Lennox Wired Controller Installation And Operation Instructions Manual

Page 1
1
©2017 Lennox Industries Inc.
Dallas, Texas, USA
INSTALLATION/ OPERATION INSTRUCTIONS
CONTROLS
507561-03 5/2017 Supersedes 8/2015
This manual must be left with the owner for future reference.
WARNING
!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency.
Frequent changes to operating mode may cause system malfunction. Allow at least one minute between mode changes to allow the system to stabilize.
IMPORTANT!
Lennox Mini-Split Systems Wired Indoor Unit Controller
Page 2
2
Shipping and Packing List
Package 1 of 1 contains;
1 – Wired Controller 1 – Installation and operation manual 1 – Cable with connector – 20 ft. (6 m)
General
The M0STAT61Q-1 mini-split wired controller is a wired local controller for Lennox mini-split indoor units.
Requirements
Turn off power supply before beginning installation. Use this controller only as de­scribed in this manual. Do not install the controller on outside walls (where there is unconditioned space on opposite side of wall) or in locations where direct sunlight may be present.
Installation
CAUTION
!
Clean controller using a clean, damp cloth. Do not spray cleanser on or around controller.
CAUTION
!
Do not install controller in areas where heavy oil, vapor, or gases containing sulfur may exist or the controller may be damaged.
Do not operate controller with wet hands.
WARNING
!
Be sure that power supply has been turned off before beginning installation.
WARNING
!
Page 3
3
IMPORTANT!
Read all of the information in this manual before using this controller. All wiring must conform to local and national building and electrical codes and ordinances. This is a 5 VDC controller. Do not install on voltages higher than 5 VDC.
IMPORTANT!
The provided cables must be used. Do not use excessive force while pulling the cable or when making the connections.
• This manual provides the installation instructions for this controller. Refer to the included wiring diagram to con­nect the controller to the indoor unit.
• The controller uses low voltage. Keep a minimum distance of 12” (305 mm) between low voltage control wire and high voltage power wires.
• Ground the shielded control wiring.
• Do not use a megger to test insula­tion.
• The controller cable length should not exceed 40 ft. (12 m).
Page 4
4
2. Remove the cover from the wall plate using a at-head screwdriver. See gure 2.
3. Mount the wall plate as appropriate for your application. See gure 3.
NOTE – Provide for future maintenance by allowing enough slack in the wiring to allow the controller to be removed from the wall if needed.
Figure 2. Remove cover from wall plate.
Slots
Figure 1. Wiring Connections
Indoor unit display board
5-conductor wire
5-conductor wire
1. Connect controller to indoor unit main control board by inserting the plug of the 5-conductor cable into the socket provided at the indoor unit
Page 5
5
Figure 3. Mount wall plate
4. Attach the wall plate using the provided screws. See gure 3.
J-box
Back plate
Back plate
Screws
Screw
Screws
Figure 4. Reattach cover to wall plate
5. Reattach the cover to the wallplate. See gure 4.
Page 6
6
RUN
GND
+5V
Field Wiring Diagram
Figure 5. Typical wiring diagram between wired controller and indoor unit
Indoor unit
display board
Shielded
5-conductor cable
Wired
controller
Specications
Table 1. Specications
Input voltage 5 VDC
Ambient temperature 23~110°F (-5~43°C)
Ambient humidity RH40%~RH90%
Emitter tube
5-way terminal
Page 7
7
Display
1
2
1 12
Operation mode indication
Follow me function
ON/OFF indication
Timer ON/OFF
Temperature display zone
Lock
Fan speed indication
• Operation mode. These icons show the current mode of opera­tion. Press the mode button to scroll through the operation modes:
Auto → Cool → Dry → Heat → Fan.
• Timer ON/OFF. These icons light to indicate that the indoor unit has a timed auto-start or auto-stop set .
• Follow me. This icon displays when the air temperature sensor in the wired remote controller is the sensor
being used by the indoor unit. When this function is off, the indoor unit uses a built-in sensor.
• ON/OFF. This icon displays when the indoor unit is turned on.
• Fan speed. Displays the current fan speed.
• Lock. This icon displays when the controller is locked.
• Temperature display. Displays set­point temperature.
Page 8
8
Description of Buttons
MODE BUTTON
TIMER ON BUTTON
FOLLOW ME BUTTON
TIMER OFF BUTTON
RESET BUTTON
ON / OFF BUTTON
ADJUST BUTTON
ADJUST BUTTON
SWING BUTTON
ECONOMY BUTTON
FAN SPEED BUTTON
LOCK BUTTON
TIMER
ON
TIMER
OFF
FOLLOW
ME
MODE
RESET
LOCK
FANSPEED
ECO
SWING
TEMP
Page 9
9
• Mode button. Press to scroll through the operation modes:
Auto → Cool → Dry → Heat → Fan.
• Timer ON button. Press to set the number of hours of delay before the indoor unit begins operation.
• Timer OFF button. Press to set the number of hours of delay before the indoor unit stops operation.
• Follow Me button. Press to activate the controller’s air temperature sen­sor. This transfers the temperature sensing function from the indoor unit to the controller. The indoor unit’s air temperature sensor will be disabled.
• Reset button. Using a blunt-tipped device (paper clip), press to cancel current settings and reset remote con­troller to factory settings.
• On/Off button. Press to turn the in­door unit on or off.
• Up arrow button. Press to increase the temperature setpoint or to scroll through settings options.
• Down arrow button. Press to de­crease the temperature setpoint or scroll through settings options.
• Swing button. Press once to initiate louver left & right oscillation. Press again to stop louver oscillation. Lou­vers remain in place where stopped. Not available in all indoor unit models.
• Economy button. Not used.
• Fan speed. Press to scroll through
the fan speeds: Auto → Low → Med → High
• Lock button. Using a blunt-tipped device (paper clip), press to lock or unlock the current setting.
Page 10
10
Operation
Start/stop operation
Press the LED power button.
• Controller ON: Power button LED lit brightly.
• Controller OFF: Power button LED not lit.
Select Fahrenheit or Celsius Display
Press and Up and Down buttons at the same time, and hold for three seconds to toggle between Fahrenheit and Celsius.
To set the operation mode
Press the Mode button to scroll through the mode selections.
• Auto – System operates in cooling or heating mode as determined by the setpoint and the room temperature.
NOTE: The use of Auto mode for multi-zone units is not recom­mend. All zones should be in the same mode of operation to ensure
there is not a conict error mode.
• Cool – System operates in cooling mode.
• Dry – System removes humidity ac­cording to preset conditions (fan speed and setpoint temperature, not
a humidistat sensor). Cannot adjust fan speed.
• Heat – System operates in heating mode.
• Fan – Fan only, no heating or cooling.
To set (or change) the room tempera­ture setting (setpoint)
Press the up arrow & down arrow but­tons to adjust the setpoint.
Dry mode
1. Press the Power button, an LED light on the indoor unit displays.
2. Press the Mode button to select Dry.
3. Adjust the temperature setpoint using up and down arrow buttons.
NOTE – Fan speed is not adjustable.
Timer operation
Timer ON and Timer OFF are used to turn on and turn off the indoor unit at se­lected intervals.
Timer ON operation
1. Press the Timer ON button. The Timer on icon, the last auto-on time, and “h” will display.
2. Press the Timer ON button again to set the amount of time before the indoor unit begins operation. Each
Page 11
11
press will increase the time in half hour increments until 10 hours, then the increment becomes 1 hour.
Timer OFF operation
1. Press the Timer OFF button. The Tim­er off icon, the last auto-off time, and “h” will display.
2. Press the Timer OFF button again to set the amount of time before the in­door unit stops operation. Each press will increase the time in half hour in­crements until 10 hours, then the in­crement becomes 1 hour.
Modify Timer ON/OFF settings
1. Press either the Timer ON button or the Timer OFF button to modify that setting.
2. Continue to press the Timer ON or Timer OFF button until the display shows the new time. Each press will increase the time in half hour incre­ments until 10 hours, then the incre­ment becomes 1 hour.
3. Set the timer to 0.0 to turn off timed operation.
Page 12
12
Troubleshooting
Fault Codes (indoor unit)
E0 Indoor unit EEPROM error
E1 Communication error between indoor unit and outdoor unit
E3 Indoor fan speed error
E4 Indoor return air temperature sensor error
E5 Indoor coil temperature sensor error
EC Low refrigerant
EE High water level alarm
F0 Outdoor current overload sensed
F1 Outdoor ambient temperature sensor error
F2 Outdoor coil temperature sensor error
F3 Compressor discharge temperature sensor error
F4 Outdoor unit EEPROM error
F5 Outdoor unit fan speed error
P0 Inverter module IPM error
P1 High or low voltage protection
P3 Outdoor unit low temperature lockout
P4 Compressor drive error
-- Mode conict
P6 Compressor high-pressure or low-pressure switch open
Loading...