Lennox XP14-018-230-01, XP14-018-230-08, XP14-018-230-03, XP14-018-230-07, XP14-018-230-09 Nstallation And Service Instructions

...
Page 1
INSTALLATION AND SERVICE
PROCEDURE
Service Literature
XP14 (HFC-410A) SERIES UNITS
Revised April 7, 2017
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
XP14
Corp. 0721-L7
TABLE OF CONTENTS
Model Number Identification 2....................
Typical Serial Number Identification 2..............
Specifications 2.................................
Electrical Data 4................................
Unit Dimensions 7...............................
Unit Parts Arrangement 8........................
Operating Gauge Set and Service Valves 10.........
Recovering Refrigerant from System 12.............
Unit Placement 13................................
Removing and Installing Panels 15.................
New or Replacement Line Set 17...................
Brazing Connections 19...........................
Flushing Line Set and Indoor Coil 22................
Installing Indoor Metering Device 23................
Leak Test Line Set and Indoor Coil 24...............
Evacuating Line Set and Indoor Coil 25.............
Electrical 26.....................................
Servicing Units Void of Charge 27..................
Unit Start-Up 27.................................
System Refrigerant 27............................
System Operation (XP14-XXX-230-01 through 07) 34. Defrost System (XP14-XXX-230-01 through 07) 36... System Operation (XP14-XXX-230-08 and later) 34...
Defrost System (XP14-XXX-230-08 and later) 36.....
Maintenance 42..................................
Start-up and Performance Checklist 47.............
Unit Wiring Diagram and Sequence of
Operations 43....................................
The XP14 is a high efficiency residential split-system heat pump unit, which features a scroll compressor and HFC-410A refrigerant. XP14 units are available in sizes ranging from 1-1/2 through 5 tons. The series is designed for use with an indoor unit with an check expansion valve approved for HFC-410A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
Page 1
This unit must be matched with an indoor coil as specified in Lennox XP14 Engineering Handbook. Coils previously charged with HCFC-22 must be flushed.
IMPORTANT
Page 2
Model Number Identification
P 14 XXX
X 2
Refrigerant Type
X = HFC-410A
Unit Type
P = Heat Pump Outdoor Unit
Series
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008 09 = 2009 10 = 2010
19 09 C
Specifications
0
230
Voltage
230 = 208/230V-1ph-60hz
Nominal Cooling Capacity
018 = 1.5 tons 024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons
05716
Month Code
A = January B = February C = March
Minor Revision Number
5 (or 6) Digit Unique Number
Unit Outdoor Fan
Model Number
XP14-018-230-01, -03, -06, -07 71 8 lbs. 4 oz. 3 18
XP14-018-230-08 71 6 lbs. 11 oz. 3 18
XP14-018-230-09 71
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Model Number
XP14-024-230-01, -03, -06, -07 71 8 lbs. 0 oz. 3 18
XP14-024-230-08 71 6 lbs. 4 oz. 3 18
XP14-024-230-09 71
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Model Number
XP14-030-230-01 through -07 71 7 lbs. 2 oz. 3 18
XP14-030-230-08 71 6 lbs. 0 oz. 3 18
XP14-030-230-09 71
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Sound Rating Number
Sound Rating Number
Sound Rating Number
(dB)
(dB)
(dB)
1
1
1
Factory Refrigerant
6 lbs. 11 oz. or
5 lbs. 11 oz.
Unit Outdoor Fan
Factory Refrigerant
6 lbs. 4 oz. or
5 lbs. 14 oz.
Unit Outdoor Fan
Factory Refrigerant
6 lbs. 0 oz. or
5 lbs. 10 oz.
Charge
Charge
Charge
2
3
2
3
2
3
Number of Blades Diameter - inches.
3 18
Number of Blades Diameter - inches.
3 18
Number of Blades Diameter - inches.
3 18
Page 2
Page 3
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
XP14-036-230-01, -02, -08, -09 71 9 lbs. 12 oz. 3 22
XP14-036-230-10 71
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
9 lbs. 12 oz. or
9 lbs. 6 oz.
3
3 22
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
XP14-042-230-01, -02 71 12 lbs. 7 oz. 4 26
XP14-042-230-08 71 11 lbs. 14 oz. 3 26
XP14-042-230-09 71
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
11 lbs. 14 oz. or
11 lbs. 8 oz.
3
3 26
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
XP14-048-230-01 73 12 lbs. 10 oz. 4 26
XP14-048-230-08 73 10 lbs. 7 oz. 3 26
XP14-048-230-09 73
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
10 lbs. 7 oz. or
10 lbs. 1 oz.
3
3 26
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
XP14-060-230-01 73 16 lbs. 0 oz. 4 26
XP14-060-230-08 73 12 lbs. 11 oz. 3 26
XP14-060-230-09 73
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
12 lbs. 11 oz. or
12 lbs. 5 oz.
3
3 26
Page 3
XP14 SERIES
Page 4
Electrical Data
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Maximum
Model Number Label Rev.
XP14-018-230-01
XP14-018-230-02 1.0 20 11.9 8.97 48.0 1/10 1075 0.7 1.4
XP14-018-230-03 1.0 20 11.9 8.97 48.0 1/10 1075 0.7 1.4
XP14-018-230-06 1.0 20 11.9 8.97 48.0 1/10 1075 0.7 1.4
XP14-018-230-07
XP14-018-230-08
XP14-018-230-09
Model Number Label Rev.
XP14-024-230-01 1.0 & 2.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
XP14-024-230-02 1.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
XP14-024-230-03 1.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
XP14-024-230-06 1.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
XP14-024-230-07
XP14-024-230-08
XP14-024-230-09
1.0, 2.0 &
3.0
1.0 20 11.9 8.97 48.0 1/10 1075 0.7 1.4
2.0 20 12.3 9.00 48.0 1/10 1075 0.7 1.4
3.0 20 12.2 9.00 48.0 1/10 1075 0.7 1.4
1.0 20 11.9 8.97 48.0 1/10 1075 0.7 1.87
2.0 20 12.3 8.96 48.0 1/6 825 1.1 1.87
3.0 20 12.3 8.96 48.0 1/6 825 1.1 1.87
1.0 20 12.3 8.96 48.0 1/6 825 1.1 1.87
2.0 20 12.3 9.00 48.0 1/6 825 1.1 1.87
3.0 20 12.2 9.00 48.0 1/6 825 1.0 1.87
1.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
2.0 30 17.9 13.50 58.0 1/10 1075 0.7 1.4
3.0 30 17.8 13.50 58.0 1/10 1075 0.7 1.4
1.0 30 17.5 13.46 58.0 1/10 1075 0.7 1.4
2.0, 3.0 &
4.0
1.0 & 2.0 30 17.9 13.44 58.0 1/6 825 1.1 1.87
3.0 30 17.9 13.50 58.0 1/6 825 1.1 1.87
Over-
current
Protection
(amps)
20 11.9 8.97 48.0 1/10 1075 0.7 1.4
Maximum
Over-
current
Protection
(amps)
30 17.9 13.44 58.0 1/6 825 1.1 1.87
Minimum
Circuity
Ampacity
1
Unit Compressor Condenser Fan
Minimum
Circuity
Ampacity
1
Rated
Load
Amps
2
(RLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Locked
Rotor Amps (LRA)
Motor HP
Motor HP
Nominal
RPM
Nominal
RPM
Full Load
Amps (FLA)
Full Load
Amps (FLA)
Locked
Rotor Amps
(LRA)
Locked
Rotor Amps (LRA)
Page 4
Page 5
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
XP14-030-230-01
1.0, 2.0 &
3.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
30 17.0 13.1 64.0 1/10 1075 0.7 1.4
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
XP14-030-230-02 1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
XP14-030-230-03 1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
XP14-030-230-05
1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
2.0 30 19.4 14.1 64.0 1/10 1075 0.7 1.4
XP14-030-230-06 1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
XP14-030-230-07
2.0 30 17.5 13.1 64.0 1/10 1075 0.7 1.4
3.0 30 17.4 13.1 64.0 1/10 1075 0.7 1.4
XP14-030-230-08
1.0 30 17.0 13.1 64.0 1/10 1075 0.7 1.4
2.0 & 3.0 25 17.1 12.8 64.0 1/6 825 1.1 1.87
1.0 25 17.1 12.8 64.0 1/6 825 1.1 1.87
XP14-030-230-09
2.0 30 17.5 13.1 64.0 1/6 825 1.1 1.87
3.0 30 17.4 13.1 64.0 1/6 825 1.1 1.87
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
XP14-036-230-01
1.0, 2.0 &
3.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
30 19.4 14.1 77.0 1/3 825 1.8 2.9
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
XP14-036-230-02 1.0 30 19.4 14.1 77.0 1/3 825 1.8 2.9
XP14-036-230-08
1.0 30 19.4 14.1 77.0 1/3 825 1.8 2.9
2.0 30 18.7 14.08 77.0 1/6 825 1.1 1.87
XP14-036-230-09 1.0 30 18.7 14.08 77.0 1/6 825 1.1 1.87
XP14-036-230-10 1.0 & 2.0 30 18.7 14.08 77.0 1/6 825 1.1 1.87
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
XP14-042-230-01
1.0 40 23.9 17.69 107.0 1/3 825 1.8 2.9
2.0 & 3.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
XP14-042-230-02 1.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
1.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
XP14-042-230-08
XP14-042-230-09
2.0, 3.0 &
4.0
40 24.2 17.92 112.0 1/3 825 1.8 2.9
1.0 40 24.2 17.92 112.0 1/3 825 1.8 2.9
2.0 40 24.2 18.0 112.0 1/3 825 1.8 2.9
Page 5
XP14 SERIES
Page 6
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
XP14-048-230-01
1.0, 2.0 &
3.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
50 29.0 21.79 117.0 1/3 825 1.8 2.1
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
XP14-048-230-02 1.0 50 29.0 21.79 117.0 1/3 825 1.8 2.1
XP14-048-230-08 1.0 50 29.0 21.76 117.0 1/3 825 1.8 2.1
XP14-048-230-09
1.0 50 29.0 21.79 117.0 1/3 825 1.8 2.1
2.0 & 3.0 50 29.0 21.76 117.0 1/3 825 1.8 2.1
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
XP14-060-230-01 1.0 & 2.0 60 34.8 26.41 134.0 1/3 825 1.8 2.1
XP14-060-230-03 1.0 60 34.8 26.41 134.0 1/3 825 1.8 2.1
1.0 60 34.8 26.41 134.0 1/3 825 1.8 2.1
XP14-060-230-08
2.0, 3.0 &
4.0
50 29.4 22.10 125.0 1/3 825 1.8 2.1
XP14-060-230-09 1.0 60 29.4 26.41 125.0 1/3 825 1.8 2.1
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 6
Page 7
Unit Dimensions - Inches (mm)
A
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
C
4-3/4”
(121)
B
TOP VIEW
SIDE VIEW
4-1/2”
(108)
Table 1. XP14-XXX-230-01 through 07
Model Number
XP14-018-230 31 (787)
XP14-024-230 31 (787)
XP14-030-230 35 (889)
XP14-036-230 31 (787)
XP14-042-230 39 (991)
XP14-048-230 39 (991)
XP14-060-230 45 (1143)
A B C
27 (686) 28 (711)
35-1/2 (902) 39-1/2 (1003)
Table 2. XP14-XXX-230-08 / -09
Model Number A B C
XP14-018-230 39 (991)
XP14-024-230 39 (991)
XP14-030-230 39 (991)
XP14-036-230 35 (889)
XP14-042-230 39 (991)
XP14-048-230 39 (991)
XP14-060-230 45 (1143)
30-1/2 (775) 35 (889)
35-1/2 (902) 39-1/2 (1003)
UNIT SUPPORT FEET
13-7/8
(352)
7-3/4 (197)
3-1/4
(83)
27-1/8
(689)
XP14-018 AND -036 BASE WITH
ELONGATED LEGS (MEDIUM)
UNIT SUPPORT FEET
20-5/8
K
(524)
4-1/2
J
(114)
3-5/8
(92)
Page 7
16-7/8
(429)
8-3/4 (222)
3-1/8
(79)
30-3/4
(781)
XP14-042 TO -060 BASE WITH
ELONGATED LEGS (LARGE)
26-7/8
(683)
3-3/4
(95)
4-5/8 (117)
XP14 SERIES
Page 8
Typical Unit Parts Arrangement
CONTROL PANEL
CONTACTOR-1POLE
GROUND LUG
CONTROL (A108)
(K1-1)
DEFROST
CAPACITOR (C12)
AMBIENT SENSOR (RT13)
COMPRESSOR HARNESS
THERMOSTAT (S40) (-036,
-042, -048 AND 060 UNITS
CONNECTION
MUFFLER
CRANKCASE HEATER
ONLY)
REVERSING VALVE
REVERSING VALVE
SOLENOID
LOW PRESSURE
SWITCH (S87)
5-TON UNIT
EXAMPLED HERE
CHECK EXPANSION VALVE
SENSING BULB
COMPRESSOR (B1)
COIL TEMPERATURE
SENSOR (RT21) - 6TH
HAIRPIN UP ON INSIDE ROW.
CHECK EXPANSION VALV E
LIQUID LINE FILTER DRIER (BI-FLOW)
CRANKCASE HEATER (-036, -042, -048 AND -060 UNITS ONLY)
HIGH PRESSURE SWITCH (AUTO-RESET) (S4)
TRUE SUCTION PORT
VAPOR LINE SERVICE VALV E
FIELD CONNECTION FOR VAPOR LINE
LIQUID LINE SERVICE
PLUMBING, SWITCHES AND SENSOR COMPONENTS
Figure 1. Typical Parts Arrangements (XP14-XXX-230-01 through 07)
VALV E
FIELD CONNECTION
FOR LIQUID LINE SET
Page 8
Page 9
CONTROL PANEL
CAPACITOR (C12)
CONTACTOR-
1POLE (K1-1)
GROUND
LUG
TRUE SUCTION
PORT
REVERSING
VALV E
MUFFLER
5-TON UNIT
EXAMPLED HERE
DEFROST CONTROL (CMC1)
ONLY ON UNITS
USING EXTERNAL
COMPRESSOR
THERMAL
PROTECTION
SWITCH (S173)
SWITCH
COVER
SWITCH
DEFROST THERMOSTAT (S6)
CHECK EXPANSION VALV E
REVERSING VALVE
SOLENOID
CRANKCASE HEATER
(-036, -042, -048 AND
060 UNITS ONLY)
LOW PRESSURE
SWITCH (S87)
LIQUID LINE FILTER DRIER (BI-FLOW)
CHECK EXPANSION VALVE SENSING BULB
CRANKCASE HEATER THERMOSTAT (S40) (-036, -042, -048 AND 060 UNITS ONLY)
HIGH PRESSURE SWITCH (AUTO-RESET) (S4)
VAPOR LINE SERVICE
LIQUID LINE
SERVICE VALVE
FIELD CONNECTION FOR VAPOR LINE (ANGLE-TYPE - ALL SIZES EXCEPT -060)
FIELD CONNECTION
FOR LIQUID LINE SET
PLUMBING, SWITCHES AND
VALV E
FIELD CONNECTION FOR VAPOR LINE (BALL-TYPE -060 ONLY)
SENSOR COMPONENTS
Figure 2. Typical Parts Arrangements (XP14-XXX-230-08)
Page 9
XP14 SERIES
Page 10
The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 3 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc ­Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C-08-1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Table 3. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.- lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 psig on the high side and a low side of 30” vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory-installed valve stem. Figure 3 provides information on how to access and operating both angle and ball service valves.
Page 10
Page 11
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CORE
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is open to the line set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
STEM CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
When service valve is CLOSED, the service port is open to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
With torque wrench: Finger tighten and
torque cap per table 3.
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
9
10
8
11
12
7
6
With torque wrench: Finger tighten and
then torque cap per table 3.
Without torque wrench: Finger tighten
and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
9
10
8
11
12
7
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
3
4
5
NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball Service Valves
Page 11
XP14 SERIES
Page 12
Recovering Refrigerant from System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
12
switch or main fuse box/breaker panel.
MAIN FUSE BOX/BREAKER PANEL
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing HCFC-22 refrigerant using one of the following procedures:
3
IMPORTANT — Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use the existing HCFC-22 to flush the system.
Remove all HCFC-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut-off valves, and you plan to use new HCFC-22 refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit's high or low-pressure switches (if applicable) when tripped can cycle the compressor OFF. Compressor can stop pumping due to tripped internal pressure relief valve. Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and
internal seals.) Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task: A Start the existing HCFC-22 system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC-22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE — It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve. D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Figure 4. Refrigerant Recovery
Page 12
Page 13
See NOTES
NOTES:
Service clearance of 30 in. must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
See
NOTES
See NOTES
See
NOTES
Control
Box
Clearance to one of the remaining two sides may be 12 in. and the final side may be 6 in.
A clearance of 24 in. must be maintained between two units.
48 in. clearance required on top of unit.
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
Figure 5. Installation Clearances
PLACING UNIT ON SLAB
Unit Placement
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
should have a slope tolerance as described in figure 6, detail B.
NOTE — If necessary for stability, anchor unit to slab as described in figure 6, detail D.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 5 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 6, detail A.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 6, detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE — Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
Page 13
XP14 SERIES
Page 14
DETAIL A
Install unit away from windows.
— Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.
— Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
DETAIL C
Elevated Slab Mounting
using Feet Extenders
LEG DETAIL
2” (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
BASE
GROUND LEVEL
STABILIZING UNIT ON UNEVEN SURFACES
DETAIL D
#10 1/2” LONG SELF-DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL — 2” WIDTH; HEIGHT AS
#10 1-1/4” LONG HEX HD SCREW
Concrete slab — use two plastic anchors (hole drill 1/4”)
Wood or plastic slab — no plastic anchor (hole drill 1/8”)
DETAIL E
Stabilizing bracket (18 gauge metal — 2” (50.8mm) width; height as required); bend to form right angle as exampled below.
— Slab Side Mounting
REQUIRED)
AND FLAT WASHER
— Deck Top Mounting
MINIMUM ONE
PER SIDE
COIL
BASE PAN
CORNER POST
2” (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2” SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
IMPORTANT — To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
Figure 6. Placement, Slab Mounting and Stabilizing Unit
SAME FASTENERS AS SLAB SIDE MOUNTING.
One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.
FOR EXTRA
STABILITY
Page 14
Page 15
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field-provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
With unit positioned at installation site, perform the following:
1. Remove two side louvered panels to expose the unit base.
2. Install the brackets as illustrated in figure 6, detail D or E using conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
Removing and Installing Panels
IMPORTANT
Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
IMPORTANT
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
Page 15
XP14 SERIES
Page 16
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slight ly.
2. Hold the panel firmly throughout this procedure. Rotate bot tom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as illus
trated in detail A and C; then upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
DETAIL A
DETAIL B
ANGLE MAY BE TOO EXTREME
HOLES
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
HOLD DOOR FIRMLY TO THE HINGED
PANEL
SIDE TO MAINTAIN
FULLY-ENGAGED TABS
PREFERRED ANGLE FOR INSTALLATION
Figure 7. Removing and Installing Panels
Page 16
Page 17
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 19.
IMPORTANT
NOTE — When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351-L9, or contact Lennox Technical Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to communicate the following information:
Model (XP14) and size of unit (e.g. -036).
Lennox highly recommends changing line set when converting the existing system from HCFC-22 to HFC-410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high-efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 4 may be reused. If system was previously charged with HCFC-22 refrigerant, then existing line set must be flushed (see Flushing the System on page 22).
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non-flare) series line set, or field-fabricated refrigerant line sizes as listed in table 4.
Table 4. Refrigerant Line Set — Inches (mm)
Model
-018
-024
-030
-036
-042
-048
-060
Valve Field Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
7/8 in. (22 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
7/8 in. (22 mm)
L15 Line Sets
L15-41 15 ft. - 50 ft. (4.6 m - 15 m)
L15-65 15 ft. - 50 ft. (4.6 m - 15 m)
Field Fabricated
Line set diameters for the unit being installed as listed
in table 4 and total length of installation.
Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds - add one ounce of every five pounds of refrigerant.
Recommended topping-off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATE RL32CF.
Polyol Ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil
must be added, it must be a Polyol Ester oil.
Page 17
XP14 SERIES
Page 18
Line Set Isolation — The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
WALL
STUD
NON-CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER‐TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
VAPOR LINE - WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON-CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE — Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID LINE
NOTE — Similar installation practices should be used if line set is to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON-CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
ROOF RAFTER
Figure 8. Line Set Installation
Page 18
Page 19
Brazing Connections
Use the procedures outline in figures 9 and 10 for brazing line set connections to service valves.
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture - Check the high and low pressures before applying heat.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper-to-copper brazing. Use 45% minimum alloy for copper-to-brass and copper-to-steel brazing.
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex plosion, that could result in property damage, personal injury or death.
Page 19
XP14 SERIES
Page 20
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT
CORE
LIQUID LINE SERVICE
VALV E
SERVICE
PORT CORE
SERVICE PORT CAP
SUCTION / VAPOR LINE
SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.
A Connect gauge set low pressure side to
liquid line service valve (service port).
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
ATTACH
GAUGES
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
HIGHLOW
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
Figure 9. Brazing Procedures
Page 20
Page 21
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.
6
Water-saturated cloths must remain water-saturated throughout the brazing and cool-down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT — Allow braze joint to cool. Apply
additional water saturated-cloths to help cool brazed joint. Do not remove water-saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER-SATURATED CLOTH
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a
water-saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated. Refer to procedures provided in this supplement.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water-saturated cloths. Refer to the unit installation instructions for the next step in preparing the unit.
SUCTION / VAPOR LINE
SERVICE VALVE
WATER-SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 10. Brazing Procedures (continued)
Page 21
XP14 SERIES
Page 22
Flushing Line Set and Indoor Coil
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor as
sembly.
C Using two wrenches, disconnect liquid line from liquid line orifice hous
ing. Take care not to twist or damage distributor tubes during this pro cess.
D Remove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
E Use a field-provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.
COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
TEFLON® RING
FIXED ORIFICE
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE (UNCASED
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INVERTED HCFC-22 CYLINDER CONTAINS CLEAN HCFC-22* TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
VAPOR
LIQUID
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY
CYLINDER
A Inverted HCFC-22 cylinder with clean refrigerant* to the vapor service
valve.
B HCFC-22 gauge set (low side) to the liquid line valve. C HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
RECOVERY MACHINE
GAUGE
MANIFOLD
LOW HIGH
CLOSED
TANK RETURN
INLET
DISCHARGE
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
SENSING
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line. D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
line assembly. F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process. G Remove and discard check expansion valve and the two Teflon® rings. H Use a field-provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant* that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line
B
set and indoor unit coil.
B Invert the cylinder of clean HCFC-22* and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D Close the valve on the inverted HCFC-22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
®
LINE
LIQUID
LINE
Figure 11. Installing Indoor Expansion Valve
Page 22
Page 23
Installing Indoor Metering Device
This outdoor unit is designed for use in systems that use check expansion valve metering devices at the indoor coil.
See the Lennox XP14 Engineering Handbook for approved expansion valve kit match-ups. The expansion valve unit can be installed internal or external to the indoor
coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
LINE
TEFLON
RING
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
A Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
B Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
®
SENSING
LINE
A Remove the field-provided fitting that temporary
reconnected the liquid line to the indoor unit's distributor
assembly. B Install one of the provided Teflon® rings around the
stubbed end of the expansion valve and lightly lubricate
the connector threads and expose surface of the Teflon
ring with refrigerant oil. C Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft-lb. D Place the remaining Teflon® washer around the other
end of the expansion valve. Lightly lubricate connector
threads and expose surface of the Teflon® ring with
refrigerant oil. E Attach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to
turn an additional 1/2 turn clockwise as illustrated in the
figure above or 20 ft-lb.
SENSING BULB INSTALLATION
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE — Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the expansion valve to
the equalizer vapor port on the vapor line. Finger tighten
the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN 7/8”, MOUNT SENSING BULB AT EITHER THE 3 OR 9 O'CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
Figure 12. Installing Indoor Expansion Valve
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
Page 23
VAPOR LINE
12
BULB
NOTE — NEVER MOUNT ON BOTTOM OF LINE.
ON 7/8” AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O'CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
XP14 SERIES
Page 24
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
CONNECT GAUGE SET
A Connect an HFC-410A manifold gauge set high pressure
1
hose to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of
HFC-410A refrigerant to the center port of the manifold gauge set.
NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
Leak Test Line Set and Indoor Coil
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
A
TO VAPOR
SERVICE VALVE
NITROGEN
HFC-410A
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the
2
following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve
on the HFC-410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [A
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak
detector.
F After leak testing disconnect gauges from service ports.
Figure 13. Leak Test
Page 24
Page 25
Evacuating Line Set and Indoor Coil
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not already done).
1
A Connect low side of manifold gauge set
with 1/4 SAE in-line tee to vapor line service valve
B Connect high side of manifold gauge
set to liquid line service valve
C Connect micron gauge available
connector on the 1/4 SAE in-line tee.
D Connect the vacuum pump (with
vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC-410A and nitrogen containers.
NITROGEN
HFC-410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
D
EVACUATE THE SYSTEM
A Open both manifold valves and start the vacuum pump.
2
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves Close valve on vacuum pump Turn off vacuum pump Disconnect manifold gauge center port hose from vacuum pump Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open manifold gauge valves to break the vacuum in the line set and indoor unit. Close manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
Close manifold gauge valves. Shut off HFC-410A cylinder. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.
RECOMMEND
MINIMUM 3/8” HOSE
10
9
11
8
7
1/6 TURN
12
1
5
6
HIGHLOW
2
3
4
Figure 14. Evacuating System
Page 25
XP14 SERIES
Page 26
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under
temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low‐voltage control power (24VAC - 40 VA minimum)
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE — Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
UNIT LOW VOLTAGE CONNECTIONS
3
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE — 24VAC, Class II circuit connections are made in the control panel.
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
A
D
B
C
TERMINAL STRIP
Page 26
ARun 24VAC control wires through cutout with grommet. BRun 24VAC control wires through wire tie. CMake 24VAC control wire connections defrost control terminal strip. DTighten wire tie to security 24V control wiring.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
Page 27
Servicing Units Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedure outlined on page
24.
2. Evacuate the system using procedure outlined on page 25.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again using procedure outlined on page 25.
5. Weigh in refrigerant using procedure outlined in figure
17.
6. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Unit Start-Up
2. Inspect all factory- and field-installed wiring for loose connections.
3. After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in table 3.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerant by using the procedures listed under System Charge.
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
REFRIGERANT TANK
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
INSIDE OUTDOOR UNIT
TEMPERATURE
D
SENSOR
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
MANIFOLD GAUGE SET
LOW
HIGH
OUTDOOR UNIT
A
C
TO LIQUID
LINE SERVICE
VALV E
TEMPERATURE SENSOR
(LIQUID LINE)
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC-410A. Set for liquid phase charging.
BConnect the manifold gauge set's low pressure side to the true suction port. See figure 1 for approximate location of the true suction port.
CConnect the manifold gauge set's high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port.
Figure 15. Gauge Set Setup and Connections
Page 27
XP14 SERIES
Page 28
ADDING OR REMOVING REFRIGERANT
This system uses HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The pre-installed liquid line filter drier is approved for use with HFC-410A only. Do not replace it with components designed for use with HCFC-22. This unit is NOT approved for use with coils which use capillary tubes or fixed orifices as a refrigerant metering device.
Check airflow using the Delta-T (DT) process using the illustration in figure 16.
AIRFLOW
INDOOR COIL
Temperature of air entering indoor coil ºF
A
Wet-bulb ºF
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
Dry-bulb
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
DRY
BULB
C
53º
T
19º
Drop
air flow
air flow
B
B
64º
All temperatures are expressed in ºF
INDOOR COIL
WET BULB
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. Determine the desired DT — Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coil — Measure the coil's dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustment — If the difference between the measured T
DT (T
DT) is within +3º, no adjustment is needed. See example below:
Drop
) = A minus C.
Drop
and the desired
Drop
Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
A
72º
DRY BULB
T
53º 19 – 15 = 4 Increase the airflow 58º 14 15 = -1 (within +3º range) no change 62º 10 15 = -5 Decrease the airflow
DT = ºF ACTION
Drop
4. Adjust the fan speed — See indoor unit instructions to increase/decrease fan speed.
Figure 16. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Page 28
Page 29
WEIGH IN
CHARGING METHOD
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refriger ant charge:
Amount specified on
nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
+
Additional charge specified per indoor
unit match-ups starting on pages 29
and 30.
+
Total Charge
=
Refrigerant Charge per Line Set Length
LIQUID LINE SET DIAMETER
3/8” (9.5 MM)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
NOTE — Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE — The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M)
3 OUNCE PER 5' (85 G PER 1.5 M)
LINE SET*
Figure 17. Using HFC-410A Weigh In Method
SUBCOOLING
1 Check the airflow as illustrated in figure 16 to be sure the indoor airflow is as required. (Make any air flow
adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check
charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures tables. (The
reference tables are a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling mode—When the outdoor ambient temperature is 60°F (15°C) and above. Target subcooling
values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6.
Using heating mode—When the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values in table below are based on 65-75°F (18-24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart listed
in table 9 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with match up tables being sure to note any additional charge for line set and/or match-up.
10 If subcooling value is greater than shown in the match up tables for the applicable unit, remove refrigerant; if less
than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
12 Disconnect gauge set and re-install both the liquid and suction service valve caps.
SATº LIQº – SCº =
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
Figure 18. Using Subcooling Method
Page 29
XP14 SERIES
Page 30
Table 5. Unit Indoor Matchups for Subcooling (XP14-XXX-230-01 through 07)
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)   (+1ºF)
*Add
charge
INDOOR MATCHUPS
XP14018 lb oz XP14030 (Continued) lb oz XP14042 (Continued) lb oz
CBX27UH-018/024 13 7 0 8 CH33-42B 6 6 1 12 CR33-50/60C,-60D 26 6 0 4 CBX32MV-018/024 15 7 0 0 CR33-30/36A/B/C 30 8 0 8 CX34-62C, -62D 12 6 0 9 CBX40UHV-024 15 7 0 0 CX34-31A/B 11 6 1 6 CX34-49C 12 6 0 7
XP14024 lb oz
CBX26UH-024 25 7 0 0
CX34-38A/B S/N# 6007
and after
CX34-38A/B Before S/N#
6007
CBX27UH-018/024 15 8 1 2 CX34-43B/C 15 11 2 14 CBX26UH-048 8 7 1 9 CBX32M-018/024 16 8 0 14 XP14036 lb oz CBX27UH-048 11 8 1 2 CBX32M-030 15 8 1 3 C33-44C 13 6 0 0 CBX32M-048, -060 11 8 1 2 CBX32MV-018/024 16 8 0 14 CBX26UH-036 26 5 0 0 CBX32MV-048 25 8 0 0 CBX32MV-024/030 15 8 1 2 CBX26UH-037 25 4 1 9 CBX32MV-060 11 8 1 2 CBX40UHV-024 16 8 0 14 CBX27UH-036 13 6 0 3 CBX40UHV-048 25 8 0 0 CBX40UHV-030 15 8 1 2 CBX32M-036 13 6 0 2 CBX40UHV-060 11 8 1 2 CH23-41 16 8 0 2 CBX32M-042 13 6 0 3 CBX32MV-068 10 7 1 12 CH33-25A 16 6 0 7 CBX32MV-036 13 6 0 3 CH23-68 20 9 2 9 CH33-42B 14 11 1 10 CBX32MV-048 11 8 2 5 CH33-50/60C 11 8 1 1 CH33-36A 16 8 1 0 CBX40UHV-036 13 6 0 3 CH33-62D 10 7 1 14 CH33-36C 16 8 0 4 CBX40UHV-042, -048 11 8 2 5 CH33-60D 11 8 0 0 CR33-30/36A/B/C 25 7 0 2 CH33-50/60C 11 8 2 5 CR33-50/60C 35 5 0 0 CX34-25A/B 16 8 0 14 CH33-44B 13 6 1 7 CR33-60D 37 6 0 0 CX34-31A/B 15 8 1 3 CH33-48B 13 6 1 8 CX34-62C, -62D 10 7 1 7 CX34-36A/B/C 16 8 1 8 CR33-50/60C 25 4 1 15 CX34-49D 11 8 0 14 CX34-38A/B S/N# 6007
and after
CX34-38A/B before S/N#
6007
11 11 2 2 CR33-48B/C 25 5 0 9 CX34-60D 11 8 0 0
14 11 2 2 CX34-49C 13 6 2 4 XP14060 lb oz
XP14030 lb oz CX34-43B/C, -50/60C 13 6 1 8 CBX26UH-048 12 7 1 0
CH23-41 11 6 0 8
CH23-51 6 6 1 12
CX34-38A/B S/N# 6007
and after
CX34-38A/B before S/N#
6007
CBX26UH-024 30 8 0 6 XP14042 lb oz CBX32M-048, -060 12 5 0 0 CBX26UH-030 29 8 2 3 CH23-68 20 9 0 13 CBX32MV-048, -060 12 5 0 0 CBX27UH-030 11 6 2 4 CBX26UH-042 27 6 0 0 CBX40UHV-048, -060 12 5 0 0 CBX32M-030 11 6 1 6 CBX27UH-042 12 6 0 8 CBX32MV-068 12 7 1 0 CBX32M-036 11 6 2 4 CBX32M-048 12 6 0 7 CH23-68 12 5 0 0 CBX32MV-024/030 11 6 1 6 CBX32MV-048 12 6 0 8 CH33-50/60C 12 5 0 0 CBX32MV-036 15 7 3 0 CBX40UHV-042, -048 12 6 0 8 CH33-62D 12 5 0 0 CBX40UHV-024, -030 11 6 1 6 CH33-43 12 6 0 7 CX34-62C, -62D 12 7 1 0 CBX40UHV-036 15 7 3 0 CH33-62D 12 6 0 10
C33-44C 11 6 2 3 CH33-50/60C 12 6 0 7
CH33-36C 11 3 0 0 CH33-60D 12 6 0 4
Target
Subcooling
HeatingCooling
(+5ºF)   (+1ºF)
*Add
charge
INDOOR MATCHUPS
Target
Subcooling
HeatingCooling
(+5ºF)   (+1ºF)
*Add
charge
6 6 2 3 CX34-60D 12 6 0 4
11 6 2 3 XP14048 lb oz
6 6 0 0 CBX26UH-060 14 4 0 0
13 6 0 0 CBX27UH-060 12 5 0 0
*Add charge = Extra matchup amount required in addi tion to charge indicated on Heat Pump nameplate (re member to also add any charge required for line set differences from 15 feet). SN indicates serial number.
Page 30
Page 31
Table 6. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG* (XP14-XXX-230-01 through 07)
IMPORTANT
Use table 8 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal lations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
XP14-018 XP14-024 XP14-030 XP14-036 XP14-042 XP14-048 XP14-060
5F (5C)**
60 (15) 346 / 139 352 / 138 338 / 137 350 / 134 373 / 139 355 / 130 351 / 117
50 (10) 323 / 117 331 / 114 334 / 112 331 / 117 363 / 117 336 / 113 333 / 105
40 (4) 306 / 98 304 / 99 312 / 93 313 / 97 348 / 97 315 / 88 316 / 88
30 (-1) 278 / 84 299 / 80 302 / 74 298 / 83 336 / 74 296 / 72 308 / 70
20 (-7) 273 / 66 283 / 66 280 / 53 284 / 66 322 / 64 286 / 64 300 / 61
65 (18) 226 / 140 233 / 137 238 / 138 220 / 138 223 / 125 231 / 136 243 / 136
70 (21) 244 / 141 252 / 138 263 / 139 236 / 140 241 / 130 248 / 139 263 / 137
75 (24) 263 / 142 271 / 140 279 / 139 256 / 141 261 / 134 271 / 140 282 / 138
80 (27) 283 / 143 292 / 141 299 / 140 276 / 142 282 / 138 291 / 142 306 / 139
85 (29) 302 / 144 314 / 142 324 / 141 298 / 143 302 / 139 312 / 143 327 / 140
90 (32) 328 / 145 338 / 143 340 / 142 321 / 144 326 / 140 335 / 144 351 / 141
95 (35) 351 / 146 361 / 145 375 / 145 344 / 144 349 / 141 359 / 145 376 / 142
100 (38) 376 / 147 387 / 146 397 / 145 369 / 146 374 / 142 384 / 146 401 / 143
105 (41) 402 / 148 412 / 147 424 / 147 394 / 147 399 / 143 411 / 148 426 / 145
110 (38) 430 / 149 441 / 148 454 / 150 421 / 148 428 / 145 439 / 149 452 / 146
115 (45) 465 / 150 471 / 151 485 / 150 449 / 149 455 / 146 468 / 150 484 / 148
*IMPORTANT—These are most popular match-up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary. **Temperature of the air entering the outside coil.
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid/ Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
Heating
Cooling
Page 31
XP14 SERIES
Page 32
Table 7. Indoor Unit Matches, Targeted Subcooling, and Add Charge Values (XP14-XXX-230-08 or higher)
HP
Indoor Coil or Air
SIZE
Handler
CBX27UH-018 13 14 1 9
CBX27UH-024 13 14 1 9 CH33-43C 4 9 1 12 CH33-62D 19 7 1 7
CBX32MV-018/024 12 14 0 0 CR33-30, -36 22 5 1 0 CR33-50, -60 29 5 0 4
CH33-25A 14 14 0 7 CX34-31 17 15 2 10 CR33-60D 29 5 0 4
-018 CH33-25B 14 13 0 5 CX34-36 25 6 0 10 CX34-49 11 6 1 4
CR33-30/36 12 5 0 7 CX34-38 10 19 2 14 CX34-50, -60 25 8 1 15
CX34-25 15 15 1 1 CX34-42 25 6 0 10 CX34-60 8 8 1 4
CX34-31 14 24 1 12 CX34-43 13 17 2 14 CX34-62C 8 11 3 10
CBX25UH-024 6 6 0 9 CX34-44, -48 9 21 2 12 CX34-62D 11 7 1 15
CBX25UH-030 17 3 0 15
CBX26UH-024 17 3 0 15 CBX26UH-036 31 3 0 4 CBX26UH-048 20 10 3 11
CBX27UH-024 12 12 1 2 CBX27UH-036 18 3 0 5 CBX27UH-048 16 6 0 0
CBX32M-018, -024 14 11 0 4 CBX27UH-042 11 4 0 1 CBX27UH-060 12 6 1 4
CBX32M-030 12 12 1 2 CBX27UH-048 11 4 0 1 CBX32M-048 16 6 0 0
CBX32MV-018/024 14 11 0 4 CBX32M-036 18 3 0 5 CBX32M-060 20 8 1 0
CBX32MV-024/030 12 12 1 2 CBX32M-042 18 3 0 5 CBX32MV-048 16 6 0 0
CBX32MV-036 11 11 2 1 CBX32MV-036 18 3 0 5 CBX32MV-060 20 8 1 0
CBX40UHV-024 11 11 2 1 CBX32MV-048 11 4 0 1 CBX32MV-068 10 8 4 5
CBX40UHV-030 11 11 2 1 CBX40UHV-042 11 4 0 1 CBX40UHV-048 16 6 0 0
-024 CH23-41 10 3 0 0 CBX40UHV-048 11 4 0 1 CBX40UHV-060 20 8 1 0
CH33-25A 20 10 1 1 CBX40UHV-036 18 3 0 5 CH23-68 24 6 2 8
CH33-25B 19 8 1 2 CH33-43B 14 8 2 1 CH33-50, -60C 17 6 1 5
CH33-31A 15 11 1 15 CH33-43C 26 9 2 10 CH33-60D 18 6 0 13
CH33-36C 10 12 0 0 CH33-44/48B 24 8 2 3 CH33-62D 13 7 3 6
CH33-36A 20 10 1 1 CH33-48C 26 9 2 10 CR33-50/60 19 6 1 1
CR33-30, -036 17 4 0 14 CH33-49C 15 8 2 12 CR33-60 19 6 1 1
CX34-25 15 9 0 15 CH33-50/60C 15 8 2 12 CX34-49C 10 6 1 9
CX34-31 15 16 0 9 CR33-48 38 5 0 0 CX34-60 28 7 3 14
CX34-36 26 6 0 9 CR33-50, -60 15 5 1 4 CX34-62C 10 6 3 12
CX34-38 10 18 1 14 CX34-38 15 4 0 9 CX34-62D 14 7 3 12
CBX25UH-030 9 3 0 8 CX34-43 23 8 2 8
CBX25UH-036 19 11 1 5 CX34-44/48 40 4 0 15 CBX26UH-060 31 6 3 0
CBX26UH-030 19 11 1 5 CX34-49 11 7 3 9 CBX27UH-060 13 7 0 8
CBX27UH-030 10 16 1 14 CX34-50/60 23 8 2 8 CBX32M-060 17 5 1 4
CBX27UH-036 10 16 1 14
CBX32M-030 15 4 2 7 CBX26UH-042 42 5 0 8 CBX32MV-060 17 5 1 4
CBX32M-036 10 16 1 14 CBX27UH-042, -048 13 5 2 2 CBX32MV-068 11 8 2 12
CBX32MV-024, -030 15 4 2 7 CBX32M-048 13 5 2 2 CBX40UHV-048 20 6 0 0
CBX32MV-036 10 16 1 14 CBX32MV-048 13 5 2 2 CBX40UHV-060 17 5 1 4
-030
CBX40UHV-030 10 16 1 14 CBX40UHV-042 13 5 2 2 CH23-68 27 7 0 13
CBX40UHV-036 10 16 1 14 CBX40UHV-048 13 5 2 2 CH33-50, -60C 11 4 0 0
CH23-41 11 4 0 8 CH23-68 20 9 1 5 CH33-62D 19 6 2 4
CH23-51 11 6 0 14 CH33-43B 7 9 3 2 CR33-50/60 19 6 2 4
CH33-31A 16 18 2 8 CH33-43C 22 5 1 0 CR33-60 23 6 1 3
CH33-31B 16 18 2 6 CH33-44/48B 18 4 0 0 CX34-62C 10 7 2 14
CH33-36A 10 6 0 6 CH33-48C 22 5 1 0 CX34-62D 19 7 3 2
CH33-36B 6 3 0 0 CH33-49C 16 6 1 6
CH33-36C 10 11 1 5 CH33-50, -60C 10 9 3 4
Subcool
Heat Cool Heat Cool Heat Cool
Additional Charge
HP
Indoor Coil or Air
SIZE
Handler
CH33-42B 16 18 2 6
-030
CBX25UH-036 31 3 0 4
-036
CBX25UH-042 42 5 0 8 CBX32MV-048 20 6 0 0
-042
Subcool
Additional Charge
HP
Indoor Coil or Air
SIZE
Handler
CH33-60D 12 8 0 9
-042
CBX25UH-048 15 6 2 5
-048
CBX25UH-060 15 6 2 0
-060
Subcool
*Amount of charge required in additional to charge shown on unit nameplate.
Additional Charge
Page 32
Page 33
Table 8. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG (XP14-XXX-230-08 or higher)
IMPORTANT
Use table 8 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in instal lations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
Vapor Pressure
Model
Number
ºF (ºC)* 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 11 5
-018 67 83 100 118 137 145 145 146 147 148 149 151 151 153 154 155
-024 58 72 88 105 123 139 140 142 143 144 145 145 146 147 147 148
-030 55 69 84 102 122 135 136 138 140 141 143 144 145 147 148 149
-036 62 76 91 106 124 135 137 139 141 143 145 146 148 150 151 153
-042 58 73 89 108 130 127 129 131 132 134 136 137 139 140 141 142
-048 60 75 90 105 121 136 137 138 139 140 141 142 143 144 146 147
-060 56 70 84 99 11 4 132 133 134 135 137 138 139 141 142 143 144
ºF (ºC)* 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 11 5
-018 272 287 305 321 339 242 259 279 302 326 351 376 406 433 462 498
-024 281 295 309 324 340 243 262 281 302 325 348 373 399 426 454 483
-030 274 286 299 313 327 250 268 288 308 330 352 376 400 426 452 480
-036 287 304 322 342 365 230 248 268 288 311 334 359 385 412 441 471
-042 293 335 368 394 411 215 234 254 275 298 321 346 371 398 426 455
-048 282 299 316 334 353 219 237 256 277 298 321 344 369 395 422 450
-060 266 285 309 337 369 222 241 262 283 306 330 354 380 406 434 463
*Temperature of the air entering the outside coil.
Heating Cooling
Liquid Pressure
Table 9. HFC-410A Temperature (°F) - Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3 34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1 35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8 37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 11 5 390.7 130 475.6 146 579.8 38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8 40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0 41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 11 9 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4 43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7 44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Page 33
XP14 SERIES
Page 34
System Operation- (XP14-XXX-230-01 through 07)
The demand defrost controller measures differential temperatures to detect when the system is performing poorly because of ice build-up on the outdoor coil. The controller self-calibrates when the defrost system starts and after each system defrost cycle. The defrost control board components are shown in figure 19.
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE - The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
FILTER DRIER
The unit is equipped with a large-capacity bi-flow filter drier which keeps the system clean and dry. If replacement is necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC-410A refrigerant.
DEFROST CONTROL BOARD
Figure 19 provides a basic illustration of the layout of the defrost control board. Table 10 provides information concerning pin-out and jumper configurations.
Note - Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR PLUG IN
(COIL, AMBIENT,
& DISCHARGE
SENSORS)
DELAY
PINS
REVERSING
VALV E
PRESSURE
SWITCH CIRCUIT
CONNECTIONS
Figure 19. Defrost Control Board
Test: Defrost Temperature Termination Shunt (Jumper) Pins—The defrost board selections are: 50, 70,
90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
LOW AMBIENT THERMOSTAT PINS
DIAGNOSTIC LEDS
24V TERMINAL STRIP CONNECTIONS
Note: The Y1 input must be active (ON) and the O” room thermostat terminal into board must be inactive.
DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 13.
DELAY MODE
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
DEFROST BOARD PRESSURE SWITCH CONNECTIONS
The unit's automatic reset pressure switches (LO PS - S87 and HI PS - S4) are factory-wired into the defrost board on the LO-PS and HI-PS terminals, respectively.
Low Pressure Switch (LO-PS)
When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. Low Pressure (auto reset) ­trip at 25 psig; reset at 40 psig. The low pressure switch is ignored under the following conditions:
during the defrost cycle and 90 seconds after the
termination of defrost
when the average ambient sensor temperature is below
15° F (-9°C)
for 90 seconds following the start up of the compressorduring test mode
High Pressure Switch (HI-PS)
When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. High Pressure (auto reset) ­trip at 590 psig; reset at 418 psig.
Low Ambient Thermostat Pins - P3 provides selection of the Y2 compressor lock-in temperature. The XP14 series heat pumps do not use a Y2 compressor and therefore these pins are not active.
FIVE-STRIKE LOCKOUT FEATURE
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The five-strike pressure switch lockout condition can be reset by cycling OFF the 24-volt power to the control board or by shorting the TEST pins between 1 and 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5-minute short cycle will occur after the switch closes.
Page 34
Page 35
Table 10. Defrost Control Board Description (XP14-XXX-230-01 through 07)
ID Description
O Out 24 VAC output connection for reversing valve
LO-PS Connection for low-pressure switch
Y2 24 VAC output for second stage compressor solenoid
Y1 24 VAC common output, switched for enabling compressor contactor
HI-PS Connection for high-pressure switch
P1 Seven position square pin header. P1 provides selection of the defrost terminate temperature based on the position of selection shunt, as
P2 The following connections are provided in the seven position P2 screw terminal block:
P3 Five position square pin header. P3 provides selection of the Y2 compressor lock-in temperature. Note: This is applicable for two stage
P4 Six position square pin header. P4 provides connections for the temperature sensors:
P5 Two position square pin header. P5 provides selection of the 30-second compressor delay option.
P6 Eight position header. P6 provides connections for the factory test connections.
well as selection pins for enabling the field test mode.
W1 24 VAC thermostat output for auxiliary heat operation
C 24 VAC system common
L Service light thermostat connection
R 24 VAC system power input
Y2 24 VAC thermostat input for second stage compressor operation
O 24 VAC thermostat input for reversing valve operation
Y1 24 VAC thermostat input for first stage compressor operation
compressor operations only.
COIL (P4-5) Ground connection for outdoor coil temperature sensor.
(P4-6) Connection for outdoor coil temperature sensor.
AMB (P4-3) Ground connection for outdoor ambient temperature sensor.
(P4-4) Connection for outdoor ambient temperature sensor.
DIS (P4-1) Ground connection for discharge temperature sensor.
(P4-2) Connection for discharge temperature sensor. Note: This is applicable for two stage compressor operations only.
Actuation—When the reversing valve is de-energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 30 minutes of heating mode compressor run time. The control will attempt to self-calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system temperatures during the 20-minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
NOTE - If ambient or coil sensor fault is detected, the board will not execute the TEST mode.
Termination—The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14-minute timer, another defrost cycle will be initiated after 30 minutes of run time.
Each test pin shorting will result in one test event. For each TEST the shunt (jumper) must be removed for at least one second and reapplied. Refer to flow chart as illustrated in figure 20 for TEST operation.
Test Mode—When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the TEST pins for two to five seconds. If the jumper remains across the TEST pins longer than five seconds, the control will ignore the TEST pins and revert to normal operation. The jumper will initiate one cycle per test.
Table 11. Sensor Temperature / Resistance Range
Temperatur e Range °F
Sensor
Outdoor (Ambient)
Coil -35 to 120
Note: Sensor resistance decreases as sensed temperature increases.
(°C)
-35 to 120 (-37) to (48)
(-37) to (48)
Resistance Values Range (ohms)
280,000 to 3750
280,000 to 3750
Pins/Wire Color
3 and 4 (Black)
5 and 6 (Brown)
Page 35
XP14 SERIES
Page 36
Enter the TEST mode by placing a shunt (jumper) across the TEST pins on the board after power-up. The TEST pins are ignored and the test function is locked out if the shunt is applied on the TEST pins before power-up. Board timings are reduced, the low-pressure switch is ignored and the board will clear any active lockout condition.
NOTE - The 30-second off cycle is NOT functional when jumpering the TEST pins.
Ambient Sensor—The ambient sensor (shown in figure
1) considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Coil Sensor—The coil temperature sensor (shown in figure 1) considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Defrost System - (XP14-XXX-230-01 through 07)
The defrost control board has three basic operational modes: normal, calibration, and defrost.
Normal Mode—The demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
Calibration Mode—The board is considered uncalibrated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
Defrost Mode—The following paragraphs provide a detailed description of the defrost system operation.
Defrost Cycles—The demand defrost control board initiates a defrost cycle based on either frost detection or time.
Frost Detection—If the compressor runs longer than
30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT - The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.
Time—If six hours of heating mode compressor run
time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
Page 36
Page 37
Table 12. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range
Degrees
Fahrenheit
136.3 2680 56.8 16657 21.6 44154 -11.3 123152
133.1 2859 56.0 16973 21.0 44851 -11.9 125787
130.1 3040 55.3 17293 20.5 45560 -12.6 128508
127.3 3223 54.6 17616 20.0 46281 -13.2 131320
124.7 3407 53.9 17942 19.4 47014 -13.9 134227
122.1 3592 53.2 18273 18.9 47759 -14.5 137234
119.7 3779 52.5 18607 18.4 48517 -15.2 140347
117.5 3968 51.9 18945 17.8 49289 -15.9 143571
115.3 4159 51.2 19287 17.3 50074 -16.5 146913
113.2 4351 50.5 19633 16.8 50873 -17.2 150378
111.2 4544 49.9 19982 16.3 51686 -17.9 153974
109.3 4740 49.2 20336 15.7 52514 -18.6 157708
107.4 4937 48.5 20695 15.2 53356 -19.3 161588
105.6 5136 47.9 21057 14.7 54215 -20.1 165624
103.9 5336 47.3 21424 14.1 55089 -20.8 169824
102.3 5539 46.6 21795 13.6 55979 -21.5 174200
100.6 5743 46.0 22171 13.1 56887 -22.3 178762
99.1 5949 45.4 22551 12.5 57811 -23.0 183522
97.6 6157 44.7 22936 12.0 58754 -23.8 188493
96.1 6367 44.1 23326 11.5 59715 -24.6 193691
94.7 6578 43.5 23720 11.0 60694 -25.4 199130
93.3 6792 42.9 24120 10.4 61693 -26.2 204829
92.0 7007 42.3 24525 9.9 62712 -27.0 210805
90.6 7225 41.7 24934 9.3 63752 -27.8 217080
89.4 7444 41.1 25349 8.8 64812 -28.7 223677
88.1 7666 40.5 25769 8.3 65895 -29.5 230621
86.9 7890 39.9 26195 7.7 67000 -30.4 237941
85.7 8115 39.3 26626 7.2 68128 -31.3 245667
84.5 8343 38.7 27063 6.7 69281 -32.2 253834
83.4 8573 38.1 27505 6.1 70458 -33.2 262482
82.3 8806 37.5 27954 5.6 71661 -34.1 271655
81.2 9040 37.0 28408 5.0 72890 -35.1 281400
80.1 9277 36.4 28868 4.5 74147 -36.1 291774
79.0 9516 35.8 29335 3.9 75431 -37.1 302840
78.0 9757 35.2 29808 3.4 76745 -38.2 314669
77.0 10001 34.7 30288 2.8 78090 -39.2 327343
76.0 10247 34.1 30774 2.3 79465
75.0 10496 33.5 31267 1.7 80873
74.1 10747 33.0 31766 1.2 82314
73.1 11000 32.4 32273 0.6 83790
72.2 11256 31.9 32787 0.0 85302
71.3 11515 31.3 33309 -0.5 86852
70.4 11776 30.7 33837 -1.1 88440
69.5 12040 30.2 34374 -1.7 90068
68.6 12306 29.6 34918 -2.2 91738
67.7 12575 29.1 35471 -2.8 93452
66.9 12847 28.6 36031 -3.4 95211
66.0 13122 28.0 36600 -4.0 97016
65.2 13400 27.5 37177 -4.6 98870
64.4 13681 26.9 37764 -5.2 100775
63.6 13964 26.4 38359 -5.7 102733
62.8 14251 25.8 38963 -6.3 104746
62.0 14540 25.3 39577 -6.9 106817
61.2 14833 24.8 40200 -7.5 108948
60.5 15129 24.2 40833 -8.2 1111 41
59.7 15428 23.7 41476 -8.8 113400
59.0 15730 23.2 42130 -9.4 115727
58.2 16036 22.6 42794 -10.0 118126
57.5 16345 22.1 43468 -10.6 120600
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Page 37
XP14 SERIES
Page 38
JUMPER
TEST
Placing the jumper on the field test pins (E33) allows the technician to:
Clear short cycle lockout Clear five-strike fault lockout Cycle the unit in and out of defrost mode Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control's TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jump ered TEST pins and revert to normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
DEMAND DEFROST CONTROL (UPPER LEFT-HAND CORNER)
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 34 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor exist, unit will go into DEFROST MODE.
If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE — Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.
Figure 20. Test Mode (XP14-XXX-230-01 through 07)
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 34 minutes.
Page 38
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
Page 39
DEFROST BOARD DIAGNOSTICS (XP14-XXX-230-01 and later)
See table 13 to determine defrost board operational conditions and to diagnose cause and solution to problems.
Table 13. Defrost Control Board Diagnostic LEDs (XP14-XXX-230-01 through 07)
DS2 Green
OFF OFF Power problem
Simultaneous SLOW Flash
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
ON ON Circuit Board Failure
DS1 Red
Condition/Code Possible Cause(s) Solution
1
Check control transformer power (24V).
2
If power is available to board and LED(s) do not light, replace board.
None required.
None required (Jumper TEST pins to override)
Normal operation
5-minute anti-short cycle delay
Ambient Sensor Problem
Coil Sensor Problem
No power (24V) to board terminals R and C or board failure.
Unit operating normally or in standby mode.
Initial power up, safety trip, end of room thermostat demand.
Sensor being detected open or shorted or out of temperature range. Board will revert to time/ temperature defrost operation. (System will still heat or cool).
Sensor being detected open or shorted or out of temperature range. Board will not perform demand or time/temperature defrost operation. (System will still heat or cool).
Indicates that board has internal component failure. Cycle 24 volt power to board. If code does not clear, replace board.
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
1
OFF
OFF ON
SLOW Flash
ON OFF
SLOW Flash
FAST Flash
SLOW Flash
OFF High Pressure Fault
ON
ON
Low Pressure Fault
Low Pressure LOCKOUT
High Pressure LOCKOUT
Discharge Line Temperature Fault
Discharge Line Temperature
LOCKOUT
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or incorrect operation of metering device.
4
Incorrect or improper sensor location or connection to system.
This model does not have a defrost line sensor, therefore this code is not applicable.
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and subcool ing temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature mea surements.
OFF
Fast Flash
Fast Flash
OFF
Discharge Sensor Fault
Discharge Sensor
LOCKOUT
The XP14 series units does not use a defrost line sensor. However, a resistor is installed across pins P4-1 and P4-2. If the resistor is missing or damage then this fault code will be displayed.
This model does not have a defrost line sensor, therefore this code is not applicable.
Page 39
XP14 SERIES
Page 40
System Operation (XP14-XXX-230-08 and Later)
IMPORTANT
Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR.
High Pressure Switch (S4)
This unit is equipped with a auto‐reset high pressure switch (single-pole, single-throw) which is located on the liquid line. The switch shuts off the compressor when discharge pressure rises above the factory setting. High
Pressure (auto reset) - trip at 590 psig, reset at 418 psig.
Low Pressure Switch (S87)
This unit is equipped an auto-reset low pressure switch which is located on the vapor line. The switch shuts off the compressor when the vapor pressure falls below the factory setting. Low Pressure (auto reset) - trip at 25 psig, reset at 40 psig.
Low Pressure Switch Bypass (S41) (Optional)
For use in applications where the heat pump is operated in outdoor ambient temperatures below 15°F.
Prevents nuisance trips form the low pressure switch Wired in parallel with the low pressure switch
Thermal Protection Switch (S173) — Compressor
Mounted
Some units are equipped with a compressor mounted normally closed temperature switch that prevents compressor damage due to overheating caused by internal friction. The switch is located on top of the compressor casing (see figure 1). This switch senses the compressor casing temperature and opens at 239-257°F (115°C-125°C) to shut off compressor operation. The auto-reset switch closes when the compressor casing temperature falls to 151-187°F (66°C-86°C), and the compressor is re-energized. This single-pole, single-throw (SPST) bi-metallic switch is wired in series with the 24V Y input signal to control compressor operation.
Crankcase Thermostat (S40) (-036, -042, -048 and
-060 Units Only)
The reference models are equipped with a 70 watt, belly band type crankcase heater. HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by a thermostat located on the liquid line. When liquid line temperature drops below 50° F the thermostat closes energizing HR1. The thermostat will open, de-energizing HR1 once liquid line temperature reaches 70° F .
Defrost Thermostat (S6)
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When defrost thermostat senses 42°F (5.5°C) or cooler, the thermostat contacts close and send a signal to the defrost control to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
Page 40
Bi-Flow Liquid Line Filter Drier
The unit is equipped with a large-capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC-410A refrigerant.
Defrost System (XP14-XXX-230-08 and Later)
The XP14 defrost system includes two components: a defrost thermostat (S6) and a defrost control (CMC1) (figure 23).
DEFROST CONTROL (CMC1)
The defrost control includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections.
P1 - FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
LOW PRESSURE
THERMOSTAT
HIGH PRESSURE
P5 -
DELAY PINS
REVERSING
VALV E
S87
SWITCH
DEFROST
S4
SWITCH
Figure 21. Outdoor Unit Defrost Control (CMC1)
(XP14-XXX-230-08 and Later)
The defrost control provides automatic switching from normal heating operation to defrost mode and back. When the defrost thermostat is closed, the control accumulates compressor run time at 30, 60 or 90 minute field adjustable intervals. When the selected compressor run time interval is reached, the defrost relay is energized and defrost begins.
Defrost Control Timing Pins (P1)
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 21). The maximum defrost period is 14 minutes and cannot be adjusted.
NOTE — Defrost control part number is listed near the P1 timing pins.
Units with defrost control 100269-02: Factory default
is 60 minutes
Units with defrost control 100269-04: Factory default
is 90 minutes If the timing selector jumper is missing, the defrost control defaults to a 90-minute defrost interval.
LEDS
24V TERMINAL STRIP CONNECTIONS
Page 41
Compressor Delay (P5)
The defrost control has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode.
Units with defrost control 100269-02: The compressor
will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.
Units with defrost control 100269-04: The compressor
will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed.
NOTE — The 30‐second compressor feature is ignored when jumpering the TEST pins.
Time Delay
The timed‐off delay is five minutes long. The delay helps to protect the compressor from short‐cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied.
Pressure Switch Circuit
The defrost control incorporates two pressure switch circuits. The high pressure switch (S4) is
factory‐connected to the defrost control's HI PS terminals (see figure 21). The defrost control also includes a low pressure, or loss‐of‐charge‐pressure, switch (S87). Switches are shown in wiring diagrams in figure 23.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the defrost control. In addition, the diagnostic LEDs will indicate a locked‐out pressure switch after the fifth occurrence of an open pressure switch as listed in table 14. The unit will remain locked out until power to the defrost control is interrupted, then re‐established or until the jumper is applied to the TEST pins for 0.5 seconds.
Defrost Control Diagnostic LEDs
The defrost control uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
Table 14. Defrost Control (CMC1) Diagnostic LED
(XP14-XXX-230-08 and Later)
Mode
No power to control OFF OFF
Normal operation / power to control
Anti‐short cycle lockout Alternating Slow FLASH
Low pressure switch fault OFF Slow FLASH
Low pressure switch lockout
High pressure switch fault Slow FLASH OFF
High pressure switch lockout
Green LED (DS2)
Simultaneous Slow FLASH
OFF ON
ON OFF
Red LED (DS1)
NOTE — The defrost control ignores input from the low‐pressure switch terminals as follows:
S during the TEST mode, S during the defrost cycle, S during the 90‐second start‐up period, S and for the first 90 seconds each time the reversing
valve switches heat/cool modes.
Page 41
XP14 SERIES
Page 42
Maintenance
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Outdoor Unit
1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Ensure the power is turned off before you clean the coil.
2. Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.
3. Visually inspect connecting lines and coils for evidence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at the unit (with the unit operating).
6. Check amp-draw outdoor fan motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
Outdoor Coil — The outdoor coil may be flushed with
a water hose.
Outdoor Coil (Sea Coast) — Moist air in ocean
locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
INDOOR UNIT
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. Check blower drive belt for wear and proper tension.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp-draw on blower motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
INDOOR COIL
1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.
NOTE The filter and all access panels must be in place any time the unit is in operation.
Page 42
Page 43
Unit Wiring Diagram and Sequence of Operations
Figure 22. XP14 Unit Wiring Diagram (XP14-XXX-230-01 through 07)
Page 43
XP14 SERIES
Page 44
Figure 23. Typical Unit Wiring Diagram (XP14-XXX-230-08 and later)
Page 44
Page 45
Figure 24. Typical Factory Wiring (Copeland Compressor) (XP14-XXX-230-08 and later)
Page 45
XP14 SERIES
Page 46
Figure 25. Typical Factory Wiring (Interlink Compressor) (XP14-XXX-230-08 and later)
Page 46
Page 47
SEQUENCE OF OPERATIONS
This is the sequence of operation for XP14 series units. The sequence is outlined by numbered steps which correspond to circled numbers on the adjacent diagram. The steps are identical for both cooling and first stage heating demand with the exception reversing valve L1 is energizedduringcoolingdemandandde-energizedduring heating demand.
NOTE- Transformer in indoor unit supplies power (24 VAC) to the thermostat and outdoor unit controls.
COOLING:
Internal thermostat wiring energizes terminal O by cooling mode selection, energizing the reversing valve L1.
1. Demand initiates at Y1 in the thermostat.
2. 24VAC energizes compressor contactor K1.
3. K1‐1 N.O. closes, energizing compressor (B1) and outdoor fan motor (B4).
END OF COOLING DEMAND:
1. Demand is satisfied. Terminal Y1 is de‐energized.
2. Compressor contactor K1 is de‐energized.
3. K1‐1 opens and compressor (B1) and outdoor fan motor (B4) are de‐energized and stop immediately.
FIRST STAGE HEAT:
Internal thermostat wiring de-energizes terminal O by heating mode selection, de-energizing the reversing valve L1.
See steps 1, 2 and 3.
END OF FIRST STAGE HEAT:
See steps 4, 5 and 6.
DEFROST MODE:
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the “W1” (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination temperature, the defrost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default termination temperature will be 90°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by time and the coil temperature did not remain above 35°F (2°C) for 4 minutes the control will go to the 30-minute Time/Temperature mode.
Start-Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Vapor Pressure;
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?
THERMOSTAT
Properly Set?  Level? 
Page 47
XP14 SERIES
Page 48
HFC-410A CHARGING INFORMATION — FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION AND SERVICE PROCEDURE
Maintenance checks using the Normal Operating Pressures table
Table 2 may be used to help perform maintenance checks. This table is not a procedure for charg ing the system and any minor variations in the pressures may be expected due to differences in installations. However, significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Charge Using the Subcooling Method
Cooling Mode—When the outdoor ambient temperature is 60°F (15°C) and above, use the cool ing mode to adjust the charge using the subcooling method. Target subcooling values in table 1 are based on 70 to 80°F (21-27°C) indoor return air temperature. Heating Mode—When the outdoor ambient temperature is below 60°F (15°C), use the heating mode to adjust the charge using the subcooling charge levels (table ). Target subcooling values in table 1 are based on 65-75°F (18-24°C) indoor return air temperature.
Matchups/Charge Levels and Line Set Lengths
Table 2 lists all the Lennox recommended indoor unit matchups along with the charge levels for the various sizes of outdoor units. Charge levels on the unit nameplate are based on installa
tions with 15' (4.6m) line sets; be sure to consider any difference in line set length (see Installation Instructions for more details).
Charge Using the Weigh‐in Method
If the system is void of refrigerant, locate and repair any leaks and then weigh in the refrigerant charge into the unit. For charge adjustments, be sure to consider line set length differences and, referring to table 1, adjust for the matchup difference.
1 - Recover the refrigerant from the unit. 2 - Conduct leak check; evacuate as previously outlined. 3 - Weigh in the unit nameplate charge, adjusting for matchup and line set length differences.
If weighing facilities are not available use the Subcooling method.
Table 1 - Normal Operating Pressures (Liquid +10 and Suction +5 psig)
Heating Mode Cooling Mode
ºF (ºC)* 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 11 5
SIZE
VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ VA P/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ
-018 65/289 80/304 97/322 116/341 137/360 132/224 134/239 135/257 136/279 138/300 138/322 140/344 141/369 142/395 145/421 146/481
-024 58/281 72/295 88/ 309 105/324 123/340 139/243 140/262 142/281 143/302 144/325 145/348 145/373 146/399 147/426 147/454 148/483
-030 55/274 69/286 84/ 299 102/313 122/327 135/250 136/268 138/288 140/308 141/330 143/352 144/376 145/400 147/426 148/452 149/480
-036 62/287 76/304 91/ 322 106/342 124/365 135/230 137/248 139/268 141/288 143/311 145/334 146/359 148/385 150/412 151/441 153/471
-042 58/293 73/335 89/ 368 108/394 130/411 127/215 129/234 131/254 132/275 134/298 136/321 137/346 139/371 140/398 141/426 142/455
-048 60/282 75/299 90/ 316 105/334 121/353 136/219 137/237 138/256 139/277 140/298 141/321 142/344 143/369 144/395 146/422 147/450
-060 56/266 70/285 84/ 309 99/ 337 114/369 132/222 133/241 134/262 135/283 137/306 138/330 139/354 141/380 142/406 143/434 144/463
*Temperature of the air entering the outside coil.
Table 2 - Indoor Unit Matches and Subcooling Charge Levels and Additional Charge
HP
Size
Indoor Coil or Air Handler
Subcool
Additional
Charge
HP
Size
Indoor Coil or Air Handler
Subcool
Additional
Charge
HP
Size
Indoor Coil or Air Handler
Subcool
Additional
Charge
Heat
(+5ºF)
Cool
(+1ºF)
Heat
(+5ºF)
Cool
(+1ºF)
Heat
(+5ºF)
Cool
(+1ºF)
lbs oz lbs oz lbs oz
CBX25UH-018 CBX25UHV-018
13 3 0 0
CH33-36B 6 3 0 0
CH33-49C 16 6 1 6
-018
CBX27UH-018 8 9 1 2
-030
CH33-36C 10 11 1 5 CH33-50, -60C 10 9 3 4
CBX27UH-024 8 9 1 2 CH33-42B 16 18 2 6
-042
CH33-60D 12 8 0 9 CBX32MV-018/024 9 4 0 3 CH33-43C 4 9 1 12 CH33-62D 19 7 1 7 CH33-25A 10 6 0 9 CR33-30, -36 22 5 1 0 CR33-50, -60 29 5 0 4 CH33-25B 11 5 0 4 CX34-31 17 15 2 10 CR33-60D 29 5 0 4 CR33-30/36 18 5 0 9 CX34-36 25 6 0 10 CX34-49 11 6 1 4 CX34-25 8 4 0 9 CX34-38 10 19 2 14 CX34-50, -60 25 8 1 15 CX34-31 10 7 0 8 CX34-42 25 6 0 10 CX34-60 8 8 1 4
-024
CBX25UH-024 CBX25UHV-024
6 6 0 9 CX34-43 13 17 2 14 CX34-62C 8 11 3 10
CBX25UH-030 CBX25UHV-030
17 3 0 15 CX34-44, -48 9 21 2 12 CX34-62D 11 7 1 15
CBX26UH-024 17 3 0 15
-036
CBX25UH-036 CBX25UHV-036
31 3 0 4
-048
CBX25UH-048
CBX25UHV-048
15 6 2 5
CBX27UH-024 12 12 1 2 CBX26UH-036 31 3 0 4 CBX26UH-048 20 10 3 11 CBX27UH-030 11 11 2 1 CBX27UH-036 18 3 0 5 CBX27UH-048 16 6 0 0 CBX32M-018, -024 14 11 0 4 CBX27UH-042 11 4 0 1 CBX27UH-060 12 6 1 4 CBX32M-030 12 12 1 2 CBX27UH-048 11 4 0 1 CBX32M-048 16 6 0 0 CBX32MV-018/024 14 11 0 4 CBX32M-036 18 3 0 5 CBX32M-060 20 8 1 0 CBX32MV-024/030 12 12 1 2 CBX32M-042 18 3 0 5 CBX32MV-048 16 6 0 0 CBX32MV-036 11 11 2 1 CBX32MV-036 18 3 0 5 CBX32MV-060 20 8 1 0 CBX40UHV-024 11 11 2 1 CBX32MV-048 11 4 0 1 CBX32MV-068 10 8 4 5 CBX40UHV-030 11 11 2 1 CBX40UHV-042 11 4 0 1 CBX40UHV-048 16 6 0 0 CH23-41 10 3 0 0 CBX40UHV-048 11 4 0 1 CBX40UHV-060 20 8 1 0 CH33-25A 20 10 1 1 CBX40UHV-036 18 3 0 5 CH23-68 24 6 2 8 CH33-25B 19 8 1 2 CH33-43B 14 8 2 1 CH33-50, -60C 17 6 1 5 CH33-31A 15 11 1 15 CH33-43C 26 9 2 10 CH33-60D 18 6 0 13 CH33-36C 10 12 0 0 CH33-44/48B 24 8 2 3 CH33-62D 13 7 3 6 CH33-36A 20 10 1 1 CH33-48C 26 9 2 10 CR33-50/60 19 6 1 1 CR33-30, -036 17 4 0 14 CH33-49C 15 8 2 12 CR33-60 19 6 1 1 CX34-25 15 9 0 15 CH33-50/60C 15 8 2 12 CX34-49C 10 6 1 9 CX34-31 15 16 0 9 CR33-48 38 5 0 0 CX34-60 28 7 3 14 CX34-36 26 6 0 9 CR33-50, -60 15 5 1 4 CX34-62C 10 6 3 12 CX34-38 10 18 1 14 CX34-38 15 4 0 9 CX34-62D 14 7 3 12
-030
CBX25UH-030 CBX25UHV-030
9 3 0 8 CX34-43 23 8 2 8
-060
CBX25UH-060
CBX25UHV-060
15 6 2 0
CBX25UH-036 19 11 1 5 CX34-44/48 40 4 0 15 CBX26UH-060 31 6 3 0 CBX26UH-030 19 11 1 5 CX34-49 11 7 3 9 CBX27UH-060 13 7 0 8 CBX27UH-030 10 16 1 14 CX34-50/60 23 8 2 8 CBX32M-060 17 5 1 4
CBX27UH-036 10 16 1 14
-042
CBX25UH-042 CBX25UHV-042
42 5 0 8 CBX32MV-048 20 6 0 0
CBX32M-030 7 10 1 3 CBX26UH-042 42 5 0 8 CBX32MV-060 17 5 1 4 CBX32M-036 10 16 1 14 CBX27UH-042, -048 13 5 2 2 CBX32MV-068 11 8 2 12 CBX32MV-024/030 7 10 1 3 CBX32M-048 13 5 2 2 CBX40UHV-048 20 6 0 0 CBX32MV-036 10 16 1 14 CBX32MV-048 13 5 2 2 CBX40UHV-060 17 5 1 4 CBX40UHV-030 10 16 1 14 CBX40UHV-042 13 5 2 2 CH23-68 27 7 0 13 CBX40UHV-036 10 16 1 14 CBX40UHV-048 13 5 2 2 CH33-50, -60C 11 4 0 0 CH23-41 11 4 0 8 CH23-68 20 9 1 5 CH33-62D 19 6 2 4 CH23-51 11 6 0 14 CH33-43B 7 9 3 2 CR33-50/60 19 6 2 4 CH33-31A 16 18 2 8 CH33-43C 22 5 1 0 CR33-60 23 6 1 3 CH33-31B 16 18 2 6 CH33-44/48B 18 4 0 0 CX34-62C 10 7 2 14 CH33-36A 10 6 0 6 CH33-48C 22 5 1 0 CX34-62D 19 7 3 2
The values in this table are most popular match-up pressures; indoor match-up, indoor air quantity, and indoor load will cause the pressures to vary. *Amount of charge required in addition to charge shown on unit
nameplate.
Page 49
HFC-410A CHARGING INFORMATION — FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION AND SERVICE PROCEDURE
Maintenance checks using the Normal Operating Pressures table
Table 2 may be used to help perform maintenance checks. This table is not a procedure for charg ing the system and any minor variations in the pressures may be expected due to differences in installations. However, significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Charge Using the Subcooling Method
Cooling Mode—When the outdoor ambient temperature is 60°F (15°C) and above, use the cool ing mode to adjust the charge using the subcooling method. Target subcooling values in table 1 are based on 70 to 80°F (21-27°C) indoor return air temperature. Heating Mode—When the outdoor ambient temperature is below 60°F (15°C), use the heating mode to adjust the charge using the subcooling charge levels (table ). Target subcooling values in table 1 are based on 65-75°F (18-24°C) indoor return air temperature.
Matchups/Charge Levels and Line Set Lengths
Table 2 lists all the Lennox recommended indoor unit matchups along with the charge levels for the various sizes of outdoor units. Charge levels on the unit nameplate are based on installa
tions with 15ft. (4.6m) line sets; on line sets with 3/8"(9.5mm) liquid line, add 3oz. addition al refrigerant for every 5ft. longer than 15ft. If line length is less than 15ft., subtract this amount (see Installation Instructions for more details).
Charge Using the Weigh‐in Method
If the system is void of refrigerant, locate and repair any leaks and then weigh in the refrigerant charge into the unit. For charge adjustments, be sure to consider line set length differences and, referring to table 1, adjust for the matchup difference. 1 - Recover the refrigerant from the unit. 2 - Conduct leak check; evacuate as previously outlined. 3 - Weigh in the unit nameplate charge, adjusting for matchup and line set length differences.
If weighing facilities are not available use the Subcooling method.
Table 1 - Normal Operating Pressures (Liquid +10 and Suction +5 psig)
Heating Mode Cooling Mode
ºF (ºC)* 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 11 5
SIZE
VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ VA P/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ
-018 65/289 80/304 97/322 116/341 137/360 132/224 134/239 135/257 136/279 138/300 138/322 140/344 141/369 142/395 145/421 146/481
-024 58/281 72/295 88/ 309 105/324 123/340 139/243 140/262 142/281 143/302 144/325 145/348 145/373 146/399 147/426 147/454 148/483
-030 55/274 69/286 84/ 299 102/313 122/327 135/250 136/268 138/288 140/308 141/330 143/352 144/376 145/400 147/426 148/452 149/480
-036 62/287 76/304 91/ 322 106/342 124/365 135/230 137/248 139/268 141/288 143/311 145/334 146/359 148/385 150/412 151/441 153/471
-042 58/293 73/335 89/ 368 108/394 130/411 127/215 129/234 131/254 132/275 134/298 136/321 137/346 139/371 140/398 141/426 142/455
-048 60/282 75/299 90/ 316 105/334 121/353 136/219 137/237 138/256 139/277 140/298 141/321 142/344 143/369 144/395 146/422 147/450
-060 56/266 70/285 84/ 309 99/ 337 114/369 132/222 133/241 134/262 135/283 137/306 138/330 139/354 141/380 142/406 143/434 144/463
*Temperature of the air entering the outside coil.
Table 2 - Indoor Unit Matches and Subcooling Charge Levels and Additional Charge**
HP
Size
Indoor Coil or Air Handler
Subcool
Additional
Charge
HP
Size
Indoor Coil or Air Handler
Subcool
Additional
Charge
HP
Size
Indoor Coil or Air
Handler
Subcool
Additional
Charge
Heat
(+
5ºF)
Cool
(+1ºF)
Heat
(+
5ºF)
Cool
(+1ºF)
Heat
(+
5ºF)
Cool
(+1ºF)
lbs oz lbs oz lbs oz
CBX25UH-018 CBX25UHV-018
13 3 0 0
CH33-36B 6 3 0 0
CH33-49C 16 6 1 6
CBX25UH-024 15 5 0 7
-030
CH33-36C 10 11 1 5 CH33-50, -60C 10 9 3 4
-018
CBX27UH-018 8 9 1 2 CH33-42B 16 18 2 6
-042
CH33-60D 12 8 0 9 CBX27UH-024 8 9 1 2 CH33-43C 4 9 1 12 CH33-62D 19 7 1 7 CBX32MV-018/024 9 4 0 3 CR33-30, -36 22 5 1 0 CR33-50, -60 29 5 0 4 CH33-25A 10 6 0 9 C33 / CX34-31 17 15 2 10 CR33-60D 29 5 0 4 CH33-25B 11 5 0 4 C33 / CX34-36 25 6 0 10 C33 / CX34-49 11 6 1 4 CR33-30/36 18 5 0 9 C33 / CX34-38 10 19 2 14 C33 / CX34-50, -60 25 8 1 15 C33 / CX34-25 8 4 0 9 C33 / CX34-42 25 6 0 10 C33 / CX34-60 8 8 1 4 C33 / CX34-31 10 7 0 8 C33 / CX34-43 13 17 2 14 C33 / CX34-62C 8 11 3 10
-024
CBX25UH-024 CBX25UHV-024
6 6 0 9 C33 / CX34-44, -48 9 21 2 12 C33 / CX34-62D 11 7 1 15
CBX25UH-030 CBX25UHV-030
17 3 0 15
-036
CBX25UH-036 CBX25UHV-036
31 3 0 4
-048
CBX25UH-048
CBX25UHV-048
15 6 2 5
CBX26UH-024 17 3 0 15 CBX26UH-036 31 3 0 4 CBX26UH-048 20 10 3 11 CBX27UH-024 12 12 1 2 CBX27UH-036 18 3 0 5 CBX27UH-048 16 6 0 0 CBX27UH-030 11 11 2 1 CBX27UH-042 11 4 0 1 CBX27UH-060 12 6 1 4 CBX32M-018, -024 14 11 0 4 CBX27UH-048 11 4 0 1 CBX32M-048 16 6 0 0 CBX32M-030 12 12 1 2 CBX32M-036 18 3 0 5 CBX32M-060 20 8 1 0 CBX32MV-018/024 14 11 0 4 CBX32M-042 18 3 0 5 CBX32MV-048 16 6 0 0 CBX32MV-024/030 12 12 1 2 CBX32MV-036 18 3 0 5 CBX32MV-060 20 8 1 0 CBX32MV-036 11 11 2 1 CBX32MV-048 11 4 0 1 CBX32MV-068 10 8 4 5 CBX40UHV-024 11 11 2 1 CBX40UHV-042 11 4 0 1 CBX40UHV-048 16 6 0 0 CBX40UHV-030 11 11 2 1 CBX40UHV-048 11 4 0 1 CBX40UHV-060 20 8 1 0 CH23-41 10 3 0 0 CBX40UHV-036 18 3 0 5 CH23-68 24 6 2 8 CH33-25A 20 10 1 1 CH33-43B 14 8 2 1 CH33-50, -60C 17 6 1 5 CH33-25B 19 8 1 2 CH33-43C 26 9 2 10 CH33-60D 18 6 0 13 CH33-31A 15 11 1 15 CH33-44/48B 24 8 2 3 CH33-62D 13 7 3 6 CH33-36C 10 12 0 0 CH33-48C 26 9 2 10 CR33-50/60 19 6 1 1 CH33-36A 20 10 1 1 CH33-49C 15 8 2 12 CR33-60 19 6 1 1 CR33-30, -036 17 4 0 14 CH33-50/60C 15 8 2 12 C33 / CX34-49C 10 6 1 9 C33 / CX34-25 15 9 0 15 CR33-48 38 5 0 0 C33 / CX34-60 28 7 3 14 C33 / CX34-31 15 16 0 9 CR33-50, -60 15 5 1 4 C33 / CX34-62C 10 6 3 12 C33 / CX34-36 26 6 0 9 C33 / CX34-38 15 4 0 9 C33 / CX34-62D 14 7 3 12
-030
CBX25UH-030 CBX25UHV-030
9 3 0 8 C33 / CX34-43 23 8 2 8
-060
CBX25UH-060
CBX25UHV-060
15 6 2 0
CBX25UH-036 19 11 1 5 C33 / CX34-44/48 40 4 0 15 CBX26UH-060 31 6 3 0 CBX26UH-030 19 11 1 5 C33 / CX34-49 11 7 3 9 CBX27UH-060 13 7 0 8 CBX27UH-030 10 16 1 14 C33 / CX34-50/60 23 8 2 8 CBX32M-060 17 5 1 4
CBX27UH-036 10 16 1 14
-042
CBX25UH-042 CBX25UHV-042
42 5 0 8 CBX32MV-048 20 6 0 0
CBX32M-030 7 10 1 3 CBX26UH-042 42 5 0 8 CBX32MV-060 17 5 1 4 CBX32M-036 10 16 1 14 CBX27UH-042, -048 13 5 2 2 CBX32MV-068 11 8 2 12 CBX32MV-024/030 7 10 1 3 CBX32M-048 13 5 2 2 CBX40UHV-048 20 6 0 0 CBX32MV-036 10 16 1 14 CBX32MV-048 13 5 2 2 CBX40UHV-060 17 5 1 4 CBX40UHV-030 10 16 1 14 CBX40UHV-042 13 5 2 2 CH23-68 27 7 0 13 CBX40UHV-036 10 16 1 14 CBX40UHV-048 13 5 2 2 CH33-50, -60C 11 4 0 0 CH23-41 11 4 0 8 CH23-68 20 9 1 5 CH33-62D 19 6 2 4 CH23-51 11 6 0 14 CH33-43B 7 9 3 2 CR33-50/60 19 6 2 4 CH33-31A 16 18 2 8 CH33-43C 22 5 1 0 CR33-60 23 6 1 3 CH33-31B 16 18 2 6 CH33-44/48B 18 4 0 0 C33 / CX34-62C 10 7 2 14 CH33-36A 10 6 0 6 CH33-48C 22 5 1 0 C33 / CX34-62D 19 7 3 2
The values in this table are most popular match-up pressures; indoor match-up, indoor air quantity, and indoor load will cause the pressures to vary. **Amount of charge required in addition to charge shown on unit name
plate.
NOTE - When you have a C33 coil (cased or uncased) with a TXV installed, use the CX34 charge info.
Page 50
HFC-410A CHARGING INFORMATION — FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION AND SERVICE PROCEDURE
Maintenance checks using the Normal Operating Pressures table
Table 2 may be used to help perform maintenance checks. This table is not a procedure for charg ing the system and any minor variations in the pressures may be expected due to differences in installations. However, significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Charge Using the Subcooling Method
Cooling Mode—When the outdoor ambient temperature is 60°F (15°C) and above, use the cool ing mode to adjust the charge using the subcooling method. Target subcooling values in table 1 are based on 70 to 80°F (21-27°C) indoor return air temperature. Heating Mode—When the outdoor ambient temperature is below 60°F (15°C), use the heating mode to adjust the charge using the subcooling charge levels (table ). Target subcooling values in table 1 are based on 65-75°F (18-24°C) indoor return air temperature.
Matchups/Charge Levels and Line Set Lengths
Table 2 lists all the Lennox recommended indoor unit matchups along with the charge levels for the various sizes of outdoor units. Charge levels on the unit nameplate are based on installa
tions with 15ft. (4.6m) line sets; on line sets with 3/8"(9.5mm) liquid line, add 3oz. addition al refrigerant for every 5ft. longer than 15ft. If line length is less than 15ft., subtract this amount (see Installation Instructions for more details).
Charge Using the Weigh‐in Method
If the system is void of refrigerant, locate and repair any leaks and then weigh in the refrigerant charge into the unit. For charge adjustments, be sure to consider line set length differences and, referring to table 1, adjust for the matchup difference. 1 - Recover the refrigerant from the unit. 2 - Conduct leak check; evacuate as previously outlined. 3 - Weigh in the unit nameplate charge, adjusting for matchup and line set length differences.
If weighing facilities are not available use the Subcooling method.
Table 1 - Normal Operating Pressures (Liquid +10 and Suction +5 psig)
ºF (ºC)* 20 30 40 50 60 65 70 75 80 85 90 95 100 105 110 11 5
SIZE
-018 65/289 80/304 97/322 116/341 137/360 132/224 134/239 135/257 136/279 138/300 138/322 140/344 141/369 142/395 145/421 146/481
-024 58/281 72/295 88/ 309 105/324 123/340 139/243 140/262 142/281 143/302 144/325 145/348 145/373 146/399 147/426 147/454 148/483
-030 55/274 69/286 84/ 299 102/313 122/327 135/250 136/268 138/288 140/308 141/330 143/352 144/376 145/400 147/426 148/452 149/480
-036 62/287 76/304 91/ 322 106/342 124/365 135/230 137/248 139/268 141/288 143/311 145/334 146/359 148/385 150/412 151/441 153/471
-042 58/293 73/335 89/ 368 108/394 130/411 127/215 129/234 131/254 132/275 134/298 136/321 137/346 139/371 140/398 141/426 142/455
-048 60/282 75/299 90/ 316 105/334 121/353 136/219 137/237 138/256 139/277 140/298 141/321 142/344 143/369 144/395 146/422 147/450
-060 56/266 70/285 84/ 309 99/ 337 114/369 132/222 133/241 134/262 135/283 137/306 138/330 139/354 141/380 142/406 143/434 144/463
*Temperature of the air entering the outside coil.
VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /LI Q VA P/L IQ VAP/ LIQ VAP/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ VA P/ LIQ VAP/ LIQ VAP/ LI Q VAP /L IQ
Heating Mode Cooling Mode
Table 2 - Indoor Unit Matches and Subcooling Charge Levels and Additional Charge**
HP
Indoor Coil or
Size
Air Handler
CBX25UH-018 CBX25UHV-018 CBX25UH-024 15 5 0 7 CH33-42B 16 18 2 6 CH33-60D 12 8 0 9 CBX27UH-018/024 8 9 1 2 CH33-43C 4 9 1 12 CH33-62D 19 7 1 7 CBX32MV-018/024 9 4 0 3 CR33-30, -36 22 5 1 0 CR33-50, -60 29 5 0 4 CBA27UHE-018/024 12 10 1 2 C37/CX38/C33/CX34-31 17 15 2 10 CR33-60D 29 5 0 4
-018
CH33-25A 10 6 0 9 C37/CX38/C33/CX34-36 25 6 0 10 C37/CX38/C33/CX34-49 11 6 1 4
CH33-25B 11 5 0 4 C37/CX38/C33/CX34-38 10 19 2 14
CR33-30/36 18 5 0 9 C37/CX38/C33/CX34-42 25 6 0 10 C37/CX38/C33/CX34-60 8 8 1 4 C37/CX38/C33/CX34-25 8 4 0 9 C37/CX38/C33/CX34-43 13 17 2 14 C37/CX38/C33/CX34-62C 8 11 3 10
C37/CX38/C33/CX34-31 10 7 0 8
CBX25UH-024 CBX25UHV-024 CBX25UH-030 CBX25UHV-030 CBX26UH-024 17 3 0 15 CBX27UH-036 18 3 0 5 CBX27UH-048 16 6 0 0 CBX27UH-024 12 12 1 2 CBX27UH-042 11 4 0 1 CBX27UH-060 12 6 1 4 CBX27UH-030 11 11 2 1 CBX27UH-048 11 4 0 1 CBX32M-048 16 6 0 0 CBX32M-018/024 14 11 0 4 CBX32M-036/042 18 3 0 5 CBX32M-060 20 8 1 0 CBX32M-030 12 12 1 2 CBX32MV-036 18 3 0 5 CBX32MV-048 16 6 0 0 CBX32MV-018/024 14 11 0 4 CBX32MV-048 11 4 0 1 CBX32MV-060 20 8 1 0 CBX32MV-024/030 12 12 1 2 CBX40UHV-042 11 4 0 1 CBX32MV-068 10 8 4 5 CBX32MV-036 11 11 2 1 CBX40UHV-048 11 4 0 1 CBX40UHV-048 16 6 0 0 CBX40UHV-024/030 11 11 2 1 CBX40UHV-036 18 3 0 5 CBX40UHV-060 20 8 1 0
-024 CBA27UHE-024 16 11 1 7 CBA27UHE-036 20 5 0 0 CBA27UHE-048 16 6 1 6
CBA27UHE-030 13 11 1 3 CBA27UHV-042 16 6 0 11 CBA27UHE-060 12 7 2 3 CH23-41 10 3 0 0 CH33-43B 14 8 2 1 CH23-68 24 6 2 8 CH33-25A 20 10 1 1 CH33-43C 26 9 2 10 CH33-50, -60C 17 6 1 5 CH33-25B 19 8 1 2 CH33-44/48B 24 8 2 3 CH33-60D 18 6 0 13 CH33-31A 15 11 1 15 CH33-48C 26 9 2 10 CH33-62D 13 7 3 6 CH33-36C 10 12 0 0 CH33-49C 15 8 2 12 CR33-50/60 19 6 1 1 CH33-36A 20 10 1 1 CH33-50/60C 15 8 2 12 CR33-60 19 6 1 1 CR33-30, -036 17 4 0 14 CR33-48 38 5 0 0 C37/CX38/C33/CX34-49C 10 6 1 9 C37/CX38/C33/CX34-25 15 9 0 15 CR33-50, -60 15 5 1 4 C37/CX38/C33/CX34-60 28 7 3 14 C37/CX38/C33/CX34-31 15 16 0 9 C37/CX38/C33/CX34-38 15 4 0 9 C37/CX38/C33/CX34-62C 10 6 3 12 C37/CX38/C33/CX34-36 26 6 0 9 C37/CX38/C33/CX34-43 23 8 2 8 C37/CX38/C33/CX34-62D 14 7 3 12 CBX25UH-030 CBX25UHV-030 CBX25UH-036 19 11 1 5 C37/CX38/C33/CX34-49 11 7 3 9 CBX26UH-060 31 6 3 0
CBX26UH-030 19 11 1 5
CBX27UH-030/036 10 16 1 14
CBX32M-030 7 10 1 3 CBX26UH-042 42 5 0 8 CBX32MV-048 20 6 0 0 CBX32M-036 10 16 1 14 CBX27UH-042, -048 13 5 2 2 CBX32MV-060 17 5 1 4 CBX32MV-024/030 7 10 1 3 CBX32M-048 13 5 2 2 CBX32MV-068 11 8 2 12
-030 CBX32MV-036 10 16 1 14 CBX32MV-048 13 5 2 2 CBX40UHV-048 20 6 0 0
CBX40UHV-030 10 16 1 14 CBX40UHV-042, -048 13 5 2 2 CBX40UHV-060 17 5 1 4 CBX40UHV-036 10 16 1 14 CBA27UHE-042 19 5 0 1 CBA27UHE-060 11 6 1 1 CBA27UHE-030/036 10 11 1 8 CBA27UHE-048 18 6 1 6 CH23-68 27 7 0 13 CH23-41 11 4 0 8 CH23-68 20 9 1 5 CH33-50, -60C 11 4 0 0 CH23-51 11 6 0 14 CH33-43B 7 9 3 2 CH33-62D 19 6 2 4 CH33-31A 16 18 2 8 CH33-43C 22 5 1 0 CR33-50/60 19 6 2 4 CH33-31B 16 18 2 6 CH33-44/48B 18 4 0 0 CR33-60 23 6 1 3 CH33-36A 10 6 0 6 CH33-48C 22 5 1 0 C37/CX38/C33/CX34-62C 10 7 2 14 CH33-36B 6 3 0 0 CH33-49C 16 6 1 6 C37/CX38/C33/CX34-62D 19 7 3 2
The values in this table are most popular match-up pressures; indoor match-up, indoor air quantity, and indoor load will cause the pressures to vary. **Amount of charge required in addition to charge shown on unit nameplate.
Subcool
Heat
(+5ºF)
13 3 0 0
6 6 0 9
17 3 0 15 CBX26UH-036 31 3 0 4 CBX26UH-048 20 10 3 11
9 3 0 8
Additional
Charge
Cool
lbs oz lbs oz lbs oz
(+1ºF)
HP
Indoor Coil or
Size
Air Handler
CH33-36C 10 11 1 5
-030
C37/CX38 C33/CX34-44/-48 CBX25UH-036 CBX25UHV-036
-036
C37/CX38 C33/CX34-44/48
C37/CX38 C33/CX34-50/60 CBX25UH-042 CBX25UHV-042
-042
Subcool
Heat
(+5ºF)
9 21 2 12 C37/CX38/C33/CX34-62D 11 7 1 15
31 3 0 4
40 4 0 15
23 8 2 8 CBX27UH-060 13 7 0 8
42 5 0 8 CBX32M-060 17 5 1 4
Cool
(+1ºF)
Additional
Charge
HP
Indoor Coil or
Size
Air Handler
CH33-50, -60C 10 9 3 4
-042
C37/CX38 C33/CX34-50, -60
CBX25UH-048 CBX25UHV-048
-048
CBX25UH-060 CBX25UHV-060
-060
Subcool
Heat
(+5ºF)
25 8 1 15
15 6 2 5
15 6 2 0
Cool
(+1ºF)
Additional
Charge