Lennox WING 3TFK, WING 4TFK, WING 5TFK, WING 3CFK, WING 4CFK Application Manual

...
APPLICATION GUIDE
WING
. PRODUCT RANGE . SYSTEM CONFIGURATION . GENERAL DESCRIPTION . SPECIFICATIONS . ELECTRICAL DATA . ELECTRICAL CONNECTIONS . INDOOR MOTOR FAN CHARACTERISTICS . OPERATING LIMITS . REFRIGERANT CONNECTIONS . DIMENSIONS AND SETTING UP TEMPLATES OUTDOOR UNIT . DESCRIPTION OUTDOOR UNIT . ENTRANCE STANDARD/ OPTIONAL OUTDOOR UNIT . DIMENSIONS AND SETTING UP TEMPLATES INDOOR UNIT . INSTALATION AND MOUNTING . OPTIONS MAINTENANCE . POINTS TO KEEP IN MIND
Congratulations you have made a wise choice with the purchase of your Lennox
air conditioning unit.
This product has been designed, assembled and supplied in one of our world class manufacturing facilities
and we feel sure that it will meet your expectations.
Lennox an international organisation with world wide distribution takes pride in supplying you with this
product.
PÁGE
CONTENTS
CONTENTS
2-3
4 5
6-9 10-11 12-14
15 16
17-19
20
21-22
23 24 25
26-27
28 29
COOLING ONLY R-407C
MODEL
OUTDOOR
UNIT
INDOOR
UNIT
V / Ph / 50 Hz
NOMINAL
CAPACITY W
COOLING ONLY
COOLING ONLY
NOMINAL
CAPACITY KW
MODEL
OUTDOOR
UNIT
INDOOR
UNIT
V / Ph / 50 Hz
NOMINAL
CAPACITY W
COOLING ONLY
COOLING ONLY
NOMINAL
CAPACITY KW
230V -1Ph
9.500
11.600
13.500
3,85
4,70
5,60
WING 3TFK
WING 4TFK
WING 5TFK
KJF 3K
KJF 4K
KJF 5K
LTX 3
LTX 5
LTX 5
230 V - 3Ph 400 V - 3Ph
WING 3TFK WING 3TFK
KJF 3K KJF 3K
KJF 4K
KJF 5K
230 V - 3Ph
400 V - 3Ph
230 V - 3Ph
400 V - 3Ph
230V-1Ph 7.350 3,06WING 2,8TFK KJF 2,8K LTX 3
WING 4TFK
WING 5TFK
230V -1Ph
9.100
12.100
14.000
3,86
5,17
7,00
WING 3CFK
WING 4CFK
WING 5CFK
KCF 3K
KCF 4K
KCF 5K
LTX 3
LTX 5
LTX 5
230 V - 3Ph 400 V - 3Ph
WING 3CFK WING 3CFK
KCF 3K KCF 3K
KCF 4K
KCF 5K
230 V - 3Ph
400 V - 3Ph
230 V - 3Ph
400 V - 3Ph
230V-1Ph 7.130 3,07WING 2,8CFK KCF 2,8K LTX 3
WING 4CFK
WING 5CFK
PRODUCT RANGE
LTX INDOOR UNIT IN COMBINATION, WITH AXIAL FAN OUTDOOR UNIT
LTX INDOOR UNIT IN COMBINATION, WITH CENTRIFUGAL FAN OUTDOOR UNIT
MODEL
OUTDOOR
UNIT
INDOOR
UNIT
V / Ph / 50 Hz
NOMINAL
CAPACITY W
COOLING
ONLY
NOMINAL
CAPACITY KW
HEAT
PUMP
COOLING
ONLY
HEAT
PUMP
MODEL
OUTDOOR
UNIT
INDOOR
UNIT
V / Ph / 50 Hz
NOMINAL
CAPACITY W
COOLING
ONLY
NOMINAL
CAPACITY KW
HEAT PUMP
COOLING
ONLY
HEAT PUMP
230V -1Ph
10.220
13.500
17.400
3,40
4,33
6,40
9.100
12.100
14.000
3,86
5,17
7,00
KCB 3S
KCB 4S
KCB 5S
230 V - 3Ph 400 V - 3Ph
KCB 3S KCB 3S
KCB 4S
KCB 5S
230 V - 3Ph
400 V - 3Ph
230 V - 3Ph
400 V - 3Ph
230V-1Ph 8.150 2,777.130 3,07KCB 2,8S
WING 3CB
WING 4CB
WING 5CB
LTX 3
LTX 5
LTX 5
WING 3CB WING 3CB
WING 2,8CB LTX 3
WING 4CB
WING 5CB
230V -1Ph
9.000
12.100
14.600
3,00
3,90
5,00
9.250
11.600
13.700
3,70
4,70
5,90
KJB 3
KJB 4
KJB 5
230 V - 3Ph 400 V - 3Ph
KJB 3 KJB 3
KJB 4
KJB 5
230 V - 3Ph
400 V - 3Ph
230 V - 3Ph
400 V - 3Ph
230V-1Ph 7.800 2,607.350 3,06KJB 2,8
WING 3TB
WING 4TB
WING 5TB
LTX 3
LTX 5
LTX 5
WING 3TB WING 3TB
WING 2,8TB LTX 3
WING 4TB
WING 5TB
PRODUCT RANGE HEAT PUMP
LTX INDOOR UNIT IN COMBINATION, WITH AXIAL FAN OUTDOOR UNIT
LTX INDOOR UNIT IN COMBINATION, WITH CENTRIFUGAL FAN OUTDOOR UNIT
HEAT PUMP R-22C
(*) Configuration from factory..
MODEL
COOLING ONLY
(*)
HEAT PUMP
SWITCH
1 2
ONOFF
ON ON
Switch 1
Switch 2
ON OFF
IMPORTANT
Prior of making the electrical connections,
set the switch for heat pump unit or for cooling only unit.
This unit is valid for operating as a cold only or heat pump application.
The unit should be configured prior to making the electrical connections, by setting the configuration
switch as follows:
NOTE:
If errors are made during the configuration of the system, switch off the main power supply, set
configuration switch in the correct position and then switch the power on.
SYSTEM CONFIGURATION (INDOOR UNIT)
Check page 8 for more information about the situation of this switch.
GENERAL DESCRIPTION
The ceiling air conditioner SPLIT, on version cooling only and heat pump, are units air condensed. The indoor unit with direct air supply, realise function of cooling , heating dehumidification, cleaning air of the sites. Also the option to incorporate with maximum facilities a heating resistance on units cooling only and also on heat pump units. The indoor unit can be combine with outdoor units provide with axial fan (KJF/ KJB) for outside installation or with outdoor unit provide with centrifugal fan (KCF/ KCB) for installation inside buildings.
The outdoor unit is made on electrozinced steel with epoxy painted finish, able to work outdoors under the worst conditions. its dimensions and features allow the unit to be positioned in almost any location. It incorporate thermal acoustic insulation. The indoor unit is finished in a decorative plastic with thermal acoustic insulation.
Made of cooper tubes and aluminium fins. Coils have been designed and manufactured to ensure maximum efficiency. The L shaped outside unit heat exchanger makes this unit compact an highly efficiency.
An hermetically sealed compressor, with internal thermal protection. It is mounted on vibration absorbent blocks both on the inside and outside, statically an dynamically balanced. In all cases the compressors are acoustically isolated, resulting in low noise.
The indoor units includes centrifugal motor fan of three speed, with exceptional features on noise level Depending on outdoor type, it includes one or two axial motor fan (units KJF/KJB), or one centrifugal fan (units KCF/ KCB),with exceptional features in noise level and flow .
The indoor unit (LTX) have an automatic dispositive to distribute horizontal air flow.
INDOOR
UNIT LTX
OUTDOOR UNIT
KJF/KJB
CABINE
ELECTRIC CIRCUIT
HEAT EXCHANGER
COMPRESSOR
COOLING CIRCUIT
OPTIONS
FANS
AIR SWEEP
Made of welded dehydrated copper pipe with service port on the suction and liquid lines. Coupling valves on outdoor unit and flare connexion on indoor unit to facilitate the refrigerant connexion. A muffler in the compressor discharge line eliminates noise and pulsation of the discharge line. The unit includes filter dryer and expansion system. It has unidirectional and reversing valves of 4 pipes for unit in heat pump.
The indoor unit electrical panel includes a printed board, which control the operating of the unit, defrosting timer thermostat and system of reversing on heat pump cycle. The unit is controlled from an infrared remote controller.
OUTDOOR UNIT
• Heating electrical heater.
OUTDOOR UNIT TYPE KJF/KJB
• Supporting with braxkets( depends on units)
• Winter control.
OUTDOOR UNIT TYPE KCF/KCB
• Winter control
• Main switch (depends on models)
• Grille external air
OUTDOOR UNIT
KCF/KCB
Cooling capacity
COMPRESSOR
OUTDOOR UNIT
FAN
Air flow outdoor unit
MODEL
REFRIGERANT
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Liquid pipe Gas pipe
INDOOR UNIT
EXPANSIÓN
PACKING DIMENSIONS
(1) Charge of refrigerant, factory charged on outdoor unit. See page 22, to calculate model refrigerant charge. (2) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit.
DB.- Dry Bulb WB.- Wet Bulb
(*) Air entry temperature into the indoor unit 27°C DB/19 °C WB (*) Air entry temperature into the outdoor unit 35ºC DB
(*)
m3/h.
Nª / Type
Type / R-407C
(1)
W
m3/h.
Kg
Kg
Max. Min.
gr.
mm. mm. mm.
mm. mm. mm.
mm.
mm.
FAN
Air flow indoor unit
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Liquid pipe Gas pipe
PACKING DIMENSIONS
845 x 1060 x 385 1085 x 1275 x 385
310 x 1430 x 680
352 x 1749 x 776
LTX 3
1.300
1.100 40
267
1.409 656
3/8"
3/4"
(2)
LTX 3
1.300
1.100 40
267
1.409 656
3/8" 3/4"
1/2" 3/4"
1/2" 3/4"
LTX 5
2.100
1.800 57
756
1.719
312
WING
5TFK
13.500
KJF 5K
5.400
1035
333
973
98
1 / ALT.
2600
WING 4TFK
11.600
KJF 4K
5.400
1035
333
973
96
1 / ALT.
2600
3/8" 3/4"
LTX 5
2.100
1.800 57
756
1.719
312
1/2"
(2)
3/4"
WING
2,8TFK
7.350
KJF 2,8K
3.100
781
333
973
78
1 / ALT.
1650
Capillary
3/8" 5/8"
3/8" 3/4"
WING
3TFK
9.500
KJF 3K
5.100
1035
333
973
85
1 / ALT.
2500
Capillary
Capillary Capillary
SPECIFICATIONS COOLING ONLY
OUTDOOR UNIT WITH AXIAL FAN
R-407C
Available pressure
(*)
(1)
W
m3/h.
Kg
Kg
m3/h.
Max. Min.
gr.
mm. mm. mm.
mm. mm. mm.
mm.
Pa
mm.
Nª / Type
Type / R-407C
(1) Charge of refrigerant, factory charged on outdoor unit. See page 22, to calculate model refrigerant charge. (2) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit.
DB.- Dry Bulb WB.- Wet Bulb
(*) Air entry temperature into the indoor unit 27°C DB/19 °C WB (*) Air entry temperature into the outdoor unit 35ºC DB
INDOOR UNIT
FAN
Air flow indoor unit
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
PACKING DIMENSIONS
Cooling capacity
COMPRESSOR
OUTDOOR UNIT
FAN
Air flow outdoor unit
MODEL
REFRIGERANT
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
EXPANSIÓN
PACKING DIMENSIONS
630 x 1140 x 850
775 x 1330 x 865
310 x 1430 x 680
352 x 1749 x 776
7.180
KCF 2,8K
2.500
505
750
1050
89
1 / ALT.
2255
WING
2,8CFK
40
3/8" 5/8"
LTX 3
1.300
1.100 40
267
1.409 656
3/8"
3/4"
(2)
LTX 3
1.300
1.100 40
3/8" 3/4"
3/8" 3/4"
267
1.409 656
750
WING 3CFK
9.100
KCF 3K
2.500
91
1 / ALT.
2350
505
1050
40
WING 4CFK
12.100
KCF 4K
3.400
525
855
1300
125
1 / ALT.
3070
3/8"
50
3/4"
LTX 5
2.100
1.800 57
756
1.719
312
1/2"
(2)
3/4"
1/2" 3/4"
1/2" 3/4"
LTX 5
2.100
1.800 57
756
1.719
312
WING
5CFK
14.000
KCF 5K
5.000
140
1 / ALT.
4950
575
855
1300
50
Capillary
Capillary
Capillary Capillary
SPECIFICATIONS COOLING ONLY
OUTDOOR UNIT WITH CENTRIFUGAL FAN
R-407C
Heating capacity
(*) Air entry temperature into the indoor unit 27°C DB/19 °C WB (*) Air entry temperature into the outdoor unit 35ºC DB (**) Air entry temperature into the indoor unit 20°C DB/12 °C WB (**) Air entry temperature into the outdoor unit 7ºC DB/6ºCWB (1) Charge of refrigerant, factory charged on outdoor unit. See page 22, to calculate model refrigerant charge (2) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..
(*) (**)
m3/h.
Type / R-22
W
m3/h.
Kg
Kg
Max. Min.
gr.
mm. mm. mm.
mm. mm. mm.
mm.
W
mm.
Cooling capacity
MODEL
Nª / Type
COMPRESSOR
OUTDOOR UNIT
FAN
Air flow outdoor unit
REFRIGERANT
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
EXPANSIÓN
PACKING DIMENSIONS
INDOOR UNIT
FAN
Air flow indoor unit
DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
PACKING DIMENSIONS
DB.- Dry Bulb WB.- Wet Bulb
WEIGHT
845 x 1060 x 385
1495 x 1057
x 430
1085 x 1275
x 385
310 x 1430 x 680
352 x 1749 x 776
7.350
KJB 2,8
3.100
781
333
973
3/8"
81
1 / ALT.
1775
5/8"
7.800
WING 2,8TB
LTX 3
1.300
1.100
267
1.409 656
40
3/8"
3/4"
(2)
9.250
KJB 3
3.100
781
333
973
83
1 / ALT.
2500
3/8" 3/4"
9.000
WING
3TB
LTX 3
1.300
1.100
267
1.409 656
40
3/8" 3/4"
11.600
KJB 4
5.400
1035
333
973
99
1 / ALT.
2800
3/8" 3/4"
12.100
WING
4TB
LTX 5
2.100
1.800 57
756
312
1.719
1/2"
(2)
3/4"
13.700
KJB 5
5.600
1330
386
1005
1/2" 3/4"
129
1 / ALT.
3500
Restrictor
14.600
WING
5TB
LTX 5
2.100
1.800 57
756
312
1.719
1/2" 3/4"
Capillary
Capillary
Capillary
SPECIFICATIONS HEAT PUMP
OUTDOOR UNIT WITH AXIAL FAN
R-22
(1)
Kg
m3/h.
Max. Min.
mm. mm. mm.
m3/h.
Kg
gr.
mm.
mm.
mm.
mm.
Pa
mm.
Nª / Type
(*) (**)
W W
Heating capacity
Cooling capacity
MODEL
COMPRESSOR
OUTDOOR UNIT
FAN
Air flow outdoor unit Available pressure
Type / R-22
REFRIGERANT
WEIGHT DIMENSIONS
Height Width Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
EXPANSIÓN
PACKING DIMENSIONS
INDOOR UNIT
FAN
Air flow indoor unit
WEIGHT DIMENSIONS
Height Width
Depth
REFRIGERANT COUPLING
Líquid pipe Gas pipe
PACKING DIMENSIONS
(*) Air entry temperature into the indoor unit 27°C DB/19 °C WB (*) Air entry temperature into the outdoor unit 35ºC DB (**) Air entry temperature into the indoor unit 20°C DB/12 °C WB (**) Air entry temperature into the outdoor unit 7ºC DB/6ºCWB (1) Charge of refrigerant, factory charged on outdoor unit. See page 22, to calculate model refrigerant charge (2) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..
DB.- Dry Bulb WB.- Wet Bulb
310 x 1430 x 680
352 x 1749 x 776
630 x 1140 x 850 775 x 1330 x 865
Capillary
Capillary
Capillary Capillary
SPECIFICATIONS HEAT PUMP
OUTDOOR UNIT WITH CENTRIFUGAL FAN
R-22
14.000
KCB 5S
17.400
WING
5CB
LTX 5
2.100
1.800 57
756
312
1.719
1/2"
3/4"
5.000
1/2" 3/4"
150
1 / ALT.
5300
575
855
1300
50
12.100
KCB 4S
13.500
WING
4CB
LTX 5
2.100
1.800 57
756
312
1.719
1/2"
(2)
3/4"
3.400
525
855
1300
135
1 / ALT.
3400
3/8" 3/4"
50
9.100
KCB 3S
10.220
WING
3CB
LTX 3
1.300
1.100
267
1.409 656
40
3/8"
3/4"
2.500
94
1 / ALT.
2525
3/8" 3/4"
505
750
1050
40
7.180
KCB 2,8S
8.150
WING 2,8CB
LTX 3
1.300
1.100
267
1.409 656
40
3/8"
3/4"
(2)
2.500
505
750
1050
3/8"
92
1 / ALT.
2425
5/8"
40
10
SOUND LEVEL
dBA
dBA
OUTDOOR UNIT
INDOOR UNIT
ELECTRICAL DATA
Indoor unit
(1)
Outdoor unit
(2)
Sound
pressure
level
Nominal total input power cooling capacity
Current max.
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
Kw Kw
V/f (50 Hz)
Kw Kw
V/f (50 Hz)
Kw
Kw
V/f (50 Hz)
A
A
A
A A
A
A
A
(Lp)
Nominal total input power cooling capacity
Current max.
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
Nominal total input power cooling capacity
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
230V / 1 Ph
230V / 1 Ph
230V-400V / 3 Ph
230V-400V / 3 Ph
230V / 1 Ph
91
2,88
17,12
2,42
14,05
KJF 2,8K
KJB 2,8
2,46
0,18 0,18
0,82
LTX 3
91
3,06
17,9
2,60
14,87
WING 2,8TFK
WING 2TB
52
WING 2,8TFK
WING 2TB
41/46 (*)
78 / 39
90
3,67
16,4/9,8
23,58
41/46 (*)
55
---
13,2/7,1
18,48
2,46
0,18
---
0,82
KJF 3K
LTX 3
WING 3TFK
78 / 39
90
3,85
16,5/10,2
24,4
----
12,8/7,7
19,3
WING 3TFK
106 / 53
4,45
20,2/11,0
56
3,65
17,2/8,0
KJF 4K
KJB 4
WING 4TFK
WING 4TB
43/48 (*)
0,25
---
3,42
1,14
LTX 5
106 / 53
4,70
21,3/12,1
3,90
18,3/9,1
WING 4TFK
WING 4TB
124 / 62
5,65
23,3/12,1
43/48 (*)
56
4,75
20,4/10,2
0,25 0,25
3,42
1,14
KJF 5K
LTX 5
WING 5TFK
WING 5TB
124 / 62
24,4/13,2
5,00
21,5/11,3
5,90
WING 5TFK
LTX 3
LTX 5
0,25 0,25
3,42
1,14
2,46
0,18 0,18
0,82
78 / 39
90
3,52
15,7/9,4
22,60
2,82
12,0/6,9
17,48
78 / 39
90
3,70
23,4
3,00
18,3
124 / 62
5,35
22,1/10,9
----
19,2/9,0
124 / 62
23,1/11,9
---
20,4/10,2
5,60
41/46 (*)
53
17,3/10,7
13,4/8,0
(1) Sound level measured to a distance of 2m from the unit, normal absorption, room size according to unit capacity. (2) Sound level measured to a distance of 5 m, free space.
(*) High speed / Low speed
WING 3TB
WING 3TB WING 5TB
KJB 3
KJB 5
SPECIFICATIONS
SET WITH AXIAL FAN OUTDOOR UNIT
11
(Lp)
dBA
dBA
Kw Kw
V/f (50 Hz)
Kw
Kw
V/f (50 Hz)
Kw
Kw
V/f (50 Hz)
A
A
A
A
A
A
A
A
SOUND LEVEL
OUTDOOR UNIT
INDOOR UNIT
ELECTRICAL DATA
Indoor unit
(1)
Outdoor unit
(2)
Sound
pressure
level
Nominal total input power cooling capacity
Current max.
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
Nominal total input power cooling capacity
Current max.
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
Nominal total input power cooling capacity
Rated current
Nominal total input power heat pump
Starting current max.
Voltage
230V / 1 Ph
230V / 1 Ph
230V / 1 Ph
230V-400V / 3 Ph
230V-400V / 3 Ph
91
2,89
19,00
2,59
14,10
KCF 2,8K KCB 2,8S
WING 2,8CFK
WING 2CB
2,46
0,18 0,18
0,82
LTX 3
91
3,07
19,82
2,77
14,92
WING 2,8CFK
WING 2CB
41/46 (*)
57
3,68
15,7/9,4
22,65
58
3,22
10,8/4,5
17,77
3,86
16,5/10,2
3,40
11,7/5,4
78 / 39
90
2,46
0,18 0,18
0,82
KCF 3K KCB 3S
LTX 3
WING 3CFK
WING 3CB
78 / 39
90
23,4
18,3
WING 3CFK
WING 3CB
41/46 (*)
4,92
20,8/11,60
4,08
15,5/8,9
5,17
21,9/12,7
4,33
16,6/10,0
60
106 / 53
KCF 4K
KCB 4S
WING 4CFK
WING 4CB
0,25 0,25
3,42
1,14
LTX 5
106 / 53
WING 4CFK
WING 4CB
43/48 (*)
6,75 6,15
21,2/12,2
7,00 6,40
22,3/13,3
24,5/16,7
23,4/15,56
62
124 / 62
0,25 0,25
3,42
1,14
KCF 5K KCB 5S
LTX 5
WING 5CFK
WING 5CB
124 / 62
WING 5CFK
WING 5CB
43/48 (*)
(1) Sound level measured to a distance of 2m from the unit, normal absorption, duct size and installation according to unit capacity.
(2)
Sound level measured to a distance of 5 m, normal absorption, duct size and installation according to unit capacity. (*) High speed / Low speed
SPECIFICATIONS
SET WITH CENTRIFUGAL FAN OUTDOOR UNIT
12
Power supply Connection indoor unit with outdoor unit Sensor connection
NOTE: The sections has been calculated to a distance no superior o 50m and a low supply of 10V
VOLTAGE
4
3
MODEL
21 21
5
NUMBER OF WIRES X SECTION
2.8
COOLING ONLY HEAT PUMP
3
230 V / 1Ph
400 V / 3Ph
230 V / 3Ph
400 V / 3Ph
230 V / 3Ph
400 V / 3Ph
230 V / 3Ph
230 V / 1Ph 400 V / 3Ph
5x4mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
6x1,5mm
2
2x1,5mm
2
4x1,5mm
2
3x4mm
2
3x4mm
2
5x2,5mm
2
4x1,5mm
2
3x4mm
2
4x4mm
2
5x2,5mm
2
4x1,5mm
2
4x4mm
2
4x1,5mm
2
4x1,5mm
2
5x2,5mm
2
4x1,5mm
2
4x6mm
2
4x1,5mm
2
5x4mm
2
4x1,5mm
2
5x2,5mm
2
4x4mm
2
5x2,5mm
2
4x4mm
2
5x2,5mm
2
4x6mm
2
6x1,5mm
2
2x1,5mm
2
4x1,5mm
2
3x4mm
2
1 2 3
1º Remove the front details at the corners and unit cover panel.
2º Remove the filters See picture
ELECTRIC
WIRING DIAGRAM
For electrical connection refer to wiring diagram
in the unit
1
OUTDOOR
UNIT
2
3
ELECTRICAL CONNECTIONS
MODELS 2,8-3-4-5
13
IMPORTANT
Prior of making the electrical connections, set the switch for heat pump unit or for cooling only
unit.
This unit is valid for operating as a cold only or heat pump application. The unit should be configured
prior to making the electrical connections, by setting the configuration switch as follows:
NOTE:
If errors are made during the configuration of the system, switch off the main power supply , set configuration switch in the correct position and then switch the power on.
Rolling side
Sides and carcass
Filters
DETAIL B
DETAIL B
1 2
(*) Configuration from factory.
MODEL
COOLING ONLY
(*)
HEAT PUMP
SWICHT
CONFIGURATION
COOLING ONLY
HEAT PUMP
ONOFF
ON ON
DETALLE A
1
3
2
Remove the front details at the corners and unit cover panel.
Switch 1
Switch 2
ON OFF
Regleta de terminales, y
conexión de la sonda exterior
Remove the filters
P.C.B(1)
4
5
4
5
SENSOR OUTDOOR
UNIT
SWICHT CONFIGURATION
PCB
SWICHT CONFIGURATION
CONNECTIONS OF OUTDOOR UNITS
-FOR HEAT PUMP UNITS, remove the resistor form the terminal
plate and connect the sensor outdoor unit
-FOR COOLING ONLY UNITS, keep connected the resistor. DON´T TOUCH.
ELECTRICAL CONNECTIONS AND SYSTEM CONFIGURATION
NOTE: THE UNIT LEAVES FACTORY
CONFIGURATED ON COOLING MODE
14
Wire overwhelm
ELECTRICAL CONNECTIONS
COOLING ONLY
HEAT PUMP
CONTROL
SENSOR
400V/50HZ 3Ph + N
PE L N 1 2 3
PE L1 PE N 1L 2L2 L3
N
LTX 5
4 5
4 5
3
OUTDOOR UNIT
CONTROL
SENSOR
230V/50HZ 3Ph
PE L N 1 2 3
PE L1 PE N 1L 2L2 L3
N
LTX 5
3
4 5
4 5
OUTDOOR UNIT
CONTROL
SENSOR
LTX 3
PE L N 1 2 3
PE
L1
N 1 2
N
3
L2
L3
4 5
4 5
230V/50HZ 3Ph
OUTDOOR UNIT
CONTROL
SENSOR
LTX 3
PE L N 1 2 3
PE
L1
N 1 2
N
3
L2
L3
4 5
4 5
400V/50HZ 3Ph + N
OUTDOOR UNIT
230V/50HZ 1Ph + N
PE L N 1 2 3
PE L N 1 2
N
4 5
3
4 5
CONTROL
SENSOR
LTX 3
OUTDOOR UNIT
230V/50HZ 3Ph
PE L N 1 2 3
PE L1 N 1 2N 3L2 L3
L3
4
5
LTX 3-5
OUTDOOR UNIT
230V/50HZ 1Ph + N
LTX 3
OUTDOOR UNIT
PE L N 1 2 3
PE L
N
1 2 43
5
400V/50HZ 3Ph + N
PE L N 1 2 3
PE L1 N 1 2N 3L2 L3
LTX 3-5
L3
4
5
OUTDOOR UNIT
15
KCF2,8K / KCB 2,8S
KCF 4K / KCB 4S KCF 5K / KCB 5S
m /h
3
m /h
3
KCF 3K / KCB 3S
AIR FLOW
1500 1700 2500 2900
110 75
40
0
1500 1650 2500
2900
100 70 54
0
4250 4650 5050
5400
150 110 50
0
2800 3100 3400
3800
110 80 50
0
OUTDOOR UNIT MOTOR-FAN CHARACTERISTICS
OUTDOOR UNIT WITH CENTRIFUGAL FAN
STATIC PRESSUERE AVIALABLE
Pa.
AIR FLOW
STATIC PRESSUERE AVIALABLE
Pa.
STATIC PRESSUERE AVIALABLE
Pa.
AIR FLOW
STATIC PRESSUERE AVIALABLE
Pa.
16
DB.- Dry Bulb WB.- Wet Bulb
DB.- Dry Bulb
WB.- Wet Bulb
STANDARD
**
**
*
*
Supply air temperature into the indoor unit ºC
Supply air temperature into the outdoor unit ºC
19° DB
46° DB
-10° DB 21°/15º
DB/WB
32°/23º DB/WB
STANDARD
19° DB
46° DB
*
*
*
**
**
-8°/-9º
DB/WB
24°/18º DB/WB
15°
DB
27°
DB
COOL CYCLE
HEAT CICLE
**
21°/15º DB/WB
32°/23º DB/WB
Supply air temperature into the indoor unit ºC
Supply air temperature into the outdoor unit ºC
THE ON/OFF LOW AMBIENT CONTROL IS STANDARD THE PROPORTIONAL LOW AMBIENT CONTROL IS OPTIONAL
L.A.C. PROPROC
L.A.C. ON/OFF
OPERATING LIMITS
OPERATING LIMITS COOLING ONLY UNITS
OPERATING LIMITS HEAT PUMP UNITS
17
PIPE DIAMETER
TIGHTENING TORQUE
TIGHTENING TORQUE
Apply the tightening torque shown in the table.
Insufficient tightening torque could cause
refrigerant leak,
excessive tightening torque will damage pipe
flare.
1/2'' 50-55 Nm
3/8''
3/4''
31-35 Nm
65-70 Nm
REFRIGERANT CONECTION FOR UNITS WITH COUPLINGS AND SERVICE VALVES NOTE: THE REFRIGERANT LINES GAS AND LIQUID, MUST BE INSULATED
Make the refrigerant connections between the outdoor and indoor unit, as follows:
-With the valves closed on outdoor unit, unscrew the flare nuts, removing all the protective hoods.
-Unscrew the flare nuts and the coupling on indoor unit, removing the protecting hoods.
-Introduce the flare nuts in the corresponding union tubes, previously isolated.
-Make the thread union of the tubes in valves and coupling using the keys, as shown in the picture.
-To do vacuum, first close the valves on outdoor unit, second connect the plug of the vacuum pump to the suction valves service port 1/4”, do vacuum to get an absolute pressure of 0.5 mm Hg. This way the vacuum will be created in indoor unit and union pipes.
-Remove the plugs and open the valves of outdoor unit.
-Verify leakage in couplings.
-Insulate pipes and service ports.
INDOOR
UNIT
Service valve
Coupling
Flared nuts
Insulation
Protective hoods
OUTDOOR
UNIT
Pipe cutter
Bent
Unpolished
CUT THE PIPE PROPERLY
AVOID FROM METALIC DUST ENTERING INTO THE PIPE
CLEAN THE BURRS
90°
YES
NO
Bent
0-0.5 m.m.
Copper pipe
FAULTY
Damaged surface Flawed Irregular
MAKE A CORRECT FLARE
Liquid line
Service port
Gas line
Wrench
REFRIGERANT CONNECTIONS
18
To locate the outdoor and the indoor units, refer to the following information.
L : Distance length between both units. 1 = Refrigerant vapour line. 2 = Liquid aspiration line.
3
4
MODEL
5
2,8
Liquid
Máx.Vertical Total vertical
+
Horizontal
Tube size
Refrigerant lines sizes Refrigerant lines sizes L
Max. number of bends
Vapour
15 25
12
15 20
8
15 20
8
15 20
8
3/8"
5/8"(1)
3/8" 3/4"
3/8"(1)
3/4"
1/2" 3/4"
If the height length is greater than 5 meters, a siphon suction must be installed on the suction line every 5 meters to ensure that oil return to the compressor. (1) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..
For other positions and longer lengths, consult the Lennox Technical Support Department for application
assistance.
The following data will be obtained from that estimation:
Pipe dimensions, Siphon suction, Insulation, Refrigerant charge
NOTE: THE REFRIGERANT LINES GAS AND LIQUID, MUST BE INSULATED
L
INDOOR UNIT
OUTDOOR U.
2
1
L
INDOOR U.
OUTDOOR U.
L
INDOOR U.
OUTDOOR U.
2
1
1
2
REFRIGERANT CONNECTIONS
DISTANCES BETWEEN UNITS
19
COOLING
ONLY
HEAT
PUMP
(gr.) (*)
(gr.) (*)
MODEL
(gr.) (**) (gr.) (***)
(gr.) (**) (gr.) (***)
54
3
2,8
(gr.) (*)
(gr.) (*)
MODEL
(gr.) (**) (gr.) (***)
(gr.) (**) (gr.) (***)
54
3
2,8
COOLING
ONLY
HEAT PUMP
1.650
30
2.500
30
2.600
30
2.600
55
45 45 45
3.500
105
1.775
2.500 2.800
5555
5555
2.255
30
2.350303.070304.950
55
45 45 45
5.300
105
2.425 2.525 3.400
55
0
5
5/0
5
0/5
5
REFRIGERANT CHARGE
(*) Refrigerant charge R-22 precharge from factory on the outdoor unit.
(**) Meter of installation line where outdoor unit is precharged+charge also to the group (***) If line is different to meters indicated on table put more or less charge of refrigerant per meter indicated.
Charge precharge on outdoor unit Charge per line 55gr/m x (6-5)m==
5300
55
T otal charge of the installation = 5355
gr
If you need to install a group WING 5CFK, with distance of line between indoor and outdoor unit of 6 meter. The refrigerant charge R-407C needed in the installation is:
EXAMPLE:
OUTDOOR UNITS TYPE KJF-K/ KJB
OUTDOOR UNITS TIPO KCF-K/ KCB
REFRIGERANT CONNECTIONS
20
AIR IN
STANDARD
AIR OUT
STANDARD
AIR IN
OPTIONAL
AIR OUT
OPTIONAL
A B
C
KCF-K KCB-S
A B C
2,8-3
4 5
KCF / KCB-S- 2,8 - 3
A
B
490
1050
750 505
1100
841
525
1300
830 525
1300
890
575
1300
830 575
1300
890
1064
660
Dimensions recommended on
point A and B are refered to the
hole of support of the unit.
Use 4 rod of a diameter of 10mm if the unit is fixed in the roof , or screw M.10 if the unit is fixed on the ground.
A
C
B
C
A
B
B
A
A
B
C
B
B
A
DIMENSIONS OF OUTDOOR UNIT WITH CENTRIFUGAL FAN (mm.)
MODELS
KCF-K / KCB-S 2,8-3
MODELS
KCF-K / KCB-S- 4-5
SETTING UP TEMPLATE (mm) UNITS 2-2,5-2,8-3
MAXIMUM DIMENSIONS
21
AIR IN STANDARD
In the electrical box is included the mechanism of high pressostat rearm.
ACCESS TO ELECTRICAL BOX
1
2
3
4
5
6
7
8
13
10
15
1514
14
12
3
9
10
11
12
4
3
6
8
10 11 12 13 14
15
POSICIÓN STANDARD
POSICIÓN OPCIONAL
POSITION STANDARD POSTION OPTIONAL
DRAINGE ( O 16 EXTERNAL) REARM ON ON HIGH PRESSOSTAT INTAKE PRESSURE (MOD.2,8-3) CONDENSATE PUMP AIR OUT
AIR IN
FAN EXCHANGER COMPRESSOR CONNETION PIPE ACCESS PANEL TO COMPRESSOR AND PIPES COMPONENTS ELECTRICAL BOX ACCESS PANEL TO ELECTRICAL BOX MAIN SWITCH (OPTIONAL) ELECTRICAL SUPPLY ENTRY ELECTRICAL SUPPLY
1 2 3 4 5 6
7 8
9
DESCRIPTION OUTDOOR UNIT KCF-K / KCB 2,8-3
22
2
3
4
5
7
8
10
6
9
11
12
3
9
1
6
8
11
6
12
5
9
8
10
POSICIÓN STANDARD POSICIÓN OPCIONAL
POSITION STANDARD POSTION OPTIONAL
8
9
10 11
12
AIR OUT
AIR IN
DRAINGE ( O 16 EXTERNAL) ELECTRICAL SUPPLY ENTRY ELECTRICAL SUPPLY MAIN SWITCH (OPTIONAL)
FAN EXCHANGER COMPRESSOR ELECTRICAL BOX CONNETION PIPE ACCESS PANEL TO COMPRESSOR AND PIPES COMPONENTS ACCESS PANEL TO ELECTRICAL BOX
1 2 3 4 5 6
7
DESCRIPTION OUTDOOR UNIT KCF / KCB-S 4 - 5
23
KCF-K / KCB 3S
A
B
C D
E
F
G
H
J
K
L M
KCF-K / KCB 4S
N
KCF-K / KCB 5S
350
470
1050 490
36,5
400
45.5
35,5
147
53,5
750 332,5
500 375 1300 525 36 432 195 110 65 35,3 830 50
---
293,4
500 375 1300 575 36 432 195 110 65 35,3 830 50 293,4
T o change entrances from standard position to optional position, you must sustitute the entrance panel correspondent, and refixe using the same fixation screw.
K
N
B
H
C
D
F
G
A
RETURN AIR
SUPPLY AIR
E
N
K
B
J
L
L
D
F
M
A
RETURN AIR
E
D
SUPPLY AIR
MODELS 4-5
E
F
K
B
J
L
D
SUPPLY AIR
L
D
F
M
A
RETURN AIR
E
E
F
K
B
H
C
D
E
F
G
A
25
RETURN AIR
SUPPLY AIR
E
RETURN AIR
STANDARD
RETURN AIR
OPTIONAL
SUPPLY AIR STANDARD
SUPPLY AIR
OPTIONAL
RETURN AIR
STANDARD
SUPPLY AIR STANDARD
RETURN AIR
OPTIONAL
SUPPLY AIR OPTIONAL
MODELS 2,8-3
ENTRANCE OPTIONAL (TO BE REALISE BY THE INSTALLATOR
ENTRANCE STANDARD
ENTRANCE STANDARD/ OPTIONAL OUTDOOR UNIT KCF-K / KCB
ENTRANCE STANDARD
ENTRANCE OPTIONAL (TO BE REALISE BY THE INSTALLATOR)
24
Ø 12
G
E
E
FF
LTX 3 LTX 5
B C
D
E
A
F
G
H I
J K
L
M N
G
D
F
F
L
N
M
E
J
H
G
D
F F
E
LTX 5
LTX 3
J
K
L
N
M
I
A B C D E F
G
KJF-2.8K
KJB-2.8
KJF-3K KJF-4K
KJB-4
KJF-5K
KJB-5KJB-3
656
756
1.104
1.330
1.076
807
223
1.409 268
1.719
14
261,5
359,5
383
267,5
312,5
177,5
177,5
52
78
460 508
653
753
162,5
213
131 157
973 781 333
973 973 973 1.005
1.035 1.035 1.330
333
333
333 386
620 620
620
620 602
198
343,5
410
343,5343,5343,5
10 10 1010
10
176,4 176,4 176,4 176,4
1.035
973
333 620
343,5
10
176,4
781
(**)
ALWAYS KEEP
FREE
FLOOR MOUNTED
A
C
B
Min. 1
0
0 (**)
D
KJF-K
KJB
A
Min. 300 (**)
B
C
KJF-K
KJB
Min. 300 (**)
Min. 150 (**)
DIMENSIONS AND SETTIING UP TEMPLATES OF OUTDOOR UNIT WITH AXIAL FAN
DIMENSIONS AND SETTING TEMPLATES OF INDOOR UNIT LTX
OUTDOOR UNIT
FLOOR MOUNTED
25
LTX 3
LTX 5
X
Y
X
Y
1.321 mm
562 mm
1.630 mm
670 mm
To remove the casing, slide them over the rolling sides and remove horizontally (See picture A).
Remove the AIR VANES by moving them in the opposite direction of the air sweep motor until they come out, then release the central fixing clip, so that the AIR SWEEP is removed giving better access to the top of the unit (See picture B).
Install the unit with the M-8 screws, always use washers. Fix the screws following the pattern on page 26. Check the strength of the screws to avoid movement of the indoor unit when removing the side and cover panel.. See picture C
A
B
C
D
INSTALLATION UNIT Install the unit in a way that the discharge air would not be direct to persons, differences of temperature can create disturbs.
Keep in mind in the installation of the unit, some ambient can supply electromagnetic radiation that can affect the good function of the unit, follow then the following instruction recommended in this document.
OPENING IN FLASE CEILING
Always install the filters. If the unit operates without filters there is a risk of damage in the indoor unit from dust..
Min. 100 mm.
A
B
C
D
AIR-SWEEP
Rolling sides
Filters
Sides and carcass
INSTALLATION INDOOR UNIT
26
LTX 3
To remove the casing, slide them over the rolling sides and remove horizontally Remove the filters. Remove drain pan. Introduce the electrical heater kit rods in the holes of one side of the coil and fix with screws on the other. Fix the contactor to the fan deck.
NOTE: The safety thermostat must always be at the top of the heater.
BEFORE ATTEMPTING TO PERFORM ANY SERVICE OR MAINTENANCE, TURN OFF
THE ELECTRICAL POWER, AND CHECK THAT THE FAN HAS STOPPED
Electric heat
Drain pan
Rolling side
Filters
Sides and carcass
Contactor
Contactor
Fan
LTX 5
Contactor
Electric Heat
Fan
Electric Heat
1 2 3 4 5
ELECTRICAL HEATER
FIG 1
INDOOR UNIT OPTIONALS
27
MAIN SWITCH The main swicth is located on the access panel to the electrical box, in such a way that the unit is disconnected when the panel is opened, for the models KCF and KCB. (Refer to the size diagram on pages 25 to 30, to see the position of the electrical box access panel)
KIT GRID OF TAKES OF FOREIGN AIR Field assembly. This kit is comprised of an air filter and grille for outdoor air intake which should be installed on the suction side of the outdoor unit.
WINTER CONTROL
The low ambient kit should be fitted to the cooling units, when the outdoor temperature is lower then 19 ºC. in cooling cycle.Keeps condensing temperature constant aprosimatelly 40ºC.
OUTDOOR UNIT OPTIONALS
28
1.- Unit do not work.
• Check electrical supply of the unit.
• Check electrical connexion.
• Check the remote controller and parameter works correctly.
2.- The fan of the unit works quicker without any 
• Check that the filter of the unit is clean.
• Check electrical connexion.
• If the problem persist, check the function of the motor.
3.- Noise on pipe system. NOTE: Some noises are normal when unit stop and 
• Check refrigerant charge is correct.
• Was the vacuum done correctly?
• Check internal temperature, could be quite low.
5.- The indoor battery freeze continuously.
• Check the air filter of the indoor unit.
• Check the level of refrigerant.
• Check strangulation air flow or recirculation.
• If the freeze persist the expansion can be obstructed.
• ¿Is the temperature below 21 º C?
• Check indoor temperature sensor.
4.- Excess of condensation 
• Check if you have configurate correctly the function mode of the unit.
• Check inverter valve of the outdoor unit.
• Check the plate PCB to the solenoid inverted valve.
6.- Unit work perfectly on cooling mode, but do not produce heat on mode heat 
• Check possible obstructions in the condensate pan, and also out of the pan.
• Check correct level of the unit.
• Check drainage pipe.
PROBLEM SOLUTION
7.-External fan stop
8.-Excessive pressure of condensation (Working cooling cycle)
• Check that the external exchanger is not dirty and obstructed.
• Check that there is no condensable gas and air in the refrigerant circuit.
• Check that the external fan works correctly.
• Check that the refrigerant charge is correct
9.-Low pressure condensation. (Working on cooling cycle)
10.-Excessive pressure on return air (Working on heat pump)
11.-Low pressure on return air. (working on heat pump)
• Check that terminal connexion are slack.
• Check the motor.
• Check the condenser situation.
• Check that that the rele of defrost is not activited (Units heat pump).
• Check that the refrigerant charge is correct
• Check possible obstruction on the expansion system of the outdoor unit, liquid 
• Check that air filter is not dirty or wrong function of indoor fan.
• Check that the refrigerant charge is correct
• Check the situation of inverter valve.
• Check retention valve situation.
• Check that the refrigerant charge is correct
• Check possible obstruction on the expansion system of the outdoor unit
• Check that the external fan works correctly.
• Check the correct function of the defrost thermostat .
POSSIBLE PROBLEMS
MAINTENANCE OF THE UNIT
29
The air filter cleaning operations do not require technical service; however when an electrical or mechanical operation is required call an Engineer.
WARNING
Electric shock hazard can cause injury or death. Before attempting to perform any service or maintenance on the unit, turn OFF the electrical power, and check that the fan has stopped.
FILTER CLEANING
Check the air filter and make sure it is not blocked with dust or dirt.
If the filter is dirty, wash it in a bowl with neutral soap and water, drying it in the shade before inserting it in the unit.
Standard Guidelines to Lennox Refac equipment
All technical data contained in these operating instructions including the diagrams and technical description remains the property of Lennox Refac and may not be used (except for the purpose of familiarising the user with the equipment), reproduced, photocopied, transferred or transmitted to third parties without prior written authorisation from Lennox Refac.
The data published in the operating instructions is based on the latest information available. We reserve the right to make modifications without notice.
We reserve the right to modify our products without notice without obligation to modify previously supplied goods.
These operating instructions contain useful and important information for the smooth operation and maintenance of your equipment.
The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault-free operation. Read the operating instructions carefully before starting the equipment, familiarise yourself with the equipment and handling of the installation and carefully follow the instructions. It is very important to be properly trained in handling the equipment. These operating instructions must be kept in a safe place near the equipment.
Like most equipment, the unit requires regular maintenance. This section concerns the maintenance personnel and management. If you have any queries or would like to receive further information on any aspect relating to your equipment, do not hesitate to contact us.
Risk of injury with
rotating objects
Low
temperatures
High
temperatures
Risk of injury with
moving objects
Electrical
voltage
Abrasive surfaces
POINTS TO KEEP IN MIND
30
www.Lennoxeurope.com
LENNOX BENELUX N.V./S.A. tél. : + 32 3 633 30 45 fax : + 32 3 633 00 89 e-mail : info.be@lennoxbenelux.com
LENNOX JANKA tél. : + 420 2 510 88 111 fax : + 420 2 579 10 393 e-mail : janka@janka.cz
LENNOX FRANCE tél. : + 33 4 72 23 20 20 fax : + 33 4 78 20 07 76 e-mail : accueil@lennoxfrance.com
LENNOX DEUTSCHLAND GmbH tél. : + 49 69 42 09 79 0 fax : + 49 69 42 09 79 40 e-mail : info.de@lennoxdeutschland.com
LENNOX DISTRIBUTION tél. : + 971 4 262 9309 fax : + 971 4 266 7082 e-fax : + 1 240 368 73 62 Mobile : 971 50 4510669 e-mail : mmrifal@emirates.net.ae
LENNOX BENELUX B.V. tél. : + 31 33 2471 800 fax : + 31 33 2459 220 e-mail : info@lennoxbenelux.com
LENNOX POLSKA Sp. z o. o. tél. : + 48 22 832 26 61 fax : + 48 22 832 26 62 e-mail :
info@lennoxpolska.pl
LENNOX CLIMATIZAÇAO LDA. tél. : +351 22 999 84 60 fax : +351 22 999 84 68 e-mail : info@lennoxportugal.com
LENNOX DISTRIBUTION MOSCOW tél. : + 7 095 246 07 46 fax : + 7 502 933 29 55 e-mail : lennox.dist.moscow@mtu-net.ru
LENNOX SLOVAKIA tél. : + 421 2 44 87 19 27 fax : + 421 2 44 88 64 72
LENNOX REFAC S.A. tél. : + 34 915 40 18 10 fax : + 34 915 42 84 04 e-mail : marketing@lennox-refac.com
LENNOX DISTRIBUTION KIEV tél. : + 380 44 213 14 21 fax : + 380 44 213 14 21 e-mail : jankauk@uct.kiev.ua
LENNOX INDUSTRIES LTD tél. : + 44 1604 599400 fax : + 44 1604 594200 e-mail : marketing@lennoxind.com
tél. : + 33 4 72 23 20 14 fax : + 33 4 72 23 20 28 e-mail : marketing@lennoxdist.com
BELGIUM :
CZECH REPUBLIC :
FRANCE :
GERMANY :
MIDDLE EAST :
NETHERLANDS :
POLAND :
PORTUGAL :
RUSSIA :
SLOVAKIA :
SPAIN :
UKRAINE :
UNITED KINGDOM :
OTHER EUROPEAN
COUNTRIES, AFRICA,
LENNOX DISTRIBUTION :
MIL55S-101 05-2001
Loading...