Lennox XC1702, CBX40UHV02, XC2105, SL28003, EL296V01 User Manual

...
2012 Lennox Industries Inc.
Dallas, Texas, USA
INSTALLER’S SYSTEM SETUP GUIDE
icomfort Wi-Fi Thermostat
Touch Screen Programmable Communicating Thermostat
CONTROLS
indoor temperature
indoor humidity is 41%
Wi−Fi
system is cooling
9:39 am Aug 15, 2012
set temp
75
cool−to
72
heat to
heat
or
cool
fan is AUTO
fan is
fan is AUTO
OFF
outdoor
temperature
80
away mode
506920−01 09/12 Supersedes 05/12
icomfort−Enabled Units
G71MPP−03 or later XC17−02 or later SLP98−01 or later XP17−02 or later SL280−03 or later XP19−06 or later EL296V−01 or later XC21−05 or later CBX40UHV−02 or later XP21−01 or later CBX32MV−06 or later
Shipping and Packing List
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER
FOR FUTURE REFERENCE
NOTICE
Read this manual before programming this thermostat.
Use this thermostat only as described in this manual.
09/12 506920−01
1 − icomfort Wi-Fi thermostat
4 − Mounting Screws 4 − Wall Anchors
1 − Installation Quick-Start Guide 1 − Installer’s System Setup Guide
1 − Homeowner’s Manual 1 − Warranty card
*2P0912* *P506920-01*
Table of Contents Page
Technical Description/Features 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Setup 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Settings screen 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Change settings (dealer info, daylight savings, fan circulate) 5. . . . . . . . . . .
Table 1. System settings defaults and ranges 6. . . . . . . . . . . . . . . . . . . . . . .
Set Time and Date 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add or Remove Non−communicating equipment 9. . . . . . . . . . . . . . . . . .
Maintenance Timers 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Unit 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Humidifier 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dehumidifier 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjust a setting screen 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Humidifier 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Dehumidifier (Humiditrol®/Aux. Dehum. installed) 16. . . . . . . .
Configure Dehumidification (no dehumidifier installed) 17. . . . . . . . . . . . . .
Humidification and Dehumidification Modeshow they work 18. . . . . . . . . . .
Use the Test Features 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set up Equipment Parameters 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use the Diagnostic Features 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
View and Clear Alerts 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enable Wi−Fi from User Home Screen 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Register the icomfort Personal Computer account registration to icomfort
PC Welcome screen, interactive demo, Gelaskins 27. . . . . . . . . . . . . . . . . . . .
Access Installer Program from User Home Screen 28. . . . . . . . . . . . . . . . . . .
Reconfigure a System 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stage Delay Timers & Differentials 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smooth Setback Recovery (SSR) 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Pump, Dual Fuel and Balance Points 32. . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Heat Control Mode 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2. Variable Capacity Furnace Operation 35. . . . . . . . . . . . . . . . . . . . . . .
Table 3. Adjustable Parameters (Installer) 37. . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4. Adjustable Parameters (User) 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 5. Alert Codes and Troubleshooting 45. . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Service Codes 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wi-Fi thermostat 26. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wi-Fi server 26. . . . . .
Table 6. Troubleshooting Tips 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat wire termination in communicating system 63. . . . . . . . . . . . . . . .
Table 7. Replacement Controls 72. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up typical icomfort systems
Indoor Unit Outdoor Unit page
icomfort−enabled furnace
icomfort−enabled furnace (dual fuel)
icomfort−enabled air handler
icomfort−enabled air handler
icomfort enabled AC 65
non−communicating AC 66
icomfort enabled HP 67
non−communicating HP not supported
icomfort enabled AC 68
non−communicating AC 69
icomfort enabled HP 70
non−communicating HP 71
CAUTION
This is a 24VAC Class 2 thermostat. Do not install on voltages higher than 30VAC.
Do not switch system to cool if the outdoor temperature is below 45°F (7°C). This can damage the cooling system.
WARNING
Electric shock hazard.
Always turn off power at the main power source by switching the circuit breaker to the OFF position before installing or removing this thermostat.
All wiring must conform to local and national building and electrical codes and ordinances.
506920−01 09/12
Page 2
icomfort Wi-Fi Thermostat − Technical Description and Features
The 24VAC icomfort Wi-Fi thermostat (figure 1) is an electronic communi- cating, color display touchscreen, 7−day programmable thermostat. It stores system parameters and settings in nonvolatile memory (i.e., it retains data when electrical power fails or is turned off). It is designed for 4−wire connec­tion to other communication devices as listed in figure 1.
The icomfort Wi-Fi thermostat can connect to online services via the inter- net through the homeowner’s Wi−Fi access point. After online registration is completed, the system may then be accessed by the homeowner from any­where using a remote internet connection via computer or personal commu­nicating device.
R i+ i− C
Thermostat connections
BEST PRACTICES! Keep all communication wiring as far away from house electrical wiring and large electrical appliances as possible (15’ [5m] recom­mended).
The thermostat also:
supports three languages (English, French, Spanish), supports air conditioning units or heat pump units with up to four stages
supports Indoor Air Quality with time-based notification of consum-
supports variable−capacity / multi−stage heat/cool, universal compati-
Important
Connections to non−communicating outdoor units and accessories are de­scribed in the Quick−Start Installation guide. (Wiring diagrams are also shown beginning on Page 59 of this manual.)
Maximum total length of all
RED
RSBus Minimum wire size is 18 gauge
icomfort−enabled Furnace Control icomfort−enabled Air Handler Control icomfort−enabled Outdoor Unit Control External Sensors − outdoor temperature, discharge air Humidify Control Dehumidify Control
YELLOW
connections on the RSBus is
GREEN
WHITE
limited to 1500 ft. (450 m). Max. length between compo­nents is 300 ft. (90 m).
Figure 1. icomfort by Lennox system
Note: icomfort Wi-Fi thermo­stat does not require shielded cable wiring.
Supports
Humidification Measurement and Control, Dew Point Adjustment Control Dehumidification Measurement and Control Humiditrol® Enhanced Dehumidification Accessory (EDA)  Multi-Stage HVAC Systems Equipment Maintenance Reminders Autochangeover Mode −− Permits control of heating, cooling, humidifi-
Outdoor Temperature Sensor (option)
Communicating outdoor units contain a built−in outdoor temperature sensor.
of heat / two stages of compressor operation (2 stages of heat pump heating, 2 stages of auxiliary back−up heating, 2 stages of emergency heating),
ables including media filters, UVC bulbs, humidifier pads, and Pure­Air system catalyst service / replacement,
bility (gas/electric/heat pump/ac), and is dual fuel capable (icomfort− enabled HP only) with two balance points.
cation, and dehumidification without user involvement.
Page 3
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Installation and Setup
IMPORTANT! Make sure the router is capable of, and set to operate in wireless network b" mode. Check router utility program or contact service provider for help. When determining the location for the Wi−Fi ther-
mostat, be sure it is in an area near enough to the homeowner’s Wi−Fi router to ensure good communications signal between the thermostat and the rout­er. (Hint: use a smart phone with Wi−Fi to find and determine signal strength.)
Refer to the Quick Start Guide for information about installing the thermostat on a wall and for wiring diagrams for field wiring the thermostat to the system using one of a number of possible configurations. (Wiring diagrams are also shown beginning on Page 59 of this manual.)
NOTE − If electric heat strips are used with an icomfortt−enabled air handler, the strips MUST be configured on the air handler control (AHC) board before beginning the discovery" sequence below.
After all wiring connections are made, apply power to the system. 24VAC will power up the thermostat.
After power is applied to the thermostat for the first time, the processor checks the system for installed communicating devices, the So Sim­ple. So Smart. So Comfortable" screen dis­plays; followed by Use this thermostat?" screen. Touch press here to continue. During the setup process, alerts may pop open to provi­de the installer with information that affects the setup. Correct the cause of any such alerts
prior to continuing setup.
(Thermostat 1)
Use this Thermostat?
press here
System settings (figure 2) appear first. As you use the up/down arrows to scroll through the settings, the right hand side will show the current value. For example, current value: 9:39 am Aug 15, 2012 shows the current date for Time and Date.
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then press edit
current value:
9:39 am Aug 15, 2012
back
edit
next
Figure 2. System settings" screen
506920−01 09/12
Page 4
up/down
arrows
radio
buttons
keyboard
Circulate Fan ON Time Range
is 15 to 50 %
Default is 35, inc: 1
set−to
45%
Select one
Not Installed 1 Stage A/C Unit
2 Stage A/C Unit 1 Stage HP Unit
2 Stage HP Unit
tool
Dealer Name
cancelsave
Outdoor Unit Type
cancelsave
Change settings
If you want to change a setting, use one of the Settings change tools shown in figure 3. (Also, see Set time and date on Page 7.) After changes have been made, use save to store the changed data or cancel to exit the screen and return to the list of settings.
Dealer Number
Use the arrows to scroll to the Dealer Number setting. Press edit and use the typewriter tool (shown in figure 3) to enter your dealer number. Press save to store the identification.
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then press edit
current value:
back
edit
next
Figure 3. Settings change tools
Page 5
Figure 4. Entering Dealer Number"
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Circulate fan ON time setting
NOTE − If the circulate fan mode is on, a timer is set to measure all the time that the fan is blowing, regardless if it is running to deliver heating or cooling or just for circulation.
Circulate" is enabled on the user’s home screen or system settings page. It keeps air circulating from 15% to 50% percent of time. The following set­tings approximate how long the fan will run at these typical settings:
15% (9 minutes fan run time per hour) 25% (15 minutes fan run time per hour) 35% (21 minutes fan run time per hour) 45% (27 minutes fan run time per hour).
Table 1 shows the range/condition and defaults for the system settings and indicates the tools used to make changes.
Table 1. System setting defaults and range
system
setting
Time and Date see Page 7
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
range/
default use
condition
Enabled/Disabled Enabled
15 to 50% (in 1%
increments)
(alpha−numeric
characters)
(alpha−numeric
characters)
35%
****
Lennox
1−800−9−LENNOX
www.lennox.com
use keyboard
tool to change
use keyboard
tool to change
506920−01 09/12
Page 6
Set time and date
Use the arrows to select Time and Date; press edit (see figure 5) to proceed to the Set current time and date" screen (figure 6).
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then press Edit
current value:
9:39 am Aug 15, 2012
edit
nextback
Figure 5. View/edit time and date
When Time and Date" screen (figure 6) appears, enter the correct date as follows:
Use the left and right arrows to change the month and year. Touch a day of the month to select it. Press on the hour or minute; up down arrows appear to allow change. Touch the am/pm field to toggle it between am and pm. When the correct date and time is set, press save to save settings and
return to previous settings screen.
Touch next to continue to next screen.
system settings
January 2012
SMTWTFS
1234567
09 : 39 am
8 9 10 11 12 13 14
15 16 17 18 19 20 21
22 23 24 25 26 27 28
29 30 31
9:39 am Aug 15, 2012
save
Figure 6. Set current time and date
Page 7
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Use about" screen & access Add or Remove Non−communicating equipment" screen
The about" screen shows details of discovered installed equipment.
From the system devices" screen, use arrow buttons to scroll to a device; then press the about button. Use the up/down arrows to scroll through and view additional information about the selected device. When finished viewing, press the back button.
Press next to advance to the Add or Remove Non−communicating equipment?" screen.
device feature list
system devices
System Heat Pump
Furnace
Thermostat
press ’about’ for more information on a highlighted device
about
Language Support
Equipment Type Name
Unit Model Number
Unit Serial Number Unit Nominal Capacity
Number of Heating Stages Heating Capacity by Stage Indoor Blower CFM Range Control Software Revision
Control Model Number
device description
Furnace
Equipment Type Name Furnace
back
(returns to
system devices screen)
9:39 am Aug 15, 2012
Figure 7. Using the about" screen and accessing Add or Remove Non−communicating equipment" screen
506920−01 09/12
back next
Page 8
system devices
System
Heat Pump Furnace Thermostat
Add or Remove Non−communi­cating equip­ment?
If no, press Next Step.
back next
yes
Add or Remove Non−communicating equipment
Figure 7 (previous page) shows how to access the Add or Remove Non− communicating equipment" screen.
Adding Non−Communicating Outdoor unitSee figure 8 for details
for adding/removing an outdoor unit.
Adding HumidifierThe procedures in figure 9 describe adding a non−
communicating humidifier which will be controlled by the icomfort Wi-Fi thermostat through the H" or HUM" terminals on the furnace or air handler.
Adding DehumidifierThe procedures in figure 10 describe adding a
non−communicating dehumidifier controlled by the icomfort Wi-Fi thermo- stat through the DH" output on the furnace or air handler.
NOTICE
For details about how the humidification and dehumidification modes operate and how to configure those modes, see additional in­formation beginning on Page 18.
HUMIDITY CONTROL TIPS
The standard humidification mode is Basic" (humidifier is energized
during a call for heat, if there is a humidification demand).
Sensed outdoor temperature, required for some features, is provided
from one of the following sources:
A downloaded via Wi−Fi when available (primary source), B sensor furnished with icomfort−enabled outdoor units, C separate outdoor sensor connected to the furnace or air handler
outdoor sensor" connections.
NOTE − If no source for outdoor temperature is present, Basic and Precision Dew Point Control" modes are not available.
If you do not have the ability to select or adjust the Humidity RH set-
point on the Indoor Humidity" button, the control is set for Display Only." In the installer program, go the equipment button and select System" and press the edit button. Select Humidification Control Mode" and press edit. Choose Basic," Precision," Basic Dew Point Control" or Precision Dew Point Control" and press save.
Adding non−communicating accessoriesAdding maintenance
timer reminders to accessories is a simple process of installing" the device, which effectively tells the thermostat to activate access to its service timers.
Timers are available for two (2) filters, Humidifier pad, UV bulb maintenance and the PureAir Air Purification system.
Page 9
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Add Non−Communicating Outdoor unit
System Devices
System
Furnace
non−communicating device list
Outdoor Unit Type
Humidifier
Dehumidifier
Add or Remove Non−communicating equipment?
to add/remove/adjust a device,
select it, then press edit
current value:
Not Installed
2a
2b
To add (or remove) an outdoor unit that is not icomfort−enabled, you must be at the Add or Remove Non−communicating equipment?" screen.
1. Press the yes button on this screen (see 1).
yes
1
nextback
edit
2. In the non−communicating device list" screen, use the arrows (2a) to highlight Outdoor Unit Type and press edit (2b).
3. Touch one of the radio buttons (3a) to select a 1−or 2−Stage AC Unit or a 1−or 2−Stage HP Unit; press save (3b).
4. Use arrows (4a) to highlight any red colored text in the device list (e.g. select Outdoor Unit Capacity; text turns white). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Change other red settings (if present) using a similar process.
NOTE − If the defaults are correct, you do not have to make any changes, but you must press save (5b). When all red text is gone, the back button will appear; press it to return to the Add or Remove Non−communicating equipment?" screen (1).
Select one
Not Installed 1 Stage A/C Unit
2 Stage A/C Unit 1 Stage HP Unit
2 Stage HP Unit
506920−01 09/12
Outdoor Unit Type
3a
cancelsave
3b
back
non−communicating device list
Outdoor Unit Type
Outdoor Unit Capacity
Outdoor Unit 1st Stage Capacity
Humidifier
Dehumidifier
9:39 am Aug 15, 2012
to add/remove/adjust a device,
select it, then press edit
current value:
2 Stage AC Unit
4a
please view and save all red settings
4b
back
Figure 8. Add non−communicating deviceOUTDOOR UNIT
Page 10
edit
Outdoor Unit Capacity
Range is 18 to 60
Default is 36, inc:1
set−to
36
5b
5a
cancelsave
Add (or Remove) Humidifier (skip if no humidifier is being used)
Before adding a humidifier, be sure that: the humidifier is wired to the furnace or air handler control as shown on the Optional
Accessories wiring diagram (see Page 61),
the entire system is wired, powered up, and the thermostat has detected the system’s
installed communicating devices, and you are at the Add or Remove Non−communi­cating equipment?" screen (see figure 7, Page 8).
system devices
System
Heat Pump
Furnace
non−communicating device list
Thermostat
Humidifier
Dehumidifier
Electronic Air Cleaner
Select one
Not Installed Bypass (24VAC) Humidifier
Power (120VAC) Humidifier Bypass and Power Humidifier
(available with furnace equipped systems only)
Humidifier
3a
3b
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Add or Remove Non− communicating equipment?
to add/remove/adjust a device,
select it, then press edit
current value:
Not Installed
2a
cancelsave
to add/remove/adjust a device,
select it, then press edit
current value:
Bypass (24VAC) Humidifier
4a
2b
yes
1
edit
nextback
edit
NOTE − Adding humidity regulating non−communicating devices may be a 2−step procedure:
To add (or remove) a humidifier,:
System
Heat Pump
Furnace
Thermostat
Bypass (24VAC) Humidifier
1st, the device must be installed (this page; after the humidifier is installed, the operation mode defaults to Basic"). 2nd, (if you want another mode, i.e. Precision, Basic Dew Point, or Precision Dew Point, the device requires further configuration (see Page 15).
1. Press the yes button on this screen (see 1).
2. In the non−communicating device list" screen, use the arrows (2a) to highlight Humidifier (note the current value, Not Installed) and press edit (2b).
3. Touch one of the radio buttons (3a) to select the type of humidifier (or select Not Installed, if removing humidifier); press save (3b).
4. The previous screen returns, but the current value now shows your selection (4a). Press the back (4b) button.
5. The Add or Remove..." screen reappears with your addition shown in the system devices list (5a). At this point, you may add more equipment (press yes) or if finished, press the next (5b) button to advance to the Adjust a setting..." screen (see page 15).
6. (If you want other than the default Basic" mode of operation) Configure the humidifier as described on Page 15.
system devices
Add or Remove Non− communicating equipment?
yes
5a
5b
nextback
back
4b
9:39 am Aug 15, 2012
Figure 9. Add or remove non−communicating deviceHUMIDIFIER
Page 11
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Add (or Remove) Humiditrol® or Auxiliary Dehumidifier (skip if no dehumidifying device is being used)
Before adding a dehumidifier, be sure that: the dehumidifier is wired to the furnace or air handler control as shown on the Option-
al Accessories wiring diagram (see Page 61),
the entire system is wired, powered up, and the thermostat has detected the sys-
tem’s installed communicating devices, and you are at the Add or Remove Non− communicating equipment?" screen (see figure 7, Page 8).
system devices
System
Furnace
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Select one
Not Installed Humiditrol
Auxiliary Dehumidifier
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Dehumidifier
3a
3b
Add or Remove Non−communicating equipment?
to add/remove/adjust a device,
select it, then press edit
current value:
2a
Not Installed
cancelsave
to add/remove/adjust a device,
select it, then press edit
current value:
Humiditrol
4a
yes
1
If ’no’, press Next Step
2b
edit
nextback
back
4b
NOTE − Adding humidity regulating non−communicating devices may be a 2−step procedure:
1st, the device must be installed (this page; after the dehumidifier is installed, the opera­tion mode defaults to Basic"). 2nd, set Humiditrol® comfort adjust overcooling and the min/max dehumidification set- points if desired (see Page 16).
To add (or remove) a dehumidifier, you must be at the Add or Remove Non−communicating equipment?" screen.
1. Press the yes button on this screen (see 1).
2. In the non−communicating device list" screen, use the arrows (2a) to highlight Dehumidifier and press edit (2b). Note the current value (e.g. Not Installed).
3. Touch one of the radio buttons (3a) to select the type of dehumidifier (or select Not Installed, if removing dehumidifier); press save (3b).
4. When you scroll to the Dehumidifier device (4a), (Note the current value, e.g. Humiditrol.) Click back (4b) to return to the Add or Remove..." screen (1).
5. The Add or Remove..." screen reappears with your addition shown in the system devices list (5a). At this point, you may add more equipment (press yes) or if finished, press the next button (5b) to advance to the Adjust a setting..." screen (see Page 13).
Humiditrol® NoteBy default, the Humiditrol Comfort Adjust (HCA) is configured for maxi­mum overcooling and minimum dehumidification setpoint of 40% RH. If these settings are satisfactory, no further configuration is necessary. If another setting is needed, change HCA and setpoint as described on Page 16.
edit
system devices
System
Heat Pump
Furnace
Thermostat
Humiditrol
5a
Add or Remove Non− communicating equipment?
yes
5b
nextback
506920−01 09/12
Figure 10. Add or remove non−communicating deviceDEHUMIDIFIER
Page 12
Adjust a setting screen (communicating devices)
Use arrows to select a device from the system devices" list; then use the about button to view information (shown on Page 8) about communicating devices (information about other devices is not available).
Use resetAll button to un−install all non−communicating devices that were added through Add or Remove..." screen and to reset any device settings made through this Adjust a setting..." screen to the factory defaults. (While editing a communicating device, the reset button is limited to only the selected device. You are asked to confirm (shown in figure 11) before resetting all.
Use this screen to access communicating devices’ settings (pressing buttons numbered from 1 to 6 in figure 11 for an example of changing heating airflow; more examples are shown on the next page). Use back to return to the previous screen or next to go on. A complete list of parameters, their defaults and setting ranges, begins on page 37.
system devices
System
Furnace
Thermostat
2 Stage HP Unit
Power (120VAC) Humidifier
Humiditrol
system devices
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
Continuous Indoor Blower Airflow
To adjust a setting, highlight it, then press Edit
Furnace
1
Low Heating Airflow
current value:
back
325
3
about
resetAll
edit
2
next
reset
edit
4
back
Figure 11. Adjust communicating device screens
Page 13
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
(if resetAll is pressed)
resetting a device to its factory default
(resetting ALL devices to their factory default)
settings will cause the system to restart the
To continue, press CONFIRM or press CANCEL
setup process.
confirm
Low Heating Airflow
Range is 325 to 450
Default is 400, inc:25
cancel
set−to
325
6
5
cancelsave
Use the up/down arrows to scroll through the device’s settings. The current setting will be displayed on the right−hand side of the screen (figure 12). For example, current value: disabled. Press edit if you want to modify that setting, or press back to return to the previous screen.
Available settings for the devices depend on the installed components. Shown below is an example of enabling and changing the balance point control from default (Disabled) to Enabled. After selecting Enabled, press save to save the changes and return to the previous screen.
The returning screen may appear with the message in red please view and save all red settings." In the example in figure 13, note that two additional items are listed in red. Use the arrows to scroll and highlight each item appearing in red. Press edit, make any desired changes, and press save.
When all affected settings have been edited/saved, the red message disappears. Press back to return to the To adjust a setting..." screen.
If no more adjustments are necessary, press next to advance to the select tests to run" screen (see Page 19).
System
Staged Delay Timers
2nd Stage Delay
3rd Stage Delay
Balance Point Control
Humiditrol Comfort Adjust
Humidification Control Mode
Select one Min Dehumidification Setpoint
OK/Humid BoundaryDisabled Enabled
Balance Point Control
cancelsave
Balance Point Control
current value
Disabled
edit
reset
back
System
Staged Delay Timers
2nd Stage Delay
3rd Stage Delay
Lock In 2nd stage HP by Outdoor Temp
Balance Point Control
High Balance Point
Low Balance Point
Humiditrol Comfort Adjust
Humidification Control Mode
Min Dehumidification Setpoint
Balance Point Control
current value
Enabled
please view and save all red settings
High Balance Point
Range is −17 to 75
Default is 0, inc:1
back
set−to
edit
reset
50
cancelsave
Figure 12. Accessing device to modify
Figure 13. Modify device settings
G71MPP or SLP98 Furnace Note:
If your icomfort Wi-Fi thermostat is being used with a G71MPP or SLP98 furnace and is set to variable−capacity mode of operation (the icomfort default with these units), the thermostat’s settings for stage timers are ignored (even if shown enabled in the thermostat). The stage timer will be used on the cooling side. The furnace software sets and controls the firing rates. The only other controlling factor is the stage temperature differentials. In Load−Tracking Variable Capacity (default for these furnaces), both stage timers and temperature differentials are ignored.
506920−01 09/12
Page 14
Adjust a setting... Configure Humidifier (skip if no humidifier is being used or if humidifier is being used and default Basic" humidification mode is desired)
Pre−adjustment REQUIREMENTS:
System Devices
System
Air Conditioner
Furnace
Thermostat
Power (120VAC) Humidifier
System
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
Select one
Display Only Basic
Precision Basic Dew Point Control
Precision Dew Point
Humidification Control Mode
3a
1a
2a
cancelsave 3b
To adjust a setting, highlight it, then press Edit
System
1b
Humidification Control Mode
current value:
Basic
back
2b
System
1st Stage Differential
back
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
Max Humidification Setpoint
OK/Humid Boundary
Outdoor Temperature Reading
9:39 am Aug 15, 2012
about
edit
resetAll
next
edit
reset
1st, the device has been installed (see Page 11). 2nd, you pressed next at the Add or Remove..." screen (see Page 11).
Configure the device as follows:
1. In the system devices" list, use the arrows (1a) to highlight System. Press edit (1b).
2. In the System" list, use the arrows (2a) to highlight Humidification Control Mode. The current value defaults to Basic mode. Press edit (2b).
3. Touch one of the radio buttons (3a) to select the mode of humidification control; press save (3b). (After saving, check that the current value now shows the new
selection).
4. Use arrows (4a) to highlight any red colored text in the list (e.g. select Max Humidifi­cation Setpoint). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Repeat for other red settings. You will not be able to advance to the next step until all red settings have been removed..
6. Press the back button to return to Adjust a setting..." screen.
NOTE − If the defaults for the settings shown in red, you are not required to make any changes, but you must go into the edit tool, and press save (5b). When all red text is gone, the back button will appear; press it to return to the Adjust a setting..." screen.
Max Humidification Setpoint
current value:
45
4a
please view and save all red settings
back
4b
edit
reset
(returns to
adjust a
setting screen)
Max Humidification Setpoint
Range is 15 to 45
Default is 45, inc:1
set−to
5a
45
5b
cancelsave
Figure 14. Adjust a non−communicating device settingHUMIDIFIER
Page 15
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Adjust a setting... Configure Humiditrol® or Auxiliary Dehumidifier
system devices
System
Air Conditioner
Furnace
Thermostat
Humiditrol
System
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min Dehumidification Setpoint
Select one
Maximum Overcooling Midpoint Overcooling
Minimum Overcooling
Humiditrol Comfort Adjust
3a
3b
Humiditrol Comfort Adjust settings are only available on units equipped with a Humiditrol See Page 18 for description of Min/ Mid/Max overcooling.
®
dehumidification device.
To adjust a setting, highlight it, then press Edit
System
1a
Dehumidification Control Mode
current value:
Midpoint Overcooling
2a
System
Staged Delay TImers
cancelsave
2nd Stage Delay
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min Dehumidification Setpoint
OD/Humid Boundary
Outdoor Temperature Reading Calibr
9:39 am Aug 15, 2012
back
1b
2b
about
resetAll
edit
reinstall
reset
edit
Pre−adjustment REQUIREMENTS:
1. In the system devices" list, use the arrows (1a) to highlight System. Press
2. Humiditrol® onlyIn the System" list, use the arrows (2a) to highlight
3. Humiditrol® onlyTouch one of the radio buttons (3a) to select the over-
4. Use arrows (4a) to highlight Min Dehumidification Setpoint; press edit
5. Use arrows (5a) to make changes; press save (5b). (After saving, check
6. Press the back button to return to Adjust a setting..." screen.
Dehumidification Control Mode
current value:
45
4a 4b
Figure 15. Adjust a non−communicating device settingDEHUMIDIFIER
1st, the device has been installed (see Page 12). 2nd, from the Add or Remove Non−communicating equipment?", press next. 3rd, in the Adjust a setting..." screen, configure the device as follows:
edit (1b).
Humiditrol Comfort Adjust. The current value defaults to Maximum Over-
cooling. Press edit (2b).
cooling level; press save (3b). (After saving, check that the current value
now shows the new selection).
(4b). Note the current value (e.g. 45).
that the current value now shows the new selection).
Min Dehumidification Setpoint
Range is 40 to 60
Default is 45, inc:1
set−to
42
5b
5a
cancelsave
6
back
edit
reset
(returns to
adjust a
setting
screen)
506920−01 09/12
Page 16
Adjust a setting... Configure Dehumidification (no dehumidifying device installed) (skip if default Basic" dehumidification mode is desired)
Pre−adjustment REQUIREMENTS:
System Devices
System
Furnace
Thermostat
2 Stage AC Unit
Power (120VAC) Humidifier
System
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
OK/Humid Boundary
Outdoor Temperature Reading
Select one
Display Only Basic
Precision
Dehumidification Control Mode
3a
3b
To adjust a setting, highlight it, then press Edit
System
1a
Dehumidification Control Mode
current value:
Display Only
2a
cancelsave
about
1b
edit
reinstall
back
next
2b
edit
System
Staged Delay Timers
back
Balance Point Control
Dehumidification Control Mode
Humidification Control Mode
Auto Changeover − Humidif. Deadband
Max Humidification Setpoint
Min Dehumidification Setpoint
OK/Humid Boundary
Outdoor Temperature Reading
reset
1st, NO physical dehumidification device has been installed. 2nd, configure the thermostat for dehumidification as follows:
1. In the system devices" list, use the arrows (1a) to highlight System. Press edit (1b).
2. In the System" list, use the arrows (2a) to highlight Dehumidification Control Mode. The current value defaults to Display Only. Press edit (2b).
3. Touch one of the radio buttons (3a) to select the mode of dehumidification control; press save (3b).
4. Use arrows (4a) to highlight any red colored text in the list (e.g. select Min Dehumidification Setpoint). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Change other red settings (e.g. Auto Changeover − Humidif. Deadband) using a similar process.
6. Press the back button to return to Adjust a setting..." screen.
NOTE − If the defaults are correct, you do not have to make any changes, but you must press save (5b). When all red text is gone, the back button will appear; press it to return to the Add or Remove Non−communicating equipment?" screen.
Dehumidification Control Mode
current value:
Precision
4a
please view and save all red settings
6
back
4b
edit
reset
Min Dehumidification Setpoint
Range is 40 to 60
Default is 45, inc:1
set−to
45
5b
5a
cancelsave
9:39 am Aug 15, 2012
Figure 16. Adjust dehumidification when not using Humiditrol or an auxiliary dehumidifier
Page 17
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Humidification and Dehumidification Modeshow they work
HUMIDIFICATION modes
BASIC & PRECISIONThese modes allow user control of RH between 15
and 45%. These conditions must be met for either mode to operate:
humidification mode has been enabled, and the unit is in HEAT mode, and humidification demand exists (24V present at H), and BASIC mode also requires presence of heating demand [Y for HP
heat, or W for gas heat (W may be energized with G de−energized)].
DEW POINT(Available only if Wi−Fi is operational or outdoor sensor is at­tached)
Basic Dew Point ControlBasic Dew Point Control adjustment mode will change the humidification setpoint based on the outdoor temperature and a user−defined dew point adjustment setting.
Precision Dew Point ControlPrecision Dew Point Control adjustment mode will operate when these conditions are met:
humidification mode has been enabled, and the unit is in HEAT mode, and humidification demand exists (24V present at H).
DEHUMIDIFICATION modes
NOTE − Basic and Precision dehumidification modes are functions of the HVAC system with NO external dehumidification devices installed. Humidi­trol and Auxiliary Dehumidifiers do not use these modes.
In BASIC mode, dehumidification occurs if these conditions are met and sig- nals are present at specific terminals:
dehumidification has been enabled on installer settings, and the unit is in COOL mode, and dehumidification demand exists (RH above setpoint), and cooling demand exists (Y1 energized).
506920−01 09/12
Page 18
In PRECISION mode, dehumidification occurs if all BASIC conditions are true, except cooling demand may or may not be present. Also note that:
Maximum overcool from cooling setpoint is 2ºF. Deadband temperature is limited to a minimum of 5ºF (instead of 3ºF
in BASIC or DISPLAY ONLY mode) because of 2ºF overcooling.
Humiditrol® or Auxiliary Dehumidifier mode requires:
NOTE − Systems using icomfortt and a dehumidifier − Dehum" jumper on furnace/air handler control does not need to be cut when using with a icom­fort Wi-Fit thermostat.
Wi−Fi is operational or outdoor sensor is installed and set up dehumidification has been enabled on installer settings, and the unit is in COOL mode, (or if in AUTO, at least one thermostat cool-
ing call made prior to the dehumidification demand), and
a dehumidification demand exists (RH above setpoint), and outdoor temp. below 95°F; indoor temp. above 65°F, and for HUMIDITROL, adjust Humiditrol® comfort parameters as follows:
MAX adj. − Indoor temp > 2°F above heating setpoint MID adj. − Indoor temp >
HEAT Setpoint+COOL Setpoint
2
MIN adj. − Indoor temp > 2°F below cooling setpoint
Auxiliary Dehumidifier (stand alone dehumidifier)
When this option is selected, dehumidification will be allowed under the fol­lowing conditions, provided there is NO call for humidification:
In the absence of heating or cooling calls, or Simultaneous with blower only calls.
If the blower is required to operate while the auxiliary dehumidifier is running, a separate wire must be installed from the auxiliary dehumidifier to the indoor unit’s G thermostat input that will energize G when the auxiliary dehumidifier is running (see wiring diagram on Page 61).
Auxiliary dehumidification is controlled by the thermostat dehumidification demand.
NOTE − Refer to HCWH Dehumidifier Installation Instructions for installation recommendations.
Use the Tests / Diagnostics features
NOTE − Test mode lasts for 30 minutes (with the temperature updating every 30 seconds) except for the defrost test, which lasts 30 seconds. Tests fea­ture provides the technician time to manually verify the equipment operation.
The tests feature is available after setup has been completed once. After you press next in the final setup screen, the select tests to run" screen (fig­ure 18) will appear. (If you want you may skip tests; press skip tests.)
If you re−select the tests button from the full option screen (figure 17), a mes­sage to press Start button below to begin system testing" appears. Press start. The resulting screen will be identical to figure 18.
tests alertssetup
press start button below to begin system testing
9:39 am Aug 15, 2012
equipment diagnostics
start
back
EXIT
Figure 17. Start testing screen
To run all of the tests, press select all. All boxes in the list of tests will be checked. Or, touch box(es) next to test(s) to run certain tests.
After the tests have been started, the screen will describe which test is run­ning and shows a diagnostic summary of each test (see figure 19). After re­viewing the results and concluding that no further tests are needed, press next to proceed to next test. The technician must verify that the test proce­dure is producing the desired result at the equipment.
select tests to run
Blower HP Heat − 1st Stage HP Heat − 2nd Stage Cooling − 1st Stage Cooling − 2nd Stage Dehumidification Gas Heat − Minimum Rate Gas Heat − Maximum Rate Humidification
9:39 am Aug 15, 2012
select all
deselect all
Figure 18. Select tests to run screen
equipment
current test: Blower
Heating Rate Blower CFM Demand Blower Off Delay Blower On Delay Indoor Blower RPM Indoor Blower Power Flame Current Flame Sense Outdoor Temperature
9:39 am Aug 15, 2012
Check Blower Operation
Figure 19. Typical tests results screens
alertssetup
% 1400CFM Off Off 0
0.0000%
0.000mA No Flame 63ºF
start
skip tests
diagnosticstests
nextcancel
Page 19
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
After pressing next after the final test, the Testing finished" screen will ap­pear (figure 20). At this point, use the EXIT button (if you have completed the required setup), or use diagnostics button (to analyze the system), or use
equipment button (if you wish to make any changes to device details).
equipment diagnosticstests alertssetup
The Testing Process is finished
press ’tests’ button to run more tests
press ’EXIT’ button to start normal operation
Set up Equipment parameters
Press equipment to set up equipment parameters and edit details of de­vices in the system without having to re−run the setup program. When the press start..." screen (figure 21A) appears, press start. The Equipment pa- rameters" screen (figure 21B) will open. You may view information about or modify communicating devices as described earlier in the setup pages, be­ginning on page 14. Use the arrows to select a device and press edit.
Use the arrows to highlight a setting and then press edit (figure 22A). In the example, the low heating airflow is changed from the default (400) to 325 (fig­ure 22B). After changing, press save. (note the current value has changed; figure 22C). Some changes may affect other settings and, if so, those af­fected will appear in red and require changing/saving to clear the red set­tings.
equipment diagnosticstests alertssetup
press start button below to edit details of devices in the system
start
9:39 am Aug 15, 2012
EXIT
Figure 20. Testing finished screen
Equipment, Alerts, Diagnostics
Press equipment if you need to set up equipment parameters and edit de­tails of devices in the system (see Page 20).
Press alerts if you need to run to see any alerts that may present or to view alerts that have been cleared (see Page 22).
Press diagnostics if you need to run to analyze the system (see Page 21).
506920−01 09/12
Page 20
equipmenttestssetup
system devices
System
Heat Pump
Furnace
Thermostat
Humiditrol
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then press Edit
Furnace
Figure 21. Equipment parameters screen
back
EXIT
about
resetAll
edit
next
system devices
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
system devices
Continuous Indoor Blower Airflow
Equipment Name
Heating Indoor Blower OFF Delay
Heating Airflow Control Type
Low Heating Airflow
9:39 am Aug 15, 2012
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
Continuous Indoor Blower Airflow
Heating Indoor Blower OFF Delay
9:39 am Aug 15, 2012
Low Heating Airflow
Range is 325 to 450
Default is 400, inc: 25
set−to
325
Figure 22. Edit equipment details
equipmenttestssetup
current value:
equipmenttestssetup
cancelsave
Low Heating Airflow
400
Low Heating Airflow
back
current value:
325
back
edit
resetAll
edit
resetAll
When finished, press back; equipment parameters screen (figure 21B re- turns); then press next. Select tests to run screen appears" (Page 19); ei­ther run tests as before or press skip tests.
The Testing process screen" (see figure 20) again appears; use the EXIT button (if you have completed the required setup), or use diagnostics but­ton (to analyze the system; see Page 21), or use equipment button again (if you want to make any further changes to device details).
Table 3 on (on Page 37) shows a list of Editable Parameters for the currently available devices designed to communicate in this system. Other devices and additional parameters may be added at a later time. Check the unit installation manuals (i.e. furnace, air handler, heat pump, ac unit) for current information and default parameters.
Run Diagnostics
NOTE − To run diagnostics and insure the system works properly, the system should be runningset the thermostat so that it will initiate a demand for cooling, heating, dehumidification, humidification, or continuous fan opera­tion.
If you need to run diagnostics to analyze the system, press the diagnostics button. The select a device" list (figure 23A) will open.
Use the arrow buttons to scroll through the list of items found on the left of the screen. The right side of the screen shows which item is selected. Use start to begin the process. A waiting" message displays while the diagnostics are being conducted, followed by a screen similar to figure 23B.
Use the arrow buttons to scroll through the information and take note of any found to be out of operating range.
Page 21
icomfort Wi-Fi 7−Day Programmable Communicating Thermostat
Press done when finished with the information. Select another device to diagnose or use EXIT (to close and go to user Home screen) if finished.
equipment diagnosticstests alertssetup
select a device:
Heat Pump
Furnace
current selection:
Furnace
start
DIAGNOSTICS
Furnace
Heating Rate 40.0%
9:39 am Aug 15, 2012
Blower CFM Demand 250 CFM Blower Off Delay Off Blower On Delay Off Indoor Blower RPM waiting Indoor Blower Power waiting Flame Current waiting Flame Sense waiting
Outdoor Temperature 88.0ºF
9:39 am Aug 15, 2012
EXIT
done
Figure 23. Select device and run diagnostics
View and clear Installer Alerts
NOTE − Service alerts remind users to service filters, humidifier pad, UV light and PureAirt Air Purification system and are not shown in the installer’s menu.
From the user’s home screen, press and hold the Lennox" logo in the bottom right corner of the thermostat to access the installer program. Press yes when asked if you want to proceed. The installer screen opens at the sys­tem and device alerts" screen (figure 24A).
The left side of the "system and device alerts" screen shows a list of each communicating device discovered in the system and check boxes for select­ing each device. Or, you may use buttons to the right of the System Devices list to select all (or deselect all). After something has been selected; use view active to list all active alerts for selected devices. If there are no alerts, the display will show There are no new alerts that require service". If there are alerts, these are stored for recall but only one alert will appear in the box at a time (see figure 24B). Use the next button to advance through all the alerts. If only one alert is present, the next button will not appear.
Alerts may pop up on the screen during setup. Details of all active alerts can only be accessed through the installer’s screens. To view all alerts present at any time, press the alerts button. System setup / Diagnostics is complete" (figure 24B) appears; close it and the Select devices to view alerts screen (figure 24A) appears.
Use view cleared alerts to list previously active alerts that were cleared by the device or installer. Until at least one alert has been cleared by the device or the installer, the message There are no new alerts that require service" will be displayed.
The first alert will be displayed in the alert screen (figure 24B), in order of:
1. red alert icon
2. yellow alert icon (service)
A red alert icon identifies a system or device issue that can prevent the sys­tem from working properly or at all, and if allowed to run, could cause dam­age to the system. The issue raised by the alert must be addressed and
corrected before clearing the alert!
Press clear (figure 24B) to clear a red alert. The alert will be stored in the cleared alerts" file. If an alert cannot be cleared, revisit the alert issue and make repairs accordingly.
506920−01 09/12
Page 22
Loading...
+ 50 hidden pages