XC25 units have refrigerant piping requirements that are unique to
this unit. Size and install the refrigerant piping per table 2 (page 14)
to ensure proper unit operation.
IMPORTANT:
Before applying any power (main, solar or low voltage) to the
outdoor unit, confirm the iComfort Wi-Fi® thermostat has
software Version 2.1 or higher installed. (Reference the iComfort
Wi-Fi® thermostat manual.)
This unit is an integral component of a system that requires an
iComfort Wi-Fi
or furnace.
®
thermostat and iComfort™-enabled air handler
®
Collection XC25 Series Units
TABLE OF CONTENTS
I. OVERVIEW
Model Number Identification2....................
Typical Serial Number Identification2..............
Specifications2.................................
Electrical Data3................................
Unit Dimensions4..............................
Typical Unit Parts Arrangement5.................
Operating Service Valves7.......................
General 7.....................................
II. INSTALLATION
Unit Placement9...............................
Removing and Installing Panels12.................
New or Replacement Line Set13..................
Brazing Connections16...........................
Flushing the System19...........................
Leak Testing the System21.......................
Evacuating the System21.........................
Electrical24.....................................
Servicing Unit Delivered Void of Charge29..........
Unit Start-Up29.................................
XC25
®
XC25
iComfort Wi-Fi
iComfort™-enabled
air handler or
furnace
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or damage to
property. Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
WARNING
Electrical Hazard
High Voltage
Wait 5 Minutes
Electrical components may hold charge. Do
not remove this panel or service this area for
5 minutes after the power has been removed.
III. SYSTEM OPERATION AND SERVICE
7-Segment Alert and System Status Codes30.......
Outdoor Control Push-Button Operation35..........
Configuring Unit39...............................
Reconfiguring Outdoor Control using iComfort Wi-Fi
Thermostat40...................................
System Overview40.............................
Maintenance41..................................
SunSource
Unit Wiring Diagrams42..........................
Factory Wiring Diagrams45.......................
Unit Sequence of Operations47...................
Component Testing50............................
System Refrigerant69............................
®
Home Energy System41..............
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
1
2013 Lennox Industries Inc.
®
Model Number identification
I. OVERVIEW
−−
C 25XXX
X
230
-02
Refrigerant Type
X = R-410A
Unit Type
C = AIR CONDITIONER
Nominal Cooling Capacity
Minor Revision Number
Voltage
230 = 208/230V-1ph-60hz
024 = 2 tons
Series
036 = 3 tons
048 = 4 tons
060 = 5 tons
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008
09 = 2009
10 = 2010
8 09C
5
05716
5 (or 6) Digit Unique Number
Month Code
A = January
B = February
C = March
Specifications
UnitOutdoor Fan
Model Number
XC25-024-230-01705913 lbs, 10 oz526
Sound Rating Number (dB)
MaximumMinimum
1
Factory Refrigerant
Charge
2
Number of BladesDiameter - inches.
UnitOutdoor Fan
Model Number
XC25-036-230-01735910 lbs, 12 oz526
Model Number
XC25-048-230-01746614 lbs, 9 oz526
Model Number
XC25-060-230-01746414 lbs, 8 oz526
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Factory refrigerant charge is sufficient for refrigerant line lengths up to 15 feet.
Sound Rating Number (dB)
MaximumMinimum
Sound Rating Number (dB)
MaximumMinimum
Sound Rating Number (dB)
MaximumMinimum
1
UnitOutdoor Fan
1
UnitOutdoor Fan
1
Factory Refrigerant
Factory Refrigerant
Factory Refrigerant
Charge
Charge
Charge
2
2
2
Number of BladesDiameter - inches.
Number of BladesDiameter - inches.
Number of BladesDiameter - inches.
XC25
2
Electrical Data
208/230V-60 Hz-1 Ph
UnitCompressorOutdoor Fan (RPM varies with compressor RPM)
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
Full
Full
Full
Full
XC25
3
Unit Dimensions -- Inches (mm)
UNIT SUPPORT
FEET
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox Product Specification bulletin.
Coils previously charged with HCFC-22 must be
flushed.
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working nearby these areas during installation or while
servicing this equipment.
16-7/8
(429)
8-3/4
(222)
3-1/8
(79)
30-3/4
(781)
26-7/8
(683)
3-3/4 (95)
4-5/8
(117)
BASE WITH ELONGATED LEGS
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be grounded in accordance with national and local
codes.
Line voltage is present at all components when unit is not
in operation on units with single‐pole contactors.
Disconnect all remote electric power supplies before
opening access panel. Unit may have multiple power
supplies.
XC25
4
Typical Unit Parts Arrangement
GROUND LUGS
CONTROL PANEL FOR
XC25-024 AND -036
CONTACTOR-SPST
(25FLA/35RES)
INVERTER REACTOR,
GROUND LUGS
230V, 4KW
OUTDOOR
CONTROL
CONTROL PANEL FOR
XC25-048 AND -060
DC INVERTER
CONTROL
INVERTER NOISE FILTER FOR
6KW INVERTER (208/240V,
60HZ, CURRENT RANGE 30A
MAXIMUM, INDUCTANCE
4.3MH)
CONTACTOR-SPST
(35FLA/40RES)
OUTDOOR CONTROL
Figure 1. Control Panel Components
5
INVERTER REACTOR,
230V, 6KW
DC INVERTER
CONTROL
XC25
VAPOR VALVE
AND GAUGE
PORT
LIQUID VALVE AND
GAUGE PORT
COMPRESSOR TOP CAP
SWITCH (THERMAL)
Typical Plumbing Components
VARIABLE-CAPACITY
COMPRESSOR - HFC-410A,
3-PHASE
LIQUID LINE SENSOR
LIQUID LINE BI-FLOW
FILTER DRIER
(HFC-410A)
LOW PRESSURE SWITCH - NORMALLY OPEN, SWITCH CLOSES
WHEN SYSTEM PRESSURES GO ABOVE 90±5, AND OPENS
WHEN SYSTEM PRESSURES DROP BELOW 40±5 PSIG
Figure 2. Plumbing (Component Locations and Specifications)
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox Product Specification bulletin.
Coils previously charged with HCFC-22 must be
flushed.
CRANKCASE HEATER THERMOSTAT
(S40) OPENS AT 70ºF, CLOSES AT 50ºF
HIGH PRESSURE SWITCH - NORMALLY CLOSED. SWITCH OPENS
WHEN SYSTEM PRESSURES REACH 590±
SYSTEM PRESSURES DROP BELOW 418±15 PSIG
15, AND CLOSES WHEN
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working nearby these areas during installation or while
servicing this equipment.
XC25
6
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
The XC25 is a high-efficiency residential split-system air
conditioner, which features a variable-capacity scroll com
pressor and uses HFC-410A refrigerant. Units are
available in 2, 3, 4 and 5-ton sizes. The series is designed
for use with an expansion valve (approved for use with
HFC-410A) in the indoor unit only.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys
tems must be capable of handling higher system operating
pressures. The gauges should be rated for use with pres
sures of 0 - 800 psig on the high side and a low side of 30”
vacuum to 250 psig, with dampened speed to 500 psi.
Gauge hoses must be rated for use at or up to 800 psig of
pressure with a 4000 psig burst rating.
Table 1. Torque Requirements
PartsRecommended Torque
Service valve cap8 ft.- lb.11 NM
Sheet metal screws16 in.- lb.2 NM
Machine screws #1028 in.- lb.3 NM
Compressor bolts90 in.- lb.10 NM
Gauge port seal cap8 ft.- lb.11 NM
TORQUE REQUIREMENTS
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 lists
torque values for fasteners.
Operating Service Valves
The liquid and vapor line service valves are used for re
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a fac
tory-installed valve stem. Figure 3 provides information on
how to access and operating both angle and ball service
valves.
IMPORTANT
Only use hex wrenches of sufficient hardness (50Rc Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs for
small valves, to 25 ft-lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using a
hex wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes #C-08-1
for further details and information.
WARNING
The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death. It
may also cause cancer, birth defects, or reproductive
harm.
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
XC25
7
SERVICE VALVES
ANGLE AND BALL
Operating Angle–Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
STEM CAP
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is
open to line set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
rotate stem counterclockwise 90°. To close, rotate stem
clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN
CLOSED)
VALV E
STEM
STEM CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
When service valve is CLOSED, the service port is open
to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from contamination and
serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
DWith torque wrench: Finger tighten and
torque cap per table 1.
DWithout torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
10
9
8
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
DWith Torque Wrench: Finger tighten and then
torque cap per table 1.
DWithout Torque Wrench: Finger tighten and
use an appropriately sized wrench to turn an
additional 1/12 turn clockwise.
10
9
8
11
11
7
7
12
6
12
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
4
5
3
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball-Type Service Valves
XC25
8
II. INSTALLATION
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift
ing heavy objects.
See Unit Dimensions on page 4 for sizing mounting slab,
platforms or supports. Refer to figure 4 for mandatory
installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
DSome localities are adopting sound ordinances based
on the unit sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
DWhen possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans
mission. For proper placement of unit in relation to a
window see figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 5, de
tail B.
NOTE - If necessary for stability, anchor unit to slab as de
scribed in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated
in figure 5, detail C.
If additional elevation is necessary, raise the unit by ex
tending the height of the unit support feet. Use a 2-inch
(50.8mm) Schedule 40 female threaded adapter to raise
the height of the unit.
The specified coupling will fit snugly into the recessed por
tion of the feet. Use additional 2-inch (50.8mm) Schedule
40 male threaded adaptors which can be threaded into the
female threaded adaptors to make additional adjustments
to the level of the unit.
NOTE - Keep the height of extenders short enough to en
sure a sturdy installation. If it is necessary to extend the
height further than what is stable, consider a different type
of field-fabricated framework that is sturdy enough for
greater heights.
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
6 (152)
12 (305)
36 (914)
ACCESS PANEL
CONTROL PANEL
ACCESS
LOCATION
30 (762)
LINE SET
CONNECTIONS
NOTES:
DCLEARANCE TO ONE OF THE THREE
SIDES MUST BE 36 INCHES (914MM).
DCLEARANCE TO ONE OF THE
REMAINING TWO SIDES MAY BE 12
INCHES (305MM) AND THE FINAL
SIDE MAY BE 6 INCHES (152MM).
NOTE - Dimensions are not to scale.
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
ACCESS PANEL
LINE SET
CONNECTIONS
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
REAR VIEW OF UNIT
Figure 4. Installation Clearances
XC25
9
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field-provided):
Always use stabilizers when unit is raised above the
factory height. (Elevated units could become unstable in
gusty wind conditions.)
Stabilizers may be used on factory height units when
mounted on unstable an uneven surface.
1. Remove the louvered panel from each side to expose
the unit base.
2. Install the brackets as illustrated in figure 5, detail D us
ing conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Locate the unit above a load-bearing wall or area of the roof
that can adequately support the unit. Consult local codes
for rooftop applications.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the
rubber to swell when it comes into contact with oil. The
rubber will then bubble and could cause leaks. Protect
the roof surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow this
notice could result in damage to roof surface.
XC25
10
DETAIL ADETAIL B
INSTALL UNIT AWAY FROM WINDOWS
TWO 90° ELBOWS INSTALLED IN LINE SET
REDUCES LINE SET VIBRATION.
Outside Unit Placement
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE
TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5
M]) AWAY FROM BUILDING STRUCTURE.
GROUND LEVEL
Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING
SLAB
DETAIL C
BASE
LEG DETAIL
2” (50.8MM) SCH 40
FEMALE THREADED
USE ADDITIONAL 2” SCH 40 MALE THREADED ADAPT
ERS WHICH CAN BE THREADED INTO THE FEMALE
THREADED ADAPTERS TO MAKE ADDITIONAL AD
JUSTMENTS TO THE LEVEL OF THE UNIT.
Elevated Slab Mounting using Feet
ADAPTER
2” (50.8MM) SCH 40
MALE THREADED
ADAPTER
Extenders
DETAIL D
Slab Side Mounting
#10 1/2” LONG SELF-DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL — 2” WIDTH; HEIGHT AS
#10 1-1/4” LONG HEX HEAD
SCREW AND FLAT WASHER
CONCRETE SLAB — USE TWO PLASTIC
ANCHORS (HOLE DRILL 1/4”)
WOOD OR PLASTIC SLAB — NO PLASTIC ANCHOR
(HOLE DRILL 1/8”)
REQUIRED)
CORNER POST
MINIMUM ONE
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL
— 2” (50.8MM) WIDTH; HEIGHT AS
REQUIRED); BEND TO FORM RIGHT ANGLE
SAME FASTENERS AS
SLAB SIDE MOUNTING.
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO
BRACKETS PER SIDE, 2” (50.8MM) FROM EACH CORNER.
PER SIDE
FOR EXTRA
STABILITY
Stabilizing Unit on Uneven Surfaces
IMPORTANT - To help stabilize an outdoor unit, some installations may require strap
ping the unit to the pad using brackets and anchors commonly available in the
marketplace.
COIL
BASE PAN
Figure 5. Placement and Slab Mounting
XC25
11
Removing and Installing Panels
ACCESS PANEL REMOVAL
PANELS
ACCESS AND LOUVERED
REMOVE AND INSTALL THE ACCESS PANEL
AS ILLUSTRATED.
WARNING
To prevent personal injury, or damage to panels, unit or structure, be
sure to observe the following:
While installing or servicing this unit, carefully stow all removed
panels out of the way, so that the panels will not cause injury to
personnel, nor cause damage to objects or structures nearby, nor will
the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather
conditions, especially windy conditions, that may cause panels to be
blown around and battered.
IMPORTANT - Do not allow panels to hang on unit by top tab. Tab
is for alignment and not designed to support weight of panel.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR
REMOVING (OR INSTALLING) PANEL.
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. REMOVE TWO SCREWS, ALLOWING THE PANEL TO SWING OPEN SLIGHTLY.
2. HOLD THE PANEL FIRMLY THROUGHOUT THIS PROCEDURE ROTATE BOTTOM
CORNER OF PANEL AWAY FROM HINGED CORNER POST UNTIL LOWER THREE TABS
CLEAR THE SLOTS AS ILLUSTRATED IN DETAIL B.
3. MOVE PANEL DOWN UNTIL LIP OF UPPER TAB CLEARS THE TOP SLOT IN CORNER
POST AS ILLUSTRATED IN DETAIL A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side
as close to the unit as possible. Then, in a continuous motion:
1. SLIGHTLY ROTATE AND GUIDE THE LIP OF TOP TAB INWARD AS ILLUSTRATED IN DETAILA AND C; THEN UPWARD INTO THE TOP SLOT OF THE HINGE CORNER POST.
2. ROTATE PANEL TO VERTICAL TO FULLY ENGAGE ALL TABS.
3. HOLDING THE PANEL'S HINGED SIDE FIRMLY IN PLACE, CLOSE THE RIGHT-HAND SIDE
OF THE PANEL, ALIGNING THE SCREW HOLES.
4. WHEN PANEL IS CORRECTLY POSITIONED AND ALIGNED, INSERT THE SCREWS AND
TIGHTEN.
LIP
SCREW
HOLES
Detail B
Detail A
REMOVE 4 SCREWS TO
REMOVE PANEL FOR
ACCESSING COMPRESSOR
AND CONTROLS.
ALIGN PANEL WITH SCREW
HOLES. INSTALL SCREWS
AND TIGHTEN.
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL
WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
Figure 6. Removing and Installing Panels
XC25
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
Detail D
12
ROTATE IN THIS DIRECTION; THEN
DOWN TO REMOVE PANEL
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY-ENGAGED TABS
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replace
ment of existing line set. If new or replacement line set is
not being installed then proceed to Brazing Connections on
page 16.
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC-22 to
HFC-410A If that is not possible and the line set is the
proper size as referenced in table 2, use the procedure
outlined under Flushing the System on page 19.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building.
Pay close attention to line set isolation during installation of
any HVAC system. When properly isolated from building
structures (walls, ceilings, floors), the refrigerant lines will
not create unnecessary vibration and subsequent sounds.
See figure 7 for recommended installation practices. Also,
consider the following when placing and installing a high-
efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
of proper size may be reused. If system was previously
charged with HCFC-22 refrigerant, then existing line set
must be flushed (see Flushing the System on page 19).
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil
must be added, it must be a Polyol ester oil.
IMPORTANT !
If this unit is being matched with an approved line set
or indoor unit coil that was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation.
Take care to empty all existing traps. Polyol ester
(POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act as
an insulator, preventing proper heat transfer. It can
also clog the expansion device and reduce system
performance and capacity.
Failure to properly flush the system per the XC25
Installation and Service Procedures will void the
warranty.
WARNING
Refrigerant can be harmful if it is inhaled.
Refrigerant must be used and recovered
responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
Fire, Explosion and Personal Safety
Hazard. Failure to follow this warning
could result in damage, personal inju
ry or death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an ex
plosion, that could result in property
damage, personal injury or death.
WARNING
When using a high pressure gas such
as nitrogen to pressurize a
refrigeration or air conditioning
system, use a regulator that can
control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
Recommended POE oils are Mobil EAL ARCTIC 22 CC or
ICI EMKARATEt RL32CF.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may
result in the low side shell and suction
tubing being pressurized. Application
of a brazing torch while pressurized
may result in ignition of the refrigerant
and oil mixture - check the high and
low pressures before unbrazing.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COMPRES
SOR.
The XC25 is a variable-capacity cooling system utilizing
variable-speed compressor technology. With the variablespeed compressor and variable pumping capacity,
additional consideration must be given to refrigerant piping
sizing and application. The following guidelines are to be
used exclusively for the XC25 systems.
XC25
13
COOLING SYSTEM (HFC410A)
DTotal equivalent length equals 180 feet (all piping and
fittings included).
NOTE - This is a general guide. Lengths may be more or
less, depending on remaining system design factors.
DMaximum linear (actual) length = 150 feet.
DMaximum linear liquid lift = 60 feet.
NOTE - Maximum lifts are dependent on total length, num
ber of elbows, and other factors that contribute to total
pressure drop.
DMaximum linear length of vapor riser = 60 feet.
DSize vertical vapor riser per table 3.
DLine set lengths up to 50 linear feet: Use rated line
sizes listed in table 2.
DLine set lengths between 51 and 150 linear feet:
Crankcase heater and nonbleed port TXV factory-in
stalled. No additional components required. Vertical
vapor riser must be sized to the vapor riser listed in
table 3 on systems with line sets longer than 51 feet.
Use tables 3 and 4 to determine the correct liquid and
vapor line sizes.
DLine set lengths over 150 linear feet: Not recom
mended.
DAdditional oil is not required for systems with line
lengths up to 150 feet.
NOTE - Recommended POE oils are Mobil EAL ARCTIC
22 CC or ICI EMKARATEt RL32CF.
SUCTION TRAPS
In systems with the outdoor unit 5 to 60 feet above the in
door unit, one trap must be installed at the bottom of the
suction riser.
Table 2. Standard Refrigerant Line Set — Up to 50 Linear Feet
Inches (mm)
Model Number (-xx*)Valve Size ConnectionsRecommended Line Sets
Note Shaded rows indicate rated liquid line size.
1. Find your unit on the left side of the table.
2. Start with the rated liquid line size (shaded row) for the outdoor unit.
3. Select the actual total linear length of your system shown at the top of the table.
4. The elevation listed in the table is the maximum allowed for the liquid line listed.
5. Consider the larger liquid line size shown in the table if the elevation does not meet your requirements.
Max. Elevation
(ft)
XC25
14
LINE SET
INSTALLATION
LINE SET ISOLATION — THE FOLLOWING ILLUSTRATIONS ARE EXAM
PLES OF PROPER REFRIGERANT LINE SET ISOLATION:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
AUTOMOTIVE
MUFFLER‐TYPE HANGER
IMPORTANT - Refrigerant lines must not contact structure.
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE - INSULATE LIQUID LINE WHEN IT IS ROUTED THROUGH AREAS
WHERE THE SURROUNDING AMBIENT TEMPERATURE COULD BECOME
HIGHER THAN THE TEMPERATURE OF THE LIQUID LINE OR WHEN
PRESSURE DROP IS EQUAL TO OR GREATER THAN 20 PSIG.
IMPORTANT - Refrigerant lines must not contact
wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL
STUD
STRAP LIQUID LINE TO
VAPOR LINE
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED
IN ARMAFLEX
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL
STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
WIRE TIE (AROUND
VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON-CORROSIVE
METAL SLEEVE
STRAP THE VAPOR LINE TO THE
JOIST OR RAFTER AT 8 FEET (2.43
METERS) INTERVALS THEN STRAP
THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR
WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN
STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
NOTE - SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF
LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
CAULK
STRAP
NON-CORROSIVE
METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID
LINE
FLOOR JOIST OR
ROOF RAFTER
WARNING - Polyol ester (POE) oils used with
HFC-410A refrigerant absorb moisture very quickly.
It is very important that the refrigerant system be kept
closed as much as possible. DO NOT remove line set
caps or service valve stub caps until you are ready to
make connections.
Figure 7. Line Set Installation
XC25
15
Brazing Connections
Use the procedures outlined in figures 8 and 9 for brazing
line set connections to service valves.
WARNING
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil mixture
- Check the high and low pressures
before applying heat.
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could re
sult in damage, personal injury or death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen, when
exposed to a spark or open flame, can
cause a fire and/or an explosion, that
could result in property damage, per
sonal injury or death.
XC25
16
PIPING PANEL REMOVAL AND LINE SET
PREPARATION
1
Remove piping panel for easier access to service valves. Cut ends
of the refrigerant lines square (free from nicks or dents) and debur
the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
STUB
CONNECTION
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction and liquid line
2
service ports.
SERVICE PORT CAP
SERVICE PORT
CORE
LIQUID LINE SERVICE VALVE
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING
LIQUID AND SUCTION LINE SERVICE VALVES
3
A.Connect gauge set low pressure side to liquid line
service valve (service port).
B.Connect gauge set center port to bottle of nitrogen
with regulator.
C.With valve core removed from the suction line service
port, nitrogen flow will have an exit point.
SUCTION SERVICE PORT MUST BE OPEN AND
SERVICE PORT CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN FLOW
SUCTION LINE
INDOOR
UNIT
C
SUCTION LINE
SERVICE VALVE
SUCTION LINE SERVICE
VALV E
LOW
ATTACH
GAUGES
B
OUTDOOR
UNIT
HIGH
SERVICE PORT
CORE
SERVICE
PORT CAP
LIQUID LINE
LIQUID LINE SERVICE
VALV E
A
Figure 8. Brazing Procedures
17
NITROGEN
XC25
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube
stubs. Use additional water-saturated cloths underneath the valve body to protect the base paint.
4
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the
5
refrigeration gauge set into the valve stem port connection
on the liquid service valve and out of the suction / vapor
valve stem port. See steps 3A, 3B and 3C on previous page
and below for manifold gauge setup.
BRAZE LINE SET
Cloths must remain water-saturated throughout the
6
brazing and cool-down process.
A.Braze liquid line to liquid line service valve.
B.Braze suction / vapor line to suction / vapor
service valve.
IMPORTANT !
Use silver alloy brazing rods with 5%
minimum silver alloy for copper-to-copper
brazing and 45% alloy for copper-to-brass
or copper-to-steel brazing.
6B
1. FIRE, PERSONAL INJURY, OR PROPERTY
DAMAGE will result if you do not wrap a water-
saturated cloth around both liquid and suction line
service valve bodies and copper tube stub while
brazing in the line set! The braze, when complete,
must be quenched with water to absorb any
residual heat.
2. Do not open service valves until refrigerant lines
and indoor coil have been leak-tested and
evacuated. Refer to procedures provided in this
supplement.
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WARNING
SUCTION / VAPOR LINE
WATER-SATURATED CLOTHS
SUCTION / VAPOR SERVICE PORT
MUST BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW EXIT
POINT FOR NITROGEN FLOW
IMPORTANT !
Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed
joints. Do not remove water-saturated cloths
until piping has cooled. Temperatures above
250ºF will damage valve seals.
6A
LIQUID LINE
WATER-SATURATED
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated
7
cloths to both services valves to cool piping. Once piping is cool, remove all water-saturated cloths. Refer to the unit installation
instructions for the next step in preparing the unit.
A.ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
B.REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS
C.DISCONNECT THE EQUALIZER LINE FROM THE CHECK EXPANSION
D.REMOVE THE VAPOR LINE SENSING BULB.
E.DISCONNECT THE LIQUID LINE FROM THE CHECK EXPANSION VALVE
F.DISCONNECT THE CHECK EXPANSION VALVE FROM THE LIQUID LINE
G.REMOVE AND DISCARD CHECK EXPANSION VALVE AND THE TWO TEF
H.USE A FIELD-PROVIDED FITTING TO TEMPORARILY RECONNECT THE
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
PANELS.
TRIBUTOR ASSEMBLY.
VALVE EQUALIZER LINE FITTING ON THE VAPOR LINE.
AT THE LIQUID LINE ASSEMBLY.
ORIFICE HOUSING. TAKE CARE NOT TO TWIST OR DAMAGE DISTRIBU
TOR TUBES DURING THIS PROCESS.
®
RINGS.
LON
LIQUID LINE TO THE INDOOR UNIT'S LIQUID LINE ORIFICE HOUSING.
LIQUID LINE
SENSING BULB
ORIFICE
HOUSING
EQUALIZER
LINE
STUB END
TEFLON
RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
SENSING
FLUSHING LINE SET
3
CAUTION -This procedure should not be performed on systems
which contain contaminants (Example, compressor burn out).
THE LINE SET AND INDOOR UNIT COIL MUST BE FLUSHED WITH AT
LEAST THE SAME AMOUNT OF CLEAN REFRIGERANT THAT PRE
VIOUSLY CHARGED THE SYSTEM. CHECK THE CHARGE IN THE
B
FLUSHING CYLINDER BEFORE PROCEEDING.
A.SET THE RECOVERY MACHINE FOR LIQUID RECOVERY AND
START THE RECOVERY MACHINE. OPEN THE GAUGE SET
VALVES TO ALLOW THE RECOVERY MACHINE TO PULL A VACU
UM ON THE EXISTING SYSTEM LINE SET AND INDOOR UNIT COIL.
B.INVERT THE CYLINDER OF CLEAN HCFC-22 AND OPEN ITS VALVE
TO ALLOW LIQUID REFRIGERANT TO FLOW INTO THE SYSTEM
THROUGH THE VAPOR LINE VALVE. ALLOW THE REFRIGERANT
TO PASS FROM THE CYLINDER AND THROUGH THE LINE SET
AND THE INDOOR UNIT COIL BEFORE IT ENTERS THE RECOVERY
MACHINE.
C.AFTER ALL OF THE LIQUID REFRIGERANT HAS BEEN RECOV
ERED, SWITCH THE RECOVERY MACHINE TO VAPOR RECOVERY
SO THAT ALL OF THE HCFC-22 VAPOR IS RECOVERED. ALLOW
THE RECOVERY MACHINE TO PULL SYSTEM DOWN TO 0.
D.CLOSE THE VALVE ON THE INVERTED HCFC-22 DRUM AND THE
GAUGE SET VALVES. PUMP THE REMAINING REFRIGERANT OUT
OF THE RECOVERY MACHINE AND TURN OFF THE MACHINE.
®
LINE
LIQUID
LINE
XC25
19
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
TYPICAL NEW CHECK EXPANSION VALVE INSTALLATION PROCEDURE
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE LENNOX XC25
PRODUCT SPECIFICATIONS FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.
4
THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
THAT WILL PROVIDE ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.
®
TEFLON
RING
A.REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR AS
SENSING
LINE
LIQUID LINE
SEMBLY.
B.INSTALL ONE OF THE PROVIDED TEFLON
STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE
THE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON
RING WITH REFRIGERANT OIL.
C.ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATELY
SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS IL
LUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.
D.PLACE THE REMAINING TEFLON
OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON
FRIGERANT OIL.
E.ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.
9 O'CLOCK TO
3 O'CLOCK
BULB
12
®
BULB
9
WASHER AROUND THE OTHER END
12
11
10
8
7
6
®
RINGS AROUND THE
®
ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9
AND 3 O'CLOCK
POSITIONS.
SENSING BULB INSTALLATION
VAPOR LINE
A.ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.
NOTE - CONFIRM PROPER THERMAL CONTACT BETWEEN
VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU
LATING THE SENSING BULB ONCE INSTALLED.
B.CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE VAPOR LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS
TRATED BELOW.
9
10
11
12
1
8
7
5
6
1/8 TURN
2
3
4
VAPOR LINE
BULB
FLARE SEAL CAP
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
12
BULB
NOTE - NEVER MOUNT THE SENSING BULB ON
BOTTOM OF LINE.
THE SENSING BULB ON
BOTTOM OF LINE.
FLARE NUT
1/2 TURN
1
2
3
4
5
®
RING WITH RE
EQUALIZER LINE INSTALLATION
REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.
XC25
20
OR
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
INSTALLING ISOLATION GROMMETS
Locate the isolation grommets (provided). Slide grommets
onto vapor and liquid lines. Insert grommets into piping
panel to isolate refrigerant lines from sheet metal edges.
SUCTION LINE
LIQUID LINE
TWO ISOLATION GROMMETS ARE
PROVIDED FOR THE LIQUID AND
SUCTION LINE PIPE PANEL PASS
THROUGH.
REAR VIEW OF UNIT EXTERIOR
PIPING PANEL
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which was
manufactured before January of 1999, the coil and line
set must be flushed prior to installation. Take care to
empty all existing traps. Polyol ester (POE) oils are
used in Lennox units charged with HFC-410A
refrigerant. Residual mineral oil can act as an insulator,
preventing proper heat transfer. It can also clog the
expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the instructions
below will void the warranty.
Leak Testing the System
IMPORTANT
Figure 10. Isolation Grommets
IMPORTANT
The Environmental Protection Agency (EPA) prohibits
the intentional venting of HFC refrigerants during
maintenance, service, repair and disposal of appliance.
Approved methods of recovery, recycling or reclaiming
must be followed.
Leak detector must be capable of sensing HFC
refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
XC25
21
LEAK TEST
LINE SET AND INDOOR COIL
NOTE - NORMALLY, THE HIGH PRESSURE HOSE IS CONNECTED TO THE LIQUID LINE
PORT. HOWEVER, CONNECTING IT TO THE VAPOR PORT BETTER PROTECTS THE
MANIFOLD GAUGE SET FROM HIGH PRESSURE DAMAGE.
LOW
HIGH
CONNECT GAUGE SET
A.CONNECT AN HFC-410A MANIFOLD GAUGE SET HIGH PRESSURE
1
2
HOSE TO THE VAPOR VALVE SERVICE PORT.
B.WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER
OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET.
NOTE - LATER IN THE PROCEDURE,
THE HFC-410A CONTAINER WILL BE
REPLACED BY THE NITROGEN
CONTAINER.
NITROGEN
TEST FOR LEAKS
AFTER THE LINE SET HAS BEEN CONNECTED TO THE INDOOR AND OUTDOOR UNITS, CHECK THE LINE SET CON
NECTIONS AND INDOOR UNIT FOR LEAKS. USE THE FOLLOWING PROCEDURE TO TEST FOR LEAKS:
A.WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET. OPEN THE VALVE ON THE HFC-410A CYLINDER (VAPOR ONLY).
B.OPEN THE HIGH PRESSURE SIDE OF THE MANIFOLD TO ALLOW HFC-410A INTO THE LINE SET AND INDOOR UNIT. WEIGH IN A TRACE
AMOUNT OF HFC-410A [A TRACE AMOUNT IS A MAXIMUM OF TWO OUNCES (57 G) REFRIGERANT OR THREE POUNDS (31 KPA) PRESSURE]. CLOSE THE VALVE ON THE HFC-410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE
SET. DISCONNECT THE HFC-410A CYLINDER.
C.CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD
GAUGE SET.
D.ADJUST DRY NITROGEN PRESSURE TO 150 PSIG (1034 KPA). OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN
ORDER TO PRESSURIZE THE LINE SET AND THE INDOOR UNIT.
E.AFTER A FEW MINUTES, OPEN ONE OF THE SERVICE VALVE PORTS AND VERIFY THAT THE REFRIGERANT ADDED TO THE SYSTEM
EARLIER IS MEASURABLE WITH A LEAK DETECTOR.
F.AFTER LEAK TESTING, DISCONNECT GAUGES FROM SERVICE PORTS.
HFC-410A
B
MANIFOLD GAUGE SET
TO VAPOR
SERVICE VALVE
OUTDOOR UNIT
A
XC25
Figure 11. System Leak Test
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.