Lennox XC15, XC15-024, XC15-030, XC15-036, XC15-042 Installation Instructions Manual

...
Page 1
INSTALLATION
E2006 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with R−22 must be flu­shed.
XC15 Outdoor Unit
XC15 outdoor units use R−410A refrigerant. This unit must be installed with a matching indoor coil and line set as out­lined in the Lennox Engineering Handbook. XC15 outdoor units are designed for use in expansion valve (TXV) sys­tems only. Refer to the Lennox Engineering Handbook for expansion valve kits which must be ordered separately.
INSTRUCTIONS
XC15 Series Units
CONDENSING UNITS
505,095M 01/06
Table of Contents
XC15 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping And Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Unit 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Panels 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set and Indoor Coil 9. . . . . . . . . .
Refrigerant Metering Device 10. . . . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 11. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−up 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Charging 13. . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 18. . . . . . . . . . . . . . . . . . . . . . . . . . .
XC15 Start−Up and Performance Check List 19. . . . . . . .
Homeowner’s Information − Maintenance 19. . . . . . . . . .
Thermostat Operation 20. . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound Reduction Cover & Assembly Procedure 20. . . .
General Information
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners, and for port and valve caps.
Litho U.S.A.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Shipping and Packing List
1 − Assembled XC15 outdoor unit 1 − Bushing (for low voltage wiring) 2 − Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
01/06 505,095M
*2P0106* *P505095M*
Table 1
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #8 16 in.− lb. 2 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities having jurisdiction before installation.
Page 1
Page 2
Unit Dimensions − inches (mm) and Parts Arrangement
TOP VIEW
39−1/2 (1003)
18
(457)
DISCHARGE AIR
9−1/4 (234)
13−1/2
(343)
10−1/2
(267)
CONTACTOR
SYSTEM OPERA-
TION MONITOR
RUN CAPACITOR
DISCHARGE LINE
VAPOR VALVE AND
GAUGE PORT
VAPOR LINE
LOW PRESSURE
SWITCH
FILTER DRIER
ELECTRICAL
INLETS
37 (940)
[−024 thru −042]
47 (1194)
[−048 and −060]
35−1/2
(902)
OUTDOOR FAN
COMPRESSOR AND SOUND REDUCTION COVER (SEE PAGE 20 FOR COVER INFORMATION)
COMPRESSOR TERMINAL PLUG
HIGH PRESSURE SWITCH
10−3/8 (264)
SUCTION LINE INLET
LIQUID LINE INLET
SIDE VIEW ACCESS VIEW
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
4−7/16
(113)
21−1/8 (537)
[−024 thru −042]
31−1/8 (791)
[−048 and −060]
18−5/8
(473)
8 (203)
1 (25)
Figure 1
Refer to unit dimensions for sizing mounting slab, plat­forms or supports. Refer to figure 2 for installation clear­ances.
Service Panel Clearance
A service clearance of 30" (762 mm) must be maintained on the access panel side of the unit (see figure 2).
505095M 1/3/06
Page 2
Page 3
Installation Clearances
(as noted)
(as noted)
30 in. (762−mm)
*A service clearance of 30" (762 mm) must be maintained on the access panel side of the unit. Clearance to one of the oth­er three sides must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
A clearance of 24" (610 mm) must be maintained between two units. 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
(as noted)
Figure 2
Roof Mounting
Install unit at a minimum of 4 inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either red­wood or steel supports are recommended.
Removing Panels
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Slab Mounting
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit. See figure
3. Slab may be level or have a slope tolerance away from the building of not more than 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm).
Slab Mounting At Ground Level
BUILDING STRUCTURE
MOUNTING SLAB
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [51 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
Figure 3
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause dam­age to objects or structures nearby, nor will the pan­els be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and bat­tered.
Access Panel
WARNING
Unit must be grounded in accordance with national and local codes. Elec­tric Shock Hazard. Can cause injury or death.
Line voltage is present at all compo­nents when unit is not in operation on units with single-pole contactors. Dis­connect all remote electric power sup­plies before opening access panel. Unit may have multiple power sup­plies.
Page 3
XC15 SERIES
Page 4
Remove and reinstall the access panel as described in fig­ure 4.
Access Panel
Removing/Installing Louvered Panels
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
Panel shown slightly ro­tated to allow top tab to exit (or enter) top slot for removing (or installing) panel.
Remove 4 screws to remove panel for accessing compressor and controls.
Install by positioning panel with holes aligned; install screws and tighten.
Figure 4
Louvered Panels
CAUTION
Physical contact with metal edges and corners can result in personal injury. Be aware of, and use cau­tion when working with panels.
Remove the louvered panels as follows:
1. Remove 2 screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinge corner post until lower 3 tabs clear the slots (see figure 5, De­tail B).
3. Move panel down until lip of upper tab clears the top slot in corner post (see figure 5, Detail A).
Position and Install PanelPosition the panel almost parallel with the unit (figure 5, Detail D) with the screw side" as close to the unit as possible. Then, in a continuous motion:
S Slightly rotate and guide the LIP of top tab inward (fig-
ure 5, Details A and C); then upward into the top slot of the hinge corner post.
S Rotate panel to vertical to fully engage all tabs. S Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw holes.
When panel is correctly positioned and aligned, insert the screws and tighten.
LIP
SCREW HOLES
Detail A
Detail B
Detail C
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail D
Figure 5
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
505095M 1/3/06
Page 4
Page 5
Refer to the furnace or blower coil installation instructions
color coded, temperature
for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
1. Install line voltage power supply to unit from a properly sized disconnect switch. See figure 6.
Typical Field Wiring Diagram
GND
L1 L2
208−230/60/1
READ
WARNING AND
NOTE
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
Figure 6
2. Ground unit at unit disconnect switch or to earth ground.
3. Connect conduit to the unit via the bottom hole using a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors. 24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 7 for field wiring diagram. A complete unit wiring dia­gram is located on the back side of the access panel.
NOTE − For proper voltages, select thermostat wire gauge per the following chart:
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
color−coded, temperature rating 35ºC minimum
4. Install room thermostat (ordered separately) on an in­side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
5. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figure 7.
6. LSOM L Terminal WiringConnect L terminal of the room thermostat to the L (Brown) field wire connec­tion.
7. LSOM Installation VerificationVerification proce­dures are described in System Operation under Sys­tem Operation Monitor (see Page 16).
NOTE − Wiring the module incorrectly will cause false LED codes. Table 8 (see page 17) describes LED op­eration when the module is incorrectly wired and the action required to correct the problem.
Typical Wiring Diagram
Figure 7
Page 5
XC15 SERIES
Page 6
Refrigerant Piping
If the XC15 unit is being installed with an indoor coil and line set, make the refrigerant connections as outlined in this section. f an existing line set and/or indoor coil is going to be used to complete the XC15 system, refer to this section, as well as the flushing section which follows.
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non− flare) series line sets as shown in table 2 or use field−fabri­cated refrigerant lines. Valve sizes are also listed in table 2.
Table 2
Refrigerant Line Sets
Valve Sizes Recommended Line Set
Liquid
Model
−024
−030
−036
−042
−048
−060 3/8 in.
Line
3/8 in. (10 mm)
3/8 in. (10 mm)
(10 mm)
Vapor Line
3/4 in. (19 mm)
7/8 in (22 mm)
1−1/8 in. (29 mm)
Liquid Line
3/8 in (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in. (19 mm)
7/8in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41 15 − 50 ft. (5 − 15 m)
L15−65 15 − 50 ft. (5 − 15m)
Field Fabricated
1. PlacementSome localities are adopting sound ordi-
nances based on the unit’s noise level registered from the adjacent property, not from the installation proper­ty. Install the unit as far as possible from the property line. When possible, do not install the unit directly out­side a window. Glass has a very high level of sound transmission (see figure 8).
Outside Unit Placement and Installation
Install unit
away from
windows
Two 90° elbows installed in line set will reduce line set vibration.
NOTE − When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
S Line set diameters for the unit being installed (from
table 2)
S Model (XC15) and size of unit (e.g. −060).
IMPORTANT
Matching XC15 with new Indoor Coil and Line SetIf an existing indoor coil equipped with an RFCI metering device is being replaced, also install a new liquid line prior to installing the XC15 unit.
Installing Refrigerant Line
If refrigerant lines are routed through a wall, seal and iso­late the opening so vibration is not transmitted to the build­ing. Pay close attention to line set isolation during installa­tion of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent noises. Also, consider the following when placing and installing a high−efficiency outdoor unit:
Figure 8
2. Line Set IsolationThe following illustrations dem-
onstrate procedures which ensure proper refrigerant line set isolation. Figure 10 shows how to install line sets on horizontal runs. Figure 11 shows how to make a transition from horizontal to vertical. Figure 12 shows how to install line sets on vertical runs.
Installing Isolation Grommets
Locate the isolation grommets (provided). Slide grommets onto vapor and liquid lines. Insert grommets into mullion to isolate refrigerant lines from sheet metal edges.
WARNING
Polyol ester (POE) oils used with R−410A refriger­ant absorb moisture very quickly. It is very impor­tant that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
505095M 1/3/06
Page 6
Page 7
Brazing Connection Procedure
Before brazing, remove the access panel (see figure 4); then remove the narrow piping panel to prevent burning off the paint (see figure 9).
Piping Panel Removal
Remove 2 screws and re­move panel before brazing.
PIPING
Line set
connection
points.
PANEL
Figure 9
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. When making line set connections, use 1 to 2 psig dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system.
3. Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing) which are rated for use with R−410A refriger­ant. While brazing-in the line set connections, wrap a wet cloth around the valve body and the copper tube stubs.
4. Quench the joints with a wet cloth to prevent possible heat damage to the valve core and opening port.
NOTE − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, seal­ing and rigidity.
5. Install the thermal expansion valve in the liquid line at the indoor coil.
NOTE − Expansion valve (not provided; obtain sepa­rately) must be approved for use with R−410A refriger­ant.
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
STRAPPING MATERIAL (Around vapor line only)
TAPE OR WIRE TIE
Refrigerant Line Sets: Installing Horizontal Runs
WIRE TIE (Around vapor line only)
8 feet
FLOOR JOIST OR ROOF RAFTER
TAPE OR WIRE TIE
8 feet
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
METAL SLEEVE
FLOOR JOIST OR ROOF RAFTER
Figure 10
Page 7
XC15 SERIES
Page 8
ANCHORED
HEAVY NYLON
WIRE TIE
Refrigerant Line Sets: Transition From Vertical To Horizontal
AUTOMOTIVE
MUFFLER-TYPE
HANGER
WALL STUD
METAL
SLEEVE
Strap Liquid Line To Va­por Line
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
WALL STUD
METAL
SLEEVE
Strap Liquid Line To Vapor Line
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
Figure 11
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE − Similar installation practices should be used if line set is to be installed on exterior of outside wall.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
IMPORTANT - Refrigerant lines must not contact wall.
LIQUID LINEVAPOR LINE
WIRE TIE
INSIDE WALL
IMPORTANT! Refrigerant lines must not contact structure.
505095M 1/3/06
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE WALL
PVC PIPE
FIBERGLASS
INSULATION
LIQUID
LINE
CAULK
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
SLEEVE
Figure 12
Page 8
Page 9
Flushing Existing Line Set & Indoor Coil
Flushing Procedure
WARNING
Danger of fire. Bleeding the refriger­ant charge from only the high side may result in the low side shell and suction tubing being pressurized. Ap­plication of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before un­brazing.
CAUTION
This procedure should not be performed on sys­tems which contain contaminants (Example: com­pressor burn out).
IMPORTANT
If this unit is being matched with an approved line set or indoor coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to instal­lation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with R−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat trans­fer. It can also clog the expansion device, and re­duce the system performance and capacity. Failure to properly flush the system per the in­structions below will void the warranty.
Required Equipment
Equipment required to flush the existing line set and indoor coil:
S two clean R−22 recovery bottles, S oil−less recovery machine with pump-down feature, S 2 gauge sets (one for R−22; one for R−410A).
IMPORTANT
The Environmental Protection Agency (EPA) pro­hibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycl­ing or reclaiming must be followed.
1. Remove existing R−22 refrigerant using the following, appropriate procedure (see figure 13):
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational AND you plan to use the existing R−22 refrigerant to flush the system −
D Disconnect all power to the existing outdoor unit. D Connect to the existing unit, a clean recovery cyl-
inder and the recovery machine according to the instructions provided with the recovery machine.
D Remove all R−22 refrigerant from the existing sys-
tem. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
D Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.
If the existing outdoor unit is equipped with manual shut−off valves AND you plan to use NEW R−22 refrigerant to flush the system
D Start the existing R−22 system in the cooling mode
and close the liquid line valve.
D Pump all of the existing R−22 refrigerant back into
the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure complete re­frigerant evacuation.)
D When the low side system pressures reach 0 psig,
close the vapor line valve.
D Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
D Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.
2. Remove the existing outdoor unit. Set the new R−410A unit and follow the brazing connection procedure (see page 7) to make line set connections.
Page 9
XC15 SERIES
Page 10
Inverted R−22 Cylinder (Contains clean R−22 to be used for flushing)
Flushing Connections
Vapor Line
EXISTING
INDOOR COIL
RECOVERY CYLINDER
EXISTING VAPOR LINE
EXISTING LIQUID LINE
Service Valve
Liquid Line Service Valve
Tank Return
Inlet
Discharge
RECOVERY MACHINE
Figure 13
3. Make low voltage and line voltage connections to the
new outdoor unit. Do NOT turn on power to unit or
open the outdoor unit service valves at this time.
4. Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush­ing procedures. Existing devices are not approved for use with R−410A refrigerant and may prevent proper flushing. Use a field−provided fitting to reconnect lines.
IMPORTANT
The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
5. Remove the pressure tap valve cores from the XC15 unit’s service valves. Connect an R−22 cylinder with clean refrigerant to the vapor service valve. Connect the R−22 gauge set to the liquid line valve. Connect a recovery machine with an empty recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex­isting system line set and indoor coil.
7. Invert the cylinder of clean R−22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
8. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that
Low
Pressure
XC15 UNIT
GAUGE MANIFOLD
NOTE − The inverted R−22 cylinder must contain at least the same amount of refrigerant as was recov­ered from the existing system.
High
Pressure
ClosedOpened
all of the R−22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the mineral oil from the existing refrigerant lines and in­door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system
is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
9. Close the valve on the inverted R−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
10. Use dry nitrogen to break the vacuum on the refriger­ant lines and indoor coil before removing the recovery machine, gauges and R−22 refrigerant drum. Reinstall pressure tap valve cores into XC15 service valves.
11. Install the expansion valve in the liquid line at the in­door coil.
Refrigerant Metering Device
XC15 units may be used in thermal expansion valve (TXV) systems only. See the indoor coil installation instructions and the Lennox Engineering Handbook for approved TXV match−ups and application information. Table 2 (on Page 6) lists liquid and vapor line sizes and correspond­ing line sets.
Expansion valves equipped with Chatleff type fittings are available from Lennox. Refer to the Engineering Hand­book for expansion valves for use with specific match−ups.
If you install an expansion valve with an indoor coil that in­cludes a fixed orifice, remove the orifice before the expan­sion valve is installed (see figure 14).
505095M 1/3/06
Page 10
Page 11
Metering Device Installation
O−RING
DISTRIBUTOR
NOTE − If necessary, remove R−22 flow control device (fixed orifice/thermal expansion valve) from existing line set before installing R−410A approved expansion valve and o−ring.
EXPANSION VALVE & O−RING (See NOTE)
STRAINER
LIQUID LINE STUB
Figure 14
IMPORTANT
Failure to remove a fixed orifice when installing an expansion valve to the indoor coil will result in im­proper operation and damage to the system.
Manifold Gauge Set
Manifold gauge sets used with systems charged with R−410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
To Open Front-Seated Service Valves:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap. Tighten finger tight, then tighten according to torque specifications table (page 1).
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly.
3. Replace the stem cap. Tighten finger tight, then tighten according to torque specifications table (page 1).
Front-Seated Liquid Line Service Valve
SCHRADER
VALV E
[open to line set
when valve is
closed (front
seated)]
(VALVE front-
seated)
To
indoor
coil
SERVICE PORT CAP
SERVICE PORT
(Valve Shown Closed)
Insert hex wrench here
STEM CAP
Service Valves
The liquid line and vapor line service valves (figures 15 and
16) and gauge ports are used for leak testing, evacuating, charging and checking charge. See table 1 (on page 1) for torque requirements.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap. Tighten finger tight, then tighten an additional 1/6 turn.
SERVICE PORT CAP
SERVICE
PORT
To indoor coil
To outdoor coil
SCHRADER VALV E
(Valve Shown Open)
insert hex wrench here
STEM CAP
To outdoor coil
Figure 15
Page 11
XC15 SERIES
Page 12
Vapor Line (Ball Type) Service Valve
Vapor line service valves function the same way as the oth­er valves; the difference is in the construction. These valves are not rebuildable. If a valve fails, replace it. The ball valve (shown in figure 16) is equipped with a service port with a factory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak−free seal.
Ball−Type Vapor Line Valve (Valve Closed)
To indoor coil
Use Adjustable Wrench To close: rotate Stem Counter-clockwise 90°. To open: rotate Stem Clockwise 90°.
SERVICE
PORT
SCHRADER
VALV E
SERVICE
PORT CAP
To outdoor coil
BALL (Shown closed)
STEM
STEM CAP
Figure 16
Leak Test with Electronic Leak Detector
1. Connect an R−410A manifold gauge set high pressure hose to the vapor valve service port. (Normally, the
high pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.)
2. With both manifold valves closed, connect the cylinder of R−410A refrigerant to the center port of the manifold gauge set. Open the valve on the R−410A cylinder (va­por only).
3. Open the high pressure side of the manifold to allow R−410A into the line set and indoor unit. Weigh in a trace amount of R−410A. [A trace amount is a maxi-
mum of 2 ounces (57 g) refrigerant or 3 pounds (31 kPa) pressure]. Close the valve on the R−410A cylin-
der and the valve on the high pressure side of the man­ifold gauge set. Disconnect the R−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure reg­ulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge dry nitrogen and R−410A mixture. Correct any leaks and recheck.
IMPORTANT
Leak Testing
After the line set has been connected to the indoor and out­door units, check the line set connections and indoor unit for leaks.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger­ant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Danger of explosion: Can cause inju­ry or death, or equipment damage.
Never use oxygen to pressurize a re­frigeration or air conditioning system. Oxygen will explode on contact with oil and could cause personal injury.
When using a high pressure gas such as dry nitrogen to pressurize a refrig­eration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to
13.8 kPa).
505095M 1/3/06
Leak detector must be capable of sensing HFC re­frigerant.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 23,000 microns.
1. Connect manifold gauge set to the service valve ports as follows:
D low pressure gauge to vapor line service valve D high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercu-
Page 12
Page 13
ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage. Avoid deep vacu­um operation. Do not use compressors to evacu­ate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void war­ranty.
7. Shut off the dry nitrogen cylinder and remove the man­ifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vac­uum pump and connect it to an upright cylinder of R−410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R−410A cylinder and remove the manifold gauge set.
Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to pre­vent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and vapor line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on pow­er to the indoor blower and close the outdoor unit dis­connect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
Refrigerant Charging
This system is charged with R−410A refrigerant which op­erates at much higher pressures than R−22. The provided liquid line filter drier is approved for use with R−410A. Do not replace it with components designed for use with R−22. This unit is NOT approved for use with coils which use cap- illary tubes as a refrigerant metering device.
Factory Charge
Units are factory charged with the amount of R−410A re­frigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 ft. (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment.
Table 3
Refrigerant Charge per Line Set Lengths
Liquid Line Set Diameter
3/8 in. (9.5mm) 3 ounces per 5 feet (85 grams per 1.52 meter)
*Add the amount shown if line length is greater than 15’ (4.57m), sub­tract the amount shown if less than 15’.
Ounces per 5 feet (grams per 1.52 meter) adjust from 15 ft. (4.57m) line set*
IMPORTANT
Mineral oils are not compatible with R−410A. If oil must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol ester oil for approved line set lengths.
Units Delivered Void of Charge
If the system is void of refrigerant, clean the system us­ing the procedure described below.
1. Use dry nitrogen to pressurize the system and check for leaks. Repair leaks, if possible.
2. Evacuate the system to remove as much of the mois­ture as possible.
3. Use dry nitrogen to break the vacuum and install a new filter drier in the liquid line.
4. Evacuate the system again. Then, weigh the appropri­ate amount of R−410A refrigerant (listed on unit name­plate) into the system.
Page 13
XC15 SERIES
Page 14
IMPORTANT
Charge adjustments may be required to allow for longer line sets and coil volumes. Check for proper charge using charging information in this manual.
5. Monitor the system to determine the amount of mois­ture remaining in the oil. Use test kit 10N46 to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If
system dryness is not verified, the compressor will fail in the future.
Checking Charge
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter­mined by the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1. Connect the manifold gauge set to the service valves:
D low pressure gauge to vapor valve service port D high pressure gauge to liquid valve service port
Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R−410A .
2. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
3. Record outdoor ambient temperature using a digital thermometer.
4. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68ºF (20ºC). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5. The outdoor temperature will determine which charg­ing method to use. Proceed with the appropriate charging procedure.
Charge Using Weigh-in MethodOutdoor Temper-
ature < 65ºF (18ºC)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit.
1. Recover the refrigerant from the unit.
2. Conduct leak check; evacuate as previously outlined.
3. Weigh in the unit nameplate charge. If weighing facili­ties are not available or if charging the unit during warm weather, use one of the following procedures.
Charge Using the Approach MethodOutdoor
Temp. >65ºF (18ºC)
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best re­sults, outdoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital thermometer.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in table 5, Normal Operating Pressures." Minor varia­tions in these pressures may be expected due to differ­ences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Con­tinue to check adjusted charge using approach values.
4. Use the same digital thermometer you used to check the outdoor ambient temperature to check the liquid line temperature.
5. The difference between the ambient and liquid tem­peratures should match values given in table 4. If the values do not agree with the those in table 4, add re­frigerant to lower the approach temperature, or recov­er refrigerant from the system to increase the ap­proach temperature.
Table 4
XC15 Approach Values
_ Liquid Line Temperature
_ Outdoor Temperature
= _ Approach Temperature
Model −024 −030 −036 −042 −048 −060
°F (°C)*
NOTE − For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures.
*F: +/−1.0°; C: +/−0.5°
10
(5.6)12(6.7)11(6.1)13(7.2)6(3.3)10(5.6)
NOTES −
S R−410A refrigerant cylinders are rose−colored. Refrig-
erant should be added through the vapor valve in the liquid state.
S Certain R−410A cylinders are identified as being
equipped with a dip tube. These allow liquid refrigerant to be drawn from the bottom of the cylinder without in­verting the cylinder. DO NOT turn this type cylinder up­side−down to draw refrigerant.
505095M 1/3/06
Page 14
Page 15
Table 5
XC15 Normal Operating Pressures In psig (liquid +/− 10 and vapor+/− 5 PSIG)*
Model
5F (5C)** Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction
65 (18.3) 239 135 246 135 245 132 260 132 224 129 242 131
70 (21.1) 255 136 266 136 264 133 282 133 241 130 262 132
75 (23.9) 274 137 285 138 285 135 302 134 259 131 282 134
80 (26.7) 293 138 306 139 306 137 325 135 279 133 303 135
85 (29.4) 317 139 328 140 328 137 347 136 301 134 326 136
90 (32.2) 339 140 350 141 352 139 370 137 323 135 349 137
95 (35.0) 362 141 374 142 375 140 395 138 347 137 372 138
100 (37.8) 387 142 399 143 400 141 421 139 372 138 397 140
105 (40.6) 415 144 423 144 425 141 446 141 397 140 422 141
110 (43.3) 440 145 450 145 452 143 475 142 422 141 448 143
115 (46.1) 469 146 477 146 476 144 504 144 449 143 475 146
* These are typical pressures only. Indoor match up, indoor air quality, and indoor load will cause the pressures to vary.
** Temperature of air entering outdoor coil.
−024 −030 −036 −042 −048 −060
Charge Using Subcooling MethodOutdoor Tem-
perature > 65ºF (18ºC)
Use the following method to obtain accurate subcooling values. Compare the measured subcooling value to the values given in table 6.
Table 6
XC15 Subcooling Values
(psig ) _ Saturation Temperature
_ Liquid Line Temperature
= _ Subcooling Value
Model −024 −030 −036 −042 −048 −060
°F
(°C)*
NOTE − For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures.
*F: +/−1.0°; C: +/−0.5°
1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital ther­mometer to record the liquid line temperature in the space provided in table 6, and at the same time, record the liquid line pressure reading in the (psig___)" space in the table.
2. Use a temperature/pressure chart for R−410A (table 7) to determine the saturation temperature for the liq­uid line pressure reading and record that in the space provided in table 6.
4
(2.2)4(2.2)6(3.3)7(3.9)6(3.3)7(3.9)
3. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine the subcooling value.
4. Compare subcooling value with those in table 6. If sub­cooling is greater than shown, recover some refriger­ant; if less than shown, add some refrigerant.
Charge using Subcooling MethodOutdoor Tem-
perature < 65ºF (18ºC)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the out­door coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are nec­essary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liq­uid pressure is in the 325−375 psig (2240−2585 kPa) range. See figure 17.
Blocking Outdoor Coil
*Outdoor coil should be blocked one side at a time with cardboard or plastic sheet until proper testing pressures are reached.
cardboard or plastic sheet
*Four−sided unit shown.
Figure 17
Page 15
XC15 SERIES
Page 16
Table 7
R−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continu­ously.
High Pressure Switch
XC15 units are equipped with a high pressure switch that is located in the liquid line to the compressor. The switch is a SPST, manual−reset switch that is normal closed. The switch opens at 590 psi.
Low Pressure Switch
XC15 units are equipped with a low pressure switch that is located in the vapor line to the compressor. The switch is a SPST, auto−reset switch that is normal closed. The switch opens at 40 psi and closes at 90 psi.
Filter Drier
A drier is factory−installed in each XC15 unit. A replace­ment drier is available from Lennox. Refer to Lennox Re­pair Part Program.
System Operation Monitor (LSOM)
The diagnostic indicator detects the most common fault conditions in the air conditioning system. When an abnor­mal condition is detected, the module communicates the specific condition through its ALERT and TRIP lights. The module is capable of detecting both mechanical and elec­trical system problems. See figure 18 for the system op­eration monitor.
System Operation Monitor
POWER LED
Y
DATA OUTPUT CONNECTOR
L
R
C
ALERT LED
TRIP LED
.25" SPADE CONNECTOR (4)
Figure 18
IMPORTANT
This monitor does not provide safety protection. The monitor is a monitoring device only and cannot control or shut down other devices.
LSOMLED Functions
Power LED (green)indicates voltage within the range of
19−28VAC is present at the system monitor power connec­tion.
Alert LED (yellow)communicates an abnormal system condition through a unique Flash Code the alert LED flashes a number of times consecutively; then pauses; then repeats the process. This consecutive flashing corre­lates to a particular abnormal condition.
Trip LED (red)indicates there is a demand signal from the thermostat but no current to the compressor is de­tected by the module.
Refer to table 8 for the complete explanation of trouble­shooting codes.
Resetting alert codesAlert codes can be reset manual­ly or automatically:
S Manual reset: Cycle the 24VAC power to LSOM off
and on. After power up, existing code will display for 1 minute and then clear.
S Automatic reset: After an alert is detected, the LSOM
continues to monitor the compressor and system. When/if conditions return to normal, the alert code is turned off automatically.
LSOML terminal connection
The L connection is used to communicate alert codes to the room thermostat. On selected Lennox SignatureStatt thermostats, a blinking check" LED will display on the room thermostat and on select White-Rodgers room ther­mostats, an icon on the display will flash. Either will flash at the same rate as the LSOM yellow alert LED.
505095M 1/3/06
Page 16
Page 17
NOTE − ROOM THERMOSTATS WITH SERVICE OR CHECK LIGHT FEATUREThe room thermostat may blink the Check" or Service" LED or it may come on solid. Confirm fault by observing and interpreting the code from the LSOM yellow alert LED at the unit.
not function as described, refer to table 8 to verify the wir­ing. Disconnect power from the compressor and 24VAC power from LSOM. Remove the wire from the Y terminal of LSOM and reapply power to the compressor, allowing the compressor to run. The yellow alert LED will begin flashing a code 8 indicating a welded contactor. Disconnect power
LSOMInstallation verification
To verify correct LSOM installation, two functional tests can be performed. Disconnect power from the compressor and force a thermostat call for cooling. The red trip LED should turn on indicating a compressor trip as long as 24VAC is measured at the Y terminal. If the red LED does
from the compressor and 24VAC power from the LSOM. While the LSOM is off, reattach the wire to the Y terminal. Reapply power to the compressor and 24VAC power to the LSOM; the yellow alert LED will flash the previous code 8 for one minute and then turn off. If the yellow LED does not function as described, refer to table 8 to verify the wiring.
Table 8
System Operation Monitor LED Troubleshooting Codes
Status LED Condition Status LED Description Status LED Troubleshooting Information
Green Power" LED ON Module has power 24VAC control power is present at the module terminal.
Green Power" LED OFF Module not powering up Determine/verify that both R and C module terminals are connected
and voltage is present at both terminals.
Red Trip" LED ON System and compressor
check out OK
Thermostat demand signal Y1 is present, but compres­sor not running
Red Trip" & Yellow Alert" LEDs Flashing
Yellow Alert" Flash Code 1*
Simultaneous flashing. Indicates that the control circuit voltage is too low for operation.
Long Run Time − Compres­sor is running extremely long run cycles
Yellow Alert" Flash Code 2*
System Pressure Trip
Discharge or suction pres­sure out of limits or compressor overloaded
Yellow Alert" Flash Code 3*
Yellow Alert" Flash
Short Cycling − Compres-
sor is running only briefly
Locked Rotor
Code 4*
Yellow Alert" Flash
Open Circuit
Code 5*
1
Verify Y terminal is connected to 24VAC at contactor coil.
2
Verify voltage at contactor coil falls below 0.5VAC when off.
3
Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed.
1
Compressor protector is open.
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
3
Evaporator coil is frozen.
4
Faulty metering device.
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning
1
High head pressure.
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
4
Return air duct has substantial leakage.
5
If low pressure switch is present, see Flash Code 1 information.
1
Thermostat demand signal is intermittent.
2
Time delay relay or control board is defective.
3
If high pressure switch is present, see Flash Code 2 information.
4
If low pressure switch is present, see Flash Code 1 information.
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambi­ent temperature.
7
Compressor windings are damaged.
.
.
.
table continued on next page
Page 17
XC15 SERIES
Page 18
System Operation Monitor LED Troubleshooting Codes
Status LED Condition Status LED Troubleshooting InformationStatus LED Description
Yellow Alert" Flash Code 6*
Yellow Alert" Flash Code 7*
Yellow Alert" Flash Code 8*
Yellow Alert" Flash Code 9*
Open Start Circuit − Current
only in run circuit
Open Run Circuit − Current only in start circuit
Welded Contactor Com- pressor always runs
Low Voltage − Control cir­cuit <17VAC
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash code by removing 24VAC power from monitor; last code will display for 1 minute after monitor is powered on.
Last code will display for 1 minute when power is cycled to module. Power must be on to module for a minimum of 1 minute for code to clear.
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
3
Compressor start winding is damaged.
1
Open circuit in compressor start wiring or connections.
2
Compressor start winding is damaged.
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at disconnect is low).
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cool­ing season, check the system as follows:
NOTE − Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.
1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Ensure the power is turned off before you clean the coil.
2. Check connecting lines and coils for signs of oil leaks.
3. Check wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp−draw outdoor fan motor. Unit nameplate _________ Actual ____________ .
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging section (Page 13).
Indoor Coil
1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.
Indoor Unit
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. Check blower for accumulation of dirt or debris.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor Unit nameplate_________ Actual ____________.
Optional Accessories
Optional accessories for the XC15 include the following (also, see Engineering Handbook for more details):
S Timed-off control S Low ambient kit
505095M 1/3/06
Page 18
Page 19
XC15 Start−Up & Performance Check List
Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type: Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps:
COOLING MODE
Suction Pressure: Liquid Pressure:
Supply Air Temperature: Ambient Temperature: Return Air: Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required sub­cooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
A B = SUBCOOLING
A B = APPROACH
A B = COIL TEMP
DROP
Homeowner Information − Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to re­move airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the in­side air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish perfor­mance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.
Page 19
XC15 SERIES
Page 20
When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and cor­ners while applying excessive force or rapid motion can result in personal injury.
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer
System Switch
Set the system switch for heating, cooling or auto opera­tion. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.
Temperature Indicator
The temperature indicator displays the actual room temperature.
and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air con­ditioning or heat pump system.
Thermostat Operation
Thermostat operations vary from one thermostat to anoth­er. The following provides general operation procedures. Refer to the user’s information manual provided with your thermostat for specific operation details.
Temperature Setting Levers
Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit offthen back onbefore pressures can equalize will put unusual stress on the unit’s compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous in­door blower operation, regardless of whether the com­pressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.
Programmable Thermostats
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your thermostat for detailed pro­gramming and operation details.
Preservice Check
If your system fails to operate, check the following before calling for service:
S Check to see that all electrical disconnect switches are
ON.
S Make sure the room thermostat Temperature Selector
and System Switch (Heat, Cool, Auto) are properly set.
S Check for any blown fuses or tripped circuit breakers. S Make sure unit access panels are in place.
S Make sure air filter is clean.
S If service is needed, locate and write down the unit
model number and have it handy before calling.
Sound Reduction Cover (SR1) Components and Assembly Procedure
LEFT TOP CAP
MIDDLE CABLE TIE
SUCTION GROMMET
LEFT SIDE COVER
BOTTOM CABLE TIE
TOP CABLE TIE
BASE
RIGHT TOP CAP
RIGHT SIDE COVER
DISCHARGE GROMMET
This diagram identifies the sound reduction components and shows the correct procedure for assembling the sound reduction cover:
1. Put SR1 base on unit base pan.
2. Install compressor on base.
3. Cover SR1 base with wet rags to protect against any brazing material.
4. Braze suction tube.
5. Braze discharge tube.
6. Cool connections to ambient temperature.
7. Perform leak check.
8. Install suction grommet.
9. Install SR1 left and right side covers.
10. Fasten 60" bottom cable tie.
11. Install discharge grommet.
12. Install top caps.
13. Fasten 36" top cable tie.
14. Fasten 36" middle cable tie.
Figure 19
505095M 1/3/06
Page 20
Loading...