XC20 units have refrigerant piping requirements that are
unique to this unit. Size and install the refrigerant piping
per table 2 (page 14) to ensure proper unit operation.
IMPORTANT:
Before applying any power (main or low voltage) to the outdoor
unit, confirm that the iComfort Wi-Fi® or iComfort® S30
thermostat has software Version 2.1 or higher installed.
(Reference the iComfort Wi-Fi® or iComfort® S30 thermostat
manual.)
This unit is an integral component of a system that requires an
iComfort Wi-Fi
iComfort
XC20
®
®
or iComfort® S30 thermostat and
-enabled air handler or furnace.
iComfort Wi-Fi
thermostat
iComfort
®
thermostat
S30
iComfort
air handler or
furnace
®
®
-enabled
XC20
®
XC20 Units
TABLE OF CONTENTS
I. OVERVIEW
Model Number Identification2....................
Typical Serial Number Identification2..............
Specifications2.................................
Electrical Data3................................
Unit Dimensions4..............................
Typical Unit Parts Arrangement5.................
Operating Service Valves7.......................
General 7.....................................
II. INSTALLATION
Unit Placement9...............................
Removing and Installing Panels12.................
New or Replacement Line Set13..................
Brazing Connections16...........................
Flushing the System19...........................
Leak Testing the System21.......................
Evacuating the System21.........................
Electrical24.....................................
Servicing Unit Delivered Void of Charge29..........
Unit Start-Up29.................................
III. SYSTEM OPERATION AND SERVICE
7-Segment Alert and System Status Codes30.......
Outdoor Control Push-Button Operation38..........
Configuring Unit42...............................
Reconfiguring Outdoor Control using iComfort Wi-Fi
iComfort
System Overview43.............................
Maintenance44..................................
Unit Wiring Diagrams45..........................
Factory Wiring Diagrams48.......................
Unit Sequence of Operations50...................
Component Testing53............................
System Refrigerant75............................
Appendix - Charging Sticker ....................
®
S30 Thermostat43.....................
®
or
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property. Installation and service must be
performed by a licensed professional installer (or
equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
1
2015 Lennox Industries Inc.
Model Number Identification
I. OVERVIEW
Refrigerant Type
X = R-410A
Unit Type
C = AIR CONDITIONER
C 20036
X
−−
230
Nominal Cooling Capacity
A
-02
Minor Revision Number
Ratings Revision Level
Voltage
230 = 208/230V-1ph-60hz
024 = 2 tons
Series
036 = 3 tons
048 = 4 tons
060 = 5 tons
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008
09 = 2009
10 = 2010
8 09C
5
05716
5 (or 6) Digit Unique Number
Month Code
A = January
B = February
C = March
Specifications
UnitOutdoor Fan
Model Number
XC20-024-230-0172657 lbs, 5 oz422
Sound Rating Number (dB)
MaximumMinimum
1
Factory Refrigerant
Charge
2
Number of BladesDiameter - inches.
UnitOutdoor Fan
Model Number
XC20-036-230-0175678 lbs, 6 oz422
Model Number
XC20-048-230-01776810 lbs, 7 oz422
Model Number
XC20-060-230-01776912 lbs, 1 oz326
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Factory refrigerant charge is sufficient for refrigerant line lengths up to 15 feet.
Sound Rating Number (dB)
MaximumMinimum
Sound Rating Number (dB)
MaximumMinimum
Sound Rating Number (dB)
MaximumMinimum
1
UnitOutdoor Fan
1
UnitOutdoor Fan
1
Factory Refrigerant
Factory Refrigerant
Factory Refrigerant
Charge
Charge
Charge
2
2
2
Number of BladesDiameter - inches.
Number of BladesDiameter - inches.
Number of BladesDiameter - inches.
XC20
2
Electrical Data
208/230V-60 Hz-1 Ph
UnitCompressorOutdoor Fan (RPM varies with compressor RPM)
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
208/230V-60 Hz-1 Ph
Rated
Load
Amps
2
(RLA)
Locked
Rotor
Amps
(LRA)
Motor
HP
CFMRPMWATTS
MAXMINMAXMINMAXMIN
Load
Amps
(FLA)
Full
Full
Full
Full
XC20
3
Unit Dimensions -- Inches (mm)
35−1/2 (902)
A
2 (51)
39−3/8 (1000)
DISCHARGE AIR
LIQUID LINE
CONNECTION
ELECTRICAL
INLETS
SUCTION LINE
CONNECTION
4−1/4(108)
4−3/4
(121)
SIDE VIEW
1 (25)
Model No.
XC20−02439991
XC20−03639991
XC20−048451143
XC20−060451143
END VIEW
in.mm
UNIT SUPPORT
FEET
A
16−7/8
(429)
8−3/4
(222)
3−1/8
(79)
26−7/8
(683)
)3−3/4 (95
30−3/4 (781)
4−5/8
(117)
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox Product Specification bulletin.
Coils previously charged with HCFC-22 must be
flushed.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take care
while handling this equipment and use protective
clothing.
BASE WITH ELONGATED LEGS
WARNING
Electric Shock Hazard. Can cause injury or death. Unit
must be grounded in accordance with national and local
codes.
Line voltage is present at all components when unit is not
in operation on units with single‐pole contactors.
Disconnect all remote electric power supplies before
opening access panel. Unit may have multiple power
supplies.
WARNING
Electrical Hazard
High Voltage
Wait 5 Minutes
Electrical components may hold charge. Do
not remove this panel or service this area for
5 minutes after the power has been
removed.
XC20
4
Typical Unit Parts Arrangement
OUTDOOR
CONTROL
INVERTER REACTOR
CONTROL PANEL FOR
XC20-024 AND -036
DC INVERTER
CONTROL
GROUND LUG
CONTACTOR-SPST
OUTDOOR CONTROL
INVERTER REACTOR
CONTROL PANEL FOR
XC20-048 AND -060
DC INVERTER
CONTROL
INVERTER NOISE FILTER
GROUND LUG
CONTACTOR-SPST
Figure 1. Control Panel Components
XC20
5
COMPRESSOR TOP CAP
SWITCH (THERMAL)
Typical Plumbing Components
COMPRESSOR
CRANKCASE HEATER THERMOSTAT
(S40) OPENS AT 70ºF, CLOSES AT 50ºF
(ONE WAY - HFC-410A)
DRIER
LIQUID LINE SENSOR
SERVICE VALVE
Figure 2. Plumbing Component Locations
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox Product Specification bulletin.
Coils previously charged with HCFC-22 must be
flushed.
LOW PRESSURE
SWITCH
HIGH PRESSURE
SERVICE VALVE
SWITCH
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take care
while handling this equipment and use protective
clothing.
XC20
6
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
The XC20 is a high-efficiency residential split-system air
conditioner, which features a variable-capacity scroll com
pressor and uses HFC-410A refrigerant. Units are
available in 2, 3, 4 and 5-ton sizes. The series is designed
for use with an expansion valve (approved for use with
HFC-410A) in the indoor unit only.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys
tems must be capable of handling higher system operating
pressures. The gauges should be rated for use with pres
sures of 0 - 800 psig on the high side and a low side of 30”
vacuum to 250 psig, with dampened speed to 500 psi.
Gauge hoses must be rated for use at or up to 800 psig of
pressure with a 4000 psig burst rating.
Table 1. Torque Requirements
PartsRecommended Torque
Service valve cap8 ft.- lb.11 NM
Sheet metal screws16 in.- lb.2 NM
Machine screws #1028 in.- lb.3 NM
Compressor bolts90 in.- lb.10 NM
Gauge port seal cap8 ft.- lb.11 NM
TORQUE REQUIREMENTS
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 lists
torque values for fasteners.
Operating Service Valves
The liquid and vapor line service valves are used for re
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a fac
tory-installed valve stem. Figure 3 provides information on
how to access and operating both angle and ball service
valves.
IMPORTANT
Only use hex wrenches of sufficient hardness (50Rc Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs for
small valves, to 25 ft-lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using a
hex wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Note #C-08-1
for further details and information.
WARNING
The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death. It
may also cause cancer, birth defects, or reproductive
harm.
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
XC20
7
SERVICE VALVES
ANGLE AND BALL
Operating Angle–Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
STEM CAP
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is
open to line set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
rotate stem counterclockwise 90°. To close, rotate stem
clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN
CLOSED)
VALV E
STEM
STEM CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
When service valve is CLOSED, the service port is open
to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from contamination and
serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
DWith torque wrench: Finger tighten and
torque cap per table 1.
DWithout torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
10
9
8
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
DWith Torque Wrench: Finger tighten and then
torque cap per table 1.
DWithout Torque Wrench: Finger tighten and
use an appropriately sized wrench to turn an
additional 1/12 turn clockwise.
10
9
8
11
11
7
7
12
6
12
6
1/6 TURN
1
2
4
5
1/12 TURN
1
4
5
3
2
3
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball-Type Service Valves
XC20
8
II. INSTALLATION
Unit Placement
CAUTION
This unit may weigh up to 320 lbs. It could take more than
two people to lift this product. Take proper precautions
when lifting heavy objects.
See Unit Dimensions on page 4 for sizing mounting slab,
platforms or supports. Refer to figure 4 for mandatory
installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
DSome localities are adopting sound ordinances based
on the unit sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
DWhen possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans
mission. For proper placement of unit in relation to a
window see figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 5, de
tail B.
NOTE - If necessary for stability, anchor unit to slab as de
scribed in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated
in figure 5, detail C.
If additional elevation is necessary, raise the unit by ex
tending the height of the unit support feet. Use a 2-inch
(50.8mm) Schedule 40 female threaded adapter to raise
the height of the unit.
The specified coupling will fit snugly into the recessed por
tion of the feet. Use additional 2-inch (50.8mm) Schedule
40 male threaded adaptors which can be threaded into the
female threaded adaptors to make additional adjustments
to the level of the unit.
NOTE - Keep the height of extenders short enough to en
sure a sturdy installation. If it is necessary to extend the
height further than what is stable, consider a different type
of field-fabricated framework that is sturdy enough for
greater heights.
NOTES:
Service clearance of 30 in. must be maintained on one of the sides
adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
Clearance to one of the remaining two sides may be 12 in. and the
final side may be 6 in.
A clearance of 24 in. must be maintained between two units.
48 in. clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
Control
Box
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for
the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may
have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be
required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
Figure 4. Installation Clearances
XC20
9
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field-provided):
Always use stabilizers when unit is raised above the
factory height. (Elevated units could become unstable in
gusty wind conditions.)
Stabilizers may be used on factory height units when
mounted on unstable an uneven surface.
1. Remove the louvered panel from each side to expose
the unit base.
2. Install the brackets as illustrated in figure 5, detail D us
ing conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Locate the unit above a load-bearing wall or area of the roof
that can adequately support the unit. Consult local codes
for rooftop applications.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the
rubber to swell when it comes into contact with oil. The
rubber will then bubble and could cause leaks. Protect
the roof surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow this
notice could result in damage to roof surface.
XC20
10
DETAIL ADETAIL B
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE
TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5
M]) AWAY FROM BUILDING STRUCTURE.
Install unit away from windows.
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
GROUND LEVEL
Slab Mounting at Ground Level
Outside Unit Placement
BUILDING
STRUCTURE
MOUNTING
SLAB
DETAIL C
BASE
LEG DETAIL
2” (50.8MM) SCH 40
FEMALE THREADED
USE ADDITIONAL 2” SCH 40 MALE THREADED ADAPT
ERS WHICH CAN BE THREADED INTO THE FEMALE
THREADED ADAPTERS TO MAKE ADDITIONAL AD
JUSTMENTS TO THE LEVEL OF THE UNIT.
Elevated Slab Mounting using Feet
ADAPTER
2” (50.8MM) SCH 40
MALE THREADED
ADAPTER
Extenders
DETAIL D
Slab Side Mounting
#10 1/2” LONG SELF-DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL — 2” WIDTH; HEIGHT AS
#10 1-1/4” LONG HEX HEAD
SCREW AND FLAT WASHER
CONCRETE SLAB — USE TWO PLASTIC
ANCHORS (HOLE DRILL 1/4”)
WOOD OR PLASTIC SLAB — NO PLASTIC ANCHOR
(HOLE DRILL 1/8”)
REQUIRED)
CORNER POST
MINIMUM ONE
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL
— 2” (50.8MM) WIDTH; HEIGHT AS
REQUIRED); BEND TO FORM RIGHT ANGLE
SAME FASTENERS AS
SLAB SIDE MOUNTING.
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, TWO
BRACKETS PER SIDE, 2” (50.8MM) FROM EACH CORNER.
PER SIDE
FOR EXTRA
STABILITY
Stabilizing Unit on Uneven Surfaces
IMPORTANT - To help stabilize an outdoor unit, some installations may require strap
ping the unit to the pad using brackets and anchors commonly available in the
marketplace.
COIL
BASE PAN
Figure 5. Placement and Slab Mounting
XC20
11
Removing and Installing Panels
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slight
ly.
2. Hold the panel firmly throughout this procedure. Rotate bot
tom corner of panel away from hinged corner post until lower
three tabs clear the slots as illustrated in Detail B.
3. Move panel down until lip of upper tab clears the top slot in
corner post as illustrated in Detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in
Detail D with the screw side as close to the unit as possible.
Then, in a continuous motion:
1. Slightly rotate and guide the lip of the top tab inward as
illustrated in Detail A and C; then upward into the top slot
of the hinge corner post.
2. Rotate the panel until it is completely vertical to fully en
gage all of the tabs.
3. Holding the panel's hinged side firmly in place, close the
right-hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the
screws and tighten.
IMPORTANT
ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR
ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
SCREW
LIP
HOLES
Detail A
Detail B
ROTATE IN THIS DIRECTION;
ANGLE MAY BE TOO
EXTREME
THEN DOWN TO REMOVE
SIDE TO MAINTAIN FULLY-ENGAGED TABS
PANEL
HOLD DOOR FIRMLY TO THE HINGED
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL
WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
Figure 6. Removing and Installing Panels
PREFERRED ANGLE
FOR INSTALLATION
XC20
12
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replace
ment of existing line set. If new or replacement line set is
not being installed then proceed to Brazing Connections on
page 16.
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC-22 to
HFC-410A If that is not possible and the line set is the
proper size as referenced in table 2, use the procedure
outlined under Flushing the System on page 19.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building.
Pay close attention to line set isolation during installation of
any HVAC system. When properly isolated from building
structures (walls, ceilings, floors), the refrigerant lines will
not create unnecessary vibration and subsequent sounds.
See figure 7 for recommended installation practices. Also,
consider the following when placing and installing a high-
efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
of proper size may be reused. If system was previously
charged with HCFC-22 refrigerant, then existing line set
must be flushed (see Flushing the System on page 19).
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil
must be added, it must be a Polyol ester oil.
IMPORTANT !
If this unit is being matched with an approved line set
or indoor unit coil that was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation.
Take care to empty all existing traps. Polyol ester
(POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act as
an insulator, preventing proper heat transfer. It can
also clog the expansion device and reduce system
performance and capacity.
Failure to properly flush the system per the XC20
Installation and Service Procedures will void the
warranty.
WARNING
Refrigerant can be harmful if it is inhaled.
Refrigerant must be used and recovered
responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
Fire, Explosion and Personal Safety
Hazard. Failure to follow this warning
could result in damage, personal inju
ry or death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an ex
plosion, that could result in property
damage, personal injury or death.
WARNING
When using a high pressure gas such
as nitrogen to pressurize a
refrigeration or air conditioning
system, use a regulator that can
control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).
Recommended POE oils are Mobil EAL ARCTIC 22 CC or
ICI EMKARATEt RL32CF.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may
result in the low side shell and suction
tubing being pressurized. Application
of a brazing torch while pressurized
may result in ignition of the refrigerant
and oil mixture - check the high and
low pressures before unbrazing.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COMPRES
SOR.
The XC20 is a variable-capacity cooling system utilizing
variable-speed compressor technology. With the variablespeed compressor and variable pumping capacity,
additional consideration must be given to refrigerant piping
sizing and application. The following guidelines are to be
used exclusively for the XC20 systems.
XC20
13
COOLING SYSTEM (HFC410A)
DTotal equivalent length equals 180 feet (all piping and
fittings included).
NOTE - This is a general guide. Lengths may be more or
less, depending on remaining system design factors.
DMaximum linear (actual) length = 150 feet.
DMaximum linear liquid lift = 60 feet.
NOTE - Maximum lifts are dependent on total length, num
ber of elbows, and other factors that contribute to total
pressure drop.
DMaximum linear length of vapor riser = 60 feet.
DSize vertical vapor riser per table 2.
DLine set lengths up to 50 linear feet: Use rated line
sizes listed in table 2.
DLine set lengths between 51 and 150 linear feet:
Crankcase heater and nonbleed port TXV factory-in
stalled. No additional components required. Vertical
vapor riser must be sized to the vapor riser listed in
table 3 on systems with line sets longer than 51 feet.
Use tables 3 and 4 to determine the correct liquid and
vapor line sizes.
DLine set lengths over 150 linear feet: Not recom
mended.
DAdditional oil is not required for systems with line
lengths up to 150 feet.
NOTE - Recommended POE oils are Mobil EAL ARCTIC
22 CC or ICI EMKARATEt RL32CF.
SUCTION TRAPS
In systems with the outdoor unit 5 to 60 feet above the in
door unit, one trap must be installed at the bottom of the
suction riser.
Table 2. Standard Refrigerant Line Set — Up to 50 Linear Feet
* Applicable to all minor revision numbers unless otherwise specified.
** Some applications may require a field-provided 1-1/8” to 7/8” adapter.
Liquid LineSuction Line
3/8” (10 mm)7/8” (22 mm)
L15 Line Set
Model
L15-65-4040 feet (12.2 m)89J61
L15-65-5050 feet (15.2 m)89J62
Line Set Length
Catalog
Number
Table 3. XC20 Line Set Guidelines — 51 to 150 Linear Feet in Length
Model
02418015060603/4”5/8”
03618015060607/8”3/4”
04818015060607/8”7/8”
06018015060607/8”7/8”
Maximum Total
Equivalent Length (ft)
Maximum Linear
(actual) Length (ft)
Maximum Vapor
Riser (ft)
Maximum
Linear Liquid
Lift (ft)
Preferred Vapor Line
Sizes for Horizontal
Runs
Required Vapor
Riser Size
Table 4. Liquid Line Diameter Selection Table
Total Linear Length (feet)
Unit
024
036
048
060
Line Size
5/16”255055484033
3/8”255060606060
3/8”255060565145
1/2”255060606060
3/8”255050413122
1/2”255060606060
3/8”255036228NR
1/2”
255075100125150
25
5060606059
Note Shaded rows indicate rated liquid line size.
1. Find your unit on the left side of the table.
2. Start with the rated liquid line size (shaded row) for the outdoor unit.
3. Select the actual total linear length of your system shown at the top of the table.
4. The elevation listed in the table is the maximum allowed for the liquid line listed.
5. Consider the larger liquid line size shown in the table if the elevation does not meet your requirements.
Max. Elevation
(ft)
XC20
14
LINE SET
INSTALLATION
LINE SET ISOLATION — THE FOLLOWING ILLUSTRATIONS ARE EXAM
PLES OF PROPER REFRIGERANT LINE SET ISOLATION:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
AUTOMOTIVE
MUFFLER‐TYPE HANGER
IMPORTANT - Refrigerant lines must not contact structure.
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE - INSULATE LIQUID LINE WHEN IT IS ROUTED THROUGH AREAS
WHERE THE SURROUNDING AMBIENT TEMPERATURE COULD BECOME
HIGHER THAN THE TEMPERATURE OF THE LIQUID LINE OR WHEN
PRESSURE DROP IS EQUAL TO OR GREATER THAN 20 PSIG.
IMPORTANT - Refrigerant lines must not contact
wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL
STUD
STRAP LIQUID LINE TO
VAPOR LINE
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED
IN ARMAFLEX
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL
STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
WIRE TIE (AROUND
VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON-CORROSIVE
METAL SLEEVE
STRAP THE VAPOR LINE TO THE
JOIST OR RAFTER AT 8 FEET (2.43
METERS) INTERVALS THEN STRAP
THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR
WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN
STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
NOTE - SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF
LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
CAULK
STRAP
NON-CORROSIVE
METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID
LINE
FLOOR JOIST OR
ROOF RAFTER
WARNING - Polyol ester (POE) oils used with
HFC-410A refrigerant absorb moisture very quickly.
It is very important that the refrigerant system be kept
closed as much as possible. DO NOT remove line set
caps or service valve stub caps until you are ready to
make connections.
Figure 7. Line Set Installation
XC20
15
Brazing Connections
Use the procedures outlined in figures 8 and 9 for brazing
line set connections to service valves.
WARNING
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil mixture
- Check the high and low pressures
before applying heat.
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could re
sult in damage, personal injury or death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen, when
exposed to a spark or open flame, can
cause a fire and/or an explosion, that
could result in property damage, per
sonal injury or death.
XC20
16
PIPING PANEL REMOVAL AND LINE SET
PREPARATION
1
Remove piping panel for easier access to service valves. Cut ends
of the refrigerant lines square (free from nicks or dents) and debur
the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
STUB
CONNECTION
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction and liquid line
2
service ports.
SERVICE PORT CAP
SERVICE PORT
CORE
LIQUID LINE SERVICE VALVE
REFRIGERANT LINE
DO NOT CRIMP SERVICE
VALVE CONNECTOR WHEN
PIPE IS SMALLER THAN
CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING
LIQUID AND SUCTION LINE SERVICE VALVES
3
A.Connect gauge set low pressure side to liquid line
service valve (service port).
B.Connect gauge set center port to bottle of nitrogen
with regulator.
C.With valve core removed from the suction line service
port, nitrogen flow will have an exit point.
SUCTION SERVICE PORT MUST BE OPEN AND
SERVICE PORT CORE REMOVED TO ALLOW
EXIT POINT FOR NITROGEN FLOW
SUCTION LINE
INDOOR
UNIT
C
SUCTION LINE
SERVICE VALVE
SUCTION LINE SERVICE
VALV E
LOW
ATTACH
GAUGES
B
OUTDOOR
UNIT
HIGH
SERVICE PORT
CORE
SERVICE
PORT CAP
LIQUID LINE
LIQUID LINE SERVICE
VALV E
A
Figure 8. Brazing Procedures
17
NITROGEN
XC20
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve
5
and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths
6
must remain water-saturated throughout the brazing and cool-down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT - Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed joint. Do not
remove water-saturated cloths until piping has cooled.
Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER-SATURATED
CLOTH
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth
around both liquid and suction line service valve bodies
and copper tube stub while brazing the line set! The braze,
when complete, must be quenched with water to absorb
any residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated.
Refer to Installation and Service Procedures manual
found on DAVENET.
SUCTION LINE
PREPARATION FOR NEXT STEP
Disconnect manifold gauge set from service ports after all connections have been brazed. Apply additional water-saturated cloths to both
7
service valves to cool piping. Once piping is cool, remove all water-saturated cloths.
A.ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B.REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS
TRIBUTOR ASSEMBLY.
C.USING TWO WRENCHES, DISCONNECT LIQUID LINE FROM LIQUID LINE
ORIFICE HOUSING. TAKE CARE NOT TO TWIST OR DAMAGE DISTRIBU
TOR TUBES DURING THIS PROCESS.
D.REMOVE AND DISCARD FIXED ORIFICE, VALVE STEM ASSEMBLY (IF
PRESENT) AND TEFLON
E.USE A FIELD-PROVIDED FITTING TO TEMPORARILY RECONNECT THE
LIQUID LINE TO THE INDOOR UNIT'S LIQUID LINE ORIFICE HOUSING.
SHOWN)
DISTRIBUTOR TUBES
REMOVE AND DISCARD
WHITE TEFLON
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
BRASS NUT
®
(IF PRESENT)
®
WASHER AS ILLUSTRATED ABOVE.
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
2
INV ERT ED HCFC-22
CYLINDER CONTAINS
CLE AN HCFC-22* TO BE
USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
RECOVERY
CYLINDER
VALV E
VAPOR
LIQUID
NEW
OUTDOOR
UNIT
B
OPENED
C
D
A.INVERTED HCFC-22 CYLINDER WITH CLEAN REFRIGERANT* TO THE
VAPOR SERVICE VALVE.
B.HCFC-22 GAUGE SET (LOW SIDE) TO THE LIQUID LINE VALVE.
C.HCFC-22 GAUGE SET CENTER PORT TO INLET ON THE RECOVERY
MACHINE WITH AN EMPTY RECOVERY TANK TO THE GAUGE SET.
D.CONNECT RECOVERY TANK TO RECOVERY MACHINE PER MACHINE
INSTRUCTIONS.
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
RECOVERY MACHINE
MANIFOLD
LOW
TANK
RETURN
INLET
DISCHARGE
GAUGE
CLOSED
(UNCASED COIL ONLY)
OR
HIGH
SHOWN)
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A.ON FULLY CASED COILS, REMOVE THE COIL ACCESS AND PLUMBING
PANELS.
B.REMOVE ANY SHIPPING CLAMPS HOLDING THE LIQUID LINE AND DIS
TRIBUTOR ASSEMBLY.
C.DISCONNECT THE EQUALIZER LINE FROM THE CHECK EXPANSION
VALVE EQUALIZER LINE FITTING ON THE VAPOR LINE.
D.REMOVE THE VAPOR LINE SENSING BULB.
E.DISCONNECT THE LIQUID LINE FROM THE CHECK EXPANSION VALVE
AT THE LIQUID LINE ASSEMBLY.
F.DISCONNECT THE CHECK EXPANSION VALVE FROM THE LIQUID LINE
ORIFICE HOUSING. DO NOT TO TWIST OR DAMAGE DISTRIBUTOR
TUBES DURING THIS PROCESS.
G.REMOVE AND DISCARD CHECK EXPANSION VALVE AND THE TWO TEF
H.USE A FIELD-PROVIDED FITTING TO TEMPORARILY RECONNECT THE
®
RINGS.
LON
LIQUID LINE TO THE INDOOR UNIT'S LIQUID LINE ORIFICE HOUSING.
ORIFICE
HOUSING
EQUALIZER
LINE
STUB END
TEFLON
RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
FLUSHING LINE SET
3
CAUTION -This procedure should not be performed on systems
which contain contaminants (Example, compressor burn out).
THE LINE SET AND INDOOR UNIT COIL MUST BE FLUSHED WITH AT
LEAST THE SAME AMOUNT OF CLEAN REFRIGERANT* THAT PRE
VIOUSLY CHARGED THE SYSTEM. CHECK THE CHARGE IN THE
FLUSHING CYLINDER BEFORE PROCEEDING.
B
A.SET THE RECOVERY MACHINE FOR LIQUID RECOVERY AND
START THE RECOVERY MACHINE. OPEN THE GAUGE SET
VALVES TO ALLOW THE RECOVERY MACHINE TO PULL A VACU
UM ON THE EXISTING SYSTEM LINE SET AND INDOOR UNIT COIL.
B.INVERT THE CYLINDER OF CLEAN HCFC-22* AND OPEN ITS
VALVE TO ALLOW LIQUID REFRIGERANT TO FLOW INTO THE SYS
TEM THROUGH THE VAPOR LINE VALVE. ALLOW THE REFRIGER
ANT TO PASS FROM THE CYLINDER AND THROUGH THE LINE SET
AND THE INDOOR UNIT COIL BEFORE IT ENTERS THE RECOVERY
MACHINE.
C.AFTER ALL OF THE LIQUID REFRIGERANT HAS BEEN RECOV
ERED, SWITCH THE RECOVERY MACHINE TO VAPOR RECOVERY
SO THAT ALL OF THE HCFC-22 VAPOR IS RECOVERED. ALLOW
THE RECOVERY MACHINE TO PULL SYSTEM DOWN TO 0.
D.CLOSE THE VALVE ON THE INVERTED HCFC-22 DRUM AND THE
GAUGE SET VALVES. PUMP THE REMAINING REFRIGERANT OUT
OF THE RECOVERY MACHINE AND TURN OFF THE MACHINE.
®
SENSING
LINE
LIQUID
LINE
XC20
19
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
TYPICAL NEW CHECK EXPANSION VALVE INSTALLATION PROCEDURE
THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE LENNOX XC20
PRODUCT SPECIFICATIONS FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.
4
THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
THAT WILL PROVIDE ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.
®
TEFLON
RING
A.REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR AS
SENSING
LINE
LIQUID LINE
SEMBLY.
B.INSTALL ONE OF THE PROVIDED TEFLON
STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE
THE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON
RING WITH REFRIGERANT OIL.
C.ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATELY
SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS IL
LUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.
D.PLACE THE REMAINING TEFLON
OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON
FRIGERANT OIL.
E.ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.
9 O'CLOCK TO
3 O'CLOCK
BULB
12
®
BULB
9
WASHER AROUND THE OTHER END
12
11
10
8
7
6
®
RINGS AROUND THE
®
ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9
AND 3 O'CLOCK
POSITIONS.
SENSING BULB INSTALLATION
VAPOR LINE
A.ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.
NOTE - CONFIRM PROPER THERMAL CONTACT BETWEEN
VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU
LATING THE SENSING BULB ONCE INSTALLED.
B.CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE VAPOR LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS
TRATED BELOW.
9
10
11
12
1
8
7
5
6
1/8 TURN
2
3
4
VAPOR LINE
BULB
FLARE SEAL CAP
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
12
BULB
NOTE - NEVER MOUNT THE SENSING BULB ON
BOTTOM OF LINE.
THE SENSING BULB ON
BOTTOM OF LINE.
FLARE NUT
1/2 TURN
1
2
3
4
5
®
RING WITH RE
EQUALIZER LINE INSTALLATION
REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.
XC20
20
OR
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
IMPORTANT
Leak Testing the System
The Environmental Protection Agency (EPA) prohibits
the intentional venting of HFC refrigerants during
maintenance, service, repair and disposal of appliance.
Approved methods of recovery, recycling or reclaiming
must be followed.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which was
manufactured before January of 1999, the coil and line
set must be flushed prior to installation. Take care to
empty all existing traps. Polyol ester (POE) oils are
used in Lennox units charged with HFC-410A
refrigerant. Residual mineral oil can act as an insulator,
preventing proper heat transfer. It can also clog the
expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the instructions
below will void the warranty.
IMPORTANT
Leak detector must be capable of sensing HFC
refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
XC20
21
LEAK TEST
LINE SET AND INDOOR COIL
NOTE - NORMALLY, THE HIGH PRESSURE HOSE IS CONNECTED TO THE LIQUID LINE
PORT. HOWEVER, CONNECTING IT TO THE VAPOR PORT BETTER PROTECTS THE
MANIFOLD GAUGE SET FROM HIGH PRESSURE DAMAGE.
LOW
HIGH
CONNECT GAUGE SET
A.CONNECT AN HFC-410A MANIFOLD GAUGE SET HIGH PRESSURE
1
2
HOSE TO THE VAPOR VALVE SERVICE PORT.
B.WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER
OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET.
NOTE - LATER IN THE PROCEDURE,
THE HFC-410A CONTAINER WILL BE
REPLACED BY THE NITROGEN
CONTAINER.
NITROGEN
TEST FOR LEAKS
AFTER THE LINE SET HAS BEEN CONNECTED TO THE INDOOR AND OUTDOOR UNITS, CHECK THE LINE SET CON
NECTIONS AND INDOOR UNIT FOR LEAKS. USE THE FOLLOWING PROCEDURE TO TEST FOR LEAKS:
A.WITH BOTH MANIFOLD VALVES CLOSED, CONNECT THE CYLINDER OF HFC-410A REFRIGERANT TO THE CENTER PORT OF THE
MANIFOLD GAUGE SET. OPEN THE VALVE ON THE HFC-410A CYLINDER (VAPOR ONLY).
B.OPEN THE HIGH PRESSURE SIDE OF THE MANIFOLD TO ALLOW HFC-410A INTO THE LINE SET AND INDOOR UNIT. WEIGH IN A TRACE
AMOUNT OF HFC-410A [A TRACE AMOUNT IS A MAXIMUM OF TWO OUNCES (57 G) REFRIGERANT OR THREE POUNDS (31 KPA) PRESSURE]. CLOSE THE VALVE ON THE HFC-410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE
SET. DISCONNECT THE HFC-410A CYLINDER.
C.CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD
GAUGE SET.
D.ADJUST DRY NITROGEN PRESSURE TO 150 PSIG (1034 KPA). OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN
ORDER TO PRESSURIZE THE LINE SET AND THE INDOOR UNIT.
E.AFTER A FEW MINUTES, OPEN ONE OF THE SERVICE VALVE PORTS AND VERIFY THAT THE REFRIGERANT ADDED TO THE SYSTEM
EARLIER IS MEASURABLE WITH A LEAK DETECTOR.
F.AFTER LEAK TESTING, DISCONNECT GAUGES FROM SERVICE PORTS.
HFC-410A
B
MANIFOLD GAUGE SET
TO VAPOR
SERVICE VALVE
OUTDOOR UNIT
A
XC20
Figure 10. System Leak Test
22
Evacuating the System
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
1
NOTE - REMOVE CORES FROM SERVICE VALVES (IF
NOT ALREADY DONE).
A.CONNECT LOW SIDE OF MANIFOLD
GAUGE SET WITH 1/4 SAE IN-LINE TEE TO
VAPOR LINE SERVICE VALVE.
B.CONNECT HIGH SIDE OF MANIFOLD
GAUGE SET TO LIQUID LINE SERVICE
VALVE.
C.CONNECT MICRON GAUGE TO AN
AVAILABLE CONNECTOR ON THE 1/4 SAE
IN-LINE TEE.
D.CONNECT THE VACUUM PUMP (WITH
VACUUM GAUGE) TO THE CENTER PORT
OF THE MANIFOLD GAUGE SET. THE
CENTER PORT LINE IS USED LATER FOR
BOTH THE AND NITROGEN
CONTAINERS.
OUTDOOR
UNIT
A
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
C
MICRON
GAUGE
LOW
TO VAPOR
SERVICE VALVE
MANIFOLD
GAUGE SET
HIGH
HFC-410A
VACUUM PUMP
B
TO LIQUID LINE
SERVICE VALVE
D
NITROGEN
EVACUATE THE SYSTEM
A.OPEN BOTH MANIFOLD VALVES AND START THE VACUUM PUMP.
2
B.EVACUATE THE LINE SET AND INDOOR UNIT TO AN ABSOLUTE PRESSURE OF 23,000 MICRONS (29.01 INCHES OF MERCURY).
NOTE - DURING THE EARLY STAGES OF EVACUATION, IT IS DESIRABLE TO CLOSE THE MANIFOLD GAUGE VALVE AT LEAST ONCE. A
RAPID RISE IN PRESSURE INDICATES A RELATIVELY LARGE LEAK. IF THIS OCCURS, REPEAT THE LEAK TESTING PROCEDURE.
NOTE - THE TERM ABSOLUTE PRESSURE REFERS TO THE TOTAL ACTUAL PRESSURE (ABOVE ABSOLUTE ZERO) WITHIN A GIVEN
VOLUME OR SYSTEM. ABSOLUTE PRESSURE IN A VACUUM IS EQUAL TO ATMOSPHERIC PRESSURE MINUS VACUUM PRESSURE.
C.WHEN THE ABSOLUTE PRESSURE REACHES 23,000 MICRONS (29.01 INCHES OF MERCURY), CLOSE THE MANIFOLD GAUGE VALVES, TURN
OFF THE VACUUM PUMP AND DISCONNECT THE MANIFOLD GAUGE CENTER PORT HOSE FROM VACUUM PUMP. ATTACH THE MANIFOLD
CENTER PORT HOSE TO A DRY NITROGEN CYLINDER WITH PRESSURE REGULATOR SET TO 150 PSIG (1034 KPA) AND PURGE THE HOSE.
OPEN THE MANIFOLD GAUGE VALVES TO BREAK THE VACUUM IN THE LINE SET AND INDOOR UNIT. CLOSE THE MANIFOLD GAUGE VALVES.
D.SHUT OFF THE DRY NITROGEN CYLINDER AND REMOVE THE MANIFOLD GAUGE HOSE FROM THE CYLINDER. OPEN THE MANIFOLD
GAUGE VALVES TO RELEASE THE DRY NITROGEN FROM THE LINE SET AND INDOOR UNIT.
E.RECONNECT THE MANIFOLD GAUGE TO THE VACUUM PUMP, TURN THE PUMP ON, AND CONTINUE TO EVACUATE THE LINE SET AND IN
DOOR UNIT UNTIL THE ABSOLUTE PRESSURE DOES NOT RISE ABOVE 500 MICRONS (29.9 INCHES OF MERCURY) WITHIN A 20-MINUTE
PERIOD AFTER SHUTTING OFF THE VACUUM PUMP AND CLOSING THE MANIFOLD GAUGE VALVES.
F.WHEN THE ABSOLUTE PRESSURE REQUIREMENT ABOVE HAS BEEN MET, DISCONNECT THE MANIFOLD HOSE FROM THE VACUUM PUMP
AND CONNECT IT TO AN UPRIGHT CYLINDER OF HFC-410A REFRIGERANT. OPEN THE MANIFOLD GAUGE VALVE 1 TO 2 PSIG IN ORDER TO
RELEASE THE VACUUM IN THE LINE SET AND INDOOR UNIT.
G.PERFORM THE FOLLOWING:
1. Close manifold gauge valves.
2
. Shut off HFC-410A cylinder.
. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
3
tool while maintaining a positive system pressure.
. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illus
4
trated.
RECOMMEND
MINIMUM 3/8” HOSE
11
10
9
8
7
12
6
1/6 TURN
1
2
3
4
5
Figure 11. Evacuating System
XC20
23
IMPORTANT
Load Shedding
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are
defined as any gas that will not condense under temperat
ures and pressures present during operation of an air
conditioning system. Non-condensables combine with re
frigerant to produce substances that corrode copper piping
and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams. Refer to unit
nameplate for minimum circuit ampacity and maximum
over-current protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air hand
ler for low‐voltage control power (24VAC - 40 VA
minimum).
Utility Load Shedding Mode ACTIVATED
(Utility Cycled Unit OFF) – The normally closed set of
contacts in the utility load shedding control receiver OPEN.
This removes 24VAC from the coil of the field-provided re
lay (catalog # 69J79). The relay contacts close (terminal 7
to terminal 2), completing the circuit between terminals R
and L on the outdoor control. The 24VAC input to terminal L
activates the load-shedding mode in the outdoor control,
cycling the outdoor unit OFF. The 7-Segment display on
the outdoor control displays a load shedding alert code
(E600) and an alert appears on the display of the iComfort
®
thermostat. The customer receives email notifica
Wi-Fi
tions when the alert occurs, if the option to receive
notifications is selected.
mode is not required, the contacts in the utility load control
receiver are closed. This provides 24VAC to the coil of the
field-provided relay (catalog # 69J79).The relay contacts
OPEN (terminal 7 to terminal 2) removing 24VAC from the
L terminal on the outdoor control. This deactivates the
load-shedding mode in the outdoor control. The outdoor
unit returns to normal operation and alert code clears once
load-shedding mode is deactivated.
For more information, see the Load-Shedding Feature Wir
ing Diagram on page 47.
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
1
REFER TO THE UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY,
AND MAXIMUM FUSE OR CIRCUIT BREAKER (HACR PER NEC).
INSTALL POWER WIRING AND PROPERLY SIZED DISCONNECT
SWITCH.
MAIN FUSE BOX/
BREAKER PANEL
DISCONNECT
SWITCH
NOTE - UNITS ARE APPROVED FOR USE ONLY WITH COPPER
CONDUCTORS. GROUND UNIT AT DISCONNECT SWITCH OR TO AN
EARTH GROUND.
Figure 12. Electrical Installation
INSTALL THERMOSTAT
INSTALL ROOM THERMOSTAT (ORDERED SEPARATELY) ON AN
INSIDE WALL, APPROXIMATELY IN THE CENTER OF THE
2
CONDITIONED AREA AND 5 FEET (1.5M) FROM THE FLOOR. IT
SHOULD NOT BE INSTALLED ON AN OUTSIDE WALL OR WHERE IT
CAN BE AFFECTED BY SUNLIGHT OR DRAFTS.
THERMOSTAT
5 FEET
(1.5M)
NOTE - 24VAC, CLASS II CIRCUIT CONNECTIONS ARE MADE IN THE CON
TROL BOX.
XC20
24
Loading...
+ 54 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.