Lennox XC14, XC14-018, XC14-024, XC14-030, XC14-036 Installation Instructions Manual

...
Page 1
INSTALLATION
2008 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
This unit must be matched with an indoor coil as specified in Lennox XC14 Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
IMPORTANT
INSTRUCTIONS
Elite® Series XC14 Units
AIR CONDITIONER
505,367M 04/08 Supersedes 01/08
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
XC14 Air Conditioner Units 1. . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . .
Removing Existing Outdoor Unit 6. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 6. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 8. . . . . . . . . . . . . . . . .
New or Replacement Line Set 9. . . . . . . . . . . . . . . . . . .
Brazing Connections 11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 11. . . . . . . . . . .
Flushing System 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 13. . . . . . . .
Testing for Leaks 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 16. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Outdoor Unit Delivered Void of Charge 17. . .
Electrical Connection 17. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 18. . . . . . . . . . . . . . .
System Operation 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information 23. . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 24. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 24. . . . . . . . . . . . .
Shipping and Packing List
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled outdoor unit. 1  Refrigerant flow control kit (Fixed Orifice)
XC14 Air Conditioner Units
The XC14 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox XC14 Engineering Handbook.
This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:
Thermal expansion valve (TXV) Fixed orifice
Litho U.S.A.
04/08 505,367M
*2P0408* *P505367M*
Page 1
Page 2
Unit Dimensions − Inches (mm)
RUN
CAPACITOR
CONTACTOR
OUTDOOR FAN
COMPRESSOR (SOUND REDUCTION HOUSING NOT SHOWN)
HIGH PRESSURE SWITCH
UNIT SUPPORT
FEET
TOP VIEW
C
DISCHARGE AIR
SIDE VIEW
SUCTION LINE CONNECTION
LIQUID LINE CONNECTION
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
4.25"
(108mm)
(121mm)
4.75"
UNIT SUPPORT
FEET
DISCHARGE
LINE
FILTER DRIER/
LIQUID LINE
CONNECTIONS
PARTS ARRANGEMENT
A
2"
(51mm)
1"
(25mm)
B
SIDE VIEW
SUCTION LINE
SUCTION VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS
8.50"
(216mm)
8.75"
(222mm)
5.50"
(140mm)
13.50"
(343mm)
XC14−018 AND −024 BASE SECTIONS
9.25"
(241mm)
8.25"
(210mm)
D
E
F
G
XC14−030 TO −060 BASE WITH
K
J
H
ELONGATED LEGS
Model
018
024
030
036
042
048 39 (991) 30.50 (775) 35 (889)
060 35 (889) 35.50 (902) 39.50 (1003) 16.875 (429) 8.75 (222) 3.125 (79) 30.75 (781) 4.625 (117) 3.75 (95) 26.875 (683)
A B C D E F G H J K
31 (787) 27 (686) 28 (711)
31 (787) 30.50 (775) 35 (889)
XC14 Dimensions − in. (mm)
13.875 (352) 7.75 (197) 3.25 (83) 27.125 (689) 3.625 (92) 4.50 (114) 20.625 (524)
Page 2
505367M 04/08
Page 3
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
1/6 TURN
12
11
10
9
8
7
1
2
3
4
5
6
11
10
9
8
Figure 1. Cap Tightening Distances
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
1/12 TURN
12
1
2
3
4
7
5
6
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See figure 3 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and suction line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each service valve is equipped with a service port which has a factory−installed valve stem.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
SERVICE PORT CAP
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
FRONT-SEATED
CORE
VALVE STEM
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 2. Angle−Type Service Valve
(Font−Seated Closed)
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
Page 3
XC14 SERIES
Page 4
OUTDOOR UNIT
(Uncased Coil Shown)
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HFC−410A
DRUM
HIGH
FILTER
DRIER
LIQUID LINE
SERVICE VALVE
COMPRESSOR
Figure 3. Typical Manifold Gauge Connection Setup
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 4. Angle−Type Service Valve
(Back−Seated Opened)
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
OUTDOOR
COIL
SUCTION LINE SERVICE VALVE
TXV
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1.
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized to wrench turn an additional 1/12 turn clockwise as illustrated in figure 1.
505367M 04/08
Page 4
Page 5
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
TO INDOOR UNIT
BALL (SHOWN CLOSED)
STEM CAP
VALV E STEM
Figure 5. Ball−Type Service Valve
Recovering Refrigerant from Existing HCFC−22 System
Remove existing HCFC−22 refrigerant using one of the following methods:
METHOD 1:
Use this method if the existing outdoor unit is not equipped with manual shut−off valves, and plan on using existing HCFC−22 refrigerant to flush the system.
NOTE − Use recovery machine instructions for specific setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
MANIFOLD GAUGES
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor OFF.
Compressor can stop pumping due to tripped internal
pressure relief valve.
Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
NOTE − It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
CLEAN RECOVERY CYLINDER
Figure 6. Typical Refrigerant Recovery (Method 1)
OUTDOOR UNIT
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves. Disconnect electrical service at the disconnect switch. Remove old outdoor unit.
Page 5
XC14 SERIES
Page 6
Positioning New Outdoor Unit
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory installation clearance requirements.
*
INSTALL UNIT
AWAY FROM WIN-
DOWS
*
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
*
*
Figure 7. Installation Clearances
NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36
in. (914 mm)
.
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
48 in. (1219 mm) clearance required on top of unit. A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 8.
TWO 90° ELBOWS
INSTALLED IN LINE SET
WILL REDUCE LINE SET
VIBRATION.
Figure 8. Outside Unit Placement
PLACING OUTDOOR UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 9.
NOTE − If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
Figure 9. Slab Mounting at Ground Level
ELEVATING THE UNIT (SMALL−BASE UNITS)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done by cutting four equal true−cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 10.
505367M 04/08
Page 6
Page 7
BASE
BASE
LEG DETAIL
4" (101.6MM) SCH 40 PIPING
Figure 10. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the pre−installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1" (25.4mm) square strips should be adequate to hold the extender in place.
ELEVATING THE UNIT (LARGER−BASE UNITS)
Unlike the small−base units which use round support feet, the larger−base units are outfitted with elongated support feet as illustrated in figure 11 which uses a similar method for elevating the unit.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
LEG DETAIL
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
Figure 11. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the
brackets as illustrated in figure 12 using conventional practices; replace the panels after installation is complete.
Slab Side Mounting
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
COIL
BASE PAN
CORNER POST
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
MINIMUM 1 PER SIDE
FOR EXTRA
STABILITY
Figure 12. Installing Stabilizer Brackets
Page 7
XC14 SERIES
Page 8
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unsta­ble in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
ROOF MOUNTING
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood, steel supports, or roofed in equipment platform is recommended.
Removing and Installing Panels
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
4. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or installing) panel.
SCREW
LIP
DETAIL A
DETAIL B
HOLES
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
PANEL
Detail C
Figure 13. Removing/Installing Louvered Panels
(Details A, B and C)
REMOVING PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 13.
NOTE − Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 13, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 13, detail A.
INSTALLING PANEL
Install the louvered panels as follows:
1. Position the panel almost parallel with the unit as illustrated in figure 14, detail D with the screw side as close to the unit as possible.
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 13, details A and C, then upward into the top slot of the hinge corner post.
3. Rotate panel to vertical to fully engage all tabs.
Maintain minimum panel angle (as close to parallel with the unit as possible) while installing panel.
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Figure 14. Removing/Installing Louvered Panels
(Detail D)
5. When panel is correctly positioned and aligned, insert the screws and tighten.
505367M 04/08
Page 8
Page 9
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set are not being installed then proceed to Brazing Connections on page 11.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in table 2.
Table 2. Refrigerant Line Set
Field Connections Recommended Line Set
Model
−018
−024
−030
−036
−042
−048
−060
Liquid
Line
3/8". (10 mm)
3/8". (10 mm)
3/8". (10 mm)
Suction
Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8". (29 mm)
Liquid
Line
3/8" (10 mm)
3/8" (10 mm)
3/8" (10 mm)
Suction
Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8" (29 mm)
L15 Line Set
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the XC14 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XC14 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set isolation:
Installation of line set on horizontal runs is
illustrated in figure 15.
Installation of a transition from horizontal to
vertical is illustrated in figure 17.
Installation of line set on vertical runs is illustrated in
figure 16.
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
8 FEET
FLOOR JOIST OR
ROOF RAFTER
WIRE TIE (AROUND SUCTION LINE ONLY)
8 FEET
TAPE OR WIRE TIE
NOTE − When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (XC14) and size of unit (e.g. −060).
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
Page 9
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
Figure 15. Refrigerant Line Set: Installing
Horizontal Runs
XC14 SERIES
Page 10
IMPORTANT - REFRIGERANT LINES
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
MUST NOT CONTACT WALL.
SUCTION LINE
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
AUTOMOTIVE MUFFLER-TYPE
HANGER
STRAP LIQUID LINE TO SUCTION LINE
WOOD BLOCK
WIRE TIE
STRAP
SLEEVE
SUCTION LINE WRAPPED
WITH ARMAFLEX
LIQUID LINE
OUTSIDE
PVC
PIPE
WALL
FIBERGLASS
INSULATION
CAULK
IMPORTANT! REFRIGERANT LINES MUST NOT CONTACT
STRUCTURE.
Figure 16. Refrigerant Line Set: Installing Vertical
Runs (New Construction Shown)
1
2
METAL SLEEVE
ANCHORED HEAVY
NYLON WIRE TIE
WALL STUD
METAL SLEEVE
SUCTION LINE − WRAPPED IN ARMAFLEX
SUCTION LINE − WRAPPED IN ARMAFLEX
LIQUID LINE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
Figure 17. Refrigerant Line Set: Transition from
Vertical to Horizontal
3
CUT AND DEBUR
INDOOR UNIT
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS AFTER
THEY HAVE COOLED.
505367M 04/08
6
BRAZE LINE SET
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
GAUGES
SERVICE
5
Figure 18. Brazing Connections
Page 10
ATTACH
SERVICE
VALVE
VALVE
OUTDOOR
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
Page 11
Brazing Connections
Use the following procedure to braze the line set to the new air conditioner unit. Figure 18 on page 10 is provided as a general guide for preparing to braze the line set to the air conditioner unit.
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
NOTE − The fixed orifice or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon R−410A sticker.
IMPORTANT
Repeat procedure starting at paragraph 4 for brazing the suction line to service port valve.
7. After all connections have been brazed, disconnect manifold gauge set from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service caps if desired to close off refrigerant ports.
Removing Indoor Unit Metering Device
Remove the existing HCFC−22 fixed orifice or TXV from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46 (LB−95325A). The kit includes:
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
BRASS NUTS (10)
Figure 19. 69J46 Kit Components
LIQUID LINE
ASSEMBLY
PISTON RETAINER
STRAINER
COPPER TUBE
Page 11
XC14 SERIES
Page 12
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
ASSEMBLY
VALVE STEM
TEFLON RING
FIXED ORIFICE
VALVE STEM CAP
REMOVE AND DISCARD VALVE STEM ASSEMBLY (IF PRESENT)
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown)
Figure 20. Typical Fixed Orifice Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon ring as illustrated in figure 20.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
TYPICAL TXV REMOVAL PROCEDURE
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
LIQUID LINE
ORIFICE
HOUSING
STUB END
TEFLON RING
TXV
TEFLON
RING
SENSING
LINE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in figure 21.
5. Disconnect the liquid line from the TXV at the liquid line assembly.
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 21.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Flushing the System
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.
Failure to properly flush the system per the instructions below will void the warranty.
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
EQUALIZER LINE
SENSING
BULB
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
Figure 21. Typical TXV Removal
505367M 04/08
LIQUID
LINE
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
If the original system used:
HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
Page 12
Page 13
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − The inverted HCFC−22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
GAUGE
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
HIGH
PRESSURE
CLOSED
Figure 22. Typical Flushing Connection
6. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor unit coil before removing the recovery machine, gauges and refrigerant drum.
Installing New Indoor Unit Metering Device
XC14 units can be configured for use in with HFC−410A fixed orifice or TXV metering devices. This section provides instructions on installing either a fixed orifice or TXV refrigerant metering device.
9
10
8
11
1/8 TURN
10
8
11
12
7
6
12
1
2
3
9
4
7
5
6
1/2 TURN
1
2
3
4
5
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
Two clean HCFC−22 recovery bottles, Oilless recovery machine with pump-down feature, Two gauge sets (one for HCFC−22; one for
HFC−410A).
PROCEDURE
1. Connect the following:
HCFC−22 cylinder with clean refrigerant to the
suction service valve,
HCFC−22 gauge set to the liquid line valve, Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 suction is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
Figure 23. Tightening Distance
TYPICAL FIXED ORIFICE INSTALLATION PROCEDURE
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s liquid line orifice housing.
2. Ensure that the fixed orifice supplied with the outdoor unit is installed with the nylon seat pointing toward the distributor assembly.
3. Apply a small amount of refrigerant oil on the Teflon ring and insert the Teflon ring securely into the orifice housing.
4. Attached the liquid line assembly to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft−lb.
5. Place the supplied fixed orifice sticker on the indoor cabinet after installation.
LIQUID LINE ORIFICE HOUSING
FIXED
(Uncased
Coil Shown)
ORIFICE
LIQUID LINE ASSEMBLY
WITH BRASS NUT
TEFLON
RING
LIQUID
LINE
Figure 24. Typical Fixed Orifice Installation
Table 3 lists both the Lennox catalog and part numbers for the fixed orifice kit provided with each unit model. In non−standard applications, the provided fixed orifice kit may not be appropriate. Figure 25 illustrates the kit components and quantities.
Page 13
XC14 SERIES
Page 14
Table 3. Indoor Unit Fixed Orifice Kits
Model Catalog Number Part Number Drill Size
XC14−018 97M74 100484−06 0.053
XC14−024 97M75 100484−08 0.057
XC14−030 97M76 100484−13 0.063
XC14−036 11W02 100484−22 0.073
XC14−042 97M78 100484−24 0.076
XC14−048 11W07 100484−31 0.083
XC14−060 11W11 100484−40 0.093
Use the Lennox catalog number to order a new or replacement fixed orifice kit.
The fixed orifice kit includes the following components:
FIXED ORIFICE (1)
FIXED ORIFICE EXTRACTOR (1)
TEFLON RING (1)
FIXED ORIFICE STICKER (1)
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE FITTING (SEE FIGURE 28 FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 27 FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
TEFLON RING
SENSING
LINE
LIQUID
LINE
Figure 25. Fixed Orifice Kit Components
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the TXV in a manner that will provide access for field servicing of the TXV. Refer to Figure 26 for reference during installation of TXV unit.
To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
Figure 26. Typical TXV Installation
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.
2. Install one of the provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
3. Attach the stubbed end of the TXV to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft−lb.
4. Place the remaining Teflon ring around the other end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
5. Attach the liquid line assembly to the TXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft−lb.
505367M 04/08
Page 14
Page 15
6. Attach the suction line sensing bulb in the proper orientation as illustrated in figure 27 using the clamp and screws provided.
NOTE − Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
SUCTION LINE
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
Table 4. Indoor Unit TXV Kits
Model Catalog Number Part Number
−018, 024, 030 and 036 37L51 37L5101
−042 39L72 39L7201
−048 and 060 91M02 100188−02
Use the Lennox catalog number to order a TXV kit.
The indoor unit TXV kit includes the following components:
BULB
SUCTION LINE
BULB
NOTE − Never mount on bottom of line.
12
12
BULB
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
Figure 27. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 28.
IMPORTANT
TXV (1)
HEX HEAD BOLTS
AND NUTS (2)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 29. TXV Kit Components
Testing for Leaks
After the line set has been connected to both the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
FLARE SEAL
CAP
OR
MALE BRASS EQUALIZER
FLARE NUT
COPPER
FLARE SEAL
BONNET
LINE FITTING
SUCTION LINE
Figure 28. Copper Flare Seal Bonnet Removal
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in figure 23.
See the XC14 Engineering Handbook for approved TXV indoor/outdoor unit match−ups and application information. Table 4 lists both the Lennox catalog and part numbers for the TXV kit required for each unit model. Figure 29 illustrates the kit components and quantities.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
Page 15
XC14 SERIES
Page 16
NOTE − Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
NOTE − Amounts of refrigerant will vary with line lengths.
7. Check all joints for leaks.
8. Purge dry nitrogen and HFC−410A mixture.
9. Correct any leaks and recheck.
10. After leak testing disconnect gauges from service ports.
Evacuating the System
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
NOTE − Remove cores from service valves if not already done.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to suction line service valve high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE − During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure this indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to vacuum pump, turn pump on, and continue to evacuate line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve pressure line set to break vacuum with 2 to 5 psi.
10. Perform the following: A Close manifold gauge valves B Shut off HFC−410A cylinder C Reinstall service valve cores by removing
manifold hose from service valve. Quickly install core with core tool while maintaining a positive system pressure.
D Replace the stem caps and secure finger tight,
then tighten an additional one−sixth (1/6) of a turn as illustrated in figure 1.
505367M 04/08
Page 16
Page 17
Servicing Outdoor Unit Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Electrical Connections
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring as illustrated in figure 30.
2. Ground unit at unit disconnect switch or to an earth ground.
NOTE − To facilitate a conduit, a cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
NOTE − 24VAC, Class II circuit connections are made in the low voltage junction box as illustrated in figure 31.
NOTE − See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent)
NOTE − For proper voltages, select thermostat wire gauge per table 5.
Table 5. Wire Run Lengths
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
WIRE TIES
CONDUIT
GROMMET
Color−coded, temperature rating 35ºC minimum
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
Figure 30. Separating High/Low Voltage Field Wiring
THERMOSTAT INDOOR UNIT
W1
R
Y
G
C
POWER
HEAT
COOLING
INDOOR
BLOWER
COMMON
R
OUTDOOR UNIT
W
Y
G
C
(COMPRESSOR
CONTACTOR)
Y1
C
Figure 31. Typical Field Low Voltage Wiring
3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated in figure 31.
5. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain separation of field installed low and high voltage circuits as illustrated in figure 30.
Page 17
XC14 SERIES
Page 18
NOTE − A complete unit wiring diagram is located inside the unit control box cover.
Figure 32. Typical Wiring Diagram
Start−Up and Charging Procedures
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System on page 17.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in figure 3.
low pressure gauge to suction line service port.high pressure gauge to liquid line service port.
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process
as illustration in figure 33.
DETERMINING CHARGE METHOD
To determine the correct charging method, use the illustration in figure 34.
505367M 04/08
Page 18
Page 19
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
53º
DRY
BULB
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
C
Drop
19º
All temperatures are expressed in ºF
DT
air flowair flow
INDOOR COIL
B
B
64º
Figure 33. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
START: Determine how refrigerant is metered
WHEN TO CHARGE?
Warm weather best Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure Indoor temperature between 70-80ºF
(21−26ºC)
(18.3ºC) and
Above
Manifold gauge set connected to unit Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure suction line temperature
APPROACH OR
SUBCOOLING
Figure 34. Determining HFC−410A Charge Method
BULB
65ºF
WET
TXV
A
72º
BULB
DRY
1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between the measured T justment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
) = A minus C.
Drop
and the desired DT (T
Drop
DT = ºF ACTION
Drop
Which
DT) is within +3º, no ad-
RFC
metering
device?
64ºF
(17.7ºC) and
Below
WEIGH-IN
40ºF
(4.4ºC) and
Above
39ºF
(3.8ºC) and
Below
WEIGH-INSUPERHEAT
START: Measure outdoor ambient temperature
USE EITHER APPROACH
OR SUBCOOLING
METHOD
WEIGH IN TXV
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 35. Using HFC−410A Weigh In TXV Method
65ºF
and
ABOVE
ABOVE or
BELOW
Page 19
64ºF and
BELOW
1. Check Liquid and suction line pressures
2. Compare unit pressures with table 7, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
XC14 SERIES
Page 20
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
64ºF and
BELOW
If refrigerant is added or removed, verify charge using the Subcooling Method.
If value is LESS than shown, add refrigerant.
If value is MORE than shown, remove refrigerant.
MORE or
LESS
65ºF
and
ABOVE
ABOVE or
BELOW
1. Confirm proper airflow across coil using figure 33.
2. Compare unit pressures with table 7, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).
4. Connect gauge set.
5. When heat demand is satisfied, set thermostat to call for cooling.
6. Allow temperatures and pressures to stabilize.
7. Record outdoor ambient temperature:
AMBº =_________
8. Record liquid line temperature:
LIQº = __________
9. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
10. Compare results with table below.
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 65 (18) 4 (2.2) 5 (2.8) 4 (2.2) 5 (2.8) 6 (3.3) 7 (3.9) 8 (4.4) 75 (24) 5 (2.8) 6 (3.3) 5 (2.8) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0) 85 (29) 6 (3.3) 6 (3.3) 6 (3.3) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0) 95 (35) 5 (2.8) 7 (3.9) 6 (3.3) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0) 105 (41) 3 (1.7) 6 (3.3) 6 (3.3) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0) 115 (45) 3 (1.7) 6 (3.3) 6 (3.3) 6 (3.3) 8 (4.4) 9 (5.0) 9 (5.0) *Temperature of air entering outdoor coil
Figure 36. Using HFC−410A Approach TXV Charge Method
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
64ºF and
ABOVE or
BELOW
BELOW
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
If refrigerant is added or removed, verify charge using the Approach Method.
If value is LESS than shown, add refrigerant.
If value is MORE than shown, remove refrigerant.
MORE or
LESS
1. Confirm proper airflow across coil using figure 33.
65ºF
and
ABOVE
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 65 (18) 10 (5.6) 10 (5.6) 10 (5.6) 11 (6.1) 10 (5.6) 8 (4.4) 8 (4.4) 75 (24) 6 (3.3) 8 (4.4) 8 (4.4) 11 (6.1) 7 (3.9) 8 (4.4) 7 (3.9) 85 (29) 6 (3.3) 8 (4.4) 7 (3.9) 11 (6.1) 7 (3.9) 8 (4.4) 8 (4.4) 95 (35) 6 (3.3) 8 (4.4) 7 (3.9) 10 (5.6) 7 (3.9) 8 (4.4) 7 (3.9) 105 (41) 10 (5.6) 8 (4.4) 7 (3.9) 10 (5.6) 7 (3.9) 8 (4.4) 6 (3.3) 115 (45) 10 (5.6) 8 (4.4) 6 (3.3) 9 (5.0) 7 (3.9) 7 (3.9) 6 (3.3) *Temperature of air entering outdoor coil
2. Compare unit pressures with table 7, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
4. Connect gauge set
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat to call for cooling
7. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value to determine saturation temperature (see table 6):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
11. Compare results with table below.
Figure 37. Using HFC−410A Subcooling TXV Charge Method
505367M 04/08
Page 20
Page 21
START: Measure outdoor ambient temperature
USE SUPERHEAT
40ºF
and
ABOVE
WEIGH IN RFC
Refrigerant Charge per Line Set Length
ABOVE or
BELOW
39ºF and
BELOW
1. Check Liquid and suction line pressures
2. Compare unit pressures with table 7, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 38. Using HFC−410A Weigh In RFC Charge Method
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant based upon line length
Wet Bulb (air entering indoor coil) ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76 40 15 18 20 23 26 29 32 34 38 41 43 46 48 51 45 13 16 18 21 24 27 30 33 36 39 41 44 46 49 50 11 14 16 19 22 25 28 31 34 37 39 42 44 47 55 9 12141720232730333638404244 60 7 10121518212427303335384043 65 - 6 10 13 16 19 21 24 27 30 33 36 38 41 70 - - 7 1013161921242730333639 75 - - - 6 9 121518212428313437 80 - - - - 5 8 12 15 18 21 25 28 31 35 85 - - - - - - 8 11 15 19 22 26 30 33 90 - - - - - - 5 9 131620242731 95 - - - - - - - 6 101418222529 100 --------81216212428 105 --------5913172226
If refrigerant is added, retest to confirm that unit is properly charged.
110 ---------611152025 115 ----------8141824
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
39ºF and
BELOW
SHº (Superheat) Values (+/−5ºF)
ABOVE or
BELOW
40ºF
and
ABOVE
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
1. Confirm proper airflow across coil using figure 33.
2. Compare unit pressures with table 7, Normal Operating Pressures.
3. Use SUPERHEAT to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
5. Connect gauge set.
6. When heat demand is satisfied, set thermostat to call for cooling.
7. Allow temperatures and pressures to stabilize.
8. Measure the suction line pressure and use the use value to determine saturation temperature (table
6):
SATº =_________
9. Record suction line temperature:
VAPº =_________
10. Subtract to determine superheat (SHº):
VAPº − _____ SATº ______ = SHº______
11. Record the wet bulb temperature (air entering indoor coil):
WB =_______
12. Record outdoor ambient temperature.
13. Compare results with table to the left.
NOTE − Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5ºF at the suction line service port.
If value is LESS than shown, add refrigerant.
Figure 39. Using HFC−410A Superheat RFC Charge Method
MORE or
LESS
If value is MORE than shown, remove refrigerant.
Page 21
If refrigerant is removed, retest to confirm that unit is properly charged.
XC14 SERIES
Page 22
Table 6. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Table 7. Normal Operating Pressures (Liquid +10 and Suction +5 psig)
Use this table to perform maintenance checks; it is not a procedure for charg­ing the system. Minor variations in these pressures may be due to differences
IMPORTANT
in installations. Significant deviations could mean that the system is not prop­erly charged or that a problem exists with some component in the system.
Model −018 −024 −030 −036 −042 −048 −060
**Temp. 5F (5C)
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
*Liquid Line Pressure / Vapor Line Pressure
Expansion Valve (TXV)
65 (18) 230 / 138 233 / 138 230 / 136 240 / 137 236 / 138 238 / 136 239 / 133 70 (21) 244 / 139 250 / 138 247 / 137 259 / 138 253 / 140 256 / 138 258 / 135 75 (24) 265 / 140 271 / 140 265 / 139 278 / 139 273 / 141 277 / 139 278 / 136 80 (27) 286 / 140 291 / 141 287 / 140 299 / 139 296 / 142 299 / 140 300 / 137 85 (29) 307 / 142 313 / 143 308 / 141 321 / 140 318 / 143 320 / 139 323 / 138 90 (32) 330 / 143 335 / 143 331 / 142 344 / 141 341 / 144 343 / 140 346 / 139
95 (35) 351 / 144 361 / 145 355 / 144 368 / 142 366 / 146 369 / 141 370 / 140 100 (38) 380 / 144 384 / 146 380 / 145 393 / 143 392 / 147 395 / 142 396 / 142 105 (41) 407 / 145 412 / 147 405 / 146 419 / 144 417 / 148 422 / 144 415 / 143 110 (43) 436 / 146 436 / 148 432 / 147 446 / 145 445 / 149 450 / 146 449 / 145 115 (45) 466 / 147 468 / 149 461 / 148 477 / 146 475 / 151 481 / 148 476 / 147
Fixed Orifice (RFC)
65 (18) 232 / 124 230 / 121 231 / 123 234 / 130 248 / 135 240 / 126 244 / 125
70 (21) 248 / 127 251 / 128 249 / 127 247 / 134 266 / 138 260 / 129 263 / 128
75 (24) 267 / 131 272 / 133 270 / 132 270 / 136 285 / 141 281 / 133 281 / 131
80 (27) 286 / 135 289 / 135 291 / 136 290 / 138 305 / 143 301 / 135 303 / 134
85 (29) 307 / 138 312 / 140 314 / 140 313 / 141 327 / 145 324 / 138 324 / 136
90 (32) 328 / 141 335 / 142 337 / 142 336 / 143 349 / 147 346 / 140 347 / 139
95 (35) 351 / 143 361 / 144 359 / 144 358 / 145 372 / 149 371 / 142 370 / 141 100 (38) 375 / 146 383 / 147 383 / 146 361 / 148 396 / 150 395 / 144 394 / 143 105 (41) 400 / 148 409 / 149 408 / 147 409 / 150 421 / 152 420 / 146 418 / 145 110 (43) 426 / 150 441 / 151 433 / 149 430 / 151 447 / 153 447 / 148 444 / 146 115 (46) 457 / 153 467 / 152 467 / 151 463 / 152 476 / 154 473 / 150 471 / 147
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary. **Temperature of the air entering the outside coil.
505367M 04/08
Page 22
Page 23
INSTALLING SERVICE VALVE CAPS
Disconnect gauge set and re−install both the liquid and suction service valve caps.
OUTDOOR UNIT
SERVICE VALVE
INSTALL CAPS
Figure 40. Installing Service Valve Port Caps
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
HIGH PRESSURE SWITCH
XC14 units are equipped with a high-pressure switch that is located in the liquid line of the compressor as illustrated in Unit Dimensions on page 2. The switch is a Single Pole, Single Throw (SPST), manual−reset switch with red cap that is normally closed and removes power from the compressor when discharge pressure rises above factory setting at 590 + 10 psi.
DISCHARGE THERMOSTAT
Each XC14 unit is equipped with a discharge thermostat located in the discharge line of the compressor. The switch (SPST, auto−reset, normally closed) and removes power from the compressor when discharge temperature exceeds the factory setting of 220ºF +5ºF.
FILTER DRIER
A filter drier is factory-installed as illustrated in Unit Dimensions on page 2, with each XC14 unit to ensure a
clean, moisture−free system. A replacement filter drier is available from Lennox. Refer to Lennox Repair Part Program.
Maintenance
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
At the beginning of each cooling season, the system should be checked as follows:
1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Ensure the power is turned off before you clean the coil.
2. Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.
3. Visually inspect connecting lines and coils for evidence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at the unit (with the unit operating).
6. Check amp−draw outdoor fan motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked.
INDOOR COIL
1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.
INDOOR UNIT
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. Check blower drive belt for wear and proper tension.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
Homeowner Information
MAINTENANCE
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable FilterMany indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air CleanerSome systems are equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
Page 23
XC14 SERIES
Page 24
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit. When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system.
THERMOSTAT OPERATION
Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user’s information manual provided with your thermostat for specific operation details.
Temperature Setting Levers Set the lever or dial to
the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit offthen back onbefore pressures can equalize will put unusual stress on the unit’s compressor.
Fan SwitchIn AUTO or INT (intermittent) mode, the
blower operates only when the thermostat calls for
heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.
System SwitchSet the system switch for heating,
cooling or auto operation. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.
Temperature IndicatorThe temperature indicator
displays the actual room temperature.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day set points for both heating and cooling. Refer to the user’s information manual provided with your thermostat for operation details.
Preservice Check
If your system fails to operate, check the following before calling for service:
Make sure all electrical disconnect switches are ON. Make sure the room thermostat Temperature Selector
and System Switch (Heat, Cool, Auto) are properly set.
Check for and replace any blown fuses, or reset any
tripped circuit breakers.
Make sure unit access panels are in place. Make sure air filter is clean. Write down the unit model number and have it handy
before calling.
Optional Accessories
Refer to the Lennox XC14 Engineering Handbook for the latest available accessories for this unit.
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Suction Pressure Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Thermostat
Voltage With Compressor Operating Calibrated? Properly Set?  Level? 
505367M 04/08
Page 24
Loading...