Lennox VCFA012S4, VCFA015S4, VCFA024S4, VCFA030S4, VCFA018S4 Installation Instructions Manual

...
©2017 Lennox Industries Inc.
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a li­censed professional HVAC installer, service agency or the gas supplier. Failure to follow safety warnings and these instruc­tions exactly could result in property damage, dan­gerous operation, serious injury, or death. Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the ap­plication needs must be made by a licensed profes­sional HVAC installer (or equivalent) using factory­specifi ed parts. Do not use this system if any part has been under water. A fl ood-damaged appliance is extremely dan- gerous. Immediately call a licensed professional HVAC service technician (or equivalent) to inspect the system and to replace all controls and electrical parts that have been wet, or to replace the system, if deemed necessary. The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
Dallas, Texas, USA
!
WARNING
INSTALLATION INSTRUCTIONS
VCFA Convertible Ceiling / Floor-Mount Indoor Units
VRF SYSTEMS -- Ceiling/Floor Indoor Units 507444-05 03/2017
General
The VCFA ceiling/fl oor-mount non-ducted indoor units are matched with an outdoor heat recovery or heat pump unit to create a VRF (variable refrigerant fl ow) system that uses HFC-410A refrigerant. The units can be suspended from the ceiling in a horizontal position or installed on the wall near the fl oor in a vertical position. Refer to the Product Specifi cation bulletin (EHB) for the proper use of these indoor units with specifi c heat pumps, heat recovery units, mode switching devices, branch pipes, line sets and controls. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Shipping and Packing List
Check the components for shipping damage. If you fi nd any damage, immediately contact the last carrier.
Package 1 of 1 contains the following: 1 - Assembled indoor unit 4 - Nuts 4 - Washers
2 - Suspension brackets (ceiling mount) NOTE - not pro-
vided with VCFA054
2 - Mounting brackets (wall/fl oor mount) 1 - Resistor 1 - Brass fl are nut 1 - Condensate drain fl exible pipe 1 - Condensate drain insulation sleeve (VCFA054 only) 1 - Water level switch cable 1 - Installation manual
!
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
1
Safety Requirements
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Do not touch the unit or the controller if your hands are wet. DO NOT spray water on the indoor unit for any reason. Do not replace a fuse with a fuse of a different rating. Do not use a jumper wire to replace a fuse. Do not insert your hands, tools or any other item into the air intake or air outlet at either the indoor or outdoor unit. Do not allow children to operate the system.
Model Number Identifi cation
V CF A 012 S 4 - 1 P
Brand/Family
V = Variable Refrigerant Flow (VRF)
Unit Type
CF = Ceiling/Floor-Mount Non-Ducted Indoor Models
Major Design Sequence
A = 1st Generation
Nominal Cooling Capacity - Btuh
012 = 12,000 Btuh 015 = 15,000 Btuh 018 = 18,000 Btuh 024 = 24,000 Btuh 030 = 30,000 Btuh 036 = 36,000 Btuh 048 = 48,000 Btuh 054 = 54,000 Btuh
System Piping
CAUTION
VRF system piping is customized for each installation. The LVSS piping report is an engineered design that must be followed. The piping diagram or diagrams included within the LVSS report have been prepared based on the information provided to the Lennox VRF applications department.
When the indicated lengths change from the fi gures stated within the report, it is imperative that prior to the commencement of the refrigerant pipe work installation, Lennox VRF applications department are informed of these proposed changes.
Upon receipt of this new information the Lennox VRF applications department will confi rm any changes that may be applicable to this installation. If changes are required, a new piping diagram will be produced and will supersede all other previously provided documents.
Failure to provide this information regarding changes to the original design may lead to insuffi cient capacity, equipment failure, warranty being made void and the refusal to commission the system.
Voltage
P = 208/230V-1 phase-60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Refrigerant Type
4 = R-410A
Cooling Effi ciency
S = Standard Effi ciency
2
Dimensions
VCFA012S4, VCFA015S4, VCFA018S4, VCFA024S4
MOUNTING
HOLES (4)
26
(660)
7-7/8 (200)
VCFA030S4
MOUNTING
HOLES (4)
7-1/8 (181)
5-1/4 (134)
3-7/8
(97)
LIQUID
PIPE
3-7/8
2-1/2
GAS PIPE
(98)
(64)
1-5/8 (41)
1-3/8 (35)
8-1/8 (207)
35-3/4 (908)
39 (991)
REAR VIEW
BOTTOM VIEW
DRAIN OUTLET
(Rear)
15-3/4 (401)14-5/8 (371)
DRAIN
OUTLET
(Either Side)
8-1/8 (206)
SIDE VIEW
26
(660)
7-7/8 (200)
7-1/8
5-1/4
(181)
(134)
1-1/2 (38)
3-7/8
(98)
2-1/2
3-7/8
(64)
(97)
LIQUID
PIPE
GAS PIPE
NOTE - Fresh Air intake not available on VHIA030 and smaller units.
1-5/8 (41)
8-1/8 (207)
47 (1195)
50-3/8 (1280)
REAR VIEW
BOTTOM VIEW
3
21-1/2 (547)20-1/4 (515)
DRAIN OUTLET
(Rear)
DRAIN
OUTLET
(Either Side)
8-1/8 (206)
SIDE VIEW
VCFA036S4, VCFA048S4
MOUNTING
HOLES (4)
26-3/4
(679)
10
12-7/8
(255)
(185)
DRAIN
OUTLET
(Either Side)
5-3/4 (146)
4-1/2 (116)
GAS PIPE
VCFA054S4
HANGING
BRACKETS (4)
26-3/4
(680)
4-1/2 (113)
LIQUID
PIPE
8-5/8 (220)
2-3/4 (70)
60-3/4 (1543)
65-3/4 (1670)
REAR VIEW
BOTTOM VIEW
42-1/8 (1070)
28-1/2 (725)24-7/8 (631)
FRESH AIR INTAKE
4 (105) dia.
9-5/8 (244)
SIDE VIEW
15
(381)
6-3/4 (172)
2-5/8 (67)
5
(127)
6-1/8
4-7/8
(157)
(124)
11-1/4
(285)
LIQUID
LINE
SUCTION
LINE
DRAIN OUTLET
65-1/2 (1613)
65-3/4 (1670)
REAR VIEW
BOTTOM VIEW
4
11-1/4
(285)
SIDE VIEW
FRESH AIR INTAKE
4 (105) dia.
Clearances
CEILING APPLICA TIONS
3/4” (19)
WALL
1”
(25.4)
SIDE VIEW
DROP CEILING
SUPPLY
AIR
CEILING AND FLOOR APPLICATIONS
WALL WALL
24
(610)
FRONT VIEW
24”
(610)
FLOOR APPLICA TIONS
Unit Flush with Wall
SUPPLY
AIR
1”
(25.4)
5
(Service Clearance
SIDE VIEW
24”
(610)
Front of Unit)
FLOOR
Unit Placement
In addition to clearances, the following items should be considered:
!
WARNING
Use the provided and specifi ed components when installing equipment. Failure to do so may result in unit falling, water leaking or electrical shocks, caus­ing personal injury or equipment or property dam age. Check stability of wall, fl oor, or ceiling and unit support. If sup port is not capable of carrying weight of the unit, unit may fall causing personal injury or equipment damage. Consider the possibility of earthquakes in your area when installing the equipment. If the unit is not correctly secured, it may fall, causing personal injury or equipment damage. Safely dispose of packing materials, which include nails, wood and other sharp objects, as well as plastic wrapping. Children playing with plastic wrap or bags risk the danger of suffocation.
!
CAUTION
Do not place items which may be damaged by water under or around the indoor unit. The unit should be installed at least 8 feet above the oor (if possible) to ensure maximum performance and comfort, when installed in the horizontal position only.
AVOID
Do not install the unit in the following locations:
• Areas exposed to petrochemicals or petrochemical products
Areas exposed to salt or other corrosive materials or caustic gasses
Areas exposed to extreme voltage variations (such as factories
Tightly enclosed areas that may impede service of the unit
• Areas exposed to fossil fuels (such as oil or gas in kitchens)
Areas exposed to strong electromagnetic forces
Areas exposed to acids or alkaline detergents (laundry rooms)
DO:
Locate the unit so that it is not exposed to direct sunlight
Locate the indoor unit so that the room can be uniformly cooled. Install unit as high as possible on the ceiling (8 feet above fl oor, if possible) for best performance (horizontal installation only).
Ensure the structural wall, fl oor, or ceiling can support the weight of the unit.
Select a location where condensate line will have the shortest run to a suitable drain per local codes.
• Allow suffi cient space around unit for proper operation and maintenance
Install unit a minimum of 3 feet away from any antenna, power cord (line) radio, telephone, security system, or intercom. Electrical interference and radio frequencies from any of these sources may affect operation
• Be sure to instruct customers how to properly operate the unit (especially maintenance of air fi lter, and operation procedure) by having them carry out operations themselves while looking at the manual provided with the controller.
Installation
Floor/Wall Applications
1. Locate a suitable position within the space where maintenance access and supply air will not be restricted or affected by obstacles. The minimum clearances are given on page 5.
Front View
Refrigerant/Drain pipe connections
Figure 1. Floor/Wall Applications
2. Locate the VCFA on a wall which is both capable of supporting the unit’s weight and which is constructed to enable the unit to fi t fl ush on the wall. An uneven wall may lead to vibration and subsequent unit damage.
3. Use suitable fasteners to secure the two mounting brackets to the wall. See fi gures 2 and 3, and the dimension drawings on pages 3, 4 and 5 to ensure proper positioning of the brackets.
Mounting
bracket
Fasteners
Figure 2. Mounting Brackets
6
A
CONCRETE CEILING
USING ANCHORS
Anchor
Threaded rod
B
Model A B
VCFA012-024 19-7/8” (505 mm) 19-7/8” (506 mm)
VCFA030 31-1/4” (795 mm) 19-7/8” (506 mm)
VCFA036-048 42-1/8” (1070 mm) 17-3/4” (450 mm)
VCFA054 42-1/8” (1070 mm) 15” (380 mm)
Figure 3. Mounting Bracket Positioning
4. The unit should be installed high enough for a gravity drain to function properly. If necessary, a fi eld provided external pump can be installed at the unit. See fi gure 1 for pipe connection locations.
5. Upon confi rming the two brackets are level, correctly spaced and secured to the wall; lift the unit onto the brackets. Confi rm the unit is level before continuing.
Ceiling Installation
1. Remove the side panel and the grille. See fi gure 4.
NOTE - Do not remove the grille on VCFA048 or 054 models.
*Do Not remove grille on VCFA048 or 054 units
Angle iron bolted in
place across wooden
joists
Threaded rod
ANGLE IRON
ACROSS
WOODEN JOISTS
Wooden joist
Figure 5. Locate Threaded Rods
4. Install suspension rods in the structural ceiling or concrete slab in a suitable location. If the structural ceiling is constructed of concrete, install anchors to accept four suitably sized threaded rods to suspend the indoor unit. If the structural ceiling includes wooden joists, use angle iron or Unistrut channel fi xed
securely in place to accept the threaded rods. NOTE -
Threaded rod (requirement of Lennox warranty program) is the ONLY acceptable method of suspending the unit; do not use chains or straps. See fi gure 5.
5. Slide one nut and one washer onto each threaded rod. Use electrical tape to keep the washer from falling off. Position the nuts slightly above the fi nal resting place of the suspension brackets.
Threaded rod
Field-provided isolation grommet
Washer
Suspension
bracket
Grille*
Figure 4. Remove Side Panel and Grille
2. Install four factory-provided mounting bolts by screwing them into the provided threaded holes in the unit body. See fi gure 7 for mounting bolt installation locations. The bolts should only extend from the body a distance which enables the bracket to engage the bolts and secure the unit.
3. Make sure that the structural ceiling is able to support the weight of the unit. It may be necessary to add support.
Side panel
Leveling nut
Figure 6. Locate Suspension Bracket on Threaded Rod
6. VCFA012-048 units: A x the two long suspension
brackets provided in accessory package to the previously installed threaded rods. See fi gure 6.
VCFA054 units: Afi x the four short suspension
brackets to the unit body. See fi gure 7. Install the VCFA054 unit directly onto the threaded rods as instructed in step 8 and then proceed to step 6. Step 9 will not apply to VCFA054 installation.
7. Slide a washer and then a nut onto each rod below each suspension bracket. Use the leveling nut (beneath suspension brackets) to adjust the bracket to the correct height. Remove the electrical tape holding the upper washers and nuts in place and tighten each of the four nuts above the brackets down onto the brackets. This will ensure that the unit remains level. See fi gure 6.
7
8. If necessary, install a fi eld-provided isolation grommet to prevent transmission of vibration from unit to structural ceiling.
9. Use either a mechanical lifting device or a minimum of two people to raise the unit.
10. Hang the unit on the suspension brackets by sliding the unit backwards on the bracket.
11. Securely tighten the mounting bolts on both sides. See gure 7.
Threaded rods
Suspension
bracket
(provided)
Mounting bolts
VCFA012-048
Suspension brackets (provided)
and
Mounting bolts
VCFA054
0.3”-0.5”
Refrigerant Piping Connections
!
WARNING
Refrigerant leaks are unlikely; however, if a refrigerant leak occurs, open a door or windows to dilute the refrigerant in the room. Turn off the unit and all other appliances that may cause a spark. Call a licensed professional HVAC technician (or equivalent) to repair the leak. Use only R410A refrigerant to charge this system. Use of other refrigerant or gas will damage the equipment. Do not allow air or other contaminants to enter system during installation of refrigerant piping. Contaminants will result in lower system capacity and abnormally high operating pressures and may result in system failure or explosion. Insulate all refrigerant piping. Refrigerant pipes may be very hot during unit operation. Do not allow contact between wiring and bare copper pipes. After refrigerant piping connections have been completed, check the system for leaks per commissioning instructions.
Field piping consists of two copper lines connected to the indoor unit. Table 1 lists the connection sizes at the indoor unit. The connections are made using the provided brass are nuts at the end of the refrigerant piping connections.
Both lines must be individually insulated.
1. The seal on the unit refrigerant piping connections should remain in place until the last possible moment. This will prevent dust or water from getting into the refrigerant piping before it is connected.
2. CAREFULLY adjust refrigerant piping connections to suit the application.
3. Slowly loosen one of the fl are nuts to release the factory nitrogen charge.
4. Remove the fl are nuts from the connections on the unit and discard the seal from each of the piping connections.
5. Slide the fl are nuts onto the ends of the fi eld-provided refrigerant piping before using a suitable fl aring tool to are the end of the copper pipe.
6. Apply recommended HFC-410A refrigerant lubricant to the outside of the fl ared refrigerant lines (fi gure 8-A).
Figure 7. Suspend Unit
Mounting bolt
(max. 1.6”)
8
IMPORTANT!
The compressor in this unit contains PVE oil (Polyvinylether). PVE oil is formulated for hydrofl uorocarbon (HFC) refrigerants, such as R- 410a, which this system contains. While it may have some miscibility properties with mineral-based oil and POE oil (Polyolester), it is not recommended to mix PVE oil with any other type of refrigerant oil.
7. Align the threaded connections with the fl ared refrigerant lines. Tighten the fl are nuts lightly at fi rst to obtain a smooth match (fi gure 8-B).
8. Once snug, continue another half-turn on each nut which should create a leak-free joint. A torque wrench may be used to tighten fl are nuts using table 2
recommendations. See fi gure 7. Do not over-tighten
a fl ared joint. Flared connections should always be accessible and must be insulated to prevent condensation.
IMPORTANT!
Always use two wrenches when tightening fl are nuts to avoid twisting refrigerant piping. DO NOT over-tighten fl are nuts.
TORQUE WRENCH
Table 1. Refrigerant Piping Connections
Size
Liquid Line Vapor Line
(Btuh)
VCFA012 & 015 1/4” 1/2”
VCFA018 - 054 3/8” 5/8”
A
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
B
Figure 8. Making Connections at Indoor Unit
(Male to Female Connection)
TO INDOOR
UNIT
TO OUTDOOR UNIT
BACKUP
WRENCH
Figure 9. Tighten Flare Nut
Table 2. Flare Nut Torque Recommendations
Outside
Diameter
Inches U.S.
1/4” 15 ft.-lb. 1/4 turn
3/8” 26 ft.-lb. 1/2 turn
1/2” 41 ft.-lb. 7/8 turn
5/8” 48 ft.-lb. 1 full turn
Recommended
Torque
No torque wrench
available
Finger tighten and
use an appropriately
sized wrench to turn an
additional:
9. After refrigerant piping has been installed and checked for leaks, apply insulation over all fl ared connections.
9
Condensate Piping Connections
!
CAUTION
Make sure that drain piping is properly routed and insulated in order to prevent both leaks and condensation.
1. Make a water-tight connection between the fi eld- provided condensate drain line and the fl exible condensate connector (5/8” I.D.).
2. Confi rm proper slope (not less than 1/4 inch per foot) and routing of condensate lines to ensure moisture is drained away from the indoor unit.
3. Drain should be as short as possible and should not have any droops or kinks that would restrict condensate ow and shall be approved resistant pipe. There must be a 2-inch space between the end of the condensate drain and the fi nal termination point (ground, open drain, etc.) to ensure that the line will drain freely.
4. After the system installation is complete, the condensate drain line must be checked for leaks and proper drainage. If a fi eld-provided condensate pump has been installed, it must be checked to ensure proper operation. This check is part of the commissioning sequence.
IMPORTANT!
Drain should have a slope of at least ¼ inch per foot and should be approved corrosion-resistant pipe. Y ou must confi rm operation of every drain and pump in the system as part of the commissioning proce­dure.
3 ft. (1 m)
VCFA
SUPPORT
STRAPS
Slope at least
1/4” per foot
Figure 10. Single Indoor Unit Suspended from Ceiling
Using a Properly Sloped Gravity Drain
DRAIN LINE
3 ft. (1 m)
VCFA VCFA VCFA
SUPPORT
STRAPS
INDIVIDUAL DRAIN OUTLET FROM EACH INDOOR UNIT
MAIN DRAIN
(Sloped at 1/4” per foot AWAY from unit and should
be supported as needed to prevent sagging.)
Figure 11. Condensate Drain Multiple Indoor Units Suspended from Ceiling Using a Single Properly Sloped
Gravity Drain
Using an External Water Level Switch
Disconnect the closed circuit loop, CN 5. Connect the water level switch cable accessory to CN 5. See unit wiring diagrams for location of CN 5.
The connection has 5 VDC current, do not supply fi eld voltage.
10
Wiring Connections
!
WARNING
Isolate the power supply before accessing unit electrical terminals. Install unit so that unit disconnect is accessible. Follow all local and national codes, as well as this installation instruction, during installation. Do NOT overload electrical circuit, as this may lead to failure and possible fi re. Use specifi ed wiring and cable to make electrical connections. Clamp cables securely and make sure that connections are tight to avoid strain on wiring. Insecure wiring connections may result in equipment failure and risk of fi re. Wiring must be installed so that all cover plates can be securely closed.
!
CAUTION
This unit must be properly grounded and protected by a circuit breaker. The ground wire for the unit must not be connected to a gas or water pipe, a lightning conductor or a telephone ground wire. Do not connect power wires to the outdoor unit until all other wiring and piping connections have been completed. Install all wiring at least 3 feet away from televisions, radios or other electronic devices in order to avoid the possibility of interference with the unit operation. Do not install the unit near a lighting appliance that includes a ballast. The ballast may affect remote control operation.
!
CAUTION
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fi xed wiring according to the National Wiring Regulation.
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
NOTE - Three-conductor shielded cable must be used for the communication wiring. This is necessary to ensure proper system communication and operation.
A circuit breaker capable of shutting down the power supply to the entire system must be installed.
A single switch can be used to supply power to units on the same system. However, branch switches and circuit breakers must be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as shown in the wiring diagram.
• Install a wiring interrupter or ground-fault circuit interrupter for the power wiring.
• Make sure the ground resistance is no greater than 100Ω. This value can be as high as 500Ω when using a grounding fault circuit interrupter since the protective ground resistance can be applied.
1. Pull the return air fi lter grille forward and remove the lters.
2. Remove one screw from each safety strap assembly (one on each side) and remove return air grille.
3. Locate the control box in the center of the unit, below and behind the fan motor.
4. Remove the two screws holding the control box onto the motor mounting bracket, and the screw at each end of the control box holding securing the box to the chassis of the unit. Lower the control box to obtain access to cover.
5. Remove the screws securing the cover and remove cover from control box.
6. Locate the terminal strip in the control box. Connect the power wiring (sized per NEC/CEC and local codes) and communications cable (three-conductor shielded cable) per fi gures 12 and 13. Refer to unit nameplate for rated voltage.
7. If the indoor unit is the fi nal unit in a group that is wired in series, install the provided resistor across terminals P and Q. See fi gure 14.
Tightening torque for the terminal screws
• Use the correct screwdriver for fi ghting the terminal screws. If the screwdriver blade is too small, the head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are over tightened, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Table 3. Terminal Screw Tightening Torque
Tightening torque (lb-ft)
Terminal base of
0.58-0.72 remote controller/Signal transmission wire (X2M)
Terminal base of power
0.87-1.06 supply (X1M)
Grounding terminal (M4) 1.06-1.43
• After wiring, confi rm all connections are correct; Then turn on power supply to the unit.
11
Indoor units and MS boxes on the same refrigeration circuit should have a common power supply but must have an independent disconnect switch installed adjacent
to the fan coil for servicing and maintenance purposes. Indoor unit and MS box power supply MUST not be taken from the outdoor unit. Always follow NEC/CEC and Local Codes.
Power DistribuƟon Box
L1/L2
L1/L2
Box
L1/L2
MS
L1/L2/L3
PQE
PQE
PQE
PQE
PQE
PQE
L1/L2/L3
L1/L2/L3
L1/L2
L1/L2
PQE
L1/L2
L1/L2
L1/L2
L1/L2
PQE
MS
PQE
L1/L2
Box
L1/L2
PQE
L1/L2
PQE
Legend
PQE CommunicaƟon wiring
L1/L2 Single-Phase power wiring
L1/L2/L3 Three-Phase power wiring
Electrical disconnect switch
Figure 12. Typical Power Wiring Diagram (VRF Heat Recovery System Shown)
12
NOTE - Each communication wire from the MS box should follow the refrigerant piping for that port.
Figure 13. Typical Communication Wiring Diagram (VRF Heat Recovery System)
13
KEY
FM1,FM2
EEV
T2B
XP1-5 XS1-5
CAP1 CAP2
XT1-2
GMA,GMB
127(
COMPONENT
EXPANSION VALVE
T1
INLETAIR TEMP.
EVAPOUTLETTEMP
IN COOLING MODE
T2
FAN CAPACITOR
TR CS
LEVEL SWITCH
TERMINAL BLOCK
GM
LEVEL SWING MOTOR
SWING MOTOR
INDOOR FAN
ELECTRONIC
COILTEMP.
PLUG JACK
TRANSFORMER
WATER
VERTICAL
&20321(17 ,1 '$6+ /,1( ,6 237,21$/ 25 ),(/' :,5,1*
&1
75
&1
5('
%/8(
••
••
;7
&1
<(//2:*5((1
GROUND
POWER IN
208/230V-1 PHASE-60-hz
&1
:+,7(
&1
6:
)$1
2121
6:
CAP1
:+,7(
&21752/ %2$5'
&1
*0
&1
*0$
<(//2:*5((1<(//2:*5 ((1 <(//2:*5 ((1
GROUND
21
6:
&1
:+,7(
&1
:+,7(
*0%
)$1&$3
- 21
6:
GROUND
&1 <(//2:
32:(5B6
(1&
&1
((9
&1
&1
&1
&1
&1
;3
;6
&21752/ ,17(5)$&( 02'8/(
;3
;6
%/$&.
;3
;6
:+,7(
;6
;3
:((./< 7,0(5 :,5(' &21752//(5
;7
&211(&7 72 :,5(' &21752 //(5
127(  5()(5 72 0$18$/ )25
•• •
&20081,&$7,21 :,5,1 *
 3/($ 6( 86( 7+(
&21'8&725 6+,(/'(' &$%/(
:,5(' &21752//( 5
•••••••
&211(&7 72 287'225 81,7
(9$3 287/(7 7(03
CS
LEVEL SWING MOTOR
GM
COMPONENT
INDOO RFA N
ELECTRONIC
EXPANSIONVAL VE
INLETAIRTEMP.
IN COOLING MODE
COILTEMP.
PLUG
JACK FAN CAPACITOR TRANSFORMER
WATER
LEVELSWITCH
TERMINAL BLOCK
VERTICAL
SWING MOTOR
KEY
)0)0
EEV
T1
T2B
T2 XP1-11 XS1-11
CAP1 CAP2
TR
XT1-2
GMA,GMB
127( &20321(17 ,1 '$6+ /,1( ,6 237,21$/ 25 ),(/' :,5,1*
208/230V-1 PHASE-60-hz
75
L2
L1
;7
POWER IN
Figure 14. VCFA012-48S4-1 Wiring Diagram
21
6:
&1
21
6:
*0$
5('
%/8(
<*
GROUND
)0$
&1
21
6:
0$,1 &21752/ %2$5'
&1
)0%
&1
&1
<*
*0
GROUND
&1
<*
GROUND
&1
&1
&1: +,7(
*0%
-
&1
((9
&1<(/ /2:
21
6:
&1
:+,7(
7
;6;3
32:(5B6
(1&
%/$&.
7
',63/$< 3$1(/
&1
&1
&1
&1
127(  5()(5 72 0$18$/ )25
7%
:,5(' &21752// (5
&21752/ ,17(5)$&( 02'8/(
;6;3
;6 ;3
;7
XY
&211(&7 72 :,5(' &21752//(5
&20081,&$7,21 :,5,1*
 3/($6( 86( 7+(
&21' 8&725 6+,(/' (' &$%/(
:((./< 7,0(5 :,5(' &21752//(5
(E)
PQ
&211(&7 72 287'225 81,7
:,5(' &21752//( 5
(E)
Figure 15. VCFA054S4-1 Wiring Diagram
14
KEY
FM1,FM2
EEV
T1
T2B
T2 XP1-5 XS1-5
CAP1 CAP2
TR
CS
XT1-2
GM
GMA,GMB
COMPONENT
INDOOR FAN ELECTRONIC
EXPANSIONVALVE
INLETAIR TEMP.
EVAPOUTLET TEMP
IN COOLING MODE
COIL TEMP.
PLUG JACK
FAN CAPACITOR
TRANSFORMER
WATER
LEVEL SWITCH
TERMINAL BLOCK
LEVEL SWING MOTOR
VERTICAL
SWING MOTOR
CN30
GND
CAP1
GROUND
GROUND
KEY
EEV
T1
T2B
T2 XP1-11 XS1-11
CAP1 CAP2
TR
CS
XT1-2
GM
GMA,GMB
COMPONENT
INDOOR FAN ELECTRONIC
EXPANSIONVALVE
INLETAIR TEMP.
IN COOLING MODE
COIL TEMP.
PLUG
JACK
FAN CAPACITOR
TRANSFORMER
WATER
LEVEL SWITCH
TERMINAL BLOCK
LEVEL SWING MOTOR
VERTICAL
SWING MOTOR
GROUND
AUXH
FAN CTON H TON
HHEinterface
Currentrange (0~1A)
Voltagerange (0~AC/DC24V)
Figure 16. VCFA012-48S4-2 Wiring Diagram
CN30 GND
HHE interface
AUXH
FAN CTON HTO N
Current range (0~1A)
Voltagerange (0~AC/DC24V)
L2
L1
GROUND
GROUND
GROUND
Figure 17. VCFA054S4-2 Wiring Diagram
15
Outside Air Connection
A limited amount of outside air can be brought into the VCFA036, 048 and 054 units (through the 4 inch (105 mm)) fresh air intake to be conditioned and mixed into the supply air.
NOTE - Fresh air must be fi ltered as the connection is after the VCFA fi lters. Failure to follow this step will deteriorate the indoor unit coil and cause condensate issues.
Outside Air Knockout
Duct Screw Holes (4)
Figure 18. Typical Outside Air Knockout
1. Knock out the outside air supply opening. See fi gure
18.
2. Remove any insulation.
3. Connect the outside air duct to cassette body using the four screw holes shown in fi gure 18.
4. Relocate the indoor unit’s return air sensor to either the controller (electronically) or physically by using the remote sensor accessory.
5. The outside air supply duct length must be 10 feet or less.
6. Flexible duct connection must be used to avoid vibration noise being transmitted into the building.
7. Use a fi eld-supplied booster fan to increase static pressure.
16
Loading...