THIS MANUAL MUST BE LEFT WITH THE OWNER FOR
FUTURE REFERENCE
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Improper installation, adjustment, alteration, ser vice
or maintenance can cause property damage, personal
injury or loss of life.
Installation and service must be performed by a licensed professional HVAC installer, service agency
or the gas supplier.
Failure to follow safety warnings and these instructions exactly could result in property damage, dangerous operation, serious injury, or death.
Any additions, changes, or conversions required in
order for the appliance to satisfactorily meet the application needs must be made by a licensed professional HVAC installer (or equivalent) using factoryspecifi ed parts.
Do not use this system if any part has been under
water. A fl ood-damaged appliance is extremely dan-
gerous. Immediately call a licensed professional
HVAC service technician (or equivalent) to inspect
the system and to replace all controls and electrical
parts that have been wet, or to replace the system, if
deemed necessary.
The State of California has determined that this
product may contain or produce a chemical or
chemicals, in very low doses, which may cause
serious illness or death. It may also cause cancer,
birth defects, or reproductive harm.
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal edges.
Be careful when you handle this equipment.
Dallas, T exas, USA
!
WARNING
!
CAUTION
INSTALLATION
INSTRUCTION
VWMA Wall-Mounted Units
VRF SYSTEMS -- Indoor Units
507462-02
10/2015
IMPORTANT!
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFCs, HCFCs and HFCs)
as of July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines and/
or incarceration may be levied for noncompliance.
These units must be installed as a part of a matched
system as specifi ed in the Product Specifi cations
(EHB) bulletin.
General
The VWMA wall-mounted indoor units are matched with an
outdoor heat recovery or heat pump unit to create a VRF
(variable refrigerant fl ow) system that uses HFC-410A
refrigerant.
Refer to the Product Specifi cation bulletin (EHB) for the
proper use of these indoor units with specifi c heat pumps,
heat recovery units, mode switching devices, branch
pipes, line sets and controls.
These instructions are intended as a general guide and do
not supersede local or national codes in any way.
Authorities having jurisdiction should be consulted before
installation.
Shipping and Packing List
Check the components for shipping damage. If you fi nd any
damage, immediately contact the last carrier.
Package 1 of 2 contains the following:
1 - Assembled indoor unit with mounting bracket
8 - Mounting bracket securing screws
8 - Plastic screw anchors
1 - Roll tape
1 - Flexible condensate drain pipe
1 - Wall sleeve
1 - Plastic cover for wall sleeve
1 - Resistor
1 - Brass fl are nut
1 - Installation manual
Not for use with V0CTRL90 Auxiliary Heat Relay.
See Service and Application Note VRF-15-01.
1
Page 2
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD.
Do not touch the unit or the controller if your hands are wet.
DO NOT spray water on the indoor unit for any reason.
Do not replace a fuse with a fuse of a different rating. Do not use a jumper wire to replace a fuse. Do not insert
your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit.
Do not allow children to operate the system.
Vertical Clearance - Clearance to Floor - 72 inches (1829 mm) Minimum
NOTE - Provide 96 inches (2438) clearance to floor for best performance
WALL
5
(127)
Minimum
Indoor Unit Placement
!
WARNING
Do not install the unit in an area where fl ammable
materials are present due to risk of explosion
resulting in serious injury or death.
If the basis underneath the unit is not strong enough
to support the weight of the unit, the unit could be fall
out of place and cause serious injury.
Use the provided and specifi ed components when
installing equipment. Failure to do so may result
in unit falling, water leaking or electrical shocks,
causing personal injury or equipment or property
damage. Check stability of wall-mounted unit
support. If support is not capable of carrying weight
of the unit, unit may fall causing personal injury or
equipment damage.
Consider the possibility of earthquakes in your
area when installing the equipment. If the unit is not
correctly secured, it may fall, causing personal injury
or equipment damage.
Safely dispose of packing materials, which include
nails, wood and other sharp objects, as well as plastic
wrapping. Children playing with plastic wrap or bags
risk the danger of suffocation.
!
CAUTION
Do not place items which may be damaged by water
under or around the indoor unit.
The unit should be installed at least 8 feet above the
fl oor (if possible) to ensure maximum performance
and comfort.
AVOID
Do not install the unit in the following locations:
• Areas exposed to salt or other corrosive materials or
caustic gases
• Areas exposed to extreme voltage variations (such as
factories)
• Tightly enclosed areas that may impede service of the
• unit.
• Areas exposed to strong electromagnetic forces
• Areas exposed to acids or alkaline detergents (laundry
• rooms)
DO:
• Locate the unit so that it is not exposed to direct sunlight.
• Locate the indoor unit so that the room can be uniformly
cooled. Install unit as high as possible on the wall (8
feet above fl oor, if possible) for best performance.
• Select a wall location that can support the weight of the
unit.
• Select a location where condensate line will have the
shortest run to a suitable drain per local codes.
• Allow suffi cient space around unit for proper operation
and maintenance (fi lter must able to be removed from
the top-front of the unit).
• Install the indoor unit a minimum of 3 feet away from
any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference and
radio frequencies from any of these sources may affect
operation.
4
Page 5
DETERMINING WALL MOUNTING PLATE LOCATION
1. Remove the wall mounting plate from the back of the
indoor unit.
Left piping
Left back piping
Right back piping
Right piping
Figure 1. Determining Exit Locations
2. Determine the best exit location for utility bundle (line
set, condensate line and wiring).
3. Position the wall mounting plate on the wall so that,
when installed, the unit will be at least 6 inches (152
mm) from the ceiling and 5 inches (127 mm) from the
wall on either side. The wall mounting plate must be
level side-to-side.
4. Use the wall mounting plate as a template to determine
the exit point for utility bundle. Mark the wall to facilitate
drilling hole for utility bundle.
Installation
WALL MOUNTING PLATE INSTALLATION
Install the wall mounting plate so that it is correctly positioned
horizontally and vertically. The indoor unit must be installed
level on the wall to allow proper condensate drainage.
1. Use a carpenter's level or measuring tape to verify the
wall mounting plate is horizontally level.
2. Secure the wall mounting plate to the wall using the
provided screws and screw anchors. NOTE - It is
important to use all screws provided to secure the wall
mounting plate to the wall. Additional holes may be
drilled through the metal wall mounting plate to better
secure wall plate. Field-provided anchors/fi xings may
be required depending on wall construction. Use the
appropriate type of anchors for the application.
3. The wall mounting plate must be installed fl ush against
the wall so that the indoor unit will be fl ush after
installation. Any space between the wall and unit will
cause noise and vibration.
4. The wall mounting plate must be installed horizontally
level on the wall.
VWMA007S4, VWMA009S4 and VMWA012S4 Units
Wall Mounting Bracket
Outline of Indoor Unit
VWMA015S4 and VWMA018S4 Units
Wall Mounting Bracket
Outline of Indoor Unit
VWMA024S4 and VWMA030S4 Units
Wall Mounting Bracket
Outline of Indoor Unit
Figure 2. Wall Mounting Brackets
5
Page 6
WALL SLEEVE INSTALLATION
The utility bundle may be routed out of the back of the unit
or out either side. If the bundle is to be routed out the back
through an external wall, use a fi eld-provided wall sleeve to
protect the utility bundle. NOTE - If the utility bundle will be
routed out the side of the indoor unit and up the wall above
a false ceiling, continue to the next section.
1. Prior to making the hole and installing the wall sleeve
for the utility bundle, check to ensure that there are no
other utilities located in the wall behind the hole location.
!
WARNING
Electric Shock Hazard. Can cause injury or death.
Avoid location where electric wiring or conduits may
be present inside the wall.
2. Cut a hole in the wall using a suitable hole saw. Hole
should be at a slight downward slant - 3/16” to 3/8”
toward the outdoor side.
INSIDE
OUTSIDE
Typical
installation
procedure
shown.
Figure 3. Boring Hole for Wall Sleeve
INSTALL UNIT ON WALL MOUNTING PLATE
1. A length of fi eld-provided fl exible condensate piping
should be connected to the drain prior to securing the
unit to the wall mounting plate.
2. If the factory-provided refrigerant piping connections
and fi eld-provided fl exible condensate piping are long
enough to enable fi nal fi eld connections after unit is
installed on wall mounting plate, use fi eld-provided tape
to bundle them together.
3. The utility bundle may be routed out of the back of the
unit or out either side. If the bundle is to be routed
out the back through an external wall, feed the utility
bundle through the wall sleeve. If the utility bundle is
to be routed out of the side of the indoor unit and up
an inside wall, carefully form the utility bundle so that it
makes a gentle 90° turn.
4. Align the back of the indoor unit with the hooks at the
top of the wall mounting plate. Move the unit from side
to side to make sure that it settles securely.
5. The bottom of the unit can be lifted to facilitate refrigerant
piping and condensate drain connections, if necessary.
See fi gure 6.
HOOKS AT TOP
OF MOUNTING
BRACKET
TEMPORARY
SPACER
(To facilitate
connections)
3. Measure the thickness of the wall from the inside edge
to the outside edge and cut the fi eld-provided wall
sleeve at a slight angle 1/4” (6 mm) shorter than the
thickness of the wall.
USE SUITABLE TOOL TO CUT PVC FOR WALL
SLEEVE AT SLIGHT ANGLE AS SHOWN.
Figure 4. Cutting PVC for Wall Sleeve
4. Place the provided plastic cover over the end of the
pipe that will be visible from the inside wall and insert
the pipe in the wall.
NOTE - When passing bundled services through an exterior
brick or concrete wall, protect the copper pipes and wiring
from the effects of these construction materials by using a
sleeve made of a suitable material. The integrity of copper
pipe and wiring can deteriorate when exposed to these
construction materials
Figure 6. Secure Unit to Wall Mounting Plate
6
Page 7
Refrigerant Piping Connections
!
WARNING
Refrigerant leaks are unlikely; however, if a refrigerant leak
occurs, open a door or windows to dilute the refrigerant
in the room. Turn of f the unit and all other appliances that
may cause a spark. Call a licensed professional HVAC
technician (or equivalent) to repair the leak.
Use only R410A refrigerant to charge this system. Use of
other refrigerant or gas will damage the equipment.
Do not allow air or other contaminants to enter system
during installation of refrigerant piping. Contaminants
will result in lower system capacity and abnormally high
operating pressures and may result in system failure or
explosion.
Insulate all refrigerant piping.
Refrigerant pipes may be very hot during unit operation.
Do not allow contact between wiring and bare copper
pipes.
After refrigerant piping connections have been completed,
check the system for leaks per commissioning instructions.
Field piping consists of two copper lines connected to the
indoor unit. Table 1 lists the connection sizes at the indoor
unit. The connections are made using the provided brass
fl are nuts at the end of the refrigerant piping connections.
Both lines must be individually insulated.
1. The seal on the unit refrigerant piping connections
should remain in place until the last possible moment.
This will prevent dust or water from getting into the
refrigerant piping before it is connected.
2. CAREFULLY adjust refrigerant piping connections to
suit the application (straight back, right or left).
3. Slowly loosen one of the fl are nuts to release the factory
nitrogen charge.
4. Remove the fl are nuts from the connections on the unit
and discard the seal from each of the piping connections.
5. Slide the fl are nuts onto the ends of the fi eld-provided
refrigerant piping before using a suitable fl aring tool to fl are the end of the copper pipe.
6. Apply recommended HFC-410A refrigerant lubricant to
the outside of the fl ared refrigerant lines (fi gure 7-A).
Table 1. Refrigerant Piping Connections
Size
(Btuh)
7000
12000
15000
18000
24000
30000
36000
48000
A
Liquid Line
in.
1/41/2
3/85/8
CANT ON THE OUTSIDE OF
Vapor Line
THE FLARE
MALE FLARE
CONNECTION
in.
B
Figure 7. Making Connections
(Male to Female Connection)
7. Align the threaded connections with the fl ared refrigerant
lines. Tighten the fl are nuts lightly at fi rst to obtain a
smooth match (fi gure 7-B).
8. Once snug, continue another half-turn on each nut
which should create a leak-free joint. A torque wrench
may be used to tighten fl are nuts using table 2
recommendations. See fi gure 4. Do not over-tighten
a fl ared joint. Flared connections should always
be accessible and must be insulated to prevent
condensation.
9. After refrigerant piping has been installed and checked
for leaks, apply insulation over the connector pipe and
all fl ared connections.
IMPORTANT!
The compressor in this unit contains PVE
oil (Polyvinylether). PVE oil is formulated for
hydrofl uorocarbon (HFC) refrigerants, such as R-
410a, which this system contains. While it may have
some miscibility properties with mineral-based oil
and POE oil (Polyolester), it is not recommended to
mix PVE oil with any other type of refrigerant oil.
IMPORTANT!
Always use two wrenches when tightening fl are
nuts to avoid twisting refrigerant piping. DO
NOT over-tighten fl are nuts.
Flared connections should always be accessible and must be insulated to prevent condensation. See fi gure 9.
INSULATE ALL FLARED CONNECTIONS
TO PREVENT CONDENSATION
1. Make a water-tight connection between the fi eld-
provided condensate drain line and the fl exible
condensate connector.
2. See fi gure 10 for applications including a single unit
and a single drain. In this case, ensure that the drain
line is properly sloped (no less than 1/4 inch per foot)
and condensate lines are routed to ensure moisture is
drained away from the indoor unit.
3. Drain should be as short as possible and should not have
any droops or kinks that would restrict condensate fl ow
and shall be approved resistant pipe. There must be
a 2-inch space between the end of the condensate
drain and the fi nal termination point (ground, open
drain, etc.) to ensure that the line will drain freely.
4. After system installation is complete, the condensate
drain line must be checked for leaks. This check is
part of the commissioning sequence. If a fi eld-provided
condensate pump has been installed, it must be
checked to ensure proper operation. This check is part
of the commissioning sequence.
UNIT
BASE
Figure 9. Insulate Flared Connections
Condensate Piping Connections
!
CAUTION
Make sure that drain piping is properly routed
and insulated in order to prevent both leaks and
condensation.
IMPORTANT!
Drain should have a slope of at least ¼ inch per
foot and should be approved corrosion-resistant pipe.
You must confi rm operation of every drain and
pump in the system as part of the commissioning procedure.
3 ft. (1 m)
SUPPORT
STRAPS
DRAIN LINE
Figure 10. Condensate Drain Piping
8
Page 9
Wiring Connections
!
WARNING
Isolate the power supply before accessing unit
electrical terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this
installation instruction, during installation. Do NOT
overload electrical circuit, as this may lead to failure
and possible fi re.
Use specifi ed wiring and cable to make electrical
connections. Clamp cables securely and make sure
that connections are tight to avoid strain on wiring.
Insecure wiring connections may result in equipment
failure and risk of fi re.
Wiring must be installed so that all cover plates can
be securely closed.
!
CAUTION
This unit must be properly grounded and protected
by a circuit breaker. The ground wire for the unit must
not be connected to a gas or water pipe, a lightning
conductor or a telephone ground wire.
Do not connect power wires to the outdoor unit until
all other wiring and piping connections have been
completed.
Install all wiring at least 3 feet away from televisions,
radios or other electronic devices in order to avoid
the possibility of interference with the unit operation.
Do not install the unit near a lighting appliance that
includes a ballast. The ballast may affect remote
control operation.
1. Lift indoor unit front panel to access the control box
over. Remove the screw(s) securing the cover. Remove
the plate.
2. Locate the terminal strip in the control box. Connect the
power wiring (sized per NEC/CEC and local codes) and
communications cable (three-conductor, shielded cable). Refer to unit nameplate for rated voltage.
3. If the indoor unit is the fi nal unit in a group that is wired
in series, install the provided resistor across terminals
P and Q.
4. Remove spacer. Secure bottom of unit to wall mounting
bracket. Continue with installation of outdoor unit and
system commissioning.
POWER WIRING
COMMUNICATIONS
WIRING
CONTROL BOX
COVER
Figure 11. Accessing Control Box
Network Address and Commissioning
After the system has been installed, each indoor unit must
be assigned an address as part of the commissioning
procedure.
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to unit nameplate for minimum circuit ampacity and
maximum overcurrent protection size.
NOTE - Three-conductor shielded cable must be used for
the communication wiring. This is necessary to ensure
proper system communication and operation.
9
Page 10
TR
CN2
(RED)
ANION
CN21
Y/G
GROUND
WHITE(GRAY)
C
WHITE
CN20
(BLUE)
FM
CN4
(WHITE)
Y/G
GROUND
ON
EEV
CN15
GMGM
CN5
DISPLAY BOARD
CN1CN2
WIRED
CONTROLLER
HEAT
DM
XP2
XS2
RED
BLUE
XT1
L1
L2
INDOOR UNIT POWER
208-230V
CN3
(WHITE)
CN7
(WHITE)
CN24
(WHITE)
CN1
(BLUE)
Z
SW6ENC1
POWER_S
MAIN CONTROL BOARD
HEAT_LHEAT_N
SW1
SW2
CN10WHITE
ONONON
SW5
J1J2
(WHITE)
CN19
CN14
YELLOW
CN13
YELLOW
CN17
(WHITE)
CN16
(RED)
CN9
CN8
XS1XP1
XY
REMOTE
ON / OFF
WEEKLY TIMER
(E)
P
TROLLER
Q(E)
XT2
Y/G
Y/G
GROUND
T1
WHITE
T1
BLACK
CONNECT TO
WIRED CONTROLLER
T2B
T2
CONNECT TO
OUTDOOR
UNIT
KEY
FM
EEV
EXPANSION VALVE
INLET AIR TEMP.
T1
EVAP OUTLET TEMP.
T2B
(COOLING MODE)
T2
XP1-7
XS1-
7
TR
XT1-2
TERMINAL BLOCK
WATER LEVEL SWITCH
CS
C
GM
DM
AUXILIARY HEATER
HEAT
ANION
ANION GENERATOR
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 12. Typical VWMA007 to 018 Wiring Diagram
COMPONENT
INDOOR FAN
ELECTRONIC
COIL TEMP.
PLUG
JACK
TRANSFORMER
FAN CAPACITORFAN CAPACITOR
SWING MOTOR
PUMP MOTOR
NOTE - Dashed line indicates optional or fieldwired components.
NOTE - If indoor unit is the final unit in a group
wired in series, install provided resistor across
terminals P and Q.
NOTE - Use 3-conductor, shielded cable for
communication wiring.
10
Page 11
DM
WHITE(GRAY)
C
WHITE
FM
REMOTE
ON / OFF
ON/OFF
DISPLAY BOARD
CN1CN2
Y/G
EEV
XS5
XP5
GROUND
XS1
XP1
ON
SW6
ENC1
POWER_S
GMGM
CN5
CN14
COMON/OFF
XP8
XS8
BLACK
T2B
CN9
(YELLOW)
XP6
XP7
XS7
XS6
WHITE
T2
T1
CN8
XP3
XS3
WIRED
CONTROLLER
XP4
XS4
TR
RED
BLUE
Z
XT1
L2
L1
INDOOR UNIT POWER
208-230V
CN15
EEV
CN10WHITE
(WHITE)
(RED)
XP1
XS1
WEEKLY TIMER
TROLLER
MAIN CONTROL BOARD
(RED)
(BLUE)
CN1
Y/G
Y/G
GROUND
CN24
(WHITE)
(YELLOW)
CN6
AL
(BLUE)
(WHITE)
ON
SW2SW5
ONON
XT2
J1J2
CONNECT TO
WIRED CONTROLLER
(E)
PQXY
CONNECT TO
OUTDOOR
UNIT
HEAT_LHEAT_N
XS2
XP2
CN3
(WHITE)
ON
SW1
KEY
FM
EEV
EXPANSION VALVE
INLET AIR TEMP.
T1
EVAP OUTLET TEMP.
T2B
(COOLING MODE)
T2
XP1-7
7
XS1-
TRANSFORMER
TR
XT1-2
TERMINAL BLOCK
WATER LEVEL SWITCH
CS
C
FAN CAPACITORFAN CAPACITOR
GM
DM
AUXILIARY HEATER
HEAT
AL
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 13. Typical VWMA024 to 030 Wiring Diagram
COMPONENT
INDOOR FAN
ELECTRONIC
COIL TEMP.
PLUG
JACK
SWING MOTOR
PUMP MOTOR
ALARM
NOTE - Dashed line indicates optional or fieldwired components.
NOTE - If indoor unit is the final unit in a group
wired in series, install provided resistor across
terminals P and Q.
NOTE - Use 3-conductor, shielded cable for
communication wiring.
11
Page 12
Outdoor unit
(main unit)
Outdoor unit
(sub1 unit)
Outdoor unit
(sub2 unit)
(H1 H2 E)
(PQE)
(H1 H2 E)(H1 H2 E)
(PQE)
Ground cable shield
DO NOT connect to E
(PQE)
MS
Box
(PQE)
MS
Box
(PQE)
P Q
Install a terminating resistor at the last indoor unit terminals P and Q of the daisy
chain and for each individual unit when connected directly to an MS Box port.
All shields of shielded cable connect to GROUND terminal,
not to terminal E.
18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive).
Typical Wiring Diagram, NEC/CEC and Local Codes apply.
NOTE - Each communication wire from the MS box should follow the refrigerant piping for that port.
Figure 14. Typical Communication Wiring Diagram (VRF Heat Recovery System)
12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.