Lennox XC20-036-230-01, XC20-060-230-01, XC20-024-230-01, XC20-048-230-01 Installation And Service Procedure

INSTALLATION AND SERVICE
PROCEDURE
Service Literature
Corp. 1407-L10
August 25, 2015
IMPORTANT
XC20 units have refrigerant piping requirements that are unique to this unit. Size and install the refrigerant piping per table 2 (page 14) to ensure proper unit operation.
IMPORTANT:
Before applying any power (main or low voltage) to the outdoor unit, confirm that the iComfort Wi-Fi® or iComfort® S30 thermostat has software Version 2.1 or higher installed. (Reference the iComfort Wi-Fi® or iComfort® S30 thermostat manual.)
This unit is an integral component of a system that requires an iComfort Wi-Fi iComfort
XC20
®
®
or iComfort® S30 thermostat and
-enabled air handler or furnace.
iComfort Wi-Fi
thermostat
iComfort
®
thermostat
S30
iComfort
air handler or
furnace
®
®
-enabled
XC20
®
XC20 Units
TABLE OF CONTENTS
I. OVERVIEW
Model Number Identification 2....................
Typical Serial Number Identification 2..............
Specifications 2.................................
Electrical Data 3................................
Unit Dimensions 4..............................
Typical Unit Parts Arrangement 5.................
Operating Service Valves 7.......................
General 7.....................................
II. INSTALLATION
Unit Placement 9...............................
Removing and Installing Panels 12.................
New or Replacement Line Set 13..................
Brazing Connections 16...........................
Flushing the System 19...........................
Leak Testing the System 21.......................
Evacuating the System 21.........................
Electrical 24.....................................
Servicing Unit Delivered Void of Charge 29..........
Unit Start-Up 29.................................
III. SYSTEM OPERATION AND SERVICE
7-Segment Alert and System Status Codes 30.......
Outdoor Control Push-Button Operation 38..........
Configuring Unit 42...............................
Reconfiguring Outdoor Control using iComfort Wi-Fi iComfort
System Overview 43.............................
Maintenance 44..................................
Unit Wiring Diagrams 45..........................
Factory Wiring Diagrams 48.......................
Unit Sequence of Operations 50...................
Component Testing 53............................
System Refrigerant 75............................
Appendix - Charging Sticker ....................
®
S30 Thermostat 43.....................
®
or
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
1
2015 Lennox Industries Inc.
Model Number Identification
I. OVERVIEW
Refrigerant Type
X = R-410A
Unit Type
C = AIR CONDITIONER
C 20 036
X
230
Nominal Cooling Capacity
A
-02
Minor Revision Number
Ratings Revision Level
Voltage
230 = 208/230V-1ph-60hz
024 = 2 tons
Series
036 = 3 tons 048 = 4 tons 060 = 5 tons
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008 09 = 2009 10 = 2010
8 09 C
5
05716
5 (or 6) Digit Unique Number
Month Code
A = January B = February C = March
Specifications
Unit Outdoor Fan
Model Number
XC20-024-230-01 72 65 7 lbs, 5 oz 4 22
Sound Rating Number (dB) Maximum Minimum
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
Unit Outdoor Fan
Model Number
XC20-036-230-01 75 67 8 lbs, 6 oz 4 22
Model Number
XC20-048-230-01 77 68 10 lbs, 7 oz 4 22
Model Number
XC20-060-230-01 77 69 12 lbs, 1 oz 3 26
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Factory refrigerant charge is sufficient for refrigerant line lengths up to 15 feet.
Sound Rating Number (dB) Maximum Minimum
Sound Rating Number (dB) Maximum Minimum
Sound Rating Number (dB) Maximum Minimum
1
Unit Outdoor Fan
1
Unit Outdoor Fan
1
Factory Refrigerant
Factory Refrigerant
Factory Refrigerant
Charge
Charge
Charge
2
2
2
Number of Blades Diameter - inches.
Number of Blades Diameter - inches.
Number of Blades Diameter - inches.
XC20
2
Electrical Data
208/230V-60 Hz-1 Ph
Unit Compressor Outdoor Fan (RPM varies with compressor RPM)
Model Number
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
XC20-024-230-01 30 19.1 13.0 13.0 1/6 2600 1500 700 400 60 25 2.8
Unit Compressor Outdoor Fan (RPM varies with compressor RPM)
Model Number
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
XC20-036-230-01 30 20.6 14.2 13.0 1/4 3600 3100 700 600 115 80 2.8
Unit Compressor Outdoor Fan (RPM varies with compressor RPM)
Model Number
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
XC20-048-230-01 50 29.1 21.0 20.0 1/3 4000 3000 800 600 160 70 2.8
Unit Compressor Outdoor Fan (RPM varies with compressor RPM)
Model Number
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
XC20-060-230-01 50 29.3 21.2 20.0 1/3 4325 2900 865 600 195 80 2.8
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor
HP
CFM RPM WATTS
MAX MIN MAX MIN MAX MIN
Load Amps (FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor
HP
CFM RPM WATTS
MAX MIN MAX MIN MAX MIN
Load Amps (FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor
HP
CFM RPM WATTS
MAX MIN MAX MIN MAX MIN
Load Amps (FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor
HP
CFM RPM WATTS
MAX MIN MAX MIN MAX MIN
Load Amps (FLA)
Full
Full
Full
Full
XC20
3
Unit Dimensions -- Inches (mm)
351/2 (902)
A
2 (51)
393/8 (1000)
DISCHARGE AIR
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
41/4(108)
43/4 (121)
SIDE VIEW
1 (25)
Model No.
XC20024 39 991
XC20036 39 991
XC20048 45 1143
XC20060 45 1143
END VIEW
in. mm
UNIT SUPPORT FEET
A
167/8
(429)
83/4 (222)
31/8
(79)
267/8
(683)
)33/4 (95
303/4 (781)
45/8 (117)
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Product Specification bulletin. Coils previously charged with HCFC-22 must be flushed.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and use protective clothing.
BASE WITH ELONGATED LEGS
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
WARNING
Electrical Hazard
High Voltage
Wait 5 Minutes
Electrical components may hold charge. Do not remove this panel or service this area for 5 minutes after the power has been removed.
XC20
4
Typical Unit Parts Arrangement
OUTDOOR
CONTROL
INVERTER REACTOR
CONTROL PANEL FOR
XC20-024 AND -036
DC INVERTER
CONTROL
GROUND LUG
CONTACTOR-SPST
OUTDOOR CONTROL
INVERTER REACTOR
CONTROL PANEL FOR
XC20-048 AND -060
DC INVERTER CONTROL
INVERTER NOISE FILTER
GROUND LUG
CONTACTOR-SPST
Figure 1. Control Panel Components
XC20
5
COMPRESSOR TOP CAP
SWITCH (THERMAL)
Typical Plumbing Components
COMPRESSOR
CRANKCASE HEATER THERMOSTAT (S40) OPENS AT 70ºF, CLOSES AT 50ºF
(ONE WAY - HFC-410A)
DRIER
LIQUID LINE SENSOR
SERVICE VALVE
Figure 2. Plumbing Component Locations
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Product Specification bulletin. Coils previously charged with HCFC-22 must be flushed.
LOW PRESSURE
SWITCH
HIGH PRESSURE
SERVICE VALVE
SWITCH
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and use protective clothing.
XC20
6
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
The XC20 is a high-efficiency residential split-system air conditioner, which features a variable-capacity scroll com pressor and uses HFC-410A refrigerant. Units are available in 2, 3, 4 and 5-ton sizes. The series is designed for use with an expansion valve (approved for use with HFC-410A) in the indoor unit only.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys tems must be capable of handling higher system operating pressures. The gauges should be rated for use with pres sures of 0 - 800 psig on the high side and a low side of 30” vacuum to 250 psig, with dampened speed to 500 psi. Gauge hoses must be rated for use at or up to 800 psig of pressure with a 4000 psig burst rating.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.- lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
TORQUE REQUIREMENTS
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
Operating Service Valves
The liquid and vapor line service valves are used for re moving refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a fac tory-installed valve stem. Figure 3 provides information on how to access and operating both angle and ball service valves.
IMPORTANT
Only use hex wrenches of sufficient hardness (50Rc ­Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using a hex wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Note #C-08-1 for further details and information.
WARNING
The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
XC20
7
SERVICE VALVES
ANGLE AND BALL
Operating Angle–Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
STEM CAP
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
When service valve is CLOSED, the service port is open to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
D With torque wrench: Finger tighten and
torque cap per table 1.
D Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
10
9
8
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
D With Torque Wrench: Finger tighten and then
torque cap per table 1.
D Without Torque Wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
10
9
8
11
11
7
7
12
6
12
6
1/6 TURN
1
2
4
5
1/12 TURN
1
4
5
3
2
3
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball-Type Service Valves
XC20
8
II. INSTALLATION
Unit Placement
CAUTION
This unit may weigh up to 320 lbs. It could take more than two people to lift this product. Take proper precautions when lifting heavy objects.
See Unit Dimensions on page 4 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
D Some localities are adopting sound ordinances based
on the unit sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
D When possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans mission. For proper placement of unit in relation to a window see figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, de tail B.
NOTE - If necessary for stability, anchor unit to slab as de scribed in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 5, detail C.
If additional elevation is necessary, raise the unit by ex tending the height of the unit support feet. Use a 2-inch (50.8mm) Schedule 40 female threaded adapter to raise the height of the unit.
The specified coupling will fit snugly into the recessed por tion of the feet. Use additional 2-inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE - Keep the height of extenders short enough to en sure a sturdy installation. If it is necessary to extend the height further than what is stable, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
NOTES:
Service clearance of 30 in. must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
Clearance to one of the remaining two sides may be 12 in. and the final side may be 6 in.
A clearance of 24 in. must be maintained between two units.
48 in. clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
Control
Box
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for
the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
Figure 4. Installation Clearances
XC20
9
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field-provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions.)
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
1. Remove the louvered panel from each side to expose the unit base.
2. Install the brackets as illustrated in figure 5, detail D us ing conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Locate the unit above a load-bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
XC20
10
DETAIL A DETAIL B
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
Install unit away from windows.
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
GROUND LEVEL
Slab Mounting at Ground Level
Outside Unit Placement
BUILDING
STRUCTURE
MOUNTING SLAB
DETAIL C
BASE
LEG DETAIL
2” (50.8MM) SCH 40
FEMALE THREADED
USE ADDITIONAL 2” SCH 40 MALE THREADED ADAPT ERS WHICH CAN BE THREADED INTO THE FEMALE THREADED ADAPTERS TO MAKE ADDITIONAL AD JUSTMENTS TO THE LEVEL OF THE UNIT.
Elevated Slab Mounting using Feet
ADAPTER
2” (50.8MM) SCH 40
MALE THREADED
ADAPTER
Extenders
DETAIL D
Slab Side Mounting
#10 1/2” LONG SELF-DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL — 2” WIDTH; HEIGHT AS
#10 1-1/4” LONG HEX HEAD
SCREW AND FLAT WASHER
CONCRETE SLAB — USE TWO PLASTIC ANCHORS (HOLE DRILL 1/4”)
WOOD OR PLASTIC SLAB — NO PLASTIC ANCHOR (HOLE DRILL 1/8”)
REQUIRED)
CORNER POST
MINIMUM ONE
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL — 2” (50.8MM) WIDTH; HEIGHT AS REQUIRED); BEND TO FORM RIGHT ANGLE
SAME FASTENERS AS SLAB SIDE MOUNTING.
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO BRACKETS PER SIDE, 2” (50.8MM) FROM EACH CORNER.
PER SIDE
FOR EXTRA
STABILITY
Stabilizing Unit on Uneven Surfaces
IMPORTANT - To help stabilize an outdoor unit, some installations may require strap
ping the unit to the pad using brackets and anchors commonly available in the marketplace.
COIL
BASE PAN
Figure 5. Placement and Slab Mounting
XC20
11
Removing and Installing Panels
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slight ly.
2. Hold the panel firmly throughout this procedure. Rotate bot tom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in Detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in Detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in Detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of the top tab inward as
illustrated in Detail A and C; then upward into the top slot of the hinge corner post.
2. Rotate the panel until it is completely vertical to fully en gage all of the tabs.
3. Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
IMPORTANT ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
SCREW
LIP
HOLES
Detail A
Detail B
ROTATE IN THIS DIRECTION;
ANGLE MAY BE TOO EXTREME
THEN DOWN TO REMOVE
SIDE TO MAINTAIN FULLY-ENGAGED TABS
PANEL
HOLD DOOR FIRMLY TO THE HINGED
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
Figure 6. Removing and Installing Panels
PREFERRED ANGLE FOR INSTALLATION
XC20
12
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replace
ment of existing line set. If new or replacement line set is
not being installed then proceed to Brazing Connections on
page 16.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC-22 to HFC-410A If that is not possible and the line set is the proper size as referenced in table 2, use the procedure outlined under Flushing the System on page 19.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building.
Pay close attention to line set isolation during installation of
any HVAC system. When properly isolated from building
structures (walls, ceilings, floors), the refrigerant lines will
not create unnecessary vibration and subsequent sounds.
See figure 7 for recommended installation practices. Also,
consider the following when placing and installing a high-
efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
of proper size may be reused. If system was previously
charged with HCFC-22 refrigerant, then existing line set
must be flushed (see Flushing the System on page 19).
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil
must be added, it must be a Polyol ester oil.
IMPORTANT !
If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device and reduce system performance and capacity.
Failure to properly flush the system per the XC20 Installation and Service Procedures will void the warranty.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal inju ry or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex plosion, that could result in property damage, personal injury or death.
WARNING
When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Recommended POE oils are Mobil EAL ARCTIC 22 CC or
ICI EMKARATEt RL32CF.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture - check the high and low pressures before unbrazing.
IMPORTANT !
Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pres sure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRES SOR.
The XC20 is a variable-capacity cooling system utilizing variable-speed compressor technology. With the variable­speed compressor and variable pumping capacity, additional consideration must be given to refrigerant piping sizing and application. The following guidelines are to be used exclusively for the XC20 systems.
XC20
13
COOLING SYSTEM (HFC410A)
D Total equivalent length equals 180 feet (all piping and
fittings included).
NOTE - This is a general guide. Lengths may be more or less, depending on remaining system design factors.
D Maximum linear (actual) length = 150 feet. D Maximum linear liquid lift = 60 feet.
NOTE - Maximum lifts are dependent on total length, num ber of elbows, and other factors that contribute to total pressure drop.
D Maximum linear length of vapor riser = 60 feet. D Size vertical vapor riser per table 2. D Line set lengths up to 50 linear feet: Use rated line
sizes listed in table 2.
D Line set lengths between 51 and 150 linear feet:
Crankcase heater and nonbleed port TXV factory-in
stalled. No additional components required. Vertical vapor riser must be sized to the vapor riser listed in table 3 on systems with line sets longer than 51 feet. Use tables 3 and 4 to determine the correct liquid and vapor line sizes.
D Line set lengths over 150 linear feet: Not recom
mended.
D Additional oil is not required for systems with line
lengths up to 150 feet.
NOTE - Recommended POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
SUCTION TRAPS
In systems with the outdoor unit 5 to 60 feet above the in door unit, one trap must be installed at the bottom of the suction riser.
Table 2. Standard Refrigerant Line Set — Up to 50 Linear Feet
Valve Size Connections Recommended Line Sets
Model Number (-xx*)
XC20-024-230-XX 3/8” (10 mm) 3/4” (19 mm) L15-41-30 30 feet (9.1 m) 89J60
XC20-036-230-XX XC20-048-230-XX
XC20-060-230-XX 3/8” (10 mm) 1-1/8” (29 mm) ** Field-fabricated
* Applicable to all minor revision numbers unless otherwise specified. ** Some applications may require a field-provided 1-1/8” to 7/8” adapter.
Liquid Line Suction Line
3/8” (10 mm) 7/8” (22 mm)
L15 Line Set Model
L15-65-40 40 feet (12.2 m) 89J61
L15-65-50 50 feet (15.2 m) 89J62
Line Set Length
Catalog Number
Table 3. XC20 Line Set Guidelines — 51 to 150 Linear Feet in Length
Model
024 180 150 60 60 3/4” 5/8”
036 180 150 60 60 7/8” 3/4”
048 180 150 60 60 7/8” 7/8”
060 180 150 60 60 7/8” 7/8”
Maximum Total
Equivalent Length (ft)
Maximum Linear
(actual) Length (ft)
Maximum Vapor
Riser (ft)
Maximum
Linear Liquid
Lift (ft)
Preferred Vapor Line
Sizes for Horizontal
Runs
Required Vapor
Riser Size
Table 4. Liquid Line Diameter Selection Table
Total Linear Length (feet)
Unit
024
036
048
060
Line Size
5/16” 25 50 55 48 40 33
3/8” 25 50 60 60 60 60
3/8” 25 50 60 56 51 45
1/2” 25 50 60 60 60 60
3/8” 25 50 50 41 31 22
1/2” 25 50 60 60 60 60
3/8” 25 50 36 22 8 NR
1/2”
25 50 75 100 125 150
25
50 60 60 60 59
Note  Shaded rows indicate rated liquid line size.
1. Find your unit on the left side of the table.
2. Start with the rated liquid line size (shaded row) for the outdoor unit.
3. Select the actual total linear length of your system shown at the top of the table.
4. The elevation listed in the table is the maximum allowed for the liquid line listed.
5. Consider the larger liquid line size shown in the table if the elevation does not meet your requirements.
Max. Elevation
(ft)
XC20
14
LINE SET
INSTALLATION
LINE SET ISOLATION — THE FOLLOWING ILLUSTRATIONS ARE EXAM
PLES OF PROPER REFRIGERANT LINE SET ISOLATION:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
AUTOMOTIVE
MUFFLER‐TYPE HANGER
IMPORTANT - Refrigerant lines must not contact structure.
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE - INSULATE LIQUID LINE WHEN IT IS ROUTED THROUGH AREAS WHERE THE SURROUNDING AMBIENT TEMPERATURE COULD BECOME HIGHER THAN THE TEMPERATURE OF THE LIQUID LINE OR WHEN PRESSURE DROP IS EQUAL TO OR GREATER THAN 20 PSIG.
IMPORTANT - Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL STUD
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON-CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN
STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
NOTE - SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
CAULK
STRAP
NON-CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID LINE
FLOOR JOIST OR
ROOF RAFTER
WARNING - Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 7. Line Set Installation
XC20
15
Brazing Connections
Use the procedures outlined in figures 8 and 9 for brazing line set connections to service valves.
WARNING
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture
- Check the high and low pressures before applying heat.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could re sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause a fire and/or an explosion, that could result in property damage, per sonal injury or death.
XC20
16
PIPING PANEL REMOVAL AND LINE SET PREPARATION
1
Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
STUB
CONNECTION
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction and liquid line
2
service ports.
SERVICE PORT CAP
SERVICE PORT CORE
LIQUID LINE SERVICE VALVE
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION LINE SERVICE VALVES
3
A. Connect gauge set low pressure side to liquid line
service valve (service port).
B. Connect gauge set center port to bottle of nitrogen
with regulator.
C. With valve core removed from the suction line service
port, nitrogen flow will have an exit point.
SUCTION SERVICE PORT MUST BE OPEN AND
SERVICE PORT CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN FLOW
SUCTION LINE
INDOOR
UNIT
C
SUCTION LINE
SERVICE VALVE
SUCTION LINE SERVICE
VALV E
LOW
ATTACH
GAUGES
B
OUTDOOR
UNIT
HIGH
SERVICE PORT CORE
SERVICE PORT CAP
LIQUID LINE
LIQUID LINE SERVICE
VALV E
A
Figure 8. Brazing Procedures
17
NITROGEN
XC20
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve
5
and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths
6
must remain water-saturated throughout the brazing and cool-down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT - Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed joint. Do not remove water-saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER-SATURATED CLOTH
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated. Refer to Installation and Service Procedures manual found on DAVENET.
SUCTION LINE
PREPARATION FOR NEXT STEP
Disconnect manifold gauge set from service ports after all connections have been brazed. Apply additional water-saturated cloths to both
7
service valves to cool piping. Once piping is cool, remove all water-saturated cloths.
SUCTION LINE SERVICE
VALV E
SERVICE VALVES, POINT FLAME
WATER-SATURATED CLOTH
WHEN BRAZING LINE SET TO
AWAY FROM SERVICE VALVE.
Figure 9. Brazing Procedures (Continued)
XC20
18
Flushing the System
LINE SET AND INDOOR COIL (1 OF 2)
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL
1B
TWO PIECE PATCH PLATE
TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL
1A
DISTRIBUTOR
ASSEMBLY
A. ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B. REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS
TRIBUTOR ASSEMBLY.
C. USING TWO WRENCHES, DISCONNECT LIQUID LINE FROM LIQUID LINE
ORIFICE HOUSING. TAKE CARE NOT TO TWIST OR DAMAGE DISTRIBU TOR TUBES DURING THIS PROCESS.
D. REMOVE AND DISCARD FIXED ORIFICE, VALVE STEM ASSEMBLY (IF
PRESENT) AND TEFLON
E. USE A FIELD-PROVIDED FITTING TO TEMPORARILY RECONNECT THE
LIQUID LINE TO THE INDOOR UNIT'S LIQUID LINE ORIFICE HOUSING.
SHOWN)
DISTRIBUTOR TUBES
REMOVE AND DISCARD
WHITE TEFLON
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
BRASS NUT
®
(IF PRESENT)
®
WASHER AS ILLUSTRATED ABOVE.
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INV ERT ED HCFC-22 CYLINDER CONTAINS CLE AN HCFC-22* TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
RECOVERY
CYLINDER
VALV E
VAPOR
LIQUID
NEW
OUTDOOR
UNIT
B
OPENED
C
D
A. INVERTED HCFC-22 CYLINDER WITH CLEAN REFRIGERANT* TO THE
VAPOR SERVICE VALVE.
B. HCFC-22 GAUGE SET (LOW SIDE) TO THE LIQUID LINE VALVE.
C. HCFC-22 GAUGE SET CENTER PORT TO INLET ON THE RECOVERY
MACHINE WITH AN EMPTY RECOVERY TANK TO THE GAUGE SET.
D. CONNECT RECOVERY TANK TO RECOVERY MACHINE PER MACHINE
INSTRUCTIONS.
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
RECOVERY MACHINE
MANIFOLD
LOW
TANK RETURN
INLET
DISCHARGE
GAUGE
CLOSED
(UNCASED COIL ONLY)
OR
HIGH
SHOWN)
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A. ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B. REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS
TRIBUTOR ASSEMBLY.
C. DISCONNECT THE EQUALIZER LINE FROM THE CHECK EXPANSION
VALVE EQUALIZER LINE FITTING ON THE VAPOR LINE.
D. REMOVE THE VAPOR LINE SENSING BULB.
E. DISCONNECT THE LIQUID LINE FROM THE CHECK EXPANSION VALVE
AT THE LIQUID LINE ASSEMBLY.
F. DISCONNECT THE CHECK EXPANSION VALVE FROM THE LIQUID LINE
ORIFICE HOUSING. DO NOT TO TWIST OR DAMAGE DISTRIBUTOR TUBES DURING THIS PROCESS.
G. REMOVE AND DISCARD CHECK EXPANSION VALVE AND THE TWO TEF
H. USE A FIELD-PROVIDED FITTING TO TEMPORARILY RECONNECT THE
®
RINGS.
LON
LIQUID LINE TO THE INDOOR UNIT'S LIQUID LINE ORIFICE HOUSING.
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
FLUSHING LINE SET
3
CAUTION -This procedure should not be performed on systems
which contain contaminants (Example, compressor burn out).
THE LINE SET AND INDOOR UNIT COIL MUST BE FLUSHED WITH AT LEAST THE SAME AMOUNT OF CLEAN REFRIGERANT* THAT PRE VIOUSLY CHARGED THE SYSTEM. CHECK THE CHARGE IN THE FLUSHING CYLINDER BEFORE PROCEEDING.
B
A. SET THE RECOVERY MACHINE FOR LIQUID RECOVERY AND
START THE RECOVERY MACHINE. OPEN THE GAUGE SET VALVES TO ALLOW THE RECOVERY MACHINE TO PULL A VACU UM ON THE EXISTING SYSTEM LINE SET AND INDOOR UNIT COIL.
B. INVERT THE CYLINDER OF CLEAN HCFC-22* AND OPEN ITS
VALVE TO ALLOW LIQUID REFRIGERANT TO FLOW INTO THE SYS TEM THROUGH THE VAPOR LINE VALVE. ALLOW THE REFRIGER ANT TO PASS FROM THE CYLINDER AND THROUGH THE LINE SET AND THE INDOOR UNIT COIL BEFORE IT ENTERS THE RECOVERY MACHINE.
C. AFTER ALL OF THE LIQUID REFRIGERANT HAS BEEN RECOV
ERED, SWITCH THE RECOVERY MACHINE TO VAPOR RECOVERY SO THAT ALL OF THE HCFC-22 VAPOR IS RECOVERED. ALLOW THE RECOVERY MACHINE TO PULL SYSTEM DOWN TO 0.
D. CLOSE THE VALVE ON THE INVERTED HCFC-22 DRUM AND THE
GAUGE SET VALVES. PUMP THE REMAINING REFRIGERANT OUT OF THE RECOVERY MACHINE AND TURN OFF THE MACHINE.
®
SENSING
LINE
LIQUID
LINE
XC20
19
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
TYPICAL NEW CHECK EXPANSION VALVE INSTALLATION PROCEDURE
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE LENNOX XC20 PRODUCT SPECIFICATIONS FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.
4
THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE SENSING BULB INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER THAT WILL PROVIDE ACCESS FOR FIELD SERVICING OF THE EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR REFERENCE DURING INSTALLATION OF EXPANSION VALVE UNIT.
®
TEFLON
RING
A. REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR AS
SENSING
LINE
LIQUID LINE
SEMBLY.
B. INSTALL ONE OF THE PROVIDED TEFLON
STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE THE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON RING WITH REFRIGERANT OIL.
C. ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS IL LUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.
D. PLACE THE REMAINING TEFLON
OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON FRIGERANT OIL.
E. ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE ABOVE OR 20 FT-LB.
9 O'CLOCK TO
3 O'CLOCK
BULB
12
®
BULB
9
WASHER AROUND THE OTHER END
12
11
10
8
7
6
®
RINGS AROUND THE
®
ON LINES SMALLER THAN 7/8”, MOUNT SENSING BULB BETWEEN THE 9 AND 3 O'CLOCK POSITIONS.
SENSING BULB INSTALLATION
VAPOR LINE
A. ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE CLAMP AND SCREWS PROVIDED.
NOTE - CONFIRM PROPER THERMAL CONTACT BETWEEN VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU LATING THE SENSING BULB ONCE INSTALLED.
B. CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO THE EQUALIZER VAPOR PORT ON THE VAPOR LINE. FINGER TIGHTEN THE FLARE NUT PLUS 1/8 TURN (7 FT-LBS) AS ILLUS TRATED BELOW.
9
10
11
12
1
8
7
5
6
1/8 TURN
2
3
4
VAPOR LINE
BULB
FLARE SEAL CAP
ON 7/8” AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O'CLOCK POSITION. NEVER MOUNT
12
BULB
NOTE - NEVER MOUNT THE SENSING BULB ON
BOTTOM OF LINE.
THE SENSING BULB ON BOTTOM OF LINE.
FLARE NUT
1/2 TURN
1
2
3
4
5
®
RING WITH RE
EQUALIZER LINE INSTALLATION
REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE TO THE RIGHT.
XC20
20
OR
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
IMPORTANT
Leak Testing the System
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
XC20
21
LEAK TEST
LINE SET AND INDOOR COIL
NOTE - NORMALLY, THE HIGH PRESSURE HOSE IS CONNECTED TO THE LIQUID LINE PORT. HOWEVER, CONNECTING IT TO THE VAPOR PORT BETTER PROTECTS THE MANIFOLD GAUGE SET FROM HIGH PRESSURE DAMAGE.
LOW
HIGH
CONNECT GAUGE SET
A. CONNECT AN HFC-410A MANIFOLD GAUGE SET HIGH PRESSURE
1
2
HOSE TO THE VAPOR VALVE SERVICE PORT.
B. WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER
OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE MANIFOLD GAUGE SET.
NOTE - LATER IN THE PROCEDURE, THE HFC-410A CONTAINER WILL BE REPLACED BY THE NITROGEN CONTAINER.
NITROGEN
TEST FOR LEAKS
AFTER THE LINE SET HAS BEEN CONNECTED TO THE INDOOR AND OUTDOOR UNITS, CHECK THE LINE SET CON NECTIONS AND INDOOR UNIT FOR LEAKS. USE THE FOLLOWING PROCEDURE TO TEST FOR LEAKS:
A. WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET. OPEN THE VALVE ON THE HFC-410A CYLINDER (VAPOR ONLY).
B. OPEN THE HIGH PRESSURE SIDE OF THE MANIFOLD TO ALLOW HFC-410A INTO THE LINE SET AND INDOOR UNIT. WEIGH IN A TRACE
AMOUNT OF HFC-410A [A TRACE AMOUNT IS A MAXIMUM OF TWO OUNCES (57 G) REFRIGERANT OR THREE POUNDS (31 KPA) PRES SURE]. CLOSE THE VALVE ON THE HFC-410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE SET. DISCONNECT THE HFC-410A CYLINDER.
C. CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD
GAUGE SET.
D. ADJUST DRY NITROGEN PRESSURE TO 150 PSIG (1034 KPA). OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN
ORDER TO PRESSURIZE THE LINE SET AND THE INDOOR UNIT.
E. AFTER A FEW MINUTES, OPEN ONE OF THE SERVICE VALVE PORTS AND VERIFY THAT THE REFRIGERANT ADDED TO THE SYSTEM
EARLIER IS MEASURABLE WITH A LEAK DETECTOR.
F. AFTER LEAK TESTING, DISCONNECT GAUGES FROM SERVICE PORTS.
HFC-410A
B
MANIFOLD GAUGE SET
TO VAPOR
SERVICE VALVE
OUTDOOR UNIT
A
XC20
Figure 10. System Leak Test
22
Evacuating the System
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
1
NOTE - REMOVE CORES FROM SERVICE VALVES (IF NOT ALREADY DONE).
A. CONNECT LOW SIDE OF MANIFOLD
GAUGE SET WITH 1/4 SAE IN-LINE TEE TO VAPOR LINE SERVICE VALVE.
B. CONNECT HIGH SIDE OF MANIFOLD
GAUGE SET TO LIQUID LINE SERVICE VALVE.
C. CONNECT MICRON GAUGE TO AN
AVAILABLE CONNECTOR ON THE 1/4 SAE IN-LINE TEE.
D. CONNECT THE VACUUM PUMP (WITH
VACUUM GAUGE) TO THE CENTER PORT OF THE MANIFOLD GAUGE SET. THE CENTER PORT LINE IS USED LATER FOR BOTH THE AND NITROGEN CONTAINERS.
OUTDOOR
UNIT
A
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
LOW
TO VAPOR
SERVICE VALVE
MANIFOLD
GAUGE SET
HIGH
HFC-410A
VACUUM PUMP
B
TO LIQUID LINE SERVICE VALVE
D
NITROGEN
EVACUATE THE SYSTEM
A. OPEN BOTH MANIFOLD VALVES AND START THE VACUUM PUMP.
2
B. EVACUATE THE LINE SET AND INDOOR UNIT TO AN ABSOLUTE PRESSURE OF 23,000 MICRONS (29.01 INCHES OF MERCURY).
NOTE - DURING THE EARLY STAGES OF EVACUATION, IT IS DESIRABLE TO CLOSE THE MANIFOLD GAUGE VALVE AT LEAST ONCE. A RAPID RISE IN PRESSURE INDICATES A RELATIVELY LARGE LEAK. IF THIS OCCURS, REPEAT THE LEAK TESTING PROCEDURE.
NOTE - THE TERM ABSOLUTE PRESSURE REFERS TO THE TOTAL ACTUAL PRESSURE (ABOVE ABSOLUTE ZERO) WITHIN A GIVEN VOLUME OR SYSTEM. ABSOLUTE PRESSURE IN A VACUUM IS EQUAL TO ATMOSPHERIC PRESSURE MINUS VACUUM PRESSURE.
C. WHEN THE ABSOLUTE PRESSURE REACHES 23,000 MICRONS (29.01 INCHES OF MERCURY), CLOSE THE MANIFOLD GAUGE VALVES, TURN
OFF THE VACUUM PUMP AND DISCONNECT THE MANIFOLD GAUGE CENTER PORT HOSE FROM VACUUM PUMP. ATTACH THE MANIFOLD CENTER PORT HOSE TO A DRY NITROGEN CYLINDER WITH PRESSURE REGULATOR SET TO 150 PSIG (1034 KPA) AND PURGE THE HOSE. OPEN THE MANIFOLD GAUGE VALVES TO BREAK THE VACUUM IN THE LINE SET AND INDOOR UNIT. CLOSE THE MANIFOLD GAUGE VALVES.
D. SHUT OFF THE DRY NITROGEN CYLINDER AND REMOVE THE MANIFOLD GAUGE HOSE FROM THE CYLINDER. OPEN THE MANIFOLD
GAUGE VALVES TO RELEASE THE DRY NITROGEN FROM THE LINE SET AND INDOOR UNIT.
E. RECONNECT THE MANIFOLD GAUGE TO THE VACUUM PUMP, TURN THE PUMP ON, AND CONTINUE TO EVACUATE THE LINE SET AND IN
DOOR UNIT UNTIL THE ABSOLUTE PRESSURE DOES NOT RISE ABOVE 500 MICRONS (29.9 INCHES OF MERCURY) WITHIN A 20-MINUTE PERIOD AFTER SHUTTING OFF THE VACUUM PUMP AND CLOSING THE MANIFOLD GAUGE VALVES.
F. WHEN THE ABSOLUTE PRESSURE REQUIREMENT ABOVE HAS BEEN MET, DISCONNECT THE MANIFOLD HOSE FROM THE VACUUM PUMP
AND CONNECT IT TO AN UPRIGHT CYLINDER OF HFC-410A REFRIGERANT. OPEN THE MANIFOLD GAUGE VALVE 1 TO 2 PSIG IN ORDER TO RELEASE THE VACUUM IN THE LINE SET AND INDOOR UNIT.
G. PERFORM THE FOLLOWING:
1. Close manifold gauge valves.
2
. Shut off HFC-410A cylinder. . Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
3
tool while maintaining a positive system pressure.
. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illus
4
trated.
RECOMMEND
MINIMUM 3/8” HOSE
11
10
9
8
7
12
6
1/6 TURN
1
2
3
4
5
Figure 11. Evacuating System
XC20
23
IMPORTANT
Load Shedding
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperat ures and pressures present during operation of an air conditioning system. Non-condensables combine with re frigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams. Refer to unit nameplate for minimum circuit ampacity and maximum over-current protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air hand ler for low‐voltage control power (24VAC - 40 VA minimum).
Utility Load Shedding Mode ACTIVATED (Utility Cycled Unit OFF) – The normally closed set of
contacts in the utility load shedding control receiver OPEN. This removes 24VAC from the coil of the field-provided re lay (catalog # 69J79). The relay contacts close (terminal 7 to terminal 2), completing the circuit between terminals R and L on the outdoor control. The 24VAC input to terminal L activates the load-shedding mode in the outdoor control, cycling the outdoor unit OFF. The 7-Segment display on the outdoor control displays a load shedding alert code (E600) and an alert appears on the display of the iComfort
®
thermostat. The customer receives email notifica
Wi-Fi tions when the alert occurs, if the option to receive notifications is selected.
Utility Load-Shedding Mode DEACTIVATED (Normal Equipment Operation) – When load shedding
mode is not required, the contacts in the utility load control receiver are closed. This provides 24VAC to the coil of the field-provided relay (catalog # 69J79).The relay contacts
OPEN (terminal 7 to terminal 2) removing 24VAC from the L terminal on the outdoor control. This deactivates the
load-shedding mode in the outdoor control. The outdoor unit returns to normal operation and alert code clears once load-shedding mode is deactivated.
For more information, see the Load-Shedding Feature Wir ing Diagram on page 47.
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
REFER TO THE UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY, AND MAXIMUM FUSE OR CIRCUIT BREAKER (HACR PER NEC). INSTALL POWER WIRING AND PROPERLY SIZED DISCONNECT SWITCH.
MAIN FUSE BOX/ BREAKER PANEL
DISCONNECT
SWITCH
NOTE - UNITS ARE APPROVED FOR USE ONLY WITH COPPER CONDUCTORS. GROUND UNIT AT DISCONNECT SWITCH OR TO AN EARTH GROUND.
Figure 12. Electrical Installation
INSTALL THERMOSTAT
INSTALL ROOM THERMOSTAT (ORDERED SEPARATELY) ON AN INSIDE WALL, APPROXIMATELY IN THE CENTER OF THE
2
CONDITIONED AREA AND 5 FEET (1.5M) FROM THE FLOOR. IT SHOULD NOT BE INSTALLED ON AN OUTSIDE WALL OR WHERE IT CAN BE AFFECTED BY SUNLIGHT OR DRAFTS.
THERMOSTAT
5 FEET
(1.5M)
NOTE - 24VAC, CLASS II CIRCUIT CONNECTIONS ARE MADE IN THE CON TROL BOX.
XC20
24
Loading...
+ 54 hidden pages