Lennox VOSB Installation Instructions Manual

Page 1
©2019 Lennox Industries Inc. Dallas, Texas, USA
VRF
THIS MANUAL MUST BE LEFT WITH THE OWNER FOR FUTURE REFERENCE
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li­censed professional HVAC installer, service agency or the gas supplier.
Failure to follow safety warnings and these instruc­tions exactly could result in property damage, dan­gerous operation, serious injury, or death.
Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the ap­plication needs must be made by a licensed profes­sional HVAC installer (or equivalent) using factory-
specied parts.
Do not use this system if any part has been under
water. A ood-damaged appliance is extremely dan-
gerous. Immediately call a licensed professional HVAC service technician (or equivalent) to inspect the system and to replace all controls and electrical parts that have been wet, or to replace the system, if deemed necessary.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
To ensure proper system performance and reliability, Lennox does not recommend operation of VRF sys­tems during any phase of construction. Construction debris, low temperatures, harmful vapors, and opera-
tion of the unit with misplaced lters can damage the
units. Failure to follow these guidelines will result in the warranty being voided.
INSTALLATION INSTRUCTION
VOSB Outside Air Ducted Units
VRF SYSTEMS -- Indoor Units 507896-02 06/2019
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFC’s and HCFC’s) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
General
The VOSB outside air ducted indoor units are matched with an outdoor heat recovery or heat pump unit to
create a VRF (variable refrigerant ow) system that uses
R-410A refrigerant. VOSB indoor units are designed for indoor installation only.
Refer to the Product Specication bulletin (EHB) for the proper use of these indoor units with specic heat
pumps, heat recovery units, mode switching devices, branch pipes, line sets and controls.
Check the components for shipping damage. If you nd
any damage, immediately contact the last carrier.
Package 1 of 1 contains the following:
1 - Assembled high-static, concealed duct unit
1 - Digital Display Panel
2 - Refrigerant piping insulation sleeves
1 - Flexible condensate connector (VOSB036-054)
1 - Hose clamp (VOSB036-054)
1 - Condensate connection pipe (VOSB072-096) (Packed in Supply side of cabinet.)
1 - Roll tape for condensate pipe (VOSB072-096)
1 - Condensate overow connection harness
1 - 120 Ohm End of Line Resistor
1 - Installation manual
1
Page 2
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Do not touch the unit or the controller if your hands are wet. DO NOT spray water on the indoor unit for any reason.
Do not replace a fuse with a fuse of a di󰀨erent rating. Do not use a jumper wire to replace a fuse. Do not insert
your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit. Do not allow children to operate the system.
Model Number Identication
V OS B 036 H 4 - 3 P
Brand/Family
V = Variable Refrigerant Flow (VRF)
Unit Type
OS = Outside Air Ducted Indoor Models
Major Design Sequence
Nominal Cooling Capacity - Btuh
B = 2nd Generation
036 = 36,000 Btuh 048 = 48,000 Btuh 054 = 54,000 Btuh 072 = 72,000 Btuh 096 = 96,000 Btuh
Refrigerant Type
4 = R-410A
Cooling E󰀩ciency
H = High E󰀩ciency
Voltage
P = 208/230V-1 phase-60hz
Controls Protocol
3 = Phase 3
NOTE - Only Lennox VRF indoor units will work with Lennox VRF outdoor units and associated mechanical equipment. Lennox Mini Split indoor units are similar in appearance but must not be connected to a Lennox VRF
refrigerant circuit. Please refer to model numbers to conrm compatibility. Model numbers for Lennox VRF units
start with a “V” and model numbers for Lennox Mini-Splits start with a “M”.
System Piping
CAUTION
VRF system piping is customized for each installation. The LVSS piping report is an engineered design that must be followed. The piping diagram or diagrams included within the LVSS report have been prepared based on the information provided to the Lennox VRF applications department.
When the indicated lengths change from the gures
stated within the report, it is imperative that prior to the commencement of the refrigerant pipe work installation, Lennox VRF applications department are informed of these proposed changes.
Upon receipt of this new information the Lennox VRF
applications department will conrm any changes that
may be applicable to this installation. If changes are required, a new piping diagram will be produced and will supersede all other previously provided documents.
Failure to provide this information regarding changes
to the original design may lead to insu󰀩cient capacity,
equipment failure, warranty being made void and the refusal to commission the system.
When using as part of a VRF Heat Recovery system, refer to the specic pipe connection details located in
the Mode Selection Box installation manual and the detailed drawing on page 16 of this manual.
NOTICE
2
Page 3
Unit Dimensions - Inches (mm)
SECTION A-A
VOSB036, 048, 054
SECTION D-D
BRACKETS FOR
SUSPENDING (4)
29-1/8
25-1/8
(740)
(638)
PRIMARY
DRAIN
CONNECTION
(Either Side)
AUXILIARY
DRAIN
CONNECTION
(Either Side)
45-1/4 (1149)
AIR FLOW
TOP VIEW
SECTION C-C
3-5/8 (92)
15-5/8
(397)
5-3/8
7-1/4
(137)
(184)
LIQUID PIPE
GAS PIPE
ELECTRICAL
CONTROL
BOX
SECTION B-B
RETURN AIR DUCT OPENING
29-1/8 (740)
23-7/8 (606)
AUXILIARY
DRAIN
CONNECTION
(Either Side)
1-5/8 (41)
7-1/2
4-7/8
(191)
(124)
AIR FLOW
LEFT SIDE VIEW
SECTION D-D
1 (25)
PRIMARY
DRAIN
CONNECTION
(Either Side)
SUPPLY AIR DUCT OPENING
(Supply Air
Duct Opening)
9-3/4 (248)
5-3/8 (137)
2-1/2 (64)
TOP OF UNIT
51-1/4 (1302)
47-1/2 (1207)
36-5/8 (930)
(Supply Air Duct Opening)
(Bottom of Unit)
SUPPLY AIR SIDE
SECTION C-C
TOP OF UNIT
RETURN AIR
DUCT OPENING
42-1/4 (1073)
(Return Air Duct Opening)
(Bottom of Unit)
RETURN AIR VIEW
SECTION A-A
16-1/2
(419)
13-3/8 (340)
(Return Air
Duct
Opening)
SUPPLY AIR DUCT OPENING
FACTORY­MOUNTED
LIFT PUMP
AUXILIARY
DRAIN
CONNECTION
(Either Side)
GAS PIPE
AIR FLOW
RIGHT SIDE VIEW
SECTION B-B
LIQUID PIPE
PRIMARY
DRAIN
CONNECTION
(Either Side)
RETURN AIR DUCT OPENING
3
Page 4
Unit Dimensions - Inches (mm)
SECTION A-A
VOSB072, 096
RETURN AIR DUCT OPENING
20-7/8
(530)
38-1/4 (972)
32-7/8 (835)
AIR FLOW
LEFT SIDE VIEW
SECTION D-D
SECTION D-D
SUPPLY AIR DUCT OPENING
38-1/4
34-5/8
(972)
(879)
(Supply Air
Duct Opening)
2 (51)
14-7/8
(378)
6
(152)
(Supply Air Duct Opening)
50 (1270)
AIR FLOW
TOP VIEW
SECTION C-C
TOP OF UNIT
56-3/4 (1441)
36-7/8 (937)
(Bottom of Unit)
SUPPLY AIR SIDE
SECTION C-C
12-1/8
(308)
BRACKETS FOR SUSPENDING (4)
GAS PIPE
LIQUID
PIPE
ELECTRICAL
CONTROL
BOX
SUPPLY AIR DUCT OPENING
19-7/8
(505)
SECTION B-B
LIQUID PIPE
AIR FLOW
RIGHT SIDE VIEW
SECTION B-B
2-3/4
(70)
GAS PIPE
RETURN AIR DUCT OPENING
DRAIN
CONNECTION
5-1/2 (140)
TOP OF UNIT
RETURN AIR
DUCT OPENING
44-1/8(1120)
(Bottom of Unit)
RETURN AIR VIEW
SECTION A-A
4
(76)
3
13-1/2
(343)
Page 5
Clearances
Refer to Figure 1 for minimum clearance requirements.
Wall
Wall
20” (508 mm) Minimum Service Clearance
Air
Flow
DUCTED
UNIT
24” (610 mm)
24” (610 mm)
Minimum
Service
Clearance
Minimum Service Clearance
TOP VIEW
Ceiling
24” (610 mm) Minimum Clearance
1” (25 mm) Minimum Clearance
CeilingSuspended
FRONT VIEW
NOTE - No part of the suspended ceiling, or other supports not directly associated with the indoor unit installation,
can be xed to, or touch the indoor unit, in any form. Minimum clearances must be observed at all times.
NOTE - Horizontal installation only.
Figure 1. Minimum Installation Clearances
5
Page 6
Unit Placement
WARNING
Do not install the unit in an area where ammable
materials are present due to risk of explosion resulting in serious injury or death.
Check suitability of structure to which the unit support
mechanism will be xed to. If structure is not capable
of carrying the weight of the unit, unit may fall causing personal injury or equipment damage.
Use the provided and specied components when
installing equipment. Failure to do so may result in unit falling, water leaking or electrical shocks, causing personal injury or equipment or property damage.
Consider the possibility of earthquakes in your area when installing the equipment. If the unit is not correctly secured, it may fall, causing personal injury or equipment damage.
Safely dispose of packing materials, which include nails, wood and other sharp objects, as well as plastic wrapping. Children playing with plastic wrap or bags risk
the danger of su󰀨ocation.
CAUTION
Do not place items which may be damaged by water under or around the unit.
The unit should be installed at least 8 feet above the
oor (if possible) to ensure maximum performance and
comfort.
AVOID
Do not install the unit in the following locations:
Areas near commercial kitchen exhaust hoods where odors and grease may enter the air stream.
Areas near ue and/or exhaust vents where ue gasses, waste gasses, or debris may enter the air stream.
Areas exposed to petrochemicals or petrochemical products
Areas exposed to salt or other corrosive materials or caustic gasses
Areas exposed to extreme voltage variations (such as factories
Tightly enclosed areas that may impede service of the unit
Areas exposed to fossil fuels (such as oil or gas in
kitchens)
Areas exposed to strong electromagnetic forces
Areas exposed to acids or alkaline detergents (laundry
rooms)
DO:
Locate the unit so that it is not exposed to direct sunlight
Ensure the structural ceiling can support the weight of the unit.
Select a location where condensate line will have the shortest run to a suitable drain per local codes.
Allow su󰀩cient space around unit for proper operation and maintenance
Install unit a minimum of 3 feet away from any antenna,
power cord (line) radio, telephone, security system, or
intercom. Electrical interference and radio frequencies
from any of these sources may a󰀨ect operation
6
Page 7
Installation
It is important to locate the unit where it can be accessed for service in the future. Refer to unit dimensions on Pages 3-5 for exact locations of suspension brackets, return air and supply air openings.
1. Make sure that the structural ceiling or slab is able to support the weight of the indoor unit. It may be necessary to add extra support.
2. Install suspension rods in the structural ceiling or concrete slab in a suitable location. If the structural ceiling is constructed of concrete,
install anchors to accept four ⅜” threaded rods to
suspend the indoor unit. If the structural ceiling includes wooden joists, use angle iron or Unistrut
channel xed securely in place to accept the ⅜”
threaded rods. NOTE - Threaded rod (requirement of Lennox warranty program) is the ONLY acceptable method of suspending the unit; do not use chains or straps. See Figure 2.
⅜” THREADED
CONCRETE CEILING
USING ANCHORS
ANCHOR
ANGLE IRON
BOLTED IN
PLACE ACROSS
WOODEN JOISTS
⅜” THREADED
ROD
ANGLE IRON
WOODEN JOISTS
WOODEN JOIST
Figure 2. Suspending Methods
3. Slide one nut and one washer onto each threaded rod.
Use electrical tape to keep the washer from failing o󰀨. Position the nuts slightly above the nal resting place
of the four suspension brackets. See Figure 3.
” THREADED
ROD
INDOOR UNIT
SUPPLY AIR
OPENING
LEVELING
FRONT VIEW
NUT
Figure 3. Suspension Hardware
ROD
ACROSS
When unit is level, tighten
nut to secure
position of
suspension
bracket on
SUSPENSION
BRACKET
rod.
” THREADED
ROD
FIELD-PROVIDED
ISOLATION GROMMET
WASHER
LEVELING
NUT
SUSPENSION
BRACKET
Figure 4. Isolation Grommet
4. Use either a mechanical lifting device or a minimum of two people to raise the unit and insert the threaded rods into the suspension brackets on the unit base. Slide a washer and then a nut onto each rod below each suspension bracket. Use the leveling nut (beneath
suspension bracket) to adjust the unit to the correct
height. Remove the electrical tape holding the upper washers and nuts in place and tighten each of the four nuts above the brackets down onto the brackets. This will ensure that the unit remains level.
5. It is recommended to install a eld-provided isolation grommet as shown in Figure 4 to prevent transmission of vibration from unit to structural ceiling.
6. If the unit is being installed in an application that includes
a sheet rock (plasterboard) ceiling, it is required that
an access panel be installed in a suitable location. This will also allow access for future maintenance (requirement of Lennox warranty program). Access is required during the commissioning process to test the condensate disposal system and to check the local disconnect.
7. The unit is factory-congured for the supply air to be
delivered from the front and the return air lter at the
rear of the unit.
INSTALLATION GUIDELINES
It is recommended to install a eld-provided isolation grommet as shown in Figure 4 to prevent transmission of vibration from unit to structural ceiling.
Provide separate support for the weight of the duct system. Duct system must not be supported by the indoor unit.
Use exible joints (canvas) at the point where the duct connects to the unit on both ends. Material must meet all local and national code requirements.
When unit is being installed in a location where even the slightest noise would be a problem (meeting room
or other very quiet space), design duct system to avoid
transmission of vibration to the structure to the extent possible.
When sizing the return air lter grille, a minimum surface area of 200 sq. in. per ton is recommended.
7
Page 8
Return Air Filter
Return Air Filter
The factory-supplied return air lter is segmented to allow
it to be separated if needed to remove it from the unit in tight spaces. The segments are connected with hook & loop (Velcro-style) straps. See Table 1 for lter dimen­sions.
Filter removal tab
Figure 5. Segmented Factory-Supplied
Return Air Filter
Remove Return Air Filter Instructions
1. Loosen the screw that secures the lter retaining bracket and slide the bracket away from the unit.
2. Grasp the lter removal tab and slide the lter out.
Filter removal tab
Figure 7. Slide Out Filter
Figure 6. Loosen Filter Retaining Bracket
Table 1. Filter Dimensions
Indoor Unit Model Filter Dimensions Each Section of Filter Dimensions
VOSB036, 048, 054
VOSB072, 096
42-5/8 x 13-1/4 x 3/8 in.
1083 x 336 x 10 mm
44-1/2 x 13-1/4 x 3/8 in.
1130 x 336 x 10 mm
External Static Pressure
External Static Pressure setting on wired controller
Use high speed air ow for selection and design.
Set the external static pressure (ESP) on wired controller, the setting value should not be 0.2 in.w.g
(50Pa) higher than the actual external static pressure
of the duct.
Hook & Loop Strap
Figure 8. Filter Partially Removed
3. Reverse these steps to reinstall the lter. Be sure to reinstall the receiver if it was detached during the
lter removal.
14-1/8 x 13-1/4 x 3/8 in.
359 x 336 x 10 mm
14-3/4 x 13-1/4 x 3/8 in.
375 x 336 x 10 mm
8
Page 9
Refrigerant Piping Connections
WARNING
Refrigerant leaks are unlikely; however, if a refrigerant leak occurs, open a door or windows to dilute the
refrigerant in the room. Turn o󰀨 the unit and all other
appliances that may cause a spark. Call a licensed
professional HVAC technician (or equivalent) to repair
the leak. Use only R410A refrigerant to charge this system. Use of other refrigerant or gas will damage the equipment. Do not allow air or other contaminants to enter system during installation of refrigerant piping. Contaminants will result in lower system capacity and abnormally high operating pressures and may result in system failure or explosion. Insulate all refrigerant piping. Refrigerant pipes may be very hot during unit operation. Do not allow contact between wiring and bare copper pipes. After refrigerant piping connections have been completed, check the system for leaks per commissioning instructions.
WARNING
Danger of re. Bleeding the refrigerant
charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
IMPORTANT
Refrigerant lines must be clean, dry, refrigerant-grade copper lines. Air handler coils should be installed
only with specied line sizes for approved system
combinations.
Handle refrigerant lines gently during the installation
process. Sharp bends or kinks in the lines will cause restrictions.
IMPORTANT
Only use brazing rods/sticks which are suitable/ recommended for air conditioning pipework installations
- Do Not Use Soft Solder.
IMPORTANT
The compressor in the unit this air handler is matched
with contains PVE oil (Polyvinyl ether). PVE oil is formulated for hydrouorocarbon (HFC) refrigerants,
such as R410A, which this system contains. While it may have some miscibility properties with mineral-based oil
and POE oil (Polyolester), it is not recommended to mix
PVE oil with any other type of refrigerant oil.
CAUTION
Brazing alloys and ux contain materials which are
hazardous to your health. Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well-ventilated areas. Wear gloves and protective goggles or face shield to
protect against burns. Wash hands with soap and water after handling brazing
alloys and ux.
CAUTION
Purge low pressure nitrogen [1 to 2 psig (6.0 to 12.8
kPA)] through the refrigerant piping during brazing. This
will help to prevent oxidation and the introduction of moisture into a system. To prevent the build-up of high levels of nitrogen when purging be sure it is done in a well ventilated area.
9
Page 10
Refrigerant lines must be connected by a qualied technician in accordance with established procedures.
Field provided piping consists of two HVAC/R rated copper lines connected to the indoor unit.
Final equipment connections must be brazed
connections. Compression or other types of ttings are not permitted for nal connections.
All refrigerant piping shall be free of defects, debris, and oil.
Copper-phosphorous brazing alloys are to be used to join all pipework connections where applicable.
Always ow/purge nitrogen to avoid oxidation while brazing.
Always use an appropriate heat absorption compound to protect the unit and internal sensors from conductive heat while brazing.
1. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or moisture from getting into the refrigerant piping before it is connected.
2. Prior to brazing remove rubber air grommets from indoor unit refrigerant line ports.
3. Slowly loosen one of the rubber plugs to release the factory nitrogen charge. Remove the rubber plug from both liquid and gas lines.
4. Connect the liquid and gas lines to the evaporator coil.
5. Reinstall the rubber grommets into the refrigerant piping panel.
6. Insulate both pipes individually.
Table 2. Refrigerant Piping Connections
Indoor Unit Size
(Btuh)
36,000
48,000
54,000
72,000
96,000
Liquid Line Vapor Line
3/8” 5/8”
3/8” 7/8”
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in condensation problems.
This is especially important when the unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
WARNING
There must be an air-tight seal between the unit and the
return air plenum. Use berglass sealing strips, caulking,
or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this unit or
any gas-fueled appliance (i.e. water heater) or carbon monoxide-producing device (i.e. wood replace) is
installed.
10
Page 11
Condensate Piping Connections
VOSB036-054 indoor units have a factory-installed
condensate lift pump capable of 28 inches (711 mm) of lift
and one gravity drain connection on each side of the unit. If using gravity drain, select one connection to use and leave the unused connection port sealed.
Seal and plug the lift pump connection port when using a gravity drain connection port. Disconnect the factory-installed lift pump that is connected to the CN labeled PUMP..
VOSB072-096 indoor units have one gravity drain connection.
CAUTION
Make sure that drain piping is properly routed and insulated in order to prevent both leaks and condensation. Follow these instructions exactly to ensure proper drainage and unit operation.
1. Use the provided hose clamp to secure the
provided exible condensate drain connector
and insulating sleeve to the drain line stub on the side of the indoor unit. See Figure 9.
NOTE - Take care not to over-tighten the hose clamps
this may damage the drain line stub.
036 SHOWN
RETURN
AIR DUCT
SUPPLY
AIR DUCT
OPENING
AUXILIARY
DRAIN
CONNECTION
(EITHER SIDE VOSB036-054)
INDOOR
UNIT
(BOTTOM OF UNIT)
AIR FLOW
FLEXIBLE DRAIN
CONNECTOR
1” I.D.
(EITHER SIDE VOSB036-054)
(ONE SIDE VOSB072--96)
OPENING
PRIMARY
DRAIN
CONNECTION
PVC DRAIN
PIPE
3. See Figure 10 for applications including a single unit and a single gravity drain. In this case, ensure that the drain line is properly sloped (no less than 1/4 inch
per foot) and condensate lines are routed to ensure
moisture is drained away from the indoor unit.
Structural Ceiling
Suspension Rods
Indoor Unit
Do not operate unit without condensate drain trap.
NOTE - Drain line should be sloped 1/4 inch per foot (18 mm per m) AWAY from unit and should be supported as needed to prevent sagging.
Do not overtighten drain fitting.
Anti-siphon vent must extend above the height of the coil drain pan by 2” (51 mm).
1 ft.
(305 mm) max
Clean Out Do not glue
3”
3”
3 ft.
(1 m)
Support
straps
Drain line
Figure 10. Sloped Condensate Gravity Drain
Single Unit
IMPORTANT
Drain should have a slope of at least 1/4 inch per foot and should be approved corrosion-resistant pipe.
4. See Figure 12 for applications including multiple units and a single gravity drain. In this case, ensure that the drain line is properly sloped (no less than 1/4 inch
per foot) and condensate lines are routed to ensure
moisture is drained away from the indoor unit. See
5. See Figure 11 for applications including a single unit using the factory-mounted lift pump.
STRUCTURAL CEILING
SUSPENSION RODS
8 in.
(203 mm)
DRAIN LINE
3 ft. (1 m)
SUPPORT
STRAPS
Max. 18 in.
CONDENSATE
LINE STUB
1” O.D.
HOSE CLAMP
INSULATION
Figure 9. Condensate Drain Connection
IMPORTANT
You must conrm operation of every drain and pump in
the system as part of the commissioning procedure.
2. Make a water-tight connection between the eld-
provided condensate drain line and the exible condensate connector (1” I.D.).
Figure 11. Condensate Drain with Lift Pump
Single Unit
6. See Figure 13 for applications including multiple units using the internal lift pump to provide lift into a single, correctly sized main drain. In this case, ensure that the main drain line is properly sloped, no less than
1/4 inch per foot (6 mm per 305 mm), and that each
individual drain is connected to the main drain exactly as shown.
11
Page 12
Install an anti-siphon vent for each trap - must extend above the height of the coil drain pan by 2” (51 mm).
Suspension
Rods
Clean Out
Indoor Unit tinU roodnItinU roodnI
3”
3”
Install a trap for each indoor unit.
Do not operate unit without condensate drain trap.
Do not overtighten drain fitting.
Figure 12. Sloped Condensate Gravity Drain
8 in.
2~3-15/16 in.
Indoor Unit
INDIVIDUAL DRAIN OUTLET FROM EACH INDOOR UNIT
(Must be connected to internal pump and must be routed to
main drain as shown.)
Max. 18 in.
(305 mm) max
Clean Out
Vent
3”
3”
NOTE - Drain line should be sloped 1/4 inch per foot (18 mm per m) AWAY from unit and should be supported as needed to prevent sagging.
Clean Out
3”
3”
Multiple Indoor Units
8 in. 8 in.
2~3-15/16 in.
Max. 18 in.
(Sloped at 1/4” per foot (6 mm per 305 mm) AWAY
from unit and should be supported as needed to prevent sagging.)
tinU roodnItinU roodnI
MAIN DRAIN
1 ft.
Vent
2~3-15/16 in.
3 ft.
(1 m)
Support
straps
Max. 18 in.
Figure 13. Condensate Drain with Lift Pump
Multiple Indoor Units
7. In all cases, drain should be as short as possible and should not have any droops or kinks that would restrict
condensate ow and shall be constructed using an
approved pipe. All drains should contain traps. There must be a 2-inch space between the end of the
8. After system installation is complete, the condensate drain line must be checked for leaks
and if a condensate pump has been tted, it must
be checked to ensure proper operation. This check is part of the commissioning procedure.
condensate drain and the nal termination point
(ground, open drain, etc.) to ensure that the line will drain freely.
Table 3. Condensate Pump Accessory Options
Capacity Brand Model Name Model # Cat #
Lennox VRF Drain Pump Kit V8DRNP05 17U32 - 18 in -
VOSB072-096
Blue Diamond
MegaBlue X87-835 14T71 13.2 66.5 ft 23 ft
*Optional pump maximum suction lift is measured from the pump outlet.
Max Flow
Rate
(gal per hr)
Max
head
Max suction lift*
12
Page 13
Table 4. Condensate Connection Sizes
Cut wire here
using solder or butt joints
Model
VOSB Outside Air Ducted
Condensate Life Pump Factory Mounted
Yes - 036-054 No - 072/096
Condensate Pump Lift Measurement
18 “ Yes
Using an External Water Level Switch
1. Disconnect the closed circuit loop connection labeled WATER.
2. Connect the provided overow harness accessory to the WATER connection. See Figure 14.
3. See unit wiring diagrams for location of the WATER connection.
The connection has 5 VDC current, do not supply eld
voltage.
Table 3 lists available external condensate pump accessories. See Table 4 for connection sizes.
Condensate Pump Facility on Indoor PCB Board
INDOOR UNIT MAIN BOARD
WATER
Connect to pump here
WATER
Condensate Outlet of Indoor Unit
1” O.D. 1-5/8” O.D.
adapter pro­vided
L1
L2
Flexible Drain Con­nection (supplied with unit)
1” I.D.
GREEN
G
PUMP CONNECTIONS
G
L2
L1
NC
COM
NO
OPTIMAL
0.5A
Wiring Connections
WARNING
Isolate the power supply before accessing unit electrical terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this installation instruction, during installation. Do NOT overload electrical circuit, as this may lead to failure and
possible re.
Use specied wiring and cable to make electrical
connections. Clamp cables securely and make sure that connections are tight to avoid strain on wiring. Insecure wiring connections may result in equipment failure and
risk of re.
Wiring must be installed so that all cover plates can be securely closed.
Do not attempt to repair a damaged power cord. Do not modify the power cord in any way. Do not attempt to extend the length of the power cord or use an extension cord with this appliance. Do not share the single power outlet with any other appliances.
Indoor and outdoor unit equipment must each be on their own a dedicated breaker.
Indoor units must have a dedicated service disconnect. Switches are acceptable; however it must be a double pole switch that disconnects L1 and L2.
Figure 14. External Water Level Switch Connection
CAUTION
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected to a gas or water pipe, a lightning conductor or a telephone ground wire. Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed. Install all wiring at least 3 feet away from televisions, radios or other electronic devices in order to avoid the possibility of interference with the unit operation. Do not install the unit near a lighting appliance that
includes a ballast. The ballast may a󰀨ect remote control
operation.
In the U.S.A., wiring must conform with current local
codes and the current National Electric Code (NEC). In
Canada, wiring must conform with current local codes and
the current Canadian Electrical Code (CEC).
Refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
NOTE - Two-conductor stranded shielded cable must be used for the communication wiring. This is necessary to ensure proper system communication and operation.
13
Page 14
1. Remove the screws that secure the control box cover. Remove the cover and place it to the side where it will not be damaged.
2. Locate the terminal strip in the control box. Connect
the power wiring (sized per NEC/CEC and local codes)
and communications cable (two-conductor shielded
cable). Refer to unit nameplate for rated voltage.
3. If the indoor unit is the nal unit in a group that is wired in series, install the provided resistor across terminals P and Q.
Indoor units and mode selection boxes on the same refrigeration circuit should have a common power supply but must have an independent disconnect switch installed adjacent to each item of equipment for servicing and maintenance purposes. Indoor unit and mode selection box power supply MUST not be taken from the outdoor unit. Always follow NEC/CEC and Local Codes.
208/230V 1Ph 60Hz
Power supply
Dedicated breaker
208/230V 3Ph 60Hz
or 460V 3Ph 60Hz
Power supply
L2L1
L1 L2
L1 L2 L3
L1 L2 L3
Mode Selection Box Indoor unit
L2 L3L1
Service Disconnect
Outdoor Unit (Main Unit)
L1 L2 L3
L1 L2 L3
L1 L2 L3
Outdoor Unit (Sub1 unit)
Service Disconnect
L1 L2 L3
Indoor unit Indoor unit
L1 L2 L3
L1 L2 L3
Service Disconnect
Outdoor Unit(Sub2 Unit)
L1 L2 L3
Fuse
L1 L2
Service Disconnect
Fuse
L1 L2
Service Disconnect
Fuse
L1 L2
Service Disconnect
L1 L2
Fuse
Service Disconnect
Figure 15. Typical Power Wiring Diagram (VRF Heat Recovery System Shown)
14
Page 15
Outdoor unit Outdoor unit
(main unit)
(sub1 unit)
Outdoor unit
(sub2 unit)
P Q H1 H2X YO AK1 K2
Outdoor Unit Communication Terminal Block
(PQ)
P Q
(H1 H2 )
Install a terminating resistor (Ω120) on terminals P&Q on the indoor unit
(H1 H2 ) (H1 H2 )
(PQ)
(PQ)
(PQ)
MS
Box
(PQ)
MS
Box
(PQ)
which is furthest from the outdoor unit.
P Q
MS Box Communication
Terminal Block
HA HB 12V COM P Q
Indoor Unit Communication Terminal Block
Ground drain wire or cable shield to MS Box and Outdoor Unit chassis
All Drain Wires will connect from outdoor unit chassis to mode selection box chassis at the end of the signal run.
18 GA., stranded, 2-conductor, shielded control wire (polarity sensitive).
Typical Wiring Diagram, NEC/CEC and Local Codes apply.
NOTE - Each communication wire from the MS box should follow the refrigerant piping for that port.
Figure 16. Typical Communication Wiring Diagram (VRF Heat Recovery System)
15
Page 16
Outdoor unit
(main unit)
Outdoor unit
(sub1 unit)
Outdoor unit
(sub2 unit)
(H1 H2 )
(H1 H2 )
(H1 H2 )
P Q H1 H2X YO AK1 K2
Outdoor Unit Communication Terminal Block
(PQ)
HA HB 12V COM P Q
Indoor Unit Communication Terminal Block
(PQ)
P Q
Install a terminating resistor (Ω120) at the last indoor unit terminals P and Q of the daisy chain.
All shields of shielded cable connect to
chassis GROUND terminal at Indoor Units.
18 GA., stranded, 2-conductor, shielded control wire (polarity sensitive).
Typical Wiring Diagram, NEC/CEC and Local Codes apply.
Ground cable shield
to Indoor Unit chassis
Figure 17. Typical Communication Wiring Diagram (VRF Heat Pump System)
Tightening torque for the terminal screws
Use the correct screwdriver for tightening the terminal screws.
If the terminal screws are over tightened, screws might be damaged.
Refer to Table 5 for the tightening torque of the terminal screws.
IMPORTANT
DO NOT adjust DIP switch settings. Settings may only be adjusted by a trained technician as part of the com­missioning procedures.
Table 5. Terminal Screw Tightening Torque
Tightening torque (lb-ft)
Terminal base of remote controller/Signal
transmission wire (X2M)
Terminal base of power
supply (X1M)
Grounding terminal (M4) 1.06-1.43
After wiring, conrm all connections are correct; Then turn on power supply to the unit.
0.58-0.72
0.87-1.06
16
Page 17
Error code
E0
E1
E2
E3
E4
E5
E6
E7
EC
Vco2
COM
XT2
HA HB 12V COM QP
Error code
U4
F8
Eb
Ed
EE
FE A0
D8
WHITE BLUE RED
BLACK
YELLOW GRAY
Error Content
Mode conflict
Communication error between indoor and main outdoor unit
T0 (Inlet air temperature sensor) malfunction
T2 (Middle of evaporator sensor) malfunction
T2B (Outlet of evaporator sensor) malfunction
T2A (Inlet of evaporator sensor) malfunction
DC fan motor error
EEPROM failure
TA (Outlet air temperature sensor) malfunction
To wired controller comm. bus
To wired controller power
To outdoor/ indoor/MS units comm. bus
CO2
78
sensor
Error Content MS self-inspection error
MS error
EEV malfunction
Outdoor unit fault High water alarm
No address Emergency stop
Remote off
CS
FAN
HHE interface
( Current range: 0-1A)
Voltage range: 0-24V AC/DC)
(
CTON
HTON
4 5 6
Code
FM T0 T2A T2B
T2 TA
XP1-5
ON/OFF SWITCH
CN50
“ +5V GND +12V ” ONLY USED FOR TESTING
Title
Indoor fan motor
Inlet air temperature sensor Inlet of evaporator sensor
Outlet of evaporator sensor Middle of evaporator sensor
Outlet air temperature sensor
Connectors
DC motor drive board
CN13
CN3
N=3
Code
XS1-5
XT1-2
PUMP
CS
ALARM
EEV
Title
Connectors
Terminals Pump motor
Water level switch Warning lamp
Electronic expansion valve
SVD Solenoid valve
NOTE:
1. Refer to manual for communication wiring
2. Please use the 2-conductor shielded twisted cable for communication
FAN
FM
Display Board
XS4
T2B
XS3
T1/T0
XS2
T2
XS1
T2A
TA
XP4
XP3
XP2
XP1
EEV
XS5
RED
WHITE
CALB K
EULB
ACKLB
XP5
CN9
CN15
CN14
CN26
CN6
CN2{L_IN}
CN4{N_IN}
GND Vco2
CN8
CN11 CN5 CN52
CN12
CN30
EARTH
CN54
Main Board
CN3 CN18
CN20
N=4
LACKB
G/Y
DER
XT1
L1 L2
ALARM
PUMP
POWER IN
NOTE:
Component in dash line is optional or field wiring
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 18. VOSB036H4-3, VOSB048H4-3, & VOSB054H4-3
Typical Wiring Diagram
CN24
SVD
17
Page 18
Error code
E0
E1
E2
E3
E4
E5
E6
E7
EC
To wired controller comm. bus
To wired controller power
To outdoor/ indoor/MS units comm. bus
Error Content
Mode conflict
Communication error between indoor and main outdoor unit
T0 (Inlet air temperature sensor) malfunction
T2 (Middle of evaporator sensor) malfunction
T2B (Outlet of evaporator sensor) malfunction
T2A (Inlet of evaporator sensor) malfunction
DC fan motor error
EEPROM failure
TA (
Outlet air
temperature sensor) malfunction
NOTE:
1. Refer to manual for communication wiring
2. Please use the 2-conductor shielded twisted cable for communication
HA HB 12V COM QP
WHITE BLUE RED
BLACK
YELLOW GRAY
XT2
Vco2
CO2
78
sensor
COM
CN15
CN14
XP5
XS4
XS3
XS2
XS1
XP4
XP3
XP2
XP1
XS5
RED
WHITE
CALB K
EULB
ACKLB
CN9
CN2{L_IN}
CN4{N_IN}
GND
Vco2
CN26
CN6
CN8
Display Board
T2B
T1/T0
T2
T2A
TA
EEV
Error code
U4
F8
Eb
Ed
EE
FE A0
D8
CN11 CN5
CN12
CN30
EARTH
Error Content MS self-inspection error
MS error
EEV malfunction
Outdoor unit fault High water alarm
No address
Emergency stop Remote off
CS
FAN
CTON
HTON
HHE interface
( Current range: 0-1A)
Voltage range: 0-24V AC/DC
(
CN54
CN52
Main Board
CN50
4 5 6
“ +5V GND +12V ” ONLY USED FOR TESTING
CN3 CN28
ON/OFF SWITCH
)
CN27
CN18
N=3
Code
Indoor fan motor
FM T0
Inlet air temperature sensor Inlet of evaporator sensor
T2A
Outlet of evaporator sensor
T2B
T2
Middle of evaporator sensor
Outlet air temperature sensor
TA
Connectors
XP1-6
DC motor drive board
CN13
N=3
CN24
CN57+
CN58-
CN20
CN29
Title
CN3
RED
BLACK
BLUE
XP6XS6
DC motor drive board
FAN
FM
Rectifier Bridge
-
~
Code
XS1-6
Connectors
XT1-2
Terminals Pump motor
PUMP
Water level switch
CS
Warning lamp
ALARM
Electronic expansion valve
EEV
SVD Solenoid valve
CN3
CN13
Lorem ipsum
~
+
BLUE
Title
FAN
FM
N=4
LACKB
G/Y
DER
XT1
L1 L2
ALARM
PUMP1
PUMP2
SVD
POWER IN
NOTE:
Component in dash line is optional or field wiring
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 19. VOSB072H4-3 and VOSB096H4-3 Typical Wiring Diagram
Dip-switch setting:
See Table 6 for allowed indoor to outdoor unit combinations.
Use the SW8-1 dip switch to set whether or not the all of the indoor units in the system are VOSB units or if there is a mix of indoor units in the system.
0 - All indoor units in the system are VOSB.
1 - VOSB and common indoor units mix in one system.
Table 6. VOSB Indoor Unit to Outdoor Unit Allowed Connection Ratio
Outdoor Unit Indoor Unit
IDU/ODU Connection Ratio
VOSB/ODU Connection Ratio
Heat Pump VOSB Only ≤100% ≤100%
Heat Pump VOSB + other indoor units ≤100% ≤30%
Heat Recovery VOSB Only NOT ALLOWED NOT ALLOWED
Heat Recovery VOSB + other indoor units ≤100% ≤30%
18
Page 19
Relocate T0 Return Air Sensor
Relocate the unit return air from inside the unit to a loca­tion within the conditioned zone whenever the return is pulling air from above the ceiling or if fresh air is being introduced and mixed into the return. The T0 sensor can­not accurately read the space temperature under these conditions if the sensor remains located inside of the unit.
This sensor can be extended with 18 AWG stranded shielded cable.
1. Identify the T0 connection on the main board - CN4.
(white wires soldered to PCB)
Figure 22. Cut the Black Wire
4. Prepare the 18 AWG stranded shielded extension cable.
5. Solder the extension cable to the black wire on each
end or use the VRF accessory V0SNSR00P (13G99)
to splice in the extension cable.
6. Locate the return air thermistor to the conditioned area of which the indoor unit serves.
Figure 20. Identify T0 Sensor Connection on PCB
2. Identify where the white wire is plugged into the black wire.
Figure 23. Sensor Thermistor
IMPORTANT
Avoid installing sensor in high load or heat loss areas such as exterior walls or walls that are against uncondi­tioned spaces, near entry doors and windows, or where direct sunlight may be present.
Figure 21. Identify White Plug into Black Wire
3. Cut the black wire between the plug and the sensor thermistor. Leave adequate room for making wiring connections on each end.
19
Page 20
Error code
E0
E1
E2
E3
E4
E5
E6
E7
EC
Error Content
Mode conflict
Communication error between indoor and main outdoor unit
T0 (Inlet air temperature sensor) malfunction
T2 (Middle of evaporator sensor) malfunction
T2B (Outlet of evaporator sensor) malfunction
T2A (Inlet of evaporator sensor) malfunction
DC fan motor error
EEPROM failure
TA (Outlet air temperature sensor) malfunction
To wired controller comm. bus
To wired controller power
To outdoor/ indoor/MS units comm. bus
CO2 sensor
Error code
U4
F8
Eb
Ed
EE
FE A0
D8
XT2
HA HB 12V COM QP
WHITE BLUE RED
BLACK
YELLOW GRAY
Vco2
78
COM
Error Content MS self-inspection error
MS error
EEV malfunction
Outdoor unit fault High water alarm
No address Emergency stop
Remote off
CS
FAN
HHE interface
( Current range: 0-1A) (
Code
XP1-5
CN50
CTON
HTON
4 5 6
Voltage range: 0-24V AC/DC)
“ +5V GND +12V ” ONLY USED FOR TESTING
Title
Indoor fan motor
FM T0
Inlet air temperature sensor Inlet of evaporator sensor
T2A
Outlet of evaporator sensor
T2B
T2
Middle of evaporator sensor
TA
Outlet air temperature sensor
Connectors
ON/OFF SWITCH
DC motor drive board
CN13
N=3
XS1-5
XT1-2 PUMP
ALARM
CN3
Code
Title
Connectors
Terminals Pump motor
Water level switch
CS
Warning lamp
Electronic expansion valve
EEV
SVD Solenoid valve
NOTE:
1. Refer to manual for communication wiring
2. Please use the 2-conductor shielded twisted cable for communication
FAN
FM
Display Board
XS4
T2B
XS3
T1/T0
XS2
T2
XS1
T2A
TA
XP4
XP3
XP2
XP1
EEV
XS5
RED
WHITE
CALB K
ACKLB
CN15
XP5
CN9
CN6
EULB
CN2{L_IN}
CN4{N_IN}
CN14
CN26
XT1
GND Vco2
CN8
DER
L1 L2
CN11 CN5 CN52
CN12
CN30
EARTH
N=4
LACKB
G/Y
CN54
Main Board
CN3 CN18
ALARM
CN20
PUMP
POWER IN
NOTE:
Component in dash line is optional or field wiring
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 24. Identify T0 Sensor on Wiring Diagram
White plug
CN4
Black wire
18 AWG stranded shielded cable
CN24
SVD
Black wire
White wire
Figure 25. Typical Wiring Connections
Setting Blower Operation
Blower cycling can be congured to determine indoor
operation.
Default operation is indoor unit blower OFF when the indoor unit is in thermo OFF.
Settings can be adjusted in the -3P controller and
cannot be congured at the indoor unit PCB.
Thermistor
Solder or connect with V0SNSR00P
Consult the specic controller manual for detailed blower setting information.
NOTE - Ensure the blower is set to the ON position when using an electrical duct heater.
20
Page 21
Mounting the Receiver/Display
The VOSB unit receiver/display must be eld-connected
and mounted. Mounting slots are available on the bottom of the electrical control box.
1. Remove receiver from accessories package.
2. Insert the two xed plastic mounting brackets on the
back of the receiver (Figure 26) into the two slots on the bottom of the electrical control box (Figure 25) and
slide to secure it.
3. Connect the 10-conductor wire of the receiver to the unit control board. Pass the wire though the cable path. See Figure 27.
Cable path
Slots
Electrical
control box
Figure 27. Receiver Mounting Location
Fixed plastic
mounting
brackets
10-conductor wire
(to unit control board)
Figure 26. Receiver
If it is necessary to position the receiver a distance from the unit, use the optional extension cable kit V0CTRL93P-1
(cat # 14R84).
Network Address and Commissioning
After the system has been installed, each indoor unit must be assigned an address as part of the commissioning procedure.
21
Page 22
Spot Check Instructions
Use the Spot Check Performance table below and the Manual button on the unit receiver to view diagnostic information the indoor unit.
Table 7. Spot Check Performance Identication Table
No. Content Recorded Value/Date
0 Normal display
1 Communication address of indoor unit
2 Indoor unit capacity (horsepower)
3 Network address of indoor unit
4 The actual setpoint temperature
5 The actual indoor temperature T1
6 The middle coil temperature T2
7 The coil inlet temperature T2A
8 The coil outlet temperature T2B
9 The discharge temperature TA
10 The actual superheat temperature
11
12 The actual subcool temperature
13 Error Code
14 Indoor software version
15 End (--) This Spot Check Performance table is located on the unit service panel.
The diagnostic information can also be obtained using the wired remote controller.
The target subcool (heating) /superheat (cooling)
temperature
22
Page 23
Troubleshooting
Digital Display
The indoor unit is equipped with a receiver that has a digital display that provides an error code. Refer to the table to view the error codes. The error code will replace the temperature setting displayed on the receiver. If more than one error has occurred, the codes will alternate so that all codes are shown.
Figure 28. Receiver/Display
Make note of the code (E1, EE, etc.), then reset the
display by pressing the ON/OFF button on the unit controller. Press the ON/OFF button a second time to reapply power to unit. If the code is still displayed, disconnect and restore power at the unit disconnect switch or circuit breaker. If the problem was temporary, the code will not reappear. If the error code reappears after power has been broken and restored at the disconnect switch or circuit breaker, call VRF Technical Support 1-844-438-8731.
Table 8. Fault Code Display on Indoor Unit Receiver
Error Code Description
FE No address
E0 Mode conict
E1 Communication error between indoor and main outdoor unit
E2 T0 (Room temperature sensor) malfunction
E3 T2 (Middle of evaporator sensor) malfunction
E4 T2B (Outlet of evaporator sensor) malfunction
E5 T2A (Inlet of evaporator sensor) malfunction
E6 DC fan motor error
E7 EEPROM failure
Eb EXV malfunction
EC TA (Discharge temperature sensor) malfunction
Ed Outdoor unit Fault
EE High Water Alarm
A0 Emergency stop
D8 Remote o󰀨
U4 MS self-inspection error
F8 MS error
Table 9. Fault Code Display on Controller
Error Code Description
F0 Communication/Address error between indoor units and wired controller
F1 Communication/Wiring error between indoor units and wired controller
E2 Controller temperature sensor error
23
Page 24
Technical Support
1-844-GET-VRF1
(1-844-438-8731)
vrftechsupport@lennoxind.com
www.LennoxVRF.com
Download the app
from the Apple App Store or the Google Play store.
24
Loading...