Improper installation, adjustment, alteration,
service or maintenance can cause personal injury,
loss of life, or damage to property.
Installation and service must be performed by a
qualified installer or service agency.
CAUTION
Physical contact with metal edges and corners
while applying excessive force or rapid motion can
result in personal injury. Be aware of, and use
caution when working near these areas during
installation or while servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFCs, HFCs, and HCFCs) as
of July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for
noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook.
Coils previously charged with HCFC−22 must be
flushed.
The XP14 outdoor unit uses HFC−410A HFC refrigerant.
This unit must be installed with a matching indoor blower
coil and line set as outlined in the Lennox Engineering
Handbook. Elite® Series XP14 outdoor units are designed
for use in check expansion valve (CTXV) systems only and
are not to be used with other refrigerant flow control
devices. An expansion valve approved for use with
HFC−410A must be ordered separately and installed prior
to operating the unit.
Shipping and Packing List
1 − Assembled XP14 outdoor unit
Check the unit components for shipping damage. If you
find any damage, immediately contact the last carrier.
Litho U.S.A.
03/10505,244M
*2P0310**P505244M*
Page 1
Page 2
Unit Dimensions − Inches (mm) and Parts Arrangement
RUN
CAPACITOR
DEFROST
BOARD
CONTACTOR
REVERSING
VALV E
FILTER DRIER/
LIQUID LINE
CONNECTIONS
TOP VIEW
C
DISCHARGE AIR
SUCTION LINE
CONNECTION
LIQUID LINE
CONNECTION
LIQUID LINE
CONNECTION
ELECTRICAL
INLETS
VAPOR LINE
CONNECTION
108)
4−3/4
(121)
4−1/4(
PARTS ARRANGEMENT
A
2 (51)
OUTDOOR FAN
COMPRESSOR
HIGH PRESSURE
SWITCH
VAPOR LINE
VAPOR VALVE AND
GAUGE PORT/SUCTION
LINE CONNECTIONS
B
SIDE VIEW
UNIT SUPPORT
FEET
8−1/2
(216)
8−3/4
(222)
5−1/2
(140)
13−1/2
(343)
XP14−018 TO −030 BASE SECTION
9−1/2
(241)
8−1/4
(210)
UNIT SUPPORT
FEET
16−7/8
(429)
8−3/4
(222)
3−1/8
(79)
1 (25)
XP14−036 TO −060 BASE WITH
ELONGATED LEGS
Model No.ABC
XP14−01831 (787)27 (686)28 (711)
XP14−02431 (787)27 (686)28 (711)
XP14−03035 (889)27 (686)28 (711)
XP14−03631 (787)35 1/2 (902)39 1/2 (1003)
XP14−04239 (991)35 1/2 (902)39 1/2 (1003)
XP14−04839 (991)35 1/2 (902)39 1/2 (1003)
XP14−06045 (1143)35 1/2 (902)39 1/2 (1003)
SIDE VIEW
30−3/4
(781)
26−7/8
(683)
3−3/4
(95)
4−5/8
(117)
505244M 10/09
Page 2
Page 3
WARNING
Product contains fiberglass wool.
Disturbing the insulation of this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is know to the State of
California to cause cancer.) Fiberglass wool may
also cause respiratory, skin and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address show below, or contact your
supervisor.
Lennox Industries Inc., PO Box 79011, Dallas, TX
75379−9011
General Information
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
Table 1. Torque Requirements
PartRecommended Torque
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #816 in.− lb.2 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
4. Locate the unit so prevailing winter winds will not blow
into the coil.
5. Locate unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil
or into unit.
See NOTES
See
NOTES
See NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on
one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914
mm)
Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between
two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
Control
Box
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
Outdoor units operate under a wide range of weather
conditions; therefore, several factors must be considered
when positioning the outdoor unit.
Position the unit to allow adequate airflow and servicing
clearance. Maintain a minimum clearance of 24 inches
(610 mm) between multiple units as illustrated in figure 1
for installation clearances.
1. Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or
position that will transmit sound or vibration to the
living area or adjacent buildings.
2. Install the unit high enough above ground or roof to
allow adequate drainage of defrost water and prevent
ice build-up.
3. In heavy snow areas, do not locate unit the where
snowdrifts will likely build. The unit base should be
elevated above the depth of average snows.
NOTE - Elevation of the unit may be accomplished by
constructing a frame using suitable materials. If a
support frame is constructed, it must not block drain
holes in unit base.
Figure 1. Installation Clearances
SLAB MOUNTING
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance away from the building of 2
degrees or 2 inches per 5 feet (50 mm per 1500 mm) to
prevent ice build-up under the unit during a defrost cycle.
NOTE − If necessary for stability, anchor unit to slab as
described in Stabilizing Unit on Uneven Surfaces on page
4.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE
TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET
[50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING
STRUCTURE
MOUNTING
SLAB
GROUND LEVEL
Figure 2. Slab Mounting Options
Page 3
XP14 SERIES
Page 4
ELEVATING THE UNIT (SMALL−BASE UNITS)
If additional elevation is necessary, raise the unit by
extending the length of the unit support feet. This may be
done by cutting four equal true−cut lengths of Schedule
(SCH) 40, 4" (101.6mm) piping to the height required as
illustrated in figure 3.
NOTE − Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is
approximately 0.25" (6.35mm) greater than the
pre−installed feet on the unit. Devise a shim that will take up
the space and hold the extenders onto the feet during this
procedure. Small strips of 0.125" (3.175mm) thick
adhesive foam may be used. One or two small 1"
(25.4mm) square strips should be adequate to hold the
extender in place.
Base
NOTE − Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
Base
Leg Detail
2" (50.8mm)
SCH 40
Female Threaded
Adapter
Figure 4. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may
require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.
Leg Detail
4" (101.6mm)
SCH 40 Piping
Figure 3. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
ELEVATING THE UNIT (LARGER−BASE UNITS)
Unlike the small−base units which use round feet, the
larger−base units are outfitted with elongated feet as
illustrated in figure 4. which uses a similar method for
elevating the unit height.
If additional elevation is necessary, raise the unit by
extending the length of the unit support feet. This may be
done with 2" SCH 40 female threaded adapter. The
specified coupling will fit snuggly into the recess portion of
the feet. Use additional 2" SCH 40 male threaded adaptors
which can be threaded into the female threaded adaptors
to make additional adjustments to the level of the unit.
TYPICAL
INSTALLATION
WITH 3 TO 4 IN.
EXTENDERS
INSTALLED
IMPORTANT!
ALWAYS USE
STABILIZER
BRACKET ON
ELEVATED
INSTALLATIONS
STABILIZER
BRACKETS
GROUND LEVEL
BUILDING
STRUCTURE
MOUNTING
SLAB
Figure 5. Elevated Slab Mounting using Feet
Extenders
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the
factory height. (Elevated units could become
unstable in gusty wind conditions).
Stabilizers may be used on factory height units
when mounted on unstable or uneven surface.
505244M 10/09
Page 4
Page 5
With unit positioned at installation site, remove two side
louvered panels to expose the unit base pan.
Install the
brackets as illustrated in figure 6 using conventional
practices; replace the panels after installation is complete.
#10 1/2" LONG
SELF−DRILLING SHEET
METAL SCREWS
STABILIZING BRACKET
(18 GAUGE METAL − 2"
WIDTH; HEIGHT AS
REQ’D)
#10 1−1/4" LONG HEX
HD SCREW &
FLATWASHER
PLASTIC ANCHOR − USE IF CONCRETE
(HOLE DRILL 1/4"); NOT IF PLASTIC SLAB
(HOLE DRILL 1/8").
Deck Top
Mounting
STABILIZING
BRACKET (18
GAUGE METAL − 2"
WIDTH; HEIGHT
AS REQ’D); BEND
TO FORM RIGHT
ANGLE
MINIMUM 1
PER SIDE
FOR EXTRA
STABILITY
COIL
BASE PAN
CORNER POST
Removing Panels
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly as illustrated in figure 8.
2. Hold the panel firmly throughout this procedure.
Rotate bottom corner of panel away from hinge corner
post until lower three tabs clear the slots as illustrated
figure 8, Detail B .
3. Move panel down until lip of upper tab clears the top
slot in corner post as illustrated in figure 8, Detail A.
Position and Install PanelPosition the panel almost
parallel with the unit as illustrated in figure 9, Detail D on
page 6 with the screw side as close to the unit as possible.
Then, in a continuous motion:
slightly rotate and guide the lip of top tab inward as
illustrated in figure 8, Details A and C; then upward into
the top slot of the hinge corner post.
rotate panel to vertical to fully engage all tabs.
holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
When panel is correctly positioned and aligned, insert the
screws and tighten.
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY,
2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
Figure 6. Installing Stabilizer Brackets
(Slab Side Mounting)
ROOF MOUNTING
Install unit 6" (152 mm) above the roof surface to avoid ice
build−up around the unit. Locate the unit above a load
bearing wall or area of the roof that can adequately support
the unit. Consult local codes for rooftop applications.
If unit cannot be located away from prevailing winter winds,
construct a wind barrier sized at least the same height and
width as outdoor unit. Position barrier 24" (610 mm) from
the sides of the unit in direction of prevailing winds as
illustrated in figure 7.
prevailing winter winds
wind barrier
24"
inlet air
inlet air
(610 mm)
inlet air
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab
is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top
slot for removing (or installing) panel.
SCREW
HOLES
LIP
Detail
A
Detail
B
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE PANEL
inlet air
Figure 7. Rooftop Application with Wind Barrier
Detail C
Figure 8. Removing/Installing Louvered Panels
(Details A, B and C)
Page 5
XP14 SERIES
Page 6
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT
AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO
EXTREME
PREFERRED ANGLE
FOR INSTALLATION
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail D
Figure 9. Removing/Installing Louvered Panels
(Detail D)
4. Units are approved for use only with copper
conductors. (A complete unit wiring diagram is
located inside the unit control box cover.)
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with
national and local codes.
NOTE − For use with copper conductors only. Refer to unit
rating plate for minimum circuit ampacity and maximum overcurrent protection size.
CAUTION
To prevent personal injury, or damage to panels,
unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow
all removed panels out of the way, so that the panels
will not cause injury to personnel, nor cause
damage to objects or structures nearby, nor will the
panels be subjected to damage (e.g., being bent or
scratched).
While handling or stowing the panels, consider any
weather conditions, especially windy conditions,
that may cause panels to be blown around and
battered.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
1. Install line voltage power supply to unit from a properly
sized unit disconnect switch.
2. Ground the unit at the unit disconnect switch or to
earth ground.
3. To facilitate conduit, a hole is provided in the bottom of
the control box. Connect conduit to the control box
using a proper conduit fitting.
Figure 10. Outdoor Unit Typical Field Wiring
NOTE − For proper voltages, select thermostat wire
gauge per the following chart:
Table 2. Wire Run Lengths
Wire run lengthAWG #Insulation type
less than 100’ (30m)18
more than 100’ (30m)16
color−coded, temperature
rating 35ºC minimum
5. Install room thermostat (ordered separately) on an
inside wall approximately in the center of the
conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it
can be affected by sunlight, drafts or vibrations.
6. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figures 11 and
12 on page 7.
NOTE − 24V, Class II circuit connections are made in the
low voltage junction box.)
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be
grounded in accordance with national
and local codes.
Line voltage is present at all
components when unit is not in
operation on units with single-pole
contactors. Disconnect all remote
electric power supplies before
opening access panel. Unit may have
multiple power supplies.
505244M 10/09
Page 6
Page 7
ThermostatIndoor UnitOutdoor Unit
24V power
R
common
C
1st-stage
W1
auxiliary heat
W3
indoor blower
G
reversing valve
O
compressor
Y1
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC
THERMOSTAT AND INDOOR UNIT.)
W1
W2
R
C
G
24V power
common
1st-stage
auxiliary heat
R
C
W1
O
Y1
ThermostatIndoor UnitOutdoor Unit
24V power24V power
R
common
C
emergency heat
E
1st-stage
W1
auxiliary heat
indoor blower
G
reversing valve
O
compressor
Y1
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC
THERMOSTAT AND INDOOR UNIT.)
W1
W2
W3
R
common
C
1st-stage
auxiliary heat
G
R
C
W1
O
Y1
EMERGENCY
HEAT RELAY
OUTDOOR
THERMOSTAT
Figure 11. Outdoor Unit and Blower Unit Thermostat
Designations
Figure 12. Outdoor Unit and Blower Unit Thermostat
Designations (with Emergency Heat Relay)
Figure 13. Typical XP14 Wiring
Page 7
XP14 SERIES
Page 8
Refrigerant Piping
IMPORTANT
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFC’s, HFC’s, and HCFC’s)
as of July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for
noncompliance.
If the XP14 unit is being installed with a new indoor coil and
line set, the plumbing connections should be made as
outlined in this section. If an existing line set and/or indoor
coil is going to be used to complete the XP14 system, refer
to the following section that includes flushing procedures.
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat,
non-flare) series line sets as shown in table 3 or use
field-fabricated refrigerant lines. Refer to Refrigerant
Piping Guide (Corp. 9351−L9) for proper size, type, and
application of field−fabricated lines. Valve sizes are also
listed in table 3.
REFRIGERANT LINE CONNECTIONS − XP14
OUTDOOR UNIT MATCHED WITH NEW INDOOR
COIL AND LINE SET
If replacing an existing coil equipped with a liquid line
functioning as a metering orifice, replace the liquid line
prior to installing the XP14 unit. Line sets are described in
table 3.
Table 3. Refrigerant Line Sets
Valve Field
Model
−018
−024
−030
−036
−042
−048
−060
Connections
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in
(19 mm)
7/8 in
(22 mm)
1−1/8 in.
(29 mm)
NOTE − When installing refrigerant lines, refer to Lennox
Refrigerant Piping Guide (Corp. 9351−L9) or Lennox
Technical Support Department Product Applications
Group for assistance. In addition, be sure to consider the
following points:
Recommended Line Set
Liquid
Line
3/8 in.
(10
mm)
3/8 in.
(10
mm)
3/8 in.
(10
mm)
Vapor
Line
3/4 in
(19 mm)
7/8 in
(22 mm)
1−1/8 in.
(29 mm)
L15
Line Sets
L15−41
15 ft. − 50 ft.
(4.6 m − 15 m)
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
Field
Fabricated
Select line set diameters from table 3 to ensure that oil
returns to the compressor.
Units are designed for line sets of up to 50 feet (15 m);
for longer line sets, consult piping guidelines.
Size vertical vapor riser to maintain minimum velocity
at minimum capacity.
INSTALLING REFRIGERANT LINE
Pay close attention to line set isolation during installation of
any heat pump or a/c system. When properly isolated from
building structures (walls, ceilings. floors), the refrigerant
lines will not create unnecessary vibration and subsequent
noises. Also, consider the following when placing and
installing a high−efficiency outdoor unit:
1. PlacementSome localities are adopting sound
ordinances based on the unit’s noise level observed
from the adjacent property, not from the installation
property. Install the unit as far as possible from the
property line. When possible, do not install the unit
directly outside a window. Glass has a very high level
of sound transmission. Figure 14 shows how to place
the outdoor unit and line set.
Install unit
away from
windows
Two 90° elbows installed in line set
will reduce line set vibration.
Figure 14. Outside Unit Placement
2. Line Set IsolationThe following illustrations
demonstrate procedures which ensure proper
refrigerant line set isolation.
Figure 15 on page 9 shows how to install line sets
on horizontal runs.
Figure 16 on page 9 shows how to install line sets
on vertical runs.
Figure 17 on page 9 shows how to make a
transition from horizontal to vertical
505244M 10/09
Page 8
Page 9
TO HANG LINE SET FROM JOIST OR
RAFTER, USE EITHER METAL STRAPPING
MATERIAL OR ANCHORED HEAVY NYLON
WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
STRAP THE SUCTION LINE TO
THE JOIST OR RAFTER AT 8 FEET
INTERVALS THEN STRAP THE
LIQUID LINE TO THE SUCTION
LINE.
8 FEET
Figure 15. Refrigerant Line Sets: Installing
Horizontal Runs
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SUCTION LINE
WIRE TIE
(AROUND
SUCTION LINE
ONLY)
TAPE OR
WIRE TIE
LIQUID LINE
WIRE TIE
INSIDE WALL
ANCHORED HEAVY
NYLON WIRE TIE
WALL
STUD
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL
STUD
METAL SLEEVE
STRAP LIQUID LINE
TO SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN
ARMAFLEX
STRAP LIQUID LINE TO
SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN
ARMAFLEX
STRAP
NOTE − SIMILAR INSTALLATION
PRACTICES SHOULD BE USED
IF LINE SET IS TO BE INSTALLED
ON EXTERIOR OF OUTSIDE
WALL.
SUCTION LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
LIQUID LINE
CAULK
SLEEVE
IMPORTANT! REFRIGERANT
LINES MUST NOT CONTACT
STRUCTURE.
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
Figure 16. Refrigerant Line Sets: Installing Vertical
Runs (New Construction Shown)
Figure 17. Refrigerant Line Sets: Transition from
Vertical to Horizontal
BRAZING CONNECTION PROCEDURE
WARNING
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept
closed as much as possible. DO NOT remove line
set caps or service valve stub caps until you are
ready to make connections.
1. Cut ends of the refrigerant lines square (free from
nicks or dents). Debur the ends. The pipe must remain
round; do not pinch end of the line.
2. Flow dry nitrogen through the refrigerant piping while
making line set connections; this prevents carbon
deposits (oxidation) buildup on the inside of the joints
being brazed. Such buildup may restrict refrigerant
flow through screens and metering devices. To do this:
Flow regulated nitrogen (at 1 to 2 psig) through the
refrigeration gauge set into the Schrader port
connection on the vapor service valve and out of
the Schrader port connection on the liquid service
valve. (Metering device (CTXV and RFC) will
allow low pressure nitrogen to flow through the
system.)
Page 9
XP14 SERIES
Page 10
While nitrogen is flowing, braze refrigerant line set
to the indoor and outdoor units. IMPORTANT: The
flow of nitrogen must have an escape path
other than through the joint to be brazed.
3. Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper−to−copper brazing or 45 percent
silver alloy for copper−to−brass or copper−to−steel
brazing) which are rated for use with HFC−410A
refrigerant.
4. Wrap a wet cloth around the valve body and the copper
tube stub to protect it from heat damage during
brazing. Wrap another wet cloth underneath the valve
body to protect the base paint.
NOTE − The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating,
sealing and rigidity.
5. Install a field−provided check expansion valve
(approved for use with HFC−410A refrigerant) in the
liquid line at the indoor coil.
Flushing Existing Line Set and Indoor
Coil
IMPORTANT
If this unit is being matched with an approved line
set or indoor coil which was previously charged
with HCFC−22 refrigerant, or if it is being matched
with a coil which was manufactured before
January of 1999, the coil and line set must be
flushed prior to installation. Take care to empty all
existing traps.
Polyol ester (POE) oils are used in Lennox units
charged with HFC−410A refrigerant. Residual
mineral oil can act as an insulator, preventing
proper heat transfer. It can also clog the check
expansion valve, reducing system performance
and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
WARNING
Danger of fire. Bleeding the
refrigerant charge from only the high
side may result in the low side shell
and suction tubing being
pressurized. Application of a brazing
torch while pressurized may result in
ignition of the refrigerant and oil
mixture − check the high and low
pressures before unbrazing.
CAUTION
This procedure should not be performed on
systems which contain contaminants (Example:
compressor burn out).
IMPORTANT
The line set and indoor coil must be flushed with
at least the same amount of clean refrigerant that
previously charged the system. Check the charge
in the flushing cylinder before proceeding.
EQUIPMENT REQUIRED FOR FLUSHING LINE SET
The following equipment is required to flush the existing
line set and indoor coil:
two clean HCFC−22 recovery cylinders
oilless recovery machine with a pump down feature
gauge set for HCFC−22 refrigerant
gauge set for HFC−410A refrigerant (see Manifold
Gauge Set section on page 12).
FLUSHING PROCEDURE
1. Remove existing HCFC−22 refrigerant using the
following, applicable procedure as illustrated in figure
18:
If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing HCFC−22
refrigerant to flush the system −
Disconnect all power to the existing outdoor unit.
Connect to the existing unit, a clean recovery
cylinder and the recovery machine according to
the instructions provided with the recovery
machine.
Remove all HCFC−22 refrigerant from the existing
system. Check gauges after shutdown to confirm
that the entire system is completely void of
refrigerant.
Disconnect the liquid and vapor lines from the
existing outdoor unit.
If the existing outdoor unit is equipped with
manual shut−off valves AND you plan to use NEW
HCFC−22 refrigerant to flush the system −
Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.
Pump all of the existing HCFC−22 refrigerant back
into the outdoor unit. (It may be necessary to
bypass the low pressure switches to ensure
complete refrigerant evacuation.)
When the low side system pressures reach 0 psig,
close the vapor line valve.
Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into
the low side of the system.
Disconnect the liquid and vapor lines from the
existing outdoor unit.
2. Remove the existing outdoor unit. Set the new
HFC−410A unit and follow the Brazing ConnectionProcedure provided on page 9 to make line set
connections. DO NOT install HFC−410A
check/expansion valve at this time.
3. Make low voltage and line voltage connections to the
new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this
time.
505244M 10/09
Page 10
Page 11
INVERTED HCFC−22
CYLINDER CONTAINS
CLEAN HCFC−22 TO BE
USED FOR FLUSHING.
A
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
D
NEW
OUTDOOR
UNIT
B
LOW
OPENED
C
RECOVERY MACHINE
GAUGE
MANIFOLD
TANK
RETURN
INLET
DISCHARGE
HIGH
CLOSED
AInverted HCFC−22 cylinder with clean refrigerant to the
suction service valve.
BHCFC−22 gauge set (low side) to the liquid line valve.
CHCFC−22 gauge set center port to inlet on the recovery
machine. with an empty recovery tank to the gauge set.
DConnect recovery tank to recovery machines per machine
instructions.
NOTE − The inverted HCFC−22 cylinder must contain at least the same
amount of refrigerant as was recovered from the existing system.
Figure 18. Flushing Connections
4. Remove the existing HCFC−22 refrigerant flow control
orifice or check expansion valve before continuing with
flushing procedures. HCFC−22 flow control devices
(fixed orifice/check expansion valve) are not approved
for use with HFC−410A refrigerant and may prevent
proper flushing. Use a field−provided fitting to
reconnect the lines.
5. Remove the pressure tap valve cores from the XP14
unit’s service valves. Connect an HCFC−22 cylinder
with clean refrigerant to the vapor service valve.
Connect the HCFC−22 gauge set to the liquid line valve
and connect a recovery machine with an empty
recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the
existing system line set and indoor coil.
7. Invert the cylinder of clean HCFC−22 and open its
valve to allow liquid refrigerant to flow into the system
through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.
8. After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that
all of the HCFC−22 vapor is recovered. Allow the
recovery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and
indoor coil. A second flushing may be done (using
clean refrigerant) if insufficient amounts of mineral oil
were removed during the first flush. After each
system flush, allow the recovery machine to pull a
vacuum on the system at the end of the
procedure.
9. Close the valve on the inverted HCFC−22 drum and
the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.
10. Use dry nitrogen to break the vacuum on the
refrigerant lines and indoor coil before removing the
recovery machine, gauges and HCFC−22 refrigerant
drum. Reinstall pressure tap valve cores into XP14
unit’s service valves.
11. Install check expansion valve (approved for use with
HFC−410A refrigerant) in the liquid line at the indoor
coil.
Refrigerant Metering Device
XP14 units may be used in check thermal expansion valve
(CTXV) systems only. See indoor coil installation
instructions and the Lennox engineering handbook for
approved HFC−410A valve match−ups and application
information.
NOTE − HFC−410A systems will not operate properly with
an HCFC−22 valve.
Check thermal expansion valves equipped with fittings are
available from Lennox. Refer to the Engineering
Handbook for applicable expansion valves for use with
specific match-ups.
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(uncased coil
only)
DISTRIBUTOR
TUBES
ACCESS FITTING
(no valve core)
On smaller lines,
bulb may be
mounted on top
9
Do not mount bulb
on bottom of line
Figure 19. Metering Device Installation
12
Suction
Line
ORIFICE
HOUSING
EQUALIZER
LINE
SENSING BULB
(insulation required)
1/2" & smaller
suction line
3
Bulb
5/8" & larger
suction line
EXPANSION VALVE
(see note)
O−RING
O−RING
STRAINER
Remove and discard
SEAL ASSEMBLY
(if applicable)
SUCTION
LINE
NOTE − If necessary, remove
HCFC−22 flow control device
(fixed orifice/check expansion
valve) from existing line set before
installing HFC−410A approved expansion valve and o−ring.
SENSING
LINE
LIQUID
LINE
Page 11
XP14 SERIES
Page 12
CHECK
EXPANSION VALVE
LOW
PRESSURE
PRESSURE
HUGH
BIFLOW
FILTER /
DRIER
MUFFLER
DISTRIBUTOR
OUTDOOR
COIL
OUTDOOR UNIT
REVERSING VALVE
NOTE − ARROWS INDICATE
DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
GAUGE MANIFOLD
TO
HFC−410
A DRUM
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant
lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
Failure to remove a fixed orifice when installing an
expansion valve on the indoor coil will result in
improper operation and damage to the system.
If you install a check thermal expansion valve with an
indoor coil that includes a fixed orifice, remove the orifice
before the check expansion valve is installed. See figure
19 for installation of the check expansion valve.
Manifold Gauge Set
Manifold gauge sets used with systems charged with
HFC−410A refrigerant must be capable of handling the
higher system operating pressures. The gauges should be
rated for use with pressures of 0 − 800 on the high side and
a low side of 30" vacuum to 250 psi with dampened speed
to 500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.
Service Valves
The service valves and gauge ports are used for leak
testing, evacuating, charging and checking charge. Each
valve is equipped with a service port which has a
factory−installed Schrader valve. A service port cap
protects the Schrader valve from contamination and
serves as the primary leak seal.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap.
Tighten finger tight, then torque per table 1 on page 3.
To Open Front-Seated Service Valves:
1. Remove stem cap with an adjustable wrench.
3. Replace the stem cap. Tighten finger tight, then torque
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension
3. Replace the stem cap. Tighten finger tight, then torque
Vapor Line Ball Valve
Ball-type service valves as illustrated in figure 22 function
the same way as the other valves but cannot be rebuilt; if
one fails, replace with a new valve. The ball valve is
equipped with a service port with a factory−installed
Schrader valve. A service port cap protects the Schrader
valve from contamination and assures a leak−free seal.
VAPOR
VAPOR
SERVICE
PORT
VAPOR
LINE
VALV E
CHECK EXPANSION VALVE
SERVICE
PORT
INDOOR
COIL
(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to back the stem out counterclockwise as
far as it will go.
per table 1 on page 3.
(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to turn the stem clockwise to seat the
valve. Tighten it firmly.
per table 1 on page 3.
STEM
SCHRADER
VALVE [OPEN TO
LINE SET WHEN
VALVE IS CLOSED
(FRONT SEATED)]
TO
OUTDOOR
COIL
SERVICE
PORT CAP
CAP
(VALVE FRONT-SEATED)
Valve in closed positionValve in open position
INSERT HEX
WRENCH HERE
TO
INDOOR
COIL
Figure 21. Front-Seated Liquid Line Valve
505244M 10/09
Page 12
Page 13
STEM
USE ADJUSTABLE WRENCH
TO OPEN: ROTATE STEM
COUNTER-CLOCKWISE 90°.
TO CLOSE: ROTATE STEM
CLOCKWISE 90°.
TO
INDOO
R COIL
CAP
STEM
SERVICE PORT
SCHRADER VALVE
TO
OUTDOOR
COIL
BALL (SHOWN
CLOSED)
SERVICE
PORT CAP
Figure 22. Ball−Type Vapor Valve (Valve Closed)
Leak Testing
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
2. With both manifold valves closed, connect the cylinder
of HFC−410A refrigerant. Open the valve on the
HFC−410A cylinder (vapor only).
3. Open the high pressure side of the manifold to allow
HFC−410A into the line set and indoor unit. Weigh in
a trace amount of HFC−410A. [A trace amount is a
maximum of 2 ounces (57 g) refrigerant or 3 pounds
(31 kPa) pressure]. Close the valve on the HFC−410A
cylinder and the valve on the high pressure side of the
manifold gauge set. Disconnect HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set.
5. Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high
pressure hose is connected to the liquid line port;
however, connecting it to the vapor port better protects
the manifold gauge set from high pressure damage.)
6. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
7. After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge dry nitrogen and
HFC−410A mixture. Correct any leaks and recheck.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire and/
or an explosion, that could result in
personal injury or death.
WARNING
Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refrigeration or air conditioning system,
use a regulator that can control the
pressure down to 1 or 2 psig (6.9 to
13.8 kPa).
USING AN ELECTRONIC LEAK DETECTOR
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
1. Connect a cylinder of HFC−410A to the center port of
the manifold gauge set.
Evacuation
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper
piping and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 23,000 microns.
1. Connect manifold gauge set to the service valve ports
as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to
the center port of the manifold gauge set.
4. Open both manifold valves; start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolutepressure of 23,000 microns (29.01 inches of
mercury). During the early stages of evacuation, it is
desirable to close the manifold gauge valve at least
once to determine if there is a rapid rise in absolutepressure. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak
testing procedure.
Page 13
XP14 SERIES
Page 14
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute
pressure in a vacuum is equal to atmospheric
pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a dry nitrogen
cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.
4. Replace stem caps and secure finger tight, then
tighten an additional (1/6) one-sixth of a turn.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
power company has been consulted and the voltage
condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on
power to indoor blower unit and close the outdoor unit
disconnect to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
IMPORTANT
WARNING
Danger of Equipment Damage! Avoid deep
vacuum operation. Do not use compressors to
evacuate a system. Extremely low vacuums can
cause internal arcing and compressor failure.
Damage caused by deep vacuum operation will
void warranty.
7. Shut off the dry nitrogen cylinder and remove the
manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the dry nitrogen from
the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9. When the absolute pressure requirement above has
been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HFC−410A refrigerant. Open the manifold gauge
valves to break the vacuum from 1 to 2 psig positive
pressure in the line set and indoor unit. Close manifold
gauge valves and shut off the HFC−410A cylinder and
remove the manifold gauge set.
Start−Up
Mineral oils are not compatible with HFC−410A. If
oil must be added, it must be a polyol ester oil.
Refrigerant Charge
This system is charged with HFC−410A refrigerant which
operates at much higher pressures than HCFC−22. The
recommended check expansion valve is approved for use
with HFC−410A. Do not replace it with a valve that is
designed to be used with HCFC−22. This unit is NOT
approved for use with coils that include metering orifices or
capillary tubes.
Units are factory-charged with the amount of HFC−410A
refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15 ft.
(4.6 m) line set. For varying lengths of line set, refer to table
3 for refrigerant charge adjustment. A blank space is
provided on the unit rating plate to list the actual field
charge.
Check Indoor Airflow before Charging
IMPORTANT
Check airflow before charging!
NOTE − Be sure that filters and indoor and outdoor coils are
clean before testing.
IMPORTANT
If unit is equipped with crankcase heater, it should
be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory− and field-installed wiring for loose
connections.
NOTE − After the system has been evacuated and before
completing all the remaining start−up steps, this is the ideal
time to adjust the amount of refrigerant made necessary by
line set length difference and by the specific indoor unit
match−up. Skip to the paragraph Setup for Checking and
Adding Charge" on page 15 to setup for charging and for
determining if charge is needed; adjust the charge
accordingly.
3. Open the liquid line and vapor line service valves
(counterclockwise) to release refrigerant charge
(contained in outdoor unit) into the system.
505244M 10/09
Page 14
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (DT) process (figure 23).
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:
temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
voltage supplied to the unit,
amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula
to determine CFM:
CFM =
Check indoor airflow using the step procedures as
illustrated in figure 23.
Figure 23. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
DT
air flowair flow
INDOOR
COIL
Step 1. Determine the desired DTMeasure entering air tempera-
ture using dry bulb (A) and wet bulb (B). DT is the intersecting value of
A and B in the table (see triangle).
Step 2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Temperature
Drop Formula: (T
Step 3. Determine if fan needs adjustmentIf the difference between the measured T
B
A
72º
B
64º
WET
BULB
DRY
BULB
+3º, no adjustment is needed. See examples: Assume DT = 15 and A
temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
Drop
53º 19–15 =4Increase the airflow
58º14–15=−1 (within +3º range) no change
62º10–15=−5 Decrease the airflow
Step 4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
) = A minus C.
Drop
and the desired DT (T
Drop
–DT=ºF ACTION
–DT) is within
Drop
Setup for Checking and Adding Charge
SETUP FOR CHARGING
Connect the manifold gauge set to the unit’s service ports
(see figure 20):
low pressure gauge to vapor service port
high pressure gauge to liquid service port
Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC−410A.
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the
unit. To calculate the total refrigerant charge:
Amount
specified
on
nameplate
Adjust amt. for
variation in
line set length
(table 4)
Additional charge
specified per
indoor unit match−up
(table 5)
++=
Total
charge
Weigh in Charge
1. Recover the refrigerant from the unit.
2. Conduct leak check; evacuate as previously outlined.
3. Weigh in the unit nameplate charge plus any charge
required for line set differences from 15 feet and any
extra indoor unit match−up amount per table 5. (If
weighing facilities are not available, use the
subcooling method.)
Table 4. Charge per Line Set Lengths
Liquid Line
Set Diameter
3/8 in. (9.5mm)3 ounce per 5 ft. (85g per 1.5m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.
Oz. per 5 ft. (g per 1.5m) adjust from
15 ft. (4.6m) line set*
Subcooling Charge
Requirementsthese items are required for charging:
Manifold gauge set connected to unit.
Thermometers for measuring outdoor ambient, liquid
line, and vapor line temperatures.
When to use cooling modeWhen outdoor
temperature is 60°F (15°C) and above, use cooling mode
to adjust charge.
When to use heating modeWhen the outdoor
temperature is below 60°F (15°C), use the heating mode to
adjust the charge.
Adding Charge for Indoor Match−UpTable 5 lists all
the Lennox recommended indoor unit matches along with
the charge levels for the various sizes of outdoor units.
Page 15
XP14 SERIES
Page 16
SATº
LIQº –
SCº =
Table 5. Adding Charge per Indoor Unit Match using Subcooling Method
Use
cooling
mode
60ºF (15ºC)
Use
heating
mode
1 Check the airflow as illustrated in figure 23 on page 15 to be sure the indoor airflow is as required.
(Make any air flow adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode
to check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table
7, (Table 7 is a general guide. Expect minor pressure variations. Significant differences may mean
improper charge or other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values in table below are based on 70 to 80°F (21−27°C) indoor return air temperature; if
necessary, operate heating to reach that temperature range; then set thermostat to cooling mode
setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6.
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target
subcooling values in table below are based on 65−75°F (18−24°C) indoor return air temperature; if
necessary, operate cooling to reach that temperature range; then set thermostat to heating mode
setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure
chart listed on page 18 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with table below, being sure to note any additional charge for line set and/or
match−up.
10 If subcooling value is greater than shown in table, remove refrigerant; if less than shown, add
refrigerant.
11 If refrigerant is added or removed, repeat steps 5 through 10 to verify charge.
505244M 10/09
Page 16
Page 17
Table 6. Air Handler/Coil Matchups and Target Subcooling
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)(+1ºF)
*Add
charge
INDOOR MATCHUPS
XP14−018lb oz XP14−030 (Continued)lb oz XP14−042 (Continued)lb oz
*Add charge = Extra matchup amount required in addition to
charge indicated on Heat Pump nameplate (remember to also
add any charge required for line set differences from 15 feet).
SN indicates serial number.
Page 17
XP14 SERIES
Page 18
Table 7. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG* (Cooling)
*IMPORTANTThese are most popular match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
The demand defrost controller measures differential
temperatures to detect when the system is performing
poorly because of ice build−up on the outdoor coil. The
controller self−calibrates when the defrost system starts
and after each system defrost cycle. The defrost control
board components are shown in figure 24.
Note − Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR PLUG IN
(COIL, AMBIENT,
& DISCHARGE
SENSORS)
DELAY
PINS
LOW
AMBIENT
THERMOSTAT
PINS
DIAGNOSTIC
LEDS
The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a
defrost cycle is required. The coil temperature probe is
designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE − The demand defrost board accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the board initiates defrost cycles.
SERVICE LIGHT OPERATION
The thermostat is not included with the unit and must be
purchased separately. Some outdoor thermostats
incorporate isolating contacts and an emergency heat
function (which includes an amber indicating light). The
service light thermostat will enable the emergency heat
light function on the room thermostat.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of
the outdoor unit is required, or when auxiliary electric heat
is staged by outdoor thermostats. When the room
thermostat is placed in the emergency heat position, the
outdoor unit control circuit is isolated from power and
field-provided relays bypass the outdoor thermostats. An
amber indicating light simultaneously comes on to remind
the homeowner that he is operating in the emergency heat
mode.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage if power has been off for over an hour and the
outdoor temperature is below 50°F (10°C). System should
be left in the emergency heat mode at least six hours to
allow the crankcase heater sufficient time to prevent
compressor slugging.
FILTER DRIER
The unit is equipped with a large−capacity biflow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of the same design and capacity.
The replacement filter drier must be suitable for use with
HFC−410A refrigerant.
DEFROST CONTROL BOARD
Figure 24 provides a basic illustration of the layout of the
defrost control board. Table 9 provides information
concerning pin−out and jumper configurations.
90, and 100°F (10, 21, 32 and 38°C). The shunt
termination pin is factory set at 50°F (10°C). If the
temperature shunt is not installed, the default termination
temperature is 90°F (32°C).
Note: The Y1 input must be active (ON) and the O" room
thermostat terminal into board must be inactive.
DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the defrost
board (DS1 [Red] and DS2 [Green]) indicate diagnostics
conditions that are described in table 10.
DELAY MODE
The defrost board has a field−selectable function to reduce
occasional sounds that may occur while the unit is cycling
in and out of the defrost mode. When a jumper is installed
on the DELAY pins, the compressor will be cycled off for 30
seconds going in and out of the defrost mode. Units are
shipped with jumper installed on DELAY pins.
DEFROST BOARD PRESSURE SWITCH
CONNECTIONS
The unit’s automatic reset pressure switches (LO PS − S87
and HI PS − S4) are factory−wired into the defrost board on
the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS)
When the low pressure switch trips, the defrost board will
cycle off the compressor, and the strike counter in the
board will count one strike. The low pressure switch is
ignored under the following conditions:
during the defrost cycle and 90 seconds after the
termination of defrost
when the average ambient sensor temperature is below
15° F (−9°C)
for 90 seconds following the start up of the compressor
during test mode
Page 19
XP14 SERIES
Page 20
Table 9. Defrost Control Board Description
IDDescription
O Out24 VAC output connection for reversing valve
LO−PSConnection for low−pressure switch
Y224 VAC output for second stage compressor solenoid
Y124 VAC common output, switched for enabling compressor
contactor
HI−PSConnection for high−pressure switch
P1Seven position square pin header. P1 provides selection of
the defrost terminate temperature based on the position of
selection shunt, as well as selection pins for enabling the
field test mode.
P2The following connections are provided in the seven posi-
tion P2 screw terminal block:
W124 VAC thermostat output for auxiliary heat op-
eration
C24 VAC system common
LService light thermostat connection
R24 VAC system power input
Y224 VAC thermostat input for second stage com-
pressor operation
O24 VAC thermostat input for reversing valve op-
eration
Y124 VAC thermostat input for first stage compres-
sor operation
P3Five position square pin header. P3 provides selection of
the Y2 compressor lock−in temperature. Note: This is ap-
plicable for two stage compressor operations only.
P4Six position square pin header. P4 provides connections for
the temperature sensors:
COIL(P4−5) Ground connection for outdoor coil tem-
perature sensor.
(P4−6) Connection for outdoor coil temperature
sensor.
AMB(P4−3) Ground connection for outdoor ambient
temperature sensor.
(P4−4) Connection for outdoor ambient temperature sensor.
DIS(P4−1) Ground connection for discharge temper-
ature sensor.
(P4−2) Connection for discharge temperature
sensor. Note: This is applicable for two stage
compressor operations only.
P5Two position square pin header. P5 provides selection of
the 30−second compressor delay option.
P6Eight position header. P6 provides connections for the fac-
tory test connections.
High Pressure Switch (HI−PS)
When the high pressure switch trips, the defrost board will
cycle off the compressor, and the strike counter in the
board will count one strike.
DEFROST BOARD PRESSURE SWITCH SETTINGS
High Pressure (auto reset) − trip at 590 psig; reset at
418 psig.
Low Pressure (auto reset) − trip at 25 psig; reset at 40
psig.
Low Ambient Thermostat Pins − P3 provides selection of
the Y2 compressor lock−in temperature. The XP14 series
heat pumps do not use a Y2 compressor and therefore
these pins are not active.
FIVE−STRIKE LOCKOUT FEATURE
The internal control logic of the board counts the pressure
switch trips only while the Y1 (Input) line is active. If a
pressure switch opens and closes four times during a Y1
(Input), the control logic will reset the pressure switch trip
counter to zero at the end of the Y1 (Input). If the pressure
switch opens for a fifth time during the current Y1 (Input),
the control will enter a lockout condition.
The five−strike pressure switch lockout condition can be
reset by cycling OFF the 24−volt power to the control board
or by shorting the TEST pins between 1 and 2 seconds. All
timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is
engaged, a 5−minute short cycle will occur after the switch
closes.
ActuationWhen the reversing valve is de−energized,
the Y1 circuit is energized, and the coil temperature is
below 35°F (2°C), the board logs the compressor run time.
If the board is not calibrated, a defrost cycle will be initiated
after 30 minutes of heating mode compressor run time.
The control will attempt to self−calibrate after this (and all
other) defrost cycle(s).
Calibration success depends on stable system
temperatures during the 20−minute calibration period. If
the board fails to calibrate, another defrost cycle will be
initiated after 45 minutes of heating mode compressor run
time. Once the defrost board is calibrated, it initiates a
demand defrost cycle when the difference between the
clear coil and frosted coil temperatures exceeds the
maximum difference allowed by the control OR after 6
hours of heating mode compressor run time has been
logged since the last defrost cycle.
NOTE − If ambient or coil sensor fault is detected, the
board will not execute the TEST mode.
TerminationThe defrost cycle ends when the coil
temperature exceeds the termination temperature or after
14 minutes of defrost operation. If the defrost is terminated
by the 14−minute timer, another defrost cycle will be
initiated after 30 minutes of run time.
Each test pin shorting will result in one test event. For
each TEST the shunt (jumper) must be removed for at
least one second and reapplied. Refer to flow chart as
illustrated in figure 25 for TEST operation.
Test ModeWhen Y1 is energized and 24V power is
being applied to the board, a test cycle can be initiated by
placing the termination temperature jumper across the
TEST pins for two to five seconds. If the jumper remains
across the TEST pins longer than five seconds, the control
will ignore the TEST pins and revert to normal operation.
The jumper will initiate one cycle per test.
505244M 10/09
Page 20
Page 21
JUMPER
TEST
Placing the jumper on the field test pins (E33) allows the technician to:
Clear short cycle lockout
Clear five−strike fault lockout
Cycle the unit in and out of defrost mode
Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be
initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper
remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For
each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
DEMAND DEFROST CONTROL
(UPPER LEFT−HAND CORNER)
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable. No other functions will be
executed and unit will continue in the
mode it was operating.
If in COOLING Mode
No further test mode operation will be
executed until the jumper is removed
from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for 34 minute
test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor exist, unit
will go into DEFROST MODE.
If ambient or coil faults exist (open or
shorted), unit will remain in HEAT
MODE.
NOTE Placing a jumper on the TEST pins will not bring the unit
out of inactive mode. The only way manually activate the heat
pump from an inactive mode is to cycle the 24VAC power to the
Control.
If jumper on TEST pins remains in
place for more than five seconds.
The unit will return to HEAT MODE
un−calibrated with defrost timer set
for 34 minutes.
Figure 25. Test Mode
Page 21
If jumper on TEST pins is removed
before a maximum of five seconds.
The unit will remain in DEFROST
MODE until termination on time or
temperature.
XP14 SERIES
Page 22
DEFROST BOARD
DEFROST
SENSOR
HARNESS
AMBIENT
SENSOR
Figure 26. Sensor Locations
505244M 10/09
Page 22
Page 23
DEFROST BOARD DIAGNOSTICS
See table 10 to determine defrost board operational conditions and to diagnose cause and solution to problems.
Table 10. Defrost Control Board Diagnostic LEDs
DS2
Green
OFFOFFPower problem
Simultaneous
SLOW Flash
Alternating SLOW
Flash
Simultaneous
FAST Flash
Alternating
FAST Flash
ONONCircuit Board Failure
DS1
Red
Condition/CodePossible Cause(s)Solution
1
Check control transformer power (24V).
2
If power is available to board and LED(s) do not
light, replace board.
None required.
None required (Jumper TEST pins to override)
Normal operation
5−minute anti−short cycle
delay
Ambient Sensor Problem
Coil Sensor Problem
No power (24V) to board terminals R
and C or board failure.
Unit operating normally or in standby
mode.
Initial power up, safety trip, end of
room thermostat demand.
Sensor being detected open or shorted or out of temperature range. Board will revert to time/
temperature defrost operation. (System will still heat or cool).
Sensor being detected open or shorted or out of temperature range. Board will not perform
demand or time/temperature defrost operation. (System will still heat or cool).
Indicates that board has internal component failure. Cycle 24 volt power to board. If code does
not clear, replace board.
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
1
OFF
SLOW
Flash
OFFON
SLOW
Flash
OFFHigh Pressure Fault
ONOFF
SLOW
Flash
FAST
Flash
ON
ON
Low Pressure Fault
Low Pressure LOCKOUT
High Pressure LOCKOUT
Discharge Line Temperature
Fault
Discharge Line Temperature
LOCKOUT
1
Restricted air flow over indoor or
outdoor coil.
2
Improper refrigerant charge in
system.
3
Improper metering device installed or
incorrect operation of metering
device.
4
Incorrect or improper sensor location
or connection to system.
This model does not have a defrost line sensor, therefore this code is not applicable.
Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for
proper current draws.
2
Check system charge using approach and subcooling temperatures.
3
Check system operating pressures and compare to
unit charging charts.
4
Make sure all pressure switches and sensors have
secure connections to system to prevent refrigerant
leaks or errors in pressure and temperature measurements.
OFF
Fast
Flash
Fast
Flash
OFF
Discharge Sensor Fault
Discharge Sensor
LOCKOUT
The XP14 series units does not use a defrost line sensor. However, a resistor is installed
across pins P4−1 and P4−2. If the resistor is missing or damage then this fault code will be
displayed.
This model does not have a defrost line sensor, therefore this code is not applicable.
Table 11. Sensor Temperature / Resistance Range
SensorTemperature Range °F (°C)Resistance Values Range (ohms)Pins/Wire Color
Outdoor (Ambient)−35 to 120 (−37) to (48)280,000 to 37503 and 4 (Black)
Coil−35 to 120 (−37) to (48)280,000 to 37505 and 6 (Brown)
Note: Sensor resistance decreases as sensed temperature increases (see figure 27).
100
TEMPERATURE (ºF)
5750
90
80
70
60
50
40
30
20
10
7450
9275
11775
15425
19975
26200
34375
46275
62700
0
1000030000500007000090000
RESISTANCE (OHMS)
85300
Figure 27. Ambient and Coil Sensors
Page 23
XP14 SERIES
Page 24
Enter the TEST mode by placing a shunt (jumper) across
the TEST pins on the board after power−up. The TEST
pins are ignored and the test function is locked out if the
shunt is applied on the TEST pins before power−up. Board
timings are reduced, the low−pressure switch is ignored
and the board will clear any active lockout condition.
NOTE − The 30−second off cycle is NOT functional when
jumpering the TEST pins.
Ambient SensorThe ambient sensor (shown in figure
26) considers outdoor temperatures below −35°F (−37°C)
or above 120°F (48°C) as a fault. If the ambient sensor is
detected as being open, shorted or out of the temperature
range of the sensor, the board will not perform demand
defrost operation. The board will revert to
time/temperature defrost operation and will display the
appropriate fault code. Heating and cooling operation will
be allowed in this fault condition.
Coil SensorThe coil temperature sensor (shown in
figure 26) considers outdoor temperatures below −35°F
(−37°C) or above 120°F (48°C) as a fault. If the coil
temperature sensor is detected as being open, shorted or
out of the temperature range of the sensor, the board will
not perform demand or time/temperature defrost
operation and will display the appropriate fault code.
Heating and cooling operation will be allowed in this fault
condition.
OPERATIONAL DESCRIPTION
The defrost control board has three basic operational
modes: normal, calibration, and defrost.
Normal ModeThe demand defrost board monitors the
O line, to determine the system operating mode
(heat/cool), outdoor ambient temperature, coil
temperature (outdoor coil) and compressor run time to
determine when a defrost cycle is required.
Calibration ModeThe board is considered uncalibrated
when power is applied to the board, after cool mode
operation, or if the coil temperature exceeds the
termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to
ensure that there is no ice on the coil. During calibration,
the temperature of both the coil and the ambient sensor
are measured to establish the temperature differential
which is required to allow a defrost cycle.
Defrost ModeThe following paragraphs provide a
detailed description of the defrost system operation.
DETAILED DEFROST SYSTEM OPERATION
Defrost CyclesThe demand defrost control board
initiates a defrost cycle based on either frost detection or
time.
Frost DetectionIf the compressor runs longer than
30 minutes and the actual difference between the clear
coil and frosted coil temperatures exceeds the
maximum difference allowed by the control, a defrost
cycle will be initiated.
IMPORTANT − The demand defrost control board will
allow a greater accumulation of frost and will initiate
fewer defrost cycles than a time/temperature defrost
system.
TimeIf six hours of heating mode compressor run
time has elapsed since the last defrost cycle while the
coil temperature remains below 35°F (2°C), the
demand defrost control will initiate a defrost cycle.
Maintenance
WARNING
Electric shock hazard. Can cause
injury or death. Before attempting to
perform any service or maintenance,
turn the electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
Before the start of each heating and cooling season, the
following service checks should be performed by a
qualified service technician. First, turn off electrical power
to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.
NOTE − It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with
units operating).
Check the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should
be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
Check the refrigerant charge and gauge the system
pressures.
Check the condensate drain line for free and
unobstructed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
NOTE − If owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked.
Refer to section on refrigerant charging in this
instruction.
User Information
MAINTENANCE
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet)
505244M 10/09
Page 24
Page 25
or behind a return air grille in the wall or ceiling. Check
the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for
your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the
disconnect switch before performing any
maintenance. The unit may have multiple power
supplies.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
NOTE − The filter and all access panels must be in
place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. This
would also apply to an auxiliary drain, if installed.
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts and diminish performance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away
from the unit and periodically check for debris which
collects around the unit.
When removing debris from around the unit, be aware
of metal edges on parts and screws. Although special
care has been taken to keep exposed edges to a
minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion
can result in personal injury.
Cleaning of the outdoor unit’s coil should be performed
by a trained service technician. Contact your dealer
and set up a schedule (preferably twice a year, but at
least once a year) to inspect and service your air
conditioning or heat pump system.
HEAT PUMP OPERATION
Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45°F (7°C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
In case of extended power outage...
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
Emergency Heat setting to obtain temporary heat without
the risk of serious damage to the heat pump.
In Emergency Heat mode, all heating demand is satisfied
by auxiliary heat; heat pump operation is locked out. After a
six-hour compressor crankcase warm-up period, the
thermostat can be switched to the Heat setting and normal
heat pump operation may resume.
THERMOSTAT OPERATIONS
Though your thermostat may vary somewhat from the
description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature
selector levers: one for heating and one for cooling. Set the
levers or dials to the desired temperature setpoints for both
heating and cooling. Avoid frequent temperature
adjustment; turning the unit off and back on before
pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This
mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous
indoor blower operation, regardless of whether the
compressor or auxiliary heat are operating. This mode is
required when constant air circulation or filtering is desired.
Page 25
XP14 SERIES
Page 26
System Switch
Set the system switch for heating, cooling or auto
operation. The auto mode allows the heat pump to
automatically switch from heating mode to cooling mode to
maintain predetermined comfort settings. Many heat
pump thermostats are also equipped with an emergency
heat mode which locks out heat pump operation and
provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which
indicates when the heat pump is operating in the
emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room
temperature.
Programmable Thermostats
Your Lennox system may be controlled by a
programmable thermostat. These thermostats provide the
added feature of programmable time-of-day setpoints for
both heating and cooling. Refer to the user’s information
manual provided with your particular thermostat for
operation details.
Preservice Check
If your system fails to operate, check the following before
calling for service:
Check to see that all electrical disconnect switches are
ON.
Make sure the room thermostat temperature selector
is properly set.
Make sure the room thermostat system switch is
properly set.
Replace any blown fuses, or reset circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean.
Identify the unit model number before calling.
OPTIONAL ACCESSORIES
Refer to the Engineering Handbook for optional
accessories that may apply to this unit. The following may
or may not apply: