Lennox VCFA012S4, VCFA015S4, VCFA024S4, VCFA030S4, VCFA018S4 Installation Instructions Manual

...
©2017 Lennox Industries Inc.
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a li­censed professional HVAC installer, service agency or the gas supplier. Failure to follow safety warnings and these instruc­tions exactly could result in property damage, dan­gerous operation, serious injury, or death. Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the ap­plication needs must be made by a licensed profes­sional HVAC installer (or equivalent) using factory­specifi ed parts. Do not use this system if any part has been under water. A fl ood-damaged appliance is extremely dan- gerous. Immediately call a licensed professional HVAC service technician (or equivalent) to inspect the system and to replace all controls and electrical parts that have been wet, or to replace the system, if deemed necessary. The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
Dallas, Texas, USA
!
WARNING
INSTALLATION INSTRUCTIONS
VCFA Convertible Ceiling / Floor-Mount Indoor Units
VRF SYSTEMS -- Ceiling/Floor Indoor Units 507444-05 03/2017
General
The VCFA ceiling/fl oor-mount non-ducted indoor units are matched with an outdoor heat recovery or heat pump unit to create a VRF (variable refrigerant fl ow) system that uses HFC-410A refrigerant. The units can be suspended from the ceiling in a horizontal position or installed on the wall near the fl oor in a vertical position. Refer to the Product Specifi cation bulletin (EHB) for the proper use of these indoor units with specifi c heat pumps, heat recovery units, mode switching devices, branch pipes, line sets and controls. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Shipping and Packing List
Check the components for shipping damage. If you fi nd any damage, immediately contact the last carrier.
Package 1 of 1 contains the following: 1 - Assembled indoor unit 4 - Nuts 4 - Washers
2 - Suspension brackets (ceiling mount) NOTE - not pro-
vided with VCFA054
2 - Mounting brackets (wall/fl oor mount) 1 - Resistor 1 - Brass fl are nut 1 - Condensate drain fl exible pipe 1 - Condensate drain insulation sleeve (VCFA054 only) 1 - Water level switch cable 1 - Installation manual
!
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
1
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Do not touch the unit or the controller if your hands are wet. DO NOT spray water on the indoor unit for any reason. Do not replace a fuse with a fuse of a different rating. Do not use a jumper wire to replace a fuse. Do not insert your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit. Do not allow children to operate the system.
Model Number Identifi cation
V CF A 012 S 4 - 1 P
Brand/Family
V = Variable Refrigerant Flow (VRF)
Unit Type
CF = Ceiling/Floor-Mount Non-Ducted Indoor Models
Major Design Sequence
A = 1st Generation
Nominal Cooling Capacity - Btuh
012 = 12,000 Btuh 015 = 15,000 Btuh 018 = 18,000 Btuh 024 = 24,000 Btuh 030 = 30,000 Btuh 036 = 36,000 Btuh 048 = 48,000 Btuh 054 = 54,000 Btuh
System Piping
CAUTION
VRF system piping is customized for each installation. The LVSS piping report is an engineered design that must be followed. The piping diagram or diagrams included within the LVSS report have been prepared based on the information provided to the Lennox VRF applications department.
When the indicated lengths change from the fi gures stated within the report, it is imperative that prior to the commencement of the refrigerant pipe work installation, Lennox VRF applications department are informed of these proposed changes.
Upon receipt of this new information the Lennox VRF applications department will confi rm any changes that may be applicable to this installation. If changes are required, a new piping diagram will be produced and will supersede all other previously provided documents.
Failure to provide this information regarding changes to the original design may lead to insuffi cient capacity, equipment failure, warranty being made void and the refusal to commission the system.
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Refrigerant Type
4 = R-410A
Cooling Effi ciency
S = Standard Effi ciency
2
Dimensions
VCFA012S4, VCFA015S4, VCFA018S4, VCFA024S4
MOUNTING
HOLES (4)
26
(660)
7-7/8 (200)
VCFA030S4
MOUNTING
HOLES (4)
7-1/8 (181)
5-1/4 (134)
3-7/8
(97)
LIQUID
PIPE
3-7/8
2-1/2
GAS PIPE
(98)
(64)
1-5/8 (41)
1-3/8 (35)
8-1/8 (207)
35-3/4 (908)
39 (991)
REAR VIEW
BOTTOM VIEW
DRAIN OUTLET
(Rear)
15-3/4 (401)14-5/8 (371)
DRAIN
OUTLET
(Either Side)
8-1/8 (206)
SIDE VIEW
26
(660)
7-7/8 (200)
7-1/8
5-1/4
(181)
(134)
1-1/2 (38)
3-7/8
(98)
2-1/2
3-7/8
(64)
(97)
LIQUID
PIPE
GAS PIPE
NOTE - Fresh Air intake not available on VHIA030 and smaller units.
1-5/8 (41)
8-1/8 (207)
47 (1195)
50-3/8 (1280)
REAR VIEW
BOTTOM VIEW
3
21-1/2 (547)20-1/4 (515)
DRAIN OUTLET
(Rear)
DRAIN
OUTLET
(Either Side)
8-1/8 (206)
SIDE VIEW
VCFA036S4, VCFA048S4
MOUNTING
HOLES (4)
26-3/4
(679)
10
12-7/8
(255)
(185)
DRAIN
OUTLET
(Either Side)
5-3/4 (146)
4-1/2 (116)
GAS PIPE
VCFA054S4
HANGING
BRACKETS (4)
26-3/4
(680)
4-1/2 (113)
LIQUID
PIPE
8-5/8 (220)
2-3/4 (70)
60-3/4 (1543)
65-3/4 (1670)
REAR VIEW
BOTTOM VIEW
42-1/8 (1070)
28-1/2 (725)24-7/8 (631)
FRESH AIR INTAKE
4 (105) dia.
9-5/8 (244)
SIDE VIEW
15
(381)
6-3/4 (172)
2-5/8 (67)
5
(127)
6-1/8
4-7/8
(157)
(124)
11-1/4
(285)
LIQUID
LINE
SUCTION
LINE
DRAIN OUTLET
65-1/2 (1613)
65-3/4 (1670)
REAR VIEW
BOTTOM VIEW
4
11-1/4
(285)
SIDE VIEW
FRESH AIR INTAKE
4 (105) dia.
Clearances
CEILING APPLICA TIONS
3/4” (19)
WALL
1”
(25.4)
SIDE VIEW
DROP CEILING
SUPPLY
AIR
CEILING AND FLOOR APPLICATIONS
WALL WALL
24
(610)
FRONT VIEW
24”
(610)
FLOOR APPLICA TIONS
Unit Flush with Wall
SUPPLY
AIR
1”
(25.4)
5
(Service Clearance
SIDE VIEW
24”
(610)
Front of Unit)
FLOOR