Lennox XC15, XC15-024, XC15-030, XC15-036, XC15-042 Installation Instructions Manual

...
Page 1
INSTALLATION
E2008 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
INSTRUCTIONS
Dave Lennox Signature Collection XC15 Units
AIR CONDITIONER
506044−01 06/08 Supersedes 04/08
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
XC15 Outdoor Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions and Parts Arrangement 2. . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . .
Removing Existing Outdoor Unit 5. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 5. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 7. . . . . . . . . . . . . . . . .
New or Replacement Line Set 8. . . . . . . . . . . . . . . . . . .
Brazing Line Set Connections 9. . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 11. . . . . . . . . . .
Flushing System 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 13. . . . . . . .
Testing for Leaks 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 15. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 15. . . . . . . . . . .
Electrical Connection 15. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 16. . . . . . . . . . . . . . .
System Operation 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lennox System Operation Monitor (LSOM) 20. . . . . . .
Maintenance 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound Reduction Cover and Assembly Procedure 23. .
Homeowner Information 23. . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 24. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 24. . . . . . . . . . . . .
Shipping and Packing List
®
Litho U.S.A.
This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
IMPORTANT
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
06/08 506044−01
*2P0608* *P506044-01*
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled outdoor unit. 1  Bag Assembly
S 1  Bushing (for low voltage wiring S 2  Isolation grommets for liquid and suction
lines.
ISOLATION GROMMETS (2)
Figure 1. Bag Assembly (Parts)
Page 1
BUSHING (1)
Page 2
Unit Dimensions − Inches (mm) and Parts Arrangement
39.40" (1003)
UNIT SUPPORT FEET
16−7/8
(429)
8−3/4 (222)
3−1/8
(79)
DISCHARGE AIR
SIDE VIEW
30−3/4
(781)
SUCTION LINE INLET
LIQUID LINE INLET
26−7/8
(683)
3−3/4 (95)
4−5/8 (117)
ELECTRICAL
INLETS
[−024] 41 (1040)
[−030 THROUGH −060]
47 (1194)
CONTACTOR
SYSTEM OPERATION
SUCTION VALVE AND
MONITOR
RUN CAPACITOR
DISCHARGE LINE
MUFFLER
GAUGE PORT
SUCTION LINE
LOW PRESSURE
SWITCH
FILTER DRIER
18.60" (470)
8.00" (203)
1 (25)
35.50" (902)
ACCESS VIEW
OUTDOOR FAN
COMPRESSOR AND SOUND REDUCTION COVER
COMPRESSOR TERMINAL PLUG
HIGH PRESSURE SWITCH
BASE WITH ELONGATED LEGS
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
506044−01 06/08
Page 2
XC15 PARTS ARRANGEMENT
VIBRATION ISOLATOR SLEEVE LOCATIONS ON −024, −030 AND
−036.
NOTE: ON THE −042, ALL THREE VIBRATION ISOLATOR SLEEVES ARE LOCATED ON THE HORIZONTAL SECTION OF THE DISCHARGE LINE.
DO NOT REMOVED THE THREE VIBRATION ISOLATOR SLEEVES (IF
PRESENT) FROM THE COMPRESSOR DISCHARGE LINE
Figure 1. Discharge Line Vibration Isolators
Page 3
XC15 Outdoor Unit
The XC15 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox XC15 Engineering Handbook.
This outdoor unit is designed for use in systems that use thermal expansion valve (TXV) refrigerant metering devices.
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings. See figure 4 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and suction line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each service valve is equipped with a service port which has a factory−installed valve stem.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 2. Cap Tightening Distances
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
SERVICE PORT CAP
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
FRONT-SEATED
CORE
VALVE STEM
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 3. Angle−Type Service Valve
(Font−Seated Closed)
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 2.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
Page 3
XC15 SERIES
Page 4
OUTDOOR UNIT
(Uncased Coil Shown)
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HFC−410A
DRUM
HIGH
FILTER
DRIER
LIQUID LINE
SERVICE VALVE
COMPRESSOR
Figure 4. Typical Manifold Gauge Connection Setup
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 5. Angle−Type Service Valve
(Back−Seated Opened)
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Tighten finger tight and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 2.
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
OUTDOOR
COIL
SUCTION LINE SERVICE VALVE
TXV
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 2.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized to wrench turn an additional 1/12 turn clockwise as illustrated in figure 2.
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE
PORT
SERVICE
PORT CORE
SERVICE PORT
TO OUTDOOR UNIT
CAP
Figure 6. Ball−Type Service Valve
TO INDOOR UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM
CAP
506044−01 06/08
Page 4
Page 5
Recovering Refrigerant from Existing System
Remove existing HCFC−22 refrigerant using one of the following methods:
METHOD 1:
Use this method if the existing outdoor unit is not equipped with manual shut−off valves, and plan on using existing HCFC−22 refrigerant to flush the system.
NOTE − Use recovery machine instructions for specific setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
MANIFOLD GAUGES
allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
NOTE − It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
Figure 7. Typical Refrigerant Recovery
(Method 1)
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
S Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor OFF.
S Compressor can stop pumping due to tripped internal
pressure relief valve.
S Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
S Disconnect line set at the service valves. S Disconnect electrical service at the disconnect switch. S Remove old outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 8 for mandatory installation clearance requirements.
CONTROL PANEL ACCESS LOCATION
*
Page 5
*
*
* SEE NOTES ON NEXT PAGE FOR FURTHER DETAILS.
Figure 8. Installation Clearances
*
XC15 SERIES
Page 6
NOTES:
S Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
S Clearance to one of the other three sides must be 36
in. (914 mm)
.
S Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
S 48 in. (1219 mm) clearance required on top of unit. S A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
Figure 10. Slab Mounting at Ground Level
NOTE − If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
INSTALL UNIT
AWAY FROM
WINDOWS
TWO 90° ELBOWS INSTALLED IN
LINE SET WILL REDUCE LINE SET
VIBRATION.
Figure 9. Outside Unit Placement
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 9.
PLACING OUTDOOR UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 10.
NOTE − Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per
1.5 m]) away from building structure.
ELEVATING THE UNIT
Unlike the small−base units which use round support feet, the larger−base units are outfitted with elongated support feet as illustrated in figure 11 which uses a similar method for elevating the unit.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
BASE
LEG DETAIL
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
Figure 11. Elevated Slab Mounting using
Feet Extenders (Larger Base Units)
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
506044−01 06/08
Page 6
Page 7
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in figure 12 using conventional
practices; replace the panels after installation is complete.
Slab Side Mounting
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
COIL
BASE PAN
CORNER POST
Removing and Installing Panels
ACCESS PANEL
Remove and reinstall access panel as shown in figure 13.
REMOVE 4 SCREWS TO REMOVE PANEL FOR ACCESSING COMPRESSOR AND CONTROLS.
INSTALL BY POSITIONING PANEL WITH HOLES ALIGNED; INSTALL SCREWS AND TIGHTEN.
Figure 13. Access Panel
CAUTION
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
STABILITY
MINIMUM 1 PER SIDE
Deck Top
Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
FOR EXTRA
Figure 12. Installing Stabilizer Brackets
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
ROOF MOUNTING
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
INSTALLING ISOLATION GROMMETS
Locate the isolation grommets (provided). Slide grommets onto suction and liquid lines. Insert grommets into mullion to isolate refrigerant lines from sheet metal edges.
REMOVING PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 14.
NOTE − Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 14, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 14, detail A.
Page 7
XC15 SERIES
Page 8
INSTALLING PANEL
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters.
IPANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
HOLES
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 14, details A and C, then upward into the top slot of the hinge corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
5. When panel is correctly positioned and aligned, insert the screws and tighten.
DETAIL A
DETAIL B
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
DETAIL C
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
Figure 14. Removing/Installing Louvered
Panels (Details A, B and C)
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE
TOO EXTREME
PREFERRED ANGLE
FOR INSTALLATION
DETAIL D
HOLD DOOR FIRMLY TO THE HINGED B SIDE TO MAINTAIN FULLY−ENGAGED TABS
Figure 15. Removing/Installing Louvered
Panels (Detail D)
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set are not being installed then proceed to Brazing Connections on page 9.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in table 2.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
IMPORTANT
Matching XC15 with a New Indoor Coil and Line SetIf installing a new indoor coil and reusing the existing line set that included a RFCI liquid line (small bore liquid line used as a metering device) then you must change to a standard size liquid line.
NOTE − When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
S Model (XC15) and size of unit (e.g. −060).
Install the louvered panels as follows:
1. Position the panel almost parallel with the unit as illustrated in figure 15, detail D with the screw side as close to the unit as possible.
506044−01 06/08
S Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S Number of elbows and if there is a rise or drop of the
piping.
Page 8
Page 9
Table 2. Refrigerant Line Set
Model
−024
−030
−036
−042
−048
−060
Field Connections
Liquid Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor Line
3/4 in.
(19 mm)
7/8 in
(22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid Line
3/8 in
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor Line
3/4 in.
(19 mm)
7/8in
(22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 − 50 ft. (5 − 15 m)
L15−65 15 − 50 ft. (5 − 15m)
Field
Fabricated
If the XC15 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XC15 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set isolation:
S Installation of line set on horizontal runs is
illustrated in figure 16.
S Installation of a transition from horizontal to
vertical is illustrated in figure 17.
S Installation of line set on vertical runs is illustrated in
figure 18.
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
8 FEET
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
WIRE TIE (AROUND SUCTION LINE ONLY)
TAPE OR
WIRE TIE
AUTOMOTIVE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN ARMAFLEX
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER
WALL STUD
METAL SLEEVE
MUFFLER-TYPE HANGER
Figure 17. Refrigerant Line Set: Transition
from Vertical to Horizontal
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
OUTSIDE
WALL
CAULK
PVC PIPE FIBERGLASS INSULATION
SUCTION LINE
SLEEVE
SUCTION LINE WRAPPED WITH ARMAFLEX
LIQUID LINE
IMPORTANT! REFRIGERANT LINES MUST NOT CONTACT
STRUCTURE.
Figure 18. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown)
Brazing Line Set Connections
LIQUID
LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
Figure 16. Refrigerant Line Set: Installing
Horizontal Runs
Use the following procedure to braze the line set to the new air conditioner unit. Figure 19 on page 10 is provided as a general guide for preparing to braze the line set to the air conditioner unit.
Page 9
XC15 SERIES
Page 10
1
2
3
CUT AND DEBUR
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS AFTER
THEY HAVE COOLED.
INDOOR UNIT
6
BRAZE LINE SET
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT
POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
Figure 19. Brazing Connections
BRAZING CONNECTION PROCEDURE
Before brazing, remove the access panel as illustrated in figure 13; then remove the narrow piping panel to prevent burning off the paint as illustrated in figure 20.
ATTACH
GAUGES
SERVICE
5
VALVE
SERVICE
VALVE
OUTDOOR
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
LINE SET
CONNECTION
POINTS.
REMOVE 2 SCREWS AND REMOVE PANEL BEFORE BRAZING.
PIPING PANEL
Figure 20. Piping Panel Removal
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon HFC−410A sticker.
506044−01 06/08
Page 10
Page 11
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
NOTE − The TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow.
IMPORTANT
Repeat procedure starting at paragraph 4 for brazing the suction line to service port valve.
7. After all connections have been brazed, disconnect manifold gauge set the from service ports and remove wrapping. Reinstall the service port core for both of the outdoor unit’s service valves.
Removing Indoor Unit Metering Device
Remove the existing HCFC−22 fixed orifice or TXV from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46 (LB−95325A). The kit includes:
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
BRASS NUTS (10)
Figure 21. 69J46 Kit Components
LIQUID LINE
ASSEMBLY
PISTON RETAINER
STRAINER
COPPER TUBE
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
VALVE STEM
VALVE STEM CAP
(Uncased Coil Shown)
REMOVE AND DISCARD FIXED ORIFICE
VALVE STEM ASSEMBLY
(IF PRESENT)
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
Figure 22. Typical Fixed Orifice Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon ring as illustrated in figure 22.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
TYPICAL TXV REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in figure 23.
5. Disconnect the liquid line from the TXV at the liquid line assembly.
Page 11
XC15 SERIES
Page 12
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
SENSING
BULB
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE
Figure 23. Typical TXV Removal
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 23.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Flushing the System
(Uncased Coil Shown)
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
If the original system used:
S HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
S HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − The inverted HCFC−22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
Figure 24. Typical Flushing Connection
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
GAUGE
PRESSURE
HIGH
CLOSED
CAUTION
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.
Failure to properly flush the system per the instructions below will void the warranty.
506044−01 06/08
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
S Two clean HCFC−22 recovery bottles, S Oilless recovery machine with pump-down feature, S Two gauge sets (one for HCFC−22; one for
HFC−410A).
PROCEDURE
1. Connect the following:
S HCFC−22 cylinder with clean refrigerant to the
suction service valve,
S HCFC−22 gauge set to the liquid line valve, S Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
Page 12
Page 13
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 suction is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
6. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor unit coil before removing the recovery machine, gauges and refrigerant drum.
Installing New Indoor Unit Metering Device
XC15 units are designed with HFC−410A TXV metering devices. This section provides instructions on installing TXV refrigerant metering device.
9
10
8
11
1/8 TURN
12
1
2
3
10
9
4
7
5
6
12
11
8
7
6
1/2 TURN
1
2
3
4
5
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the TXV in a manner that will provide access for field servicing of the TXV. Refer to Figure 27 for reference during installation of TXV unit.
To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.
2. Install one of the provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
3. Attach the stubbed end of the TXV to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 25, or 20 ft−lb.
4. Place the remaining Teflon ring around the other end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB END
TXV
TEFLON
RING
Figure 25. Tightening Distance
XC15 ENGINEERING HANDBOOK
See the XC15 Engineering Handbook for approved indoor/outdoor match−ups, applicable TXV kits and application information.
The following is the typical contents of a TXV kit:
TXV (1)
HEX HEAD BOLTS
AND NUTS (2)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 26. TXV Kit Components
TEFLON
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE FIGURE 29 FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 28 FOR BULB POSITIONING.
EQUALIZER LINE
RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION LINE
SENSING
LINE
LIQUID
LINE
Figure 27. Typical TXV Installation
5. Attach the liquid line assembly to the TXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 25, or 20 ft−lb.
Page 13
XC15 SERIES
Page 14
6. Attach the suction line sensing bulb in the proper orientation as illustrated in figure 28 using the clamp and screws provided.
NOTE − Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
SUCTION LINE
BULB
SUCTION LINE
BULB
12
12
BULB
BULB
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
NOTE − NEVER MOUNT ON BOTTOM OF LINE.
Figure 28. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 29.
IMPORTANT
FLARE SEAL
CAP
OR
MALE BRASS EQUALIZER
Figure 29. Copper Flare Seal Bonnet Removal
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in figure 25.
Testing for Leaks
After the line set has been connected to both the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
506044−01 06/08
FLARE NUT
COPPER
FLARE SEAL
BONNET
LINE FITTING
SUCTION LINE
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
NOTE − Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
NOTE − Amounts of refrigerant will vary with line lengths.
7. Check all joints for leaks.
8. Purge dry nitrogen and HFC−410A mixture.
9. Correct any leaks and recheck.
Page 14
Page 15
10. After leak testing disconnect gauges from service ports.
Evacuating the System
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
1. Connect manifold gauge set to the service valve ports as follows:
S low pressure gauge to suction line service valve S high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE − During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
10. Close manifold gauge valves and shut off the HFC−410A cylinder and remove the manifold gauge set.
Servicing Unit Delivered Void of Charge
If the system is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Electrical Connections
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring.
2. Ground unit at unit disconnect switch or to an earth ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
NOTE − 24VAC, Class II circuit connections are made in the low voltage junction box. See figure 30 for field wiring diagram.
Page 15
XC15 SERIES
Page 16
NOTE − A COMPLETE UNIT WIRING DIAGRAM IS LOCATED INSIDE THE UNIT CONTROL BOX COVER.
Figure 30. Typical Wiring Diagram
NOTE − See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent)
NOTE − For proper voltages, select thermostat wire gauge per the following chart:
Table 3. Wire Run Lengths
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
color−coded, temperature rating 35ºC minimum
3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated in figure 30.
5. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain separation of field installed low and high voltage circuits.
Start−Up and Charging Procedures
3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System on page 17.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in figure 4.
D low pressure gauge to suction line service port.
D high pressure gauge to liquid line service port.
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
506044−01 06/08
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process
as illustration in figure 31.
DETERMINING CHARGE METHOD
To determine the correct charging method, use the illustration in figure 32.
Page 16
Page 17
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
DRY
BULB
C
53º
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
Drop
19º
All temperatures are
expressed in ºF
Figure 31. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
DT
air flowair flow
INDOOR COIL
1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between the measured T
B
A
72º
B
64º
WET
BULB
DRY
BULB
justment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
) = A minus C.
Drop
and the desired DT (T
Drop
DT = ºF ACTION
Drop
DT) is within +3º, no ad-
START: Determine the correct charge method:
TXV
65ºF
(18.3ºC) and
Above
APPROACH OR
64ºF
(17.7ºC) and
Below
WEIGH-IN
SUBCOOLING
Figure 32. Determining Charge Method
START: Measure outdoor ambient temperature
USE EITHER APPROACH
OR SUBCOOLING
METHOD
ABOVE
WHEN TO CHARGE?
S Warm weather best S Can charge in colder weather
CHARGE METHOD? Determine by:
S Outdoor ambient temperature
REQUIREMENTS:
S Sufficient heat load in structure S Indoor temperature between 70-80ºF (21−26ºC) S Manifold gauge set connected to unit S Thermometers:
to measure outdoor ambient temperature
to measure liquid line temperature
to measure suction line temperature
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 5,
BELOW
Above or
below 65ºF
(18ºC)?
Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
WEIGH IN
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Figure 33. Using Weigh In TXV Method
Page 17
XC15 SERIES
Page 18
START: Measure outdoor ambient temperature
DO NOT CHARGE UNIT
USE WEIGH-IN METHOD
(Results of charging at low
Weigh-in or remove refriger-
temperatures not reliable)
ant based upon line length
If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove refrigerant.
BELOW
Ambient 65ºF
If refrigerant added or removed, retest to confirm that unit is properly charged
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
Models
ºF (ºC)* −024 −030 −036 −042 −048 −060. . . . . .
Any 8 (4.4) 13 (7.2) 13 (7.2) 15 (8.3) 6 (3.3) 10 (5.6). . *Temperature of air entering outdoor coil
Figure 34. Using Approach TXV Method
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
If refrigerant added or removed, verify charge using the approach method
If value is greater than shown, remove refrigerant; if less than shown, add refrigerant
BELOW
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
Ambient 65ºF
Outdoor
(18ºC)?
Outdoor
(18ºC)?
ABOVE
ABOVE
1. Confirm proper airflow across coil using figure
31.
2. Compare unit pressures with Table 5, Normal Operating Pressures.
3. Use APPROACH to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).
5. Connect gauge set.
6. When heat demand is satisfied, set thermostat to call for cooling.
7. Allow temperatures and pressures to stabilize.
8. Record outdoor ambient temperature:
AMBº =_________
9. Record line temp:
LIQº = __________
10. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
11. Compare results with table to the left.
1. Confirm proper airflow across coil using figure
31.
2. Compare unit pressures with Table 5, Normal Operating Pressures.
3. Use SUBCOOLING to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
5. Connect gauge set
6. Measure outdoor ambient temperature
7. When heat demand is satisfied, set thermostat to call for cooling
8. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.
9. Record liquid line temp:
LIQº = ______
10. Measure liquid line pressure and use the value to determine saturation temperature (see table 4):
SATº = ______
11. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
12. Compare results with table to the left.
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
Models
ºF (ºC)* −024 −030 −036 −042 −048 −060. . . . . .
Any 7 (3.9.) 4 (2.2) 5 (2.8) 7 (3.9) 6 (3.3) 7 (3.9). . . *Temperature of air entering outdoor coil
Figure 35. Using Subcooling TXV Method
506044−01 06/08
Page 18
Page 19
Table 4. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0 33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3 34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1 35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9 36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8 37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8 38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8 39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8 40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0 41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1 42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4 43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7 44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1 45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5 46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Table 5. Normal Operating Pressures (Liquid +10 and Suction +5 psig)
Use this table to perform maintenance checks; it is not a procedure for charg­ing the system. Minor variations in these pressures may be due to differences
IMPORTANT
in installations. Significant deviations could mean that the system is not prop­erly charged or that a problem exists with some component in the system.
Model −024 −030 −036 −042 −048 −060
°F (°C)** Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction
65 (18.3) 238 139 246 138 251 133 261 144 224 129 242 131 70 (21.1) 256 139 265 139 270 134 281 145 241 130 262 132 75 (23.9) 275 140 287 140 291 134 303 146 259 131 282 134 80 (26.7) 296 141 307 141 312 134 326 147 279 133 303 135 85 (29.4) 319 142 330 142 335 136 350 148 301 134 326 136 90 (32.2) 342 142 354 143 359 137 376 149 323 135 349 137
95 (35.0) 366 143 379 144 384 138 402 150 347 137 372 138 100 (37.8) 392 144 404 144 411 140 430 151 372 138 397 140 105 (40.6) 418 146 432 145 438 141 459 152 397 140 422 141 110 (43.3) 448 146 461 147 468 143 490 153 422 141 448 143 115 (46.1) 480 147 491 148 501 144 525 154 449 143 475 146
* These are typical pressures only. Indoor match up, indoor air quality, and indoor load will cause the pressures to vary. ** Temperature of air entering outdoor coil.
INSTALLING SERVICE VALVE CAPS
Disconnect gauge set and re−install both the liquid and suction service valve caps.
OUTDOOR UNIT
SERVICE VALVE
INSTALL CAPS
Figure 36. Installing Service Valve Port Caps
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
HIGH PRESSURE SWITCH
XC15 units are equipped with a high-pressure switch that is located in the liquid line of the compressor as illustrated
in Unit Dimensions on page 2.
The switch is a Single Pole, Single Throw (SPST), manual−reset switch which is normally closed and removes power from the compressor when discharge pressure rises above factory setting at 590 + 10 psi. The manual−reset switch can be identified by a red cap that is press to reset the module.
LOW PRESSURE SWITCH
XC15 units are equipped with a low pressure switch that is located in the suction line to the compressor as illustrated in Unit Dimensions on page 2. The switch is a Single Pole, Single Throw (SPST), auto−reset switch that is normal closed. The switch opens at 40 psi and closes at 90 psi.
FILTER DRIER
A drier is factory−installed in each XC15 unit as illustrated in Unit Dimensions on page 2. A replacement drier is available from Lennox. Refer to Lennox Repair Part Program.
Page 19
XC15 SERIES
Page 20
Lennox System Operation Monitor (LSOM) (100034−2)
The diagnostic indicator detects the most common fault conditions in the air conditioning system. When an abnormal condition is detected, the module communicates the specific condition through its ALERT and TRIP lights. The module is capable of detecting both mechanical and electrical system problems.
RUN
COMMON
START
IMPORTANT
This monitor does not provide safety protection. The is a monitoring device only and cannot control or shut down other devices.
LSOMLED FUNCTIONS
The LSOM LED functions are described in the following table. Refer to table 8 for the complete explanation of troubleshooting codes.
Table 6. LED Functions
Label
Power Green
Alert Yellow
Trip Red
RESETTING ALERT CODES
Alert codes can be reset manually or automatically:
Manual Reset
Cycle the 24VAC power to LSOM off and on. After power up, existing code will display for 60 seconds and then clear. Manual reset can be achieve by any of the following methods:
S Disconnecting R wire from the LSOM’s R terminal.
S Turning the indoor unit off an on again.
Automatic Reset
After an alert is detected, the LSOM continues to monitor the compressor and system. When/if conditions return to normal, the alert code is turned off automatically.
COMPRESSOR WIRE ROUTING
The scroll compressor’s run R, common C, and start S wires are factory routed through the holes in the LSOM marked R, C, and S as illustrated in figure 37. The common C wire need not be routed through the module for it to operate properly.
LED
Color
Function
Indicates voltage within the range of 19−28VAC is present at the system monitor power connection.
Communicates an abnormal system condition through a unique flash code. The alert LED flashes a number of times consecutively; then pauses; then repeats the process. This consecutive flashing correlates to a particular abnormal condition.
Indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module.
Figure 37. Compressor Wire Routing
(Factory Installed)
TERMINAL CONNECTIONS
This section address terminal connections and their purpose.
Power (R and C Terminals)
LSOM requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat. The module can not be powered by the C terminal, defrost board or other control board without experiencing nuisance alerts.
When constant 24VAC (R wire) is not present in the outdoor unit, use one of the spare wires in the thermostat cable to bring power to the module. Connect the other end of the spare wire to R at the indoor unit or thermostat.
Thermostat Demand Wiring (Y Terminal)
LSOM requires a thermostat demand signal to operate properly. The thermostat demand signal input terminal, labeled Y on the module, should always be connected to the compressor contactor coil so that when the coil is energized, the demand signal input is 24VAC. When thermostat demand is not present, Y should be less than
0.5VAC.
Alert Communication (L Terminal) (Optional)
The L terminal is used to communicate alert codes to the room thermostat. On selected Lennox Comfort Sense, Elite and Merit thermostats there is an L terminal for direct input from the LSOM. See specific thermostat user guide on how alerts are displayed.
Data Port Terminal
The data port terminal is for future use and has not been implemented at this time.
INSTALLATION VERIFICATION
To verify correct LSOM installation, perform the two following functional tests:
Function Test 1
1. Disconnect power from the compressor.
2. Force a thermostat call for cooling.
3. The red LED should turn on indicating a compressor
trip as long as 24VAC is measured at the Y terminal. If the red LED does not function as described, refer to table 7 to verify the wiring.
Function Test 2
1. Disconnect power from the compressor and 24VAC power from LSOM.
2. Remove the wire from the Y terminal of LSOM and reapply power to the compressor, allowing the
506044−01 06/08
Page 20
Page 21
compressor to run. The yellow LED will begin flashing a code 8 indicating a welded contactor.
3. Disconnect power from the compressor and 24VAC power from the LSOM. While the LSOM is off, reattach the wire to the Y terminal.
Table 7. LSOM Module LED Troubleshooting Codes
Status LED Condition
Mis−wired Module Indication
4. Reapply power to the compressor and 24VAC power to the LSOM; the yellow LED will flash the previous code for 60 seconds and then turn off. If the yellow LED does not function as described, refer to table 7 to verify the wiring.
Status LED Troubleshooting Information
Green LED ON Module not powering up.
Green LED Intermittent
Red LED ON
Red and Yellow LED Simultaneous flashing.
Module powers up only when compressor runs.
LED is on but system and compressor check OK.
Table 8. LSOM System LED Troubleshooting Codes
Status LED Condition
Red LED ON
Yellow Flash Code 1
Yellow Flash Code 2
Status LED Description Status LED Troubleshooting Information
Thermostat demand signal Y1 is present, but compressor not running
Long Run Time − Compressor is running extremely long run cycles.
System Pressure Trip − Discharge or suction pressure out of limits or compressor overloaded
Determine/verify that both R and C module terminals are connected and voltage is present at both terminals.
Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have a constant source.
1
Verify Y terminal is connected to 24VAC at contactor coil.
2
Verify voltage at contactor coil falls below 0.5VAC when off.
3
Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed.
Indicates that the control circuit voltage is too low for operation. Verify R and C terminals are supplied with 19−28VAC.
1
Compressor protector is open.
S Check for high head pressure S Check compressor supply voltage
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low or high pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
S Check blower relay coil and contacts S Check blower motor capacitor S Check blower motor for failure or blockage S Check evaporator blower wiring and connectors S Check indoor blower control board S Check thermostat wiring for open circuit
3
Evaporator coil is frozen.
S Check for low suction pressure S Check for excessively low thermostat setting S Check evaporator airflow (coil blockages or return air filter) S Check ductwork or registers for blockage.
4
Faulty metering device.
S Check TXV bulb installation (size, location and contact) S Check if TXV is stuck closed or defective
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning
S Check thermostat sub−base or wiring for short circuit S Check thermostat installation (location and level)
1
High head pressure.
S Check high pressure switch if present in system S Check if system is overcharged with refrigerant S Check for non−condensable in system
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
S Check fan capacitor S Check fan wiring and connectors S Check fan motor for failure or blockage
4
Return air duct has substantial leakage.
.
.
.
Page 21
XC15 SERIES
Page 22
Status LED Condition
Yellow Flash Code 3
Yellow Flash Code 4 Locked Rotor
Yellow Flash Code 5 Open Circuit
Yellow Flash Code 6
Yellow Flash Code 7
Yellow Flash Code 8
Yellow Flash Code 9
Short Cycling − Compressor is
running only briefly
Open Start Circuit − Current only in run circuit
Open Run Circuit − Current only in start circuit
Welded Contactor − Compressor always runs
Low Voltage − Control circuit <17VAC
Status LED Troubleshooting InformationStatus LED Description
1
Thermostat demand signal is intermittent.
2
Time delay relay or control board is defective.
3
If high pressure switch is present, see Flash Code 2 information.
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
S Check wiring connections
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
S Check compressor contactor wiring and connectors S Check for compressor contactor failure (burned, pitted or open) S Check wiring and connectors between supply and compressor S Check for low pilot voltage at compressor contactor coil
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient tempera­ture.
7
Compressor windings are damaged.
S Check compressor motor winding resistance
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply and the compressor S" terminal
3
Compressor start winding is damaged.
S Check compressor motor winding resistance
1
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply and the compressor R" terminal
2
Compressor start winding is damaged.
S Check compressor motor winding resistance
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at disconnect is low).
S Check wiring connections
NOTE − Last code will display for 1 minute when power is cycled to module. Power must be on to module for a minimum of 1 minute for code to clear.
Maintenance
At the beginning of each cooling season, check the system as follows:
NOTE − Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Ensure the power is turned off before you clean the coil.
2. Check connecting lines and coils for signs of oil leaks.
3. Check wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp−draw outdoor fan motor:
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
UNIT NAMEPLATE: _________ ACTUAL: __________
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked.
INDOOR COIL
1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.
Page 22
506044−01 06/08
Page 23
INDOOR UNIT
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. Check blower for accumulation of dirt or debris.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor:
UNIT NAMEPLATE: _________ ACTUAL: __________
Sound Reduction (SR1) Cover
ASSEMBLY PROCEDURE
Figure 38 identifies the sound reduction parts. Assembly procedures are as follows:
1. Put SR1 base on unit base pan.
2. Install compressor on base.
3. Cover SR1 base with wet rags to protect against any brazing material.
4. Braze suction tube.
5. Braze discharge tube.
6. Cool connections to ambient temperature.
7. Perform leak check.
8. Install suction grommet.
9. Install SR1 left and right side covers.
10. Fasten 60" bottom cable tie.
11. Install discharge grommet.
12. Install top caps.
13. Fasten 36" top cable tie.
14. Fasten 36" middle cable tie.
TOP CABLE TIE
LEFT TOP CAP
MIDDLE CABLE
GROMMET
LEFT SIDE COVER
SUCTION
TIE
BASE
BOTTOM CABLE
TIE
COVER
Figure 38. Sound Reduction Cover Parts
RIGHT
SIDE
DISCHARGE GROMMET
RIGHT TOP CAP
Homeowner Information
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
MAINTENANCE
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit. When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with
Page 23
XC15 SERIES
Page 24
metal edges and corners while applying excessive force or rapid motion can result in personal injury. Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system.
THERMOSTAT OPERATION
Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user’s information manual provided with your thermostat for specific operation details.
Temperature Setting LeversSet the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit offthen back onbefore pressures can equalize will put unusual stress on the unit’s compressor.
Fan Switch In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.
System Switch Set the system switch for heating,
cooling or auto operation. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.
Temperature Indicator The temperature indicator displays the actual room temperature.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day set points for both heating and cooling. Refer to the user’s information manual provided with your thermostat for operation details.
PRESERVICE CHECK
If your system fails to operate, check the following before calling for service:
S Make sure all electrical disconnect switches are ON. S Make sure the room thermostat temperature selector
AND the system switch are properly set.
S Replace any blown fuses, or reset circuit breakers. S Make sure unit access panels are in place. S Make sure air filter is clean. S Locate and record unit model number before calling.
Optional Accessories
Refer to the Lennox XC15 Engineering Handbook for the latest available optional accessories for this unit.
XC15 Start−Up and Performance Checklist
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
Rated Load Amps Actual Amps Rated Volts Actual Volts
Condenser Fan Full Load Amps Actual Amps:
COOLING MODE
Suction Pressure: Liquid Pressure:
Supply Air Temperature: Ambient Temperature: Return Air: Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F) A B = COIL TEMP DROP
Return Air Temperature (A)
minus Supply Air Temperature (B)
A B = SUBCOOLING
A B = APPROACH
506044−01 06/08
Page 24
Loading...