Lennox XP14 Elite Series, Elite xP14-018, Elite xP14-024, Elite xP14-030, Elite xP14-036 Installation Instructions Manual

...
Page 1
ze jv
,1_2008 Lennox industries Inc.
Dallas, Texas, USA
INSTALLATION INSTRUCTIONS
XP14 Elite ®Series Units
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
CAUTION
A IMPORTANT
A IMPORTANT
HEAT PUMP UNITS _]_Technical
04108 Supersedes 11/07
XP14 Outdoor Unit ............................ 1
Shipping and Packing List ...................... 1
Unit Dimensions and Parts Arrangement ......... 2
General Information ........................... 3
Setting the Unit ............................... 3
Removing Panels ............................. 5
Electrical ..................................... 6
Refrigerant Piping ............................. 8
Flushing Existing Line Set and Indoor Coil ........ 10
Refrigerant Metering Device .................... 12
Manifold Gauge Set ........................... 13
Service Valves ................................ 13
Leak Testing .................................. 14
Evacuation ................................... 14
Start-Up ...................................... 15
Refrigerant Charge ............................ 15
Check Indoor Airflow before Charging ............ 15
Setup for Checking and Adding Charge .......... 16
Pre-Charge Maintenance Checks ................ 16
Weigh in Charge .............................. 17
Subcooling Charge ............................ 17
Defrost System ............................... 19
Maintenance .................................. 24
User Information .............................. 24
Start-up and Performance Checklist .............. 26
The XP14 outdoor unit uses HFC-410A HFC refrigerant. This unit must be installed with a matching indoor blower coil and line set as outlined in the Lennox Engineering Handbook, Elite® Series XP14 outdoor units are designed
for use in check thermal expansion valve (CTXV) systems
only and are not to be used with other refrigerant flow control devices. An expansion valve approved for use with HFC-410A must be ordered separately and installed prior to operating the unit,
.ELL1 Publications
04/08
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
1 - Assembled XP14 outdoor unit
Check the unit components for shipping damage. If you
find any damage, immediately contact the last carrier,
Page 1
505,244M
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Page 2
RUN
DEFROST
UNIT SUPPORT
FEET _/
TOP VIEW
C
DISCHARGE AIR t
SIDE VIEW
i i
(
SUCTION LINE VALVE
FILTER DRIER/
LIQUID LINE CONNECTION
LIQUID LINE CONNECTION
ELECTRICAL INLETS
VAPOR LINE
/CONNECTION
4-1/4( 4-3/4
108) (121)
CONNECTIONS
f _
t
9-1/2
REVERSING
LIQ
PARTS ARRANGEMENT
B "-=
r
1
A
2(51)
1
I I I__._J
1 (25) SIDE VIEW
FEET\
UNIT SUPPORT _
18-7/8 @ @ ®
(429)
HIGH PRESSURE SWITCH
VAPOR LINE
VAPOR VALVE AND
BAUGE PORT/SUCTION
LINE CONNECTIONS
-[
26-7/8
(683)
(
_ _ 1(_413)
XP14-018 TO -030 BASE SECTION
Model No. A B C
xP14-018 31 (787) 27 (686) 28 (711) xP14-024 31 (787) 27 (686) 28 (711)
xP14-030 35 (889) 27 (686) 28 (711) xP14-036 31 (787) 35 1/2 (902) 39 1/2 (1003)
xP14-042 39 (991) 35 1/2 (902) 39 1/2 (1003) xP14-048 39 (991) 35 1/2 (902) 39 1/2 (1003)
xP14-060 45 (1143) 35 1/2 (902) 39 1/2 (1003)
505244M 04/08
(2il)
8-1/4 (210)
i_
Page 2
8-3/4 (222)
t
3-1/8
(79) _ (781)
XP14-036 TO -060 BASE WITH
ELONGATED LEGS
_2
3-3/4
(95)
_4-5/8
(117)
Page 3
WARNING
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities
having jurisdiction before installation. When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM
Machine screws #8 16 in.- lb. 2 NM Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
4. Locate the unit so prevailing winter winds will not blow into the coil.
5. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil
or into unit.
NOTES:
Service clearance of 30 in, (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm),
A clearance of 24 in, (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit,
CAUTION
Outdoor units operate under a wide range of weather conditions; therefore, several factors must be considered
when positioning the outdoor unit.
Position the unit to allow adequate airflow and servicing clearance. Maintain a minimum clearance of 24 inches
(610 mm) between multiple units as illustrated in figure 1
for installation clearances.
1. Place a sound-absorbing material, such as Isomode, under the unit if it will be installed in a location or
position that will transmit sound or vibration to the living area or adjacent buildings.
2. Install the unit high enough above ground or roof to allow adequate drainage of defrost water and prevent
ice build-up.
3. In heavy snow areas, do not locate unit the where snowdrifts will likely build. The unit base should be elevated above the depth of average snows.
NOTE- Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain
holes in unit base.
Figure 1. Installation Clearances
SLAB MOUNTING
When installing unit at grade level, the top of the slab should be high enough above grade so that water from
higher ground will not collect around the unit. The slab should have a slope tolerance away from the building of 2
degrees or 2 inches per 5 feet (50 mm per 1500 mm) to prevent ice build-up under the unit during a defrost cycle.
NOTE - If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
4.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET
[50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BU,LD,NG
STRUCTURE MOUNTING_ --7-
SLAB
-/
GROUND LEVEL
Figure 2. Slab Mounting Options
Page 3
.....1
XP14 SERIES
Page 4
ELEVATING THE UNIT (SMALL-BASE UNITS) If additional elevation is necessary, raise the unit by
extending the length of the unit support feet. This may be done by cutting four equal true-cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as
illustrated in figure 3,
NOTE - Keep the height of extenders short enough to ensure a sturdy installation, If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0,25" (6.35mm) greater than the
pre-installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this
procedure, Small strips of 0,125" (3.175mm) thick adhesive foam may be used, One or two small 1"
(25,4mm) square strips should be adequate to hold the extender in place.
Base
NOTE - Keep the height of extenders short enough to ensure a sturdy instaflation, If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
Base
Leg Detail
2" (50.Smm)
SCH 40
Female Threaded
Adapter
Figure 4. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.
Leg Detail
4" (101.6mm)
SCH 40 Piping
Figure 3. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
ELEVATING THE UNIT (LARGER-BASE UNITS)
Unlike the small-base units which use round feet, the larger-base units are outfitted with elongated feet as
illustrated in figure 4. which uses a similar method for elevating the unit height,
If additional elevation is necessary, raise the unit by extending the length of the unit support feet, This may be
done with 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recess portion of the feet. Use additional 2" SCH 40 male threaded adaptors
which can bethreaded into the female threaded adaptors
to make additional adjustments to the level of the unit,
TYPICAL i-L INSTALLATION __'-_
WITH 3 TO 4 IN. EXTENDERS
IMPORTANT! STRUCTURE INSTALLED _ BUILDING
ALWAYS USE MOUNTING _ ---FSTABILIZER BRACKET ON SLAB
ELEVATED INSTALLATIONS
STABILIZER BRACKETS
GROUND LEVEL
Figure 5. Elevated Slab Mounting using Feet
Extenders
,& IMPORTANT
505244M 04/08
Page 4
Page 5
With unit positioned at installation site, remove two side Iouvered panels to expose the unit base pan. Install the
brackets as illustrated in figure 6 using conventional
)ractices; replace the panels after installation is complete,
#101/2" LONG
SELF-DRILLING SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE METAL - 2"
WIDTH; HEIGHT AS
REQ'D)
#101-1/4" LONG HEX
HD SCREW & FLATWASHER
PLASTIC ANCHOR - USE IF CONCRETE (HOLE DRILL 1/4"); NOT IF PLASTIC SLAB
(HOLE DRILL 1/8").
COIL
BASE PAN
_J _ Mounting __
STABILIZING MINIMUM 1
l Deck Top
ANGLE
PERS'DE\2 L
'I _:_ 'l'
Remove the Iouvered panels as follows:
1, Remove two screws, allowing the panel to swing open
slightly as illustrated in figure 8,
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated
figure 8, Detail B.
3, Move panel down until lip of upper tab clears the top
slot in corner post as illustrated in figure 8, Detail A.
Position and Install Panel--Position the panel almost parallel with the unit as illustrated in figure 9, Detail D on
page 6 with the screw side as close to the unit as possible, Then, in a continuous motion:
slightly rotate and guide the lip of top tab inward as illustrated in figure 8, Details A and C; then upward into
the top slot of the hinge corner post,
rotate panel to vertical to fully engage all tabs,
holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw
holes,
When panel is correctly positioned and aligned, insert the screws and tighten,
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
Figure 6. Installing Stabilizer Brackets
(Slab Side Mounting)
ROOF MOUNTING
Install unit 6" (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load
bearing wall or area of the roof that can adequately support the unit, Consult local codes for rooftop applications.
If unit cannot be located away from prevailing winter winds, construct a wind barrier sized at least the same height and
width as outdoor unit, Position barrier 24" (610 mm) from
the sides of the unit in direction of prevailing winds as illustrated in figure 7,
prevailing winter winds
r wind barrier I
24"
inlet air ,_ _641'0 mm)
4_ inlet air
inlet al_
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab
is for alignment and not designed to support weight of panel. Panel shown slightly rotated to allow top tab to exit (or enter) top
slot for removing (or installing) panel.
SCREW
{OLES
LIP
Detail
A
Detail
B
iiiiiii+
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE PANEL
O inlet air
Figure 7. Rooftop Application with Wind Barrier
Figure 8. Removing/Installing Louvered Panels
(Details A, B and C)
Page 5
XP14 SERIES
Page 6
MAINTAINMINIMUMPANELANGLE(ASCLOSETOPARALLELWITHTHEUNIT
ASPOSSIBLE)WHILEINSTALLINGPANEL. ANGLEMAYBETOO SIDETOMAINTAIN
EXTREME --_ FULLY_ENGAGEDTABS
PREFERREDANGLE
FORINSTALLATION
Detail D
Figure 9. Removing/Installing Louvered Panels
HOLDDOORFIRMLYTOTHEHINGED
(Detail D)
CAUTION
In the U,S.A.. wiring must conform with current local codes and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC), Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum overcurrent protection size,
1. Install line voltage power supply to unit from a properly sized unit disconnect switch,
2. Ground the unit at the unit disconnect switch or to earth ground.
3. To facilitate conduit, a hole is provided inthe bottom of the control box, Connect conduit to the control box
using a proper conduit fitting,
4. Units are approved for use only with copper conductors. (A complete unit wiring diagram is located inside the unit control box cover.)
LINE VOLTAGE FIELD INSTALLED
WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJU- RY or DEATH, Unit must be grounded in accordance with
national and local codes.
Z,/iXXNOTE - For use with copper conductors only. Refer to unit
rating plate for minimum circuit ampacity and maximum over- current protection size.
Figure 10. Outdoor Unit Typical Field Wiring
NOTE - For proper voltages, select thermostat wire gauge per the following chart:
Table 2. Wire Run Lengths
Wire run length AWG # Insulation type
less than 100' (30m) 18 more than 100' (30m) 16
5. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations,
6. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit, See figures 11 and
12 on page 7,
NOTE - 24V, Class II circuit connections are made in the low voltage junction box,)
color-coded, temperature rating 35°C minimum
,WARNING
505244M 04/08
Page 6
Page 7
Thermostat Indoor Unit Outdoor Unit
24Vpower
common _ L
1st-stage FE
E
_L
......... ©1
1st-stage auxiliary heat (_ I
@1 OI
indoor blower
®1
@comp....... GI
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
Thermostat Indoor Unit Outdoor Unit
. 24V power 24V power
©c ........ 2®-..0 ........
(_. emergency heat i -- -- //_i OUTDOOR
(_). 1st-stage 'auxiliary heat .(_ // 1st-stage
',@ :'-:/- _ EMERGENCY
] I_) _ HEAT RELAY
THERMOSTAT
i
auxiliary h_t-- (_
k@"
indoor blower
reversing valve
®
compressor
G
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
@ @.
® @
Figure 11. Outdoor Unit and Blower Unit Thermostat
Designations
"34O
CI2
CAPAC l TOR
HRI
AIOB
DEFROST CONTROL
;01L _MB )IS
OUT
OPS
f2 OUT
;0M
fl OUT
-PS
if--,
I_f
iv v
C_SSOR CONTACTOR
Figure 12. Outdoor Unit and Blower Unit Thermostat
Designations (with Emergency Heat Relay)
RT21 RTI5
DEFROST AMBIENT
COIL SENSOR
SENSOR
FOR _ WITH COPPER CONDUCTORS ORLY.RERERTO UNIT RATIN6
PLATE FOR ¥INIMII_I CII_IIT
KI
s_r
HI_
PRESSORE
SWITCH
Q
PRESSURE SWITCH
©
AI08 I--
KI
LI
REVERSING
VAL_
®
A_PACITY ANOgAXINUff OVER-
,6_ REFER TO COMPRESSORIN U_IT
CtI_NT RqOTECTION SIZE
OR DEATH.UNIT MI_T B_ OR(X/NOEDIN
m_ SENSOR,OmOOOR_ve (_m_L)
_ITH NATION_. AND LOCALCO_S,
,r=, C831 lily
x_2av
_3)"1
._&,?_-- [.--.__
A2 SIGNATURE
81MZ8
T_ISTED
®-I----
r- -- --
-@-I----
-@-I----
I F----
I
D
I
Ig
I
II
Q-
.IJ
-- --t-- d
--J
@
Figure 13. Typical XP14 Wiring
Page 7
-Jl'
XP14 SERIES
Page 8
A IMPORTANT
If the XP14 unit is being installed with a new indoor coil and line set, the plumbing connections should be made as
outlined in this section. Ifan existing line set and/or indoor coil is going to be used to complete the XP14 system, refer
to the following section that includes flushing procedures. Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-flare) series line sets as shown in table 3 or use
field-fabricated refrigerant lines. Refer to Refrigerant
Piping Guide (Corp. 9351-L9) for proper size, type, and application of field-fabricated lines. Valve sizes are also
listed in table 3.
REFRIGERANT LINE CONNECTIONS - XP14 OUTDOOR UNIT MATCHED WITH NEW INDOOR COIL AND LINE SET
If replacing an existing coil equipped with a liquid line
functioning as a metering orifice, replace the liquid line
prior to installing the XP14 unit. Line sets are described in table 3.
Table 3. Refrigerant Line Sets
Valve Field
Model
-018
-024 (10 mm) (19 mm)
-030
-036
-042 (10 mm) (22 mm)
-048
-060 (10 ram) (29 ram)
Connections
Liquid Vapor Line Line
3/8 in. 3/4 in
3/8 in. 7/8 in
3/8 in, 1-1/8 in.
NOTE - When installing refrigerant lines, refer to Lennox Refrigerant Piping Guide (Corp. 9351-L9) or Lennox
Technical Support Department Product Appficafions Group for assistance. In addition, be sure toconsider the following points:
Recommended Line Set
Liquid Vapor L15 Line Line Line Sets
3/8 in. 3/4 in L15-41 (10 (19 mm) 15 ft, - 50 ft.
mm) (4.6 m - 15 m) 3/8 in. L15-65
(10 7/8 in mm) (22 mm) 15 ft, - 50 ft.
3/8 in, 1-1/8 in. Field (10 (29 mm) Fabricated
mm)
(4.6 m - 15 m)
Select line set diameters from table 3 to ensure that oil returns to the compressor.
Unitsaredesignedforlinesetsofupto50feet(15m); for longer line sets, consult piping guidelines.
Size vertical vapor riser to maintain minimum velocity at minimum capacity.
INSTALLING REFRIGERANT LINE
Pay close attention to line set isolation during installation of
any heat pump or a/c system. When properly isolated from building structures (walls, ceilings, floors), the refrigerant
lines will not create unnecessary vibration and subsequent noises. Also, consider the following when placing and installing a high-efficiency outdoor unit:
1, Placement--Some localities are adopting sound
ordinances based on the unit's noise level observed from the adjacent property, not from the installation property, Install the unit as far as possible from the
property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. Figure 14 shows how to place
the outdoor unit and line set,
Install unit _ \_\
away from //
windows _
zz'.11111III III I IIIrb---.
will reduce line set vibration.
Figure 14. Outside Unit Placement
2. Line Set Isolation--The following illustrations demonstrate procedures which ensure proper refrigerant line set isolation.
Figure 15 on page 9 shows how to install line sets
on horizontal runs.
Figure 16 on page 9 shows how to install line sets
on vertical runs.
Figure 17 on page 10 shows how to make a
transition from horizontal to vertical
505244M 04/08
Page 8
Page 9
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
STRAPPING MATERIAL (Around vapor line only)
8 feet
FLOOR JOIST OR ROOF RAFTER
r\
/ /
METAL FLOOR JOIST OR SLEEVE ROOF RAFTER
TAPE OR WIRE TIE
8 feet WIRE TIE
WIRE TIE
(Around vapor line only)
TAPE OR
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap
the liquid line to the vapor line.
Figure 15. Refrigerant Line Sets: Installing Horizontal Runs
NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.
OUTSIDE WALL IMPORTANT - Refrigerant
lines must not contact wall. VAPOR LINE LIQUIDLINE
IMPORTANT! Refrigerant
lines must not contact
structure.
-_. WIRE TIE INSIDE WALL
- STRAP
SLEEVE
VAPOR LINE WRAPPED
WIRE TIE
_" .---------WOOD BLOCK
.___---- WIRE TIE
STRAP
[_ CAULK
PVC PiPE FIBERGLASS
iNSULATiON
SLEEVE
Figure 16. Refrigerant Line Sets: Installing Vertical Runs (New Construction Shown)
Page 9
XP14 SERIES
Page 10
ANCHORED
HEAVY NYLON
WIRE TIE
AUTOMOTIVE
MUFFLER-TYPE
HANGER
WALL STUD
Strap Liquid Line To Va- Strap Liquid Line
por Line To Vapor Line
UID LINE
METAL VAPOR LINE - WRAPPED METAL VAPOR LINE - WRAPPED
SLEEVE IN ARMAFLEX SLEEVE IN ARMAFLEX
Figure 17. Refrigerant Line Sets: Transition from Vertical to Horizontal
WARNING
BRAZING CONNECTION PROCEDURE
1, Cut ends of the refrigerant lines square (free from
nicks or dents), Debur the ends. The pipe must remain round; do not pinch end of the line.
2, Flow dry nitrogen through the refrigerant piping while
making line set connections; this prevents carbon deposits (oxidation) buildup on the inside of the joints being brazed. Such buildup may restrict refrigerant
flow through screens and metering devices, To do this:
WALL STUD
LIQUID LINE
NOTE - The tube end must stay bottomed in the fitting
I
during final assembly to ensure proper seating, sealing and rigidity,
5. Install a field-provided check expansion valve (approved for use with HFC-410A refrigerant) in the
liquid line at the indoor coil,
XkIMPORTANT
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the Schrader port
connection on the vapor service valve and out of
the Schrader port connection on the liquid service valve. (Metering device (CTXV and RFC) will allow low pressure nitrogen to flow through the
system,) While nitrogen is flowing, braze refrigerant line set
to the indoor and outdoor units, IMPORTANT" The
flow of nitrogen must have an escape path other than through the joint to be brazed.
3. Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing) which are rated for use with HFC-410A refrigerant,
4, Wrap a wet cloth around the valve body and the copper
tube stub to protect it from heat damage during brazing. Wrap another wet cloth underneath the valve body to protect the base paint,
505244M 04/08
kWARNING
Page 10
Page 11
CAUTION
EQUIPMENT REQUIRED FOR FLUSHING LINE SET
The following equipment is required to flush the existing line set and indoor coil:
two clean HCFC-22 recovery cylinders
oilless recovery machine with a pump down feature
gauge set for HCFC-22 refrigerant
gauge set for HFC-410A refrigerant (see Manifold Gauge Set section on page 13),
FLUSHING PROCEDURE
1, Remove existing HCFC-22 refrigerant using the
following, applicable procedure as illustrated in figure
18: If the existing outdoor unit is not equipped with
shut-off valves, or if the unit is not operational AND you plan to use the existing HCFC-22 refrigerant to flush the system -
Disconnect all power to the existing outdoor unit,
Connect to the existing unit, a clean recovery cylinder and the recovery machine according to
the instructions provided with the recovery
machine,
Remove all HCFC-22 refrigerant from the existing
system. Check gauges after shutdown to confirm that the entire system is completely void of
refrigerant.
Disconnect the liquid and vapor lines from the
existing outdoor unit.
If the existing outdoor unit is equipped with manual shut-off valves AND you plan to use NEW HCFC-22 refrigerant to flush the system -
Start the existing HCFC-22 system in the cooling mode and close the liquid line valve.
Pump all of the existing HCFC-22 refrigerant back into the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure
complete refrigerant evacuation.)
When the low side system pressures reach 0psig, close the vapor line valve.
Disconnect all power to the existing outdoor unit. Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the low side of the system.
Disconnect the liquid and vapor lines from the existing outdoor unit,
,
Remove the existing outdoor unit, Set the new HFC-410A unit and follow the Brazing Connection Procedure provided on page 10 to make line set
connections. DO NOT install HFC-410A check/expansion valve at this time.
,
Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit or open the outdoor unit service valves at this
time.
,
Remove the existing HCFC-22 refrigerant flow control orifice or check expansion valve before continuing with flushing procedures. HCFC-22 flow control devices (fixed orifice/check expansion valve) are not approved for use with HFC-410A refrigerant and may prevent proper flushing. Use a field-provided fitting to
reconnect the lines,
IMPORTANT
Inverted HCFC-22 Cylinder
(Contains clean HCFC-22 to be used for flushing)
EXISTING VAPOR LINE
EXISTING LIQUID LINE LIQUID LINE
RECOVERY CYLINDER
VAPOR LINE
SERVICE VALVE
SERVICE VALVE
NOTE - The inverted HCFC-22 cylinder must
Tank ReturnInlet
, Discharge
RECOVERY MACHINE
contain at least the same amount of refrigerant as was recovered from the existing system.
Figure 18. Flushing Connections
Page 11
Low High
Pressure Pressure
Opened ! ! Closed
XP14 SERIES
Page 12
5. Remove the pressure tap valve cores from the XP14 unit's service valves. Connect an HCFC-22 cylinder
with clean refrigerant to the vapor service valve,
Connect the HCFC-22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil.
7. Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system
through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine,
8. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system,
NOTE - A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil, A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil
were removed during the first flush. After each
system flush, allow the recovery machine to pull a vacuum on the system at the end of the
procedure.
9. Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.
10. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the
recovery machine, gauges and HCFC-22 refrigerant drum. Reinstall pressure tap valve cores into XP14
unit's service valves.
11. Install check expansion valve (approved for use with HFC-410A refrigerant) in the liquid line at the indoor
coil.
XP 14 units may be used in check thermal expansion valve (CTXV) systems only. See indoor coil installation
instructions and the Lennox engineering handbook for approved HFC-410A valve match-ups and application
information,
NOTE - HFC-410A systems will not operate properly with an HCFC-22 valve,
Check thermal expansion valves equipped with fittings are available from Lennox, Refer to the Engineering
Handbook for applicable expansion valves for use with specific match-ups, See table 4 for applicable indoor check
expansion valve kits.
Table 4. Indoor Check Expansion Valve Kits
MODEL Kit Number
XP14-018, -024, -030 49L24 XP14-036, -042 49L25 XP14-048, -060 91M02
PATcHTWo(UncaSedpECEpLATECoil Shown) _ - _
(uncased coil ORIFICE I EXPANSION VALVE only) HOUSING
TUBES X
ACCESS FITTIN/ (no valve core) SENSING BULB
On smaller lines, 1/2" & smaller
bo,bmaybe
mounted on top
1 pi'EsNuISalN°(n re qu' red )
I (see no_e)
_ _g
NOTE - If necessary, remove HCFC-22 flow control device
(fixed orifice/check expansion valve) from existing line set before
Do not mount bulb
on bo{tom of line
5/8" & larger suction line
installing HFC-410A approved ex- pansion valve and o-ring.
Figure 19. Metering Device Installation
IMPORTANT
If you install a check thermal expansion valve with an
indoor coil that includes a fixed orifice, remove the orifice before the check expansion valve is installed. See figure
19 for installation of the check expansion valve.
505244M 04/08
Page 12
Page 13
CHECK
EXPANSIONVAL_
LOW HUGH
PRESSUREPRESSURE
DISTRIBUTOR
BIFLOW
FILTE
DRIER OUTDOOR
COIL
OUTDOOR UNiT
REVERSING VALVE
NOTE - ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
INDOOR I
COMPRESSOR
v
NOTE- Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant
lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
Figure 20. XP14 Cooling Cycle (Showing Gauge Manifold Connections)
Manifold gauge sets used with systems charged with HFC-410A refrigerant must be capable of handling the
higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 on the high side and
a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.
The service valves and gauge ports are used for leak testing, evacuating, charging and checking charge. Each
valve is equipped with a service port which has a
factory-installed Schrader valve. A service port cap
protects the Schrader valve from contamination and serves as the primary leak seal.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap. Tighten finger tight, then torque per table 1 on page 3.
To Open Front-Seated Service Valves:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap. Tighten finger tight, then torque per table 1on page 3.
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension (3/16" for liquidqine valve sizes; 5/16" for vapor-line
valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly.
Vapor Line Ball Valve
VAPOR
SERVICE .INE
POR_ /ALVE
/APOR
CHECK EXPANSION VALVE --
VAPOR
SERVICE
PORT
ilhd II
:ll--
INDOOR
COIL
3. Replace the stem cap. Tighten finger tight, then torque per table 1 on page 3.
SCHRADER CAP
VALVE ]OPEN TO
LINE SET WHEN
VALVE IS CLOSED ",LLJ
]FRONT SEATED)] _
OUT- DOOR
COl
SERVICE PORT CAP
Valve in closed position
STEM INSERT HEX
WRENCH HERE,
/
_VALVE FRONT-SEATED)
Valve in open position
Figure 21. Front-Seated Liquid Line Valve
Ball-type service valves as illustrated in figure 22 function the same way as the other valves but cannot be rebuilt; if
one fails, replace with a new valve. The ball valve is equipped with a service port with a factory-installed Schrader valve. A service port cap protects the Schrader
valve from contamination and assures a leak-free seal.
CAP
USE ADJUSTABLE WRENC
TO OPEN: ROTATE STEM _STEM COUNTER-CLOCKWISE 90 °.
TO CLOSE: ROTATE STEM CLOCKWISE 90° .
TO INDOO
R COIL SERVICE
STEM
SERVICE PORT
(_SCHRADER VALVE
TO OUTDOOR
COIL
BALL (SHOWN
PORT CAP
Figure 22. Bali-Type Vapor Valve (Valve Closed)
Page 13
XP14 SERIES
Page 14
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor unit for leaks.
WARNING
, WARNING [
pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage,)
.
Adjust dry nitrogen pressure to 150 psig (1034 kPa), Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
7,
After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge dry nitrogen and
HFC-410A mixture. Correct any leaks and recheck.
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping and compressor parts.
IMPORTANT
WARNING
USING AN ELECTRONIC LEAK DETECTOR
IMPORTANT
1. Connect a cylinder of HFC-410A to the center port of the manifold gauge set,
2. With both manifold valves closed, connect the cylinder of HFC-410A refrigerant, Open the valve on the HFC-410A cylinder (vapor only),
3. Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit, Weigh in a trace amount of HFC-410A. [A trace amount is a
maximum of 2 ounces (57 g) refrigerant or 3 pounds (31 kPa) pressure]. Close the valve on the HFC-410A
cylinder and the valve on the high pressure side of the manifold gauge set, Disconnect HFC-410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold
gauge set,
5. Connect the manifold gauge set high pressure hose to the vapor valve service port, (Normally, the high
I
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set,
4. Open both manifold valves; start thevacuum pump,
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of
mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure, A rapid rise in pressure indicates a
relatively large leak, If this occurs, repeat the leak testing procedure,
NOTE - The term absolute pressure means the total actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric
pressure minus vacuum pressure,
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen
cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor unit, Close the manifold gauge valves.
505244M 04/08
Page 14
Page 15
Xk WARNING
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the dry nitrogen from
the line set and indoor unit,
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HFC-410A refrigerant, Open the manifold gauge
valves to break the vacuum from 1 to 2 psig positive
pressure in the line set and indoor unit, Close manifold
gauge valves and shut off the HFC-410A cylinder and
remove the manifold gauge set,
power company has been consulted and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to indoor blower unit and close the outdoor unit
disconnect to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
A IMPORTANT
This system is charged with HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The recommended check expansion valve is approved for use
with HFC-410A. Do not replace it with a valve that is
designed to be used with HCFC-22. This unit is NOT approved for use with coils that include metering orifices or capillary tubes,
Units are factory-charged with the amount of HFC-410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15ft. (4,6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment, A blank space is provided on the unit rating plate to list the actual field charge.
IMPORTANT
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory- and field-installed wiring for loose connections,
NOTE - After the system has been evacuated and before completing all the remaining start-up steps, this is the ideal time to adjust the amount of refrigerant made necessary by line set length difference and by the specific indoor unit match-up, Skip to the paragraph "Setup for Checking and
Adding Charge" on page 16 to setup for charging and for
determining if charge is needed; adjust the charge accordingly
3. Open the liquid line and vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system,
4. Replace stem caps and secure finger tight, then tighten an additional (1/6) one-sixth of a turn,
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
A IMPORTANT
NOTE - Be sure that filters and indoor and outdoor coils are clean before testing,
COOLING MODE INDOOR AIRFLOW CHECK Check airflow using the Delta-T (DT) process (figure 23). HEATING MODE INDOOR AIRFLOW CHECK Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:
temperature rise between the return air and supply air temperatures at the indoor coil blower unit,
voltage supplied to the unit,
amperage being drawn by the heat unit(s),
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Check indoor airflow using the step procedures as illustrated in figure 23.
Amps x Voltsx 3.41
1.08x Temperature rise (F)
Page 15
XP14 SERIES
Page 16
Temp. ] DT
ofair 180 24 24 24 23 23 22 22 22 20 19 18 17 16 15 entering._178 23 23 23 22 22 21 21 20 19 18 17 16 15 14
indoor _ I _ coilOF _lru 22 22 22 21 21 20 19 19 18 17 16 15 14 13
I _'174 21 21 21 20 19 19 18 17 16 16 15 14 13 12 _[72 20 20 19 18 17 17 16Z_15 14 13 12 11 10
Wet-bulb°F 57 58 59 60 61 62 63 64 65 66 67 68 69 70 ]
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
m
DRY
BULB
9o
All temperatures are INDOOR WET expressed in °F COIL BULB
Figure 23. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart
SETUP FOR CHARGING Connect the manifold gauge set to the unit's service ports
(see figure 20):
low pressure gauge to vapor service port
high pressure gauge to liquid service port Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC-410A,
_6
Step 1. Determine the desired DT--Measure entering air tempera- ture using dry bulb (A) and wet bulb (B) DT is the intersecting value of A and B inthe table (see triangle)
Step 2. Find temperature drop across ceil--Measure the coil's dry
bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (TDrop) = A minus C.
Step 3. Determine if fan needs adjustment--If the difference be- tween the measured TDrop and the desired DT (TDropiDT) is within
+3°, no adjustment is needed. See examples: Assume DT = 15 and A temp. =72 °, these C temperatures would necessitate stated actions:
C° TDrop- DT = °F ACTION
53° 19 15 = 4 Increase the airflow 58° 14 15 = -1 (within +3 ° range) no change
62° 10 15 = -5 Decrease the airflow Step 4. Adjust the fan speed--See indoor unit instructions to in-
crease/decrease fan speed
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3 °.
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the unit, To calculate the total refrigerant charge:
Amount Adjust amt. for Additional charge specified variation in specified per
on line set length indoor unit match-up Total nameplate (table 6) (table 7) charge
+ + =
505244M 04/08
Page 16
Page 17
IMPORTANT
Table 5. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG* (Cooling)
XP14-018 XP14-024 XP14-030 XP14-036 XP14-042 XP14-048 XP14-060
Liquid/ Liquid/ Liquid/ Liquid/ Liquid/ Liquid/ Liquid/
°F (°C)** Vapor Vapor Vapor Vapor Vapor Vapor Vapor
Heating
60 (15) 346 / 139 352 / 138 338 / 137 350 / 134 373 / 139 355 / 130 351 / 117 50 (10) 323 / 117 331 / 114 334 / 112 331 / 117 363 / 117 336 / 113 333 / 105
40 (4) 306 / 98 304 / 99 312 / 93 313 / 97 348 / 97 315 / 88 316 / 88 30 (-1) 278 / 84 299 / 80 302 / 74 298 / 83 336 / 74 296 / 72 308 / 70 20 (-7) 273 / 66 283 / 66 280 / 53 284 / 66 322 / 64 286 / 64 300 / 61
Cooling
65 (18) 226 / 140 233 / 137 238 / 138 220 / 138 223 / 125 231 / 136 243 / 136 70 (21) 244 / 141 252 / 138 263 / 139 236 / 140 241 / 130 248 / 139 263 / 137 75 (24) 263 / 142 271 / 140 279 / 139 256 / 141 261 / 134 271 / 140 282 / 138 80 (27) 283 / 143 292 / 141 299 / 140 276 / 142 282 / 138 291 / 142 306 / 139 85 (29) 302 / 144 314 / 142 324 / 141 298 / 143 302 / 139 312 / 143 327 / 140 90 (32) 328 / 145 338 / 143 340 / 142 321 / 144 326 / 140 335 / 144 351 / 141 95 (35) 351 / 146 361 / 145 375 / 145 344 / 144 349 / 141 359 / 145 376 / 142
100 (38) 376 / 147 387 / 146 397 / 145 369 / 146 374 / 142 384 / 146 401 / 143 105 (41) 402 / 148 412 / 147 424 / 147 394 / 147 399 / 143 411 / 148 426 / 145 110 (38) 430 / 149 441 / 148 454 / 150 421 / 148 428 / 145 439 / 149 452 / 146 115 (45) 465 / 150 471 / 151 485 / 150 449 / 149 455 / 146 468 / 150 484 / 148
*IMPORTANT--These are most popular match-up pressures. Indoor match up, indoor air quality, and indoor
load cause pressures to vary.
**Temperature of the air entering the outside coil.
1. Recover the refrigerant from the unit,
2. Conduct leak check; evacuate as previously outlined, 3, Weigh in the unit nameplate charge plus any charge
required for line set differences from 15 feet and any
extra indoor unit match-up amount per table 7, (If weighing facilities are not available, use the
subcooling method,)
Table 6. Charge per Line Set Lengths
Liquid Line Oz. per 5 ft. (g per 1.5m) adjust from
Set Diameter 15 ft. (4.6m) lineset*
3/8 in. (9.5mm) 3 ounce per 5 ft. (85g per 1.5m) NOTE - *if line length is greater than 15 ft. (4.6 m), add this amount, If
line length is less than 15 ft. (4.6 m), subtract this amount.
Requirements--these items are required for charging:
Manifold gauge set connected to unit.
Thermometers for measuring outdoor ambient, liquid line, and vapor line temperatures,
When to use cooling mode--When outdoor
temperature is 60°F (15°C) and above, use cooling mode to adjust charge,
When to use heating mode--When the outdoor
temperature is below 60°F (15°C), use the heating mode to adjust the charge,
Adding Charge for Indoor Match-Up--Table 7 lists all
the Lennox recommended indoor unit matches along with the charge levels for the various sizes of outdoor units,
Page 17
XP14 SERIES
Page 18
Table 7. Adding Charge per Indoor Unit Match using Subcooling Method
Use
!___ ___ cooling
mode
_ 60°F (15°C) -
+use
_I heating
mode
1 Check the airflow as illustrated in figure 23 on page 16 to be sure the indoor airflow is as
required. (Make any air flow adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or
heating mode to check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating
Pressures table 5, (Table 5 is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem. )
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling mode--When the outdoor ambient temperature is 60°F (15°C) and above.
Target subcooling values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68°F (20°C). When pressures have stabilized,
continue with step 6.
Using heating mode--When the outdoor ambient temperature is below 60°F (15°C). Target subcooling values in table below are based on 65-75°F (18-24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set
thermostat to heating mode setpoint to 77°F (25°C). When pressures have stabilized, continue with step 6.
9 Compare SC° results with table below, being sure to note any additional charge for line
set and/or match-up.
10 If subcooling value is greater than shown in table, remove refrigerant; if less than shown,
add refrigerant.
11 If refrigerant is added or removed, repeat steps 5
INDOOR HEAT Cooling Heating
Subcool Target
MATCH-UP:,..O.,.PUMPI +°F1I I°F1
CBX27UH-018/024 13 7 CBX32MV-018/024 15 7
CH23-41 16 8 0 2 CBX26UH-024 25 7 0 0 CBX26UH-036 26 5
CBX27UH-018/024 15 8 1 2 CBX26UH-037 25 4 CBX32M-018/024 16 8 0 14 CBX27UH-036 13 6 CBX32M-030 15 8 1 3 CBX32M-036 13 6
CBX32MV-018/024 16 8 0 14 CBX32M-042 13 6 CBX32MV-024/030 15 8 1 2 CBX32MV-036 13 6 CH33-42B 14 11 1 10 CBX32MV-048 11 8 CH33-36A 16 8 1 0 C33-44C 13 6 CH33-36C 16 8 0 4 CH33-50/60C 11 8
CR33-30/36A/B/C 25 7 0 2 CH33-44B 13 6 CX34-25A/B 16 8 0 14 CH33-48B 13 6 CX34-31A/B 15 8 1 3 CR33-50/60C 25 4 CX34-36A/B/C 16 8 1 8 CR33-48B/C 25 5
CX34-38A/B 14 11 2 2 CX34-49C 13 6
CH23-41 11 6 0 8 CX34-38A/B, -44/48C 13 6 0H23-51 6 6 112 _II
CBX26UH-024 30 8 0 6 CH23-68 20 9 CBX26UH-030 29 8 2 3 CBX26UH-042 27 6
CBX27UH-030 11 6 2 4 CBX27UH-042 12 6 CBX32M-030 11 6 1 6 CBX32M-048 12 6 CBX32M-036 11 6 2 4 CBX32MV-048 12 6 CBX32MV-024/030 11 6 1 6 CH33-62D 12 6
CBX32MV-036 11 6 2 4 CH33-50/60C 12 6 C33-44C 11 6 2 3 CH33-60D 12 6 CH33-36C 11 3 0 0 CR33-50/60C,-60D 26 6 CH33-42B 6 6 1 12 CBX33-042,-048 12 7
CR33-30/36A/B/C 30 8 0 8 CBX33-060 12 6 *Add charge = Extra match-up amount required in addition to charge indicated on Heat Pump nameplate
ences from 15 feet).
*Add
charge
+
o 8 o o
INDOOR HEAT Cooling Heating
MATCH-UPPO+
CX34-31A/B 11 6 CX34-38A/B 11 6 CX34-43B/C 15 11
CX34-43B/C, -50/60C 13 6
Subcool Target
I I ll'3,+"I I I llm=.)
through 10 to verify charge.
*Add INDOOR HEAT Cooling Heating *Add
charge MATCH-UP PUMP I±5°F1 Ill°F1 charge
1 6 CX34-62C, -62D 12 6 0 9 2 3 CX34-49C 12 6 0 7
2 14 CX34-60D 12 6 0 4
0 0 CH23-68 20 9 2 9 1 9 CBX26UH-048 8 7 1 9 0 3 CBX27UH-048 11 8 1 2 0 2 CBX32M-048,-060 11 8 1 2 0 3 CBX32MV-048, -060 11 8 1 2
0 3 CBX32MV-068 10 7 1 12 2 5 CH33-50/60C 11 8 1 1 0 0 CH33-62D 10 7 1 14 2 5 CH33-60D 11 8 0 0
1 7 CR33-50/60C 35 5 0 0 1 8 CR33-60D 37 6 0 0 1 15 CBX33-048, -060 12 8 1 2 0 9 CX34-62C, -62D 10 7 1 7
2 4 CX34-49D 11 8 0 14 1 8 CX34-60D 11 8 0 0
CH23-68 12 5 0 0
0 13 CBX26UH-048 12 7 1 0 0 0 CBX26UH-060 14 4 0 0
0 8 CBX27UH-060 12 5 0 0 0 7 CBX32M-048,-060 12 5 0 0 0 8 CBX32MV-048, -060 12 5 0 0 0 10 CBX32MV-068 12 7 1 0
0 7 CH33-50/60C 12 5 0 0 0 4 CH33-62D 12 5 0 0 0 4 CBX33-060 12 8 0 0 0 4 CX34-62C,-62D 12 7 1 0
0 7
(remember to also add any charge required for line set differ-
Subcool Target
I ll_ [,+Immmm
505244M 04/08
Page 18
Page 19
Table 8. HFC-410A Temp. (°F) - Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
SERVICE LIGHT OPERATION The thermostat is not included with the unit and must be
purchased separately. Some outdoor thermostats incorporate isolating contacts and an emergency heat
function (which includes an amber indicating light), The
service light thermostat will enable the emergency heat light function on the room thermostat,
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and
field-provided relays bypass the outdoor thermostats. An
amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat
mode. Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power outage if power has been off for over an hour and the
outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to
allow the crankcase heater sufficient time to prevent compressor slugging,
FILTER DRIER The unit is equipped with a large-capacity biflow filter drier
which keeps the system clean and dry, If replacement is
necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC-410A refrigerant,
DEFROST CONTROL BOARD Figure 24 provides a basic illustration of the layout of the
defrost control board. Table 9 provides information concerning pin-out and jumper configurations,
DEFROST SYSTEM DESCRIPTION The demand defrost controller measures differential temperatures to detect when the system is performing
poorly because of ice build-up on the outdoor coil, The controller self-calibrates when the defrost system starts and after each system defrost cycle. The defrost control
board components are shown in figure 24, The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE - The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
Page 19
Note - Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION -
PIN SETTINGS
SENSOR PLUG IN
(COIL, AMBIENT, -
& DISCHARGE
SENSORS)
DELAY
REVERSING
VALVE
PRESSURE
SWITCH CIRCUIT _
CONNECTIONS
PINS
IT'_pI
_ O FAR
0
= I]
0 o#t
o
.o-PS
COMMON
©
Iololololo1_1olol 0
TSTPS Df C _ 0 YI Y2
®
Z @c
@L
o
LOW
AMBIENT
THERMOSTAT PINS
_ DIAGNOSTIC
LEDS
24V TERMINAL STRIP
CONNECTIONS
Figure 24. Defrost Control Board
XP14 SERIES
Page 20
Table 9. Defrost Control Board Description
ID Description
O Out 24 VAC output connection for reversing valve
LO-PS Connection for low-pressure switch
Y2 24 VAC output for second stage compressor solenoid Y1 24 VAC common output, switched for enabling compressor
HI-PS Connection for high-pressure switch P1 Seven position square pin header. P1 provides selection of
P2 The following connections are provided in the seven posi-
P3 Five position square pin header. P3 provides selection of
P4 Six position square pin header. P4 provides connections for
P5 Two position square pin header. P5 provides selection of
P6 Eight position header. P6 provides connections for the fac-
contactor
the defrost terminate temperature based on the position of selection shunt, as well as selection pins for enabling the
field test mode.
tion P2 screw terminal block: Wl 24 VAC thermostat output for auxiliary heat op-
C 24 VAC system common L Service light thermostat connection
R 24 VAC system power input Y2 24 VAC thermostat input for second stage com-
O 24 VAC thermostat input for reversing valve op-
Y1 24 VAC thermostat input for first stage compres-
the Y2 compressor lock-in temperature. Note: This is ap-
plicable for two stage compressor operations only.
the temperature sensors: COIL (P4-5) Ground connection for outdoor coil tem-
AMB (P4-3) Ground connection for outdoor ambient
DIS (P4-1) Ground connection for discharge temper-
the 30-second compressor delay option.
tory test connections.
eration
pressor operation
eration
sor operation
perature sensor. (P4-6) Connection for outdoor coil temperature
sensor
temperature sensor.
(P4-4) Connection for outdoor ambient tempera-
ture sensor.
ature sensor.
(P4-2) Connection for discharge temperature sensor. Note: This is applicable for two stage compressor operations only.
Test: Defrost Temperature Termination Shunt (Jumper) Pins--The defrost board selections are: 50, 70,
90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the
temperature shunt is not installed, the default termination temperature is g0°F (32°C).
Note: The Y1 input must be active (ON) and the "0" room thermostat terminal into board must be inactive.
DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics
conditions that are described in table 10.
DELAY MODE
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling
in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30
seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins. DEFROST BOARD PRESSURE SWITCH
CONNECTIONS The unit's automatic reset pressure switches (LOPS - $87
and Ht PS - $4) are factory-wired into the defrost board on the LO-PS and Ht-PS terminals, respectively.
Low Pressure Switch (LO-PS) When the low pressure switch trips, the defrost board will
cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is
ignored under the following conditions:
during the defrost cycle and 90 seconds after the termination of defrost
when the average ambient sensor temperature is below
15° F (-9°C)
for 90 seconds following the start up of the compressor
during test mode
High Pressure Switch (HI-PS)
When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the
board will count one strike.
DEFROST BOARD PRESSURE SWITCH SETTINGS
High Pressure (auto reset) - trip at 590 psig; reset at
418 psig.
Low Pressure (auto reset) - trip at 25 psig; reset at 55
psig.
Low Ambient Thermostat Pins - P3 provides selection of
the Y2 compressor lock-in temperature. The XP14 series heat pumps do not use a Y2 compressor and therefore
these pins are not active.
FIVE-STRIKE LOCKOUT FEATURE
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a
pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip
counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The five-strike pressure switch lockout condition can be reset by cycling OFF the 24*volt power to the control board
or by shorting the TEST pins between 1 and 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is
engaged, a 5-minute short cycle will occur after the switch closes.
505244M 04/08
Page 20
Page 21
Actuation--When the reversing valve is de-energized,
the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time.
If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time.
The control will attempt to self-calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system temperatures during the 20-minute calibration period. If
the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run
time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the
maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been
logged since the last defrost cycle.
NOTE - If ambient or coil fault is detected, the board willnot execute the TEST mode.
Termination--The defrost cycle ends when the coil temperature exceeds the termination temperature or after
Y1 Active ('O"line inactive) ]
Short test pins for longer than 1 second but less than 2 seconds
14 minutes of defrost operation. If the defrost is terminated
by the 14-minute timer, another defrost cycle will be initiated after 34 minutes of run time.
Each test pin shorting will result in one test event. For each TEST the shunt (jumper) must be removed for at
least one second and reapplied. Refer to flow chart as illustrated in figure 25 for TEST operation.
Test Mode--When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by
placing the termination temperature jumper across the TEST pins for two to five seconds. If the jumper remains
across the TEST pins longer than five seconds, the control
will ignore the TEST pins and revert to normal operation.
The jumper will initiate one cycle per test. Enter the TEST mode by placing a shunt (jumper) across
the TEST pins on the board after power-up. The TEST pins are ignored and the test function is locked out if the
shunt is applied on the TEST pins before power-up. Board timings are reduced, the low-pressure switch is ignored
and the board will clear any active lockout condition.
NOTE - The 30-second off cycle is NOT functional when
jumpering the TEST pins.
I
i
Short test pins for more than 2 seconds
Clear any short cycle lockout and
5 strike fault lockout function, if applicable. No other functions will
be executed and unit will continue in the mode it was operating.
Test pin short REMAINS in place for more than 5 seconds / Test short REMOVED before maximum
The unit will return to Heat mode un-calibrated with defrost timer set for I 34 minutes. No further test mode operation will be executed until the test The unit will remain in Defrost mode until
short s removed and re apped, j termination on time or temperature
IIf in COOLING Mode
No further test mode operation will be executed
until the test short is removed and reapp ed.
Figure 25. Test Mode
Clear any short cycle lockout and 5 strike fault lockout
function, if applicable.
IIIfin Mode IIIfin Mode
The controller will check for ambient and coil faults (open or shorted). If a
fault exists, the unitwill remain in Heat
Mode and no further test mode
operation will be executed until the test short is removed and re applied. If
no fault exists the unit will go into Defrost mode.
pins
of 5 seconds
The unit will terminate defrost and enter Heat Mode un-calibratedwith defrost timer set for 34 minute test. No
further test mode operation will be executed until the test short
is removed and reapplied.
a
Page 21
XP14 SERIES
Page 22
DEFROST BOARD DIAGNOSTICS
See table 10 to determine defrost board operational conditions and to diagnose cause and solution to problems.
Table 10. Defrost Control Board Diagnostic LEDs
DS2 DSl Green Red
OFF OFF Power problem and C or board failure.
Simultaneous Unit operating normally or in standby SLOW Flash Normal operation mode. None required.
Alternating SLOW 5-minute anti-short cycle Initial power up, safety trip, end of
Flash delay room thermostat demand.
Simultaneous Sensor being detected open or shorted or out of temperature range. Board will revert to time/
FAST Flash Ambient Sensor Problem temperature defrost operation. (System will still heat or cool).
Alternating Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform
FAST Flash demand or time/temperature defrost operation. (System will still heat or cool).
Condition/Code Possible Cause(s) Solution
1 Check control transformer power (24V).
No power (24V) to board terminals R 2 If power is available to board and LED(s) do not
light, replace board.
None required (Jumper TEST pins to override)
ON Circuit Board Failure not clear, replace board.
ON Indicates that board has internal component failure. Cycle 24 volt power to board. If code does
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
OFF Low Pressure Fault
OFF ON Low Pressure LOCKOUT
SLOW Flash
1 Restricted air flow over indoor or
outdoor coil.
2 Improper refrigerant charge in
system,
3 Improper metering device installed or
SLOW
Flash OFF High Pressure Fault
incorrect operation of metering
device,
4 Incorrect or improper sensor location
ON OFF High Pressure LOCKOUT
SLOW Discharge Line Temperature
Flash ON Fault
FAST Discharge Line Temperature Flash ON LOCKOUT
OFF across pins P4-1 and P4-2. If the resistor is missing or damage then this fault code will be
Fast Flash This model does not have a defrost line sensor, therefore this code is not applicable.
Fast Flash Discharge Sensor Fault
OFF Discharge Sensor
LOCKOUT
or connection to system.
This model does not have a defrost line sensor, therefore this code is not applicable.
The XP14 series units does not use a defrost line sensor, However, a resistor is installed
displayed.
1 Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for proper current draws.
2 Check system charge using approach and subcool-
ing temperatures,
3 Check system operating pressures and compare to
unit charging charts.
4 Make sure all pressure switches and sensors have
secure connections to system to prevent refrigerant leaks or errors in pressure and temperature mea-
surements.
Table 11. Sensor Temperature/Resistance Range
Sensor Temperature Range °F (°C) Resistance Values Range (ohms) Pins/Wire Color Outdoor (Ambient) -35 to 120 (-37) to (48) 280,000 to 3750 3 and 4 (Black)
Coil -35 to 120 (-37) to (48) 280,000 to 3750 5 and 6 (Brown) Note: Sensor resistance decreases as sensed temperature increases (see figure 26).
lOO
90 8o
70 | 11775
60 |B 15425
50 _119975
30 [] 34375
w
20 m46275
10 62700 85300
o I I
505244M 04/08
5750
m, 7450
i
26200
III
10000 30000 50000 70000 90000
RESISTANCE(OHMS)
Figure 26. Ambient and Coil Sensors
Page 22
Page 23
DEFROST BOARD DEFROST
SENSOR
HARNESS
Figure 27. Sensor Locations
Ambient Sensor--The ambient sensor (shown in figure
27) considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the ambient sensor is
detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand
defrost operation. The board will revert to time/temperature defrost operation and will display the
appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Coil Sensor--The coil temperature sensor (shown in
figure 27) considers outdoor temperatures below -35°F
(-37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or
out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost
operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault
condition.
OPERATIONAL DESCRIPTION
The defrost control board has three basic operational modes: normal, calibration, and defrost.
Normal Mode--The demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil
temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
050 APPLY GREASE BETWEEN RETURN BEND AND SENSOR
CLIP COIL TEMPSENSORFROM
THE DEFROSTBOARDON THE HAIRPIN SHOWN.6fh HAIRPIN
UP ON INSIDE ROW. WIRES
ROUTED DOWN
Calibration Mode--The board is considered uncalibrated
when power is applied to the board, after cool mode
operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor
are measured to establish the temperature differential
which is required to allow a defrost cycle.
Defrost Mode--The following paragraphs provide a detailed description of the defrost system operation.
DETAILED DEFROST SYSTEM OPERATION Defrost Cycles--The demand defrost control board
initiates a defrost cycle based on either frost detection or time,
Frost Detection--If the compressor runs longer than 34 minutes and the actual difference between the clear
coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost
cycle will be initiated,
IMPORTANT - The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost
system.
Time--If six hours of heating mode compressor run time has elapsed since the last defrost cycle while the
Page 23
XP14 SERIES
Page 24
coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
2, Disposable Filter--Disposable filters should be
replaced with a filter of the same type and size,
NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
,WARNING I
Before the start of each heating and cooling season, the
following service checks should be performed by a
qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose.
NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with units operating).
Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
Check the refrigerant charge and gauge the system pressures.
Check the condensate drain line for free and unobstructed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM
Refer tothe unit information service manual for pressure drop tables and procedure.
NOTE - if owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this
instruction.
MAINTENANCE
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter--Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
IMPORTANT
3, Reusable Filter--Many indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or grille.
NOTE - The filter and all access panels must be in place any time the unit is in operation.
4, Electronic Air Cleaner--Some systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate
formed as your system removes humidity from the inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. This would also apply to an auxiliary drain, if installed.
A IMPORTANT
. Outdoor Unit--Make sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which
collects around the unit. When removing debris from around the unit, be aware
of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury.
Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system.
505244M 04/08
Page 24
Page 25
HEAT PUMP OPERATION Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space, This is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space,
Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost,
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand: however, the unit will return to normal operation at the
conclusion of the defrost cycle,
In case of extended power outage...
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant
slugging during cold weather operation, If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the Emergency Heat setting to obtain temporary heat without
the risk of serious damage to the heat pump, tn Emergency Heat mode, all heating demand is satisfied
by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the
thermostat can be switched to the Heat setting and normal heat pump operation may resume,
THERMOSTAT OPERATIONS Though your thermostat may vary somewhat from the
description below, its operation will be similar. Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the
levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature
adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is
required when constant air circulation or filtering is desired,
System Switch Set the system switch for heating, cooling or auto
operation, The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to
maintain predetermined comfort settings, Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and
provides temporary heat supplied by the auxiliary heat, Indicating Light Most heat pump thermostats have an amber light which
indicates when the heat pump is operating in the emergency heat mode,
Temperature Indicator The temperature indicator displays the actual room
temperature, Programmable Thermostats Your Lennox system may be controlled by a
programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for
both heating and cooling, Refer to the user's information manual provided with your particular thermostat for operation details. Preservice Check
If your system fails to operate, check the following before calling for service:
Check to see that all electrical disconnect switches are ON.
Make sure the room thermostat temperature selector is properly set.
Make sure the room thermostat system switch is properly set.
Replace any blown fuses, or reset circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean,
Identify the unit model number before calling,
OPTIONAL ACCESSORIES Refer to the Engineering Handbook for optional
accessories that may apply to this unit, The following may or may not apply:
Loss of charge kit
High pressure switch kit
Mild weather kit
Compressor monitor
Compressor crankcase heater
Mounting bases
Timed off control
Stand-off kit
Sound cover
Low ambient kit
Monitor kit
SignatureStat'" room thermostat
Page 25
XP14 SERIES
Page 26
Job Name
Job no.
Date
Job Location Installer
Unit Model No,
Serial No.
Nameplate Voltage Rated Load Ampacity
Compressor Amperage:
Maximum Fuse or Circuit Breaker Electrical Connections Tight? _1
Indoor Filter clean? _1
Indoor Blower RPM __ S.P. Drop Over Indoor (Dry) Vapor Pressure;
Refrigerant Lines: - Leak Checked? Service Valves: --- Fully Opened? _]
Properly Insulated?
Caps Tight? _]
SEQUENCE OF OPERATION
Heating Correct?
Cooling Correct?
City City
State State
Service Technician
Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp.
Outdoor Fan Checked?
Voltage With Compressor Operating
THERMOSTAT
Calibrated? _ Properly Set? _ Level?
505244M 04/08
Page 26
Loading...