Lennox XP13-024-230, XP13-042-230, XP13-030-230, XP13-036-230, XP13-048-230 Installation Instructions Manual

...
Page 1
INSTALLATION
E2012 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
General
This XP13 outdoor heat pump is designed for use with HFC−410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. See the Lennox XP13 Product Specifications bulletin (EHB) for approved indoor component match ups.
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
INSTRUCTIONS
Elite® Series XP13 Units
HEAT PUMP UNITS 506728−01
7/2012 Supersedes 3/2012
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or service agency.
NOTICE !
For more in−depth information, consult the Installa­tion and Service Procedures manual, available as Corp. 0528−L10 on DaveNet or through the Technical Support department at 800−453−6669.
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at discon­nect switch.
Litho U.S.A.
STEP 1 −− SETTING THE UNIT −− Clearances
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
6 (152)
CONTROL PANEL
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
ACCESS
LOCATION
30 (762)
NOTES:
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
7/2012 506728−01
*2P72012* *P506728-01*
FIGURE 1
Page 1
Page 2
UNIT DIMENSIONS − INCHES (MM)
A
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
C
4−3/4"
(121)
B
TOP VIEW
Model Number
XP13−018−230
XP13−024−230
SIDE VIEW
35 (889) 27 (686) 28 (711)
4−1/2"
(108)
A B C
XP13−030−230 31 (787) 30−1/2 (775) 35 (889)
XP13−036−230 39 (991) 30−1/2 (775) 35 (889)
XP13−042−230 45 (1143) 30−1/2 (775) 35 (889)
XP13−048−230 35 (889) 30−1/2 (775) 35 (889)
XP13−060−230 39 (991) 30−1/2 (775) 35 (889)
UNIT SUPPORT
FEET
8−1/2 (216)
8−3/4 (222)
9−1/2 (241)
8−1/4 (210)
UNIT SUPPORT FEET
13−7/8
(352)
7−3/4 (197)
20−5/8
K
(524)
4−1/2
J
(114)
5−1/2 (140)
13−1/2
(343)
XP13−018 AND −024 BASE SECTION (SMALL)
STEP 1 −− SETTING THE UNIT (Continued)
−− Unit Placement
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment.
Page 2
3−1/4
(83)
27−1/8
(689)
3−5/8
(92)
XP13−030 TO −060 BASE WITH ELONGATED
LEGS (MEDIUM)
NOTICE !
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the rubber to degrade. Failure to follow this notice could result in damage to roof surface.
Page 3
WARNING
To prevent personal injury, as well as damage to panels, unit or structure, observe the following:
While installing or servicing this unit, carefully stow all removed panels so that the panels will not cause injury to personnel, objects or nearby structures. Also, take care to store panels where they will not be subject to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions (especially wind) that may cause panels to be blown around and damaged.
IMPORTANT !
Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit performance and longevity.
PLACEMENT
Install unit away from windows.
ELEVATED SLAB MOUNTING USING
FEET EXTENDERS
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2" (50.8MM) SCH 40 MALE THREADED ADAPTER
LEG DETAIL
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
BASE
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
BUILDING
STRUCTURE
MOUNTING SLAB
FIGURE 4
STABILIZING UNIT ON UNEVEN SURFACES
#10 X 1/2" LONG
SELF−DRILLING
SHEET METAL
SCREWS
STABILIZING BRACKET
(18 GAUGE METAL  2"
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1−1/4" LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab  use two plastic anchors (hole drill 1/4")
!
IMPORTANT !
CORNER POST
Unit Stabilizer Bracket Use
(field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions.)
Stabilizers may be used on any unit installed on unstable and uneven surfaces.
COIL
BASE PAN
GROUND LEVEL
FIGURE 3
FIGURE 5
Page 3
XP13 SERIES
Page 4
STEP 2 −− REFRIGERANT PIPING −− Flush­ing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc-
tions. For more information, refer to the Installation and Service Procedures manual available on Dave­Net. CAUTION − DO NOT attempt to flush and re−use ex- isting line sets or indoor coil when the system con­tains contaminants (i.e., compressor burn out).
NOTE − When installing refrigerant lines longer than 50 feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual available on DaveNet (Corp. 9351−L9), or contact the Technical Support Department Product Ap­plication group for assistance.
NOTE − For new or replacement line set installation, refer to Service and Application Note − Corp. 9112−L4 (C−91−4).
TABLE 1
REFRIGERANT LINE SET  INCHES (MM)
WARNING
When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
Field Connec-
Model
−018
−024
−030
−036
−042
−048
−060
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Liquid Line
3/8" (10 mm)
3/8" (10 mm)
3/8" (10 mm)
tions
Suction Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8" (29 mm)
Recommended Line Set
Liquid Line
3/8" (10 mm)
3/8" (10 mm)
3/8" (10 mm)
Suction Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8" (29 mm)
L15 Line Set
L15−41  15 ft. − 50 ft. (4.6 m − 15 m)
L15−65  15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
IMPORTANT !
If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installa­tion. Take care to empty all existing traps. Polyol es­ter (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device and reduce sys­tem performance and capacity.
Failure to properly flush the system per this instruc­tion and the detailed Installation and Service Proce­dures manual will void the warranty.
WARNING
Fire, Explosion and Personal Safety Haz­ard. Failure to follow this warning could re­sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an explosion, that could result in property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT !
Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pres­sure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COM­PRESSOR.
Page 4
Page 5
STEP 2 −− REFRIGERANT PIPING −− Removing Existing Indoor Metering Device
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
A. On fully cased coils, remove the coil access and plumbing panels. B. Remove any shipping clamps from the liquid line and distributor as-
sembly.
C. Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro­cess.
D. Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above.
E. Use a field−provided fitting to temporarily reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
(UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE
OR
BRASS NUT
1B
TWO−PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
LIQUID
D
A. HCFC−22 cylinder with clean refrigerant (positioned to deliver liquid
refrigerant) to the vapor service valve.
B. HCFC−22 gauge set (low side) to the liquid line valve. C. HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.
D. Connect recovery tank to recovery machine per machine instructions.
CYLINDER CONTAINING CLEAN HCFC−22 TO BE USED FOR FLUSHING (Positioned to deliver liquid
A
refrigerant)
1
OUTDOOR
B
VAPOR
NEW
UNIT
C
GAUGE
MANIFOLD
LOW HIGH
OPENED
TANK RETURN
INLET
DISCHARGE
RECOVERY MACHINE
CLOSED
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
LINE
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A. On fully cased coils, remove the coil access and plumbing panels. B. Remove any shipping clamps from the liquid line and distributor
assembly.
C. Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D. Remove the vapor line sensing bulb. E. Disconnect the liquid line from the check expansion valve at the
liquid line assembly.
F. Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
G. Remove and discard check expansion valve and the two Teflon
rings.
H. Use a field−provided fitting to temporarily reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor
B
unit coil.
B. Position the cylinder of clean HCFC−22 for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull the system down to 0.
D. Close the valve on the inverted HCFC−22 drum and the gauge set
valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
®
FIGURE 6
Page 5
XP13 SERIES
Page 6
STEP 2 −− REFRIGERANT PIPING −− Brazing Procedures
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT CORE
LIQUID LINE SERVICE
VALV E
SUCTION / VAPOR LINE
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.
A. Connect gauge set low pressure side to
liquid line service valve (service port).
B. Connect gauge set center port to bottle of
nitrogen with regulator.
C. Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
ATTACH
GAUGES
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
SERVICE
PORT CORE
SERVICE PORT CAP
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
VALV E
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux.
SERVICE
VALV E
A
FIGURE 7
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
NITROGEN
Page 6
Page 7
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water−saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water−saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water−saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths must
6
remain water−saturated throughout the brazing and cool−down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT  Allow braze joint to cool. Apply
additional water−saturated cloths to help cool brazed joint. Do not remove water−saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER−SATURATED CLOTH
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water−saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to Installation and Service Procedures manual found on DAVENET.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water−saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water−saturated cloths.
SUCTION / VAPOR LINE
SERVICE VALVE
WATER−SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
FIGURE 7 (CONTINUED)
Page 7
XP13 SERIES
Page 8
STEP 3 −− INSTALLING INDOOR EXPANSION VALVE
This outdoor unit is designed for use in systems that include an check/expansion valve metering device. See the XP13 Product Specifications bulletin (EHB) for approved check/expansion valve kit match−ups and application information. The
check/expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check/expansion valve in a manner that will provide access for future field service of the check expansion valve. Refer to below illustration for reference during installation of check/expansion valve.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
CHECK
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
RING
LIQUID LINE
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
A. Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.
B. Remove the field−provided fitting that temporarily recon-
nected the liquid line to the indoor unit’s distributor assemb­ly.
®
SENSING
LINE
C. Install one of the provided Teflon® rings around the
stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.
D. Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or or tighten to 20 ft−lb.
E. Place the remaining Teflon® washer around the other
end of the check expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
F. Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft−lb.
SENSING BULB INSTALLATION
A. Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and screws provided.
NOTE  Confirm proper thermal contact between vapor line and check expansion bulb before insulating the sensing bulb once installed.
B. Connect the equalizer line from the check expansion
valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
FIGURE 8
Page 8
VAPOR LINE
12
BULB
NOTE  NEVER MOUNT THE SENSING BULB
ON BOTTOM OF LINE.
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT THE SENSING BULB ON BOTTOM OF LINE.
BULB
Page 9
STEP 4 −− LEAK TEST AND EVACUATION
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
1
2
B
TO VAPOR
SERVICE VALVE
NOTE − Position canister to deliver liquid refrigerant.
NITROGEN
CONNECT GAUGE SET
A Connect the high pressure hose of an HFC−410A manifold gauge set to the vapor valve service port.
NOTE  Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of
the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of
the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit.
Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refriger- ant or three pounds (31 kPa) pressure.] Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
C Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
D Adjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
F After leak testing, disconnect gauges from service ports.
HFC−410A
A
FIGURE 9
Page 9
XP13 SERIES
Page 10
STEP 4 −− LEAK TEST AND EVACUATION (Continued)
CONNECT GAUGE SET
NOTE  Remove cores from service valves (if not already done).
3
A Connect low side of manifold gauge set with
1/4 SAE in−line tee to vapor line service valve
B Connect high side of manifold gauge set to
liquid line service valve
C Connect available micron gauge connector
on the 1/4 SAE in−line tee.
D Connect the vacuum pump (with vacuum
gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
NITROGEN
NOTE − Position canister to deliver liquid refrigerant.
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
EVACUATION
1/4 SAE TEE WITH SWIVEL
A
COUPLER
C
B
500
MICRON
GAUGE
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
LOW
MANIFOLD
D
EVACUATE THE SYSTEM
4
A Open both manifold valves and start the vacuum pump. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following:
S Close manifold gauge valves. S Close valve on vacuum pump. S Turn off vacuum pump.
S Disconnect manifold gauge center port hose from vacuum pump. S Attach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.
S Open manifold gauge valves to break the vacuum in the line set and indoor
unit.
S Close manifold gauge valves.
D Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC−410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
S Close manifold gauge valves. S Shut off HFC−410A cylinder.
S Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
S Replace stem caps and finger tighten them, then tighten an additional one−sixth (1/6) of a turn as illustrated.
Possible equipment damage.
Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuum can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
WARNING !
RECOMMEND
MINIMUM 3/8" HOSE
1/6 TURN
11
10
9
8
7
HIGH
12
1
2
3
4
5
6
FIGURE 10
Page 10
Page 11
STEP 5 −− ELECTRICAL −− Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han­dler for low-voltage control power (24VAC − 40 VA mini­mum)
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to pre­vent compressor damage as a result of slugging.
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
IMPORTANT !
CAUTION
Electrostatic discharge can affect electronic components. Take care during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge.
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or connect to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
FIGURE 11
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control panel.
Page 11
XP13 SERIES
Page 12
Unit Low Voltage Wiring
3
A
THERMOSTAT INDOOR UNIT
24V POWER
R
C
COMMON
W1
1ST-STAGE
AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
C
CUTOUT WITH
GROMMET
24V CONTROL WIRES
Typical 24VAC Control Wiring Diagrams (Field Installed)
R
24V POWER
C
COMMON
W1
1ST-STAGE
W2
W3
AUXILIARY
HEAT
G
WIRE NUTS
BLACK
B
OUTDOOR UNIT
YELLOW
R
C
W1
O
Y1
D
TIGHTEN WIRE TIE
FIGURE 12
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
A Run 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie. C Make 24VAC control wire connections using field provided wire
nuts.
D Tighten wire tie to security 24V control wiring.
NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.
NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS SEPARATION OF FIELD−NSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
THERMOSTAT
R
24V POWER 24V POWER
C
COMMON
E
EMERGENCY
HEAT
W1
1ST-STAGE AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
INDOOR UNIT OUTDOOR UNIT
W1
W2
W3
R
C
G
COMMON
1ST-STAGE AUXILIARY
HEAT
R
C
W1
O
Y1
EMERGENCY
HEAT RELAY
OUTDOOR THERMOSTAT
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJU­RY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over­current protection size.
FIGURE 13
Page 12
Page 13
Charging
The XP13 unit is factory−charged with enough HFC−410A refrigerant to accommodate a 15−foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker on the unit access panel. Detailed information is given in the XP13 Installation and Service Procedures manual, which is available on DaveNet.
Defrost System
The defrost system includes a defrost thermostat (S6) and a defrost control (CMC1).
DEFROST CONTROL (CMC1)
This defrost control includes the combined functions of a time/temperature defrost control, defrost relay, time delay, diagnostic LEDs, and a terminal strip for field wiring con­nections.
DEFROST CONTROL (CMC1)
DEFROST TIMING
PINS (P1)
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT (S6)
S4
HIGH PRESSURE
SWITCH
FIGURE 14
The defrost control provides automatic switching from nor­mal heating operation to defrost mode and back. When the defrost thermostat is closed, the control accumulates com­pressor run time at 30, 60 or 90 minute field adjustable in­tervals. When the selected compressor run time interval is reached, the defrost relay is energized and defrost begins.
Defrost Control Timing Pins (P1)
Each timing pin selection provides a different accumu­lated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initi­ated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 14). The maximum defrost period is 14 minutes and cannot be adjusted.
NOTE  Defrost control part number is listed near the P1 timing pins.
S Factory default is 90 minutes. S If the timing selector jumper is missing, the defrost
control defaults to a 90−minute defrost interval.
LEDS
24V TERMINAL STRIP CONNECTIONS
SERVICE LIGHT CONNECTIONS
Compressor Delay (P5)
The defrost control has a field−selectable function to re­duce occasional sounds that may occur while the unit is cycling in and out of the defrost mode.
The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed.
NOTE  The 30-second compressor feature is ignored when jumpering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the pow­er to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumper­ed. If the jumper is in the TEST position at power-up, the
defrost control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the defrost control will enter the defrost mode. If the jumper is re­moved before an additional 5−second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5−sec­ond period has elapsed, the defrost will terminate and the test option will not function again until the jumper is re­moved and re−applied.
Service Light Connection
The defrost control includes terminal connections for a ser­vice light which provides a signal that activates the room thermostat service light during periods of inefficient opera­tion.
Defrost Control Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
TABLE 2
DEFROST CONTROL (CMC1) DIAGNOSTIC LEDS
Mode Green LED (DS2) Red LED (DS1)
No power to con­trol
Normal operation / power to control
Anti-short cycle lockout
High pressure switch fault
High pressure switch lockout
OFF OFF
Simultaneous Slow FLASH
Alternating Slow FLASH
Slow FLASH OFF
ON OFF
HIGH PRESSURE SWITCH (S4)
This unit is equipped with a high pressure switch which is located on the liquid line. The SPST, normally closed pres­sure switch opens when liquid line pressure rises above the factory setting of 590 + 15 psig and automatically re­sets at 418 + 15 psig.
Page 13
XP13 SERIES
Page 14
Start−Up and Performance Checklist
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
Rated Load Amps: Actual Amps Rated Volts
Condenser Fan Full Load Amps Actual Amps:
COOLING MODE
Suction Pressure: Liquid Pressure:
Supply Air Temperature: Ambient Temperature: Return Air: Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
A B = SUBCOOLING
A B = APPROACH
A B = COIL TEMP DROP
Actual Volts
Page 14
Page 15
Homeowners Information
Cleaning of the outdoor unit’s coil should be performed by a licensed professional service technician (or equivalent). Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and ser­vice your outdoor unit. The following maintenance may be performed by the homeowner.
IMPORTANT !
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts, diminish performance and affect longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its proper operation.
S Please contact your dealer to schedule proper inspec-
tion and maintenance for your equipment.
S Make sure no obstructions restrict airflow to the outdoor
unit.
S Grass clippings, leaves, or shrubs crowding the unit can
cause the unit to work harder and use more energy.
S Keep shrubbery trimmed away from the unit and periodi-
cally check for debris which collects around the unit.
S Keep snow level below the louvered panels to ensure
proper performance.
Routine Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
NOTE The filter and all access panels must be in place any time the unit is in operation. If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
S Ask your Lennox dealer to show you where your indoor
unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
S Disposable filters should be replaced with a filter of the
same type and size.
S The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for
obstructions. (This would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the ComfortSense® 7000 thermostat homeowner manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
S Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of consid­erably hotter air to heat the space.
S Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45F (7C). An electronic control activates a de- frost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
S During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the de­frost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMER­GENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satis­fied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before calling for service:
S Verify room thermostat settings are correct. S Verify that all electrical disconnect switches are ON. S Check for any blown fuses or tripped circuit breakers. S Verify unit access panels are in place. S Verify air filter is clean. S If service is needed, locate and write down the unit
model number and have it handy before calling.
Page 15
XP13 SERIES
Loading...