Lennox TSA036H4N41, TSA048H4N41, TSA060H4N41, TSA042H4N41 Installation Instructions Manual

Page 1
INSTALLATION
2008 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
INSTRUCTIONS
T−Classt TSA*H4 Units
TSA036H4N41, TSA042H4N41, TSA048H4N41 and TSA060H4N41
AIR CONDITIONER
506083−01 03/08
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
TSA*H4 Air Conditioners 1. . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 4. . . . . . .
Removing Existing Outdoor Unit 5. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 5. . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 6. . . . . . . . . . . . . . . . . . . . .
Brazing Connections 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 8. . . . . . . . . . . .
Flushing the System 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 10. . . . . . . . .
Testing for Leaks 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 12. . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 13. . . . . . . . . . .
Electrical Connections 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 15. . . . . . . . . . . . . . . .
System Operation 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information 19. . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 20. . . . . . . . . . . . . .
Shipping and Packing List
Litho U.S.A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as specified in the Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
03/08 506083−01
*2P0308* *P506083-01*
Check the unit for shipping damage and that all included items listed below are intact. If damaged, or if parts are missing, immediately contact the last carrier.
1  Assembled outdoor unit 1  Liquid line filter drier
TSA*H4 Air Conditioners
The TSA*H4 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the TSA*H4 Engineering Handbook. TSA*H4 Air Conditioners are designed for use in thermal expansion valve (TXV) systems.
Page 1
Page 2
Unit Dimensions − Inches (mm)
A
A
B
SIDE VIEW
Model Numbers A B
TSA036H4N41 28−1/4 (718) 37−1/4 (946)
TSA042H4N41 28−1/4 (718) 29−1/4 (743)
TSA048H4N41 28−1/4 (718) 37−1/4 (946)
TSA060H4N41 32−1/4 (819) 33−1/4 (845)
OUTDOOR COIL FAN
COMPRESSOR
SUCTION AND LIQUID LINE
OPTIONAL UNIT STAND-OFF KIT (4)
CONNECTION
(FIELD INSTALLED)
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
DISCHARGE AIR
SIDE VIEW
Table 1. Torque Requirements
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See figure 1 for a typical manifold gauge connection setup for charging.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
506083−01 03/08
The liquid and suction line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Page 2
Page 3
OUTDOOR UNIT
(Uncased Coil Shown)
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HFC−410A
DRUM
HIGH
LIQUID LINE
SERVICE VALVE
COMPRESSOR
FILTER DRIER
Figure 1. Typical Manifold Gauge Connection Setup
Each service valve is equipped with a service port which has a factory−installed valve stem.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 2. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 2.
OUTDOOR
COIL
SUCTION LINE SERVICE VALVE
TXV
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 2.
NOTE − A label with specific torque requirement may be affixed to the stem cap. If the label is present, use the specified torque.
NOTE− To prevent stripping of the cap, the appropriately sized wrench should fit snugly over the cap before tightening the cap.
SERVICE PORT CAP
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR UNIT
CORE
VALVE IS FRONT−SEATED
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
STEM CAP
(CLOSED)
Figure 3. Angle−Type Service Valve
(Font−Seated Closed)
Page 3
TSA*H4 SERIES
Page 4
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
VALVE IS BACK−SEATED
(OPENED)
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 4. Angle−Type Service Valve
(Back−Seated Opened)
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
Open to line set when valve is closed, to both line set and unit when valve is open.
Use appropriately sized wrench.
To open rotate stem counterclockwise 90°.
To close rotate stem clockwise 90°.
TO INDOOR UNIT
BALL (SHOWN CLOSED)
VALV E STEM
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 2.
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Recovering Refrigerant from Existing HCFC−22 System
Remove existing HCFC−22 refrigerant using the following procedures:
METHOD 1:
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 refrigerant to flush the system, then:
NOTE − Use recovery machine instructions for specific setup requirements.
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recovery machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
STEM CAP
Figure 5. Ball−Type Service Valve
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 2.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
RECOVERY MACHINE
CLEAN RECOVERY CYLINDER
MANIFOLD GAUGES
OUTDOOR UNIT
Figure 6. Typical Refrigerant Recovery (Method 1)
NOTE − Use recovery machine instructions for specific setup requirements.
METHOD 2:
If the existing outdoor unit is equipped with manual shut−off valves and you plan to use new HCFC−22 refrigerant to flush the system then:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump all of the existing HCFC−22 refrigerant back into the outdoor unit.
NOTE − It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.
506083−01 03/08
Page 4
Page 5
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves. Disconnect electrical service at the disconnect switch. Remove existing outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY
FROM WINDOWS
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory installation clearance requirements.
(SEE NOTES BELOW
FIGURE)
(SEE NOTES
BELOW
FIGURE)
SEE NOTES
BELOW FIGURE)
(SEE NOTES
BELOW
FIGURE)
Figure 7. Installation Clearances
NOTES:
Service panel access clearance of 30 in. (762 mm)
must be maintained.
Clearance to one of the other three sides must be 36
in. (914 mm)
.
TWO 90° ELBOWS INSTALLED
IN LINE SET WILL REDUCE
LINE SET VIBRATION.
Figure 8. Outside Unit Placement and Installation
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in figure 9.
DISCHARGE AIR
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
Clearance on one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
Clearance required on top of unit is 48 in. (1219 mm).
A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
Figure 9. Typical Slab Mounting at Ground Level
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in figure 9.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Either redwood, steel supports, or roofed in equipment platform is recommended.
Page 5
TSA*H4 SERIES
Page 6
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set is not being installed or replace then proceed to Brazing Connections on page 7.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high−efficiency air conditioner:
Typically a liquid line used to meter flow is 1/4" in diameter and copper.
LIQUID LINE FILTER DRIER INSTALLATION
The filter drier (one is shipped with each TSA*H4 unit) must be field installed in the liquid line between the outdoor unit’s liquid line service valve and the indoor coil’s expansion valve. This filter drier must be installed to ensure a clean, moisture−free system. Failure to install the filter drier will void the warranty. A replacement filter drier is available from Lennox. See Brazing Connections on page 7 for special procedures on brazing.
BRAZE CONNECTION
POINTS
REFRIGERANT LINE SET
Field refrigerant line set consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non−flare) series line set, or use field−fabricated refrigerant lines as listed below.
Table 2. Refrigerant Line Set
Models
−036
−042
−048
−060
Field Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
Suction Line
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
Suction Line
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Set
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE − When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (TSA*H4) and size of unit (e.g. −060). Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the TSA*H4 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the TSA*H4 unit.
LIQUID
LINE
OUTDOOR
UNIT
LIQUID LINE
SERVICE VALVE
LINE
LIQUID LINE
FILTER DRIER
Figure 10. Typical Liquid Line Filter Drier
Installation INSTALLING LINE SET Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set isolation:
Installation of line set on horizontal runs is
illustrated in figure 11.
Installation of line set on vertical runs is illustrated in
figure 12.
Installation of a transition from vertical to
horizontal is illustrated in figure 13.
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
Strap the suction line to the joist or rafter at 8 feet intervals then strap the liquid line to the suction line.
8 FEET
Figure 11. Refrigerant Line Set: Installing
Horizontal Runs
WIRE TIE (AROUND SUCTION LINE ONLY)
TAPE OR WIRE TIE
506083−01 03/08
Page 6
Page 7
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
SLEEVE
SUCTION LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID
LINE
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
SUCTION LINE WRAPPED WITH
OUTSIDE
WALL
PVC PIPE FIBERGLASS INSULATION
ARMAFLEX
LIQUID LINE
IMPORTANT! REFRIGERANT
LINES MUST NOT CONTACT
CAULK
STRUCTURE.
Figure 12. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown)
AUTOMOTIVE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN ARMAFLEX
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER
WALL STUD
METAL SLEEVE
MUFFLER-TYPE HANGER
Figure 13. Refrigerant Line Set: Transition
from Vertical to Horizontal
Brazing Connections
Use the following procedure to braze the line set to the new outdoor unit. Figure 14 is provided as a general guide for preparing to braze the line set to the outdoor unit.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around both the liquid and suction line service valve body and copper tube stub. Use another wet cloth underneath the valve body to protect the base paint.
Page 7
TSA*H4 SERIES
Page 8
1
2
3
CUT AND DEBUR
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS AFTER
THEY HAVE COOLED.
INDOOR UNIT
6
BRAZE LINE SET
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
Figure 14. Brazing Connections
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
NOTE − The RFCIV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow. Repeat procedure starting at paragraph 4 for brazing the suction line to service valve.
7. After all connections have been brazed, disconnect manifold gauge set from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service caps if desired to close off refrigerant ports.
Removing Indoor Unit Metering Device
ATTACH
GAUGES
SERVICE
5
VALVE
SERVICE
VALVE
OUTDOOR
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes the following:
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
BRASS NUTS (10)
LIQUID LINE
ASSEMBLY
Figure 15. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
PISTON RETAINER
STRAINER
COPPER TUBE
Remove the existing HCFC−22 fixed orifice or thermal expansion valve from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
506083−01 03/08
4. Remove and discard Teflon ring, orifice, and valve stem assembly if present as illustrated in figure 16.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Page 8
Page 9
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
ORIFICE
REMOVE AND DISCARD VALVE STEM ASSEMBLY (IF PRESENT)
BRASS NUT
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 17.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
DISTRIBUTOR
ASSEMBLY
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
VALVE STEM
VALVE STEM CAP
(Uncased Coil Shown)
Figure 16. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
Use following procedure for a typical TXV removal:
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
LIQUID LINE
ORIFICE HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
TXV
TEFLON
RING
SENSING
LINE
Flushing Existing System
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.
Failure to properly flush the system per the instructions below will void the warranty.
IMPORTANT
LIQUID LINE ASSEMBLY
WITH BRASS NUT
MALE EQUALIZER LINE
FITTING
SENSING BULB
SUCTION
LINE
LIQUID
LINE
Figure 17. Typical TXV Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in figure 17.
5. Disconnect the liquid line from the TXV at the liquid line assembly.
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
If the original system used HCFC−22 refrigerant, then the system must be flushed. If the original system used HFC−410A refrigerant, then proceed to Installing New Refrigerant Metering Device on page 10.
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
Two clean HCFC−22 recovery bottles, Oilless recovery machine with pump-down feature,
Page 9
TSA*H4 SERIES
Page 10
Two gauge sets (one for HCFC−22; one for
HFC−410A).
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − The inverted HCFC−22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
GAUGE
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
HIGH
PRESSURE
CLOSED
Figure 18. Typical Flushing Connection
FLUSHING PROCEDURE
1. Connect the following:
HCFC−22 cylinder with clean refrigerant to the
suction service valve,
HCFC−22 gauge set to the liquid line valve, Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
6. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor unit coil before removing the recovery machine, gauges and HCFC−22 refrigerant drum.
Installing New Indoor Unit Metering Device
TSA*H4 units are used in thermal expansion valve (TXV) systems only.
1/8 TURN
12
11
8
7
6
9
10
8
11
12
1
2
3
10
9
4
7
5
6
Figure 19. Tightening Distance
TSA*H4 ENGINEERING HANDBOOK
See the TSA*H4 Engineering Handbook for approved indoor/outdoor match−ups, applicable TXV kit, and application information.
Figure 20 illustrates the typical TXV kit parts and quantities.
TXV (1)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 20. TXV Kit Components
1/2 TURN
1
2
3
4
5
HEX HEAD BOLTS
AND NUTS (2)
506083−01 03/08
Page 10
Page 11
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the TXV and provide an access for field servicing of the TXV. Refer to Figure 21 for reference during installation of TXV unit.
6. Attach the sensing bulb of the TXV in the proper orientation as illustrated in figure 22 to the suction line using the clamp and screws provided.
SUCTION LINE
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE FITTING (SEE FIGURE 23 FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 22 FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE
BULB
SUCTION LINE
BULB
12
12
BULB
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
NOTE − NEVER MOUNT ON BOTTOM OF LINE.
Figure 22. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line.
IMPORTANT
When removing the seal nut, ensure that the copper flare seal bonnet is removed.
Figure 21. Typical TXV Installation
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s liquid line orifice housing.
2. Install one of the provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
3. Attach the stubbed end of the kit valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 19, or 20 ft−lb.
4. Place the remaining Teflon washer around the other end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
5. Attach the liquid line assembly to the TXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 19, or 20 ft−lb.
FLARE SEAL
CAP
OR
MALE BRASS EQUALIZER
FLARE NUT
COPPER
FLARE SEAL
BONNET
LINE FITTING
SUCTION LINE
Figure 23. Copper Flare Seal Bonnet Removal
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in figure 19.
NOTE − To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
Page 11
TSA*H4 SERIES
Page 12
Testing for Leaks
After the line set has been connected to the indoor unit and outdoor unit, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
6. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected.
NOTE − Amounts of refrigerant will vary with line lengths.
7. Check all joints for leaks.
8. Purge dry nitrogen and HFC−410A mixture.
9. Correct any leaks and recheck.
10. After leak testing disconnect gauges from service ports.
Evacuating the System
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
LEAK TEST PROCEDURE
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
NOTE − Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
506083−01 03/08
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
EVACUATING PROCEDURE
NOTE − Remove cores from service valves if not already done.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to suction line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE − During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
Page 12
Page 13
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit.
10. Perform the following:
A Close manifold gauge valves B Shut off HFC−410A cylinder C Reinstall service valve cores by removing
manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure.
D Replace the stem caps and secure finger tight,
then tighten an additional one−sixth (1/6) of a turn as illustrated in figure 2.
In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Electric Shock Hazard. Can cause injury or death.
Line voltage is present at all components on units with single-pole contactors, even when unit is not in operation!
Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel.
Unit must be grounded in accordance with national and local codes.
HIGH VOLTAGE FIELD WIRING
Gnd
WIRE NUTS
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
Serving Unit Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Electrical Connections
In the United States, wiring must conform with current local codes and the current National Electric Code (NEC).
Page 13
GROMMET
GND
L3
L1
L2
Figure 24. Separating High/Low Voltage Field Wiring
(Typical Field Wiring)
WIRING CONNECTIONS
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring as illustrated in figures 24 and figure 25.
2. Ground unit at unit disconnect switch or to an earth ground.
3. Connect conduit to the unit using provided conduit bushing.
4. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
NOTE − For proper voltages, select thermostat wire gauge per the following table:
TSA*H4 SERIES
Page 14
5. Install low−voltage wiring from outdoor to indoor unit and from thermostat to indoor unit.
THERMOSTAT
R
POWER
INDOOR UNIT
R
6. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provided low voltage strain relief and to maintain separation of field installed low and high voltage circuits as illustrated in figure 25.
NOTE − 24VAC, Class II circuit connections are made in the low voltage junction box
W1
Y
G
C
HEAT
COOLING
INDOOR BLOWER
COMMON
W
Y
G
C
OUTDOOR UNIT
Y1
C
Figure 25. Low Voltage Wiring Diagram
(Typical Field Wiring)
Table 3. Wire Run Lengths
Wire Run Length AWG # Insulation Type
Less than 100 feet (30m)
More than 100 feet (30m)
18
16
Color−coded with a minimum temperature rating of 35ºC.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
NOTE − A complete unit wiring diagram is located inside the unit control box cover.
NOTE − See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent)
THREE-PHASE SCROLL VOLTAGE PHASING
Three-phase scroll compressors must be phased sequentially to ensure correct compressor rotation and operation. Incorrect line voltage phasing may cause compressor damage and abnormal unit operation. Power wires are color-coded as follows: Line 1 − red, line 2 − yellow, line 3 − blue.
Note: The thermostat used may be electro−me­chanical or electronic.
COOLING:
1. Cooling demand imitates a 24VAC signal from Y1 in the thermostat.
2. 24VAC from indoor unit Y1 energizes contacts K1−1, K1−2 and K1−3.
3. K1−1, K1−2 and K1−3 N.O. close, energizing compressor B1 and outdoor fan motor B4.
506083−01 03/08
END OF COOLING DEMAND:
1. Cooling demand is satisfied. Terminal Y1 is de−energized.
2. Compressor contacts K1−1, K1−2 and K1−3 are de−energized.
3. K1−1, K1−2 and K1−3 open and compressor B1 and outdoor fan motor B4 are de−energized and stop immediately.
Figure 26. Typical Unit Wiring Diagram
Page 14
Page 15
Start−Up and Charging Procedures
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open both the liquid and suction line service valves to release the refrigerant charge contained in the outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
53º
DRY
BULB
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
C
Drop
19º
All temperatures are expressed in ºF
DT
air flowair flow
INDOOR COIL
B
A
72º
B
64º
WET
BULB
DRY
BULB
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in figure 1.
low pressure gauge to suction line service port. high pressure gauge to liquid line service port.
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process
as illustration in figure 27.
DETERMINING CHARGE METHOD
To determine the correct charging method, use the illustration in figure 27.
1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between the measured T adjustment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T 53º 19 15 = 4 Increase the airflow
58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to increase/
decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
) = A minus C.
Drop
and the desired DT (T
Drop
DT = ºF ACTION
Drop
DT) is within +3º, no
Drop
Figure 27. Checking Indoor Coil Airflow Guide
Page 15
TSA*H4 SERIES
Page 16
START: Determine how refrigerant is metered
WHEN TO CHARGE?
Warm weather best Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure Indoor temperature between 70-80ºF (21−26ºC) Manifold gauge set connected to unit Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure suction line temperature
Figure 28. Determining Charge Method
OUTDOOR AMBIENT
TEMPERATURE
65ºF (18.3ºC)
and ABOVE
APPROACH OR
SUBCOOLING
TXV
64ºF (17.7ºC)
and BELOW
WEIGH-IN
START: Measure outdoor ambient temperature
USE EITHER APPROACH
OR SUBCOOLING
METHOD
65ºF
and
ABOVE
WEIGH IN TXV
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 29. Weigh In Method
ABOVE or
BELOW
64ºF and
BELOW
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 27, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
506083−01 03/08
Page 16
Page 17
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
64ºF and
ABOVE or
BELOW
BELOW
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
If refrigerant is added or removed, verify charge using the Approach Method.
If value is LESS than shown, add refrigerant.
If value is MORE than shown, remove refrigerant.
MORE or
LESS
65ºF
and
ABOVE
1. Confirm proper airflow across coil using figure
27.
2. Compare unit pressures with Table 4, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
4. Connect gauge set
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat to
call for cooling
7. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value to
determine saturation temperature (see table 5):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
11. Compare results with table below.
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −036 −042 −048 −060 65 (18) 13 (7.2) 10 (5.6) 8 (4.4) 8 (4.4) 75 (24) 9 (5.0) 7 (3.9) 8 (4.4) 7 (3.9) 85 (29) 7 (3.9) 7 (3.9) 8 (4.4) 8 (4.4) 95 (35) 8 (4.4) 7 (3.9) 8 (4.4) 7 (3.9) 105 (41) 9 (5.0) 7 (3.9) 8 (4.4) 6 (3.3) 115 (45) 10 (5.6) 7 (3.9) 7 (3.9) 6 (3.3) *Temperature of air entering outdoor coil
Figure 30. HFC−410A Subcooling TXV Charge
START: Measure outdoor ambient temperature
DO NOT CHARGE UNIT
USE WEIGH-IN METHOD
(Results of charging at low
Weigh-in or remove refrigerant
temperatures not reliable)
based upon line length
64ºF and
BELOW
If refrigerant is added or removed, verify charge using the Subcooling Method.
If value is LESS than shown, add refrigerant.
If value is MORE than shown, remove refrigerant.
MORE or
LESS
ABOVE or
BELOW
1. Confirm proper airflow across coil using figure
65ºF
and
ABOVE
27.
2. Compare unit pressures with Table 4, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).
4. Connect gauge set.
5. When heat demand is satisfied, set thermostat to call for cooling.
6. Allow temperatures and pressures to stabilize.
7. Record outdoor ambient temperature:
AMBº =_________
8. Record liquid line temperature:
LIQº = __________
9. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
10. Compare results with table below.
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −036 −042 −048 −060 65 (18) 2 (1.1) 6 (3.3) 7 (3.9) 8 (4.4) 75 (24) 5 (2.8) 8 (4.4) 8 (4.4) 9 (5.0) 85 (29) 8 (4.4) 8 (4.4) 8 (4.4) 9 (5.0) 95 (35) 7 (3.9) 8 (4.4) 8 (4.4) 9 (5.0) 105 (41) 6 (3.3) 8 (4.4) 8 (4.4) 9 (5.0) 115 (45) 6 (3.3) 8 (4.4) 9 (5.0) 9 (5.0) *Temperature of air entering outdoor coil
Figure 31. HFC−410A Approach TXV Charge
Page 17
TSA*H4 SERIES
Page 18
Table 4. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)
IMPORTANT
Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
TSA*H4
5F (5C)* Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction
−036 −042 −048 −060
Expansion Valve (TXV)
65 (18) 238 / 132 236 / 138 238 / 136 239 / 133
70 (21) 254 / 135 253 / 140 256 / 138 258 / 135
75 (24) 273 / 138 273 / 141 277 / 139 278 / 136
80 (27) 293 / 140 296 / 142 299 / 140 300 / 137
85 (29) 316 / 142 318 / 143 320 / 139 323 / 138
90 (32) 340 / 143 341 / 144 343 / 140 346 / 139
95 (35) 366 / 144 366 / 146 369 / 141 370 / 140
100 (38) 392 / 145 392 / 147 395 / 142 396 / 142
105 (41) 420 / 147 417 / 148 422 / 144 415 / 143
110 (43) 449 / 148 445 / 149 450 / 146 449 / 145
115 (45) 480 / 149 475 / 151 481 / 148 476 / 147
Table 5. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 11 0 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 11 2 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 11 3 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 11 4 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
INSTALLING SERVICE VALVE CAPS
Disconnect gauge set and install all service valve caps for both the liquid and suction line valves.
OUTDOOR UNIT
SERVICE VALVES
Figure 32. Installing Service Valve Caps
506083−01 03/08
INSTALL CAPS
System Operation
The outdoor unit and indoor blower will cycle on and off as dictated by demands from the room thermostat. When the thermostat’s blower switch is in the ON position, the indoor blower will operate continuously.
HIGH PRESSURE SWITCH
TSA*H4 units are equipped with a high-pressure switch that is located in the liquid line of the compressor. The switch (SPST, manual reset, normally closed) removes power from the compressor when discharge pressure rises above factory setting at 590 + 10 psi.
Page 18
Page 19
LOW PRESSURE SWITCH
TSA*H4 units are equipped with a low pressure switch that is located in the suction line to the compressor. The switch is a SPST, auto−reset switch that is normally closed. The switch opens at 25 psi and closes at 40 psi.
Maintenance
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
OUTDOOR UNIT
1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
7. Inspect drain holes in coil compartment base and clean if necessary.
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
INDOOR COIL
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
INDOOR UNIT
1. Clean or change filters.
2. Blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
UNIT NAMEPLATE: _________ ACTUAL: __________
OPTIONAL ACCESSORIES
Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may not apply:
Timed Off Control Sound Cover Suction Line Drier Stand−Off Kit Low Ambient Kit
Homeowner Information
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
NOTE − A white residue may appear on the coil guards and grilles on outdoor units. The residue is a non−toxic byproduct of manufacturing the flexible coating. It can be removed by wiping the coil guard with a cloth.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
1. Make sure power is off before cleaning. Clean and inspect outdoor coil. The coil may be flushed with a water hose.
2. The outdoor coil is protected by an inner mesh screen and a wire cage (see figure 33). If debris has collected between the mesh screen and the coil and cannot be dislodged by spraying unpressurized water from inside coil surface to the outside, the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage.
3. Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully remove the inner mesh screen.
4. Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.
5. If the push pin is loose and tends not to stay in place, brush the fins with a fin brush (22 fins/in). Line up the
Page 19
TSA*H4 SERIES
Page 20
push pin a couple fins to the right or left of the original hole and re−insert the pin.
9 PINS USED ON −048 AND −060; 6 PINS ALL
OTHERS
PUSH PIN
MESH
SCREEN
Figure 33. Cleaning Debris from Mesh
THERMOSTAT OPERATION
Though your thermostat may vary somewhat from the description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This
mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator
Temperature indicator displays actual room temperature.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your thermostat for operation details.
PRESERVICE CHECK
If your system fails to operate, check the following before calling for service:
Make sure all electrical disconnect switches are ON. Make sure the room thermostat temperature selector
AND the system switch are properly set.
Replace any blown fuses, or reset circuit breakers. Make sure unit access panels are in place. Make sure air filter is clean. Locate and record unit model number before calling.
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Suction Pressure Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Thermostat
Voltage With Compressor Operating Calibrated? Properly Set?  Level? 
506083−01 03/08
Page 20
Loading...