Lennox V0STAT54P-2 Installation And Operation Instructions Manual

1
©2017 Lennox Industries Inc.
Dallas, Texas, USA
INSTALLATION/ OPERATION INSTRUCTIONS
CONTROLS 507596-04 04/2017
THIS MANUAL MUST BE LEFT WITH THE OWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency.
Frequent changes to operating mode may cause system malfunction. Allow at least one minute between mode changes to allow the system to stabilize.
IMPORTANT!
!
V0STAT54P-2 Indoor Unit Non-programmable Controller
Electrostatic discharge can affect elec­tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.
IMPORTANT!
2
Shipping and Packing List
Package 1 of 1 contains;
1 – Wired Controller 1 – Installation and operation manual 2 – Plastic spacers
General
The V0STAT54P-2 is a wired non-program­mable local controller that controls up to 16 VRF indoor units. These instructions are intended as a general guide and do not su­persede local codes in any way. Consult au­thorities having jurisdiction before installation.
Requirements
• Four-conductor cable is required for in­stallation.
• Be sure that power supply has been turned off before beginning installation.
This controller should be used only as de­scribed in this manual.
• Do not install the controller on outside walls (where there is unconditioned space on opposite side of wall) or in locations where direct sunlight may be present.
Installation
Clean controller using a clean, damp cloth. Do not spray cleanser on or around controller.
Do not install controller in areas where harmful gases containing sulfur or other damaging agents may exist or the controller may be damaged.
CAUTION
!
CAUTION
!
Power wiring between controller and fi rst indoor unit:
Minimum 18 AWG stranded shielded cable up to 164 feet (50 m).
Ensure there are no gaps between the controller back cover and the mounting surface.
Fill any holes in the wall behind the controller to avoid false readings from infi ltration.
Ground the shielded control wiring.
Do not use a megger to test insulation.
Communication wiring between indoor units:
Minimum 18 AWG stranded shielded cable.
3
Do not operate controller with wet hands.
CAUTION
!
Read all of the information in this manual before using this controller. All wiring must conform to local and national building and electrical codes and ordinances. This is
a 12 VDC controller. Do not install on voltages higher than 12 VDC.
This manual provides the installation instructions for this controller. Refer to the included wiring diagrams to connect the controller to the indoor unit.
• The controller uses low voltage. Keep a minimum distance of 12” (305 mm) be­tween low voltage control wire and high voltage power wires.
IMPORTANT!
Figure 1. Remove Controller from Back Cover
1. Remove the controller from the back cover using a at head screw driver as shown. See gure 1.
4
Figure 2. Installation
4. At the controller, wire the fi eld-provided 4-conductor shielded cable to X / Y / GND / 12V terminal of the controller. See fi gure 3.
2. Adjust the length of the two plastic spacers as needed to allow the controller to be mounted
ush with the wall. NOTE – Be sure to provide for future maintenance by allowing enough slack in the wiring to allow the controller to be removed from the wall if needed. See gure 2.
3. Attach the back cover using fi eld-provided screws.
Figure 3. Connection at Controller
4-conductor wiring
X 12VY GND
5
Figure 4. Wire to One Indoor Unit
5. Reattach the controller to the back cover.
6. Connect the controller to one or more indoor units, up to 16. Use 4-conductor shielded cable to connect to the fi rst indoor unit. NOTE - Wiring is polarity sensitive. See fi gure 4.
COM 12VX Y
12V X Y E
NOTE - Connect up to 16 indoor units NOTE - Ground cable shielding at indoor unit
6
Specifi cations
Input voltage 12 VDC Ambient temperature 23~110°F (-5~43°C) Ambient humidity RH40%~RH90%
Table 1. Specifi cations
Figure 5. Wire Multiple Indoor Units
COM 12VX Y
12V X Y E 12V X Y E 12V X Y E
NOTE - Connect up to 16 indoor units NOTE - Ground cable shielding at one end of each length of cable
7. Daisy chain 3-conductor control wiring to each additional indoor unit using the X Y E termi­nals in the electrical control box of the indoor unit. Do not daisy chain 12V power cable. See gure 5. NOTE - Wiring is polarity sensitive.
7
Description of Buttons
Power Button
Fan Speed Button
Up-Arrow
Button
Mode
Button
Cooling
Mode
Heating
Mode
Auto
Mode
Dry
Mode
Fan
Mode
Locked
Function
Centralized
Controller
Locked
Cooling
Setpoint
Heating
Setpoint
Down-Arrow
Button
Room
Temperature
Swing
Fan Speed
8
Operation
After powering on the controller, wait 30 sec­onds for initialization The indoor unit cannot be controlled by the controller until initializa­tion is complete.
Start/Stop Operation
Press the power button.
Controller ON: LED display lit.
Controller OFF: LED display not lit.
Set Operation Mode
Press the Mode button to scroll through the mode selections.
Cool – System operates in cooling mode.
Heat – System operates in heating mode.
Auto -- System operates in auto mode.
• Dry -- System operates in dehumidifi ca- tion mode. NOTE - fan speed cannot be
adjusted during dry mode.
Fan – Fan only, no heating or cooling.
To set (or change) the room temperature setting (setpoint)
Press the up-arrow & down-arrow buttons to adjust the setpoint.
When in Auto mode, separate heating and cooling setpoints can be set. Press the Mode button to switch between heating and cooling setpoints.
NOTE - Indoor units connected to a local con­troller may also be controlled by a centralized controller. Indoor units respond to the last command sent. It is recommended that in­door units be controlled from a single source of control, either local controller or central­ized controller but not both, to avoid confl icts in commands.
9
MODEFAN SPEED
FAN SPEED
COOL
HEAT
ROOM TEMP.
Figure 6. Function Lock Indicator
Function Lock
Indicator
Louver Swing Operation
Press both the up-arrow button and the down­arrow button simultaneously to start louver auto swing operation. The louvers will move automatically until stopped.
Press both the up-arrow button and the down-arrow button simultaneously again to stop the swing operation. The louvers will remain in position where stopped. Do not move louvers manually; only move louvers using the auto swing function.
NOTE - Not available on all indoor unit types.
Lock Operation
Some operational functions can be locked. See table 2
10
Lock Type Operation
Simultaneously press the buttons shown below
User Experience
Lock operation mode
The Mode button is inactive. User cannot change operation mode using this controller.
Lock fan speed
The fan speed button is inac­tive. User cannot change fan speed using this controller.
Lock temperature increase
The Up-arrow button is inactive. User cannot raise setpoint us­ing this controller.
Lock temperature decrease
The Down-arrow button is inac­tive. User cannot lower setpoint using this controller.
Lock ON/OFF status
The Power button is inactive User cannot turn the indoor unit on or off using this controller.
Lock all buttons
All buttons are inactive. User cannot make any changes to the indoor unit using this controller.
Unlock all buttons
All buttons are active. User can make any changes to the indoor unit using this controller.
Table 2. Lock Operation Functions
11
Controller Settings
Press and hold the Fan speed button and the Mode button for 5 seconds to access the controller settings.
Use Table 3 to setup the controller.
When in Settings mode:
• Press the Fan speed button to accept
the current setting parameters and pro­ceed to the next setting.
• Press the Up-arrow and Down-arrow
buttons to adjust parameters.
Press the Power button to restart control­ler.
Centralized Controller Locks Controller
If a function of the indoor unit is locked by a centralized controller (e.g. mode, tempera­ture setpoint, swing, etc.), the V0STAT54P-2 controller will not be able to adjust that locked function. The function must be unlocked at the cen­tralized controller before the local controller can operate it.
MODEFAN SPEED
Figure 7. Controller Settings
Settings
Code
Settings Number
(see table 3)
Settings
Parameter
12
Table 3. Controller Settings
Code Function Set-
tings No.
Value Note
EE
Power off – Memory settings for Auto Mode
NOTE – When Auto mode is being used, setpoint, fan speed, and operation mode (cooling or heating) is memorized by the indoor unit.
10 on (default)
When Auto mode is being used, the controller will memorize the user setting of Auto mode before powering off. When power is restored, the controller mode will be set to Auto mode.
11 off
When Auto mode is being used, the controller will not memorize the user setting of Auto mode before powering off. When power is restored, the controller mode will be set to the operation mode of indoor unit (cooling or heating).
CF
Temperature unit
20 °C The controller will use °C 21 °F (default) The controller will use °F
Gr Not used 40 Not used Not used
Fr
Room temperature sensor location
50 0 Use indoor unit sensor
51 1 (default)
Use controller sensor
NOTE - Required setting if multiple indoor units are con­nected to the controller.
13
Code Function Set-
tings No.
Value Note
t1
Room temper­ature sensor calibration
60
Fahrenheit:-4°F/
-3°F/ -2°F/ -1°F/ 0°F (Default)/ 1°F/ 2°F/ 3°F/ 4°F Celsius: -2°C/ -1°C/ 0°C (Default)/ 1°C/ 2°C
Adjust the calibration of the room temperature senor. Value selected will be added to the temperature sensor value.
Au
Auto mode en­able/disable
70 on (default)
Auto mode enable (heat recovery systems only)
71 off
Auto mode disable (heat pump systems)
Th
Setpoint upper limitation for heating mode
80
Fahrenheit: 86°F~62°F (86°F default) Celsius: 30°C~17°C (30°C default)
When the system is in heat­ing mode, users can not set the temperature higher than the set value.
Tl
Setpoint lower limitation for cooling mode
90
Fahrenheit: 62°F~86°F (62°F default) Celsius: 17°C~30°C (17°C default)
In cooling mode, users can­not set the temperature lower than the set value.
FC
Set indoor unit fan ON/OFF when cooling requirement is satisfi ed.
A0 on (default)
Keeps the indoor fan on when cooling setpoint is satisfi ed.
A1 off
Turns the indoor fan off when cooling setpoint is satisfi ed.
14
Code Function Set-
tings No.
Value Note
FH
Set indoor unit fan ON/OFF when heating requirement is satisfi ed.
b0 on (default)
Keeps the indoor fan on when heating setpoint is satisfi ed.
b1 --
Turns the indoor fan off when heating setpoint is satisfi ed.
NOTE - FH code only. Simultaneously press the Fan Speed, Down-Arrow, Up-Arrow and Mode buttons to toggle between “on” and “--”.
dr
HHE Relay Kit - Enable or Disable Alternative Heat (note: see setting L0, code d5 for Alternate Heat settings)
C0 on
Enable Alternative Heat using the HHE Relay Kit.
C1 off (default)
Disable Alternative Heat us­ing the HHE Relay Kit.
d1
HHE Relay Kit
- Auxiliary Heat Settings
d3 3°F/2°C (default)
When using the HHE relay kit, auxiliary heat will be activated when room temperature is 3°F/2°C lower than setpoint in heating mode.
d5 5°F/3°C
When using the HHE relay kit, auxiliary heat will be activated when room temperature is 5°F/3°C lower than setpoint in heating mode.
15
Code Function Set-
tings No.
Value Note
d5
HHE Relay Kit ­Alternative Heat Settings (note: see setting CX, code dr for to set Alternative heat to Enable/Disable). When alternative heat is enabled and outdoor am­bient temperature is lower than the setting, The alternate heat source is the only heat source for heating, the VRF system will stop supplying heat until ambient temperature is higher than the setting.
L0
0 7°F/-14°C 1 (default) 10°F/-12°C 2 15°F/-9°C 3 20°F/-7°C 4 25°F/-4°C 5 30°F/-1°C 6 35°F/-2°C 7 40°F/4°C 8 45°F/7°C 9 50°F/10°C 10 55°F/13°C 11 60°F/16°C 12 65°F/18°C 13 70°F/21°C 14 72°F/22°C
16
Indoor Unit Status Query
• Press and hold the Mode button for 5 sec­onds to access the indoor unit status query.
• Use the up-arrow and down-arrow buttons to scroll through the indoor unit statuses
• Indoor unit operation status (Figure 8)
• Indoor unit evaporator coil temperature (T2 and T2b) (Figure 9)
• Room temperature sensor location (wired controller or indoor unit) (Figure 10)
• On/Off status of dry contact one (Fan) (Figure 11)
• On/Off status of dry contact two (CTON) (Figure 12)
• On/Off status of dry contact three (HTON) (Figure 13)
• On/Off status of dry contact four (AUXH) (Figure 14)
FAN SPEED
COOL
SWING
Figure 8. Indoor Unit Operation Status
Setpoint
Operation Mode
Fan Speed
Indoor Unit Address
Figure 9. Indoor Unit Coil Temperature
T2b
T2
Indoor Unit Address
Louver Auto­Swing
17
Figure 10. Room Temp Sensor Location
Room Temp Sensor Location 0 = Indoor Unit 1 = Controller
Indoor Unit Address
Figure 11. On/Off Status of HHE Relay - Fan
Figure 12. On/Off Status of HHE Relay - CTON
Figure 13. On/Off Status of HHE Relay - HTON
Not used
HHE Relay Four-Dry Contact - Fan
Dry Contact Status on = Dry contact closed
-- = Dry contact open
HHE Relay Four-Dry Contact - CTON
Dry Contact Status on = Dry contact closed
-- = Dry contact open
HHE Relay Four-Dry Contact - HTON
Dry Contact Status on = Dry contact closed
-- = Dry contact open
18
Figure 14. On/Off Status of HHE Relay Kit - AUXH
Figure 15. Switch to Next Indoor Unit
MODEFAN SPEED
FAN SPEED
COOL
Connected to Multiple Indoor Units
Press the Fan speed button to switch to ad­ditional indoor units. The controller will display operation mode, fan speed, temperature set­ting, swing status and address of indoor unit.
HHE Relay Kit Four-Dry Contact - AUXH
Dry Contact Status on = Dry contact closed
-- = Dry contact open
19
Fault Code Query
Figure 16. Enter Fault Code Query
MODEFAN SPEED
Figure 17. View Past 10 Fault Codes
MODEFAN SPEED
Figure 18. Switch Between Fault Codes
MODEFAN SPEED
• Press and hold the Mode button for 5 seconds to access the indoor unit status query.
Press the Mode button to access the fault code query. The last 10 fault codes are stored.
• Press the Fan Speed button to scroll through the fault codes.
When multiple fault codes have occurred at the same time, use the up-arrow and down-arrow buttons to see each code.
20
Error Codes
The V0STAT54P-2 controller displays the last 10 error codes. To view error codes, see the instructions on the previous page.
If the error code is for an indoor unit, the unit address also displays.
Figure 19. Error Code Display
MODEFAN SPEED
Error Code
Indoor Unit Address
Table 4. Indoor Unit Error Codes
Error Code
Description
F0
Communication error between the indoor unit and the wired controller (may affect other indoor units in the system)
F1
Communication error between the indoor unit and the controller
F2 Controller EEPROM error
E1
Communication error between the indoor unit and the outdoor
unit E2 T1 temperature sensor error E3 T2A temperature sensor error E4 T2B temperature sensor error E5 Outdoor unit error E6 Fan motor error E7 Indoor unit EEPROM error E8 Indoor unit DC motor error
EE Condensate pump error
Loading...