Lennox XC21 Series Unit Information

Page 1
2010 Lennox Industries Inc.
Revised October 12, 2010
XC21
Service Literature
Corp. 1007−L2
XC21 (HFC−410A) SERIES UNITS
THIS SERVICE MANUAL IS APPLICABLE TO BUILD
XC21−XXX−230−04 OR LATER.
NOTICE
A thermostat is not included and must be ordered separately.
D The Lennox icomfort Touch thermostat must be used
in communicating applications.
D In non−communicating applications, the Lennox
ComfortSense
®
7000 thermostat may be used, as well
as other non−communicating thermostats.
In all cases, setup is critical to ensure proper system operation.
Field wiring examples for non−communicating applications begin on page 24.
See the icomfort Toucht thermostat Quick Start Guide for communicating and partial communicating field wiring connections.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
Accessories
For update−to−date information, see any of the following publications:
S Lennox XC21 Engineering Handbook S Lennox Product Catalog S Lennox Price Book
TABLE OF CONTENTS
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Typical Serial Number Identification 2. . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 6. . . . . . . . .
Unit Placement 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 11. . . . . . . . . . . . . . . . .
New or Replacement Line Set 12. . . . . . . . . . . . . . . . . .
Brazing Connections 14. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing the System 17. . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing the System 19. . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 21. . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Control Wiring 24. . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Conditioner Control (A175) Jumpers
and Terminals 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 27. . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating and Temperature Pressures 31. . . . . . . . . .
System Operations 32. . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Status, Fault and Lockout LED Codes 36. . . .
Component Field Configuration and
Troubleshooting 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SunSource
®
Home Energy System 50. . . . . . . . . . . . . .
Checklists 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Wiring Diagrams 52. . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Sequence of Operations 54. . . . . . . . . . . . . . . . . . .
The XC21 is a high efficiency residential split−system air conditioner unit, which features a one−stage scroll compressor, icomfortt control and HFC−410A refrigerant. Units are available in 2, 3, 4 and 5−ton sizes. This model series is designed for use with an expansion valve metering device only. Refer to the XC17 Engineering Handbook for ordering the correct indoor coil expansion valve.
This model is also SunSourcet ready beginning with XC21−XXX−230−05 build.
This document provides information only on build XC21−XXX−230−04 and later which features the new air conditioner control hardware and other enhancements. Refer to Corp. 0504−L2 for earlier model version service related information.
Page 2
XC21
Model Number Identification
C 21
XXX
Unit Type
C = Air Conditioner
Series
Nominal Cooling Capacity
024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons
Minor Revision Number
230
Voltage
230 = 208/230V−1ph−60hz
Refrigerant Type
X = R−410A
X
04
Typical Serial Number Identification
8 09 C
Year Code
08 = 2008 09 = 2009 10 = 2010
Month Code
A = January B = February C = March
05716
5 (or 6) Digit Unique
Number
Location Code
19 = Saltillo, Mexico 20 = Gainesville, FL
56 = Stuttgart, AR
58 = Marshalltown, IA
5
Specifications
Model Number
Unit Outdoor Fan
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter − inches.
XC21−024−230−04 69 12 lbs. 0 oz. 3 26.0
XC21−024−230−05 69 11 lbs. 12 oz. 5 26.1
XC21−024−230−06 69 11 lbs. 12 oz. 5 26.1
XC21−036−230−04 71 12 lbs. 5 oz. 3 26.0
XC21−036−230−05 71 12 lbs. 5 oz. 5 26.1
XC21−036−230−06 71 12 lbs. 5 oz. 5 26.1
XC21−048−230−04 73 13 lbs. 0 oz. 3 26.1
XC21−048−230−05 73 13 lbs. 0 oz. 5 26.1
XC21−048−230−06 73 13 lbs. 0 oz. 5 26.1
XC21−060−230−04 73 13 lbs. 0 oz. 3 26.0
XC21−060−230−05 73 13 lbs. 0 oz. 5 26.1
XC21−060−230−06 73 13 lbs. 0 oz. 5 26.1
1
Tested according to AHRI Standard 270−2008 test conditions.
2
Refrigerant charge sufficient for 15 feet length of refrigerant lines.
Page 3
XC21
Electrical Data
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps
(LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−024−230−04 25 15.7 10.3 52.0 1/3 700 820 2.8
XC21−024−230−05 30 18.9 13.5 58.3 1/4 475 550 2.0
XC21−024−230−06 30 18.9 13.5 58.3 1/4 475 550 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−036−230−04 40 23.7 16.7 82.0 1/3 700 820 2.8
XC21−036−230−05 35 22.9 16.7 82.0 1/4 475 550 2.0
XC21−036−230−06 35 22.9 16.7 82.0 1/4 475 550 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−048−230−04 50 29.3 21.2 96.0 1/3 700 820 2.8
XC21−048−230−05 45 28.5 21.2 96.0 1/4 600 675 2.0
XC21−048−230−06 45 28.5 21.2 96.0 1/4 600 675 2.0
208/230V−60 Hz−1 Ph
Model Number
Unit Compressor Condenser Fan
Maximum
Over−
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM 1−Stage
Nominal
RPM 2−Stage
Full Load
Amps (FLA)
XC21−060−230−04 60 34.9 25.7 118.0 1/3 700 820 2.8
XC21−060−230−05 50 25.7 25.7 118.0 1/4 600 675 2.0
XC21−060−230−06 50 25.7 25.7 118.0 1/4 600 675 2.0
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 4
XC21
Unit Dimensions − Inches (mm) and Parts Arrangement
39−1/2 (1003)
35−1/2
(902)
47
(1194)
18−1/2
(470)
8 (203)
1 (25)
4−1/2 (114)
LIQUID LINE INLET
ELECTRICAL
INLETS
SIDE VIEW
ACCESS VIEW
DISCHARGE AIR
4−5/8 (117)
BASE WITH ELONGATED LEGS
16−7/8
(429)
8−3/4 (222)
26−7/8
(683)
3−3/4 (95)
30−3/4
(781)
3−1/8
(79)
SUCTION LINE INLET
UNIT SUPPORT FEET
Page 5
XC21
Typical Unit Parts Arrangement
LIQUID LINE FILTER
DRIER (SINGLE FLOW)
LIQUID LINE SER-
VICE VALVE PORT
SUCTION LINE SERVICE
VALVE PORT
FIELD CONNECTION FOR
SUCTION LINE
HIGH DISCHARGE LINE
TEMPERATURE SENSOR (RT28)
LOW PRESSURE SWITCH
(S87)
HIGH PRESSURE SWITCH (S4)
CRANKCASE THERMOSTAT (S40)
COMPRESSOR HARNESS
FIELD CONNECTION FOR
LIQUID LINE
GROUND LUG
HIGH VOLTAGE FIELD
CONNECTIONS
CONTACTOR−1 POLE (K1)
MAIN CONTROL
(A175)
CAPACITOR (C12)
FAN MOTOR CONTROL (A177)
(BUILD −05 AND LATER)
WIRE TIE
OUTDOOR AMBIENT
TEMPERATURE SENSOR (RT13)
FAN MOTOR SURGE PROTECTION (BUILD
−05 ONLY) LATER VERSIONS HAVE SURGE PROTECTION BUILT INTO FAN MOTOR.
SECOND GROUND LUG FOR SOURCESOURCE
®
(BUILD −05 AND LATER)
Figure 1. Plumbing, Switches and Sensor Components
Page 6
XC21
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working nearby these areas during installation or while servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem.
Figure 2 provides information
on how to access and operating both angle and ball service valves.
Page 7
XC21
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT CORE
SERVICE PORT CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
TO OUTDOOR UNIT
STEM CAP
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
TO INDOOR
UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
BALL (SHOWN CLOSED)
SERVICE PORT
CORE
TO INDOOR UNIT
TO OUTDOOR
UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CAP
STEM CAP
VALV E STEM
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.
1
2
3
4
5
6
7
8
9
10
11
12
1/12 TURN
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
S With torque wrench: Finger tighten and
torque cap per table 1.
S Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
1
2
3
4
5
6
7
8
9
10
11
12
1/6 TURN
WHEN SERVICE VALV E IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
torque cap per table 1.
S Without Torque Wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 8
XC21
CONTROL PANEL
ACCESS
LOCATION
6 (152)
36 (914)
12 (305)
30 (762)
LINE SET CONNECTIONS
24 (610)
LINE SET
CONNECTIONS
ACCESS PANEL
REAR VIEW OF UNIT
48 (1219)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
Figure 3. Installation Clearances
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to Figure 3 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 4, Detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in Figure 4, Detail B.
NOTE  If necessary for stability, anchor unit to slab as described in Figure 4, Detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in Figure 4, Detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
Page 9
XC21
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
With unit positioned at installation site, perform the following
:
1. Remove two side louvered panels to expose the unit base.
2. Install the brackets as illustrated in Figure 4, Detail D using conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some rubber roofing material may absorbed oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
MOUNTING SLAB
BUILDING
STRUCTURE
GROUND LEVEL
Outside Unit Placement
Slab Mounting at Ground Level
INSTALL UNIT AWAY FROM WINDOWS
DETAIL A
DETAIL B
Figure 4. Placement, Slab Mounting and Stabilizing Unit
Page 10
XC21
LEG DETAIL
BASE
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO BRACKETS PER SIDE, 2" (50.8MM) FROM EACH CORNER.
CONCRETE SLAB  USE TWO PLASTIC ANCHORS (HOLE DRILL 1/4")
COIL
BASE PAN
CORNER POST
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
REQUIRED)
Slab Side Mounting
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
#10 1−1/4" LONG HEX HD SCREW
AND FLAT WASHER
MINIMUM ONE
PER SIDE
FOR EXTRA
STABILITY
Elevated Slab Mounting using Feet
Extenders
Stabilizing Unit on Uneven Surfaces
WOOD OR PLASTIC SLAB  NO PLASTIC ANCHOR
(HOLE DRILL 1/8")
SAME FASTENERS AS SLAB SIDE MOUNTING.
IMPORTANT  To help stabilize an outdoor unit, some installations may re­quire strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
DETAIL C
DETAIL D
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the lev­el of the unit.
STABILIZING BRACKET (18 GAUGE METAL  2" (50.8MM) WIDTH; HEIGHT AS REQUIRED); BEND TO FORM RIGHT ANGLE
Deck Top Mounting
Figure 5. Placement, Slab Mounting and Stabilizing Unit
Page 11
XC21
Removing and Installing Panels
REMOVE 4 SCREWS TO REMOVE PANEL FOR ACCESSING COMPRESSOR AND CONTROLS.
POSITION PANEL WITH HOLES ALIGNED; INSTALL SCREWS AND TIGHTEN.
ACCESS PANEL REMOVAL
Removal and reinstallation of the access panel is as illustrated.
Detail A
Detail C
Detail B
ROTATE IN THIS DIRECTION; THEN
DOWN TO REMOVE PANEL
SCREW
HOLES
LIP
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
PREFERRED ANGLE FOR INSTALLATION
Detail D
ANGLE MAY BE TOO EXTREME
HOLD DOOR FIRMLY
ALONG THE HINGED SIDE
TO MAINTAIN FULLY−EN-
GAGED TABS
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel
away from hinged corner post until lower three tabs clear the slots as illustrated in Detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illus-
trated in Detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in Detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as illustrated in Detail A and C;
then upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
PANELS
ACCESS AND LOUVERED
IMPORTANT  Do not allow panels to hang on unit by top tab. Tab is for align-
ment and not designed to support weight of panel.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
To prevent personal injury, or damage to panels, unit or structure, be sure to ob­serve the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., be­ing bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
WARNING
Figure 6. Removing and Installing Panels
Page 12
XC21
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 14.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See Figure 7 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page 17).
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections).
Table 2. Refrigerant Line Set Requirements
Models Liquid
Line
Vapor/ Suction Line
L15 Line Set
−024, −036 and−048
3/8 (10mm)
7/8 (22mm)
L15 line set sizes are dependent on unit match up. See indoor unit Engineering Handbook to determine correct line set sizes.
−060 3/8 (10mm)
1−1/8 (29mm)
Field Fabricated
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter.
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to communicate the following information:
S Model (XC21) and size of unit (e.g. −036).
S Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S Number of elbows vertical rise or drop in the piping.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must
be added, it must be a Polyol ester oil.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Page 13
XC21
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
WALL STUD
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED IN ARMAFLEX
AUTOMOTIVE
MUFFLER-TYPE HANGER
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
Line Set Isolation  The following illustrations are
examples of proper refrigerant line set isolation:
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
WIRE TIE (AROUND VAPOR LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR WIRE TIE
To hang line set from joist or rafter, use either metal strapping materi­al or anchored heavy nylon wire ties.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
OUTSIDE
WALL
VAPOR LINE WRAPPED
WITH ARMAFLEX
LIQUID LINE
OUTSIDE WALL
LIQUID LINE
VAPOR LINE
WOOD BLOCK
BETWEEN STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
INSTALLATION
LINE SET
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NON−CORROSIVE METAL SLEEVE
IMPORTANT  Refrigerant lines must not contact structure.
NON−CORROSIVE METAL SLEEVE
8 FEET (2.43 METERS)
IMPORTANT  Refrigerant lines must not contact wall
WARNING Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 7. Line Set Installation
Page 14
XC21
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture
− Check the high and low pressures before applying heat.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
Page 15
XC21
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION LINE SERVICE VALVES
OUTDOOR
UNIT
LIQUID LINE
SUCTION LINE
LIQUID LINE SERVICE
VALV E
SUCTION LINE
SERVICE VALVE
ATTACH
GAUGES
INDOOR
UNIT
SUCTION SERVICE PORT MUST BE OPEN AND
SERVICE PORT CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN FLOW
A Connect gauge set low pressure side to liquid line
service valve (service port).
B Connect gauge set center port to bottle of nitrogen
with regulator.
C With valve core removed from the suction line service
port, nitrogen flow will have an exit point.
NITROGEN
HIGH
LOW
B
A
C
PIPING PANEL REMOVAL AND PREPARING LINE SET
CAP AND CORE REMOVAL
Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
Remove service cap and core from both the suction and liquid line service ports.
1
2
LIQUID LINE SERVICE VALVE
SERVICE PORT CORE
SERVICE PORT CAP
SERVICE PORT CORE
SERVICE PORT CAP
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
COPPER TUBE
STUB
SERVICE VALVE CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
REDUCER
3
SUCTION LINE SERVICE
VALV E
LINE SET SIZE IS SMALLER
THAN CONNECTION
Figure 8. Brazing Procedures
Page 16
XC21
BRAZE LINE SET
Water saturated cloths must remain water saturated throughout the brazing and cool−down process.
6
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step in preparing the unit.
PREPARATION FOR NEXT STEP
7
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use additional water saturated cloths underneath the valve body to protect the base paint.
4
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A,
3B and 3C on previous page and below for manifold gauge setup.
5
SUCTION / VAPOR LINE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a water
saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement.
LIQUID LINE
WATER SATURATED
CLOTHS
WATER SATURATED CLOTHS
A Braze liquid line to liquid line service valve.
B Braze suction / vapor line to suction / vapor service
valve.
6A
6B
SUCTION / VAPOR SERVICE PORT
MUST BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW EXIT
POINT FOR NITROGEN FLOW
IMPORTANT  Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed joints. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
Figure 9. Brazing Procedures (Continued)
Page 17
XC21
Flushing the System
SENSING
LINE
TEFLON RING
FIXED ORIFICE
(Uncased Coil Shown)
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR TUBES
DISTRIBUTOR
ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON SEAL (IF
PRESENT)
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
D Remove and discard fixed orifice, valve stem assembly if present
and Teflon washer as illustrated above.
E Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
TYPICAL CHECK EXPANSION VALVE
REMOVAL PROCEDURE
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
VAPOR
LINE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR
TUBES
LIQUID
LINE
MALE EQUALIZER
LINE FITTING
EQUALIZER LINE
CHECK
EXPANSION
VALV E
TEFLON RING
(Uncased Coil Shown)
STUB END
TEFLON
RING
SENSING BULB
LIQUID LINE
ORIFICE
HOUSING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
G Remove and discard check expansion valve and the two Teflon rings. H Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
LOW
HIGH
EXISTING
INDOOR
UNIT
GAUGE
MANIFOLD
INV ERTED HCFC−22 CYLINDER CONTAINS CLE AN HCFC−22 TO BE USED FOR FLUSHING.
LIQUID LINE SERVICE
VALV E
INLET
DISCHARGE
TANK RETURN
CLOSED
OPENED
RECOVERY
CYLINDER
RECOVERY MACHINE
NEW
OUTDOOR
UNIT
VAPOR LINE
SERVICE VALVE
VAPOR
LIQUID
1
A Inverted HCFC−22 cylinder with clean refrigerant to the vapor
service valve.
B HCFC−22 gauge set (low side) to the liquid line valve. C HCFC−22 gauge set center port to inlet on the recovery machine
with an empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine
instructions.
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
A
B
C
D
B
OR
FLUSHING LINE SET
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the re­covery machine to pull a vacuum on the existing system line set and indoor unit coil.
B Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the sys­tem. Check the charge in the flushing cylinder before proceeding.
LINE SET AND INDOOR COIL (1 OF 2)
FLUSHING
1
2
3
CAUTION This procedure should not be performed on sys-
tems which contain contaminants (Example compressor burn out.
Page 18
XC21
A Attach the vapor line sensing bulb in the proper orientation
as illustrated to the right using the clamp and screws pro­vided.
NOTE  Confirm proper thermal contact between vapor line and check expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the
check expansion valve to the equalizer vapor port on the vapor line. Finger tight­en the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
The check expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check expansion valve in a manner that will provide access for field servicing of the check expansion valve. Refer to below illustration for reference during installation of check expansion valve unit.
TYPICAL CHECK EXPANSION VALVE INSTALLATION PROCEDURE
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
VAPOR
LINE
LIQUID LINE
ORIFICE
HOUSING
DISTRIBUTOR
TUBES
LIQUID LINE
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING
LINE
EQUALIZER LINE
CHECK
EXPANSION
VALV E
TEFLON RING
(Uncased Coil Shown)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SENSING BULB INSTALLATION FOR BULB POSITIONING.
STUB
END
TEFLON
RING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
DISTRIBUTOR
ASSEMBLY
This outdoor unit is designed for use in systems that use check expansion valve metering device. See the Lennox XC21 Engineering Hand- book for approved check expansion valve kit match−ups and application information.
A Remove the field−provided fitting that temporary reconnected the liq-
uid line to the indoor unit’s distributor assembly.
B Install one of the provided Teflon rings around the stubbed end of the
check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
C Attach the stubbed end of the check expansion valve to the liquid line
orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.
D Place the remaining Teflon washer around the other end of the check
expansion valve. Lightly lubricate connector threads and expose sur­face of the Teflon ring with refrigerant oil.
E Attach the liquid line assembly to the check expansion valve. Finger
tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
12
BULB
VAPOR LINE
VAPOR LINE
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
BULB
BULB
BULB
VAPOR LINE
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
FLARE SEAL CAP
OR
1
2
3
4
5
6
7
8
9
10
11
12
1/2 TURN
SENSING BULB INSTALLATION
EQUALIZER LINE INSTALLATION
1
2
3
4
5
6
7
8
9
10
11
12
1/8 TURN
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
4
A Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
B Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
Loading...
+ 40 hidden pages