The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death. It
may also cause cancer, birth defects, or reproductive
harm.
General
This XP13 outdoor heat pump is designed for use with
HFC−410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. See the Lennox
XP13 Product Specifications bulletin (EHB) for approved
indoor component match ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
INSTRUCTIONS
Elite® Series XP13 Units
HEAT PUMP UNITS
506728−01
7/2012
Supersedes 3/2012
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
NOTICE !
For more in−depth information, consult the Installation and Service Procedures manual, available as
Corp. 0528−L10 on DaveNet or through the Technical
Support department at 800−453−6669.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
Litho U.S.A.
STEP 1 −− SETTING THE UNIT −− Clearances
CLEARANCE ON ALL SIDES INCHES (MILLIMETERS)
6 (152)
CONTROL PANEL
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
ACCESS
LOCATION
30 (762)
NOTES:
SClearance to one of the other three
sides must be 36 inches (914mm).
SClearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
7/2012506728−01
*2P72012**P506728-01*
FIGURE 1
Page 1
Page 2
UNIT DIMENSIONS − INCHES (MM)
A
LIQUID LINE
CONNECTION
ELECTRICAL INLETS
SUCTION LINE
CONNECTION
C
4−3/4"
(121)
B
TOP VIEW
Model Number
XP13−018−230
XP13−024−230
SIDE VIEW
35 (889)27 (686)28 (711)
4−1/2"
(108)
ABC
XP13−030−23031 (787)30−1/2 (775)35 (889)
XP13−036−23039 (991)30−1/2 (775)35 (889)
XP13−042−23045 (1143)30−1/2 (775)35 (889)
XP13−048−23035 (889)30−1/2 (775)35 (889)
XP13−060−23039 (991)30−1/2 (775)35 (889)
UNIT SUPPORT
FEET
8−1/2
(216)
8−3/4
(222)
9−1/2
(241)
8−1/4
(210)
UNIT SUPPORT FEET
13−7/8
(352)
7−3/4
(197)
20−5/8
K
(524)
4−1/2
J
(114)
5−1/2
(140)
13−1/2
(343)
XP13−018 AND −024 BASE SECTION (SMALL)
STEP 1 −− SETTING THE UNIT (Continued)
−− Unit Placement
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment.
Page 2
3−1/4
(83)
27−1/8
(689)
3−5/8
(92)
XP13−030 TO −060 BASE WITH ELONGATED
LEGS (MEDIUM)
NOTICE !
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to degrade. Failure to follow this notice
could result in damage to roof surface.
Page 3
WARNING
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following:
While installing or servicing this unit, carefully stow all
removed panels so that the panels will not cause injury
to personnel, objects or nearby structures. Also, take
care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions (especially wind) that may cause
panels to be blown around and damaged.
IMPORTANT !
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor
unit. Prolonged exposure to exhaust gases and the
chemicals contained within them may cause
condensation to form on the steel cabinet and other
metal components of the outdoor unit. This will
diminish unit performance and longevity.
PLACEMENT
Install unit away from windows.
ELEVATED SLAB MOUNTING USING
FEET EXTENDERS
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2" (50.8MM)
SCH 40 MALE
THREADED
ADAPTER
LEG DETAIL
Use additional 2" SCH 40 male
threaded adapters which can
be threaded into the female
threaded adapters to make
additional adjustments to the
level of the unit.
BASE
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
MOUNTING
SLAB
FIGURE 4
STABILIZING UNIT ON UNEVEN SURFACES
#10 X 1/2" LONG
SELF−DRILLING
SHEET METAL
SCREWS
STABILIZING BRACKET
(18 GAUGE METAL 2"
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1−1/4" LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab use two
plastic anchors (hole drill 1/4")
!
IMPORTANT !
CORNER POST
Unit Stabilizer Bracket Use
(field−provided):
Always use stabilizers when unit is raised
above the factory height.
(Elevated units could become unstable in
gusty wind conditions.)
Stabilizers may be used on any unit installed
on unstable and uneven surfaces.
COIL
BASE PAN
GROUND LEVEL
FIGURE 3
FIGURE 5
Page 3
XP13 SERIES
Page 4
STEP 2 −− REFRIGERANT PIPING −− Flushing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc-
tions. For more information, refer to the Installation
and Service Procedures manual available on DaveNet. CAUTION − DO NOT attempt to flush and re−use ex-
isting line sets or indoor coil when the system containscontaminants (i.e., compressor burn out).
NOTE − When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on DaveNet (Corp. 9351−L9),
or contact the Technical Support Department Product Application group for assistance.
NOTE − For new or replacement line set installation, refer
to Service and Application Note − Corp. 9112−L4 (C−91−4).
TABLE 1
REFRIGERANT LINE SET INCHES (MM)
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
Field Connec-
Model
−018
−024
−030
−036
−042
−048
−060
NOTE Some applications may required a field provided 7/8" to
1−1/8" adapter
Liquid
Line
3/8"
(10
mm)
3/8"
(10
mm)
3/8"
(10
mm)
tions
Suction
Line
3/4" (19
mm)
7/8" (22
mm)
1−1/8"
(29
mm)
Recommended Line Set
Liquid
Line
3/8"
(10
mm)
3/8"
(10
mm)
3/8"
(10
mm)
Suction
Line
3/4" (19
mm)
7/8" (22
mm)
1−1/8"
(29
mm)
L15 Line Set
L15−41 15 ft. −
50 ft. (4.6 m − 15
m)
L15−65 15 ft. −
50 ft. (4.6 m − 15
m)
Field Fabricated
IMPORTANT !
If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with
HFC−410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce system performance and capacity.
Failure to properly flush the system per this instruction and the detailed Installation and Service Procedures manual will void the warranty.
WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COMPRESSOR.
A. On fully cased coils, remove the coil access and plumbing panels.
B. Remove any shipping clamps from the liquid line and distributor
assembly.
C. Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D. Remove the vapor line sensing bulb.
E. Disconnect the liquid line from the check expansion valve at the
liquid line assembly.
F.Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during
this process.
G. Remove and discard check expansion valve and the two Teflon
rings.
H. Use a field−provided fitting to temporarily reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant that previously charged the system. Check
the charge in the flushing cylinder before proceeding.
A. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
B
unit coil.
B. Position the cylinder of clean HCFC−22 for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.
C. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.
D. Close the valve on the inverted HCFC−22 drum and the gauge set
valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line
service ports.
SERVICE PORT
CAP
SERVICE
PORT
CORE
LIQUID LINE SERVICE
VALV E
SUCTION / VAPOR LINE
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
A. Connect gauge set low pressure side to
liquid line service valve (service port).
B. Connect gauge set center port to bottle of
nitrogen with regulator.
C. Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
ATTACH
GAUGES
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
SERVICE
PORT
CORE
SERVICE
PORT CAP
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
VALV E
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well−ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
SERVICE
VALV E
A
FIGURE 7
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture. Check the high and low
pressures before applying heat.
NITROGEN
Page 6
Page 7
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water−saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water−saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water−saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths must
6
remain water−saturated throughout the brazing and cool−down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT Allow braze joint to cool. Apply
additional water−saturated cloths to help cool brazed
joint. Do not remove water−saturated cloths until
piping has cooled. Temperatures above 250ºF will
damage valve seals.
LIQUID LINE
WATER−SATURATED
CLOTH
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water−saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak−tested and evacuated. Refer
to Installation and Service Procedures manual found on
DAVENET.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water−saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water−saturated cloths.
SUCTION / VAPOR LINE
SERVICE VALVE
WATER−SATURATED
CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
FIGURE 7 (CONTINUED)
Page 7
XP13 SERIES
Page 8
STEP 3 −− INSTALLING INDOOR EXPANSION VALVE
This outdoor unit is designed for use in systems that include an check/expansion valve metering device. See the XP13
Product Specifications bulletin (EHB) for approved check/expansion valve kit match−ups and application information. The
check/expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the check/expansion valve in a manner that will provide access for future field
service of the check expansion valve. Refer to below illustration for reference during installation of check/expansion valve.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
VAPOR
CHECK
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
RING
LIQUID LINE
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
A. Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure below.
B. Remove the field−provided fitting that temporarily recon-
nected the liquid line to the indoor unit’s distributor assembly.
®
SENSING
LINE
C. Install one of the provided Teflon® rings around the
stubbed end of the check expansion valve and lightly
lubricate the connector threads and expose surface of
the Teflon® ring with refrigerant oil.
D. Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or or tighten
to 20 ft−lb.
E. Place the remaining Teflon® washer around the other
end of the check expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon
ring with refrigerant oil.
F.Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in the figure above or tighten to 20 ft−lb.
SENSING BULB INSTALLATION
A. Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE Confirm proper thermal contact between vapor line
and check expansion bulb before insulating the sensing bulb
once installed.
B. Connect the equalizer line from the check expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
FIGURE 8
Page 8
VAPOR LINE
12
BULB
NOTE NEVER MOUNT THE SENSING BULB
ON BOTTOM OF LINE.
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.
BULB
Page 9
STEP 4 −− LEAK TEST AND EVACUATION
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
1
2
B
TO VAPOR
SERVICE VALVE
NOTE − Position
canister to deliver
liquid refrigerant.
NITROGEN
CONNECT GAUGE SET
AConnect the high pressure hose of an HFC−410A manifold gauge set to the vapor valve service port.
NOTE Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the vapor port better protects the manifold gauge set from high pressure damage.
BWith both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of
the manifold gauge set.
NOTE Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections
and indoor unit for leaks. Use the following procedure to test for leaks:
AWith both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of
the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).
BOpen the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit.
Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refriger-ant or three pounds (31 kPa) pressure.] Close the valve on the HFC−410A cylinder and the valve on
the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
CConnect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
DAdjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
EAfter a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
FAfter leak testing, disconnect gauges from service ports.
HFC−410A
A
FIGURE 9
Page 9
XP13 SERIES
Page 10
STEP 4 −− LEAK TEST AND EVACUATION (Continued)
CONNECT GAUGE SET
NOTE Remove cores from service valves (if not already done).
3
AConnect low side of manifold gauge set with
1/4 SAE in−line tee to vapor line service valve
BConnect high side of manifold gauge set to
liquid line service valve
CConnect available micron gauge connector
on the 1/4 SAE in−line tee.
DConnect the vacuum pump (with vacuum
gauge) to the center port of the manifold
gauge set. The center port line will be used
later for both the HFC−410A and nitrogen
containers.
NITROGEN
NOTE − Position
canister to deliver
liquid refrigerant.
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
EVACUATION
1/4 SAE TEE WITH SWIVEL
A
COUPLER
C
B
500
MICRON
GAUGE
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
LOW
MANIFOLD
D
EVACUATE THE SYSTEM
4
AOpen both manifold valves and start the vacuum pump.
BEvacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute pressure
in a vacuum is equal to atmospheric pressure minus vacuum pressure.
CWhen the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following:
SClose manifold gauge valves.
SClose valve on vacuum pump.
STurn off vacuum pump.
SDisconnect manifold gauge center port hose from vacuum pump.
SAttach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.
SOpen manifold gauge valves to break the vacuum in the line set and indoor
unit.
SClose manifold gauge valves.
DShut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.
EReconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing
the manifold gauge valves.
FWhen the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC−410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line
set and indoor unit.
GPerform the following:
SClose manifold gauge valves.
SShut off HFC−410A cylinder.
SReinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
SReplace stem caps and finger tighten them, then tighten an additional one−sixth (1/6) of a turn as illustrated.
Possible equipment damage.
Avoid deep vacuum operation. Do not use
compressors to evacuate a system.
Extremely low vacuum can cause internal
arcing and compressor failure. Damage
caused by deep vacuum operation will
void warranty.
WARNING !
RECOMMEND
MINIMUM 3/8" HOSE
1/6 TURN
11
10
9
8
7
HIGH
12
1
2
3
4
5
6
FIGURE 10
Page 10
Page 11
STEP 5 −− ELECTRICAL −− Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
IMPORTANT !
CAUTION
Electrostatic discharge can affect
electronic components. Take care
during unit installation and service to
protect the unit’s electronic controls.
Precautions will help to avoid control
exposure to electrostatic discharge by
putting the unit, the control and the
technician at the same electrostatic
potential. Touch hand and all tools on an
unpainted unit surface before
performing any service procedure to
neutralize electrostatic charge.
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and
maximum fuse or circuit breaker (HACR per NEC). Install power
wiring and properly sized disconnect switch.
NOTE Units are approved for use only with copper conductors.
Ground unit at disconnect switch or connect to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
FIGURE 11
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet
(1.5m) from the floor. It should not be installed on an outside wall
or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE 24VAC, Class II circuit connections are made in the control
panel.
Page 11
XP13 SERIES
Page 12
Unit Low Voltage Wiring
3
A
THERMOSTATINDOOR UNIT
24V POWER
R
C
COMMON
W1
1ST-STAGE
AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
C
CUTOUT WITH
GROMMET
24V CONTROL WIRES
Typical 24VAC Control Wiring Diagrams (Field Installed)
R
24V POWER
C
COMMON
W1
1ST-STAGE
W2
W3
AUXILIARY
HEAT
G
WIRE NUTS
BLACK
B
OUTDOOR UNIT
YELLOW
R
C
W1
O
Y1
D
TIGHTEN WIRE TIE
FIGURE 12
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTHAWG# INSULATION TYPE
LESS THAN 100’ (30 METERS)18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS)16 35ºC MINIMUM.
ARun 24VAC control wires through cutout with grommet.
BRun 24VAC control wires through wire tie.
CMake 24VAC control wire connections using field provided wire
nuts.
DTighten wire tie to security 24V control wiring.
NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)
GAUGE PER TABLE ABOVE.
NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS
SEPARATION OF FIELD−NSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL
BOX.
THERMOSTAT
R
24V POWER24V POWER
C
COMMON
E
EMERGENCY
HEAT
W1
1ST-STAGE
AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)
INDOOR UNITOUTDOOR UNIT
W1
W2
W3
R
C
G
COMMON
1ST-STAGE
AUXILIARY
HEAT
R
C
W1
O
Y1
EMERGENCY
HEAT RELAY
OUTDOOR
THERMOSTAT
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with
national and local codes.
NOTE − For use with copper conductors only. Refer to unit
rating plate for minimum circuit ampacity and maximum overcurrent protection size.
FIGURE 13
Page 12
Page 13
Charging
The XP13 unit is factory−charged with enough HFC−410A
refrigerant to accommodate a 15−foot length of refrigerant
piping. Charge should be checked and adjusted using the
tables provided on the charging procedure sticker on the
unit access panel. Detailed information is given in the
XP13 Installation and Service Procedures manual, which
is available on DaveNet.
Defrost System
The defrost system includes a defrost thermostat (S6) and
a defrost control (CMC1).
DEFROST CONTROL (CMC1)
This defrost control includes the combined functions of a
time/temperature defrost control, defrost relay, time delay,
diagnostic LEDs, and a terminal strip for field wiring connections.
DEFROST CONTROL (CMC1)
DEFROST TIMING
PINS (P1)
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT (S6)
S4
HIGH PRESSURE
SWITCH
FIGURE 14
The defrost control provides automatic switching from normal heating operation to defrost mode and back. When the
defrost thermostat is closed, the control accumulates compressor run time at 30, 60 or 90 minute field adjustable intervals. When the selected compressor run time interval is
reached, the defrost relay is energized and defrost begins.
Defrost Control Timing Pins (P1)
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle.
This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60
(T2), or 90 (T3) minutes (see figure 14). The maximum
defrost period is 14 minutes and cannot be adjusted.
NOTE Defrost control part number is listed near the P1
timing pins.
SFactory default is 90 minutes.
SIf the timing selector jumper is missing, the defrost
control defaults to a 90−minute defrost interval.
LEDS
24V TERMINAL
STRIP
CONNECTIONS
SERVICE LIGHT
CONNECTIONS
Compressor Delay (P5)
The defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode.
The compressor will be cycled off for 30 seconds going in
and out of the defrost mode when the compressor delay
jumper is installed.
NOTE The 30-second compressor feature is ignored
when jumpering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps to
protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The
delay is bypassed by placing the timer select jumper
across the TEST pins for 0.5 seconds.
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power-up, the
defrost control will ignore the test pins. When the jumper is
placed across the TEST pins for two seconds, the defrost
control will enter the defrost mode. If the jumper is removed before an additional 5−second period has elapsed
(7 seconds total), the unit will remain in defrost mode until
the defrost thermostat opens or 14 minutes have passed. If
the jumper is not removed until after the additional 5−second period has elapsed, the defrost will terminate and the
test option will not function again until the jumper is removed and re−applied.
Service Light Connection
The defrost control includes terminal connections for a service light which provides a signal that activates the room
thermostat service light during periods of inefficient operation.
Defrost Control Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition.
TABLE 2
DEFROST CONTROL (CMC1) DIAGNOSTIC LEDS
ModeGreen LED (DS2)Red LED (DS1)
No power to control
Normal operation /
power to control
Anti-short cycle
lockout
High pressure
switch fault
High pressure
switch lockout
OFFOFF
Simultaneous Slow FLASH
Alternating Slow FLASH
Slow FLASHOFF
ONOFF
HIGH PRESSURE SWITCH (S4)
This unit is equipped with a high pressure switch which is
located on the liquid line. The SPST, normally closed pressure switch opens when liquid line pressure rises above
the factory setting of 590 + 15 psig and automatically resets at 418 + 15 psig.
Page 13
XP13 SERIES
Page 14
Start−Up and Performance Checklist
Customer Address
Indoor Unit ModelSerial
Outdoor Unit ModelSerial
Notes:
START UP CHECKS
Refrigerant Type:
Rated Load Amps: Actual AmpsRated Volts
Condenser Fan Full Load AmpsActual Amps:
COOLING MODE
Suction Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air: Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
AB=SUBCOOLING
AB=APPROACH
AB= COIL TEMP DROP
Actual Volts
Page 14
Page 15
Homeowners Information
Cleaning of the outdoor unit’s coil should be performed by
a licensed professional service technician (or equivalent).
Contact your dealer and set up a schedule (preferably
twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be
performed by the homeowner.
IMPORTANT !
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its
proper operation.
S Please contact your dealer to schedule proper inspec-
tion and maintenance for your equipment.
S Make sure no obstructions restrict airflow to the outdoor
unit.
S Grass clippings, leaves, or shrubs crowding the unit can
cause the unit to work harder and use more energy.
S Keep shrubbery trimmed away from the unit and periodi-
cally check for debris which collects around the unit.
S Keep snow level below the louvered panels to ensure
proper performance.
Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
NOTE The filter and all access panels must be in place
any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.
SAsk your Lennox dealer to show you where your indoor
unit’s filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind
a return air grille in the wall or ceiling. Check the filter
monthly and clean or replace it as needed.
SDisposable filters should be replaced with a filter of the
same type and size.
SThe indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show
you the location of the drain line and how to check for
obstructions. (This would also apply to an auxiliary
drain, if installed.)
Thermostat Operation
See the ComfortSense® 7000 thermostat homeowner
manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
SHeat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of considerably hotter air to heat the space.
SDo not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45F (7C). An electronic control activates a de-
frost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
SDuring the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the
unit will return to normal operation at the conclusion of
the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the
risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out.
After a six-hour compressor crankcase warm-up period,
the thermostat can be switched to the HEAT setting and
normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before
calling for service:
SVerify room thermostat settings are correct.
SVerify that all electrical disconnect switches are ON.
SCheck for any blown fuses or tripped circuit breakers.
SVerify unit access panels are in place.
SVerify air filter is clean.
SIf service is needed, locate and write down the unit
model number and have it handy before calling.
Page 15
XP13 SERIES
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.