Improper installation, adjustment, alteration,
service or maintenance can cause personal injury,
loss of life, or damage to property.
Installation and service must be performed by a
licensed professional installer (or equivalent) or a
service agency.
CAUTION
Physical contact with metal edges and corners
while applying excessive force or rapid motion can
result in personal injury. Be aware of, and use
caution when working near these areas during
installation or while servicing this equipment.
INSTRUCTIONS
T−Classt TSA*H4 Units
TSA036H4N41, TSA042H4N41,
TSA048H4N41 and TSA060H4N41
The Clean Air Act of 1990 bans the intentional
venting of refrigerant (CFCs, HCFCs and HFCs) as
of July 1, 1992. Approved methods of recovery,
recycling or reclaiming must be followed. Fines
and/or incarceration may be levied for
noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as
specified in the Lennox Engineering Handbook.
Coils previously charged with HCFC−22 must be
flushed.
03/08506083−01
*2P0308**P506083-01*
Check the unit for shipping damage and that all included
items listed below are intact. If damaged, or if parts are
missing, immediately contact the last carrier.
1 Assembled outdoor unit
1 Liquid line filter drier
TSA*H4 Air Conditioners
The TSA*H4 Air Conditioners, which will also be referred to
in this instruction as the outdoor unit, uses HFC−410A
refrigerant. This outdoor unit must be installed with a
matching indoor unit and line set as outlined in the TSA*H4
Engineering Handbook. TSA*H4 Air Conditioners are
designed for use in thermal expansion valve (TXV)
systems.
Page 1
Unit Dimensions − Inches (mm)
A
A
B
SIDE VIEW
Model NumbersAB
TSA036H4N4128−1/4 (718)37−1/4 (946)
TSA042H4N4128−1/4 (718)29−1/4 (743)
TSA048H4N4128−1/4 (718)37−1/4 (946)
TSA060H4N4132−1/4 (819)33−1/4 (845)
OUTDOOR COIL FAN
COMPRESSOR
SUCTION AND LIQUID LINE
OPTIONAL UNIT STAND-OFF KIT (4)
CONNECTION
(FIELD INSTALLED)
PartsRecommended Torque
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
DISCHARGE AIR
SIDE VIEW
Table 1. Torque Requirements
WARNING
This product and/or the indoor unit it is matched
with may contain fiberglass wool.
Disturbing the insulation during installation,
maintenance, or repair will expose you to fiberglass
wool dust. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California
to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold
gauge set that features low loss anti−blow back fittings.
See figure 1 for a typical manifold gauge connection setup
for charging.
Manifold gauge sets used with HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 on the high side and a low side of
30" vacuum to 250 psi with dampened speed to 500 psi.
Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
IMPORTANT
Only use Allen wrenches of sufficient hardness
(50Rc − Rockwell Harness Scale minimum). Fully
insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9
ft−lbs for small valves, to 25 ft−lbs for large valves) to
prevent refrigerant loss during shipping and
handling. Using an Allen wrench rated at less than
50Rc risks rounding or breaking off the wrench, or
stripping the valve stem recess.
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
506083−01 03/08
The liquid and suction line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Page 2
OUTDOOR UNIT
(Uncased Coil Shown)
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HFC−410A
DRUM
HIGH
LIQUID LINE
SERVICE VALVE
COMPRESSOR
FILTER DRIER
Figure 1. Typical Manifold Gauge Connection Setup
Each service valve is equipped with a service port which
has a factory−installed valve stem.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 2. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and
fitted snugly over the cap before tightening.
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.
OUTDOOR
COIL
SUCTION LINE
SERVICE VALVE
TXV
To Open and Close Angle−TypeService Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension
(3/16" for liquid-line valve sizes and 5/16" for
suction-line valve sizes) to back the stem out
counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.
NOTE − A label with specific torque requirement may be
affixed to the stem cap. If the label is present, use the
specified torque.
NOTE− To prevent stripping of the cap, the appropriately
sized wrench should fit snugly over the cap before
tightening the cap.
SERVICE PORT CAP
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR UNIT
CORE
VALVE IS FRONT−SEATED
SERVICE PORT
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
STEM CAP
(CLOSED)
Figure 3. Angle−Type Service Valve
(Font−Seated Closed)
Page 3
TSA*H4 SERIES
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
VALVE IS BACK−SEATED
(OPENED)
SERVICE PORT
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
Figure 4. Angle−Type Service Valve
(Back−Seated Opened)
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
Open to line set when valve is closed, to
both line set and unit when valve is open.
Use appropriately sized
wrench.
To open rotate stem
counterclockwise 90°.
To close rotate stem clockwise
90°.
TO INDOOR UNIT
BALL (SHOWN
CLOSED)
VALV E
STEM
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.
NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified torque.
Recovering Refrigerant from Existing
HCFC−22 System
Remove existing HCFC−22 refrigerant using the following
procedures:
METHOD 1:
If the existing outdoor unit is not equipped with shut−off
valves, or if the unit is not operational and you plan to use
the existing HCFC−22 refrigerant to flush the system, then:
NOTE − Use recovery machine instructions for specific
setup requirements.
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean
recovery cylinder and a recovery machine. Use the
instructions provided with the recovery machine on
how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing
system. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
STEM CAP
Figure 5. Ball−Type Service Valve
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrench to open. To open
valve, rotate stem counterclockwise 90°. To close
rotate stem clockwise 90°.
RECOVERY MACHINE
CLEAN RECOVERY
CYLINDER
MANIFOLD GAUGES
OUTDOOR UNIT
Figure 6. Typical Refrigerant Recovery (Method 1)
NOTE − Use recovery machine instructions for specific
setup requirements.
METHOD 2:
If the existing outdoor unit is equipped with manual shut−off
valves and you plan to use new HCFC−22 refrigerant to
flush the system then:
1. Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.
2. Pump all of the existing HCFC−22 refrigerant back into
the outdoor unit.
NOTE − It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.
506083−01 03/08
Page 4
3. When the low side system pressures reach 0 psig,
close the suction line valve.
4. Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the
low side of the system.
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves.
Disconnect electrical service at the disconnect switch.
Remove existing outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY
FROM WINDOWS
See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to figure 7 for mandatory
installation clearance requirements.
(SEE NOTES BELOW
FIGURE)
(SEE NOTES
BELOW
FIGURE)
SEE NOTES
BELOW FIGURE)
(SEE NOTES
BELOW
FIGURE)
Figure 7. Installation Clearances
NOTES:
Service panel access clearance of 30 in. (762 mm)
must be maintained.
Clearance to one of the other three sides must be 36
in. (914 mm)
.
TWO 90° ELBOWS INSTALLED
IN LINE SET WILL REDUCE
LINE SET VIBRATION.
Figure 8. Outside Unit Placement and Installation
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground would not collect around the unit as
illustrated in figure 9.
DISCHARGE AIR
BUILDING
STRUCTURE
MOUNTING
SLAB
GROUND LEVEL
Clearance on one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
Clearance required on top of unit is 48 in. (1219 mm).
A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
Figure 9. Typical Slab Mounting at Ground Level
Slab may be level or have a slope tolerance away from the
building of not more than two degrees, or 2 inches per 5
feet (51 mm per 1524 mm) as illustrated in figure 9.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above
the surface of the roof. Ensure the weight of the unit is
properly distributed over roof joists and rafters. Either
redwood, steel supports, or roofed in equipment platform is
recommended.
Page 5
TSA*H4 SERIES
New or Replacement Line Set
This section provides information on installation or
replacement of existing line set. If line set is not being
installed or replace then proceed to Brazing Connections
on page 7.
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds.
Also, consider the following when placing and installing a
high−efficiency air conditioner:
Typically a liquid line used to meter flow is 1/4" in diameter
and copper.
LIQUID LINE FILTER DRIER INSTALLATION
The filter drier (one is shipped with each TSA*H4 unit)
must be field installed in the liquid line between the outdoor
unit’s liquid line service valve and the indoor coil’s
expansion valve. This filter drier must be installed to
ensure a clean, moisture−free system. Failure to install the
filter drier will void the warranty. A replacement filter drier is
available from Lennox. See Brazing Connections on page
7 for special procedures on brazing.
BRAZE CONNECTION
POINTS
REFRIGERANT LINE SET
Field refrigerant line set consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or braze connections). Use Lennox L15 (braze,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed below.
Table 2. Refrigerant Line Set
Models
−036
−042
−048
−060
Field
Connections
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Suction
Line
7/8 in
(22 mm)
1−1/8 in.
(29 mm)
Recommended Line Set
Liquid
Line
3/8 in.
(10
mm)
3/8 in.
(10
mm)
Suction
Line
7/8 in
(22 mm)
1−1/8 in.
(29 mm)
L15
Line Set
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
Field
Fabricated
NOTE − When installing refrigerant lines longer than 50
feet, contact Lennox Technical Support Product
Applications for assistance or Lennox piping manual. To
obtain the correct information from Lennox, be sure to
communicate the following points:
Model (TSA*H4) and size of unit (e.g. −060).
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.
If the TSA*H4 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served
as a metering device (RFCI), the liquid line must be
replaced prior to the installation of the TSA*H4 unit.
LIQUID
LINE
OUTDOOR
UNIT
LIQUID LINE
SERVICE VALVE
LINE
LIQUID LINE
FILTER DRIER
Figure 10. Typical Liquid Line Filter Drier
Installation
INSTALLING LINE SET
Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set
isolation:
Installation of line set on horizontal runs is
illustrated in figure 11.
Installation of line set on vertical runs is illustrated in
figure 12.
Installation of a transition from vertical to
horizontal is illustrated in figure 13.
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
Strap the suction line to the
joist or rafter at 8 feet
intervals then strap the
liquid line to the suction line.
8 FEET
Figure 11. Refrigerant Line Set: Installing
Horizontal Runs
WIRE TIE
(AROUND
SUCTION LINE
ONLY)
TAPE OR
WIRE TIE
506083−01 03/08
Page 6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.