Lennox TSA036S4, TSA042S4, TSA048S4, TSA060S4 User Manual

E N G I N E E R I N G D A T A
A I R C O N D I T I O N E R S
TS
T−CLASSt SPLIT SYSTEM UNITS
Standard Efficiency − R−410A − 60 HZ
Bulletin No. 210461
March 2008
Supersedes July 2007

MODEL NUMBER IDENTIFICATION

TSA Y1036 S 44 n
T = T−Classt Product Line
S = Split−System Air Conditioner
Brand/Family
Unit Type
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity − Tons
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
S = Standard Efficiency
3 to 5 Tons
Cooling Capacity − 33,400 to 62,500 Btuh
Vol ta ge
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V−3 phase−60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Coil Type
4 = Four−sided
Part Load Capability
N = No part load, single stage compressor
Refrigerant Type
4 = R−410A

FEATURES

CONTENTS
ARI Rating Tables Pages 10−18. . . . . . . . . . . . . . . . . . . . . .
Dimensions Page 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features Pages 2−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Guide Specifications Pages 19 − 23. . . . . . . . . . . . . . . . . . .
Indoor Coil / Air Handler Substitution Page 9. . . . . . . . . . .
Installation Clearances Page 7. . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification Page 1. . . . . . . . . . . . . . . . . .
Outdoor Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warranty
Compressor − limited warranty for five years. All other covered components − one year.
Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.
Approvals
Certified in Accordance with the USE certification program, which is based on ARI Standard 210/240−2005. Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in ARI Standard 270-95. Tested in the Lennox Research Laboratory environmental test room. Rated According to U.S. Department of Energy (DOE) test procedures. Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC. Units are UL listed and CSA certified. ISO 9001 Registered Manufacturing Quality System. E
NERGY STAR® certified units are designed to use less
energy, help save money on utility bills, and help protect the environment.
Applications
SEER up to 14.0. 3 through 5 ton. Three−phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Matching add-on furnace indoor coils or air handlers provide a wide range of cooling capacities and applications. See ARI Ratings table. See Indoor Coils and Air Handlers tab sections for unit data. Units shipped completely factory assembled, piped and wired. Each unit test operated at the factory ensuring proper operation. Installer must set air conditioner, connect refrigerant lines and make electrical connections to complete job.
For expanded ratings, see www.lennoxcommercial.com.
B
C
D
REFRIGERANT SYSTEM
Refrigerant
Non−chlorine, ozone friendly, R−410A. Unit pre−charged with refrigerant. See Specification table.
Condenser Fan
B
Direct drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity. Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. Fan motor has sleeve bearings and is inherently protected. Motor totally enclosed for maximum protection from weather, dust and corrosion. Rain shield on motor provides additional protection from moisture. Louvered steel top fan guard furnished as standard. Fan service access accomplished by removal of top panel.
E
F
TS − 3 to 5 Ton R−410A Air Conditioners / Page 2
FEATURES
REFRIGERANT SYSTEM − CONTINUED
Copper Tube/Enhanced Fin Coil
C
Lennox designed and fabricated coil. Ripple-edged aluminum fins. Copper tube construction. Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer. Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction. Coil is factory tested under high pressure to ensure leakproof construction. Entire coil is accessible for cleaning. PVC coated steel wire coil guard furnished as standard.
High Pressure Switch Kit
Protects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil. Manual reset.
OPTIONS
Expansion Valve Kits
Must be ordered extra and field installed on certain indoor units. See ARI Ratings tables. Chatleff−style fittings.
Loss of Charge Kit
Helps protect the compressor from damage due to low refrigerant charge conditions. SPST, normally−closed switch, automatic reset switch mounted on suction line.
Refrigerant Line Kits
Refrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory. Suction line fully insulated. Lines are stubbed at both ends. Not available for −060 models and must be field fabricated.
Compressor
Copeland Scrollt Compressor
D
Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. Compressor is installed in the unit on resilient rubber mounts for vibration free operation.
Compressor Crankcase Heater
Protects against refrigerant migration that can occur during low ambient operation.
OPTIONS
Compressor Low Ambient Cut−Off
Non-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.
Compressor Sound Cover
A reinforced vinyl compressor cover containing a 1−1/2 inch thick batt of fiberglass insulation. All open edges are sealed with a one−inch wide hook and loop fastening tape.
Compressor Timed−Off Control
Kit prevents compressor short−cycling and allows time for suction and discharge pressure to equalize. Permits compressor start−up in an unloaded condition. Automatic reset with 5 minute delay between compressor shut−off and start−up.
TS − 3 to 5 Ton R−410A Air Conditioners / Page 3
FEATURES
Cabinet
E
Heavy gauge steel cabinet with five station metal wash process. Powder paint finish provides superior rust and corrosion protection. Painted base section. Control box is conveniently located with all controls factory wired. Corner patch plate allows access to compressor components. Drainage holes are provided in base section for moisture removal.
Refrigerant Line Connections, Electrical Inlets,
F
Service Valves
Sweat connection suction and liquid lines are located on corner of unit cabinet. Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.
OPTIONS
Hail Guards
Constructed of louvered heavy gauge steel painted to match cabinet. Surrounds unit on all four sides to prevent damage to the coil.
Mounting Base
Provides permanent foundation for outdoor units. High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot. Can be shipped singly or in packages of 6 to a carton.
Unit Stand-Off Kit
Black high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture. Four feet are furnished per order number.
CONTROLS
OPTIONS
L Connection® Network
See L Connection Engineering Handbook Bulletin in Controls section for details.
Low Ambient Control
Air conditioners operate satisfactorily down to 45°F outdoor air temperature without any additional controls. The Low Ambient Control Kit allows unit operation down to 30°F. Freezestat should be installed on compressors equipped with a low ambient kit. A compressor lock−out thermostat should be added to terminate compressor operation below recommended operation conditions.
Freezestat
Installs on or near the vapor line of the indoor coil or on the suction line. Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint. Opens at 29°F and closes at 58°F.
Time Delay Relay Kit
Delays the indoor blower−off time during the cooling cycle. See ARI Rating Tables for usage.
TS − 3 to 5 Ton R−410A Air Conditioners / Page 4
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Compliant − E
NERGY STAR
Sensors For Touchscreen Thermostat
1
Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1
Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . . . . . . . . . . . . C0SNZN73AE1−
1
Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR03AE1−
Accessories For Touchscreen Thermostat
Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−
1
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4) C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.
DIGITAL NON−PROGRAMMABLE THERMOSTATS
Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control
Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L
Sensor For Digital Non−Programmable Thermostats Above
Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−
Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down Temperature Control
One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L
Sensor For Digital Non−Programmable Thermostats Above
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR04AE1−
Accessories For Digital Non−Programmable Thermostats Above
Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC17AE1−
®
Qualified − Backlit Display − Automatic Changeover
C0STAT02AE1L
TS − 3 to 5 Ton R−410A Air Conditioners / Page 5

SPECIFICATIONS

General Data
Connections (sweat)
1
Refrigerant (R-410A) furnished 5 lbs. 9 oz. 8 lbs. 3 oz. 8 lbs. 4 oz. 10 lbs. 0 oz.
Outdoor Coil area - sq. ft.
Outdoor Fan
Shipping Data − lbs. 1 package 135 177 200 222

ELECTRICAL DATA

Line voltage data − 60 hz − 3ph 208/230V 460V 208/230V 460V 208/230V 460V 575V 208/230V 460V 575V
2
Maximum overcurrent protection (amps) 20 15 30 15 30 15 15 35 15 15
Compressor
Outdoor Fan Motor
OPTIONAL ACcESSORIES − must be ordered extra
Compressor Low Ambient Cut−Off 45F08 S S S S
Compressor Sound Cover 69J03 S S S S
Compressor Time−Off Control 47J27 S S S S
Freezestat
Hail Guards
Loss of Charge Kit 84M23 S S S S
4
Low Ambient Kit (down to 30°F) 34M72 S S S S
Mounting Base
Refrigerant Line Sets
Time Delay Relay Kit 58M81 S S S S
Unit Stand−Off Kit 94J45 S S S S
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Freezestat is recommended with Low Ambient Kit.
Model No. TSA036S4 TSA042S4 TSA048S4 TSA060S4
Nominal Tonnage 3
3.5 4 5
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
Suction line o.d. − in. 7/8
Net face
Outer coil
Inner coil
13.22 15.11 16.32 21.00
− − −
7/8 7/8 1-1/8
14.40 15.71 20.25
Tube diameter − in. 5/16 5/16 5/16 5/16
Fins per inch − No. of rows 26 − 1 22 − 2 22 − 2 22 − 2
Diam. − in. − No. of blades 18 − 4 18 − 4 22 − 4 22 − 4
Motor hp 208/230V − 1/5
1/3 1/4 1/4
460V − 1/6
Cfm 2400 2930 3500 3830
Rpm 1090 1100 825 825
Watts 185 310 320 330
3
Minimum circuit ampacity 14.2 7.8 18.6 8.4 18.8 8.8 7.0 21.3 10.7 8.3
Rated load amps
Power factor
Locked rotor amps
Full load amps
Locked rotor amps
10.4 5.8 13.5 6.0 13.7 6.2 4.8 15.6 7.8 5.8
.85
73
.84 .83 .81 .90 .92 .88 .90 .91 .90
38 88 44 83.1 41 30.4 110 52 35.5
1.1 .55 1.7 1.0 1.7 1.0 1.0 1.7 1.0 1.0
1.9
1.1 4.1 2.2 3.1 2.3 2.3 3.1 2.3 2.3
3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
92M88 S
92M89 S
92M92 S
92M90 S
69J06 S S
69J07 S S
L15−65−30, L15−65−40,
S S S
L15−65−50
Field Fabricate S
TS − 3 to 5 Ton R−410A Air Conditioners / Page 6
INSTALLATION CLEARANCES − INCHES (MM)
Model N
Numb
(dB)
NOTES:
See NOTES
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
See
NOTES
See NOTES
See
NOTES
CONTROL
BOX
OUTDOOR SOUND DATA
1
Unit
o.
125
TSA036S4 70.5 67.5 69.5 72.5 69.5 63 59 76
TSA042S4 74 76.5 76.5 75.5 72 68 63.5 80
TSA048S4 73.5 76 76 76.5 72.5 69.5 64.5 80
TSA060S4 73.5 74.5 77 75 72 69 64.5 80
NOTE − the octave sound power data does not include tonal correction.
1
Tested according to ARI Standard 270 test conditions.
Octave Band Sound Power Levels dBA, re 10
250 500 1000 2000 4000 8000
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
−12
Center Frequency − HZ
Watts
1
Sound Rating
er
TS − 3 to 5 Ton R−410A Air Conditioners / Page 7
DIMENSIONS − INCHES (MM)
Model N
INLET
AIR
INLET AIR
INLET AIR
TOP VIEW
A
INLET
AIR
LIQUID LINE
CONNECTION
(Around perimeter of base)
SUCTION LINE
CONNECTION
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
COIL DRAIN OUTLETS
CONDENSER
COIL FAN
4-3/8 (111 )
6-3/8 (162)
4-3/8 (111 )
6-3/8 (162)
COMPRESSOR
4-3/8 (111 )
4-3/8 (111 )
TOP VIEW BASE SECTION
A
DISCHARGE AIR
4-3/8 (111)
4-3/8 (111)
COMPRESSOR
BC
SUCTION &
LIQUID LINE
CONNECTIONS
ELECTRICAL
INLETS
2-3/4 (70)
2 (51)
SIDE VIEW
TSA036S4
3/4
(19)
o.
in.
A B C
mm in. mm in. mm
24-1/4 616 29-1/4 743 28-1/2 724
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
SIDE VIEW
TSA042S4 24-1/4 616 33-1/4 845 32-1/2 826
TSA048S4 28-1/4 718 29−1/4 743 28−1/2 724
TSA060S4 28-1/4 718 37−1/4 946 36−1/4 921
TS − 3 to 5 Ton R−410A Air Conditioners / Page 8