Lennox VOSA036S4, VOSA048S4, VOSA054S4, VOSA072S4 Installation Instruction

Page 1
©2017 Lennox Industries Inc.
Dallas, Texas, USA
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li­censed professional HVAC installer, service agency or the gas supplier.
Failure to follow safety warnings and these instruc­tions exactly could result in property damage, dan­gerous operation, serious injury, or death.
Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the ap­plication needs must be made by a licensed profes­sional HVAC installer (or equivalent) using factory­specifi ed parts.
Do not use this system if any part has been under water. A fl ood-damaged appliance is extremely dan- gerous. Immediately call a licensed professional HVAC service technician (or equivalent) to inspect the system and to replace all controls and electrical parts that have been wet, or to replace the system, if deemed necessary.
The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
NOTE - VOSA054 and VOSA072 units have special wiring and piping considerations, see page 17.
INSTALLATION INSTRUCTION
VOSA Outdoor Air Units
VRF SYSTEMS -- Indoor Units 507447-01 03/2017
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.
General
The VOSA dedicated outdoor air concealed ducted indoor units are matched with an outdoor heat pump unit (excluding Mini-VRF) to create a VRF (variable refrigerant fl ow) system that uses HFC-410A refrigerant.
Refer to the Product Specifi cation bulletin (EHB) for the proper use of these indoor units with specifi c heat pumps, heat recovery units, mode switching devices, branch pipes, line sets and controls.
Shipping and Packing List
Check the components for shipping damage. If you fi nd any damage, immediately contact the last carrier.
Package 1 of 1 contains the following:
1 - Assembled dedicated outdoor air concealed ducted unit
Refrigerant piping insulation sleeves
2 - VOSA036 and VOSA048
4 - VOSA054 and VOSA072
1 - Flexible condensate connector (VOSA036-048)
1 - Hose clamp (VOSA036-048)
1 - Condensate connection pipe (VOSA054-072)
1 - Roll tape for condensate pipe (VOSA054-072)
1 - Branch pipe kit (VOSA054-096)
Flare Nuts
1 - VOSA036-048
2 - VOSA054-096
2 - Connector for electronic expansion valves and liquid lines (VOSA054-072)
1 - Resistor
1 - Installation manual
1
Page 2
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Do not touch the unit or the controller if your hands are wet. DO NOT spray water on the indoor unit for any reason. Do not replace a fuse with a fuse of a different rating. Do not use a jumper wire to replace a fuse. Do not insert your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit. Do not allow children to operate the system.
Model Number Identifi cation
V OS A 036 S 4 - 1 P
Brand/Family
V = Variable Refrigerant Flow (VRF)
Unit Type
OS = Dedicated Outdoor Air Concealed Ducted Indoor Models
Major Design Sequence
A = 1st Generation
Nominal Cooling Capacity - Btuh
036 = 36,000 Btuh 048 = 48,000 Btuh 054 = 54,000 Btuh 072 = 72,000 Btuh
System Piping
CAUTION
VRF system piping is customized for each installation. The LVSS piping report is an engineered design that must be followed. The piping diagram or diagrams included within the LVSS report have been prepared based on the information provided to the Lennox VRF applications department.
When the indicated lengths change from the fi gures stated within the report, it is imperative that prior to the commencement of the refrigerant pipe work installation, Lennox VRF applications department are informed of these proposed changes.
Upon receipt of this new information the Lennox VRF applications department will confi rm any changes that may be applicable to this installation. If changes are required, a new piping diagram will be produced and will supersede all other previously provided documents.
Failure to provide this information regarding changes to the original design may lead to insuffi cient capacity, equipment failure, warranty being made void and the refusal to commission the system.
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Refrigerant Type
4 = R-410A
Cooling Effi ciency
S = Standard Effi ciency
2
Page 3
Unit Dimensions - Inches (mm)
VOSA036S4, VOSA048S4
13-3/8 (339)
(Duct Opening)
3-1/4
(83)
2-1/2
(65)
HOLES FOR SUSPENDING (4)
25-1/8
(638)
23-5/8
(600)
2 (51)
1-1/4
(38)
42-1/4 (1073)
(Duct Opening)
RETURN AIR VIEW
AIRRETURN
45-1/4 (1149)
RETURN AIR
DUCT FLANGE
1-3/8
(35)
3-1/2
(89)
2-3/4
(70)
3-1/4
(83)
LIQUID
PIPE
5-3/8 (137)
5/8 (16)
10 (253)
GAS PIPE
DRAIN
CONNECTION
(Either Side)
SUPPLY AIR
DUCT FLANGE
5-3/8 (109)
3-1/4
(83)
AIRSUPPLY
TOP VIEW
51-1/4 (1302)
36-5/8 (930)
1-1/8 (29)
9-7/8 (251)
(Duct Opening)
SUPPL Y AIR VIEW
3
3-1/2
(89)
3/4 (19)
2-1/4 (57)
10-5/8
(270)
16-1/2
(419)
ELECTRICAL
CONTROL
BOX
Page 4
VOSA036S4, VOSA048S4
13-3/8
(339)
(Return
Air Duct
Opening)
2
(51)
1-5/8 (41)
7-3/8 (187)
GAS PIPE
BOX
4-7/8 (124)
4-7/8 (124)
27-1/4
(692)
1/2
(11)
9-7/8
(251) (Supply Air Duct
Opening)
1-3/8
(35)
AUXILIARY
DRAIN
CONNECTION
(Either Side)
ELECTRICAL
CONTROL
1/2 (11)
LEFT SIDE VIEW RIGHT SIDE VIEW
ELECTRONIC
EXPANSION
VALVE
1-5/8
(41)
7-3/8 (187)
LIQUID
PIPE
16-1/2
(419)
DRAIN
CONNECTION
(Either Side)
4
Page 5
Unit Dimensions - Inches (mm)
VOSA054S4, VOSA072S4
13-1/2 (343)
(Duct Opening)
3-7/8 (98)
HOLES FOR
SUSPENDING (4)
32
(813)
3
(76)
SUPPLY AIR
DUCT FLANGE
2-3/8 (60)
44-1/8 (1121)
(Duct Opening)
RETURN AIR VIEW
AIRRETURN
50-1/4 (1276)
56-3/4 (1141)
AIRSUPPLY
RETURN AIR
DUCT FLANGE
GAS
PIPES (2)
2-1/4 (57)
2-5/8 (67)
LIQUID
PIPES (2)
TOP VIEW
2 (51)
15 (381)
(Duct Opening)
8 (203)
37 (940)
(Duct Opening)
SUPPL Y AIR VIEW
ELECTRONIC
EXPANSION
VALVES
18-1/2
(470)
ELECTRICAL
CONTROL
BOX
DRAIN
CONNECTION
RIGHT SIDE VIEW
LIQUID
PIPES (2)
GAS
PIPES (2)
4
(102)
5 (127)
1-3/4 (44)
2-3/4
(70)
5
Page 6
Clearances
Refer to fi gure 1 for minimum clearance requirements.
Wall
Wall
Air
Flow
20” (508 mm) Minimum Service Clearance
24” (610 mm)
24” (610 mm)
Minimum
Service
Clearance
Minimum Service Clearance
TOP VIEW
Ceiling
1” (25 mm) Minimum Clearance
1” (25 mm) Minimum Clearance
CeilingSuspended
FRONT VIEW
NOTE - No part of the suspended ceiling, or other supports not directly associated with the indoor unit installation, can be fi xed to, or touch the indoor unit, in any form. Minimum clearances must be observed at all times.
Figure 1. Minimum Installation Clearances
6
Page 7
Unit Placement
WARNING
Use the provided and specifi ed components when installing equipment. Failure to do so may result in unit falling, water leaking or electrical shocks, caus ing personal injury or equipment or property dam age.
Check stability of wall, fl oor, or ceiling and unit support. If sup port is not capable of carrying weight of the unit, unit may fall causing personal injury or equipment damage.
Consider the possibility of earthquakes in your area when installing the equipment. If the unit is not correctly secured, it may fall, causing personal injury or equipment damage.
Safely dispose of packing materials, which include nails, wood and other sharp objects, as well as plastic wrapping. Children playing with plastic wrap or bags risk the danger of suffocation.
CAUTION
Do not place items which may be damaged by water under or around the indoor unit.
The unit should be installed at least 8 feet above the oor (if possible) to ensure maximum performance and comfort, when installed in the horizontal position only.
AVOID
Do not install the unit in the following locations:
• Areas exposed to petrochemicals or petrochemical products
Areas exposed to salt or other corrosive materials or caustic gasses
Areas exposed to extreme voltage variations (such as factories
Tightly enclosed areas that may impede service of the unit
Areas exposed to fossil fuels (such as oil or gas in kitchens)
Areas exposed to strong electromagnetic forces
Areas exposed to acids or alkaline detergents (laundry rooms)
DO:
• Locate the unit so that it is not exposed to direct sunlight
Ensure the structural ceiling can support the weight of the unit.
Select a location where condensate line will have the shortest run to a suitable drain per local codes.
• Allow suffi cient space around unit for proper operation and maintenance
Install unit a minimum of 3 feet away from any antenna, power cord (line) radio, telephone, security system, or intercom. Electrical interference and radio frequencies from any of these sources may affect operation
7
Page 8
Installation
It is important to locate the unit where it can be accessed for service in the future. Refer to unit dimensions on Page 3 for exact locations of suspension brackets, return air and supply air openings.
1. Make sure that the structural ceiling or slab is able to support the weight of the indoor unit. It may be necessary to add extra support.
2. Install suspension rods in the structural ceiling or concrete slab in a suitable location. If the structural ceiling is constructed of concrete, install anchors to accept four ” threaded rods to suspend the indoor unit. If the structural ceiling includes wooden joists, use angle iron or Unistrut channel fi xed securely in place to accept the ⅜”
threaded rods. NOTE - Threaded rod (requirement
of Lennox warranty program) is the ONLY acceptable method of suspending the unit; do not use chains or straps. See gure 2.
Ǫ´7+5($'(D
CONCRETE CEILING
USING ANCHORS
$1&+25
ANGLE IRON
BOLTED IN
PLACE ACROSS
WOODEN JOISTS
Ǫ´7+5($'(D
ROD
ANGLE IRON
WOODEN JOISTS
WOODEN JOIST
Figure 2. Suspending Methods
3. Slide one nut and one washer onto each threaded rod. Use electrical tape to keep the washer from failing off. Position the nuts slightly above the fi nal resting place of the four suspension brackets. See fi gure 3.
Ǫ” THREADED
ROD
INDOOR UNIT
SUPPLY AIR
OPENING
LEVELING
FRONT VIEW
NUT
Figure 3. Suspension Hardware
ROD
ACROSS
When unit is level, tighten
nut to secure
position of
suspension
bracket on
SUSPENSION
BRACKET
rod.
Ǫ” THREADED
ROD
FIELD-PROVIDED
ISOLATION GROMMET
WASHER
LEVELING
NUT
SUSPENSION
BRACKET
Figure 4. Isolation Grommet
4. Use either a mechanical lifting device or a minimum of two people to raise the unit and insert the threaded rods into the suspension brackets on the cassette base. Slide a washer and then a nut onto each rod below each suspension bracket. Use the leveling nut (beneath suspension bracket) to adjust the unit to the correct height. Remove the electrical tape holding the upper washers and nuts in place and tighten each of the four nuts above the brackets down onto the brackets. This will ensure that the unit remains level.
5. If necessary, install a fi eld-provided isolation grommet as shown in fi gure 4 to prevent transmission of vibration from unit to structural ceiling.
6. If the unit is being installed in an application that includes a sheet rock (plasterboard) ceiling, it is required that an access panel be installed in a suitable location. This will also allow access for future maintenance (requirement of Lennox warranty program). Access is required during the commissioning process to test the condensate disposal system (See fi gures 10, 11 and 12), to check the electronic expansion valve and associated fl are nuts (See fi gure 5), and to check the local disconnect.
7. The unit is factory-confi gured for the supply air to be delivered from the front and the return air fi lter at the rear of the unit.
INSTALLATION GUIDELINES
• Install a eld-provided isolation grommet as shown in gure 4 to prevent transmission of vibration from unit
to structural ceiling.
Provide separate support for the weight of the duct system. Duct system must not be supported by the indoor unit.
• Use fl exible joints (canvas) at the point where the duct connects to the unit on both ends. Material must meet all local and national code requirements.
When unit is being installed in a location where even the slightest noise would be a problem (meeting room or other very quiet space), design duct system to avoid transmission of vibration to the structure to the extent possible.
8
Page 9
Refrigerant Piping Connections
WARNING
Refrigerant leaks are unlikely; however, if a refrigerant leak occurs, open a door or windows to dilute the refrigerant in the room. Turn off the unit and all other appliances that may cause a spark. Call a licensed professional HVAC technician (or equivalent) to repair the leak.
Use only R410A refrigerant to charge this system. Use of other refrigerant or gas will damage the equipment.
Do not allow air or other contaminants to enter system during installation of refrigerant piping. Contaminants will result in lower system capacity and abnormally high operating pressures and may result in system failure or explosion.
Insulate all refrigerant piping. Refrigerant pipes may be very hot during unit
operation. Do not allow contact between wiring and bare copper pipes.
After refrigerant piping connections have been completed, check the system for leaks per commissioning instructions.
NOTE - See page 21 for additional piping instructions for VOSA054 and 072 units.
Field piping consists of two copper lines connected to the indoor unit. Table 1 lists the connection sizes at the indoor unit. The connections are made using the provided brass are nuts at the end of the refrigerant piping connections.
Both lines must be individually insulated.
NOTE - Always slide a fl are nut onto the fi eld-provided
refrigerant piping before fl aring the lines.
1. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or water from getting into the refrigerant piping before it is connected.
2. Slowly loosen one of the fl are nuts to release the factory nitrogen charge.
3. Remove the fl are nuts and discard the seal from each of the piping connections.
4. Slide the fl are nuts onto the ends of the fi eld-provided refrigerant piping before using a suitable fl aring tool to are the end of the copper pipe.
IMPORTANT
The compressor in this unit contains PVE oil (Polyvinylether). PVE oil is formulated for hydrofl uorocarbon (HFC) refrigerants, such as R- 410a, which this system contains. While it may have some miscibility properties with mineral-based oil and POE oil (Polyolester), it is not recommended to mix PVE oil with any other type of refrigerant oil.
5. Apply recommended HFC-410A refrigerant lubricant to the outside of the fi eld-provided fl ared line sets (fi gure 5 -- A).
6. Align the union tube and fl ared refrigerant lines with each other, then tighten the fl are nuts lightly at fi rst to obtain a smooth match (fi gure 5 -- B).
Table 1. Refrigerant Piping Connections
System Size
(Btuh)
36000
48000
54000
72000
A
Liquid Line Vapor Line
3/8” 5/8”
3/8” (2) 5/8” (2)
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
B
Figure 5. Making Connections at Indoor Unit
(Male to Female Connection)
7. Once snug, continue another half-turn on each nut which should create a leak-free joint. A torque wrench may be used to tighten fl are nuts using Table 2 recommendations. See fi gure 6. Do not over-tighten a fl ared joint.
IMPORTANT
Always use two wrenches when tightening fl are nuts to avoid twisting refrigerant piping. DO NOT over-tighten fl are nuts.
TORQUE WRENCH
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 6. Tighten Flare Nut
BACKUP
WRENCH
9
Page 10
8. Flared connections should always be accessible and must be insulated to prevent condensation. See fi gure
7.
Table 2. Flare Nut Torque Recommendations
Outside
Diameter
Inches U.S.
3/8” 26 ft.-lb. 1/2 turn
5/8” 48 ft.-lb. 1 full turn
UNIT BASE
Recommended
Torque
INSULATE ALL FLARED CONNECTIONS
TO PREVENT CONDENSATION
No torque wrench
available
Finger tighten and
use an appropriately
sized wrench to turn an
additional:
Incoming liquid line connection
Incoming suction line connection
Connect these two pipes
Connect these two pipes
Figure 7. Insulate Flared Connections
9. Locate the pre-formed copper connector pipes provided in the bag assembly (VOSA054-072 only). These pipes are used to connect the unit piping to the electronic expansion valves. Remove the plastic seal from each end of the pipe. See fi gure 8.
10. Apply a small amount of recommended HFC-410A refrigerant lubricant to the outside of the fl ared ends of the connector.
11. Immediately align the connector pipe with the identifi ed piping in fi gures 8 & 9. Hand-tighten the fl are nuts at rst. Then, use two wrenches to continue to tighten the nuts without twisting the pipes. See fi gure 6.
Torque requirements are given in table 2. Again, do
not over-tighten the fl ared joints.
12. After refrigerant piping has been installed and checked for leaks, apply insulation over the connector pipes and all fl ared connections.
Incoming suction line connection
Incoming liquid line connection
Figure 8. VOSA054/072 Refrigerant Connections
Incoming suction line connection
Incoming liquid line connection
Figure 9. VOSA036/048 Refrigerant Connections
10
Page 11
Condensate Piping Connections
CAUTION
Make sure that drain piping is properly routed and insulated in order to prevent both leaks and condensation. Follow these instructions exactly to ensure proper drainage and unit operation.
1. Use the provided hose clamp to secure the provided fl exible condensate drain connector and insulating sleeve to the drain line stub on the side of the indoor unit. See fi gure 10.
NOTE - T ake care not to over -tighten the hose clamps this may damage the drain line stub.
024 shown
CONTROL
BOX
3. See fi gure 11 for applications including a single unit and a single drain. In this case, ensure that the drain line is properly sloped (no less than 1/4 inch per foot) and condensate lines are routed to ensure moisture is drained away from the indoor unit.
Structural Ceiling
Suspension Rods
Indoor Unit
Do not operate unit without condensate drain trap.
NOTE - Drain line should be sloped 1/4 inch per foot (18 mm per m) AWAY from unit and should be supported as needed to prevent sagging.
Do not overtighten drain fitting.
Anti-siphon vent must extend above the height of the coil drain pan by 2” (51 mm).
1 ft.
(305 mm) max
Clean Out Do not glue
3”
3”
3 ft.
(1 m)
Support
straps
Drain line
Figure 11. Sloped Condensate Drain -- Single Unit
AUXILIARY
DRAIN
CONNECTION
(Either Side)
INDOOR
CONDENSATE
LINE STUB
UNIT
(Bottom of Unit)
FLEXIBLE DRAIN
CONNECTOR
HOSE CLAMP
PRIMARY
DRAIN
CONNECTION
(Either Side)
PVC DRAIN
PIPE
INSULATION
Figure 10. Condensate Drain Connection
IMPORTANT
You must confi rm operation of every drain and pump in the system as part of the commissioning procedure.
2. Make a water-tight connection between the fi eld- provided condensate drain line and the fl exible condensate connector (VOSA036-048 5/8” I.D., VOSA054-072 1” I.D.).
Install an anti-siphon vent for each trap - must extend above the height of the coil drain pan by 2” (51 mm).
IMPORTANT
Drain should have a slope of at least 1/4 inch per foot and should be approved corrosion-resistant pipe.
4. See fi gure 12 for applications including multiple units and a single drain. In this case, ensure that the drain line is properly sloped (no less than 1/4 inch per foot) and condensate lines are routed to ensure moisture is drained away from the indoor unit.
5. In all cases, drain should be as short as possible and should not have any droops or kinks that would restrict condensate fl ow and shall be constructed using an
approved pipe. All drains should contain traps. There
must be a 2-inch space between the end of the condensate drain and the fi nal termination point (ground, open drain, etc.) to ensure that the line will drain freely.
6. After system installation is complete, the condensate drain line must be checked for leaks and if a condensate pump has been fi tted, it must be checked to ensure proper operation. This check is part of the commissioning procedure.
Suspension
Rods
Indoor Unit tinU roodnItinU roodnI
Install a trap for each indoor unit.
Do not operate unit without condensate drain trap.
Do not overtighten drain fitting.
Clean Out Do not glue
3”
3”
Figure 12. Using a Main Drain to Serve Multiple Indoor Units with Gravity Drains
1 ft.
Clean Out Do not glue
Vent
3”
3”
NOTE - Drain line should be sloped 1/4 inch per foot (18 mm per m) AWAY from unit and should be supported as needed to prevent sagging.
(305 mm) max
Clean Out Do not glue
Vent
3”
3”
11
3 ft.
(1 m)
Support
straps
Page 12
Wiring Connections
WARNING
Isolate the power supply before accessing unit electrical terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this installation instruction, during installation. Do NOT overload electrical circuit, as this may lead to failure and possible fi re.
Use specifi ed wiring and cable to make electrical connections. Clamp cables securely and make sure that connections are tight to avoid strain on wiring. Insecure wiring connections may result in equipment failure and risk of fi re.
Wiring must be installed so that all cover plates can be securely closed.
CAUTION
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected to a gas or water pipe, a lightning conductor or a telephone ground wire.
Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed.
Install all wiring at least 3 feet away from televisions, radios or other electronic devices in order to avoid the possibility of interference with the unit operation.
Do not install the unit near a lighting appliance that includes a ballast. The ballast may affect remote control operation.
CAUTION
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fi xed wiring according to the National Wiring Regulation.
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
NOTE - Three-conductor stranded shielded cable must be used for the communication wiring. This is necessary to ensure proper system communication and operation.
NOTE - See page 27 for wiring and piping instructions for VOSA054 and 072 units.
A circuit breaker capable of shutting down the power supply to the entire system must be installed.
A single switch can be used to supply power to units on the same system. However, branch switches and circuit breakers must be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as shown in the wiring diagram.
• Install a wiring interrupter or ground-fault circuit interrupter for the power wiring.
Make sure the ground resistance is no greater than 100Ω. This value can be as high as 500Ω when using a grounding fault circuit interrupter since the protective ground resistance can be applied.
1. Remove the screws that secure the control box cover. Remove the cover and place it to the side where it will not be damaged.
2. Locate the terminal strip in the control box. Connect the power wiring (sized per NEC/CEC and local codes) and communications cable (three-core, shielded cable). Refer to unit nameplate for rated voltage.
3. If the indoor unit is the fi nal unit in a group that is wired in series, install the provided resistor across terminals P and Q.
4. The infra-red receiver / display panel is factory installed and can be repositioned, if necessary. Use optional extension cable kit V0CTRL93P-1 (cat # 14R84).
12
Page 13
Tightening torque for the terminal screws
Use the correct screwdriver for fi ghting the terminal screws. If the screwdriver blade is too small, the head of the screw might be damaged, and the screw will not be properly tightened.
• If the terminal screws are over tightened, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
IMPORTANT
DO NOT adjust DIP switch settings. Settings may only be adjusted by a trained technician as part of the com­missioning procedures.
Table 3. Terminal Screw Tightening Torque
Tightening torque (lb-ft)
Terminal base of remote controller/Signal transmission wire (X2M)
Terminal base of power supply (X1M)
Grounding terminal (M4) 1.06-1.43
• After wiring, confi rm all connections are correct; Then turn on power supply to the unit.
0.58-0.72
0.87-1.06
Power DistribuƟon Box
Legend
PQE CommunicaƟon wiring
L1/L2 Single-Phase power wiring
Electrical disconnect switch
L1/L2
L1/L2
L1/L2
L1/L2
L1/L2
L1/L2
PQE
PQE
PQE
PQE
PQE
PQE
PQE
PQE
PQE
PQE
L1/L2
L1/L2
L1/L2
L1/L2
L1/L2
L1/L2
PQE
L1/L2
L1/L2
L1/L2
Figure 13. Typical Power Wiring Diagram (VRF Heat Pump System Shown)
13
PQE
L1/L2
PQE
L1/L2
PQE
L1/L2
PQE
Page 14
Outdoor unit
(main unit)
Outdoor unit
(sub1 unit)
Outdoor unit
(sub2 unit)
(PQE)
(H1 H2 E) (H1 H2 E)
Ground cable shield
(H1 H2 E)
DO NOT connect to E
(PQE)
P Q
Install a terminating resistor at the last indoor unit terminals P and Q of the daisy chain.
All shields of shielded cable connect to GROUND terminal,
not to terminal E.
18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive).
Typical Wiring Diagram, NEC/CEC and Local Codes apply.
Figure 14. Typical Communication Wiring Diagram (VRF Heat Pump System Shown)
14
Page 15
KEY
FM
EEV
TA T0
T2B
T2 XP1-7 XS1-7
C
TR PUMP
CS
XT1-2
GM
COMPONENT
INDOOR FAN ELECTRONIC
EXPANSIONVALVE OUTLETAIRTEMP.
INLETAIR TEMP.
EVAPOUTLETTEMP
IN COOLING MODE
COIL TEMP.
PLUG JACK
FAN CAPACITOR
TRANSFORMER PUMP MOTOR
WATER
LEVEL SWITCH
TERMINAL BLOCK
SWING MOTOR
;6
&1
;3
',63/$< %2$5'
;3
&1δ<(//2:ε
32:(5B6
21
-
6:
&1
(1&
&1
&1
&1
&1
&1
;6
:,5(' &21752//(5
&21752/ ,17(5)$&( 02'8/(
;6
;3
:((./< 7,0(5 :,5(' &21752//(5
ALARM
&1
TA
BLACK
&1
21
6:
21
6:
&1
&1δ:+,7(ε
21
6:
75
&1
&1
;6
5('
%/8(
&1
&1
0$,1 &21752/ %2$5'
5<
5<
5<
3
3
&1
<*
*5281'
5('
:+,7(
&
:+,7(*5$<
)0
<(//2:*5((1
*5281'
:+,7(
7
%/$&.
7
φ
127( &20321(17 ,1 '$6+ /,1( ,6 237,21$/ 25 ),(/' :,5,1*
;7
/
,1'225 32:(5
L2
   
z
No addres s g ive n on initial uni t start -u p
z Mode conflict
z Communication error
between indoor and outdoor unit
Timer and R un LEDs flashing simultaneously, or "FE" displayed
Def rost LEDflas hing,
or "E0" d isplayed
Timer LE D flashin g or "E1" displayed
z Temp se nsor (T1) erro r
z Temp sens or T2 error˄˅
z Temp sens or T2B error˄˅
Run LED flashingor 2"
displaye d
RunLEDflashingor 3"
displayed
RunLED flashing or "E4"
disp l ayed
"E
"E
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 15. VOSA036S4-1 and VOSA048S4-1 Typical Wiring Diagram
7%
z Eeprom error
z Outdoor unit error
z Water level alarm
((9
;7
&211(&7 72 :,5(' &21752//(5
127(  5()(5 72 0$18$/ )25
Defrost L ED flashing slowly or "E7" displayed
AlarmLED flashing slowlyor "Ed" displayed
Alarm LED flashing or
E" displayed"E
(E)
P Q (E)XY
&211(&7 72 287'225 81,7
&20081,&$7,21 :,5,1*
 3/($6( 86( 7+(
&21'8&725 6+,(/'(' &$%/(
15
Page 16
75%
φ
127( &20321(17 ,1 '$6+ /,1( ,6 237,21$/ 25 ),(/' :,5,1*
KEY
COMPONENT
FM1(FM2)
TA(A),TA(B) T0(A),T0(B)
T2B(A),T2B(B)
T2(A),T2(B)
XP0-9 XS0-9
TR(A),TR(B)
XT1-3
RL1-3
CAP1(CAP2)
290-0G2
EEV
INDOORFAN ELECTRONIC
EXPANSIONVALVE OUTLETAIR TEMP.
INLETAIRTEMP.
EVAPOUTLET TEMP
IN COOLING MODE
COIL TEMP.
PLUG JACK
TRANSFORMER
TERMINAL BLOCK
RELAY
FAN CAPACITOR
NOISE FILTER
:+,7(
&1
7%
&1
%/$&.
7%
TA (B)
&1
&1
21
21
6:
6:
COMM.BUS
BLACK
&1
21
6:
0$,1 &21752/ %2$5'%
% 6<67(0
&1 &1
((9
7%%
;7
&211(&7 72 :,5(' &21752//(5
127(  5()(5 72 0$18$/ )25
TO CCM
&1
&1
32:(5B6
21
-
6:
(1&
&1
XY PQ
&20081,&$7,21 :,5,1*
 3/($6( 86( 7+(
&21'8&725 6+,(/'(' &$%/(
E
&211(&7 72 287'225 81,7
&1 
',63/$< %2$5'
;6
TA(A)
75$
&1
&1
&1
&1
&1
0$,1 &21752/ %2$5'$
BLACK
21
6: 6:
TO CCM
COMM. BUS
&1 &1
&1
21
21
6:
;3
&1 
-
&21752/ ,17(5)$&( 02'8/ (
32 :(5 B6
21
6:
(1&
$ 6<67(0
&1 
&1
&1
:+,7(
((9
7%$7$
XY PQ
&20081,&$7,21 :,5,1*
 3/($6( 86( 7+(
&21'8&725 6+,(/'(' &$%/(
;7
L2
/
72 ,1'225 32:(5
BLUE
&1
5/
5('
<*
GROUND
&20
5(' 5(' 5('
*
7 
5<5<5<
5/
5/
&20
&20
0(',80+,*+
/2:
<* <*< *
&1
BLACK
:+,7(
7$
;7
&211(&7 72 :,5(' &21752//(5
127(  5()(5 72 0$18$/ )25
&1
E
&211(&7 72 287'225 81,7
:,5(' &21752/ /(5
z
No addr ess gi v e n on initial uni t sta rt -up
z Mode conflict
z Commun ication error
between indoorand outdoor unit
Timer andRunLEDs flashingsimultaneously, or "FE" displayed
Defros t LED flas hing,
or "E0"displayed
Timer LED flashing or "E1" displayed
z Temp sensor (T1 ) erro r
z Temp sensor T2 error˄˅
z Temp sensor T2B error˄˅
Run LED flashingor 2"
display ed
RunLEDflashingor 3"
displ a yed
RunLED flashing or "E4"
displayed
"E
"E
Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring.
Figure 16. VOSA054S4-1 and VOSA072S4-1 Typical Wiring Diagram
z Eepr om error
z Outdoor u ni t error
z Water level alarm
Defros t L ED flashing slowly or "E7" displaye d
AlarmLED flashing slowly or "Ed" displayed
Alarm LED flashingor
E"displayed"E
16
Page 17
VOSA054 and 072 Piping and Wiring Connections
VOSA054 and 072 units have two control boards in the control box and have two gas pipes, two liquid pipes, two branch pipes and two electronic expansion valves (EXV).
The additional boards and piping connections require special considerations when connecting the piping and communication wiring.
LED Display
Control box
Refrigerant piping
(two sets)
Condensate pipe
EXV B
EXV A
Control board B
Control board A
Terminal block
Inside of Control Box
Figure 28. VOSA054 and 072 Unit Identifi cation
17
Page 18
Communication (PQE) Wiring
NOTE - Control board A is the bottom control board and Control board B is the top control board in the electronic control box.
Control Board B - Top
Control Board A - Bottom
Terminal Block A
PQE
Terminal Block B
PQE
Figure 30. VOSA054 and 072 Terminal Block
Figure 29. VOSA054 and 072 Main Control Boards
18
Page 19
Connect the incoming PQE wiring to the terminal block for Control board A.
If this is the last indoor unit in the system, no additional PQE wiring is needed.
Add a resistor between P and Q on Control board B.
IDU Control Box
Main Control Board
Connecting V0STAT51
Connect the V0STAT51 cable to the cable attached to Control board A.
IDU Control Box
Main Control Board
B
B
Main Control Board
A
Terminal set A Terminal set B
X Y E P Q
Wiring in
Figure 31. VOSA054 and 072 Connect Communication
Wires to Single Indoor Unit
If there are additional indoor units, the outgoing wiring is connected to the terminal block for Control board B.
X Y E P Q
IDU Control Box
Main Control Board
CN10
A
Terminal set A Terminal set B
X Y E P Q
Plug in
V0STAT51 Controller
Figure 33. VOSA054 and 072 Connect to Single Indoor
To control more than one VHIA072 or 096 unit from the same controller,
1. Connect the V0STAT51-1P cable to Control board A.
2. Connect Control board B XYE to the next indoor unit to be controlled by the controller
IDU Control Box
X Y E P Q
Unit
Main Control Board
B
Main Control Board
A
Terminal set A Terminal set B
X Y E P Q
Wiring in Wiring out
Figure 32. VOSA054 and 072 Connect Communication
Wires to Additional Indoor Units
X Y E P Q
Main Control Board
B
Main Control Board
CN10
A
Terminal set A Terminal set B
X Y E P Q
Plug in
V0STAT51
Controller
Figure 34. VOSA054 and 072 Connect to Additional
Indoor Units
X Y E P Q
Wiring out
19
Page 20
Refrigerant Piping
Use the provided branch pipe kit to connect both sets of refrigerant line connections.
Locate branch pipes no more than 32 feet from indoor unit.
See piping report
for pipe sizes
Liquid branch pipe
(Provided with VOSA unit)
3/8”
Piping between branch pipe and indoor unit: liquid line = 3/8” and gas line = 5/8“.
Consult LVSS piping report diagram for all other piping sizes.
VOSA054/072
Liquid pipe Gas pipe
Gas branch pipe (Provided with VOSA unit)
32’ maximum distance
between branch pipes and indoor unit
Figure 35. Piping for VOSA054 and 072
Incoming liquid line connection
Incoming suction line connection
Connect these two pipes
5/8”
Connect these two pipes
Figure 37. VOSA054 and 072 Refrigerant Connections
Incoming suction line connection
Incoming liquid line connection
20
Loading...