These instructions are intended as a
general guide and do not supersede
local codes in any way. Consult
authorities having jurisdiction before
installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
NOTICE TO INSTALLER
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on
page 12 to avoid damaging the service valve’s internal seals.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HFCs, and HCFCs) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
Check the unit for shipping damage and listed times below
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook. Coils
previously charged with HCFC−22 must be flushed.
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.
06/11506728−01
are intact. If damaged, or if parts are missing, immediately
contact the last shipping carrier.
1 Assembled XP13 outdoor unit
General
The XP13 outdoor unit uses HFC−410A refrigerant. This
unit must be installed with a matching indoor blower coil
and line set as outlined in the XP13 Engineering
Handbook. These outdoor units are designed for use in
check / expansion valve (CTXV) systems only and are not
to be used with other refrigerant flow control devices. An
indoor coil check / expansion valve approved for use with
HFC−410A must be ordered separately and installed prior
to operating the unit.
FIELD CONNECTION FOR VAPOR
LINE (ANGLE−TYPE − ALL OTHER
SIZES)
FIELD CONNECTION
FOR LIQUID LINE SET
CHECK EXPANSION
VALV E
LIQUID LINE FILTER
DRIER (BI−FLOW)
CRANKCASE HEATER THERMOSTAT (S40)
(−042, −048 AND 060 UNITS ONLY)
HIGH PRESSURE SWITCH
(AUTO−RESET) (S4)
VAPOR LINE SERVICE
VALV E
FIELD CONNECTION
FOR VAPOR LINE
(BALL−TYPE −060 ONLY)
PLUMBING, SWITCHES AND
SENSOR COMPONENTS
Figure 1. Typical Parts Arrangements
Page 3
XP13 SERIES
Caps and Fasteners Torque Requirements
Operating Gauge Set and Service Valves
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc −
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for
small valves, to 25 ft−lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes
Corp.0807−L5 (C−08−1) for further details and
information.
When servicing or repairing HVAC equipment and
components, ensure the fasteners are appropriately
tightened. Table 1 list torque values for various caps and
fasteners.
Table 1. Torque Requirements
PartsRecommended Torque
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for
refrigerant recovery, flushing, leak testing, evacuating,
weighing in refrigerant and optimizing system charge.
Each valve is equipped with a service port which has a
factory−installed valve core. Figure 2 provides information
on how to access and operate both angle− and ball−type
service valves.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low−loss anti−blow back fittings.
Manifold gauge set used for HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The manifold gauges should be rated
for:
High side Pressure range of 0 − 800 pound−force per
square inch gauge (psig)
Low side Use with 30" vacuum to 250 psig with
dampened speed to 500 psig
Manifold gauge set hoses must be rated for use to 800
psig of pressure with a 4000 psig burst rating.
506728−01
Page 4
Operating Angle−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16"
for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open
the service valve.
SERVICE PORT
CORE
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
TO INDOOR
UNIT
TO OUTDOOR
UNIT
VALVE STEM
SHOWN
CLOSED
INSERT HEX−HEAD
2
EXTENSION HERE
TO INDOOR
UNIT
TO OUTDOOR UNIT
When service valve is OPEN, the service port is open to line set,
indoor and outdoor unit.
STEM CAP
Operating Ball−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open.
ATo open rotate stem
counterclockwise
90°.
BTo close rotate stem
clockwise 90°.
SERVICE PORT
SERVICE PORT CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
NOTE A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
TO INDOOR UNIT
BALL (SHOWN CLOSED)
VALVE STEM
2
REMOVE
1
STEM CAP
When service valve stem is in the CLOSED position,
the service port is open to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and
tighten as follows:
With torque wrench: Finger tighten and torque cap per table 1.
Without torque wrench: Finger tighten and use an appropriately sized
wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and
serves as the primary seal. Replace the stem cap and
tighten as follows:
With Torque Wrench: Finger tighten and then
torque cap per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise.
Figure 2. Angle and Ball−Type Service Valves
9
10
9
10
8
8
1
11
7
11
7
REMOVE
STEM CAP
1/6 TURN
12
1
2
4
5
6
1/12 TURN
12
1
2
4
5
6
3
3
Page 5
XP13 SERIES
Recovering Refrigerant from Existing System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
1
switch and/or main fuse box/breaker panel.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
3
Remove existing HCFC−22 refrigerant using one of the following procedures:
METHOD 1:
Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or
if the unit is not operational and you plan to use the existing HCFC−22 to flush
the system.
Recover all HCFC−22 refrigerant from the existing system using a recovery
machine and clean recovery cylinder. Check gauges after shutdown to confirm
that the entire system is completely void of refrigerant.
METHOD 2:
Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves,
and you plan to use new HCFC−22 refrigerant to flush the system.
Perform the following task:
AStart the existing HCFC−22 system in the cooling mode and close the liquid line
valve.
BUse the compressor to pump as much of the existing HCFC−22 refrigerant into
the outdoor unit until the outdoor system is full. Turn the outdoor unit main power
OFF and use a recovery machine to remove the remaining refrigerant from the
system.
NOTE It may be necessary to bypass the low pressure switches (if equipped) to
ensure complete refrigerant evacuation.
CWhen the low side system pressures reach 0 psig, close the vapor line valve.
DCheck gauges after shutdown to confirm that the valves are not allowing
refrigerant to flow back into the low side of the system.
CONNECT MANIFOLD GAUGE SET
Connect a manifold gauge set, clean recovery cylinder and a
2
recovery machine to the service ports of the existing unit..
NOTE Use the recovery machine instructions to make
the correct manifold gauge set connections for recovery
refrigerant. The illustration below is a typical connection.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY
CYLINDER
OUTDOOR UNIT
METHOD 2 LIMITATIONS
NOTE When using Method 2, the listed devices
below could prevent full system charge recovery into
the outdoor unit:
Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycle the
compressor OFF.
Compressor can stop pumping due to tripped
internal pressure relief valve.
Compressor has internal vacuum protection that
is designed to unload the scrolls (compressor
stops pumping) when the pressure ratio meets a
certain value or when the suction pressure is as
high as 20 psig. (Compressor suction
pressures should never be allowed to go into
a vacuum. Prolonged operation at low suction
pressures will result in overheating of the
scrolls and permanent damage to the scroll
tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower
pressure due to any of the above mentioned system
conditions, shut off the vapor valve. Turn OFF the main
power to unit and use a recovery machine to recover
any refrigerant left in the indoor coil and line set.
HIGH
Figure 3. Refrigerant Recovery
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance,
service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
506728−01
Page 6
New Outdoor Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Remove existing outdoor unit prior to placement of new
outdoor unit. See Unit Dimensions on page 2 for sizing
mounting slab, platforms or supports. Refer to figure 4 for
mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 5,
detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 5,
detail B.
NOTE If necessary for stability, anchor unit to slab as
described in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated
in figure 5, detail C.
If additional elevation is necessary, raise the unit by
extending the height of the unit support feet. This may be
achieved by using a 2 inch (50.8mm) schedule 40 female
threaded adapter.
NOTE Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build−up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit. Consult local codes for
rooftop applications. See figure 5, detail F for other roof top
mounting considerations.
CLEARANCE ON ALL SIDES INCHES (MILLIMETERS)
NOTES:
Service clearance of 30 inches (762 mm) must be
maintained on one of the sides adjacent to the
control panel
Clearance to one of the other three sides must be 36
inches (914mm).
Clearance to one of the remaining two sides may be
12 inches (305mm) and the final side may be 6
inches (152mm).
CONTROL PANEL ACCESS
LOCATION
MINIMUM CLEARANCE BETWEEN TWO UNITS
24
(610)
Figure 4. Installation Clearances
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell
when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid
exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof
surface.
Page 7
XP13 SERIES
DETAIL A
Install unit away from windows.
Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2)
degrees (or two inches per five feet [50 mm per 1.5 m]) away from
building structure.
Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING
SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
Elevated Slab Mounting
DETAIL C
LEG DETAIL
2" (50.8MM) SCH 40
FEMALE THREADED
2" (50.8MM) SCH 40
MALE THREADED
Use additional 2" SCH 40 male threaded adapters which
can be threaded into the female threaded adapters to
make additional adjustments to the level of the unit.
DETAIL E
using Feet Extenders
ADAPTER
ADAPTER
Deck Top Mounting
BASE
GROUND LEVEL
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL 2" WIDTH; HEIGHT AS
#10 1−1/4" LONG HEX HD SCREW
Concrete slab use two plastic anchors (hole
drill 1/4")
Wood or plastic slab no plastic anchor (hole
drill 1/8")
Stabilizing bracket (18 gauge metal 2" (50.8mm) width; height as required); bend to form
right angle as exampled below.
DETAIL F
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be
constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24
inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.
Slab Side Mounting
COIL
BASE PAN
REQUIRED)
AND FLAT WASHER
CORNER POST
Roof Top Mounting
PREVAILING WINTER WINDS
WIND BARRIER
INLET AIR
506728−01
One bracket per side
(minimum). For extra
stability, two brackets per
side, two inches (51mm)
from each corner.
SAME FASTENERS AS
SLAB SIDE MOUNTING.
Figure 5. Placement, Slab Mounting and Stabilizing Unit
MINIMUM ONE
PER SIDE
FOR EXTRA
STABILITY
Page 8
INLET AIR
INLET AIR
INLET AIR
Removing and Installing Panels
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly.
2. Hold the panel firmly throughout this procedure. Rotate
bottom corner of panel away from hinged corner post until
lower three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in
corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in
detail D with the screw side as close to the unit as possible.
Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as
illustrated in detail A and C; then upward into the top
slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
4. When panel is correctly positioned and aligned, insert
the screws and tighten.
Detail C
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR
ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
HOLES
Detail A
Detail B
ROTATE IN THIS DIRECTION;
ANGLE MAY BE TOO
EXTREME
THEN DOWN TO REMOVE
HOLD DOOR FIRMLY TO THE HINGED
PANEL
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
PREFERRED ANGLE
FOR INSTALLATION
Detail D
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO
PARALLEL WITH THE UNIT AS POSSIBLE) WHILE
INSTALLING PANEL.
Figure 6. Removing and Installing Panels
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause
injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g.,
being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause
panels to be blown around and battered.
Page 9
XP13 SERIES
Line Set Requirements
This section provides information on: installation of new or
replacement line set.
Adding Polyol ester oil requirements
New or replacement line set installation
Using existing line set.
ADDING POLYOL ESTER OIL REQUIREMENTS
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol Ester oil.
The compressor is charged with sufficient Polyol Ester oil
(POE) for line set lengths up to 50 feet. Recommend
adding oil to system based on the amount of refrigerant
charge in the system. Systems with 20 pounds or less of
refrigerant required no oil to be added.
For systems over 20 pounds − add one ounce for every five
(5) pounds of HFC−410A refrigerant.
Recommended topping−off POE oils are Mobil EAL
ARCTIC 22 CC or ICI EMKARATE RL32CF.
NEW OR REPLACEMENT LINE SET INSTALLATION
Field refrigerant piping consists of both liquid and vapor
lines from the outdoor unit to the indoor coil. Use Lennox
L15 (sweat, non−flare) series line set, or field−fabricated
refrigerant line sizes as specified in table 2.
If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 7 for recommended
installation practices.
NOTE When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351−L9, or contact
Lennox Technical Support Product Applications for
assistance. To obtain the correct information from Lennox,
be sure to communicate the following information:
Table 2. Refrigerant Line Set Inches (mm)
Model (XP13) and size of unit (e.g. −036).
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows vertical rise or drop in the piping.
USING EXISTING LINE SET
Things to consider:
Liquid line that meter the refrigerant, such as RFC1
liquid line, must not be used in this application.
Existing line set of proper size as listed in table 2 may
be reused.
If system was previously charged with HCFC−22
refrigerant, then existing line set must be flushed (see
Flushing Line Set and Indoor Coil on page 15).
If existing line set is being used, then proceed to BrazingConnections on page 11.
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A. If that is not possible and the line set is the
proper size as reference in table 2, use the procedure
outlined under Flushing Line Set and Indoor Coil on page
13.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
NOTE Some applications may required a field provided 7/8" to 1−1/8" adapter
506728−01
Liquid LineSuction LineLiquid LineSuction LineL15 Line Set
3/8" (10 mm)3/4" (19 mm)3/8" (10 mm)3/4" (19 mm)L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
3/8" (10 mm)7/8" (22 mm)3/8" (10 mm)7/8" (22 mm)L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field ConnectionsRecommended Line Set
Page 10
Line Set Isolation The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL
STUD
NON−CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO
VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED
IN ARMAFLEX
REFRIGERANT LINE SET INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
WIRE TIE (AROUND
VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE
METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST
OR RAFTER AT 8 FEET (2.43 METERS)
INTERVALS THEN STRAP THE LIQUID
LINE TO THE VAPOR LINE.
TAPE OR
WIRE TIE
REFRIGERANT LINE SET INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater
than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID
LINE
NOTE Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON−CORROSIVE
METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
ROOF RAFTER
Figure 7. Line Set Installation
Page 11
XP13 SERIES
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves.
WARNING
Polyol Ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture − Check the high and low
pressures before applying heat.
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well−ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver
alloy for copper−to−copper brazing. Use 45% minimum
alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an explosion, that could result in property
damage, personal injury or death.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
506728−01
Page 12
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
CUT AND DEBUR
CAP AND CORE REMOVAL
Remove service cap and core from both the suction / vapor and
2
liquid line service ports.
SERVICE PORT
CAP
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
COPPER TUBE
REDUCER
SERVICE VALVE
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
SERVICE
PORT
CORE
SUCTION / VAPOR LINE
SERVICE VALVE (BALL−TYPE
FOR −060 AND ANGLE−TYPE
FOR ALL OTHER SIZES)
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
AConnect gauge set low pressure side to liquid line service valve (service port).
BConnect gauge set center port to bottle of nitrogen with regulator.
CRemove core from valve in suction / vapor line service port to allow nitrogen to escape.
SERVICE
PORT
CORE
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
LOW
ATTACH
GAUGES
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 8. Brazing Procedures
B
OUTDOOR
UNIT
HIGH
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
Page 13
XP13 SERIES
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
BRAZE LINE SET
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water
6
saturated cloths must remain water saturated throughout the brazing and cool−down process.
SUCTION / VAPOR LINE
SERVICE VALVE
VAPOR LINE SERVICE VALVE
COULD BE EITHER A ANGLE−TYPE
OR BALL−TYPE VALVE.
WHEN BRAZING
LINE SET TO
SERVICE VALVES,
POINT FLAME
AWAY FROM
SERVICE VALVE.
LIQUID LINE SERVICE VALVE
ANGLE−TYPE SERVICE
VAL VE
WATER SATURATED
CLOTH
LIQUID LINE
SUCTION / VAPOR LINE
WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both
7
service valves to cool piping. Once piping is cool, remove all water saturated cloths.
FROM SERVICE VALVE.
Figure 9. Brazing Procedures (continued)
WATER SATURATED
CLOTH
IMPORTANT
Allow braze joint to cool. Apply additional water saturated cloths to help cool brazed joint. Do not remove water saturated
cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing
in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated.
Refer to procedures provided in this supplement.
506728−01
Page 14
Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil
Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then
remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 16.
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps holding the liquid line and distributor as-
sembly.
CUsing two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this process.
DRemove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
EUse a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
TEFLON® RING
FIXED ORIFICE
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE (UNCASED
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
2
INVERTED HCFC−22
CYLINDER CONTAINS
CLEAN HCFC−22 TO BE
USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
LIQUID
VAPOR
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY MACHINE
AInverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
BHCFC−22 gauge set (low side) to the liquid line valve.
CHCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
DConnect recovery tank to recovery machines per machine instructions.
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps holding the liquid line and distributor
assembly.
CDisconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
DRemove the vapor line sensing bulb.
EDisconnect the liquid line from the check expansion valve at the liquid
line assembly.
FDisconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
GRemove and discard check expansion valve and the two Teflon® rings.
HUse a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
LIQUID LINE
SENSING BULB
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.
ASet the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
B
set and indoor unit coil.
BInvert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line
valve. Allow the refrigerant to pass from the cylinder and through
the line set and the indoor unit coil before it enters the recovery
machine.
CAfter all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull down to 0
the system.
DClose the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
LINE
LIQUID
LINE
Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures
Page 15
XP13 SERIES
Installing New Indoor Metering Device
This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased
separately) at the indoor coil.
See the Lennox XP13 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion
valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing
of the check / expansion valve (see figure 11).
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
VAPOR
CHECK /
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
RING
SENSING
LIQUID LINE
BRASS NUT
LIQUID LINE
Sensing bulb insulation is
required if mounted external to
the coil casing.
EQUALIZER LINE INSTALLATION
Remove and discard either the flare seal cap or flare nut with
copper flare seal bonnet from the equalizer line port on the vapor
line as illustrated in the figure to the right.
®
LINE
ARemove the field−provided fitting that temporarily
reconnected the liquid line to the indoor unit’s distributor
assembly.
BInstall one of the provided Teflon® rings around the
stubbed end of the check / expansion valve and lightly
lubricate the connector threads and expose surface of
the Teflon® ring with refrigerant oil.
CAttach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft−lb.
DPlace the remaining Teflon® washer around the other
end of the check / expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon
ring with refrigerant oil.
EAttach the liquid line assembly to the check / expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in the figure above or 20 ft−lb.
SENSING BULB INSTALLATION
AAttach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE Confirm proper thermal contact between vapor line
and expansion bulb before insulating the sensing bulb once
installed.
BConnect the equalizer line from the check / expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT ON
BOTTOM OF LINE.
BULB
Leak Test Line Set and Indoor Coil
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
CONNECT GAUGE SET
AConnect an HFC−410A manifold gauge set high pressure hose to the
vapor valve service port.
NOTE Normally, the high pressure hose is connected to the liquid
line port. However, connecting it to the vapor port better protects the
manifold gauge set from high pressure damage.
BWith both manifold valves closed, connect the cylinder of HFC−410A
refrigerant to the center port of the manifold gauge set.
NOTE Later in the procedure, the
HFC−410A container will be replaced by
the nitrogen container.
HIGHLOW
MANIFOLD GAUGE SET
NITROGEN
Figure 12. Manifold Gauge Set Connections for Leak Testing
TEST FOR LEAKS
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. Use the following procedure to test for leaks:
1. With both manifold valves closed, connect the cylinder
of HFC−410A refrigerant to the center port of the
manifold gauge set. Open the valve on the HFC−410A
cylinder (vapor only).
2. Open the high pressure side of the manifold to allow
HFC−410A into the line set and indoor unit. Weigh in
a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure
HFC−410A
B
TO VAPOR
SERVICE VALVE
(ANGLE OR BALL
TYPE)
A
OUTDOOR UNIT
side of the manifold gauge set. Disconnect the
HFC−410A cylinder.
3. Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set.
4. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
5. After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
6. After leak testing disconnect gauges from service
ports.
Page 17
XP13 SERIES
Evacuating Line Set and Indoor Coil
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any
gas that will not condense under temperatures and pressures present during operation of an air conditioning system.
Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and
compressor parts.
CONNECT GAUGE SET
NOTE Remove cores from service valves (if not already done).
1
AConnect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line
service valve
BConnect high side of manifold gauge
set to liquid line service valve
CConnect micron gauge available
connector on the 1/4 SAE in−line tee.
DConnect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC−410A and nitrogen containers.
NITROGEN
OUTDOOR
UNIT
HFC−410A
VACUUM PUMP
A
B
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
C
MICRON
GAUGE
TO LIQUID LINE
SERVICE VALVE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VALVE
RECOMMEND
MINIMUM 3/8" HOSE
D
EVACUATE THE SYSTEM
AOpen both manifold valves and start the vacuum pump.
2
BEvacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
CWhen the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves
Close valve on vacuum pump and turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
DShut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
EReconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
FWhen the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.
GPerform the following:
Close manifold gauge valves.
Shut off HFC−410A cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
10
9
11
8
1/6 TURN
12
7
6
HIGHLOW
1
2
3
4
5
506728−01
Figure 13. Evacuating Line Set and Indoor Coil
Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air
handler for low-voltage control power (24VAC − 40 VA
minimum)
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and
maximum fuse or circuit breaker (HACR per NEC). Install power
wiring and properly sized disconnect switch.
NOTE Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
UNIT LOW VOLTAGE CONNECTIONS
3
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet
(1.5m) from the floor. It should not be installed on an outside wall
or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE 24VAC, Class II circuit connections are made in the control
panel.
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTHAWG# INSULATION TYPE
LESS THAN 100’ (30 METERS)18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS)16 35ºC MINIMUM.
A
D
B
C
TERMINAL STRIP
Page 19
ARun 24VAC control wires through cutout with grommet.
BRun 24VAC control wires through wire tie.
CMake 24VAC control wire connections defrost control terminal strip.
DTighten wire tie to security 24V control wiring.
NOTE − FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)
GAUGE PER TABLE ABOVE.
NOTE − WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN
SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE − DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL
BOX.
XP13 SERIES
Figure 14. Typical Unit Wiring Diagram
506728−01
Page 20
Figure 15. Typical Factory Wiring
Unit Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.
UNIT START−UP
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose
connections.
3. Verify that the manifold gauge set is connected as
illustrated in figure 17. Use a temperature sensor
positioned near the liquid line service port as illustrated
in figure 17 which will be required later when using the
subcooling method for optimizing the system
refrigerant charge.
4. Replace the stem caps and tighten to the value listed
in table 1.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.
6. Open both the liquid and vapor line service valves to
release the refrigerant charge contained in outdoor
unit into the system.
7. Use figure 16 to determine next step in system
preparation.
OPEN BOTH VAPOR AND LIQUID SERVICE
VALVE STEMS TO RELEASE
REFRIGERANT FROM OUTDOOR UNIT TO
GO TO SERVICE AND WEIGH
IN REFRIGERANT CHARGE
FOR OUTDOOR UNITS
DELIVERED VOID OF CHARGE
ON PAGE 22.
SYSTEM.
REFRIGERANT
PRESENT
YESNO
GO TO OPTIMIZING SYSTEMREFRIGERANT CHARGE ON
PAGE 24.
Figure 16. Outdoor Unit Factory Charge
Page 21
XP13 SERIES
Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge
The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the
next section if refrigerant charge is present.
LEAK CHECK, REPAIR AND EVACUATE
If the outdoor unit is void of refrigerant, clean the system
using the procedure described below.
1. Leak check system using procedures provided on
page 17. Repair any leaks discovered during leak test.
2. Evacuate the system using procedure provided in
figure 13.
3. Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again using procedure in figure
13.
CONNECT MANIFOLD GAUGE SET AND WEIGH−IN
CHARGE
After the evacuation procedure, reconnect the manifold
gauge set as illustrated in figure 17.
NOTE − Temperature sensor illustrated in figure 17 is not
required for initial system weigh in charging.
MANIFOLD GAUGE SET
1. Close manifold gauge set valves and connect the
gauge set as exampled in figure 17.
2. Check that fan rotates freely.
3. Inspect all factory− and field−installed wiring for loose
connections.
4. Open the high side manifold gauge valve and weigh in
liquid refrigerant. Use figure 18 to calculate the correct
weigh−in charge.
5. Close manifold gauge valves.
6. Monitor the system to determine the amount of
moisture remaining in the oil. It may be necessary to
replace the bi−flow filter drier several times to achieve
the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
7. Continue to Optimizing System Refrigerant Charge
on page 24 to optimize the system charge using
subcooling method.
GAUGE SET
NOTE Refrigerant
tank should be turned
right−side−up to deliver
vapor during charge
optimizing procedure.
HFC−410A
REFRIGERANT
TANK
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set
for liquid phase charging.
BConnect the manifold gauge set’s low pressure side to the true suction port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port (use only for subcooling
method).
LOW
A
TO LIQUID
LINE SERVICE
VALV E
C
HIGH
TRUE SUCTION PORT
CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE
B
CONNECTION
TEMPERATURE
SENSOR
(LIQUID LINE)
D
NOTE For simplify the illustration,
the line set is not shown connected to
service valves.
Figure 17. Typical Gauge Set Connections for Initial Weight−in Charge or Optimizing System Charge
506728−01
Page 22
WEIGH−IN CHARGING
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount specified on
nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
+
Refrigerant Charge per Line Set Length
LIQUID LINE SET DIAMETER
3/8" (9.5 MM)
*If line length is greater than 15 feet (4.6 meters), add this amount. If line length
is less than 15 feet (4.6 meters), subtract this amount.
NOTE Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature
of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
OUNCES PER 5 FEET (GRAMS PER 1.5 METERS)
ADJUST FROM 15 FEET (4.6 METERS) LINE SET*
3 OUNCE PER 5’ (85 GRAMS PER 1.5 M)
Figure 18. Using HFC−410A Weigh In Method
Additional charge specified per
match indoor air handler or coil
listed in table 3.
+
Total Charge
=
OUTDOOR UNIT
CHECK / EXPANSION
VALV E
BI−FLOW FILTER / DRIER
SERVICE PORT
MUFFLER
LIQUID LINE
DISTRIBUTOR
OUTDOOR
COIL
COMPRESSOR
REVERSING VALVE
TRUE SUCTION
PORT
VAPOR
SERVICE
PORT
CHECK / EXPANSION VALVE
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and
indoor coil. Use true suction port to measure vapor pressure during charging.
Figure 19. Heat Pump Cooling Cycle
NOTE − ARROWS INDICATE DIRECTION
OF REFRIGERANT FLOW
INDOOR UNIT
INDOOR
COIL
Page 23
XP13 SERIES
Optimizing System Refrigerant Charge
This section provides instructions on optimizing the
system charge. This section includes:
1. Move the low−side manifold gauge hose from the
vapor line service valve to the true suction port (see
figure 17).
2. Set the thermostat for either cooling or heating
demand. Turn on power to the indoor unit and close
the outdoor unit disconnect switch to start the unit.
3. Allow unit to run for five minutes to allow pressures to
stabilize.
4. Check the airflow as instructed under Adjusting IndoorAirflow to verify or adjust indoor airflow for maximum
efficiency. Make any air flow adjustments before
continuing with the optimizing procedure.
5. Use subcooling method to optimize the system
charge (see figure 21). Adjust charge as necessary.
ADJUSTING INDOOR AIRFLOW
Heating Mode Indoor Airflow Check
(Only use when indoor unit has electric heat)
Indoor blower airflow (CFM) may be calculated by
energizing electric heat and measuring:
Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
Measuring voltage supplied to the unit,
Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in the following
formula to determine CFM:
CFM =
Check airflow using the Delta−T (DT) process using figure
Figure 20. Checking Airflow over Indoor Coil Using Delta−T Formula
1. Determine the desired DTMeasure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between
the measured T
+
3º, no adjustment is needed. See examples: Assume DT =
and the desired DT (T
Drop
) = A minus C.
Drop
15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
53º 19–15 =4Increase the airflow
58º14–15=−1 (within +3º range) no change
62º10–15=−5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
–DT=ºF ACTION
Drop
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within
3º.
+
–DT) is within
Drop
506728−01
Page 24
OPTIMIZE CHARGE USING SUBCOOLING
1. Check liquid and vapor line pressures. Compare pressures with either second−stage heat
or cooling mode normal operating pressures listed in table 4. Table 4 is a general guide
and expect minor pressures variations. Significant pressure differences may indicate
improper charge or other system problem.
2. Decide whether to use cooling or heating mode based on current outdoor ambient
USE
COOLING
MODE
60ºF
(15ºC)
USE
HEATING
MODE
temperature:
AUse COOLING MODE when:
Outdoor ambient temperature is 60°F (15.5°C) and above.
Indoor return air temperature range is between 70 to 80°F (21−27°C). This
temperature range is what the target subcooling values are base upon in table
3.
If indoor return air temperature is not within reference range, set thermostat to
cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit into
second−stage (high−capacity) cooling mode. When operating and temperature
pressures have stabilized, continue to step 3.
BUse HEATING MODE when:
Outdoor ambient temperature is 59°F (15.0°C) and below.
Indoor return air temperature range is between 65−75°F (18−24°C). This
temperature range is what the target subcooling values are base upon in table
3.
If indoor return air temperature is not within reference range, set thermostat to
heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit into
second−stage (high−capacity) heating mode. When operating and temperature
pressures have stabilized, continue to step 3.
SATº
LIQº–
SCº=
3. Read the liquid line pressure; then find its corresponding temperature pressure listed in
table 5 and record it in the SATº space to the left.
4. Read the liquid line temperature; record in the LIQº space to the left.
5. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in
SCº space to the left..
6. Compare SCº results with table 3 (either Heating or Cooling mode column), also
consider any additional charge required for line set lengths longer than 15 feet and/or unit
matched component combinations (Add Charge column).
7. If subcooling value is:
AGREATER than shown for the applicable unit match component, REMOVE
refrigerant;
BLESS than shown for the applicable unit match component, ADD refrigerant.
8. If refrigerant is added or removed, repeat steps 3 through 6 to verify charge.
9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit.
10. Replace the stem and service port caps and tighten as specified in Operating ServiceValves on page .
11. Recheck voltage while the unit is running. Power must be within range shown on the
nameplate.
Figure 21. Using HFC−410A Subcooling Method Second Stage (High Capacity)
Page 25
XP13 SERIES
APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND
ADD CHARGE VALUES
Listed below are the approved matched system
components (air handlers and indoor coils), targeted
subcooling and add charge values for the XP13. This
information is also listed on the unit charging sticker
located on the outdoor unit access panel.
Subcooling values listed in the following tables are based
on outdoor ambient air temperature of:
60°F (15.5°C) and above for cooling mode
59°F (15.0°C) and below for heating mode.
Table 3. Unit Indoor Matches, Targeted Subcooling, and Add Charge Values
*Amount of charge required in additional to charge shown on unit nameplate.CX34−62D7700
Subcooling
HeatCoolLbsOz.HeatCoolLbsOz.HeatCoolLbsOz.
*Additional
Charge
Indoor Coil or Air
Size
Handler
CBX26UH−036191500CBX27UH−04810815
−036
CBX26UH−04211711CR33−60D76012
−042
Subcooling
*Additional
Charge
Indoor Coil or Air
Size
Handler
CBX26UH−0487712
−048
CBX26UH−06068111
−060
Subcooling
*Additional
Charge
Table 4. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG
IMPORTANT
Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer
to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some
component in the system.
Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.
High Pressure Switch (S4)
This unit is equipped with a auto-reset high pressure
switch (single−pole, single−throw) which is located on the
liquid line. The switch shuts off the compressor when
discharge pressure rises above the factory setting. High
Pressure (auto reset) − trip at 590 psig, reset at 418 psig.
Low Pressure Switch (S87)
This unit is equipped an auto−reset low pressure switch
which is located on the vapor line. The switch shuts off the
compressor when the vapor pressure falls below the
factory setting. Low Pressure (auto reset) − trip at 25 psig,
reset at 40 psig.
Low Pressure Switch Bypass (S41) (Optional)
For use in applications where the heat pump is operated in
outdoor ambient temperatures below 15°F.
Prevents nuisance trips form the low pressure switch
Wired in parallel with the low pressure switch
Thermal Protection Switch (S173) Compressor
Mounted
Some units are equipped with a compressor mounted
normally closed temperature switch that prevents
compressor damage due to overheating caused by
internal friction. The switch is located on top of the
compressor casing (see figure 1). This switch senses the
compressor casing temperature and opens at 239−257°F
(115°C−125°C) to shut off compressor operation. The
auto−reset switch closes when the compressor casing
temperature falls to 151−187°F (66°C−86°C), and the
compressor is re−energized. This single−pole, single−throw
(SPST) bi−metallic switch is wired in series with the 24V Y
input signal to control compressor operation.
Crankcase Thermostat (S40) (−042, −048 and −060
Units Only)
The reference models are equipped with a 70 watt, belly
band type crankcase heater. HR1 prevents liquid from
accumulating in the compressor. HR1 is controlled by a
thermostat located on the liquid line. When liquid line
temperature drops below 50° F the thermostat closes
energizing HR1. The thermostat will open, de−energizing
HR1 once liquid line temperature reaches 70° F .
Defrost Thermostat (S6)
The defrost thermostat is located on the liquid line between
the check/expansion valve and the distributor. When
defrost thermostat senses 42°F (5.5°C) or cooler, the
thermostat contacts close and send a signal to the defrost
control to start the defrost timing. It also terminates defrost
when the liquid line warms up to 70°F (21°C).
Bi−Flow Liquid Line Filter Drier
The unit is equipped with a large−capacity biflow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of the same design and capacity.
The replacement filter drier must be suitable for use with
HFC−410A refrigerant.
Defrost System
The XP13 defrost system includes two components: a
defrost thermostat (S6) and a defrost control (CMC1)
(figure 14).
FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT
S4
HIGH PRESSURE
SWITCH
Figure 22. Defrost Control (CMC1)
DEFROST CONTROL (CMC1)
The defrost control includes the combined functions of a
time/temperature defrost control, defrost relay, diagnostic
LEDs and terminal strip for field wiring connections.
The defrost control provides automatic switching from
normal heating operation to defrost mode and back. When
the defrost thermostat is closed, the control accumulates
compressor run time at 30, 60 or 90 minute field adjustable
intervals. When the selected compressor run time interval
is reached, the defrost relay is energized and defrost
begins.
Defrost Control Timing Pins (P1)
Each timing pin selection provides a different
accumulated compressor run time period for one defrost
cycle. This time period must occur before a defrost cycle
is initiated. The defrost interval can be adjusted to 30
(T1), 60 (T2), or 90 (T3) minutes (see figure 22). The
maximum defrost period is 14 minutes and cannot be
adjusted.
NOTE Defrost control part number is listed near the P1
timing pins.
Units with defrost control 100269−02: Factory default
is 60 minutes
Units with defrost control 100269−04: Factory default
is 90 minutes
If the timing selector jumper is missing, the defrost
control defaults to a 90−minute defrost interval.
LEDS
24V TERMINAL
STRIP
CONNECTIONS
506728−01
Page 28
Compressor Delay (P5)
The defrost control has a field−selectable function to
reduce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode.
Units with defrost control 100269−02: The compressor
will be cycled off for 30 seconds going in and out of the
defrost mode when the compressor delay jumper is
removed.
Units with defrost control 100269−04: The compressor
will be cycled off for 30 seconds going in and out of the
defrost mode when the compressor delay jumper is
installed.
NOTE The 30-second compressor feature is ignored
when jumpering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps to
protect the compressor from short-cycling in case the
power to the unit is interrupted or a pressure switch opens.
The delay is bypassed by placing the timer select jumper
across the TEST pins for 0.5 seconds.
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or
jumpered. If the jumper is in the TEST position at
power-up, the defrost control will ignore the test pins.
When the jumper is placed across the TEST pins for two
seconds, the defrost control will enter the defrost mode. If
the jumper is removed before an additional 5−second
period has elapsed (7 seconds total), the unit will remain in
defrost mode until the defrost thermostat opens or 14
minutes have passed. If the jumper is not removed until
after the additional 5−second period has elapsed, the
defrost will terminate and the test option will not function
again until the jumper is removed and re−applied.
Defrost Control Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition.
Table 6. Defrost Control (CMC1) Diagnostic LEDs
ModeGreen LED (DS2)Red LED (DS1)
No power to control
Normal operation /
power to control
Anti-short cycle
lockout
High pressure
switch fault
High pressure
switch lockout
OFFOFF
Simultaneous Slow FLASH
Alternating Slow FLASH
Slow FLASHOFF
ONOFF
Page 29
XP13 SERIES
Maintenance
DEALER
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:
Outdoor Unit
1. Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned
off before you clean the coil.
2. Outdoor fan motor is prelubricated and sealed. No
further lubrication is needed.
3. Visually inspect connecting lines and coils for
evidence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at the unit (with the unit
operating).
6. Check amp−draw outdoor fan motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
NOTE − If owner reports insufficient cooling, the unit should
be gauged and refrigerant charge checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more
frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)
Outdoor Coil The outdoor coil may be flushed with
a water hose.
Outdoor Coil (Sea Coast) Moist air in ocean
locations can carry salt, which is corrosive to most
metal. Units that are located near the ocean require
frequent inspections and maintenance. These
inspections will determine the necessary need to wash
the unit including the outdoor coil. Consult your
installing contractor for proper intervals/procedures
for your geographic area or service contract.
INDOOR UNIT
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
3. Check blower drive belt for wear and proper tension.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
INDOOR COIL
1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.
NOTE
any time the unit is in operation.
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit. The
following maintenance may be performed by the
homeowner.
The filter and all access panels must be in place
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure of the
unit to treated water (i.e., sprinkler systems, soakers,
waste water, etc.) will corrode the surface of steel and
aluminum parts and diminish performance and longevity
of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its
proper operation.
Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
Make sure no obstructions restrict airflow to the
outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more
energy.
Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the
unit.
Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air Filter Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either
at the indoor unit (installed internal or external to the
cabinet) or behind a return air grille in the wall or
ceiling. Check the filter monthly and clean or replace
it as needed.
2. Disposable Filter Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.
3. Reusable Filter Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
NOTE The filter and all access panels must be in place
any time the unit is in operation.
4. Indoor Unit The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
506728−01
Page 30
Thermostat Operation
See the thermostat homeowner manual for instructions on
how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45F (7C). The heat pump control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
EMERGENCY HEAT setting to obtain temporary heat
without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is locked
out. After a six-hour compressor crankcase warm-up
period, the thermostat can be switched to the HEAT setting
and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before
calling for service:
Verify room thermostat settings are correct.
Verify that all electrical disconnect switches are ON.
Check for any blown fuses or tripped circuit breakers.
Verify unit access panels are in place.
Verify air filter is clean.
If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update−to−date information, see any of the following
publications:
Lennox XP13 Engineering Handbook
Lennox Product Catalog
Lennox Price Book
Page 31
XP13 SERIES
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Vapor Pressure;
Refrigerant Lines:Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Calibrated?
THERMOSTAT
Properly Set? Level?
Heating Correct?Cooling Correct?
506728−01
Page 32
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.