Lennox XP15, XP15-042, XP15-024, XP15-030, XP15-036 Installation Instructions Manual

...
Page 1
INSTALLATION
,1,_2008LennoxindustriesInc,
®
Dallas,Texas,USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
X_ WARNING
_, CAUTION
Dave Lennox Signature ®
Collection XP15 Units
HEAT PUMP UNITS _-_Technical 505,328M U£[ Publications
04/08 Litho U.S.A.
Supersedes 03/08
XP15 Outdoor Unit ............................ 1
Shipping and Packing List ...................... 1
Unit Dimensions ............................... 2
General Information ........................... 2
Recovering Refrigerant from Existing System ..... 4
Positioning New Outdoor Unit .................. 5
Removing Panel .............................. 6
Electrical Connections ......................... 7
New or Replacement Line Set ................... 9
Brazing Line Set Connections ................... 11
Removing Existing Refrigerant Metering Device . .. 11
Testing for Leaks .............................. 11
Removing Service Valve Port Core .............. 12
Flushing Existing System ....................... 12
Installing New Refrigerant Metering Device ....... 13
Installing Service Valve Port Core ............... 14
Evacuating the System ......................... 14
Start-Up Procedures ........................... 15
System Operations ............................ 19
Lennox System Operation Monitor (LSOM) ....... 19
Defrost System ............................... 21
Maintenance .................................. 26
Homeowner Information ........................ 26
Start-Up and Performance Checklist ............. 28
A IMPORTANT
IMPORTANT
04/08
IIIHIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
The Lennox XP15 outdoor units use HFC-410A refrigerant, This unit must be installed with a matching
indoor coil and line set as outlined in the Lennox Engineering Handbook, XP15 series outdoor units are
designed for use in check expansion valve (CTXV) systems only, and are not designed to be used with other
refrigerant flow control devices. The Lennox Engineering Handbook lists compatible indoor CTXV kits which are
ordered separately.
1 - Assembled XP15 outdoor unit 1 - Bushing (for low voltage wiring)
2 - Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Page 1
505,328M
IIIIIIIIIIIIIIIIIIIIIIHIIIIIIIIIIIIIIIIIIIIIIII
Page 2
39-1/2 DISCHARGE AIR (1003) t
35-1/2
(902)
ELECTRICAL IN_ETS __
37 (94O)
[-024 thru -042]
47 (1194)
[-048 and -060]
UNIT SUPPORT
FEET \
Y
16-7/8
(429)
8 -3/4
(2_2)
3-1/8
(79) "-_
BASE WITH ELONGATED LEGS
SIDE VIEW
® ® ®
VAPOR LINE
INLET
LIQUID LINE
/INLET
DEFROST CONTROL
& CONTACTOR
OPERATION MONITOR
VAPOR VALVE AND
26-7/8 GAUGE PORT ..
(6_3) DISCHARGE LINE
3-3/4 (95) VAPOR
_' FILTER
4-5/8
(117)
18!1/2
(470)
SYSTEM
4-7/16.__
(113)
7--
8 (203)
1 (25)
XP15 Parts Arrangement
ACCESS VIEW
FAN
CAPACITOR
COMPRESSOR
DOME
COMPRESSOR
PLUG
LOW PRESSURE
HIGH PRESSURE SWITCH
WARNING
505328M 04/08
I
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities
who have jurisdiction before installation. When servicing or repairing HVAC components, ensure
caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
Page 2
Page 3
USINGMANIFOLD GAUGE SETS
HFC-410A refrigerant manifold gauge sets must be capable of handling higher system operating pressures.
The gauge set shall be rated for use with pressures of 0 - 800 psig on the high side, and a low side of 30 inches of
vacuum (Hg) to 250 psig, which retards when opened to 500 psig. Gauge hoses must be rated for use up to 800 psig
of pressure with a 4000 psig burst rating, OPERATING SERVICE VALVES
IMPORTANT
The liquid and vapor lines service valves with gauge ports as illustrated in figures 2 and 3 are used for removing
refrigerant, flushing, leak testing, evacuating, checking charge and charging,
Each valve is equipped with a service port which has a
factory-installed valve stem.
1/6 TURN
1/12 TURN
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1 on page 2.
Without Torque Wrench: Finger tighten and with an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle-Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak-free seal.
1, Remove stem cap with a wrench,
2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes and 5/16" for vapor-line valve sizes) to back the stem out
counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1 on page 2.
Without Torque Wrench: Finger tighten and with an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 1,
NOTE -A label with specific torque requirements may be affixed to the stem cap, If the label is present, use the specified torque listed,
SERVICE PORT CAP
SERVICE PORT _
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS]
VALVE STEM
VALVE IS FRONT-SEATED
o
(CLOSED)
jSERV,CEPORT
,, HHERE
This illustrates how to use a wrench to tighten caps an additional
1/6 or 1/12 turn clockwise.
Figure 1. Cap Tightening Distances
IMPORTANT
Operating Angle-Type Service Valve
To Access Angle-Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap using an appropriately sized wrench.
Page 3
FRON%SEATEI_
TO INDOOR
CORE _ _ "i
UNIT
TO OUTDOOR _
UNIT
SERVICE PORT CAP _ _:_ VALVE IS(oPENED)BACK=SEATED
CORE SERVICE PORT
SERVICE PORT _
OPEN TO BOTH
INDOOR AND (VALVE STEM
OUTDOOR UNITS] L _ _ SHOWNOPEN)INSERTHEX
VALVE STEM WRENCH HERE
TO INDOOR
UNIT
BACKED-SEATE_ __
TO OUT
UNIT
Figure 2. Angle -Type Service Valve
XP15 SERIES
Page 4
Operating Bali-Type Service Valve
To Access Bali-Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal,
1, Remove service port cap using an appropriately sized
wrench,
2. Connect gauge to the service port. 3, When testing is completed, replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table table 1 on page 2.
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1,
To Open and Close Bali-Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak-free seal,
1, Remove stem cap with a wrench,
2, Use an adjustable wrench to open, To open valve,
rotate stem counterclockwise 90°, To close rotate stem clockwise 90°.
3, Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table 1 on page 2.
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 1.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified valve listed.
Remove existing HCFC-22 refrigerant using one of the
following methods:
METHOD 1:
If the existing outdoor unit is not equipped with shut-off
valves, or if the unit is not operational and you plan to use the existing HCFC-22 or refrigerant to flush the system:
1, Disconnect all power to the existing outdoor unit,
2, Connect to the existing unit a gauge set, clean
recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections,
3, Remove all HCFC-22 refrigerant from the existing
system, Check gauges after shutdown to confirm that the entire system is completely void of refrigerant,
4, Disconnect the liquid and vapor lines from the existing
outdoor unit,
5, Remove the existing outdoor unit,
NOTE - Use recovery machine instructions for specific setup requirements.
Recovery Machine
\
Manifold Gauges
/
To INDOOR UNIT
Open to line set when valve is closed, to both line set
and unit when valve is open.
Service Port
Service Port
Core
Service Port
Cap
To outdoor unit
Use Adjustable Wrench To open: rotate Stem Counter-Clock- wise 90°.To close: rotate Stem clockwise 90°.
Figure 3. Bali-Type Service Valve
Ball (Shown Closed)
Valve Stem
t
STEM CAP
Clean Recovery Cylinder
Figure 4. Typical Refrigerant Recovery (Method 1)
METHOD 2:
If the existing outdoor unit is equipped with manual shut-off
valves and you plan to use new HCFC-22 refrigerant to flush the system -
1, Start the existing HCFC-22 system in the cooling
mode and close the liquid line valve,
2, Pump all of the existing HCFC-22 refrigerant back into
the outdoor unit,
NOTE - It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.
Outdoor/_Unit
505328M 04/08
Page 4
Page 5
3.Whenthelowsidesystempressuresreach0 psig, closethevaporlinevalve,
4. Disconnectall powerto the existingoutdoorunit. Checkgaugesaftershutdownto confirmthat the
valvesarenotallowingrefrigeranttoflowbackintothe
lowsideofthesystem,
5. Disconnecttheliquidandvaporlinesfromtheexisting outdoorunit.
6. Removetheexistingoutdoorunit,
CAUTION
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports, Refer to figure 5 for mandatory installation clearance requirements.
Install unit away
from windows
Two 90° elbows installed inline set -
will reduce line set vibration.
Figure 6. Outside Unit Placement
PLACING UNIT ON SLAB When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from higher ground would not collect around the unit as
illustrated in figure 7. Slab may be level or have a slope tolerance away from the building of not more than two
degrees, or 2 inches per 5 feet (51 mm per 1524 mm).
NOTES: Service clearance of 30 in, (762 mm) must be maintained on one of
the sides adjacent to the control box, Clearance to one of the other three sides must be 36 in, (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in, (152 mm)
48 in, (1219 ram) clearance required on top of unit, A clearance of 24 in, (610 mm) must be maintained between two
units
Figure 5. Installation Clearances POSITIONING CONSIDERATIONS Some localities are adopting sound ordinances based on
the unit's sound level registered from the adjacent property, not from the installation property, Install the unit
as far as possible from the property line. When possible, do not install the unit directly outside a window, Glass has a
very high level of sound transmission. For proper placement of unit in relation to a window see the provided
illustration in figure 6.
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
Building Structure
J
7/ Mounting
-T--
Slab
Figure 7. Ground Level Slab Mounting
INSTALLING UNIT ON ROOF Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that
can adequately support the unit, Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed as illustrated in figure 8. Size barrier at least the same height and width as
outdoor unit, Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
Page 5
XP15 SERIES
Page 6
PREVAILING _.
WINTER WINDS
I WIND BARRIER
INLET AIR ,_
1
2_'_6" 10 ram)
With unit positioned at installation site, remove two side Iouvered panels to expose the unit base pan. Install the
brackets as illustrated in figure 10 using conventional practices; replace the panels after installation is complete.
INLETAIR
O INLET AIR
Figure 8. Rooftop Application and Wind Barrier
NOTE - If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces.
ELEVATING THE UNIT These units are outfitted with elongated-shaped feet as
illustrated in figure 9.
BASE
IMPORTANT
Slab Side Mounting
#101/2" LONG
SELF-DRILLING SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE METAL - 2"
RW/DTDHi HEIGHT AS _,_1 f, _ #10 1-1/4" LONG HEX
HD SCREW AND FLATWASHER
PLASTIC ANCHOR - USE IF CONCRETE (HOLE DRILL 1/4"); NOT IF PLASTIC SLAB
(HOLE DRILL 1/8").
/
LEG DETAIL 2"(50.8MM)
SCH 40
FEMALE THREADED ADAPTER
Figure 9. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be
done with 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recess portion of
the feet. Use additional 2" SCH 40 male threaded adapters
which can be threaded into the female threaded adapters
to make additional adjustments to the level of the unit.
NOTE - Keep the height of extenders short enough to ensure a sturdy installation, If it is necessary to extend further, consider a different type of field-fabricated
framework that is sturdy enough for greater heights.
STABILIZING UNIT ON UNEVEN SURFACES
Mounting
STABILIZING MINIMUM 1 BRACKET (18 PER SIDE
GAUGE METAL - 2" WIDTH; HEIGHT
AS REQ'D); BEND TO FORM RIGHT FOR EXTRA
I Deck Top
ANGLE STABILITY
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO BRACKETS PER SIDE, 2" FROM EACH CORNER.
Figure 10. Installing Stabilizer Brackets
CAUTION
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.
505328M 04/08
Page 6
Page 7
REMOVE4SCREWSTOREMOVEPANELFOR
ACCESSINGCOMPRESSORANDCONTROLS.
_ INSTALLBYPOSITIONINGPANELWITHHOLES
ALIGNED;INSTALLSCREWSANDTIGHTEN.
Figure 11. Access Panel
IMPORTANT! DO NOT ALLOW K-_ PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT
ANDNOTDESIGNEDTOSUPPORT
)
WE,GHTOFPANEL
PANEL SHOWN SLIGHTLY _ _
ROTATED TO ALLOW TOP TAB TO _
EXIT (OR ENTER) TOP SLOT FOR _ PANEL.
REMOVING (OR INSTALLING) _
SCREW
L. HOLES......_ _iiii_///l _
ii
Detail A
Detail B -_-_\_
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO THE HINGED SIDE TO MAINTAIN
EXTREME FULLY-ENGAGED TABS
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY ALONG
Detail D
Figure 13. Removing/Installing Louvered Panels
(Detail D)
ACCESS PANEL
Removal and reinstallation of the access panel is illustrated in figure 11,
LOUVERED PANELS
Remove the Iouvered panels as follows:
1, Remove two screws, allowing the panel to swing open
slightly.
U
2, Hold the panel firmly throughout this procedure.
Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in figure 12, detail B.
t_
3, Move panel down until lip of upper tab clears the top
slot in corner post as illustrated in figure 12, detail A, Position and Install Panel--Position the panel almost parallel with the unit as illustrated in figure 13, detail D with
the screw side as close to the unit as possible. Then, in a continuous motion:
Slightly rotate and guide the lip of top tab inward as
illustrated in figure 12, details A and C; then upward
into the top slot of the hinge corner post.
Rotate panel to vertical to fully engage all tabs,
Holding the panel's hinged side firmly in place, close
the right-hand side of the panel, aligning the screw
holes. When panel is correctly positioned and aligned, insert the
screws and tighten.
Figure 12. Removing/Installing Louvered Panels
(Detail A, B and C)
A'kWARNING
In the U,S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC), ELECTRICAL AND CONTROL CONNECTIONS
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum overcurrent protection size.
NOTE - Connect conduit to the unit using a proper conduit fitting. Units are approved for use only with copper conductors. A complete unit wiring diagram is located on the back side of the unit's access panel.
NOTE - For proper voltages, select thermostat wire gauge
per the following chart:
Page 7
XP15 SERIES
Page 8
Table 2. Wire Run Length
Wire Run Length AWG # Insulation Type
less than 100' (30m) 18 color-coded, temperature more than 100' (30m) 16 rating 35°C minimum
1. Install room thermostat (ordered separately) on an inside wall approximately in the center of the area and 5 feet (1.5 m) from the floor. Do not installon an outside
wall or where sunlight, drafts or vibrations affect it.
2. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated in
figure 14.
3. Install line voltage power supply to unit from a properly sized disconnect switch as illustrated in figure 15.
4. Ground unit from ground lug as illustrated in figure 15 to unit disconnect switch, or to an earth ground.
LI _._
z_
RTI$
AMBIENT
SENSOR
@
R721 DEFROST
COIL SENSOR
S4HIGH
PRESSURE
SWITCH
$87 LOW
PRESSURE
SWITCH
©
LI
REVERSING
VALVE
©
LZ_
CONTACTOR
OMPRESSOR
54O
AI32
HRI
A
AI32
A
EQUIPMENT
GROUND
COMPRESSOR
CONTACTOR
BLACK
CB31MV
TBI
CBX32MV
A2 SIGNATURE
81M2B
TWISTEO
PAIR
(W5_ (W8
"-(v _
G
BI
© @
A NOTE
FOR USE WITH COPPER CONDUCTORS ONLY.
w
I
REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND
MAXIMUM OVER CURRENT PROTECTION SIZE
A REFER TO COMPRESSOR N UNIT
FOR ACTUAL TERMINAL mRmANGEMENT.
Z_ WARNING
ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH.UNIT MUST BE GROUNDED IN ACCOROANCE WITH NATIONAL AND LOCAL CODES.
A RTI4 SENSOR, OUTDOOR TEMP (OPTIONAL)
LINE VOLTAGE FIELD INSTALLED CLASS II VOLTAGE FIELD INSTALLED
Figure 14. Typical Low-Voltage Field Wiring
GROUNDLUG
CONTACTOR
DEFROST CONTROL
GROUND
208-230/60/1 L1
L2
-''_/ L_)NNNTOoXRt LYs'<oTE_ OPERATION
"__ _[3_/ _ CAPACITOR
K1-1 COMPRESSOR CONTACTOR
BOARD (DCB)
WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes. NOTE - For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
CONTROLBOX _'-
Figure 15. Typical High-Voltage Field Wiring (Unit Panel)
505328M 04/08
Page 8
Page 9
This sectionprovidesinformationon installationor replacementofexistinglinesets.Iflinesetsarenotbeing
installedorreplace,thenproceedtoBrazing Connections
on page 11. If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the building, Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings, floors), the
refrigerant lines will not create unnecessary vibration and subsequent sounds.
REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat, non41are) series line sets, or use field-fabricated
refrigerant lines as listed in table 3.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
IMPORTANT
Line sets for heat pump applications can not be installed underground. For more information see the Lennox
Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications
for assistance.
Table 3. Refrigerant Line Sets
Valve Sizes Recommended Line Set
Model Liquid Vapor Liquid Vapor L15
Line Line Line Line LineSets
-024
-030 (10mm) (19mm) (10mm) (19mm) 15-50ft.
-- (5 - 15 m)
-036
-042 3/8 in. 7/8 in 3/8 in. 7/Sin L15-65
-060 (10 ram) (29 ram) (10 ram) (29 ram) Fabricated
3/8 in. 3/4 in. 3/8 in 3/4 in. L15-41
15 - 50 ft.
(10mm) (22mm) (10mm) (22mm) (5-15m) 3/8 in. 1-1/8 in, 3/8 in. 1-1/8 in, Field
INSTALLING LINE SET Line Set Isolation--This reference illustrates
procedures, which ensure proper refrigerant line set isolation:
Installation of line sets on horizontal runs is illustrated in figure 16.
Installation of line sets on vertical runs is illustrated in figure 17 on page 10.
Installation of a transition from horizontal to vertical is illustrated in figure 18 on page 10.
When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication
Guidelines, or contact Lennox Technical Support Product
Applications for assistance. To obtain the correct
information from Lennox, be sure to communicate the
following points:
Model (XP15) and size (e.g. -060) of unit. Line set diameters for the unit being installed (from
table 3)
Number of elbows and if there is a rise or drop of the piping.
TO HANG LINE SET FROM JOIST OR RAFTER,
USE EITHER METAL STRAPPING MATERIAL OR
ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND VAPOR LINE
ONLY)
METAL JOIST OR RAFTER AT 8 FEET
TAPE OR LIQUID LINE TO THE VAPOR LINE.
FLOOR JOIST OR _ _ _% ROOF RAFTER _-
SLEEVE INTERVALS THEN STRAP THE
STRAP THE VAPOR LINE TO THE
WIRE TIE (AROUND VAPOR LINE ONLY
8 FEET TAPE OR
_._ I1
Figure 16. Refrigerant Line Sets: Installing
Horizontal Runs
WIRE TIE
Page 9
XP15 SERIES
Page 10
OUTSIDEWALLREFRIGERANTLINESMUST
IMPORTANT-
NOTCONTACTWALL.VAPORLINELIQUIDLINE
NOTE-SIMILAR
INSTALLATION
PRACTICESSHOULDBE
USEDIFLINESETISTO
BEINSTALLEDON
EXTERIOROFOUTSIDE
WALL.
VAPORLINEWRAPPED
WITHARMAFLEX
ANCHOREDHEAVY
NYLONWIRETIE
WALL
STUD
METALSLEEVE
AUTOMOTIVE
MUFFLER-TYPEHANGER
VAPORLINE-WRAPPED
INARMAFLEX
WALL
STUD
STRAPLIQUIDLINE
TOVAPORLINE
JIDLINE
IMPORTANT!
REFRIGERANTLINES
MUSTNOTCONTACT
STRUCTURE.
PVC_ CAULK
PIPE FIBERGLASS
INSULATION
Figure 17. Refrigerant Line Sets: Installing Vertical
Runs (New Construction Shown)
1
CUT AND DEBUR
INDOOR UNIT
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT
POINT FOR NITROGEN SERVICE
j SUCTION LINE _ /VALVE
_QU_DUNE SERV_CEJ
IUIDLINE
TOVAPORLINE
LIQUID
LINE
METALSLEEVE INARMAFLEX
Figure 18. Refrigerant Line Sets: Transition from
Vertical to Horizontal
VALVE
VAPORLINEWRAPPED
UNIT
outdoor
INSTALL CORE ONLY FOR
3OTH SERVICE PORTS after they
have coolED.
505328M 04/08
Figure 19. Brazing Connections
Page 10
Page 11
ISOLATION GROMMETS
Locate the provided isolation grommets Slide grommets onto vapor and liquid lines Insert grommets into mullion to
isolate refrigerant lines from sheet metal edges
Use the following procedure to braze the line set to the new outdoor unit Figure 19 is provided as a general guide for
preparing to braze the line sets to the outdoor unit Before brazing, remove the access panel as illustrated in
figure 11; then remove the narrow piping panel to prevent
burning off the paint as illustrated in figure 20
REMOVE TWO SCREWS
AND REMOVE PANEL
BEFORE BRAZING
LINE SET
CONNECTION
POINTS
Figure 20. Piping Panel Removal
WARNING
underneath the valve body to protect the base paint, Also, shield the light maroon R-410A sticker.
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of
the valve stem port connection on the vapor service valve. The CTXV metering device at the indoor unit coil will allow low pressure nitrogen to flow through the system,)
Note: Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing or 45
percent silver alloy for copper-to-brass or copper-to-steel
brazing,
6. Braze the line set to the liquid line service valve. Turn off nitrogen flow, Repeat procedure starting at paragraph 4 for brazing the vapor line set to service
valve,
After brazing the vapor line set to the service valve,
disconnect gauge from service port, remove wrapping and replace service port cores.
Remove the existing HCFC-22 refrigerant flow control orifice or thermal expansion valve from the indoor coil. Existing devices are not approved for use with HFC-410A
refrigerant and may prevent proper flushing. Use a
field-provided fitting to reconnect lines, See figure 23 on
page 13 for disassembly and typical removal instructions.
_WARNING
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the vapor and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve,
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth
After the line set has been connected to both the indoor
and outdoor units, check the line set connections at both the indoor and outdoor units unit for leaks. Use the
following procedure to test for leaks:
IMPORTANT
WARNING
AWARNING
Page 11
XP15 SERIES
Page 12
WARNING I OUTOOORO.,T
1 Connect an HFC410A manifold gauge set high
pressure hose to the vapor valve service port
(Normally the high pressure hose is connected to the liquid line port; however, connecting it to the vapor port
better protects the manifold gauge set from high
pressure damage.)
2 With both manifold valves closed connect the cylinder
of HFC410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A
cylinder (vapor only)
3 Open the high pressure side of the manifold to allow
HFC 410A into the line set and indoor unit
4 Weigh in a trace amount of HFC410A [,4 trace
amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure].
5, Close the valve on the HFC-410A cylinder and the
valve on the high pressure side of the manifold gauge set.
6. Disconnect the HFC-410A cylinder, 7, Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set, 8, Adjust dry nitrogen pressure to 150 psig (1034 kPa), 9, Open the valve on the high side of the manifold gauge
set in order to pressurize the lineset and the indoor unit,
10, After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector,
11, After leak testing disconnect gauges from service
ports,
SERVICE VALVE
REMOVE SERVICE
PORT CAP
REMOVE PORT CORE
Figure 21. Typical Service Valve Port Core Removal
A IMPORTANT
A IMPORTANT
A CAUTION
A IMPORTANT
Remove both of the outdoor unit's service port cores (liquid and vapor) as illustrated in figure 21,
505328M 04/08
If new lines are used then proceed to Installing New
Refrigerant Metering Device. Otherwise proceed with the
following procedure,
Page 12
Page 13
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
Two clean HCFC-22 recovery bottles,
Oilless recovery machine with pump-down feature,
Two gauge sets (one for HCFC-22; one for HFC-410A),
RECOVERY MACHINE
NOTE - The inverted HCFC-22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system.
6, Close the valve on the inverted HCFC-22 drum and
the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
XP15 units are used in check thermal expansion valve (CTXV) systems only, See the indoor unit coil installation
instructions and the Lennox Engineering Handbook for approved CTXV match-ups and application information. Table 3 on page 9 lists liquid and vapor line sizes and
corresponding line sets,
(Uncased Coil Shown)_ -
TWO PIECE PATCH
PLATE(UNCASED OR
COIL ONLY) ORIFICE NSION VALVE
TUBES
HOUSING
I EXPA )RI FICE _""_
I (SEE NOTE)
Figure 22. Typical Flushing Connection
PROCEDURE
1, Verify that the existing HCFC-22 refrigerant flow
control device has been removed before continuing
with flushing procedures. Existing devices are not approved for use with HFC-410A refrigerant and may
prevent proper flushing.
2, Connect an HCFC-22 cylinder with clean refrigerant to
the vapor service valve. Connect the HCFC-22 gauge set to the liquid line valve. Connect a recovery
machine with an empty recovery tank to the gauge set
as illustrated in figure 22.
3, Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the
existing system line set and indoor unit coil.
4, Invert the cylinder of clean HCFC-22 and open its
valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine,
5, After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the
recovery machine to pull a vacuum on the system,
NOTE - A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor unit coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
ACCESS FITTING
(NO VALVE CORE)
On smaller vapor lines, bulb may be
mounted on top or side-mounted (prefer-
ably at 3 o'clock position). On 518"and larger lines, mount bulb
approximately at the 4 or 8 o'clock posi- tions; never mount on bottom of line.
o @clock
NOTE - If necessary, remove HCFC-22 flow control device (fixed orifice/check expansion valve) from existing line set before instal-
ling HFC-410A approved expansion valve and o-ring.
Figure 23. Typical Metering Device Installation
The thermostatic expansion valve or check / thermostatic expansion valve, can be installed internal or external to the
indoor coil. In applications where an uncased coil is being installed in a field provided plenum, install the CTXV and provide an access for field servicing of the CTXV. Refer to Figure 23 for reference during installation of CTXV,
Page1
XP15 SERIES
Page 14
1, On fully cased coils, remove the coil access and
plumbing panels,
2, Remove any shipping clamps holding the liquid line
and distributor assembly,
3. Using two wrenches, disconnect liquid line from distributor. Take care not to twist or damage distributor tubes during this process,
4, Remove and discard RFC bullet and Teflon washer,
5. Remove and discard cap from the equalizer line port on the vapor line. Check for valve core in port fitting and if installed, remove from port.
6. Install one of the provided Teflon washers around the stubbed end of the CTXV,
7. Attach the stubbed end of the kit valve to the distributor assembly.
8. Place the remaining Teflon washer around the other end of the CTXV.
9. Attach the liquid line to the CTXV.
10. Attach the sensing bulb of the CTXV in the proper orientation to the vapor line using the clamp an screws provided with the CTXV,
11. Connect the equalizer line from the CTXV to the equalizer vapor port on the vapor line.
12. To prevent against any possibility of water damage, properly insulate all parts of the CTXV assemble that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
13. The expansion/check valve can be installed internally in coil blowers, or external or internal to indoor coil only
applications,
Expansion valves equipped with Chatleff type fittings are available from Lennox, Refer to the Engineering
Handbook for CTXV kits for use with specific match-ups.
Table 4. Indoor CTXV Kits
Model Kit Number XP15-024 and -036 49L24
XP15-048 and -060 91M02
A IMPORTANT
If the indoor unit being installed came with a fixed orifice type metering device, remove that orifice and install the
CTXV as illustrated in figure 23.
Re-install both of the outdoor unit's service port cores (liquid and vapor) as illustrated in figure 24.
LIQUID AND VAPOR
SERVICE VALVES DO NOT INSTALL
CAPS AT THIS TIME
O TOOO .
INSTALL SERVICE
PORT CORES
Figure 24. Typical Service Valve Port Core
Installation
WARNING
A IMPORTANT
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under
temperatures and pressures present during operation of an air conditioning system. Non-condensables and water
vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set,
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of
mercury).
NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak, If this occurs, repeat the leak testing procedure.
NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacuum
pressure,
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge
505328M 04_8
Page 14
Page 15
valves,turnoffthevacuumpumpanddisconnectthe
manifoldgaugecenterporthosefromvacuumpump.
Attachthemanifoldcenterporthosetoadrynitrogen
cylinderwithpressureregulatorsetto150psig(1034 kPa)andpurgethehose.Openthemanifoldgauge
valvestobreakthevacuuminthelinesetandindoor
unit.Closethemanifoldgaugevalves,
7, Shutoff thedry nitrogencylinderandremovethe
manifoldgaugehosefromthe cylinder.Openthe manifoldgaugevalvestoreleasethedrynitrogenfrom
thelinesetandindoorunit,
8, Reconnectthemanifoldgaugetothevacuumpump,
turnthepumpon,andcontinuetoevacuatethelineset andindoorunituntiltheabsolutepressuredoesnot
riseabove500microns(29.9inchesofmercury)within a20-minuteperiodaftershuttingoffthevacuumpump andclosingthemanifoldgaugevalves.
9,Whentheabsolutepressurerequirementabovehas
beenmet,disconnectthe manifoldhosefrom the vacuumpumpandconnectittoanuprightcylinderof
HFC-410Arefrigerant,Openthemanifoldgaugevalve
1to2 psiginordertoreleasethevacuuminthelineset andindoorunit,
10,Close manifoldgaugevalvesand shut off the
HFC-410Acylinderandremovethe manifoldgauge set,
SERVICINGUNITSDELIVEREDVOIDOFCHARGE Ifthesystemisvoidofrefrigerant,cleanthesystemusing
theproceduredescribedbelow,
1, Usenitrogentopressurizethesystemandcheckfor
leaks,Repairallleaks,
2, Evacuatethe systemto removeas muchof the
moistureaspossible,
3, Usenitrogentobreakthevacuumandinstalla new
filterdrierinthesystem.
4, Evacuatethe system again. Then, weigh the
appropriateamountofHFC-410Arefrigerantaslisted onunitnameplateintothesystem.
5, Monitorthe systemto determinethe amountof
moistureremainingintheoil.Itmaybenecessaryto
replacethefilterdrierseveraltimesto achievethe
requireddrynesslevel.If systemdryness is not verified,thecompressorwillfail inthefuture.
4, Replace the stem caps and tighten as specified in
Operating Service Valves on page 3.
5, Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you
have consulted with the power company and the voltage condition has been corrected,
6, Set the thermostat for a cooling demand. Turn on
power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7, Recheck voltage while the unit is running. Power must
be within range shown on the nameplate,
8, Check system for sufficient refrigerant by using the
procedures listed under Testing and Charging
System,
TESTING AND CHARGING SYSTEM This system uses HFC-410A refrigerant which operates at
much higher pressures than HCFC-22. The pre-installed liquid line filter drier is approved for use with HFC-410A
only, Do not replace liquid line filter drier with components designed for use with HCFC-22,
NOTE - This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device,
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC-410A.
2. Connect the manifold gauge set to the unit's service ports as illustrated in figure 25,
low pressure gauge to vapor service port
high pressure gauge to liquid service port
COOLING MODE INDOOR AIRFLOW CHECK Check airflow using the Delta-T (DT) process as illustrated
in figure 26 on page 16. HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
temperature rise between the return air and supply air temperatures at the indoor coil blower unit,
voltage supplied to the unit,
amperage being drawn by the heat unit(s),
Then, apply the measurements taken in following formula to determine CFM:
IMPORTANT
1. Rotate fan to check for frozen bearings or binding.
2, Inspect all factory- and field-installed wiring for loose
connections.
3, After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system,
Page15
CFM =
CALCULATING CHARGE If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the unit, To calculate the total refrigerant charge:
Amount Adjust amount for specified per specified variation in indoor unit
on line set length match-up Total
nameplate (table in figure 27) (tables 6 through 11) charge
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Additional charge
+ + =
XP15 SERIES
Page 16
CHECK
EXPANSIONVALVE
LOW HIGH [
PRESSUREPRESSURE
_:[tGAUGEMANIFO%D1]:_
DISTRIBUTOR
DRIER OUTDOOR
MUFFLER
CO,L
OUTDOOR UNIT
REVERSING VALVE
NOTE - ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
HFC-410 LINEI
ADRUM VALVE COMPRESSOF
J2
NOTE- Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging,
Figure 25. XP15 Cooling Cycle (Showing Gauge Manifold Connections)
Temp. l of air I 80 24
entering,_ I 78 23 indoor _ I ==
coil °F _'?1
I
All temperatures are expressed in °F 6
I
"- 17421
Wet-bulb °F 57
24 24 23 23 22 22 22 20 19 18 17 16 15 23 23 22 22 21 21 20 19 18 17 16 15 14
22
22 22 21 21 20 19 19 18 17 16 15 14 13
tu
21 21 20 19 19 18 17 16 16 15 14 13 12 20 19 18 17 17 161L55_15 14 13 12 11 10
72 20
70 19
19 18 18 17 17 16 15 15 14 13 12 11 10 58 59 60 61 62 63 64 65 66 67 68 69 70 I
19°
DT
n
iNDOOR WET
COiL BULB
DRY
BULB
1. Determine the desired DT--Measure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersect-
ing value of A and B in the table (see triangle).
2. Find temperature drop across coil--Measure the coil's dry bulb entering and leaving air temperatures (A and C). Tem-
perature Drop Formula: (TDrop) = A minus C.
3. Determine if fan needs adjustment--If the difference between
$
the measured TDrop and the desired DT (TDrop-DT) is within +_3°, no adjustment is needed. See examples: Assume DT =
15 and A temp. = 72 °, these C temperatures would necessi-
LEILI9 _LaL_d EI(3LIUII_:
C° TDrop- DT = °F ACTION
53° 19 - 15 = 4 Increase the airflow 58° 14 - 15 = -1 (within +3° range) no change
62° 10 - 15 = -5 Decrease the airflow
4. Adjust the fan speed--See indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck tempera-
tures to confirm that the temperature drop and DT are within +_30.
Figure 26. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart
VAPOR LINE VALVE
CHECK EXPANSION VALVE --
INDOOR
COIL
WEIGH
Refrigerant Charge per Line Set Length
Liquid Line Ounces per 5 feet (g per 1.5 m)
Set Diameter adjust from 15 feet (4.6 m) line set*
3t8" (9.5 mm) 3 ounce per 5' (85 g per 1.5 m)
NOTE - *If line length is greater than 15 ft. (4.6 m), add this
amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
505328M 04/08
L_NNOX
HIHIIIJI|I[I
@:L,
Figure 27. Using Weigh In Method
Page 16
1. Check Liquid and suction line pressures
2. Compare unit pressures with table 5, Normal Operating Pressures,
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences
over feet,
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor
unit for charge information.
Page 17
8UBCOOLING 1
2
3
USE COOLING
USE HEATING
%
MODE
60°F (15 °) --
MODE
4
Check the airflow as illustrated in figure 26 to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following
procedure.) Measure outdoor ambient temperature; determine whether to use cooling mode
or heating mode to check charge. Connect gauge set. Check Liquid and Vapor line pressures. Compare pressures with Normal
Operating Pressures table 5, (The reference table is a general guide. Expect
minor pressure variations. Significant differences may mean improper charge or other system problem. )
Set thermostat for heat/cool demand, depending on mode being used: Using cooling mode--When the outdoor ambient temperature is 60°F (15°C) and
above. Target subcooling values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that
temperature range; then set thermostat to cooling mode setpoint to 68°F (20°C). When pressures have stabilized, continue with step 6.
SATo LIQo -
SCo =
Using heating mode--When the outdoor ambient temperature is below 60°F (15°C). Target subcooling values in table below are based on 65-75°F (18-24°C) indoor
return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77°F (25°C). When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQ ° space.
7 Read the liquid line pressure; then find its corresponding temperature in the
temperature/pressure chart listed in table 12 and record it in the SAT° space.
8 Subtract LIQ° temp. from SAT° temp. to determine subcooling; record it in SC° space. 9 Compare SC° results with table below, being sure to note any additional charge for
line set and/or match-up.
10 If subcooling value is greater than shown in tables 6 through 11for the applicable unit,
remove refrigerant; if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
Figure 28. Using Subcooling Method
Table 5. Normal Operating Pressure - Liquid +10 and Vapor +5 PSIG*
IMPORTANT
|lliiliTo]ilv/_-I IP.|l[[o]i[-.lllilllii['4-"[_]l)i] I[:t-$"]!ll':-.t-lliiL.]Iv|i[_ :--,).-4i[:[_rlrl_irilrlll_l_-41[-4i[_-4.111i!11i1,¢ _-"ll .F'[|[o]i[..'!ll_-'l[i-']'_ilil i,_.]i|l[ill_l[q 1['4i[_:t-11
""""'"" il"""T II
XP15-024 XP15-030 XP15-036 XP15-042 XP15-048 XP15-060
..aidI vo o. I vo o. I vo o...aidI Vo o. I Vo o. I Vo o.
HEATINGOPERATION
20 (-7.0) 315 65 308 62 284 59 293 58 312 62 349 61 30 (-1.0) 340 81 317 76 296 71 312 71 332 76 375 74
40 (4.4) 364 97 339 89 313 87 321 82 353 92 384 88
50 (10) 394 115 359 107 326 106 337 103 374 110 406 107
COOLING OPERATION
65 (18.3) 237 141 250 141 260 139 265 141 242 139 255 136 75 (23.9) 274 143 292 143 298 141 309 144 279 140 297 138 85 (29.4) 319 145 336 145 344 143 360 147 322 142 343 140
95 (35.0) 364 147 385 147 393 145 408 149 370 144 392 142 105 (40.6) 415 149 438 148 446 148 462 151 423 147 447 145 115 (49.0) 469 152 497 151 506 150 522 154 479 149 510 148
*These are most-popular-match-up pressure& Indoor match up, indoor air quality, and indoor load cause pressures to vary. **Temperature of the air entering the outdoor coi!.
Page 17
XP15 SERIES
Page 18
Table 6. XP15-024
Target *Add
INDOOR MATCHUPS Heat Cool
CH23-51 14 6 0 14 CBX27UH-030-230 13 6 2 4 CB3OU-31 15 5 O 1
CBX32M-030 15 5 O 1 CBX32M-036 13 6 2 4 CBX32MV-024/030 15 5 O O
CBX32MV-036 13 6 2 4 CH33-42 14 6 O 14
CR33-48 38 7 3 1 CX34-31 15 5 0 1 CX34-38 SN# 6007 and after 6 6 1 15
CX34-38 before SN# 6007 13 6 1 15
Subcooling charge
(+5OF) (+1OF) Ib oz
Table 7. XP15-030
Target *Add
INDOOR MATCHUPS Heat Cool
CH23-51 13 5 0 4 CBX27UH-030-230 12 5 0 10
CBX27UH-036-230 13 5 0 8 CB30U-31 14 5 0 0
CB30U-41/46 12 5 0 10 CBX32M-030 14 5 0 0 CBX32M-036 12 5 0 10
CBX32MV-024/030 14 5 0 0 CBX32MV-036 12 5 0 10 CR33-48 31 4 0 13
CX34-38 SN# 6007 and after 5 5 0 8 CX34-38 before SN# 6007 13 5 0 8
CX34-43 9 5 1 4 CX34-49 6 5 2 0 CX34-50/60C 9 5 1 4
Subcooling charge
(+5OF) (+1OF) Ib oz
Table 8. XP15-036
Target *Add
INDOOR MATCHUPS Heat Cool
CBX27UH-036-230 13 4 0 3 CBX27UH-042-230 5 5 O 12 CB3OU-41/46 13 4 O 3
CB3OU-51 5 5 O 12 CBX32M-042 13 4 O 3
CBX32M-048 5 5 O 12 CBX32MV-036 13 4 O 3
CBX32MV-048 5 5 O 12 C33-44C 13 4 O 3 CH33-42 14 4 O 1
CH33-44/48B 9 4 O 7 CH33-48C 7 5 O 7
CH33-49C 5 5 O 12 CH33-62D 5 7 O 14 CR33-48C 37 4 O 5
CR33-50/60 32 5 O 10 CX34-31 15 4 O O CX34-38 SN# 6007 and after 4 4 O 3
CX34-38 before SN# 6007 13 4 O 3 CX34-43 7 5 O 7
CX34-44/48 13 4 O 3 CX34-49 6 5 O 11
Subcooling charge
(+5OF) (+1OF) Ib oz
Table 9. XP15-042
Target *Add
INDOOR MATCHUPS Heat Cool
CH33-62D 7 7 0 13 CBX27UH-042-230 9 4 O 11 CBX27UH-048-230 9 4 O 11
CB3OU-51*P 9 4 O 11 CBX32M-048 9 4 O 11 CBX32MV-048 9 4 O 11
C33-44C 13 4 O O CH33-44/48B, -48C 12 4 O 5
CH33-49C 9 4 O 12 CR33-48 35 3 O 2 CX34-38 SN# 6007 and after 4 4 O O
CX34-38 before SN# 6007 13 4 O O CX34-43 12 4 O 5
CX34-44/48B 13 4 O O CX34-50/60C 12 4 O 5
Subcooling charge
(+5OF) (+1OF) Ib oz
Table 10. XP1 _-048
Target *Add
INDOOR MATCHUPS Heat Cool
CH23-68 21 4 0 12 CBX27UH-048-230 22 4 O 3 CBX27UH-060-230 12 4 O 11
CB3OU-51*P 22 4 O 3 CB3OU-65*P 12 4 O 3
CBX32M-048 22 4 O 3 CBX32M-060 12 4 O 3 CBX32MV-048 22 4 O 3
CBX32MV-060 12 4 O 3 CBX32MV-068 12 4 O 7 CH33-62D 12 4 O 8
CX34-49C 13 4 O 2 CX34-6OD 14 4 O O
CX34-62D 12 4 O 5
Subcooling charge
(+5OF) (+1OF) Ib oz
Table 11. XP15-060
Target *Add
INDOOR MATCHUPS Heat Cool
CH23-68 28 6 0 0 CBX27UH-060-230 17 6 O O
CB3OU-51*R -65"P 19 6 O 2 CBX32M-O48*R -O6O*P 19 6 O 2
CBX32MV-O48*R -O6O*P 19 6 O 2 CH33-62D 18 6 O 1
*Amount of charge required in addition to charge shown on unit
nameplate. (Remember to consider lineset length difference.)
Subcooling charge
(+5OF) (+IOF) Ib oz
505328M 04_8
Page 18
Page 19
Table 12. HFC-410A Temperature (°F) -
Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
INSTALLING SERVICE VALVE CAPS Disconnect gauge set and re-install all service valve caps.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is
staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit
control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light
simultaneously comes on to remind the homeowner that the unit is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power
outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C), The system
should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to
prevent compressor slugging. HIGH-PRESSURE SWITCH
XP15 units are equipped with a high-pressure switch that is located in the liquid line to the compressor. The normally
closed SPST auto-reset switch opens at 590 psi, LOW-PRESSURE SWITCH XP15 units are equipped with a low-pressure switch that is
located in the vapor line to the compressor. The normally closed SPST auto-reset switch opens at 25 psi and closes
at 55 psi, SINGLE-SPEED CONDENSER FAN MOTOR
The XP15 is equipped with a single-speed condenser fan motor. The compressor contactor and defrost control
board (DCB) controls the operation of the motor, FILTER DRIER The unit is equipped with a large-capacity biflow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of like design and capacity, Replacement filter driers must be suitable for use with
HFC-410A refrigerant,
OUTDOOR UNIT
SERVICE VALVE _ _/
Figure 29. Installing Service Valve Port Caps
The outdoor unit and indoor blower cycle on demand from the room thermostat, When the thermostat blower switch
is in the ON position, the indoor blower operates continuously.
THERMOSTAT OPERATION
Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber
indicating light). The thermostat is not included with the unit and must be purchased separately,
INSTALL CAPS
The LSOM detects the most common fault conditions in the system. When an abnormal condition is detected, the
LSOM communicates the specific condition through its
ALERT and TRIP lights, The LSOM is capable of detecting
both mechanical and electrical system problems. See
figure 30 for LSOM LED locations.
POWER LED .....
TRIP LED
ALERT LED
Figure 30. LSOM
Page 19
XP15 SERIES
Page 20
Table 13. LSOM LED Troubleshooting Codes
Status LED Status LED Condition Description
Green Power LED ON LSOM has power
Green Power LED OFF LSOM not powering up
Red Trip LED ON
Red Trip and Yellow
Alert LEDs Flashing Simultaneous flashing,
Yellow Alert Flash Code 1"
Yellow Alert Flash Code 2*
Yellow Alert Flash Code 3*
Yellow Alert Flash Code 4*
Yellow Alert Flash Code 5*
Yellow Alert Flash Open Start Circuit - Cur-
Code 6* rent only in run circuit
Yellow Alert Flash Open Run Circuit - Current Code 7* only in start circuit
Yellow Alert Flash Welded Contactor - Code 8* Compressor always runs
Yellow Alert Flash Low Voltage - Control cir- Code 9* cuit <17VAC
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALER Tflash code by removing 24VAC power
from LSOM; last code will display for 1minute after LSOM is powered on. Note: If the unit is equipped with a two-stagged compressor, upon Y2 signal detection and after five seconds, the LSOM will send 24 VAC to the solenoid.
Once the solenoid is fully energized, the LSOM reduces voltage to between 4 to 18 VDC .Every 15 minutes the solenoid voltage will be increase to 24 volts for a few seconds to ensure solenoid valve is engaged until Y2 signal is no longer present.
System and compressor check out OK
Thermostat demand signal Y1 is present, but compressor not running
NO TE - During 5-minute delay in LSOM the red trip
LED will be on.
Long Run Time - Compres- sor is running extremely long run cycles
System Pressure Trip - Discharge or vapor pressure
out of limits or compressor overloaded
Short Cycling - Compres- sor is running only briefly
Locked Rotor
Open Circuit
Status LED Troubleshooting Information
24VAC control power is present at the LSOM terminal. Determine/verify that both R and C LSOM terminals are connected and voltage is present
at both terminals. 1Verify Y terminal is connected to 24VAC at contactor coil.
2Verify voltage at contactor coil falls below 0.5VAC when off. 3Verify 24VAC is present across Y and C when thermostat demand signal is present; if not
present, R and C wires are reversed. 1 Compressor protector is open. 2 Outdoor unit power disconnect is open. 3 Compressor circuit breaker or fuse(s) is open.
4 Broken wire or connector is not making contact.
5 Low pressure switch open if present in the system. 6 Compressor contactor has failed to close.
Indicates that the control circuit voltage is too low for operation.
1 LOW refrigerant charge.
2 Evaporator blower is not running. 3 Evaporator coil is frozen.
4 Faulty metering device.
5 Condenser coil is dirty. 6 Liquid line restriction (filter drier blocked if present). 7 Thermostat is malfunctioning.
1 Check high head pressure or discharge line sensor. 2 Condenser coil poor air circulation (dirty, blocked, damaged).
3 Condenser fan is not running.
4 Return air duct has substantial leakage.
5 If low pressure switch is present, see Flash Code 1 information. 1 Thermostat demand signal is intermittent.
2 Time delay relay or DCB is defective. 3 If high pressure switch is present, see Flash Code 2 information.
4 If low pressure switch is present, see Flash Code 2 information.
1 Run capacitor has failed. 2 Low line voltage (contact utility if voltage at disconnect is low). 3 Excessive liquid refrigerant in the compressor.
4 Compressor bearings are seized.
1 Outdoor unit power disconnect is open. 2 Unit circuit breaker or fuse(s) is open.
3 Unit contactor has failed to close.
4 High pressure switch is open and requires manual reset.
5 Open circuit in compressor supply wiring or connections. 6 Unusually long compressor protector reset time due to extreme ambient temperature. 7 Compressor windings are damaged.
1 Run capacitor has failed. 2 Open circuit in compressor start wiring or connections.
3 Compressor start winding is damaged. 1 Open circuit in compressor start wiring or connec_ons.
2 Compressor start winding is damaged. 1 Compressor contactor failed to open.
2 Thermostat demand signal not connected to LSOM. 1 Control circuit transformer is overloaded.
2 Low line voltage (contact utility if voltage at disconnect is low).
505328M 04_8
Page 20
Page 21
LSOM--LED Functions
A IMPORTANT
See table 13 on page 20 for the complete explanation of troubleshooting codes.
LED Color
Green Power 19-28VAC is present at LSOM con-
Yellow Alert
Red Trip the compressor is detected by the
Function Description
Indicates voltage within the range of
nection.
Communicates an abnormal system condition through a unique flash code.
The alert LED flashes a number of times consecutively; then pauses;
then repeats the process. This consecutive flashing correlates to a particular abnormal condition.
Indicates there is a demand signal
from the thermostat but no current to LSOM.
Y terminal, If the red LED does not function as described, refer to table 13 on page 20 to verify the
wiring,
TEST 2:
1. Disconnect power from the compressor and 24VAC power from the LSOM
2. Remove the wire from the Y terminal of LSOM and reapply power to the compressor, allowing the
compressor to run. The yellow alert LED will begin flashing a code 8 indicating a welded contactor,
3. While the LSOM is off, reattach the wire to the Y terminal,
4. Reapply power to the compressor and 24VAC power to the LSOM; the yellow alert LED will flash the
previous code 8 for one minute and then turn off. If the yellow LED does not function as described, refer to table 13 on page 20 to verify the wiring,
DEFROST CONTROL BOARD (DCB) FUNCTION The DCB measures differential temperatures to detect
when the system is performing poorly because of ice
build-up on the outdoor coil. The DCB self-calibrates when the defrost system starts and after each system defrost
cycle. The DCB components are illustrated in figure 31.
Resetting Alert Codes
Alert codes can be reset manually or automatically:
Cycle the 24VAC power to LSOM off and on. Af-
Manual ter power up, existing code will display for one
minute and then clear. After an alert is detected, the LSOM continues
Automatic to monitor the compressor and system. Whentif
conditions return to normal, the alert code is turned off automatically.
LSOM--L Terminal Connection
The L connection is used to communicate alert codes to the room thermostat. On selected Lennox SignatureStat"
thermostats, a blinking check LED will display on the room thermostat and on select White-Rodgers room
thermostats, an icon on the display will flash. Either will
flash at the same rate as the LSOM yellow alert LED,
NOTE - ROOM THERMOSTATS WITH SERVICE OR CHECK LIGHT FEATURE--The room thermostat may
blink the Check or Service LED or it may come on sofid, Confirm fault by observing and interpreting the code from
the LSOM yellow alert LED at the unit,
LSOM--Installation Verification
To verify correct LSOM installation, two functional tests can be performed.
TEST 1:
1. Disconnect power from the compressor and force a thermostat call for cooling.
2. The red trip LED should turn on indicating a compressor trip as long as 24VAC is measured at the
Note - Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR
PLUG IN (COIL AND AMBIENT
SENSORS)
DELAY
REVERSING
VALVE
PRESSURE
SWITCH
CIRCUIT
CONNECTIONS
rEs_ PI [_ O rAN
°
PINS
o_7 o
O wl
0-Ps
¢0_MON _2
TStPS O_ C _ 0 v_ _2
LOW AMBIENT
THERMOSTAT PINS
_DIAGNOSTIC
LEDS
24V TERMINAL STRIP
CONNECTIONS
Figure 31. Defrost Control Board (DCB)
The DCB monitors ambient temperature, outdoor coil temperature, and total run time to determine when a
defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE - The DCB accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the DCB initiates defrost cycles.
Page 21
XP15 SERIES
Page 22
Pressure Switch Connections
The unit's automatic reset pressure switches (LO PS - $87 and HI PS - $4) are factory-wired into the DCB on the
LO-PS and HI-PS terminals, respectively.
Pressure Switch Event Settings The following are the auto reset event values for low and high pressures thresholds:
High Pressure (auto reset) - trip at 590 psig, reset to
418 psig.
Low Pressure (auto reset) - trip at 25 psig, reset to 55
psig.
Five-Strike Lockout Safety Function The five-strike lockout safety function is designed to protect the unit's compressor from damage. The DCB monitors for an active state on the DCB's Y1 input as
referenced in figure 31 on page 21. When the Y1 input is active the internal control logic of the DCB will do the
following:
Count any HI-PS and LO-PS pressure switch trips
(open and close).
If a pressure switch trips four times during the current
active state on the Y1 input, then the DCB's control logic will reset the pressure switch trip counter to zero at the end of currently active Y1 input state.
If the pressure switch opens for a fifth time during the
current Y1 input state, the DCB will enter a lockout condition.
The system will require servicing to determine the cause of the pressure switch condition. Once the condition has
been rectified, use the following procedure to reset the DCB.
DEFROST SYSTEM SENSORS Sensors connect to the DCB through a field-replaceable
harness assembly that plugs into the DCB. Through the sensors, the DCB detects outdoor ambient and coil
temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Sensor resistance values can be checked by ohming across pins shown in table 14.
NOTE - When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 14, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will
need to be replaced.
Table 14. Sensor Temperature / Resistanc4 Range
Temperature Resistance values Pins/Wire
Sensor Range °F (°C) range (ohms) Color
Outdoor -35 (-37) to 120 280,000 to 3750 3 and 4
(48) (Black)
Coil -35 (-37) to 120 280,000 to 3750 5 and 6
(48) (Brown)
Note: Sensor resistance increases as sensed temperature
decreases.
Ambient Sensor--The ambient sensor as illustrated in figure 32 on page 24 considers outdoor temperatures
below -35°F (-37°C) or above 120°F (48°C) as a fault. Ifthe ambient sensor is detected as being open, shorted or out
505328M 04/08
of the temperature range of the sensor, the DCB will not perform demand defrost operation. The DCB will revert to
time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will
be allowed in this fault condition, Coil Sensor--The coil temperature sensor as illustrated
in figure 32 on page 24, considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. Ifthe
coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the DCB will
not perform demand or time/temperature defrost operation and will display the appropriate fault code.
Heating and cooling operation will be allowed in this fault
condition.
NOTE - Within a single room thermostat demand, if five-strikes occur, the DCB will lock out the unit. The DCB's
24 volt power R must be cycled OFF, or the TESTpins on DCB must be shorted between 1 to 2 seconds to reset the
DCB.
DCB OPERATIONAL MODES
The DCB has four basic operational modes which are TEST, NORMAL CALIBRATION and DEFROST.
TEST
1. When Y1 is energized and 24V power is being applied to the DCB, a test cycle can be initiated by: placing the termination temperature jumper across the Test pins (P1) for 2 to 5 seconds.
2. If the jumper remains across the Test pins longer than five seconds, the DCB will ignore the test pins and
revert to normal operation,
3. The jumper will initiate one cycle per test.
4, Enter the TEST MODE by placing a jumper across the
TEST pins on the DCB after power-up. The TEST pins are ignored and the test function is locked out if the
shunt is applied on the TEST pins before power-up.
5, DCB timings are reduced, the low-pressure switch is
ignored and the DCB will clear any active lock out condition,
6, Each test pin shorting will result in one test event, For
each TEST the jumper must be removed for at least one second and reapplied, Refer to flow chart illustrated in figure 33 on page 24 for TEST operation,
NOTE - The Y1 input must be active (ON) and the 0 room thermostat terminal into DCB must be inactive
NORMAL
The DCB monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required,
CALIBRATION
The DCB is considered uncalibrated when power is applied to the DCB, after cool mode operation, or if the coil
temperature exceeds the termination temperature when it is in heat mode.
DEFROST
For detail information on DEFROST MODE, see Detail
Defrost Mode Operation on page 26.
Page 22
Page 23
Table 15. Defrost Control Board (DCB) Inputs, Outputs and Configurable Settings
DCB DCB Label or Location Description Purpose Function
P1 TEST Test Mode
P1 50, 70, 90, 100
Wl Output C 24VAC Common L Thermostat Service Light
P2 R 24VAC
Y2 Thermostat Input O Thermostat Input
Y1 Thermostat Input
P3 55, 50, 45, 40 Low Ambient Thermostat Pins
DIS-YEL Coil Sensor
P4
P5
P6 DS1 DS2
FAN
O OUT
LO-PS
Y2 OUT Y2 OUT 24 VAC Output
Y1 OUT Y1 OUT 24 VAC Common Output
HS-PS HS-PS High-Pressure Switch
24V 24V 24 Volt output
AMB-BLACK Ambient Sensor
COIL-BROWN Discharge Sensor
DELAY
TST, PS DF, C, R, O, Y1, Y2 RED LED
GREEN LED TWO CONNECTORS O OUT
LO-PS
L Line output
Defrost Temperature Termina-
tion Shunt (Jumper) Pins
24VAC Thermostat Input /
Delay Mode
Factory Test Connectors
Diagnostic LED
Condenser Fan Operation
24 VAC output
Low-Pressure Switch
See Test Mode on page 22 for further details. The DCB as illustrated in figure 31 on page 21 has valid selections
which are: 50, 70, 90, and 100°F (10, 21,32 and 38°C), The shunt termination pin is factory set at 50°F (10°C). If the temperature
shunt is not installed, the default termination temperature is 90°F (32°C).
24VAC input/output from indoor thermostat to indoor unit.
24VAC common Thermostat service light connection,
24VAC Controls the second stage operation of the unit,
Reversing valve solenoid. Controls the operation of the unit, Provides selection of the Y2 compressor lock-in temperature. Val-
id options are 40, 45, 50 and 55 degrees Fahrenheit, (P4-5) Ground connection for outdoor coil temperature sensor.
(P4-6) Connection for outdoor coil temperature sensor. (P4-3) Ground connection for outdoor ambient temperature sen-
sor. (P4-4) Connection for outdoor ambient temperature sensor.
No discharge sensor is used, replaced by !OK resistor.
The DCB has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the
defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE - The 30 second off cycle is NOT functional when
jumperingthe TES Tpins on P1.
No field use. Valid states for DCB's two LEDs are OFF, ON and FLASHING
which indicate diagnostics conditions that are described in table
16 on page on page 25.
These two connections provide power for the condenser fan. 24 VAC output connection for reversing valve. When the low pressure switch trips, the DCB will cycle off the
compressor, and the strike counter in the DCB will count one strike. The low pressure switch is ignored under the following
conditions:
during the defrost cycle and 90 seconds after the termination of defrost
when the average ambient sensor temperature is below 0°F (-18°C)
for 90 seconds following the start up of the compressor
during TEST mode
24 VAC output for second stage compressor solenoid. 24 VAC common output, switched for enabling compressor
contactor. When the high pressure switch trips, the DCB will cycle off the
compressor, and the strike counter in the DCB will count one strike.
24VAC service light output, 24VAC typically used to supply power to the Lennox System
Operation Monitor (LSOM)
Page23
XP15 SERIES
Page 24
WIRETIE
\
SLEEVE
AMBIENT SENSOR - Extend tip of plastic sensor just outside of
plastic sleeve. Place ambient sensor and wire
from DCB inside of plastic sleeve and route through gap between corner post and coil support as
shown. Secure with wire tie.
24 TUBES
UP
APRIL 2006)
12 TUBES / UP
16 TUBES UP
/
/
NOTE- No discharge sensor used; replaced by fOK resistor
Figure 32. Heat Pump Unit Sensor Locations
Short test pins for Iongerthan one second
but less than two
seconds
Clear any short cycle lockout and five-strike
fault lockout function, if applicable. No other
functions will be executed and unit will continue inthe mode it
was operating.
L
.finOO0.,N ModeII .fin.E T,N Mode II
No further test mode operation will be
executed until the test short is removed and
reapplied.
MODELS -024 AND -036
COIL SENSOR - Clip coil temperature sensor from the DCB on the return bend shown on models as follows:
Model -024 and -036:12 tubes up from bottom (11-1/2"); Model -048 and -060 (before April 2006): 16 tubes up from bottom (15-1/2") Model -048 and -060 (after April 2006): 24 tubes up from bottom (23-1/2")
1
Y1 Active ("0" line inactive) /
Short test pins for more than two seconds
Clear any short cycle lockout and five-strike
fault lockout function, if applicable.
The DCB will check for ambient and coil faults (open or shorted). If a fault exists,
the unit will remain in HEAT MODE and
no further TEST MODE operation will be
executed until the test short is removed and reapplied. If no fault exists the unit
will go into DEFROST MODE.
MODELS -048 AND -060
If in DEFROST Mode ]
The unit will terminate defrost and enter HEAT MODE un-calibrated with defrost timer set for 34 minute test. No further test
mode operation will be executed until the test
short is removed and reapplied.
Test pin short REMAINS in place for more than five seconds
The unit will return to HEAT MODE un-calibrated with defrost timer set for 34 minutes. No further test mode operation will be
executed until the test short is removed and reapplied.
505328M 04/08
Test pins short REMOVED before a maximum of five seconds
The unit will remain in DEFROST MODE until termination on time or temperature.
Figure 33. Test Mode
Page 24
Page 25
Table 16. DCB Diagnostic LEDs
DS2 DS1 Green Red
OFF OFF Power problem Cor DCB failure.
SIMULTANEOUS Unit operating normally or in standby None required.
SLOW FLASH Normal operation mode.
ALTERNATING Initial power up, safety trip, end of room None required (Jumper TEST pins to override)
SLOW FLASH 5-minute anti-short cycle delay thermostat demand. SIMULTANEOUS Sensor being detected open or shorted or out of temperature range. DCB will revert to
FAST FLASH Ambient sensor problem time/temperaturedefrost operation. (System will still heat or cool).
ALTERNATING Sensor being detected open or shorted or out of temperature range. DCB will not perform demand
FAST FLASH Coil sensor problem or time/temperature defrost operation. (System will still heat or cool).
Condition Possible Cause(s) Solution
1 Check control transformer power (24V).
No power (24V) to DCB terminals R and 2 If power is available to DCB and LED(s) do not light,
replace DCB.
ON DCB failure clear, replace DCB.
ON Indicates that DCB has internal component failure. Cycle 24 volt power to DCB. If code does not
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
OFF FLASH Low pressure fault
OFF ON Low pressure lockout
SLOW
FLASH OFF High pressure fault
ON OFF High pressure lockout
SLOW Discharge line temperature
FLASH ON fault FAST
FLASH ON
OFF FLASH
FAST FLASH OFF
SLOW Discharge line temperature
FLASH ON fault
FAST Discharge line temperature FLASH ON lockout
SLOW
FAST
Discharge line temperature Lockout
Discharge sensor fault
Discharge sensorlockout
1 Restricted air flow over indoor or out-
door coil.
2 Improper refrigerant charge in sys-
tem.
3 Improper metering device installed or
incorrect operation of metering de-
vice.
4 Incorrect or improper sensor location
or connection to system.
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output if active). The compressor will remain off
until the discharge temperature has dropped below 225°F (107°C).
The board detects open sensor or out of temperature sensor range. This fault is detected by allow-
ing the unit to run for 90 seconds before checking sensor resistance. Ifthe sensor resistance is not
within range after 90 seconds, the board will count one fault. After five faults, the board will lockout.
Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.
1 Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and subcooling temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant
leaks or errors in pressure and temperature measurements.
OFF Discharge sensor fault installed across pins P4-1 and P4-2. If the resistor is missing or damaged then this fault code will
FAST Discharge sensor lockout FLASH Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.
FAST FLASH
OFF
Some heat pump units do not use a defrost line sensor. However, on these units a resistor is
be displayed.
Page 25
XP15 SERIES
Page 26
DETAILED DEFROST MODE OPERATION
The defrost mode has three basic operational modes
which are defrost cycles, actuation and termination, These
modes are described as follows: Defrost Cycles--The demand DCB initiates a defrost
cycle based on either frost detection or time,
_WARNING
Event Frost
Detection
Time
Actuation--When the reversing valve is de-energized,
the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the DCB logs the compressor run time.
If the DCB is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time.
The DCB will attempt to self-calibrate after this (and all other) defrost cycle(s),
Calibration success depends on stable system temperatures during the 20-minute calibration period. If
the DCB fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run time, Once the DCB is calibrated, it initiates a demand
defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the DCB or after six hours of heating
mode compressor run time has been logged since the last defrost cycle,
NOTE - If ambient or coil fault is detected, the DCB will not execute the TEST mode.
Termination--The defrost cycle ends when the coil temperature exceeds the termination temperature or after
14 minutes of defrost operation, If the defrost is terminated by the 14-minute timer, another defrost cycle will be initiated after 34 minutes of run time,
DCB DIAGNOSTICS
See table 16 on page 25 to determine DCB operational conditions and to diagnose cause and solution to
problems.
Description
If the compressor runs longer than 34
minutes and the actual difference between the clear coil and frosted coil temperatures
exceeds the maximum difference allowed by the DCB, a defrost cycle will be initiated.
IMPORTANT - The DCB will allow a greater accumulation of frost and will
initiate fewer defrost cycles than a time/temperature defrost system.
If six hours of heating mode compressor
run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the DCB will initiate a defrost cycle.
Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose.
NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with units operating).
Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
Check the refrigerant charge and gauge the system pressures.
Check the condensate drain line for free and unobstructed flow; clean, if necessary.
Outdoor unit fan motor is prelubricated and sealed. No further lubrication is needed.
NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this
instruction.
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1, Air Filter--Ask your Lennox dealer to show you where
your indoor unit's filter is located. Itwill be either at the indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2, Disposable Filter--Disposable filters should be
replaced with a filter of the same type and size,
NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Before the start of each heating and cooling season, the
following service checks should be performed by a
qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance.
505328M 04/08
3, Reusable Filter--Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
Page 26
Page 27
mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE - The filter and all access panels must be in place any time the unit is in operation.
4, Electronic Air Cleaner--Some systems are
equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.
5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
6, Outdoor Unit--Make sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which
collects around the unit. When removing debris from around the unit, be aware
of metal edges on parts and screws. Although special
care has been taken to keep exposed edges to a
minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion
can result in personal injury.
Cleaning of the outdoor unit's coil should be performed
by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at
least once a year) to inspect and service your heat
pump system.
HEAT PUMP OPERATION Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the conclusion of the defrost cycle.
EXTENDED POWER OUTAGE RESTART PROCEDURE
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant
slugging during cold weather operation. If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the emergency heat setting to obtain temporary heat without
the risk of serious damage to the heat pump. In emergency heat mode, all heating demand is satisfied
by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the
thermostat can be switched to the Heat setting and normal heat pump operation may resume.
THERMOSTAT OPERATION Though your thermostat may vary somewhat from the
description below, its operation will be similar. Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the
levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature
adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the
compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch Set the system switch for heating, cooling or auto
operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to
maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency
heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light Most heat pump thermostats have an amber light which
indicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator The temperature indicator displays the actual room
temperature.
Page27
XP15 SERIES
Page 28
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat, These thermostats provide the
added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information
manual provided with your particular thermostat for operation details,
PRESERVlCE CHECK If your system fails to operate, check the following before
calling for service:
Check to see that all electrical disconnect switches are ON,
Check for any blown fuses or tripped circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean.
If service is needed, locate and write down the unit model number and have it handy before calling.
OPTIONAL ACCESSORIES Optional accessories for the XP15 include the following
(also, see Engineering Handbook for more details):
Compressor starter kit
Low ambient kit
Make sure the room thermostat temperature selector and system switch (HEAT, COOL and AUTO) are
properly set,
Customer Address Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
Vapor line drier
Wire tie kit
START-UP CHECKS
Refrigerant Type: Rated Load Amps
Condenser Fan Full Load Amps
Actual Amps Actual Amps:
Rated Volts Actual Volts
COOLING MODE
Vapor Pressure: Supply Air Temperature:
Liquid Pressure:
Ambient Temperature:
Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature: System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required subcooling and approach
temperatures.) Subcooling: A B
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach: A B
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F) A B
Return Air Temperature (A)
minus Supply Air Temperature (B)
SUBCOOLING
COIL TEMP DROP
APPROACH
505328M 04/08
Page 28
Loading...