Lennox X4147 Installation Instructions Manual

E2007 Lennox Industries Inc.
Dallas, Texas, USA
3 Heat / 2 Cool Programmable
Touch Screen Thermostat
INSTALLATION
INSTRUCTIONS
WARNING
505,044M 8/2007
Page 2
Table of Contents
General Page 2. . . . . . . . . . . . . . . . .
Shipping and Packing List Page 2.
NecessaryTools Page 2. . . . . . . . . .
Thermostat Location Page 2. . . . . .
Remove Existing Thermostat Page 3
Thermostat Installation Page 4. . . .
Wiring Connections Page 4. . . . . . .
LED Indicator Page 5. . . . . . . . . . . .
Outdoor Temp. Sensor Page 5. . . .
Field Wiring Diagrams Page 6. . . .
Install Batteries Page 8. . . . . . . . . .
Attach T’stat to Wallplate Page 8. .
Set Calendar and Clock Page 8. . .
Adv. Heat Pump Features Page 9.
Installer Set−Up Page 11. . . . . . . . . .
System Test Page 19. . . . . . . . . . . . .
Troubleshooting Page 20. . . . . . . . . .
General
The Lennox X4147 programmable touch-screen thermostat provides control for up to three stages of heating and two stages of cooling. The thermo­stat may be used to control either a conventional HVAC system which in­cludes an outdoor condensing unit and indoor furnace or a heat pump unit and indoor air handler. The thermostat ter­minal block accommodates 24V power common from the furnace or air han­dler. Three AAA alkaline batteries are provided to be used as an alternate power source or as a back−up in case of an interruption of power.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled thermostat (includes
wallplate and thermostat)
1− Bag assembly containing the fol-
lowing: 2 − Screws
2 − Wall anchors 3 − AAA alkaline batteries
1 − Installation instruction
1 − Owner’s guide
1 − Warranty certificate
Necessary Tools
S No. 2 Phillips screwdriver S Standard pocket screwdriver S Drill S Drill bits (use 3/16" for drywall and
7/32" for plaster)
S Pencil S Level S Hammer S Electrical tape
Thermostat Location
Install the thermostat about 5 feet (1.5m) above the floor in an area with good air circulation.
Do not install the thermostat where it may be affected by the following:
S Drafts or dead spots behind doors
and in corners.
S Hot or cold air from ducts. S Radiant heat from the sun or ap-
pliances.
S Concealed pipes or chimneys. S Adjacent unconditioned areas
(outside wall behind the thermo­stat).
Page 3
Remove Existing Thermostat
If this thermostat is being used to re­place an existing thermostat, remove the old thermostat:
1 − Turn off power at the heating and/
or cooling system or fuse/circuit breaker panel.
2 − Remove the cover from the exist-
ing thermostat.
3 − Remove securing screws and re-
move existing thermostat from wall or wallplate. Disconnect and label the existing wires.
4 − Remove any remaining portion of
the existing thermostat from the wall. Do not install the replace­ment thermostat faceplate on the existing wallplate. Though the wallplates may appear to be the same and the faceplate may fit on the existing wallplate, the terminal positions may vary in important ways. In addition, serial number and part number information is
carried on the replacement wall­plate.
Do not allow the thermostat wires to fall behind the drywall.
WARNING
This thermostat must be installed using the provided re­placement wallplate.
Failure to do so will bypass ther­mostat control and activate con­tinuous heating.
Y
G
C
R
W
OLD THERMOSTAT
.18
.
2
.
25
.
3
.
9
.
7 .
5
.
4
L O
N
G
E
R
THERMOSTAT
COVER
WALLPLATE
WARNING
MERCURY NOTICE
If the existing thermostat includes a mercury bulb, the thermostat must be disposed of properly.
Contact your local waste management authority for instructions re­garding recycling and proper disposal of thermostats which include mercury bulbs.
Page 4
Thermostat Installation
The thermostat may be installed hori­zontally in a 4 in. X 2 in. (101.6 mm X
50.8 mm) wiring box or on the wall us­ing the provided anchors.
1 − Separate the wallplate from the
thermostat as shown.
THERMOSTAT
WALLPLATE
WIRE HOLE
2 − Pass the labeled wires through the
hole on the wallplate.
3 − Position the wallplate on the wall
with the arrow pointing up. Level the wallplate (for appearance only) and use a pencil to mark the mounting holes.
WALLPLATE
LEVEL
PLACE LEVEL ON SUPPORT TABS
MARK MOUNTING HOLES (2)
4 − If anchors are used, move the
wallplate aside and drill two new holes (3/16" for drywall; 7/32" for plaster).
5 − Tap the provided wall anchors into
the drilled holes until the back of the anchor head touches the wall surface.
6 − Position the wallplate over the an-
chors and pull the thermostat wires back through the wiring opening.
7 − Secure the wallplate using the
provided screws.
DRILLED HOLES (2)
WALL ANCHORS (2)
MOUNTING SCREWS (2)
WALLPLATE
NOTE
Thermostat heat function will not operate if thermostat has been stored at, or is being used in, ambient temperatures at or above 90°F. Heat function will be enabled after thermostat has been placed in ambient tempera­tures less than 90°F for about 30 minutes.
Wiring Connections
WARNING
Use minimum 18 guage wire for all thermostat connections.
IMPORTANT
Do not connect the wires to this thermostat based on wire color. Improper wiring may cause damage to the HVAC system.
Page 5
1 − Make wiring connections per the
appropriate wiring diagram on page 6 or 7. Refer to the table below for terminal designations.
Terminal Description
Y2 Second−stage cooling
W2 (AUX)
Second−stage heating (or auxiliary heating)
W (E)
First−stage heating
(or emergency heating) S1 Remote outdoor sensor S2 Remote outdoor sensor
R 24V power O Reversing valve B Reversing valve G Fan relay Y First−stage cooling C 24V common
L Equipment monitor
2 − Refer to inner terminal labels
when using the thermostat with conventional systems (gas, oil or electric heat plus air conditioning). Refer to outer terminal labels in heat pump applications. See fig­ure below.
3 − Loosen screws of terminals that
will be used. Insert appropriate wires in the terminal block under
the loosened screws. Securely tighten each screw.
C
Y
B
O
R
G
INSERT WIRE IN HOLE
WIRE HOLE
WALLPLATE
SCREW
TERMINALS
LETTER
DESIGNATIONS
LABELED WIRES
TERMINAL
BLOCK
4 − Connect wires to the correspond-
ing screw terminals per the ap­propriate diagram.
5 − Push excess wire back into the
wall.
6 − Plug hole with nonflammable in-
sulation to prevent drafts from af­fecting thermostat.
LED Indicator
An LED indicator is located in the up­per right corner of the thermostat. It is only visible when lit.
When an equipment monitor is con­nected to the thermostat L terminal, the LED lights when the monitor sends a check or failure message to the ther­mostat.
The LED requires the use of 24Vac common power. The indicator will not light when the thermostat is powered by the batteries alone, or when 24Vac power is interrupted.
Outdoor Temperature Sensor
Install the optional outdoor tempera­ture sensor (X4148) as outlined in the instructions provided with the sensor.
Page 6
Field Wiring Diagrams
TYPICAL CONVENTIONAL MULTI−STAGE APPLICATION
TWO−STAGE HEAT / TWO−STAGE COOL
TYPICAL MULTI−STAGE HEAT PUMP APPLICATION
NO AUXILIARY HEAT
TYPICAL MULTI−STAGE HEAT PUMP APPLICATION
WITH AUXILIARY HEAT
Loading...
+ 14 hidden pages