G71MPP−03 or laterXC17−02 or later
SLP98−01 or laterXP17−02 or later
SL280−03 or laterXP19−06 or later
EL296V−01 or laterXC21−05 or later
CBX40UHV−02 or laterXP21−01 or later
CBX32MV−06 or later
Shipping and Packing List
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER
FOR FUTURE REFERENCE
NOTICE
Read this manual before programming this thermostat.
Use this thermostat only as described in this manual.
This is a 24VAC Class 2 thermostat. Do not install on voltages higher than
30VAC.
Do not switch system to cool if the outdoor temperature is below 45°F
(7°C). This can damage the cooling system.
WARNING
Electric shock hazard.
Always turn off power at the main power source by switching the circuit
breaker to the OFF position before installing or removing this thermostat.
All wiring must conform to local and national building and electrical
codes and ordinances.
506920−01 09/12
Page 2
icomfortWi-Fi Thermostat − Technical Description and Features
The 24VAC icomfortWi-Fi thermostat (figure 1) is an electronic communi-
cating, color display touchscreen, 7−day programmable thermostat. It stores
system parameters and settings in nonvolatile memory (i.e., it retains data
when electrical power fails or is turned off). It is designed for 4−wire connection to other communication devices as listed in figure 1.
The icomfortWi-Fi thermostat can connect to online services via the inter-
net through the homeowner’s Wi−Fi access point. After online registration is
completed, the system may then be accessed by the homeowner from anywhere using a remote internet connection via computer or personal communicating device.
R i+ i− C
Thermostat
connections
BEST PRACTICES! Keep all communication wiring as far away from house
electrical wiring and large electrical appliances as possible (15’ [5m] recommended).
The thermostat also:
supports three languages (English, French, Spanish),
supports air conditioning units or heat pump units with up to four stages
supports Indoor Air Quality with time-based notification of consum-
Connections to non−communicating outdoor units and accessories are described in the Quick−Start Installation guide. (Wiring diagrams are also
shown beginning on Page 59 of this manual.)
Maximum total length of all
RED
RSBus
Minimum wire
size is 18 gauge
icomfort−enabled Furnace Control
icomfort−enabled Air Handler Control
icomfort−enabled Outdoor Unit Control
External Sensors − outdoor temperature, discharge air
Humidify Control
Dehumidify Control
YELLOW
connections on the RSBus is
GREEN
WHITE
limited to 1500 ft. (450 m).
Max. length between components is 300 ft. (90 m).
Figure 1. icomfort by Lennox system
Note: icomfort
Wi-Fi thermostat does not
require
shielded cable
wiring.
Supports
Humidification Measurement and Control,
Dew Point Adjustment Control
Dehumidification Measurement and Control
Humiditrol® Enhanced Dehumidification Accessory (EDA)
Multi-Stage HVAC Systems
Equipment Maintenance Reminders
Autochangeover Mode −− Permits control of heating, cooling, humidifi-
Outdoor Temperature Sensor (option)
Communicating outdoor units contain a built−in outdoor temperature sensor.
of heat / two stages of compressor operation (2 stages of heat pump
heating, 2 stages of auxiliary back−up heating, 2 stages of emergency
heating),
ables including media filters, UVC bulbs, humidifier pads, and PureAir system catalyst service / replacement,
bility (gas/electric/heat pump/ac), and is dual fuel capable (icomfort−
enabled HP only) with two balance points.
cation, and dehumidification without user involvement.
IMPORTANT! Make sure the router is capable of, and set to operate in
wireless network b" mode. Check router utility program or contact
service provider for help. When determining the location for the Wi−Fi ther-
mostat, be sure it is in an area near enough to the homeowner’s Wi−Fi router
to ensure good communications signal between the thermostat and the router. (Hint: use a smart phone with Wi−Fi to find and determine signal
strength.)
Refer to the Quick Start Guide for information about installing the thermostat
on a wall and for wiring diagrams for field wiring the thermostat to the system
using one of a number of possible configurations. (Wiring diagrams are also
shown beginning on Page 59 of this manual.)
NOTE − If electric heat strips are used with an icomfortt−enabled air handler,
the strips MUST be configured on the air handler control (AHC) board before
beginning the discovery" sequence below.
After all wiring connections are made, apply power to the system. 24VAC will
power up the thermostat.
After power is applied to the thermostat for the
first time, the processor checks the system for
installed communicating devices, the So Simple. So Smart. So Comfortable" screen displays; followed by Use this thermostat?"
screen. Touch press here to continue. During
the setup process, alerts may pop open to provide the installer with information that affects the
setup. Correct the cause of any such alerts
prior to continuing setup.
(Thermostat 1)
Use this Thermostat?
press here
System settings (figure 2) appear first. As you use the up/down arrows to
scroll through the settings, the right hand side will show the current value.
For example, current value: 9:39 am Aug 15, 2012 shows the current date
for Time and Date.
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then
press edit
current value:
9:39 am Aug 15, 2012
back
edit
next
Figure 2. System settings" screen
506920−01 09/12
Page 4
up/down
arrows
radio
buttons
keyboard
Circulate Fan ON Time Range
is 15 to 50 %
Default is 35, inc: 1
set−to
45%
Select one
Not Installed1 Stage A/C Unit
2 Stage A/C Unit1 Stage HP Unit
2 Stage HP Unit
tool
Dealer Name
cancelsave
Outdoor Unit Type
cancelsave
Change settings
If you want to change a setting, use one of the Settings change tools shown
in figure 3. (Also, see Set time and date on Page 7.) After changes have
been made, use save to store the changed data or cancel to exit the screen
and return to the list of settings.
Dealer Number
Use the arrows to scroll to the Dealer Number setting. Press edit and use the
typewriter tool (shown in figure 3) to enter your dealer number. Press save to
store the identification.
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then
press edit
NOTE − If the circulate fan mode is on, a timer is set to measure all the time
that the fan is blowing, regardless if it is running to deliver heating or cooling
or just for circulation.
Circulate" is enabled on the user’s home screen or system settings page.
It keeps air circulating from 15% to 50% percent of time. The following settings approximate how long the fan will run at these typical settings:
15% (9 minutes fan run time per hour)
25% (15 minutes fan run time per hour)
35% (21 minutes fan run time per hour)
45% (27 minutes fan run time per hour).
Table 1 shows the range/condition and defaults for the system settings and
indicates the tools used to make changes.
Table 1. System setting defaults and range
system
setting
Time and Datesee Page 7
Daylight Saving
Time
Circulate Fan
ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
range/
defaultuse
condition
Enabled/DisabledEnabled
15 to 50% (in 1%
increments)
(alpha−numeric
characters)
(alpha−numeric
characters)
35%
****
Lennox
1−800−9−LENNOX
www.lennox.com
use keyboard
tool to change
use keyboard
tool to change
506920−01 09/12
Page 6
Set time and date
Use the arrows to select Time and Date; press edit (see figure 5) to proceed
to the Set current time and date" screen (figure 6).
system settings
Time and Date
Daylight Saving Time
Circulate Fan ON Time
System Name
Dealer Number
Dealer Name
Dealer Address
Dealer Phone
Dealer Email
Dealer Website
9:39 am Aug 15, 2012
To adjust a setting, highlight it, then
press Edit
current value:
9:39 am Aug 15, 2012
edit
nextback
Figure 5. View/edit time and date
When Time and Date" screen (figure 6) appears, enter the correct date as
follows:
Use the left and right arrows to change the month and year.
Touch a day of the month to select it.
Press on the hour or minute; up down arrows appear to allow change.
Touch the am/pm field to toggle it between am and pm.
When the correct date and time is set, press save to save settings and
Use about" screen & access Add or Remove Non−communicating equipment" screen
The about" screen shows details of discovered installed equipment.
From the system devices" screen, use arrow buttons to scroll to a device; then press the about button. Use the up/down arrows to scroll through and view
additional information about the selected device. When finished viewing, press the back button.
Press next to advance to the Add or Remove Non−communicating equipment?" screen.
device feature list
system devices
System
Heat Pump
Furnace
Thermostat
press ’about’ for
more information on
a highlighted device
about
Language Support
Equipment Type Name
Unit Model Number
Unit Serial Number
Unit Nominal Capacity
Number of Heating Stages
Heating Capacity by Stage
Indoor Blower CFM Range
Control Software Revision
Control Model Number
device description
Furnace
Equipment Type Name
Furnace
back
(returns to
system
devices
screen)
9:39 am Aug 15, 2012
Figure 7. Using the about" screen and accessing Add or Remove Non−communicating equipment" screen
506920−01 09/12
backnext
Page 8
system devices
System
Heat Pump
Furnace
Thermostat
Add or Remove
Non−communicating equipment?
If no, press Next
Step.
backnext
yes
Add or Remove Non−communicating equipment
Figure 7 (previous page) shows how to access the Add or Remove Non−
communicating equipment" screen.
Adding Non−Communicating Outdoor unitSee figure 8 for details
for adding/removing an outdoor unit.
Adding HumidifierThe procedures in figure 9 describe adding a non−
communicating humidifier which will be controlled by the icomfortWi-Fi
thermostat through the H" or HUM" terminals on the furnace or air handler.
Adding DehumidifierThe procedures in figure 10 describe adding a
non−communicating dehumidifier controlled by the icomfortWi-Fi thermo-
stat through the DH" output on the furnace or air handler.
NOTICE
For details about how the humidification and dehumidification
modes operate and how to configure those modes, see additional information beginning on Page 18.
HUMIDITY CONTROL TIPS
The standard humidification mode is Basic" (humidifier is energized
during a call for heat, if there is a humidification demand).
Sensed outdoor temperature, required for some features, is provided
from one of the following sources:
Adownloaded via Wi−Fi when available (primary source),
Bsensor furnished with icomfort−enabled outdoor units,
Cseparate outdoor sensor connected to the furnace or air handler
outdoor sensor" connections.
NOTE − If no source for outdoor temperature is present, Basic and
Precision Dew Point Control" modes are not available.
If you do not have the ability to select or adjust the Humidity RH set-
point on the Indoor Humidity" button, the control is set for Display
Only." In the installer program, go the equipment button and select
System" and press the edit button. Select Humidification Control
Mode" and press edit. Choose Basic," Precision," Basic Dew Point
Control" or Precision Dew Point Control" and press save.
timer reminders to accessories is a simple process of installing" the device,
which effectively tells the thermostat to activate access to its service timers.
Timers are available for two (2) filters, Humidifier pad, UV bulb maintenance
and the PureAir Air Purification system.
To add (or remove) an outdoor unit that is not icomfort−enabled, you must be at
the Add or Remove Non−communicating equipment?" screen.
1. Press the yes button on this screen (see 1).
yes
1
nextback
edit
2. In the non−communicating device list" screen, use the arrows (2a) to
highlight Outdoor Unit Type and press edit (2b).
3. Touch one of the radio buttons (3a) to select a 1−or 2−Stage AC Unit or a
1−or 2−Stage HP Unit; press save (3b).
4. Use arrows (4a) to highlight any red colored text in the device list (e.g.
select Outdoor Unit Capacity; text turns white). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Change other red
settings (if present) using a similar process.
NOTE − If the defaults are correct, you do not have to make any changes, but you
must press save (5b). When all red text is gone, the back button will appear; press
it to return to the Add or Remove Non−communicating equipment?" screen (1).
Select one
Not Installed1 Stage A/C Unit
2 Stage A/C Unit1 Stage HP Unit
2 Stage HP Unit
506920−01 09/12
Outdoor Unit Type
3a
cancelsave
3b
back
non−communicating device list
Outdoor Unit Type
Outdoor Unit Capacity
Outdoor Unit 1st Stage Capacity
Humidifier
Dehumidifier
9:39 am Aug 15, 2012
to add/remove/adjust a device,
select it, then press edit
current value:
2 Stage AC Unit
4a
please view and save all
red settings
4b
back
Figure 8. Add non−communicating deviceOUTDOOR UNIT
Page 10
edit
Outdoor Unit Capacity
Range is 18 to 60
Default is 36, inc:1
set−to
36
5b
5a
cancelsave
Add (or Remove) Humidifier (skip if no humidifier is being used)
Before adding a humidifier, be sure that:
the humidifier is wired to the furnace or air handler control as shown on the Optional
Accessories wiring diagram (see Page 61),
the entire system is wired, powered up, and the thermostat has detected the system’s
installed communicating devices, and you are at the Add or Remove Non−communicating equipment?" screen (see figure 7, Page 8).
system devices
System
Heat Pump
Furnace
non−communicating device list
Thermostat
Humidifier
Dehumidifier
Electronic Air Cleaner
Select one
Not InstalledBypass (24VAC) Humidifier
Power (120VAC) HumidifierBypass and Power Humidifier
(available with furnace equipped systems only)
Humidifier
3a
3b
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Add or Remove Non−
communicating
equipment?
to add/remove/adjust a device,
select it, then press edit
current value:
Not Installed
2a
cancelsave
to add/remove/adjust a device,
select it, then press edit
current value:
Bypass (24VAC) Humidifier
4a
2b
yes
1
edit
nextback
edit
NOTE − Adding humidity regulating non−communicating devices may be a 2−step procedure:
To add (or remove) a humidifier,:
System
Heat Pump
Furnace
Thermostat
Bypass (24VAC) Humidifier
1st, the device must be installed (this page; after the humidifier is installed, the operation
mode defaults to Basic").
2nd, (if you want another mode, i.e. Precision, Basic Dew Point, or Precision Dew Point,
the device requires further configuration (see Page 15).
1. Press the yes button on this screen (see 1).
2. In the non−communicating device list" screen, use the arrows (2a) to highlight
Humidifier (note the current value, Not Installed) and press edit (2b).
3. Touch one of the radio buttons (3a) to select the type of humidifier (or select NotInstalled, if removing humidifier); press save (3b).
4. The previous screen returns, but the current value now shows your selection (4a).
Press the back (4b) button.
5. The Add or Remove..." screen reappears with your addition shown in the system
devices list (5a). At this point, you may add more equipment (press yes) or if
finished, press the next (5b) button to advance to the Adjust a setting..." screen
(see page 15).
6. (If you want other than the default Basic" mode of operation) Configure the
humidifier as described on Page 15.
system devices
Add or Remove Non−
communicating
equipment?
yes
5a
5b
nextback
back
4b
9:39 am Aug 15, 2012
Figure 9. Add or remove non−communicating deviceHUMIDIFIER
Add (or Remove) Humiditrol® or Auxiliary Dehumidifier (skip if no dehumidifying device is being used)
Before adding a dehumidifier, be sure that:
the dehumidifier is wired to the furnace or air handler control as shown on the Option-
al Accessories wiring diagram (see Page 61),
the entire system is wired, powered up, and the thermostat has detected the sys-
tem’s installed communicating devices, and you are at the Add or Remove Non−
communicating equipment?" screen (see figure 7, Page 8).
system devices
System
Furnace
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Select one
Not InstalledHumiditrol
Auxiliary Dehumidifier
non−communicating device list
Humidifier
Dehumidifier
Electronic Air Cleaner
Dehumidifier
3a
3b
Add or Remove
Non−communicating
equipment?
to add/remove/adjust a device,
select it, then press edit
current value:
2a
Not Installed
cancelsave
to add/remove/adjust a device,
select it, then press edit
current value:
Humiditrol
4a
yes
1
If ’no’, press Next Step
2b
edit
nextback
back
4b
NOTE − Adding humidity regulating non−communicating devices may be a 2−step procedure:
1st, the device must be installed (this page; after the dehumidifier is installed, the operation mode defaults to Basic").
2nd, set Humiditrol® comfort adjust overcooling and the min/max dehumidification set-
points if desired (see Page 16).
To add (or remove) a dehumidifier, you must be at the Add or Remove Non−communicating
equipment?" screen.
1. Press the yes button on this screen (see 1).
2. In the non−communicating device list" screen, use the arrows (2a) to highlight
Dehumidifier and press edit (2b). Note the current value (e.g. Not Installed).
3. Touch one of the radio buttons (3a) to select the type of dehumidifier (or select NotInstalled, if removing dehumidifier); press save (3b).
4. When you scroll to the Dehumidifier device (4a), (Note the current value, e.g.
Humiditrol.) Click back (4b) to return to the Add or Remove..." screen (1).
5. The Add or Remove..." screen reappears with your addition shown in the system
devices list (5a). At this point, you may add more equipment (press yes) or if
finished, press the next button (5b) to advance to the Adjust a setting..." screen
(see Page 13).
Humiditrol® NoteBy default, the Humiditrol Comfort Adjust (HCA) is configured for maximum overcooling and minimum dehumidification setpoint of 40% RH. If these settings are
satisfactory, no further configuration is necessary. If another setting is needed, change HCA
and setpoint as described on Page 16.
edit
system devices
System
Heat Pump
Furnace
Thermostat
Humiditrol
5a
Add or Remove Non−
communicating
equipment?
yes
5b
nextback
506920−01 09/12
Figure 10. Add or remove non−communicating deviceDEHUMIDIFIER
Page 12
Adjust a setting screen (communicating devices)
Use arrows to select a device from the system devices" list; then use the about button to view information (shown on Page 8) about communicating
devices (information about other devices is not available).
Use resetAll button to un−install all non−communicating devices that were added through Add or Remove..." screen and to reset any device settings made
through this Adjust a setting..." screen to the factory defaults. (While editing a communicating device, the reset button is limited to only the selected device.
You are asked to confirm (shown in figure 11) before resetting all.
Use this screen to access communicating devices’ settings (pressing buttons numbered from 1 to 6 in figure 11 for an example of changing heating airflow;
more examples are shown on the next page). Use back to return to the previous screen or next to go on. A complete list of parameters, their defaults and
setting ranges, begins on page 37.
system devices
System
Furnace
Thermostat
2 Stage HP Unit
Power (120VAC) Humidifier
Humiditrol
system devices
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
Continuous Indoor Blower Airflow
To adjust a setting,
highlight it, then press
Edit
Use the up/down arrows to scroll through the device’s settings. The current setting will be displayed on the right−hand side of the screen (figure 12). For
example, current value: disabled. Press edit if you want to modify that setting, or press back to return to the previous screen.
Available settings for the devices depend on the installed components. Shown below is an example of enabling and changing the balance point control from
default (Disabled) to Enabled. After selecting Enabled, press save to save the changes and return to the previous screen.
The returning screen may appear with the message in red please view and save all red settings." In the example in figure 13, note that two additional items are
listed in red. Use the arrows to scroll and highlight each item appearing in red. Press edit, make any desired changes, and press save.
When all affected settings have been edited/saved, the red message disappears. Press back to return to the To adjust a setting..." screen.
If no more adjustments are necessary, press next to advance to the select tests to run" screen (see Page 19).
System
Staged Delay Timers
2nd Stage Delay
3rd Stage Delay
Balance Point Control
Humiditrol Comfort Adjust
Humidification Control Mode
Select one
Min Dehumidification Setpoint
OK/Humid BoundaryDisabledEnabled
Balance Point Control
cancelsave
Balance Point Control
current value
Disabled
edit
reset
back
System
Staged Delay Timers
2nd Stage Delay
3rd Stage Delay
Lock In 2nd stage HP by Outdoor Temp
Balance Point Control
High Balance Point
Low Balance Point
Humiditrol Comfort Adjust
Humidification Control Mode
Min Dehumidification Setpoint
Balance Point Control
current value
Enabled
please view and save all
red settings
High Balance Point
Range is −17 to 75
Default is 0, inc:1
back
set−to
edit
reset
50
cancelsave
Figure 12. Accessing device to modify
Figure 13. Modify device settings
G71MPP or SLP98 Furnace Note:
If your icomfortWi-Fi thermostat is being used with a G71MPP or SLP98 furnace and is set to variable−capacity mode of operation (the icomfort default
with these units), the thermostat’s settings for stage timers are ignored (even if shown enabled in the thermostat). The stage timer will be used on the cooling
side. The furnace software sets and controls the firing rates. The only other controlling factor is the stage temperature differentials. In Load−Tracking Variable
Capacity (default for these furnaces), both stage timers and temperature differentials are ignored.
506920−01 09/12
Page 14
Adjust a setting... Configure Humidifier (skip if no humidifier is being used or if humidifier is being used and default
Basic" humidification mode is desired)
Pre−adjustment REQUIREMENTS:
System Devices
System
Air Conditioner
Furnace
Thermostat
Power (120VAC) Humidifier
System
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
Select one
Display OnlyBasic
PrecisionBasic Dew Point Control
Precision Dew Point
Humidification Control Mode
3a
1a
2a
cancelsave 3b
To adjust a setting, highlight it,
then press Edit
System
1b
Humidification Control Mode
current value:
Basic
back
2b
System
1st Stage Differential
back
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
Max Humidification Setpoint
OK/Humid Boundary
Outdoor Temperature Reading
9:39 am Aug 15, 2012
about
edit
resetAll
next
edit
reset
1st, the device has been installed (see Page 11).
2nd, you pressed next at the Add or Remove..." screen (see Page 11).
Configure the device as follows:
1. In the system devices" list, use the arrows (1a) to highlight System. Press edit (1b).
2. In the System" list, use the arrows (2a) to highlight Humidification Control Mode.
The current value defaults to Basic mode. Press edit (2b).
3. Touch one of the radio buttons (3a) to select the mode of humidification control;
press save (3b). (After saving, check that the current value now shows the new
selection).
4. Use arrows (4a) to highlight any red colored text in the list (e.g. select Max Humidification Setpoint). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Repeat for other red settings.
You will not be able to advance to the next step until all red settings have been
removed..
6. Press the back button to return to Adjust a setting..." screen.
NOTE − If the defaults for the settings shown in red, you are not required to make any changes,
but you must go into the edit tool, and press save (5b). When all red text is gone, the back button
will appear; press it to return to the Adjust a setting..." screen.
Max Humidification Setpoint
current value:
45
4a
please view and save all
red settings
back
4b
edit
reset
(returns to
adjust a
setting
screen)
Max Humidification Setpoint
Range is 15 to 45
Default is 45, inc:1
set−to
5a
45
5b
cancelsave
Figure 14. Adjust a non−communicating device settingHUMIDIFIER
Adjust a setting... Configure Humiditrol® or Auxiliary Dehumidifier
system devices
System
Air Conditioner
Furnace
Thermostat
Humiditrol
System
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min Dehumidification Setpoint
Select one
Maximum OvercoolingMidpoint Overcooling
Minimum Overcooling
Humiditrol Comfort Adjust
3a
3b
Humiditrol Comfort Adjust settings are
only available on units equipped with
a Humiditrol
See Page 18 for description of Min/
Mid/Max overcooling.
®
dehumidification device.
To adjust a setting,
highlight it,
then press Edit
System
1a
Dehumidification Control Mode
current value:
Midpoint Overcooling
2a
System
Staged Delay TImers
cancelsave
2nd Stage Delay
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min Dehumidification Setpoint
OD/Humid Boundary
Outdoor Temperature Reading Calibr
9:39 am Aug 15, 2012
back
1b
2b
about
resetAll
edit
reinstall
reset
edit
Pre−adjustment REQUIREMENTS:
1. In the system devices" list, use the arrows (1a) to highlight System. Press
2. Humiditrol® onlyIn the System" list, use the arrows (2a) to highlight
3. Humiditrol® onlyTouch one of the radio buttons (3a) to select the over-
4. Use arrows (4a) to highlight Min Dehumidification Setpoint; press edit
5. Use arrows (5a) to make changes; press save (5b). (After saving, check
6. Press the back button to return to Adjust a setting..." screen.
Dehumidification Control Mode
current value:
45
4a4b
Figure 15. Adjust a non−communicating device settingDEHUMIDIFIER
1st, the device has been installed (see Page 12).
2nd, from the Add or Remove Non−communicating equipment?", press next.
3rd, in the Adjust a setting..." screen, configure the device as follows:
edit (1b).
Humiditrol Comfort Adjust. The current value defaults to Maximum Over-
cooling. Press edit (2b).
cooling level; press save (3b). (After saving, check that the current value
now shows the new selection).
(4b). Note the current value (e.g. 45).
that the current value now shows the new selection).
Min Dehumidification Setpoint
Range is 40 to 60
Default is 45, inc:1
set−to
42
5b
5a
cancelsave
6
back
edit
reset
(returns to
adjust a
setting
screen)
506920−01 09/12
Page 16
Adjust a setting... Configure Dehumidification (no dehumidifying device installed)
(skip if default Basic" dehumidification mode is desired)
Pre−adjustment REQUIREMENTS:
System Devices
System
Furnace
Thermostat
2 Stage AC Unit
Power (120VAC) Humidifier
System
2nd Stage Differential
Staged Delay Timers
2nd Stage Delay
Dehumidification Control Mode
Humidification Control Mode
OK/Humid Boundary
Outdoor Temperature Reading
Select one
Display OnlyBasic
Precision
Dehumidification Control Mode
3a
3b
To adjust a setting, highlight it,
then press Edit
System
1a
Dehumidification Control Mode
current value:
Display Only
2a
cancelsave
about
1b
edit
reinstall
back
next
2b
edit
System
Staged Delay Timers
back
Balance Point Control
Dehumidification Control Mode
Humidification Control Mode
Auto Changeover − Humidif. Deadband
Max Humidification Setpoint
Min Dehumidification Setpoint
OK/Humid Boundary
Outdoor Temperature Reading
reset
1st, NO physical dehumidification device has been installed.
2nd, configure the thermostat for dehumidification as follows:
1. In the system devices" list, use the arrows (1a) to highlight System.
Press edit (1b).
2. In the System" list, use the arrows (2a) to highlight DehumidificationControl Mode. The current value defaults to Display Only. Press edit
(2b).
3. Touch one of the radio buttons (3a) to select the mode of dehumidification
control; press save (3b).
4. Use arrows (4a) to highlight any red colored text in the list (e.g. select Min
Dehumidification Setpoint). Press edit (4b).
5. Use arrows (5a) to make changes; press save (5b). Change other red
settings (e.g. Auto Changeover − Humidif. Deadband) using a similar
process.
6. Press the back button to return to Adjust a setting..." screen.
NOTE − If the defaults are correct, you do not have to make any changes, but you
must press save (5b). When all red text is gone, the back button will appear; press it
to return to the Add or Remove Non−communicating equipment?" screen.
Dehumidification Control Mode
current value:
Precision
4a
please view and save all
red settings
6
back
4b
edit
reset
Min Dehumidification Setpoint
Range is 40 to 60
Default is 45, inc:1
set−to
45
5b
5a
cancelsave
9:39 am Aug 15, 2012
Figure 16. Adjust dehumidification when not using Humiditrol or an auxiliary dehumidifier
Humidification and Dehumidification Modeshow they work
HUMIDIFICATION modes
BASIC & PRECISIONThese modes allow user control of RH between 15
and 45%. These conditions must be met for either mode to operate:
humidification mode has been enabled, and
the unit is in HEAT mode, and
humidification demand exists (24V present at H), and
BASIC mode also requires presence of heating demand [Y for HP
heat, or W for gas heat (W may be energized with G de−energized)].
DEW POINT(Available only if Wi−Fi is operational or outdoor sensor is attached)
Basic Dew Point ControlBasic Dew Point Control adjustment mode will
change the humidification setpoint based on the outdoor temperature and a
user−defined dew point adjustment setting.
Precision Dew Point ControlPrecision Dew Point Control adjustment
mode will operate when these conditions are met:
humidification mode has been enabled, and
the unit is in HEAT mode, and
humidification demand exists (24V present at H).
DEHUMIDIFICATION modes
NOTE − Basic and Precision dehumidification modes are functions of the
HVAC system with NO external dehumidification devices installed. Humiditrol and Auxiliary Dehumidifiers do not use these modes.
In BASIC mode, dehumidification occurs if these conditions are met and sig-
nals are present at specific terminals:
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, and
dehumidification demand exists (RH above setpoint), and
cooling demand exists (Y1 energized).
506920−01 09/12
Page 18
In PRECISION mode, dehumidification occurs if all BASIC conditions are
true, except cooling demand may or may not be present. Also note that:
Maximum overcool from cooling setpoint is 2ºF.
Deadband temperature is limited to a minimum of 5ºF (instead of 3ºF
in BASIC or DISPLAY ONLY mode) because of 2ºF overcooling.
Humiditrol® or Auxiliary Dehumidifier mode requires:
NOTE − Systems using icomfortt and a dehumidifier − Dehum" jumper on
furnace/air handler control does not need to be cut when using with a icomfortWi-Fit thermostat.
Wi−Fi is operational or outdoor sensor is installed and set up
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, (or if in AUTO, at least one thermostat cool-
ing call made prior to the dehumidification demand), and
a dehumidification demand exists (RH above setpoint), and
outdoor temp. below 95°F; indoor temp. above 65°F, and
for HUMIDITROL, adjust Humiditrol® comfort parameters as follows:
MIN adj. − Indoor temp > 2°F below cooling setpoint
Auxiliary Dehumidifier (stand alone dehumidifier)
When this option is selected, dehumidification will be allowed under the following conditions, provided there is NO call for humidification:
In the absence of heating or cooling calls, or
Simultaneous with blower only calls.
If the blower is required to operate while the auxiliary dehumidifier is running,
a separate wire must be installed from the auxiliary dehumidifier to the indoor
unit’s G thermostat input that will energize G when the auxiliary dehumidifier
is running (see wiring diagram on Page 61).
Auxiliary dehumidification is controlled by the thermostat dehumidification
demand.
NOTE − Refer to HCWH Dehumidifier Installation Instructions for installation
recommendations.
Use the Tests / Diagnostics features
NOTE − Test mode lasts for 30 minutes (with the temperature updating every
30 seconds) except for the defrost test, which lasts 30 seconds. Tests feature provides the technician time to manually verify the equipment operation.
The tests feature is available after setup has been completed once. After
you press next in the final setup screen, the select tests to run" screen (figure 18) will appear. (If you want you may skip tests; press skip tests.)
If you re−select the tests button from the full option screen (figure 17), a message to press Start button below to begin system testing" appears. Press
start. The resulting screen will be identical to figure 18.
testsalertssetup
press start button below to begin system testing
9:39 am Aug 15, 2012
equipmentdiagnostics
start
back
EXIT
Figure 17. Start testing screen
To run all of the tests, press select all. All boxes in the list of tests will be
checked. Or, touch box(es) next to test(s) to run certain tests.
After the tests have been started, the screen will describe which test is running and shows a diagnostic summary of each test (see figure 19). After reviewing the results and concluding that no further tests are needed, press
next to proceed to next test. The technician must verify that the test procedure is producing the desired result at the equipment.
select tests to run
Blower
HP Heat − 1st Stage
HP Heat − 2nd Stage
Cooling − 1st Stage
Cooling − 2nd Stage
Dehumidification
Gas Heat − Minimum Rate
Gas Heat − Maximum Rate
Humidification
9:39 am Aug 15, 2012
select all
deselect all
Figure 18. Select tests to run screen
equipment
current test: Blower
Heating Rate
Blower CFM Demand
Blower Off Delay
Blower On Delay
Indoor Blower RPM
Indoor Blower Power
Flame Current
Flame Sense
Outdoor Temperature
After pressing next after the final test, the Testing finished" screen will appear (figure 20). At this point, use the EXIT button (if you have completed the
required setup), or use diagnostics button (to analyze the system), or use
equipment button (if you wish to make any changes to device details).
equipmentdiagnosticstestsalertssetup
The Testing Process is finished
press ’tests’ button to run more tests
press ’EXIT’ button to start normal operation
Set up Equipment parameters
Press equipment to set up equipment parameters and edit details of devices in the system without having to re−run the setup program. When the
press start..." screen (figure 21A) appears, press start. The Equipment pa-
rameters" screen (figure 21B) will open. You may view information about or
modify communicating devices as described earlier in the setup pages, beginning on page 14. Use the arrows to select a device and press edit.
Use the arrows to highlight a setting and then press edit (figure 22A). In the
example, the low heating airflow is changed from the default (400) to 325 (figure 22B). After changing, press save. (note the current value has changed;
figure 22C). Some changes may affect other settings and, if so, those affected will appear in red and require changing/saving to clear the red settings.
equipmentdiagnosticstestsalertssetup
press start button below to edit details of devices in the system
start
9:39 am Aug 15, 2012
EXIT
Figure 20. Testing finished screen
Equipment, Alerts, Diagnostics
Press equipment if you need to set up equipment parameters and edit details of devices in the system (see Page 20).
Press alerts if you need to run to see any alerts that may present or to view
alerts that have been cleared (see Page 22).
Press diagnostics if you need to run to analyze the system (see Page 21).
506920−01 09/12
Page 20
equipmenttestssetup
system devices
System
Heat Pump
Furnace
Thermostat
Humiditrol
9:39 am Aug 15, 2012
To adjust a setting,
highlight it, then
press Edit
Furnace
Figure 21. Equipment parameters screen
back
EXIT
about
resetAll
edit
next
system devices
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
system devices
Continuous Indoor Blower Airflow
Equipment Name
Heating Indoor Blower OFF Delay
Heating Airflow Control Type
Low Heating Airflow
9:39 am Aug 15, 2012
High Heating Airflow
High Cooling Airflow
Airflow Profile − Cooling
High HP Airflow
Continuous Indoor Blower Airflow
Heating Indoor Blower OFF Delay
9:39 am Aug 15, 2012
Low Heating Airflow
Range is 325 to 450
Default is 400, inc: 25
set−to
325
Figure 22. Edit equipment details
equipmenttestssetup
current value:
equipmenttestssetup
cancelsave
Low Heating Airflow
400
Low Heating Airflow
back
current value:
325
back
edit
resetAll
edit
resetAll
When finished, press back; equipment parameters screen (figure 21B re-
turns); then press next. Select tests to run screen appears" (Page 19); either run tests as before or press skip tests.
The Testing process screen" (see figure 20) again appears; use the EXIT
button (if you have completed the required setup), or use diagnostics button (to analyze the system; see Page 21), or use equipment button again (if
you want to make any further changes to device details).
Table 3 on (on Page 37) shows a list of Editable Parameters for the currently
available devices designed to communicate in this system. Other devices
and additional parameters may be added at a later time. Check the unit
installation manuals (i.e. furnace, air handler, heat pump, ac unit) for current
information and default parameters.
Run Diagnostics
NOTE − To run diagnostics and insure the system works properly, the system
should be runningset the thermostat so that it will initiate a demand for
cooling, heating, dehumidification, humidification, or continuous fan operation.
If you need to run diagnostics to analyze the system, press the diagnostics
button. The select a device" list (figure 23A) will open.
Use the arrow buttons to scroll through the list of items found on the left of the
screen. The right side of the screen shows which item is selected. Use start
to begin the process. A waiting" message displays while the diagnostics are
being conducted, followed by a screen similar to figure 23B.
Use the arrow buttons to scroll through the information and take note of any
found to be out of operating range.
Press done when finished with the information. Select another device to
diagnose or use EXIT (to close and go to user Home screen) if finished.
equipmentdiagnosticstestsalertssetup
select a device:
Heat Pump
Furnace
current selection:
Furnace
start
DIAGNOSTICS
Furnace
Heating Rate40.0%
9:39 am Aug 15, 2012
Blower CFM Demand250 CFM
Blower Off DelayOff
Blower On DelayOff
Indoor Blower RPMwaiting
Indoor Blower Powerwaiting
Flame Currentwaiting
Flame Sensewaiting
Outdoor Temperature88.0ºF
9:39 am Aug 15, 2012
EXIT
done
Figure 23. Select device and run diagnostics
View and clear Installer Alerts
NOTE − Service alerts remind users to service filters, humidifier pad, UV light and
PureAirt Air Purification system and are not shown in the installer’s menu.
From the user’s home screen, press and hold the Lennox" logo in the bottom
right corner of the thermostat to access the installer program. Press yes
when asked if you want to proceed. The installer screen opens at the system and device alerts" screen (figure 24A).
The left side of the "system and device alerts" screen shows a list of each
communicating device discovered in the system and check boxes for selecting each device. Or, you may use buttons to the right of the System Devices
list to select all (or deselect all). After something has been selected; useview active to list all active alerts for selected devices. If there are no alerts,
the display will show There are no new alerts that require service". If there
are alerts, these are stored for recall but only one alert will appear in the box
at a time (see figure 24B). Use the next button to advance through all the
alerts. If only one alert is present, the next button will not appear.
Alerts may pop up on the screen during setup. Details of all active alerts can
only be accessed through the installer’s screens. To view all alerts present at
any time, press the alerts button. System setup / Diagnostics is complete"
(figure 24B) appears; close it and the Select devices to view alerts screen
(figure 24A) appears.
Use view cleared alerts to list previously active alerts that were cleared by
the device or installer. Until at least one alert has been cleared by the device
or the installer, the message There are no new alerts that require service"
will be displayed.
The first alert will be displayed in the alert screen (figure 24B), in order of:
1. red alert icon
2. yellow alert icon (service)
A red alert icon identifies a system or device issue that can prevent the system from working properly or at all, and if allowed to run, could cause damage to the system. The issue raised by the alert must be addressed and
corrected before clearing the alert!
Press clear (figure 24B) to clear a red alert. The alert will be stored in the
cleared alerts" file. If an alert cannot be cleared, revisit the alert issue and
make repairs accordingly.
506920−01 09/12
Page 22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.