Lennox TPA036H4, TPA042H4, TPA048H4, TPA060H4 User Manual

E N G I N E E R I N G D A T A
TP
T−CLASSt − SPLIT SYSTEM UNITS
High Efficiency − R−410A − 60 HZ
H E A T P U M P O U T D O O R U N I T S
Bulletin No. 210497
May 2008
3 to 5 Tons
Cooling Capacity − 33,800 to 59,000 Btuh
Heating Capacity − 34,000 to 56,000 Btuh
MODEL NUMBER IDENTIFICATION
TPA Y1036 h 44 n
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Brand/Family
T = T−Classt Product Line
Unit Type
P = Heat Pump Outdoor Unit
Nominal Cooling Capacity − Tons
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
H = High Efficiency
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Vol ta ge
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz
Refrigerant Type
4 = R−410A
Part Load Capability
N = No part load, single stage compressor
Coil type
4 = Four−sided
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 2
FEATURES
CONTENTS
ARI Rating Tables Pages 9−17. . . . . . . . . . . . . . . . . . . . . . .
Commercial Control Systems Page 5. . . . . . . . . . . . . . . . .
Dimensions Page 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features Page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Guide Specifications Pages 18−22. . . . . . . . . . . . . . . . . . . .
Indoor Coil/Air Handler Substitution Page 9. . . . . . . . . . . .
Installation Clearances Page 7. . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification Page 1. . . . . . . . . . . . . . . . . .
Optional Accessories Page 6. . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warranty
Compressor − limited warranty for five years. All other covered components − one year.
Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.
Approvals
Certified in Accordance with the USE certification program, which is based on ARI Standard 210/240−2005. Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in ARI Standard 270-95. Tested in the Lennox Research Laboratory environmental test room. Rated According to U.S. Department of Energy (DOE) test procedures. Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC. Units are UL and ULC listed. ISO 9001 Registered Manufacturing Quality System. E
NERGY STAR® certified units are designed to use less
energy, help save money on utility bills, and help protect the environment.
Applications
SEER up to 15.0. Heating COP up to 4.04. HSPF (Region IV) 9.0. 3 through 5 tons. Three−phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Designed for applications with remotely located indoor air handler units. See Air Handlers sections for indoor unit data. Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory insuring proper operation. Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job.
For expanded ratings, see www.lennoxcommercial.com.
B
C
D
E
F
G
H
I
J
REFRIGERATION SYSTEM
Refrigerant
Non−chlorine, ozone friendly, R−410A. Unit is factory pre−charged with refrigerant. Total system refrigerant charge is dependant on outdoor unit size, indoor unit size and refrigerant line length. Refer to Installation Instructions for "Indoor Unit Match−Up and Sub−Cooling Charge Levels" to determine correct amount of charge required.
Outdoor Coil Fan
Direct drive fan moves large air volumes uniformly through entire outdoor coil for high refrigerant cooling and heating capacity. Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. Fan motor has sleeve bearings and is inherently protected. Motor totally enclosed for maximum protection from weather, dust and corrosion. Rain shield on motor provides additional protection from moisture. Louvered steel top fan guard furnished as standard. Fan service access accomplished by removal of top panel.
B
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 3
FEATURES
REFRIGERATION SYSTEM (CONTINUED)
Copper Tube/Enhanced Fin Coil
Lennox designed and fabricated coil. Ripple-edged aluminum fins. Copper tube construction. Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer. Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction. Coil is factory tested under high pressure to ensure leakproof construction. Entire coil is accessible for cleaning. PVC coated steel wire coil guard furnished as standard.
Expansion Valve − Outdoor Unit
Designed and sized specifically for use in heat pump system. Sensing bulb is located on the suction line between the reversing valve and the compressor to sense evaporator suction temperature in any cycle. Factory installed and piped.
High Capacity Liquid Line Drier
Factory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system. 100% molecular−sieve, bead type bi−flow drier.
Reversing Valve
4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa. Valve operates on pressure differential between outdoor unit and indoor unit of the system. Factory installed.
High Pressure Switch Kit
Protects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil. Automatic reset.
OPTIONS
Refrigerant Line Kits
Refrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory. Suction line fully insulated. Lines are stubbed at both ends. Not available for −060 models and must be field fabricated.
Loss of Charge Kit
Helps protect the compressor from damage due low refrigerant charge conditions. SPST, normally−closed switch, automatic reset switch mounted on suction line.
Compressor
Scroll Compressor
Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. Muffler in discharge line reduces operating sound levels. Compressor is installed in the unit on resilient rubber mounts for vibration free operation.
Compressor Crankcase Heater
Protects against refrigerant migration that can occur during low ambient operation.
OPTIONS
Compressor Low Ambient Cut−Off
Non-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.
Compressor Sound Cover
A reinforced vinyl compressor cover containing a 1−1/2 inch thick batt of fiberglass insulation. All open edges are sealed with a one−inch wide hook and loop fastening tape.
C
D E
F
G
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 4
FEATURES
Cabinet
Heavy gauge steel cabinet with five station metal wash process. Powder paint finish provides superior rust and corrosion protection. Painted base section. Control box is conveniently located with all controls factory wired. Corner patch plate allows access to compressor components. Drainage holes are provided in base section for moisture removal.
Refrigerant Line Connections, Electrical Inlets, Service Valves
Sweat connection vapor and liquid lines are located on corner of unit cabinet. Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.
OPTIONS
Hail Guards
Constructed of louvered heavy gauge steel painted to match cabinet. Surrounds unit on all four sides to prevent damage to the coil.
Mounting Base
Provides permanent foundation for outdoor units. High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot. Can be shipped singly or in packages of 6 to a carton.
Unit Stand-Off Kit
Black high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture. Four feet are furnished per order number.
CONTROLS
Defrost Control
Solid-state control furnished as standard. Gives a demand defrost cycle whenever system heating performance falls below optimum levels. The sensing element on coil determines when defrost cycle is required and when to terminate cycle. Anti−short cycle (5 minutes) incorporated into the board. Diagnostic LED’s furnished as an aid in troubleshooting. Conveniently located in control box.
OPTIONS
Freezestat
Installs on or near the discharge line of the indoor coil or on the suction line. Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint. Opens at 29°F and closes at 58°F.
L Connection
®
Network
See L Connection Engineering Handbook Bulletin in Controls section for details.
Low Ambient Control
Air conditioners operate satisfactorily down to 45°F outdoor air temperature without any additional controls. Two low ambient control options are available for field installation. The Low Ambient Control Kit allows unit operation down to 30°F. The second control option allows unit operation down to 0°F. This option requires that the outdoor fan motor and capacitor be changed. See Low Ambient Control Option table, page 7, for ordering information. Freezestat should be installed on compressors equipped with a low ambient kit. A compressor lock−out thermostat should be added to terminate compressor operation below recommended operation conditions (on/off operation, 30°F or modulating operation, 0°F).
Mild Weather Kit
Heat pump units operate satisfactorily in the heating mode at outdoor air temperatures up to 75_F. Mild Weather Kit can be field installed, allowing heating operation above 75_F.
Monitor Kit − Service Light
Contains ambient compensating thermistor and service light thermostat. For use with thermostats requiring input for indicator lights.
Outdoor Thermostat Kit
An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable. Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line. Thermostat kit and mounting box must be ordered extra.
Thermostat
Thermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.
Time Delay Relay Kit
Delays the indoor blower−off time during the cooling cycle. See ARI Rating Tables for usage.
H
I
J
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 5
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Compliant − E
NERGY STAR
®
Qualified − Backlit Display − Automatic Changeover
C0STAT02AE1L
Sensors For Touchscreen Thermostat
1
Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1
Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . . . . . . . . . . . . C0SNZN73AE1−
1
Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR03AE1−
Accessories For Touchscreen Thermostat
Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−
1
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4) C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.
DIGITAL NON−PROGRAMMABLE THERMOSTATS
Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control
Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L
Sensor For Digital Non−Programmable Thermostats Above
Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−
Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down Temperature Control
One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L
Sensor For Digital Non−Programmable Thermostats Above
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR04AE1−
Accessories For Digital Non−Programmable Thermostats Above
Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC17AE1−
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 6
SPECIFICATIONS
General
Model No. TPA036H4 TPA042H4 TPA048H4 TPA060H4
Data
Nominal Tonnage 3
3.5 4 5
1
Sound Rating Number 79 79 80 80
Connections
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
(sweat)
Vapor line o.d. − in. 7/8
7/8 7/8 1-1/8
2
Refrigerant R−410A charge furnished 9 lbs. 12 oz. 12 lbs. 7 oz. 12 lbs. 10 oz. 16 lbs. 0 oz.
Outdoor
Net face area
Outer coil 19.39 24.93 24.93 29.09
Coil sq. ft.
Inner coil 18.77
24.13 24.13 28.16
Tube diameter − in. 5/16 5/16 5/16 5/16
No. of rows 2 2 2 2
Fins per inch 22 22 22 22
Outdoor
Diameter − in. 26 26 26 26
Fan
No. of Blades 4
4 4 4
Motor hp 1/3 1/3 1/3 1/3
Cfm 4090 4347 4347 4550
Rpm 844 843 843 830
Watts 299 299 299 307
Shipping Data − lbs. 1 package 212 257 262 307
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 460V 208/230V 460V 208/230V 460V 208/230V 460V
3
Maximum overcurrent protection (amps) 20 15 30 15 30 15 35 15
4
Minimum circuit ampacity 13.1 8.1 18.6 8.4 18.9 8.7 21.8 10.7
Compressor
Rated Load Amps
9.6 5.6 13.5 6.0 13.7 6.2 16.0 7.8
p
Locked Rotor Amps
71
38 88 44 83.1 41. 110 52
Power Factor
.85
.84 .83 .81 .90 .92 .90 .91
Outdoor
Full Load Amps
1.8 1.0 1.8 1.0 1.8 1.0 1.8 1.0
Fan Motor
Locked Rotor Amps
2.9
2.5 2.9 2.5 2.9 2.5 2.9 2.5
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Sound Cover 69J03 S S S S
Freezestat
3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
Hail Guards
27W34 S
27W36 S S
94M94 S
Indoor Blower Off Delay Relay 58M81 S S S S
Loss of Charge Kit 84M23 S S S S
Low Ambient Control Options − See table page 7 S S S S
Mild Weather Kit 33M07 S S S S
Monitor Kit − Service Light 76F53 S S S S
Mounting Base 69J07 S S S S
Outdoor
Thermostat 56A87 S S S S
Thermostat Kit
Mounting Box 31461 S
S S
Refrigerant Line Sets
L15−65−30 L15−65−40
L15−65−50
S S S
Field Fabricate S
Unit Stand−Off Kit 94J45 S S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 7
LOW AMBIENT CONTROL Option (Down to 0°F)
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No. TPA036H4
TPA042H4 TPA048H4 TPA060H4
Speed Control Kit X5867 S S S S
Weatherproof Kit 56N41 S S S S
Motor
1/2 HP − 230V 69H75 S S S S
460V 69H76 S S S S
Capacitor with mounting bracket 53H06 S S S S
OUTDOOR SOUND DATA
1
Unit
Octave Band Sound Power Levels dBA, re 10
−12
Watts
Center Frequency − HZ
1
Sound
Ratin
g
Model N
o.
125
250 500 1000 2000 4000 8000
Rating
Number (dB)
TPA036H4 78.5 77.5 77.5 74.5 69.5 63.5 61.5 79
TPA042H4 76.5 78 78.5 73.5 69.5 63.5 58.5 79
TPA048H4 75.5 78 78.5 75 70 63.5 58.5 80
TPA060H4 75 77.5 77.5 75.5 70 65 65 80
NOTE − the octave sound power data does not include tonal correction.
1
Tested according to ARI Standard 270-95 test conditions.
INSTALLATION CLEARANCES − INCHES (MM)
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 8
DIMENSIONS − INCHES (MM)
6-3/8 (162)
4-3/8 (111 )
SIDE VIEW
VAPOR &
LIQUID LINE
CONNECTIONS
INLET
AIR
INLET
AIR
DISCHARGE AIR
SIDE VIEW
TOP VIEW
OUTDOOR
COIL FAN
COMPRESSOR
INLET AIR
INLET AIR
SUCTION LINE
CONNECTION
2-3/4 (70)
A
ELECTRICAL
INLETS
LIQUID LINE
CONNECTION
TOP VIEW BASE SECTION
4-3/8 (111 )
COMPRESSOR
COIL DRAIN OUTLETS
(Around perimeter of base)
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
BC
A
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
2 (51)
3/4
(19)
4-3/8 (111 )
4-3/8 (111 )
4-3/8
(111)
4-3/8
(111)
6-3/8 (162)
A B C
Model N
o.
in.
mm in. mm in. mm
TPA036H4
32−1/4 819 29-1/4 743 28-1/2 724
TPA042H4 TPA048H4
32-1/4 819 37 940 36−1/4 921
TPA060H4 32−1/4 819 43-1/4 1099 42-1/2 1080