Lennox XC21 User Manual

INSTALLATION
E2012 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
General
This XC21 outdoor unit is designed for use with HFC−410A refrigerant only. This unit must be installed with an ap­proved indoor unit. See the Lennox XC21 Product Specifi­cations bulletin (EHB) for approved indoor component match ups.
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
INSTRUCTIONS
Dave Lennox Signature Collection XC21 System
AIR CONDITIONERS 506923−01 7/2012
Supersedes 4/2012
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or service agency.
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at discon­nect switch.
NOTICE !
For more in−depth information, consult the Installa­tion and Service Procedures manual, available as Corp.1007−L2 on DaveNet or through the Technical Support department at 800−453−6669.
®
Litho U.S.A.
STEP 1 −− SETTING THE UNIT −− Clearances
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
6 (152)
CONTROL
PANEL ACCESS
LOCATION
24
(610)
30 (762)
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN TWO UNITS
NOTES:
S Clearance to access panel must be 30
inches (762mm).
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining two
sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
ACCESS PANEL
LINE SET
CONNECTIONS
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
REAR VIEW OF UNIT
FIGURE 1
7/2012 506923−01
Page 1
*2P72012* *P506923-01*
UNIT DIMENSIONS − INCHES (MM)
39−1/2 (1003)
DISCHARGE AIR
SUCTIOn LINE INLET
LIQUID LINE INLET
ELECTRICAL
INLETS
47
(1194)
18−1/2
(470)
35−1/2
(902)
4−1/2 (114)
8 (203)
SIDE VIEW
UNIT SUPPORT FEET
16−7/8
(429)
8−3/4 (222)
3−1/8
(79)
BASE WITH ELONGATED LEGS
STEP 1 −− SETTING THE UNIT (Continued)
−− Unit Placement
WARNING
To prevent personal injury, as well as damage to panels, unit or structure, observe the following:
While installing or servicing this unit, carefully stow all removed panels so that the panels will not cause injury to personnel, objects or nearby structures. Also, take care to store panels where they will not be subject to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions (especially wind) that may cause panels to be blown around and damaged.
30−3/4
(781)
1 (25)
26−7/8
(683)
3−3/4 (95)
4−5/8 (117)
ACCESS VIEW
NOTICE !
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the rubber to degrade. Failure to follow this notice could result in damage to roof surface.
IMPORTANT !
Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit performance and longevity.
Page 2
PLACEMENT
INSTALL UNIT AWAY
FROM WINDOWS
STABILIZING UNIT ON UNEVEN SURFACES
#10 X 1/2" LONG
SELF−DRILLING
SHEET METAL
SCREWS
COIL
TWO 90_ ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
BUILDING
STRUCTURE
DISCHARGE AIR
MOUNTING SLAB
GROUND LEVEL
FIGURE 3
ELEVATED SLAB MOUNTING USING FEET
EXTENDERS
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2" (50.8MM) SCH 40 MALE THREADED ADAPTER
LEG DETAIL
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
BASE
STABILIZING BRACKET
(18 GAUGE METAL  2"
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1−1/4" LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab  use two plastic anchors (hole drill 1/4")
!
IMPORTANT !
CORNER POST
BASE PAN
Unit Stabilizer Bracket Use
(field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions.)
Stabilizers may be used on any unit installed on unstable and uneven surfaces.
FIGURE 5
STEP 2 −− REFRIGERANT PIPING −− Flush­ing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc-
tions. For more information, refer to the Installation and Service Procedures manual available on Dave­Net. CAUTION − DO NOT attempt to flush and re−use ex- isting line sets or indoor coil when the system con­tains contaminants (i.e., compressor burn out).
NOTE − When installing refrigerant lines longer than 50 feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual available on DaveNet (Corp. 9351−L9), or contact the Technical Support Department Product Ap­plication group for assistance.
NOTE − For new or replacement line set installation, refer to Service and Application Note − Corp. 9112−L4 (C−91−4).
TABLE 1
REFRIGERANT LINE SET  INCHES (MM)
Models Liquid
Line
−024, −036 and−048
3/8 (10) 7/8 (22) L15 line set sizes are
Vapor/ Suction Line
L15 Line Set
dependent on unit match up. See XP21 Engineering Handbook to determine correct line set sizes.
FIGURE 4
−060 3/8 (10) 1−1/8 (29) Field Fabricated
NOTE  Some applications may required a field−provided 7/8" to 1−1/8" adapter.
Page 3
XC21 SERIES
IMPORTANT !
If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installa­tion. Take care to empty all existing traps. Polyol es­ter (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device and reduce sys­tem performance and capacity.
Failure to properly flush the system per this instruc­tion and the detailed Installation and Service Proce­dures manual will void the warranty.
WARNING
When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Fire, Explosion and Personal Safety Haz­ard. Failure to follow this warning could re­sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an explosion, that could result in property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT !
Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pres­sure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COM­PRESSOR.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment.
Page 4
STEP 2 −− REFRIGERANT PIPING −− Removing Existing Indoor Metering Device
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor as-
sembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro­cess.
4. Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above.
5. Use a field−provided fitting to temporarily reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
(UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE
OR
BRASS NUT
1B
TWO−PIECE PATCH PLATE
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
CYLINDER CONTAINING CLEAN HCFC−22 TO BE USED FOR FLUSHING (Positioned to deliver liquid
A
refrigerant)
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
VAPOR
LIQUID
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY MACHINE
1. HCFC−22 cylinder with clean refrigerant (positioned to deliver liquid
refrigerant) to the vapor service valve.
2. HCFC−22 gauge set (low side) to the liquid line valve.
3. HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.
4. Connect recovery tank to recovery machine per machine instructions.
GAUGE
MANIFOLD
LOW HIGH
CLOSED
TANK RETURN
INLET
DISCHARGE
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps from the liquid line and distributor
assembly.
3. Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
4. Remove the vapor line sensing bulb.
5. Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
6. Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard check expansion valve and the two Teflon® rings.
8. Use a field−provided fitting to temporarily reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
LIQUID LINE
SENSING BULB
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
1. Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
2. Position the cylinder of clean HCFC−22 for delivery of liquid refrigerant
3. After all of the liquid refrigerant has been recovered, switch the
4. Close the valve on the inverted HCFC−22 drum and the gauge set
B
and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull the system down to 0.
valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
LINE
LIQUID
LINE
FIGURE 6
Page 5
XC21 SERIES
STEP 2 −− REFRIGERANT PIPING −− Brazing Procedures
PIPING PANEL REMOVAL / PREPARING LINE SET
Remove piping panel to access service valves. Cut
1
ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
REFRIGERANT LINE
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction /
2
vapor and liquid line service ports.
SERVICE PORT CAP
SERVICE PORT CORE
LIQUID LINE SERVICE VALVE
SERVICE PORT CORE
SERVICE PORT CAP
SUCTION / VAPOR LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
A. Connect gauge set low pressure side to liquid line service valve (service port). B. Connect gauge set center port to bottle of nitrogen with regulator. C. With valve core removed from the suction / vapor line service port, nitrogen flow will have an exit point.
HIGHLOW
ATTACH
GAUGES
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN AND SERVICE PORT CORE REMOVED
TO ALLOW EXIT POINT FOR NITROGEN FLOW
SUCTION / VAPOR
LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
A
B
OUTDOOR
UNIT
NITROGEN
FIGURE 7
Page 6
Loading...
+ 13 hidden pages