The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death. It
may also cause cancer, birth defects, or reproductive
harm.
General
This XP13 outdoor heat pump is designed for use with
HFC−410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. See the Lennox
XP13 Product Specifications bulletin (EHB) for approved
indoor component match ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
INSTRUCTIONS
Elite® Series XP13 Units
HEAT PUMP UNITS
506728−01
7/2012
Supersedes 3/2012
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
NOTICE !
For more in−depth information, consult the Installation and Service Procedures manual, available as
Corp. 0528−L10 on DaveNet or through the Technical
Support department at 800−453−6669.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
Litho U.S.A.
STEP 1 −− SETTING THE UNIT −− Clearances
CLEARANCE ON ALL SIDES INCHES (MILLIMETERS)
6 (152)
CONTROL PANEL
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
ACCESS
LOCATION
30 (762)
NOTES:
SClearance to one of the other three
sides must be 36 inches (914mm).
SClearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
7/2012506728−01
*2P72012**P506728-01*
FIGURE 1
Page 1
UNIT DIMENSIONS − INCHES (MM)
A
LIQUID LINE
CONNECTION
ELECTRICAL INLETS
SUCTION LINE
CONNECTION
C
4−3/4"
(121)
B
TOP VIEW
Model Number
XP13−018−230
XP13−024−230
SIDE VIEW
35 (889)27 (686)28 (711)
4−1/2"
(108)
ABC
XP13−030−23031 (787)30−1/2 (775)35 (889)
XP13−036−23039 (991)30−1/2 (775)35 (889)
XP13−042−23045 (1143)30−1/2 (775)35 (889)
XP13−048−23035 (889)30−1/2 (775)35 (889)
XP13−060−23039 (991)30−1/2 (775)35 (889)
UNIT SUPPORT
FEET
8−1/2
(216)
8−3/4
(222)
9−1/2
(241)
8−1/4
(210)
UNIT SUPPORT FEET
13−7/8
(352)
7−3/4
(197)
20−5/8
K
(524)
4−1/2
J
(114)
5−1/2
(140)
13−1/2
(343)
XP13−018 AND −024 BASE SECTION (SMALL)
STEP 1 −− SETTING THE UNIT (Continued)
−− Unit Placement
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment.
Page 2
3−1/4
(83)
27−1/8
(689)
3−5/8
(92)
XP13−030 TO −060 BASE WITH ELONGATED
LEGS (MEDIUM)
NOTICE !
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to degrade. Failure to follow this notice
could result in damage to roof surface.
WARNING
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following:
While installing or servicing this unit, carefully stow all
removed panels so that the panels will not cause injury
to personnel, objects or nearby structures. Also, take
care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions (especially wind) that may cause
panels to be blown around and damaged.
IMPORTANT !
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor
unit. Prolonged exposure to exhaust gases and the
chemicals contained within them may cause
condensation to form on the steel cabinet and other
metal components of the outdoor unit. This will
diminish unit performance and longevity.
PLACEMENT
Install unit away from windows.
ELEVATED SLAB MOUNTING USING
FEET EXTENDERS
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2" (50.8MM)
SCH 40 MALE
THREADED
ADAPTER
LEG DETAIL
Use additional 2" SCH 40 male
threaded adapters which can
be threaded into the female
threaded adapters to make
additional adjustments to the
level of the unit.
BASE
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
MOUNTING
SLAB
FIGURE 4
STABILIZING UNIT ON UNEVEN SURFACES
#10 X 1/2" LONG
SELF−DRILLING
SHEET METAL
SCREWS
STABILIZING BRACKET
(18 GAUGE METAL 2"
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1−1/4" LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab use two
plastic anchors (hole drill 1/4")
!
IMPORTANT !
CORNER POST
Unit Stabilizer Bracket Use
(field−provided):
Always use stabilizers when unit is raised
above the factory height.
(Elevated units could become unstable in
gusty wind conditions.)
Stabilizers may be used on any unit installed
on unstable and uneven surfaces.
COIL
BASE PAN
GROUND LEVEL
FIGURE 3
FIGURE 5
Page 3
XP13 SERIES
STEP 2 −− REFRIGERANT PIPING −− Flushing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc-
tions. For more information, refer to the Installation
and Service Procedures manual available on DaveNet. CAUTION − DO NOT attempt to flush and re−use ex-
isting line sets or indoor coil when the system containscontaminants (i.e., compressor burn out).
NOTE − When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on DaveNet (Corp. 9351−L9),
or contact the Technical Support Department Product Application group for assistance.
NOTE − For new or replacement line set installation, refer
to Service and Application Note − Corp. 9112−L4 (C−91−4).
TABLE 1
REFRIGERANT LINE SET INCHES (MM)
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
Field Connec-
Model
−018
−024
−030
−036
−042
−048
−060
NOTE Some applications may required a field provided 7/8" to
1−1/8" adapter
Liquid
Line
3/8"
(10
mm)
3/8"
(10
mm)
3/8"
(10
mm)
tions
Suction
Line
3/4" (19
mm)
7/8" (22
mm)
1−1/8"
(29
mm)
Recommended Line Set
Liquid
Line
3/8"
(10
mm)
3/8"
(10
mm)
3/8"
(10
mm)
Suction
Line
3/4" (19
mm)
7/8" (22
mm)
1−1/8"
(29
mm)
L15 Line Set
L15−41 15 ft. −
50 ft. (4.6 m − 15
m)
L15−65 15 ft. −
50 ft. (4.6 m − 15
m)
Field Fabricated
IMPORTANT !
If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with
HFC−410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce system performance and capacity.
Failure to properly flush the system per this instruction and the detailed Installation and Service Procedures manual will void the warranty.
WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COMPRESSOR.
A. On fully cased coils, remove the coil access and plumbing panels.
B. Remove any shipping clamps from the liquid line and distributor
assembly.
C. Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D. Remove the vapor line sensing bulb.
E. Disconnect the liquid line from the check expansion valve at the
liquid line assembly.
F.Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during
this process.
G. Remove and discard check expansion valve and the two Teflon
rings.
H. Use a field−provided fitting to temporarily reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant that previously charged the system. Check
the charge in the flushing cylinder before proceeding.
A. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
B
unit coil.
B. Position the cylinder of clean HCFC−22 for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.
C. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.
D. Close the valve on the inverted HCFC−22 drum and the gauge set
valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
®
FIGURE 6
Page 5
XP13 SERIES
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.