lbs for small valves, to 25 ft−lbs for large valves) to
prevent refrigerant loss during shipping and
handling. Using an Allen wrench rated at less than
50Rc risks rounding or breaking off the wrench, or
stripping the valve stem recess.
The liquid and vapor lines service valves with gauge ports
as illustrated in figures 2 and 3 are used for removing
refrigerant, flushing, leak testing, evacuating, checking
charge and charging.
Each valve is equipped with a service port which has a
factory−installed valve stem.
1/6 TURN
12
11
10
9
8
7
This illustrates how to use a wrench to tighten caps an additional
1/6 or 1/12 turn clockwise.
1
2
3
4
5
6
11
10
9
8
1/12 TURN
12
1
2
3
4
7
5
6
Figure 1. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, an
appropriately sized wrench should be used and
fitted snugly over the cap before tightening.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
SWith Torque Wrench: Finger tighten and then
tighten per table 1 on page 2.
SWithout Torque Wrench: Finger tighten and with an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension
(3/16" for liquid-line valve sizes and 5/16" for
vapor-line valve sizes) to back the stem out
counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
SWith Torque Wrench: Tighten finger tight and then
tighten per table 1 on page 2.
SWithout Torque Wrench: Finger tighten and with an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 1.
NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified torque listed.
SERVICE PORT CAP
SERVICE PORT
CORE
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS]
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS]
VALVE STEM
BACKED-SEATED
UNIT
VALVE IS FRONT−SEATED
(CLOSED)
SERVICE PORT
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
STEM CAP
VALVE IS BACK−SEATED
(OPENED)
SERVICE PORT
(VALVE STEM
SHOWN OPEN)
INSERT HEX
WRENCH HERE
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap using an appropriately sized
wrench.
Page 3
TO INDOOR
UNIT
TO OUTDOOR
UNIT
STEM CAP
Figure 2. Angle −Type Service Valve
XP15 SERIES
Page 4
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap using an appropriately sized
wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
SWith Torque Wrench: Finger tighten and then
tighten per table table 1 on page 2.
SWithout Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an adjustable wrench to open. To open valve,
rotate stem counterclockwise 90°. To close rotate
stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
SWith Torque Wrench: Finger tighten and then
tighten per table 1 on page 2.
SWithout Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 1.
NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified valve listed.
Recovering Refrigerant from Existing
HCFC−22 System
Remove existing HCFC−22 refrigerant using one of the
following methods:
METHOD 1:
If the existing outdoor unit is not equipped with shut−off
valves, or if the unit is not operational and you plan to use
the existing HCFC−22 or refrigerant to flush the system:
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean
recovery cylinder and a recovery machine. Use the
instructions provided with the recover machine on how
to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing
system. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.
4. Disconnect the liquid and vapor lines from the existing
outdoor unit.
5. Remove the existing outdoor unit.
NOTE − Use recovery machine instructions for specific
setup requirements.
Manifold GaugesRecovery Machine
TOINDOORUNIT
Open to line set when valve
is closed, to both line set
and unit when valve is open.
Service Port
Service Port
Core
Service Port
Cap
To outdoor unit
Use Adjustable Wrench To open: rotate Stem Counter-Clockwise 90°.To close: rotate Stem clockwise 90°.
Ball (Shown Closed)
Valve Stem
STEM CAP
Figure 3. Ball−Type Service Valve
Clean Recovery Cylinder
Outdoor Unit
Figure 4. Typical Refrigerant Recovery (Method 1)
METHOD 2:
If the existing outdoor unit is equipped with manual shut−off
valves and you plan to use new HCFC−22 refrigerant to
flush the system −
1. Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.
2. Pump all of the existing HCFC−22 refrigerant back into
the outdoor unit.
NOTE − It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.
505328M 06/09
Page 4
Page 5
3. When the low side system pressures reach 0 psig,
close the vapor line valve.
4. Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the
low side of the system.
5. Disconnect the liquid and vapor lines from the existing
outdoor unit.
6. Remove the existing outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to figure 5 for mandatory
installation clearance requirements.
See NOTES
Install unit away
from windows
Two 90° elbows installed in line set
will reduce line set vibration.
Figure 6. Outside Unit Placement
PLACING UNIT ON SLAB
When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground would not collect around the unit as
illustrated in figure 7. Slab may be level or have a slope
tolerance away from the building of not more than two
degrees, or 2 inches per 5 feet (51 mm per 1524 mm).
See
NOTES
See NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of
the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm)
48 in. (1219 mm) clearance required on top of unit.
A clearance of 24 in. (610 mm) must be maintained between two
units
NOTES
Control
Box
See
Figure 5. Installation Clearances
POSITIONING CONSIDERATIONS
Some localities are adopting sound ordinances based on
the unit’s sound level registered from the adjacent
property, not from the installation property. Install the unit
as far as possible from the property line. When possible,
do not install the unit directly outside a window. Glass has a
very high level of sound transmission. For proper
placement of unit in relation to a window see the provided
illustration in figure 6.
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
Building
Structure
Mounting
Slab
GROUND LEVEL
Figure 7. Ground Level Slab Mounting
INSTALLING UNIT ON ROOF
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build−up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit. Consult local codes for
rooftop applications.
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed as illustrated in
figure 8. Size barrier at least the same height and width as
outdoor unit. Mount barrier 24 inches (610 mm) from the
sides of the unit in the direction of prevailing winds.
Page 5
XP15 SERIES
Page 6
PREVAILING
WINTER WINDS
WIND BARRIER
INLET AIR
INLET AIR
INLET AIR
24"
(610 mm)
Figure 8. Rooftop Application and Wind Barrier
NOTE − If necessary for stability, anchor unit to slab as
described in Stabilizing Unit on Uneven Surfaces.
ELEVATING THE UNIT
These units are outfitted with elongated−shaped feet as
illustrated in figure 9.
BASE
With unit positioned at installation site, remove two side
louvered panels to expose the unit base pan.Install the
brackets as illustrated in figure 10 using conventional
practices; replace the panels after installation is complete.
IMPORTANT
Using field−provided stabilizer brackets:
Always use stabilizers when unit is raised above the
factory height. (Elevated units could become
unstable in gusty wind conditions).
Stabilizers may be used on factory height units
when mounted on an unstable or uneven surface.
Slab Side Mounting
#10 1/2" LONG
SELF−DRILLING SHEET
METAL SCREWS
STABILIZING BRACKET
(18 GAUGE METAL − 2"
WIDTH; HEIGHT AS
REQ’D)
#10 1−1/4" LONG HEX
HD SCREW AND
FLATWASHER
COIL
BASE PAN
CORNER POST
LEG DETAIL
2" (50.8MM)
SCH 40
FEMALE
THREADED
ADAPTER
Figure 9. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
If additional elevation is necessary, raise the unit by
extending the height of the unit support feet. This may be
done with 2" SCH 40 female threaded adapter. The
specified coupling will fit snuggly into the recess portion of
the feet. Use additional 2" SCH 40 male threaded adapters
which can be threaded into the female threaded adapters
to make additional adjustments to the level of the unit.
NOTE − Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may
require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.
PLASTIC ANCHOR − USE IF CONCRETE
(HOLE DRILL 1/4"); NOT IF PLASTIC SLAB
(HOLE DRILL 1/8").
Deck Top
Mounting
STABILIZING
BRACKET (18
GAUGE METAL − 2"
WIDTH; HEIGHT
AS REQ’D); BEND
TO FORM RIGHT
ANGLE
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY,
TWO BRACKETS PER SIDE, 2" FROM EACH CORNER.
Figure 10. Installing Stabilizer Brackets
MINIMUM 1
PER SIDE
FOR EXTRA
STABILITY
Removing Panels
CAUTION
To prevent personal injury, or damage to panels,
unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow
all removed panels out of the way, so that the panels
will not cause injury to personnel, nor cause
damage to objects or structures nearby, nor will the
panels be subjected to damage (e.g., being bent or
scratched).
While handling or stowing the panels, consider any
weather conditions, especially windy conditions,
that may cause panels to be blown around and
battered.
505328M 06/09
Page 6
Page 7
REMOVE 4 SCREWS TO REMOVE PANEL FOR
ACCESSING COMPRESSOR AND CONTROLS.
INSTALL BY POSITIONING PANEL WITH HOLES
ALIGNED; INSTALL SCREWS AND TIGHTEN.
Figure 11. Access Panel
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT
AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO
EXTREME
PREFERRED ANGLE
FOR INSTALLATION
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail D
IMPORTANT! DO NOT ALLOW
PANELS TO HANG ON UNIT BY
TOP TAB. TAB IS FOR ALIGNMENT
AND NOT DESIGNED TO SUPPORT
WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY
ROTATED TO ALLOW TOP TAB TO
EXIT (OR ENTER) TOP SLOT FOR
REMOVING (OR INSTALLING)
PANEL.
SCREW
HOLES
LIP
Detail A
Detail B
Detail C
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE PANEL
Figure 12. Removing/Installing Louvered Panels
(Detail A, B and C)
WARNING
Unit must be grounded in accordance
with national and local codes.
Electric Shock Hazard. Can cause
injury or death.
Line voltage is present at all
components when unit is not in
operation on units with single-pole
contactors. Disconnect all remote
electric power supplies before
opening access panel. Unit may have
multiple power supplies.
Figure 13. Removing/Installing Louvered Panels
(Detail D)
ACCESS PANEL
Removal and reinstallation of the access panel is
illustrated in figure 11.
LOUVERED PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly.
2. Hold the panel firmly throughout this procedure.
Rotate bottom corner of panel away from hinged
corner post until lower three tabs clear the slots as
illustrated in figure 12, detail B.
3. Move panel down until lip of upper tab clears the top
slot in corner post as illustrated in figure 12, detail A.
Position and Install PanelPosition the panel almost
parallel with the unit as illustrated in figure 13, detail D with
the screw side as close to the unit as possible. Then, in a
continuous motion:
SSlightly rotate and guide the lip of top tab inward as
illustrated in figure 12, details A and C; then upward
into the top slot of the hinge corner post.
SRotate panel to vertical to fully engage all tabs.
SHolding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
When panel is correctly positioned and aligned, insert the
screws and tighten.
Electrical Connections
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
ELECTRICAL AND CONTROL CONNECTIONS
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
NOTE − Connect conduit to the unit using a proper conduit
fitting. Units are approved for use only with copper
conductors. A complete unit wiring diagram is located on
the back side of the unit’s access panel.
NOTE − For proper voltages, select thermostat wire gauge
per the following chart:
Page 7
XP15 SERIES
Page 8
Table 2. Wire Run Length
Wire Run LengthAWG #Insulation Type
less than 100’ (30m)18
more than 100’ (30m)16
color−coded, temperature
rating 35ºC minimum
1. Install room thermostat (ordered separately) on an
inside wall approximately in the center of the area and
5 feet (1.5 m) from the floor. Do not install on an outside
wall or where sunlight, drafts or vibrations affect it.
2. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit as illustrated in
figure 14.
3. Install line voltage power supply to unit from a properly
sized disconnect switch as illustrated in figure 15.
4. Ground unit from ground lug as illustrated in figure 15
to unit disconnect switch, or to an earth ground.
Figure 14. Typical Low−Voltage Field Wiring
READ WARNING AND NOTE
GROUND LUG
GROUND
208−230/60/1
L1
L2
K1−1 COMPRESSOR CONTACTOR
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
GROUND LUG
CONTACTOR
CONTROL BOX
DEFROST CONTROL
BOARD (DCB)
LENNOX SYSTEM OPERATION
MONITOR (LSOM)
CAPACITOR
Figure 15. Typical High−Voltage Field Wiring (Unit Panel)
505328M 06/09
Page 8
Page 9
New or Replacement Line Set
This section provides information on installation or
replacement of existing line sets. If line sets are not being
installed or replace, then proceed to Brazing Connections
on page 11.
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat,
non−flare) series line sets, or use field−fabricated
refrigerant lines as listed in table 3.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
IMPORTANT
Matching XP15 with a New Indoor Coil and Line
SetIf installing a new indoor coil and reusing the
existing line set that included a RFCI liquid line
(small bore liquid line used as a metering device)
then you must change to a standard size liquid line.
Line sets for heat pump applications can not be installed
underground. For more information see the LennoxRefrigerant Piping Design and Fabrication Guidelines, or
contact Lennox Technical Support Product Applications
for assistance.
Table 3. Refrigerant Line Sets
Valve SizesRecommended Line Set
Model
−024
−030
−036
−042
−048
−060
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8 in
(22 mm)
1−1/8 in.
(29 mm)
Liquid
Line
3/8 in
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8in
(22 mm)
1−1/8 in.
(29 mm)
L15
Line Sets
L15−41
15 − 50 ft.
(5 − 15 m)
L15−65
15 − 50 ft.
(5 − 15m)
Field
Fabricated
INSTALLING LINE SET
Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set
isolation:
SInstallation of line sets on horizontal runs is
illustrated in figure 16.
SInstallation of line sets on vertical runs is illustrated
in figure 17 on page 10 .
SInstallation of a transition from horizontal to
vertical is illustrated in figure 18 on page 10.
TO HANG LINE SET FROM JOIST OR RAFTER,
USE EITHER METAL STRAPPING MATERIAL OR
ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND VAPOR LINE
ONLY)
8 FEET
WIRE TIE (AROUND
VAPOR LINE ONLY
When installing refrigerant lines longer than 50 feet, see
the Lennox Refrigerant Piping Design and FabricationGuidelines, or contact Lennox Technical Support Product
Applications for assistance. To obtain the correct
information from Lennox, be sure to communicate the
following points:
SModel (XP15) and size (e.g. −060) of unit.
SLine set diameters for the unit being installed (from
table 3)
SNumber of elbows and if there is a rise or drop of the
piping.
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
TAPE OR
FLOOR JOIST OR
ROOF RAFTER
WIRE TIE
METAL
SLEEVE
8 FEET
STRAP THE VAPOR LINE TO THE
JOIST OR RAFTER AT 8 FEET
INTERVALS THEN STRAP THE
LIQUID LINE TO THE VAPOR LINE.
Figure 16. Refrigerant Line Sets: Installing
Horizontal Runs
Page 9
XP15 SERIES
Page 10
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
IMPORTANT -
REFRIGERANT LINES MUST
NOT CONTACT WALL.
VAPOR LINE
LIQUID LINE
ANCHORED HEAVY
NYLON WIRE TIE
NOTE − SIMILAR
INSTALLATION
PRACTICES SHOULD BE
USED IF LINE SET IS TO
BE INSTALLED ON
EXTERIOR OF OUTSIDE
WALL.
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
LIQUID LINE
CAULK
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
SLEEVE
IMPORTANT!
REFRIGERANT LINES
MUST NOT CONTACT
STRUCTURE.
WALL
STUD
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL
STUD
METAL SLEEVE
STRAP LIQUID LINE
TO VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED
IN ARMAFLEX
VAPOR LINE WRAPPED
IN ARMAFLEX
STRAP LIQUID LINE
TO VAPOR LINE
LIQUID
LINE
Figure 17. Refrigerant Line Sets: Installing Vertical
Runs (New Construction Shown)
1
CUT AND DEBUR
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS after they
have coolED.
INDOOR UNIT
6
BRAZE LINE SET
2
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT
POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
Figure 19. Brazing Connections
5
Figure 18. Refrigerant Line Sets: Transition from
Vertical to Horizontal
3
ATTACH
GAUGES
SERVICE
VALVE
SERVICE
VALVE
outdoor
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
505328M 06/09
Page 10
Page 11
ISOLATION GROMMETS
Locate the provided isolation grommets. Slide grommets
onto vapor and liquid lines. Insert grommets into mullion to
isolate refrigerant lines from sheet metal edges.
Brazing Line Set Connections
Use the following procedure to braze the line set to the new
outdoor unit. Figure 19 is provided as a general guide for
preparing to braze the line sets to the outdoor unit.
Before brazing, remove the access panel as illustrated in
figure 11; then remove the narrow piping panel to prevent
burning off the paint as illustrated in figure 20.
REMOVE TWO SCREWS
AND REMOVE PANEL
BEFORE BRAZING.
PIPING
LINE SET
CONNECTION
POINTS.
Figure 20. Piping Panel Removal
PANEL
WARNING
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept
closed as much as possible. DO NOT remove line
set caps or service valve stub caps until you are
ready to make connections.
underneath the valve body to protect the base paint.
Also, shield the light maroon R−410A sticker.
5. Flow regulated nitrogen (at 1 to 2 psig) through the
refrigeration gauge set into the valve stem port
connection on the liquid line service valve and out of
the valve stem port connection on the vapor service
valve. The CTXV metering device at the indoor unit
coil will allow low pressure nitrogen to flow through the
system.)
Note: Use silver alloy brazing rods with five or six percent
minimum silver alloy for copper−to−copper brazing or 45
percent silver alloy for copper−to−brass or copper−to−steel
brazing.
6. Braze the line set to the liquid line service valve. Turn
off nitrogen flow. Repeat procedure starting at
paragraph 4 for brazing the vapor line set to service
valve.
After brazing the vapor line set to the service valve,
disconnect gauge from service port, remove wrapping and
replace service port cores.
Removing Existing Refrigerant Metering
Device
Remove the existing HCFC−22 refrigerant flow control
orifice or thermal expansion valve from the indoor coil.
Existing devices are not approved for use with HFC−410A
refrigerant and may prevent proper flushing. Use a
field−provided fitting to reconnect lines. See figure 23 on
page 13 for disassembly and typical removal instructions.
Testing for Leaks
After the line set has been connected to both the indoor
and outdoor units, check the line set connections at both
the indoor and outdoor units unit for leaks. Use the
following procedure to test for leaks:
WARNING
Danger of fire. Bleeding the
refrigerant charge from only the high
side may result in the low side shell
and suction tubing being
pressurized. Application of a brazing
torch while pressurized may result in
ignition of the refrigerant and oil
mixture − check the high and low
pressures before unbrazing.
1. Cut ends of the refrigerant lines square (free from
nicks or dents). Debur the ends. The pipe must remain
round, do not pinch end of the line.
2. Remove service cap and core from both the vapor and
liquid line service ports.
3. Connect gauge low pressure side to liquid line service
valve.
4. To protect components during brazing, wrap a wet
cloth around the liquid line service valve body and
copper tube stub and use another wet cloth
IMPORTANT
Leak detector must be capable of sensing HFC
refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled.
Refrigerant must be used and recovered
responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
When using a high pressure gas such
as dry nitrogen to pressurize a
refrigeration or air conditioning
system, use a regulator that can
control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
Page 11
XP15 SERIES
Page 12
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire and/
or an explosion, that could result in
personal injury or death.
OUTDOOR UNIT
SERVICE VALVE
REMOVE SERVICE
PORT CAP
REMOVE PORT CORE
Figure 21. Typical Service Valve Port Core Removal
Flushing Existing System
IMPORTANT
1. Connect an HFC−410A manifold gauge set high
pressure hose to the vapor valve service port.
(Normally, the high pressure hose is connected to the
liquid line port; however, connecting it to the vapor port
better protects the manifold gauge set from high
pressure damage.)
2. With both manifold valves closed, connect the cylinder
of HFC−410A refrigerant to the center port of the
manifold gauge set. Open the valve on the HFC−410A
cylinder (vapor only).
3. Open the high pressure side of the manifold to allow
HFC−410A into the line set and indoor unit.
4. Weigh in a trace amount of HFC−410A. [A trace
amount is a maximum of two ounces (57 g) refrigerant
or three pounds (31 kPa) pressure].
5. Close the valve on the HFC−410A cylinder and the
valve on the high pressure side of the manifold gauge
set.
6. Disconnect the HFC−410A cylinder.
7. Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set.
8. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
9. Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
10. After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
11. After leak testing disconnect gauges from service
ports.
Removing Service Valve Port Core
Remove both of the outdoor unit’s service port cores (liquid
and vapor) as illustrated in figure 21.
The line set and indoor unit coil must be flushed
with at least the same amount of clean refrigerant
that previously charged the system. Check the
charge in the flushing cylinder before proceeding.
IMPORTANT
If this unit is being matched with an approved line
set or indoor unit coil which was previously
charged with mineral oil, or if it is being matched
with a coil which was manufactured before
January of 1999, the coil and line set must be
flushed prior to installation. Take care to empty all
existing traps. Polyol ester (POE) oils are used in
Lennox units charged with HFC−410A refrigerant.
Residual mineral oil can act as an insulator,
preventing proper heat transfer. It can also clog
the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
CAUTION
This procedure should not be performed on
systems which contain contaminants (Example:
compressor burn out).
IMPORTANT
The Environmental Protection Agency (EPA)
prohibits the intentional venting of HFC refrigerants
during maintenance, service, repair and disposal of
appliance. Approved methods of recovery,
recycling or reclaiming must be followed.
If new lines are used then proceed to Installing New
Refrigerant Metering Device. Otherwise proceed with the
following procedure.
505328M 06/09
Page 12
Page 13
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor
unit coil:
STwo clean HCFC−22 recovery bottles,
SOilless recovery machine with pump-down feature,
STwo gauge sets (one for HCFC−22; one for
HFC−410A).
INVERTED HCFC−22 CYLINDER
CONTAINS CLEAN HCFC−22 TO
BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
NOTE − The inverted HCFC−22 cylinder must contain at least the same
amount of refrigerant as was recovered from the existing system.
Figure 22. Typical Flushing Connection
PROCEDURE
1. Verify that the existing HCFC−22 refrigerant flow
control device has been removed before continuing
with flushing procedures. Existing devices are not
approved for use with HFC−410A refrigerant and may
prevent proper flushing.
2. Connect an HCFC−22 cylinder with clean refrigerant to
the vapor service valve. Connect the HCFC−22 gauge
set to the liquid line valve. Connect a recovery
machine with an empty recovery tank to the gauge set
as illustrated in figure 22.
3. Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the
existing system line set and indoor unit coil.
4. Invert the cylinder of clean HCFC−22 and open its
valve to allow liquid refrigerant to flow into the system
through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the
indoor unit coil before it enters the recovery machine.
5. After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that
all of the HCFC−22 vapor is recovered. Allow the
recovery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and indoor
unit coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. Each time the system is
flushed, you must allow the recovery machine to pull a
vacuum on the system at the end of the procedure.
MANIFOLD
LOW
PRESSURE
TANK
RETURN
INLET
DISCHARGE
GAUGE
PRESSURE
HIGH
CLOSED
Page 13
6. Close the valve on the inverted HCFC−22 drum and
the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.
Installing New Refrigerant Metering
Device
XP15 units are used in check thermal expansion valve
(CTXV) systems only. See the indoor unit coil installation
instructions and the Lennox Engineering Handbook for
approved CTXV match−ups and application information.
Table 3 on page 9 lists liquid and vapor line sizes and
corresponding line sets.
(Uncased Coil Shown)
TWO PIECE PATCH
PLATE(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
ACCESS FITTING
(NO VALVE CORE)
On smaller vapor lines, bulb may be
mounted on top or side-mounted (prefer-
ORIFICE
HOUSING
O−RING
EQUALIZER
LINE
SENSING BULB
(INSULATION REQUIRED)
ably at 3 o’clock position).
On 5/8" and larger lines, mount bulb
approximately at the 4 or 8 o’clock positions; never mount on bottom of line.
12
9
VAPORLine
3 o’clock
Bulb
NOTE − If necessary, remove HCFC−22 flow control device (fixed
orifice/check expansion valve) from existing line set before installing HFC−410A approved expansion valve and o−ring.
Figure 23. Typical Metering Device Installation
The thermostatic expansion valve or check / thermostatic
expansion valve, can be installed internal or external to the
indoor coil. In applications where an uncased coil is being
installed in a field provided plenum, install the CTXV and
provide an access for field servicing of the CTXV. Refer to
Figure 23 for reference during installation of CTXV.
1. On fully cased coils, remove the coil access and
plumbing panels.
ORIFICE
OR
EXPANSION VALVE
(SEE NOTE)
REMOVE AND DISCARD
SEAL ASSEMBLY (IF
APPLICABLE)
VAPOR
O−RING
STRAINER
LINE
SENSING
LINE
LIQUID
LINE
XP15 SERIES
Page 14
2. Remove any shipping clamps holding the liquid line
and distributor assembly.
3. Using two wrenches, disconnect liquid line from
distributor. Take care not to twist or damage distributor
tubes during this process.
4. Remove and discard RFC bullet and Teflon washer.
5. Remove and discard cap from the equalizer line port
on the vapor line. Check for valve core in port fitting
and if installed, remove from port.
6. Install one of the provided Teflon washers around the
stubbed end of the CTXV.
7. Attach the stubbed end of the kit valve to the distributor
assembly.
8. Place the remaining Teflon washer around the other
end of the CTXV.
9. Attach the liquid line to the CTXV.
10. Attach the sensing bulb of the CTXV in the proper
orientation to the vapor line using the clamp an screws
provided with the CTXV.
OUTDOOR UNIT
LIQUID AND VAPOR
SERVICE VALVES
INSTALL SERVICE
PORT CORES
Figure 24. Typical Service Valve Port Core
Installation
DO NOT INSTALL
CAPS AT THIS TIME
Evacuating the System
WARNING
Danger of Equipment Damage. Avoid deep
vacuum operation. Do not use compressors to
evacuate a system. Extremely low vacuums can
cause internal arcing and compressor failure.
Damage caused by deep vacuum operation will
void warranty.
IMPORTANT
11. Connect the equalizer line from the CTXV to the
equalizer vapor port on the vapor line.
12. To prevent against any possibility of water damage,
properly insulate all parts of the CTXV assemble that
may sweat due to temperature differences between
the valve and its surrounding ambient temperatures.
13. The expansion/check valve can be installed internally
in coil blowers, or external or internal to indoor coil only
applications.
Expansion valves equipped with Chatleff type fittings are
available from Lennox. Refer to the Engineering
Handbook for CTXV kits for use with specific match−ups.
Table 4. Indoor CTXV Kits
Model
XP15−024 and −03649L24
XP15−048 and −06091M02
Kit Number
IMPORTANT
Failure to remove a fixed orifice when installing an
expansion valve to the indoor coil will result in
improper operation and damage to the system.
If the indoor unit being installed came with a fixed orifice
type metering device, remove that orifice and install the
CTXV as illustrated in figure 23.
Installing Service Valve Port Core
Re−install both of the outdoor unit’s service port cores
(liquid and vapor) as illustrated in figure 24.
505328M 06/09
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are
defined as any gas that will not condense under
temperatures and pressures present during operation of
an air conditioning system. Non−condensables and water
vapor combine with refrigerant to produce substances that
corrode copper piping and compressor parts.
1. Connect manifold gauge set to the service valve ports
as follows:
Slow pressure gauge to vapor line service valve
Shigh pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to
the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum
pump.
5. Evacuate the line set and indoor unit to an absolutepressure of 23,000 microns (29.01 inches of
mercury).
NOTE − During the early stages of evacuation, it is
desirable to close the manifold gauge valve at least once to
determine if there is a rapid rise in sure indicates a
relatively large leak. If this occurs, repeat the leak testingprocedure.
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system, above
the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacuum
pressure.
6. When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
Page 14
Page 15
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a dry nitrogen
cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the
manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the dry nitrogen from
the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9. When the absolute pressure requirement above has
been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HFC−410A refrigerant. Open the manifold gauge valve
1 to 2 psig in order to release the vacuum in the line set
and indoor unit.
10. Close manifold gauge valves and shut off the
HFC−410A cylinder and remove the manifold gauge
set.
SERVICING UNITS DELIVERED VOID OF CHARGE
If the system is void of refrigerant, clean the system using
the procedure described below.
1. Use nitrogen to pressurize the system and check for
leaks. Repair all leaks.
2. Evacuate the system to remove as much of the
moisture as possible.
3. Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again. Then, weigh the
appropriate amount of HFC−410A refrigerant as listed
on unit nameplate into the system.
5. Monitor the system to determine the amount of
moisture remaining in the oil. It may be necessary to
replace the filter drier several times to achieve the
required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Start−Up Procedures
IMPORTANT
4. Replace the stem caps and tighten as specified in
Operating Service Valves on page 3.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on
power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
8. Check system for sufficient refrigerant by using the
procedures listed under Testing and ChargingSystem.
TESTING AND CHARGING SYSTEM
This system uses HFC−410A refrigerant which operates at
much higher pressures than HCFC−22. The pre−installed
liquid line filter drier is approved for use with HFC−410A
only. Do not replace liquid line filter drier with components
designed for use with HCFC−22.
NOTE − This unit is NOT approved for use with coils which
use capillary tubes as a refrigerant metering device.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service
ports as illustrated in figure 25.
Slow pressure gauge to vapor service port
Shigh pressure gauge to liquid service port
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (DT) process as illustrated
in figure 26 on page 16.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:
Stemperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
Svoltage supplied to the unit,
Samperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula
to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to
prevent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory− and field−installed wiring for loose
connections.
3. After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.
Page 15
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the
unit. To calculate the total refrigerant charge:
Amount
specified
on
nameplate
Adjust amount for
variation in
line set length
(table in figure 27)
Additional charge
specified per
indoor unit
match−up
(tables 6 through 11)
Total
charge
++=
XP15 SERIES
Page 16
CHECK
EXPANSION VALVE
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HFC−410
A DRUM
HIGH
LIQUID
LINE
VALV E
BI−FLOW
FILTER /
DRIER
LIQUID
SERVICE
PORT
OUTDOOR
COIL
MUFFLER
COMPRESSOR
DISTRIBUTOR
OUTDOOR UNIT
REVERSING VALVE
VAPOR
SERVICE
PORT
VAPOR LINE
VALV E
NOTE − ARROWS INDICATE
DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant
lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
Figure 26. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
DT
air flowair flow
INDOOR
COIL
1. Determine the desired DTMeasure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between
B
A
72º
the measured T
+
3º, no adjustment is needed. See examples: Assume DT =
15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
B
64º
WET
BULB
DRY
BULB
53º 19–15 =4Increase the airflow
58º14–15=−1 (within +3º range) no change
62º10–15=−5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within
3º.
+
CHECK EXPANSION VALVE
Drop
and the desired DT (T
Drop
–DT=ºF ACTION
Drop
) = A minus C.
Drop
INDOOR
COIL
–DT) is within
WEIGH IN
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this
amount. If line length is less than 15 ft. (4.6 m), subtract this
amount.
505328M 06/09
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 27. Using Weigh In Method
1. Check Liquid and suction line pressures
2. Compare unit pressures with table 5,
Normal Operating Pressures.
3. Conduct leak check; evacuate as
previously outlined.
4. Weigh in the unit nameplate charge plus
any charge required for line set differences
over feet.
This nameplate is for illustration purposes
only. Go to actual nameplate on outdoor
unit for charge information.
Page 16
Page 17
SUBCOOLING
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
1 Check the airflow as illustrated in figure 26 to be sure the indoor airflow is as
required. (Make any air flow adjustments before continuing with the following
procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode
or heating mode to check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal
Operating Pressures table 5, (The reference table is a general guide. Expect
minor pressure variations. Significant differences may mean improper charge or
other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and
above. Target subcooling values in table below are based on 70 to 80°F (21−27°C)
indoor return air temperature; if necessary, operate heating to reach that
temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC).
When pressures have stabilized, continue with step 6.
SATº
LIQº –
SCº=
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C).
Target subcooling values in table below are based on 65−75°F (18−24°C) indoor
return air temperature; if necessary, operate cooling to reach that temperature range;
then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have
stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the
temperature/ pressure chart listed in table 12 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with table below, being sure to note any additional charge for
line set and/or match−up.
10 If subcooling value is greater than shown in tables 6 through 11 for the applicable unit,
remove refrigerant; if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
Figure 28. Using Subcooling Method
Table 5. Normal Operating Pressure − Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Minor variations in these pressures may be expected due to differences in installations. Significant differences
could mean that the system is not properly charged or that a problem exists with some component in the system.
XP15−024XP15−030XP15−036XP15−042XP15−048XP15−060
5F (5C)**
HEATING OPERATION
20 (−7.0)315653086228459293583126234961
30 (−1.0)340813177629671312713327637574
40 (4.4)364973398931387321823539238488
50 (10)39411535910732610633710337411 0406107
COOLING OPERATION
65 (18.3)237141250141260139265141242139255136
75 (23.9)274143292143298141309144279140297138
85 (29.4)319145336145344143360147322142343140
95 (35.0)364147385147393145408149370144392142
105 (40.6)415149438148446148462151423147447145
115 (49.0)469152497151506150522154479149510148
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outdoor coil.
Disconnect gauge set and re−install all service valve caps.
OUTDOOR UNIT
SERVICE VALVE
INSTALL CAPS
Figure 29. Installing Service Valve Port Caps
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of the
outdoor unit is required, or when auxiliary electric heat is
staged by outdoor thermostats. When the room thermostat is
placed in the emergency heat position, the outdoor unit
control circuit is isolated from power and field-provided relays
bypass the outdoor thermostats. An amber indicating light
simultaneously comes on to remind the homeowner that the
unit is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage if power has been off for over an hour and the
outdoor temperature is below 50°F (10°C). The system
should be left in the emergency heat mode at least six
hours to allow the crankcase heater sufficient time to
prevent compressor slugging.
HIGH-PRESSURE SWITCH
XP15 units are equipped with a high-pressure switch that
is located in the liquid line to the compressor. The normally
closed SPST auto−reset switch opens at 590 psi.
LOW-PRESSURE SWITCH
XP15 units are equipped with a low-pressure switch that is
located in the vapor line to the compressor. The normally
closed SPST auto−reset switch opens at 25 psi and closes
at 40 psi.
SINGLE-SPEED CONDENSER FAN MOTOR
The XP15 is equipped with a single-speed condenser fan
motor. The compressor contactor and defrost control
board (DCB) controls the operation of the motor.
FILTER DRIER
The unit is equipped with a large−capacity biflow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of like design and capacity.
Replacement filter driers must be suitable for use with
HFC−410A refrigerant.
Lennox System Operation Monitor
(LSOM)
The LSOM detects the most common fault conditions in
the system. When an abnormal condition is detected, the
LSOM communicates the specific condition through its
ALERT and TRIP lights. The LSOM is capable of detecting
both mechanical and electrical system problems. See
figure 30 for LSOM LED locations.
System Operations
The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch
is in the ON position, the indoor blower operates
continuously.
THERMOSTAT OPERATION
Some indoor thermostats incorporate isolating contacts
and an emergency heat function (which includes an amber
indicating light). The thermostat is not included with the
unit and must be purchased separately.
POWER LED
TRIP LED
ALERT LED
Figure 30. LSOM
Page 19
XP15 SERIES
Page 20
Table 13. LSOM LED Troubleshooting Codes
Status LED
Condition
Green Power LED ONLSOM has power24VAC control power is present at the LSOM terminal.
Green Power LED OFFLSOM not powering up
Red Trip LED ON
Red Trip and Yellow
Alert LEDs Flashing
Yellow Alert Flash
Code 1*
Yellow Alert Flash
Code 2*
Yellow Alert Flash
Code 3*
Yellow Alert Flash
Code 4*
Yellow Alert Flash
Code 5*
Yellow Alert Flash
Code 6*
Yellow Alert Flash
Code 7*
Yellow Alert Flash
Code 8*
Yellow Alert Flash
Code 9*
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash code by removing 24VAC power
from LSOM; last code will display for 1 minute after LSOM is powered on.
Note: If the unit is equipped with a two−stagged compressor, upon Y2 signal detection and after five seconds, the LSOM will send 24 VAC to the solenoid.
Once the solenoid is fully energized, the LSOM reduces voltage to between 4 to 18 VDC . Every 15 minutes the solenoid voltage will be increase to 24 volts
for a few seconds to ensure solenoid valve is engaged until Y2 signal is no longer present.
Status LED
Description
Status LED Troubleshooting Information
Determine/verify that both R and C LSOM terminals are connected and voltage is present
at both terminals.
1
Verify Y terminal is connected to 24VAC at contactor coil.
System and compressor
check out OK
2
Verify voltage at contactor coil falls below 0.5VAC when off.
3
Verify 24VAC is present across Y and C when thermostat demand signal is present; if not
present, R and C wires are reversed.
1
Thermostat demand signal
Y1 is present, but
compressor not running
NOTE − During 5-minute
delay in LSOM the red trip
LED will be on.
Compressor protector is open.
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low pressure switch open if present in the system.
6
Compressor contactor has failed to close.
Simultaneous flashing.Indicates that the control circuit voltage is too low for operation.
1
Low refrigerant charge.
2
Evaporator blower is not running.
3
Long Run Time − Compressor is running extremely
long run cycles
System Pressure Trip −
Discharge or vapor pressure
out of limits or compressor
overloaded
Short Cycling − Compressor is running only briefly
Locked Rotor
Open Circuit
Open Start Circuit − Cur-
rent only in run circuit
Open Run Circuit − Current
only in start circuit
Welded Contactor −
Compressor always runs
Low Voltage − Control circuit <17VAC
Evaporator coil is frozen.
4
Faulty metering device.
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning
1
Check high head pressure or discharge line sensor.
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
4
Return air duct has substantial leakage.
5
If low pressure switch is present, see Flash Code 1 information.
1
Thermostat demand signal is intermittent.
2
Time delay relay or DCB is defective.
3
If high pressure switch is present, see Flash Code 2 information.
4
If low pressure switch is present, see Flash Code 2 information.
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient temperature.
7
Compressor windings are damaged.
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
3
Compressor start winding is damaged.
1
Open circuit in compressor start wiring or connections.
2
Compressor start winding is damaged.
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to LSOM.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at disconnect is low).
.
.
.
505328M 06/09
Page 20
Page 21
LSOMLED Functions
Defrost System
IMPORTANT
This monitor does not provide safety protection.
The monitor is a monitoring device only and cannot
control or shut down other devices.
See table 13 on page 20 for the complete explanation of
troubleshooting codes.
LED
Color
GreenPower
YellowAlert
RedTrip
FunctionDescription
Indicates voltage within the range of
19−28VAC is present at LSOM connection.
Communicates an abnormal system
condition through a unique flash code.
The alert LED flashes a number of
times consecutively; then pauses;
then repeats the process. This
consecutive flashing correlates to a
particular abnormal condition.
Indicates there is a demand signal
from the thermostat but no current to
the compressor is detected by the
LSOM.
DEFROST CONTROL BOARD (DCB) FUNCTION
The DCB measures differential temperatures to detect
when the system is performing poorly because of ice
build−up on the outdoor coil. The DCB self−calibrates when
the defrost system starts and after each system defrost
cycle. The DCB components are illustrated in figure 31.
Note − Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR
PLUG IN (COIL
AND AMBIENT
SENSORS)
DELAY
PINS
REVERSING
VALV E
PRESSURE
SWITCH
CIRCUIT
CONNECTIONS
LOW
AMBIENT
THERMOSTAT
PINS
DIAGNOSTIC
LEDS
24V TERMINAL
STRIP
CONNECTIONS
Resetting Alert Codes
Alert codes can be reset manually or automatically:
Cycle the 24VAC power to LSOM off and on. Af-
Manual
ter power up, existing code will display for one
minute and then clear.
After an alert is detected, the LSOM continues
Automatic
to monitor the compressor and system. When/if
conditions return to normal, the alert code is
turned off automatically.
LSOML Terminal Connection
The L connection is used to communicate alert codes to
the room thermostat. On selected Lennox SignatureStatt
thermostats, a blinking check LED will display on the room
thermostat and on select White-Rodgers room
thermostats, an icon on the display will flash. Either will
flash at the same rate as the LSOM yellow alert LED.
NOTE − ROOM THERMOSTATS WITH SERVICE OR
CHECK LIGHT FEATUREThe room thermostat may
blink the Check or Service LED or it may come on solid.
Confirm fault by observing and interpreting the code from
the LSOM yellow alert LED at the unit.
Figure 31. Defrost Control Board (DCB)
The DCB monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a
defrost cycle is required. The coil temperature probe is
designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE − The DCB accurately measures the performance of
the system as frost accumulates on the outdoor coil. This
typically will translate into longer running time between
defrost cycles as more frost accumulates on the outdoor
coil before the DCB initiates defrost cycles.
Pressure Switch Connections
The unit’s automatic reset pressure switches (LO PS − S87
and HI PS − S4) are factory−wired into the DCB on the
LO−PS and HI−PS terminals, respectively.
Pressure Switch Event Settings
The following are the auto reset event values for low and
high pressures thresholds:
SHigh Pressure (auto reset) − trip at 590 psig, reset to
418 psig.
SLow Pressure (auto reset) − trip at 25 psig, reset to 55
psig.
Page 21
XP15 SERIES
Page 22
Table 14. Defrost Control Board (DCB) Inputs, Outputs and Configurable Settings
DCB
Location
P1TESTTest ModeSee Test Mode on page 22 for further details.
P150, 70, 90, 100
P2
P355, 50, 45, 40Low Ambient Thermostat Pins
P4
P5DELAYDelay Mode
P6TST, PS DF, C, R, O, Y1, Y2Factory Test ConnectorsNo field use.
DS1RED LED
DS2GREEN LED
FANTWO CONNECTORSCondenser Fan OperationThese two connections provide power for the condenser fan.
O OUTO OUT24 VAC output24 VAC output connection for reversing valve.
DCB Label or
Description
W1
C24VAC Common24VAC common
LThermostat Service LightThermostat service light connection.
R24VAC24VAC
Y2Thermostat InputControls the second stage operation of the unit.
OThermostat InputReversing valve solenoid.
Y1Thermostat InputControls the operation of the unit.
DIS−YELCoil Sensor
AMB−BLACKAmbient Sensor
COIL−BROWNDischarge SensorNo discharge sensor is used; replaced by 10K resistor.
PurposeFunction
The DCB as illustrated in figure 31 on page 21 has valid selections
Defrost Temperature Termination Shunt (Jumper) Pins
24VAC Thermostat Input /
Output
Diagnostic LED
which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt
termination pin is factory set at 50°F (10°C). If the temperature
shunt is not installed, the default termination temperature is 90°F
(32°C).
24VAC input/output from indoor thermostat to indoor unit.
Provides selection of the Y2 compressor lock−in temperature. Valid options are 40, 45, 50 and 55 degrees Fahrenheit.
(P4−5) Ground connection for outdoor coil temperature sensor.
(P4−6) Connection for outdoor coil temperature sensor.
(P4−3) Ground connection for outdoor ambient temperature sensor.
(P4−4) Connection for outdoor ambient temperature sensor.
The DCB has a field−selectable function to reduce occasional
sounds that may occur while the unit is cycling in and out of the
defrost mode. When a jumper is installed on the DELAY pins, the
compressor will be cycled off for 30 seconds going in and out of
the defrost mode. Units are shipped with jumper installed on
DELAY pins.
NOTE − The 30 second off cycle is NOT functional when
jumpering the TEST pins on P1.
Valid states for DCB’s two LEDs are OFF, ON and FLASHING
which indicate diagnostics conditions that are described in table
16 on page on page 24.
When the low pressure switch trips, the DCB will cycle off the
compressor, and the strike counter in the DCB will count one
strike. The low pressure switch is ignored under the following
conditions:
Sduring the defrost cycle and 90 seconds after the termination
LO−PSLO−PSLow−Pressure Switch
of defrost
Swhen the average ambient sensor temperature is below 0°F
(−18°C)
Sfor 90 seconds following the start up of the compressor
Sduring TEST mode
Y2 OUTY2 OUT24 VAC Output24 VAC output for second stage compressor solenoid.
Y1 OUTY1 OUT24 VAC Common Output
HS−PSHS−PSHigh−Pressure Switch
LLLine output24VAC service light output.
24V24V24 Volt output
24 VAC common output, switched for enabling compressor
contactor.
When the high pressure switch trips, the DCB will cycle off the
compressor, and the strike counter in the DCB will count one
strike.
24VAC typically used to supply power to the Lennox System
Operation Monitor (LSOM)
505328M 06/09
Page 22
Page 23
WIRE TIE
SLEEVE
AMBIENT SENSOR − Extend tip
of plastic sensor just outside of
plastic sleeve.
Place ambient sensor and wire
from DCB inside of plastic sleeve
and route through gap between
corner post and coil support as
shown. Secure with wire tie.
NOTE − No discharge sensor used;
replaced by 10K resistor.
MODELS −024, −036 AND −042
COIL SENSOR − Clip coil temperature sensor from the
DCB on the return bend shown on models as follows:
Figure 32. Heat Pump Unit Sensor Locations
24 TUBES
12 TUBES
UP
MODELS −048 AND −060
UP
Five−Strike Lockout Safety Function
The five−strike lockout safety function is designed to
protect the unit’s compressor from damage. The DCB
monitors for an active state on the DCB’s Y1 input as
referenced in figure 31 on page 21. When the Y1 input is
active the internal control logic of the DCB will do the
following:
SCount any HI−PS and LO−PS pressure switch trips
(open and close).
SIfa pressure switch trips four times during the current
active state on the Y1 input, then the DCB’s control
logic will reset the pressure switch trip counter to zero
at the end of currently active Y1 input state.
SIf the pressure switch opens for a fifth time during the
current Y1 input state, the DCB will enter a lockout
condition.
The system will require servicing to determine the cause of
the pressure switch condition. Once the condition has
been rectified, use the following procedure to reset the
DCB.
DEFROST SYSTEM SENSORS
Sensors connect to the DCB through a field-replaceable
harness assembly that plugs into the DCB. Through the
sensors, the DCB detects outdoor ambient and coil
temperature fault conditions. As the detected temperature
changes, the resistance across the sensor changes.
Sensor resistance values can be checked by ohming
across pins shown in table 15.
NOTE − When checking the ohms across a sensor, be
aware that a sensor showing a resistance value that is not
within the range shown in table 15, may be performing as
designed. However, if a shorted or open circuit is detected,
then the sensor may be faulty and the sensor harness will
need to be replaced.
Table 15. Sensor Temperature / Resistance Range
Temperature
Sensor
Outdoor−35 (−37) to 120
Coil−35 (−37) to 120
Note: Sensor resistance increases as sensed temperature
decreases.
Range °F (°C)
(48)
(48)
Resistance values
range (ohms)
280,000 to 37503 and 4
280,000 to 37505 and 6
Pins/Wire
Color
(Black)
(Brown)
Ambient SensorThe ambient sensor as illustrated in
figure 32 on page 23 considers outdoor temperatures
below −35°F (−37°C) or above 120°F (48°C) as a fault. If the
ambient sensor is detected as being open, shorted or out
of the temperature range of the sensor, the DCB will not
perform demand defrost operation. The DCB will revert to
time/temperature defrost operation and will display the
appropriate fault code. Heating and cooling operation will
be allowed in this fault condition.
Coil SensorThe coil temperature sensor as illustrated
in figure 32 on page 23, considers outdoor temperatures
below −35°F (−37°C) or above 120°F (48°C) as a fault. If the
coil temperature sensor is detected as being open, shorted
or out of the temperature range of the sensor, the DCB will
not perform demand or time/temperature defrost
operation and will display the appropriate fault code.
Heating and cooling operation will be allowed in this fault
condition.
NOTE − Within a single room thermostat demand, if
five−strikes occur, the DCB will lock out the unit. The DCB’s
24 volt power R must be cycled OFF, or the TEST pins on
DCB must be shorted between 1 to 2 seconds to reset the
DCB.
DCB OPERATIONAL MODES
The DCB has four basic operational modes which are
TEST, NORMAL CALIBRATION and DEFROST.
Page 23
XP15 SERIES
Page 24
TEST
See Figure 33 for details concerning Test Mode
operations.
NORMAL
The DCB monitors the O line, to determine the system
operating mode (heat/cool), outdoor ambient temperature,
coil temperature (outdoor coil) and compressor run time to
determine when a defrost cycle is required.
Table 16. DCB Diagnostic LEDs
DS2
Green
OFFOFFPower problem
SIMULTANEOUS
SLOW FLASH
ALTERNATING
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
FAST FLASH
ONONDCB failure
DS1
Red
ConditionPossible Cause(s)Solution
No power (24V) to DCB terminals R and
C or DCB failure.
Normal operation
5−minute anti−short cycle delay
Ambient sensor problem
Coil sensor problem
Unit operating normally or in standby
mode.
Initial power up, safety trip, end of room
thermostat demand.
Sensor being detected open or shorted or out of temperature range. DCB will revert to
time/temperature defrost operation. (System will still heat or cool).
Sensor being detected open or shorted or out of temperature range. DCB will not perform demand
or time/temperature defrost operation. (System will still heat or cool).
Indicates that DCB has internal component failure. Cycle 24 volt power to DCB. If code does not
clear, replace DCB.
CALIBRATION
The DCB is considered uncalibrated when power is
applied to the DCB, after cool mode operation, or if the coil
temperature exceeds the termination temperature when it
is in heat mode.
DEFROST
For detail information on DEFROST MODE, see Detail
Defrost Mode Operation on page 26.
1
Check control transformer power (24V).
2
If power is available to DCB and LED(s) do not light,
replace DCB.
None required.
None required (Jumper TEST pins to override)
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
1
OFF
OFFONLow pressure lockout
SLOW
FLASH
ONOFFHigh pressure lockout
SLOW
FLASH
OFFHigh pressure fault
Low pressure fault
Units WITH Discharge Line Sensor
SLOW
FLASH
FAST
FLASH
OFF
FAST
FLASH
ON
ON
FAST
FLASH
OFF
Discharge line temperature
fault
Discharge line temperature
Lockout
Discharge sensor fault
Discharge sensor lockout
Units WITHOUT Discharge Line Sensor
SLOW
FLASH
FAST
FLASH
OFF
FAST
FLASH
ON
ON
FAST
FLASH
OFF
Discharge line temperature
fault
Discharge line temperature
lockout
Discharge sensor fault
Discharge sensor lockout
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or
incorrect operation of metering device.
4
Incorrect or improper sensor location
or connection to system.
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature
exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de−energize
the compressor contactor output (and the defrost output if active). The compressor will remain off
until the discharge temperature has dropped below 225ºF (107ºC).
The board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not
within range after 90 seconds, the board will count one fault. After five faults, the board will lockout.
Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.
Some heat pump units do not use a defrost line sensor. However, on these units a resistor is
installed across pins P4−1 and P4−2. If the resistor is missing or damaged then this fault code will
be displayed.
Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.
Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for
proper current draws.
2
Check system charge using approach and
subcooling temperatures.
3
Check system operating pressures and compare to
unit charging charts.
4
Make sure all pressure switches and sensors have
secure connections to system to prevent refrigerant
leaks or errors in pressure and temperature
measurements.
505328M 06/09
Page 24
Page 25
Placing the jumper on the test pins allows the technician to:
SClear short cycle lockout
JUMPER
SClear five−strike fault lockout
SCycle the unit in and out of defrost mode
SPlace the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Demand Defrost Control, a test cycle
can be initiated by placing a jumper on the Demand Defrost Control’s TEST pins for 2 to 5 seconds.
If the jumper remains on the TEST pins for longer than five seconds, the Demand Defrost Control
will ignore the jumpered TEST pins and revert to normal operation.
The control will initiate one test event each time a jumper is placed on the TEST pins. For
each TEST the jumper must be removed for at least one second and then reapplied.
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable. No other functions will be
executed and unit will continue in the
mode it was operating.
If in COOLING Mode
No further test mode operation will be
executed until the jumper is removed
from the TEST pins and reapplied.
Y1 Active
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for 30 minute
test.
DEMAND DEFROST CONTROL
(UPPER LEFT−HAND CORNER)
INACTIVE
If in HEATING Mode
If no ambient or coil sensor ault exist,
unit will go into DEFROST MODE.
If ambient or coil faults exist (open or
shorted), unit will remain in HEAT
MODE.
NOTE Placing a jumper on the TEST pins will not bring the unit
out of inactive mode. The only way manually activate the heat
pump from an inactive mode is to cycle the 24VAC power to the
Demand Defrost Control.
If jumper on TEST pins remains in
place for more than five seconds.
The unit will return to HEAT MODE
un−calibrated with defrost timer set
for 30 minutes.
Figure 33. Test Mode
Page 25
If jumper on TEST pins is removed
before a maximum of five seconds.
The unit will remain in DEFROST
MODE until termination on time or
temperature.
XP15 SERIES
Page 26
DETAILED DEFROST MODE OPERATION
The defrost mode has three basic operational modes
which are defrost cycles, actuation and termination. These
modes are described as follows:
Defrost CyclesThe demand DCB initiates a defrost
cycle based on either frost detection or time.
Event
Frost
Detection
TimeIf six hours of heating mode compressor
ActuationWhen the reversing valve is de−energized,
the Y1 circuit is energized, and the coil temperature is
below 35°F (2°C), the DCB logs the compressor run time.
If the DCB is not calibrated, a defrost cycle will be initiated
after 30 minutes of heating mode compressor run time.
The DCB will attempt to self−calibrate after this (and all
other) defrost cycle(s).
Calibration success depends on stable system
temperatures during the 20−minute calibration period. If
the DCB fails to calibrate, another defrost cycle will be
initiated after 45 minutes of heating mode compressor run
time. Once the DCB is calibrated, it initiates a demand
defrost cycle when the difference between the clear coil
and frosted coil temperatures exceeds the maximum
difference allowed by the DCB or after six hours of heating
mode compressor run time has been logged since the last
defrost cycle.
NOTE − If ambient or coil fault is detected, the DCB will not
execute the TEST mode.
TerminationThe defrost cycle ends when the coil
temperature exceeds the termination temperature or after
14 minutes of defrost operation. If the defrost is terminated
by the 14−minute timer, another defrost cycle will be
initiated after 30 minutes of run time.
DCB DIAGNOSTICS
See table 16 on page 24 to determine DCB operational
conditions and to diagnose cause and solution to
problems.
Description
If the compressor runs longer than 30
minutes and the actual difference between
the clear coil and frosted coil temperatures
exceeds the maximum difference allowed
by the DCB, a defrost cycle will be initiated.
IMPORTANT − The DCB will allow a
greater accumulation of frost and will
initiate fewer defrost cycles than a
time/temperature defrost system.
run time has elapsed since the last defrost
cycle while the coil temperature remains
below 35°F (2°C), the DCB will initiate a
defrost cycle.
Maintenance
Before the start of each heating and cooling season, the
following service checks should be performed by a
qualified service technician. First, turn off electrical power
to the unit prior to performing unit maintenance.
WARNING
Electric shock hazard.
Can cause injury or death.
Before attempting to perform any
service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
SInspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.
NOTE − It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)
SVisually inspect the refrigerant lines and coils for leaks.
SCheck wiring for loose connections.
SCheck voltage at the indoor and outdoor units (with
units operating).
SCheck the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should
be compared with those given on unit nameplate.
SCheck, clean (or replace) indoor unit filters.
SCheck the refrigerant charge and gauge the system
pressures.
SCheck the condensate drain line for free and
unobstructed flow; clean, if necessary.
SOutdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
NOTE − If owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked.
Refer to section on refrigerant charging in this
instruction.
Homeowner Information
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check
the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for
your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the
disconnect switch before performing any
maintenance. The unit may have multiple power
supplies.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a
505328M 06/09
Page 26
Page 27
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
NOTE − The filter and all access panels must be in
place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts and diminish
performance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away
from the unit and periodically check for debris which
collects around the unit.
When removing debris from around the unit, be aware
of metal edges on parts and screws. Although special
care has been taken to keep exposed edges to a
minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion
can result in personal injury.
Cleaning of the outdoor unit’s coil should be performed
by a trained service technician. Contact your dealer
and set up a schedule (preferably twice a year, but at
least once a year) to inspect and service your heat
pump system.
HEAT PUMP OPERATION
Your new Lennox heat pump has several characteristics
that you should be aware of:
SHeat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
SDo not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45°F (7°C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
SDuring the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
EXTENDED POWER OUTAGE RESTART
PROCEDURE
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
emergency heat setting to obtain temporary heat without
the risk of serious damage to the heat pump.
In emergency heat mode, all heating demand is satisfied
by auxiliary heat; heat pump operation is locked out. After a
six-hour compressor crankcase warm-up period, the
thermostat can be switched to the Heat setting and normal
heat pump operation may resume.
THERMOSTAT OPERATION
Though your thermostat may vary somewhat from the
description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature
selector levers: one for heating and one for cooling. Set the
levers or dials to the desired temperature setpoints for both
heating and cooling. Avoid frequent temperature
adjustment; turning the unit off and back on before
pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This
mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous
indoor blower operation, regardless of whether the
compressor or auxiliary heat are operating. This mode is
required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto
operation. The auto mode allows the heat pump to
automatically switch from heating mode to cooling mode to
maintain predetermined comfort settings. Many heat
pump thermostats are also equipped with an emergency
heat mode which locks out heat pump operation and
provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which
indicates when the heat pump is operating in the
emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room
temperature.
Page 27
XP15 SERIES
Page 28
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a
programmable thermostat. These thermostats provide the
added feature of programmable time-of-day setpoints for
both heating and cooling. Refer to the user’s information
manual provided with your particular thermostat for
operation details.
PRESERVICE CHECK
If your system fails to operate, check the following before
calling for service:
SCheck to see that all electrical disconnect switches are
ON.
SMake sure the room thermostat temperature selector
and system switch (HEAT, COOL and AUTO) are
properly set.
SCheck for any blown fuses or tripped circuit breakers.
SMake sure unit access panels are in place.
SMake sure air filter is clean.
SIf service is needed, locate and write down the unit
model number and have it handy before calling.
OPTIONAL ACCESSORIES
Optional accessories for the XP15 include the following
(also, see Engineering Handbook for more details):
SCompressor starter kit
SLow ambient kit
SVapor line drier
SWire tie kit
SSnow Guard (X8782)
SSnow Shield Kit (44W14)
Start−Up and Performance Checklist
Customer Address
Indoor Unit ModelSerial
Outdoor Unit ModelSerial
Notes:
START−UP CHECKS
Refrigerant Type:
Rated Load AmpsActual AmpsRated VoltsActual Volts
Condenser Fan Full Load AmpsActual Amps:
COOLING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach
temperatures.)
Subcooling:A
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:A
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F)A
Return Air Temperature (A)
minus Supply Air Temperature (B)
B
B
B
SUBCOOLING
=
=
COIL TEMP DROP
=
APPROACH
505328M 06/09
Page 28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.