Lennox VRB096, VRB168, VRB216, VRB192, VRB240 Installation & Operation Instructions

...
INSTALLATION/OPERATION
VRF
INSTRUCTIONS
©2018 Lennox Industries Inc. Dallas, Texas, USA
OWNER FOR FUTURE REFERENCE
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
!
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency. Failure to follow safety warnings and these instruc tions exactly could result in property damage, dan gerous operation, serious injury, or death. Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the ap plication needs must be made by a licensed profes sional HVAC
installer (or equivalent) using factory-specied
parts. Do not use this system if any part has been
under water. A ood-damaged appliance is
extremely dan gerous. Immediately call a licensed professional HVAC service technician (or equivalent) to inspect the system and to replace all controls and electrical parts that have been wet, or to replace the system, if deemed necessary.
VRB Heat Recovery
VRF SYSTEMS OUTDOOR UNITS 507885-03 05/2019
!
WARNING
Do not change the settings of any protection devices installed in the outdoor unit. If the pressure switch, thermal switch, or other protection device is shorted or forcibly
operated, re or explosion may occur. Do not use parts other than those specied by Lennox or re and/or explosion may occur.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for non-
compliance. These units must be installed as part of a
matched system as specied in the Product Specications (EHB) bulletin.
General
The VRB heat recovery outdoor units are matched with up to 64 indoor units per system to create a VRF
(variable refrigerant ow) system that uses HFC-
410A refrigerant.
Refer to the Product Specication bulletin (EHB)
for the proper use of these heat recovery units with
matching indoor units, mode selection boxes, branch pipes, line sets and controls.
Shipping and Packing List
Check the components for shipping damage. If you nd any damage, immediately contact the last car­rier. Package 1 of 1 contains the following: 1 - Assembled VRB heat recovery outdoor unit 1 - Outdoor unit installation instruction 1 - Piping accessory package
1
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Do not touch the unit or the controller if your hands are wet.
Do not operate appliances with an open ame near the unit. Do not replace a fuse with a fuse of a di󰀨erent rating. Do not attempt to bypass a fuse.
Do not insert your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit. Do not allow children to operate the system.
Model Number Identication
V R B 072 H 4 M -3 Y
Brand/Family
V = Variable Refrigerant Flow (VRF)
Unit Type
R = Heat Recovery Outdoor Unit
Major Design Sequence
B = 2nd Generation
Nominal Cooling Capacity - Tons 072 = 6 Tons
096 = 8 Tons 120 = 10 Tons 144 = 12 Tons 168 = 14 Tons 192 = 16 Tons 216 = 18 Tons 240 = 20 Tons 264 = 22 Tons
288 = 24 Tons 312 = 26 Tons 336 = 28 Tons 360 = 30 Tons 384 = 32 Tons 408 = 34 Tons 432 = 36 Tons 456 = 38 Tons 480 = 40 Tons 504 = 41 Tons
Voltage
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz
Controls Protocol
3 = Phase 3
Refrigerant Circuits
M = Multiple Circuits
Refrigerant Type
4 = R-410A
Cooling E󰀩ciency
H = High E󰀩ciency
NOTE - Lennox VRF and Lennox Mini-Split products are similar in appearance to each other. Refer to the unit’s model number to determine if the unit is a VRF (V) or Mini-Split (M) unit. It is not possible to mix the two types of equipment on any system.
System Piping
CAUTION
VRF system piping is customized for each installation. The Lennox VRF Selection Software (LVSS) piping report is an
engineered design that must be followed. The piping diagram or diagrams included within the LVSS report have been
prepared based on the information provided to the Lennox VRF applications department. When the indicated lengths change from the gures stated within the report, it is imperative that prior to the commencement
of the refrigerant pipe work installation, Lennox VRF applications department are informed of these proposed changes. Upon receipt of this new information the Lennox VRF applications department will conrm any changes that may be
applicable to this installation. If changes are required, a new piping diagram will be produced and will supersede all other
previously provided documents.
Failure to provide this information regarding changes to the original design may lead to insu󰀩cient capacity, equipment failure, warranty being made void and the refusal to commission the system.
2
Unit Dimensions - inches (mm)
CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
072, 096, 120 121 55 203 92 211 96 251 114 27-3/4 705 12-1/4 311
AA
DD
EE
TOP VIEW
52-3/4 (1340)
BB
FF
CC
CENTER OF GRAVITY
64-3/8 (1635)
BACK VIEW
LAG BOLT DESIGNATION
(BOTH SIDES)
(TO ACCESS LAG BOLT)
PARALLEL MODULE
PIPING KNOCKOUT
FORKLIFT SLOT
REFRIGERANT LINE PATH
FRONT VIEW
(BOTH SIDES)
11-3/4 (298)
53-1/8 (1349)
BASE PAN VIEW
3
LIFTING HOLES
(BOTH SIDES)
(FOR RIGGING)
6-1/4 (159)
18-7/8 (479)
29-7/8 (759)
31-1/2 (800)
SIDE VIEW
29-1/2
(749)
4-1/8 (105)
Unit Dimensions - inches (mm)
CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
144, 168, 192 172 78 264 120 330 150 321 146 37-3/4 953 12 305
AA
DD
EE
TOP VIEW
68-1/2 (1740)
BB
FF
CC
CENTER OF GRAVITY
72 (1829)
BACK VIEW
LAG BOLT DESIGNATION
(BOTH SIDES)
(TO ACCESS LAG BOLT)
PARALLEL MODULE
PIPING KNOCKOUT
REFRIGERANT LINE PATH
FRONT VIEW
FORKLIFT SLOT
(BOTH SIDES)
11-3/8 (289)
68-1/2 (1740)
BASE PAN VIEW
4
6-1/4 (159)
18-7/8 (479)
30 (762)
32-5/8 (829)
SIDE VIEW
29-3/4 (756)
4-1/8 (105)
Dimensions - Piping Details - inches (mm)
Internal valve layouts are the same in both heat
recovery and heat pump units, it is their function that is di󰀨erent. Pay close attention when making nal
piping connections.
Low pressure gas valve
High pressure gas balance valve
Low pressure gas pipe (1-1/8 in. diameter 072-120 sizes) (1-3/8 in. diameter 144-192 sizes)
High pressure gas balance pipe
(3/4 in. diameter)
6-1/4 (159)
5-5/8 (143)
Heat Recovery internal valve layouts are described below. See the Heat Pump installation manual for
heat pump internal valve information.
High pressure gas valve
Liquid side valve
Liquid side valve
Oil balance valve
Liquid side pipe (5/8 in. diameter 072-120 sizes) (3/4 in. diameter 144-192 sizes)
High pressure gas pipe (1-1/8 in. diameter 072-120 sizes) (1-3/8 in. diameter 144-192 sizes)
Oil balance pipe
(1/4 in. diameter)
5
Outdoor Unit Placement Considerations
!
WARNING
Use the provided and specied components
when installing equipment. Failure to do so may result in unit falling, water leaking or electrical shocks, caus ing personal injury or equipment or property dam age. Check stability of unit support. If sup port is not capable of carrying weight of the unit, unit may fall causing personal injury or equipment damage. Safely dispose of packing materials, which include nails, wood and other sharp objects, as well as plastic wrapping. Children playing with plastic wrap or bags risk the danger of
su󰀨ocation.
IMPORTANT!
Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit perfor­mance and longevity.
In addition to clearances, the following items should
be considered when setting the outdoor unit:
2007 EPA Noise Policy. Observe local code adoptions/enforcement as consideration should be used when selecting an outdoor unit’s perma­nent placement. Sound data for each unit can be
found in the Product Specications Document.
Glass has a very high level of sound transmis­sion. When possible, do not install the unit direct­ly outside a window.
Avoid installing the unit in areas exposed to ex-
treme voltage variations (such as factories).
Install unit level.
Allow su󰀩cient space around unit for proper op­eration and maintenance.
Install the outdoor unit a minimum of 3 ft. (1 m)
away from any antenna, power cord (line), radio, telephone, security system, or intercom. Electri-
cal interference and radio frequencies from any
of these sources may a󰀨ect operation.
Outdoor unit shall maintain a minimum distance
of 10 ft. (3 m) from dryer exhaust vents.
Outdoor unit shall maintain a minimum distance of 10 ft. (3 m) from Type 1 kitchen exhaust out­lets.
Coating outdoor coils is recommended in appli­cations installed in coastal regions less than 30
miles (48 kilometers) inland.
6
SINGLE ROW
Lifting the Unit
Do not hold the air inlet grille while lifting the unit. This could result in damage to the cabinet.
39 (991)
Do not touch the fan blades with your hands or other objects while lifting the unit.
Air Flow
Air Flow
31 (800)
39 (991)
39 (991)
Front Front
4 to 20 (102 to 508)
TWO ROWS
39 (991)
39 (991)
Front Front
39 (991)
Front Front
39 (991)
4 to 20 (102 to 508)
THREE OR MORE ROWS
FrontRear
Air Flow
Air Flow
31 (800)
39 (991)
39 (991)
39 (991)
39 (991)
39 (991)
Front Front
Air Flow
Front Front
Air Flow
31 (800)
Front Front
4 to 20 (102 to 508)
Figure 1. Installation Clearances - inches (mm)
7
NOTICE
Drawings in this manual are for illustrative purposes and should not be used as a template for fabricating eld-supplied accessories or apparatuses. Consider the environment in which this unit is being installed and make necessary adjustments to ensure safe operation. Local codes prevail.
Clearances from Obstructions
Allow adequate air ow clearance on all sides of
the unit. See Figure 1 and this section.
Allow at least 39 in. (991 mm) clearance in front
of the unit for maintenance and service access. The outdoor unit service access is via hinged service doors that swing open in front of the unit. Figure 2.
>39”
(991 mm)
Rear Side
Front Side
>32”
(813 mm)
Front SideRear Side
Figure 3. Perimeter Obstructions
Allow at least 120 in. (3048 mm) clearance above the unit. If an obstruction above the unit does not
allow for adequate clearance, a eld-supplied
discharge duct is required. The discharge duct should be installed in such a way as to ensure that discharge air goes beyond the obstruction and does not cause recirculation of discharge air. Ensure that the static capabilities of the outdoor
unit are not exceeded. Figure 4.
Figure 2. Maintenance & Service Clearance
Perimeter obstructions that are 32 in. (813
mm) taller than the top of the outdoor unit require a eld supplied air discharge duct
to avoid recirculation of discharge air. The discharge duct should be installed to at least the height of the surrounding obstructions
(for ex. walls) to ensure that discharge air
goes over the height of the obstruction. Ensure that the static capabilities of the outdoor
unit are not exceeded. Figure 3.
!
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects. Take care when using a sling to lift the unit for in stallation. The unit center of gravity is not at its physical center.
>120”
(3048 mm)
Front Side Rear Side
Figure 4. Obstructions Above the Unit
8
Cold Climate Considerations
Select a location where high winds and snow will not
a󰀨ect the unit. In areas where typical ambient tem­peratures are below 50°F (10°C), the following pre-
cautions should be observed.
Locate unit away from overhanging roof lines
which would allow water or ice to drop on, or in front of, coil or into unit.
Eaves
Icicle
Wrong Installation
Install snow guards to prevent snow fall from en­tering air inlet and outlet.
Correct Installation
Snow Guard Kit
Snow level
Wrong Installation
Snow Guard Kit
RearFrontRearFront
Snow level
RearFront
Figure 5. Do Not Locate Under Roof Overhang
The unit base should be elevated above the
depth of average snows plus 12 in. (305 mm). In heavy snow areas, do not locate the unit where
drifting will occur.
Correct Installation
RearFront
Snow Drifts
NOTE - Snow guards are recommended on both sides and rear of the unit as shown in this example.
Figure 7. Elevate Above Average Snow Level
& Protect Coil
If necessary, install the unit on a raised base made of angle iron and that allows snow and wind to pass through
Correct Installation
RearFront
Wrong Installation
Defrost
Water
RearFront
Defrost
Water
Wind
RearFront
Snowdrift
Wrong Installation
Figure 6. Do Not Locate Where Drifting Will Occur
Defrost
Water
Figure 8. Secure Unit to
Weather Resistant Support
IMPORTANT
These illustrations are examples of possible snow
protection options. They should not be used as a template for fabricating the snow protection apparatuses. Consider the environment in which this unit is being installed and make necessary adjustments to ensure safe operation.
9
When installed in areas where low ambient tem-
peratures exist, locate unit so winter prevailing
winds do not blow directly on to the outdoor unit.
Wind
Rear Front
Wind
Wind
Inlet
Outlet
RearFront
Outlet
llation
Wrong Installation
Wrong Installation
Air Discharge Duct
Before installing the air duct, remove the two fan guards from the top of the unit.
Duct each outdoor unit separately. Do not use a combined plenum as this may result in air not being discharged directly to the outside.
Discharge air duct shall be constructed of steel and installed in a manner which prevents sagging and or collapsing.
Only one bend is allowed in the air duct.
Duct louvers will reduce air volume, cooling and
heating capacity and e󰀩ciency. Louvers are not recommended; if they are required by the job,
the louver angle should be no larger than 15°.
It may be necessary to install a exible connector between the unit and the duct to reduce vibration noise.
Table 1. Static Pressure Settings
Static Pressure Description
0 WG (0 Pa) Default
0-0.08 WG (0-20
Pa)
Above 0.08 WG
(20 Pa)
Remove fan guard, < 10 ft. (3 m)
duct length
Contact Lennox VRF Applications
Support
RearFront
Correct Installation
Figure 9. Protect Unit from Prevailing Winds
NOTE - Use dip switch S4 to change outdoor unit static pressure settings.
10
Support
C
Radius
E
A
Radius
3-1/2 in.
(89 mm)
15°
4 in. (102 mm)
Air Outlet Louver
072, 096, 120 -- 50-3/4 in. (1289 mm)
144, 168, 192 -- 65 in. (1651 mm)
B
F
8 × ST3.9
self-threading screws
Fan guards
(remove
first)
!
Contact the Lennox VRF
applications department for assistance with ducting applications
that di󰀨er from these images.
Figure 10. Air Discharge Duct
072, 096, 120
A A ≥ 12 in.(305 mm)
B B ≥ 10 in. (254 mm)
C C ≤ 118-1/8 in. (3000 mm)
D D ≥ 24 in. (610 mm)
E E = A + 24 in. (610 mm)
F 24 in. (610 mm)
(Front or Rear Connection)
11
144, 168, 192
A A ≥ 12 in.(305 mm)
B B ≥ 10 in. (254 mm)
C C ≤ 118-1/8 in. (3000 mm)
D D ≥ 28-3/8 in. (721 mm)
E E = A + 24 in. (610 mm)
F 28-3/8 in. (721 mm)
Discharge Duct Pressure Curves
VRB072
VRB120
6-ton Air Volume (CFM)
15000
14000
13000
12000
11000
10000
9000
8000
7000
6000
0 0.04 0.08 0.1 2 0.16 0.2 0.24 0.2 8 0.32
Static Pressure (in.wg.) Air Volume (CFM)
0 13934
0.04 13320
0.08 12667
0.12 12010
0.16 11236
0.2 10163
0.24 8940
0.28 7902
0.32 7094
10-ton Air Volume (CFM)
18000
16000
14000
12000
10000
8000
6000
0 0.04 0.08 0.12 0.16 0.2 0.24 0.28 0.32
Static Pressure (in.wg.) Air Volume (CFM)
0 15667
0.04 15090
0.08 14508
0.12 13907
0.16 13261
0.2 12467
0.24 11554
0.28 10655
0.32 9709
VRB096
8-ton Air Volume (CFM)
16000
15000
14000
13000
12000
11000
10000
9000
8000
7000
6000
0 0.04 0.08 0.12 0.16 0.2 0.24 0.28 0.32
Static Pressure (in.wg.) Air Volume (CFM)
0 14800
0.04 14205
0.08 13587
0.12 12958
0.16 12248
0.2 11315
0.24 10247
0.28 9279
0.32 8402
VRB144, 168, & 192
12~16-ton Air Volume (CFM)
25000
24000
23000
22000
21000
20000
19000
18000
17000
0 0.04 0.08 0.12 0.16 0.2 0.24 0.28 0.32
Static Pressure (in.wg.) Air Volume (CFM)
0 24544
0.04 24079
0.08 23559
0.12 22986
0.16 22360
0.2 21679
0.24 20945
0.28 20157
0.32 19315
12
Main/Sub Outdoor Unit Placement
A VRF system consisting of more than two outdoor units must be placed in order from the
largest to the smallest capacity. See gure 8.
The largest capacity outdoor unit must be installed closest to the main pipe leading into the building. See Figure 11.
The largest capacity outdoor unit address is the
main unit, while the others are the sub units. See
Figure 11.
All of the outdoor units manifolded together should be installed at the same elevation.
Main unit placed closest to main pipe leading into building
Main piping
to building
16-ton
Outdoor Unit
Branch Pipe Kits
14-ton 10-ton
NOTE - All of the outdoor units manifolded together should be installed at the same elevation.
If the unit coil cannot be installed away from
prevailing winter winds, a wind barrier should
be constructed. Size barrier at least the same height and width as outdoor unit. Install barrier
12 inches (305 mm) minimum from the sides of
the unit in the direction of prevailing winds.
IMPORTANT!
Roof Damage! This system contains both refrigerant and
oil. Some rubber roong material may absorb
oil. This will cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid expo sure to refrigerant and oil during service and instal lation. Failure to follow this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab or Frame
Use lag bolts (min. 3/8 in.) at all four corners to secure the unit to the eld-provided slab or frame.
Isolation material can be used to control vibration or
sound transmission. Lag bolts must extend through
material to the slab or frame. See Figure 12.
Figure 11. Main/Sub Unit Placement
(40-Ton System Example)
Installation
Slab or Roof Mounting
Install the unit a minimum of 8 inches (203 mm)
above the roof or ground surface to avoid ice build­up around the unit. Locate the unit above a load­bearing area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
Use a eld supplied slab or suitably sized steelwork to construct a base for locating the condensing unit. All supporting work should be veried by a qualied engineer.
NOTE - Prefabricated light duty equipment pads are NOT suitable for use.
Support the unit across the front and back of the unit.
Use lag
bolts (4) to
secure unit to slab or approved frame at each corner
8 in. (203 mm)
Figure 12. Secure Outdoor Unit
to Approved Structure
13
Refrigerant Piping Connections
!
WARNING
Refrigerant leaks are unlikely; however, if a refriger ant leak occurs, open a door or windows
to dilute the refrigerant in the room. Turn o󰀨 the
unit and all other appliances that may cause a spark. Call a li censed professional HVAC technician (or equiva lent) to repair the leak. Use only R-410A refrigerant to charge this system. Use of other refrigerant or gas will damage the equipment. Do not allow air or other contaminants to enter sys tem during installation of refrigerant piping. Con taminants will result in lower system capacity and abnormally high operating pressures and may res ult in system failure or explosion. Insulate all refrigerant piping. Refrigerant pipes may be very hot during unit opera tion. Do not allow contact between wiring and bare copper pipes. After refrigerant piping connections have been completed, check the system for leaks per commis sioning instructions.
Both liquid and gas (vapor) lines must be indi-
vidually insulated.
Field piping consists of three HVAC/R eld-pro-
vided copper refrigerant lines connected to the outdoor unit. These lines carry the liquid and va­por refrigerant to and from the mode selection
box(es).
Refrigerant piping and wiring connections can be brought into the outdoor unit through openings
provided in the front, side(s), or underside (rec­ommended) of the unit.
Refrigerant piping must be connected using
mode selection boxes and individual branch pipe
kits. Six mode selection boxes are available in
varying sizes to accommodate connection of one to 41 indoor units.
The following restrictions apply to each VRB sys­tem:
Total refrigerant pipe length 3280 ft. (1000 m)
Longest pipe length actual) 574 ft. (175 m)
Level di󰀨erence between indoor units 98 ft.
(30 m)
Piping length from the rst branch pipe to the
farthest indoor unit 132/295 ft. (40/90 m)
For each branch pipe, allow 20” (508 mm) of equivalent length.
!
Contact the Lennox VRF applications department
for assistance.
When the outdoor unit is installed 164 feet (50
m) or more above the indoor units, install an oil return trap every 33 feet (10 m) in the main low
pressure gas pipe. See Figure 13 for trap speci-
cations.
≥1ft
≥1ft
Figure 13. Oil Return Trap
When the outdoor unit is 132 feet (40 m) or more below the indoor units, increase the diameter of
the liquid line pipe from the outdoor unit to the
rst branch pipe by one size. ! Contact the Len­nox VRF applications department for assistance.
To extend the length from the rst branch pipe to the farthest indoor unit beyond 132 ft. (40 m) and up to 295 ft. (90 m), the following three conditions
must be met.
1. Increase diameter of the main pipe between
the rst and the last branch pipes. If the diam­eter of the pipe is the same as the main outdoor
pipe, then it does not need to be increased. Ex: If 132 ft.<L1+L7+L9+L10 ≤ 295 ft., in-
crease the diameter of all the pipes by one size.
2. The length from the indoor unit to the nearest
branch pipe must be 132 ft. (40 m) or less. Ex: a,b,c,d,e,f,g,h,i,j,k,l,m ≤ 132 ft.
3. The di󰀨erence between [the distance from
the outdoor unit to the farthest indoor
unit] and [the distance from the outdoor unit to the nearest indoor unit] is ≤132 ft. Ex:(L1+L7+L9+L11+11+j+k+n)
-(L1+L7+L8+p) ≤ 132 ft.
!
Contact the Lennox VRF applications department
for assistance.
IMPORTANT!
The compressor in this unit contains PVE oil (Polyvinylether). PVE oil is formulated for hy-
drouorocarbon (HFC) refrigerants, such as R-
410a, which this system contains. While it may have some miscibility properties with mineral based oil and POE oil (Polyolester), you should not mix PVE oil with any other type of refriger­ant oil.
14
Maximum Permitted Refrigerant Pipe Length and Maximum Height Difference
OUTDOOR UNITS (one or more outdoor units)
NOTE - Capacities are shown in parenthesis
a
b
c
MS1
L1
A
L2
L3
B
L4
C
L6
L5
MS3
MS2
INDOOR UNITS
N1
(024)
N2
(024)
d
e
The first line Branch Pipe
N4
(009)
N3
(048)
Maximum equivalent single piping length - 656 ft.(200 m)
L7
Maximum piping length from the first Branch Pipe joint to the farthest indoor unit - 295 ft. (90 m)
LEGEND
Branch Pipe
Mode Selection Box (MS)
Maximum level difference between
Indoor Unit
L8
D
L9
L10
E
L11
F
MS6
Indoor Unit and Outdoor Unit - 361 ft. (110 m)
MS7
f
MS4
L12
MS5
L13
Maximum piping length from MS Device to downstream indoor unit - 131 ft. (40 m)
k
j
r
N13 (018)
q
N12
(048)
p
N11
(048)
l
N5
(048)
g
i
m n
N8
(009)
h
N9
(018)
N6
(024)
N7
(024)
N10 (018)
Maximum level difference between indoor units - 98 ft. (30 m)
Piping Length Permitted value Piping
Total piping length
Single piping length
Piping length from the rst branch joint to the
Piping
Length
farthest indoor unit
Actual length 574 ft. (175 m) Equivalent length2 656 ft. (200 m)
Piping length from Mode Selection Box (MS) to
the downstream indoor unit of itself
Level di󰀨erence between
indoor unit and outdoor unit
Level
Level di󰀨erence between indoor units 98 ft. (30 m) - - -
Di󰀨erence
NOTES:
The rst branch in all systems must be centrally located between all Mode Selection (MS) Boxes.
1
When counting the total piping length, double the actual length of the distribution pipes between rst Branch Pipe joint and Mode Selection Box (MS): Installation.
Total piping length = L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11+L12+L13)×2+a+b+c+d+e+f+g+h+i+j+k+l+m+n+p+q+r ≤ 3280 ft.(1000 m).
2
Each Branch Pipe or bend is equivalent to 20 in. (508 mm).
3
The maximum allowable piping length from the rst Branch Pipe joint to the farthest indoor unit must be ≤ 132 ft. (40 m), but if the following conditions are met, the
maximum allowable length can be extended to 295 ft. (90 m):
• The piping length from each indoor unit to the nearest Branch Pipe joint or direct connected Mode Selection Box (MS) must be less than 132 ft. (40m) (b to r).
• The di󰀨erence in length between the outdoor unit to the farthest indoor unit, and the outdoor unit to the nearest indoor unit is ≤ 132 ft. (40 m). Example: The farthest indoor unit is N10, The nearest indoor unit is N11 (L1+L7+L9+L11+j+k+n) minus (L1+L7+L8+p) ≤ 132 ft. (40 m).
• Increase the distribution pipe diameter between the rst Branch Pipe and Mode Selection Box (MS) L2-L13. If the pipe diameter is the same as the main outdoor pipe,
it does not need to be increased.
Pipe Size Allowable Increase Diameters (in.):
3/8 to 1/2 1/2 to 5/8 5/8 to 3/4 3/4 to 7/8 7/8 to 1-1/8 1-1/8 to 1-3/8 1-3/8 to 1-5/8 1-5/8 to 2-1/8
4
When the outdoor unit is higher than indoor units and the level di󰀨erence is over 164 ft. (50 m), it is required to set an oil return bend every 33 ft.(10 m) in the gas pipe of
the main pipe. Refer to Installation Instructions for additional details.
5
When the outdoor unit is lower than indoor units and the level di󰀨erence is more than 132 ft.(40 m), the main liquid pipe pipe need to increase by one size.
Outdoor unit up4 360 ft. (110 m) - - -
Outdoor unit down
1
3280 ft. (1000 m)
3
132/295 ft. (40/90 m) L7+L9+L11+j+k+n
132 ft. (40 m) j+k+n
5
230 ft. (70 m) - - -
L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11+L12+L1
3)×2+a+b+c+d+e+f+g+h+i+j+k+l+m+n+p+q+r
L1+L7+L9+L11+j+k+n
15
Loading...
+ 33 hidden pages