Lennox TPA036H4, TPA042H4, TPA048H4, TPA060H4 User Manual

Page 1
E N G I N E E R I N G D A T A
TP
T−CLASSt − SPLIT SYSTEM UNITS
High Efficiency − R−410A − 60 HZ
H E A T P U M P O U T D O O R U N I T S
Bulletin No. 210497
May 2008
3 to 5 Tons
Cooling Capacity − 33,800 to 59,000 Btuh
Heating Capacity − 34,000 to 56,000 Btuh
MODEL NUMBER IDENTIFICATION
TPA Y1036 h 44 n
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Brand/Family
T = T−Classt Product Line
Unit Type
P = Heat Pump Outdoor Unit
Nominal Cooling Capacity − Tons
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
H = High Efficiency
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Vol ta ge
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz
Refrigerant Type
4 = R−410A
Part Load Capability
N = No part load, single stage compressor
Coil type
4 = Four−sided
Page 2
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 2
FEATURES
CONTENTS
ARI Rating Tables Pages 9−17. . . . . . . . . . . . . . . . . . . . . . .
Commercial Control Systems Page 5. . . . . . . . . . . . . . . . .
Dimensions Page 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features Page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Guide Specifications Pages 18−22. . . . . . . . . . . . . . . . . . . .
Indoor Coil/Air Handler Substitution Page 9. . . . . . . . . . . .
Installation Clearances Page 7. . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification Page 1. . . . . . . . . . . . . . . . . .
Optional Accessories Page 6. . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warranty
Compressor − limited warranty for five years. All other covered components − one year.
Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.
Approvals
Certified in Accordance with the USE certification program, which is based on ARI Standard 210/240−2005. Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in ARI Standard 270-95. Tested in the Lennox Research Laboratory environmental test room. Rated According to U.S. Department of Energy (DOE) test procedures. Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC. Units are UL and ULC listed. ISO 9001 Registered Manufacturing Quality System. E
NERGY STAR® certified units are designed to use less
energy, help save money on utility bills, and help protect the environment.
Applications
SEER up to 15.0. Heating COP up to 4.04. HSPF (Region IV) 9.0. 3 through 5 tons. Three−phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Designed for applications with remotely located indoor air handler units. See Air Handlers sections for indoor unit data. Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory insuring proper operation. Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job.
For expanded ratings, see www.lennoxcommercial.com.
B
C
D
E
F
G
H
I
J
REFRIGERATION SYSTEM
Refrigerant
Non−chlorine, ozone friendly, R−410A. Unit is factory pre−charged with refrigerant. Total system refrigerant charge is dependant on outdoor unit size, indoor unit size and refrigerant line length. Refer to Installation Instructions for "Indoor Unit Match−Up and Sub−Cooling Charge Levels" to determine correct amount of charge required.
Outdoor Coil Fan
Direct drive fan moves large air volumes uniformly through entire outdoor coil for high refrigerant cooling and heating capacity. Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. Fan motor has sleeve bearings and is inherently protected. Motor totally enclosed for maximum protection from weather, dust and corrosion. Rain shield on motor provides additional protection from moisture. Louvered steel top fan guard furnished as standard. Fan service access accomplished by removal of top panel.
B
Page 3
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 3
FEATURES
REFRIGERATION SYSTEM (CONTINUED)
Copper Tube/Enhanced Fin Coil
Lennox designed and fabricated coil. Ripple-edged aluminum fins. Copper tube construction. Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer. Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction. Coil is factory tested under high pressure to ensure leakproof construction. Entire coil is accessible for cleaning. PVC coated steel wire coil guard furnished as standard.
Expansion Valve − Outdoor Unit
Designed and sized specifically for use in heat pump system. Sensing bulb is located on the suction line between the reversing valve and the compressor to sense evaporator suction temperature in any cycle. Factory installed and piped.
High Capacity Liquid Line Drier
Factory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system. 100% molecular−sieve, bead type bi−flow drier.
Reversing Valve
4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa. Valve operates on pressure differential between outdoor unit and indoor unit of the system. Factory installed.
High Pressure Switch Kit
Protects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil. Automatic reset.
OPTIONS
Refrigerant Line Kits
Refrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory. Suction line fully insulated. Lines are stubbed at both ends. Not available for −060 models and must be field fabricated.
Loss of Charge Kit
Helps protect the compressor from damage due low refrigerant charge conditions. SPST, normally−closed switch, automatic reset switch mounted on suction line.
Compressor
Scroll Compressor
Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. Muffler in discharge line reduces operating sound levels. Compressor is installed in the unit on resilient rubber mounts for vibration free operation.
Compressor Crankcase Heater
Protects against refrigerant migration that can occur during low ambient operation.
OPTIONS
Compressor Low Ambient Cut−Off
Non-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.
Compressor Sound Cover
A reinforced vinyl compressor cover containing a 1−1/2 inch thick batt of fiberglass insulation. All open edges are sealed with a one−inch wide hook and loop fastening tape.
C
D E
F
G
Page 4
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 4
FEATURES
Cabinet
Heavy gauge steel cabinet with five station metal wash process. Powder paint finish provides superior rust and corrosion protection. Painted base section. Control box is conveniently located with all controls factory wired. Corner patch plate allows access to compressor components. Drainage holes are provided in base section for moisture removal.
Refrigerant Line Connections, Electrical Inlets, Service Valves
Sweat connection vapor and liquid lines are located on corner of unit cabinet. Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.
OPTIONS
Hail Guards
Constructed of louvered heavy gauge steel painted to match cabinet. Surrounds unit on all four sides to prevent damage to the coil.
Mounting Base
Provides permanent foundation for outdoor units. High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot. Can be shipped singly or in packages of 6 to a carton.
Unit Stand-Off Kit
Black high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture. Four feet are furnished per order number.
CONTROLS
Defrost Control
Solid-state control furnished as standard. Gives a demand defrost cycle whenever system heating performance falls below optimum levels. The sensing element on coil determines when defrost cycle is required and when to terminate cycle. Anti−short cycle (5 minutes) incorporated into the board. Diagnostic LED’s furnished as an aid in troubleshooting. Conveniently located in control box.
OPTIONS
Freezestat
Installs on or near the discharge line of the indoor coil or on the suction line. Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint. Opens at 29°F and closes at 58°F.
L Connection
®
Network
See L Connection Engineering Handbook Bulletin in Controls section for details.
Low Ambient Control
Air conditioners operate satisfactorily down to 45°F outdoor air temperature without any additional controls. Two low ambient control options are available for field installation. The Low Ambient Control Kit allows unit operation down to 30°F. The second control option allows unit operation down to 0°F. This option requires that the outdoor fan motor and capacitor be changed. See Low Ambient Control Option table, page 7, for ordering information. Freezestat should be installed on compressors equipped with a low ambient kit. A compressor lock−out thermostat should be added to terminate compressor operation below recommended operation conditions (on/off operation, 30°F or modulating operation, 0°F).
Mild Weather Kit
Heat pump units operate satisfactorily in the heating mode at outdoor air temperatures up to 75_F. Mild Weather Kit can be field installed, allowing heating operation above 75_F.
Monitor Kit − Service Light
Contains ambient compensating thermistor and service light thermostat. For use with thermostats requiring input for indicator lights.
Outdoor Thermostat Kit
An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable. Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line. Thermostat kit and mounting box must be ordered extra.
Thermostat
Thermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.
Time Delay Relay Kit
Delays the indoor blower−off time during the cooling cycle. See ARI Rating Tables for usage.
H
I
J
Page 5
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 5
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Compliant − E
NERGY STAR
®
Qualified − Backlit Display − Automatic Changeover
C0STAT02AE1L
Sensors For Touchscreen Thermostat
1
Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1
Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . . . . . . . . . . . . C0SNZN73AE1−
1
Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR03AE1−
Accessories For Touchscreen Thermostat
Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−
1
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4) C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.
DIGITAL NON−PROGRAMMABLE THERMOSTATS
Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control
Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L
Sensor For Digital Non−Programmable Thermostats Above
Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−
Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down Temperature Control
One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L
Sensor For Digital Non−Programmable Thermostats Above
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR04AE1−
Accessories For Digital Non−Programmable Thermostats Above
Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC17AE1−
Page 6
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 6
SPECIFICATIONS
General
Model No. TPA036H4 TPA042H4 TPA048H4 TPA060H4
Data
Nominal Tonnage 3
3.5 4 5
1
Sound Rating Number 79 79 80 80
Connections
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
(sweat)
Vapor line o.d. − in. 7/8
7/8 7/8 1-1/8
2
Refrigerant R−410A charge furnished 9 lbs. 12 oz. 12 lbs. 7 oz. 12 lbs. 10 oz. 16 lbs. 0 oz.
Outdoor
Net face area
Outer coil 19.39 24.93 24.93 29.09
Coil sq. ft.
Inner coil 18.77
24.13 24.13 28.16
Tube diameter − in. 5/16 5/16 5/16 5/16
No. of rows 2 2 2 2
Fins per inch 22 22 22 22
Outdoor
Diameter − in. 26 26 26 26
Fan
No. of Blades 4
4 4 4
Motor hp 1/3 1/3 1/3 1/3
Cfm 4090 4347 4347 4550
Rpm 844 843 843 830
Watts 299 299 299 307
Shipping Data − lbs. 1 package 212 257 262 307
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 460V 208/230V 460V 208/230V 460V 208/230V 460V
3
Maximum overcurrent protection (amps) 20 15 30 15 30 15 35 15
4
Minimum circuit ampacity 13.1 8.1 18.6 8.4 18.9 8.7 21.8 10.7
Compressor
Rated Load Amps
9.6 5.6 13.5 6.0 13.7 6.2 16.0 7.8
p
Locked Rotor Amps
71
38 88 44 83.1 41. 110 52
Power Factor
.85
.84 .83 .81 .90 .92 .90 .91
Outdoor
Full Load Amps
1.8 1.0 1.8 1.0 1.8 1.0 1.8 1.0
Fan Motor
Locked Rotor Amps
2.9
2.5 2.9 2.5 2.9 2.5 2.9 2.5
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Sound Cover 69J03 S S S S
Freezestat
3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
Hail Guards
27W34 S
27W36 S S
94M94 S
Indoor Blower Off Delay Relay 58M81 S S S S
Loss of Charge Kit 84M23 S S S S
Low Ambient Control Options − See table page 7 S S S S
Mild Weather Kit 33M07 S S S S
Monitor Kit − Service Light 76F53 S S S S
Mounting Base 69J07 S S S S
Outdoor
Thermostat 56A87 S S S S
Thermostat Kit
Mounting Box 31461 S
S S
Refrigerant Line Sets
L15−65−30 L15−65−40
L15−65−50
S S S
Field Fabricate S
Unit Stand−Off Kit 94J45 S S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 7
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 7
LOW AMBIENT CONTROL Option (Down to 0°F)
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No. TPA036H4
TPA042H4 TPA048H4 TPA060H4
Speed Control Kit X5867 S S S S
Weatherproof Kit 56N41 S S S S
Motor
1/2 HP − 230V 69H75 S S S S
460V 69H76 S S S S
Capacitor with mounting bracket 53H06 S S S S
OUTDOOR SOUND DATA
1
Unit
Octave Band Sound Power Levels dBA, re 10
−12
Watts
Center Frequency − HZ
1
Sound
Ratin
g
Model N
o.
125
250 500 1000 2000 4000 8000
Rating
Number (dB)
TPA036H4 78.5 77.5 77.5 74.5 69.5 63.5 61.5 79
TPA042H4 76.5 78 78.5 73.5 69.5 63.5 58.5 79
TPA048H4 75.5 78 78.5 75 70 63.5 58.5 80
TPA060H4 75 77.5 77.5 75.5 70 65 65 80
NOTE − the octave sound power data does not include tonal correction.
1
Tested according to ARI Standard 270-95 test conditions.
INSTALLATION CLEARANCES − INCHES (MM)
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
Page 8
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 8
DIMENSIONS − INCHES (MM)
6-3/8 (162)
4-3/8 (111 )
SIDE VIEW
VAPOR &
LIQUID LINE
CONNECTIONS
INLET
AIR
INLET
AIR
DISCHARGE AIR
SIDE VIEW
TOP VIEW
OUTDOOR
COIL FAN
COMPRESSOR
INLET AIR
INLET AIR
SUCTION LINE
CONNECTION
2-3/4 (70)
A
ELECTRICAL
INLETS
LIQUID LINE
CONNECTION
TOP VIEW BASE SECTION
4-3/8 (111 )
COMPRESSOR
COIL DRAIN OUTLETS
(Around perimeter of base)
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
BC
A
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
2 (51)
3/4
(19)
4-3/8 (111 )
4-3/8 (111 )
4-3/8
(111)
4-3/8
(111)
6-3/8 (162)
A B C
Model N
o.
in.
mm in. mm in. mm
TPA036H4
32−1/4 819 29-1/4 743 28-1/2 724
TPA042H4 TPA048H4
32-1/4 819 37 940 36−1/4 921
TPA060H4 32−1/4 819 43-1/4 1099 42-1/2 1080
Page 9
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 9
ARI RATINGS − INDOOR COIL / AIR HANDLER SUBSTITUTION
Substituting Coils in the ARI Tables
Most R−22 and R−410A indoor coils and air handlers are the same except for the factory installed expansion device. C33 coils can be used in place of the CX34 coils, CB26UH, CB27UH and CB30M air handlers can be used in place of the CBX26UH, CBX27UH and CBX32M, respectively. The expansion device is based on the size of the outdoor unit. The factory installed RFC or TXV on the C33/CB26UH/CB27UH/CB30M must be replaced to correspond to the outdoor unit. The correct TXV’s are:
3−3.5 ton heat pumps 49L25 4−5 ton heat pumps 91M02
Example:
A four−ton heat pump is being installed. The ARI table shows that CBX32M−048 is a matching air handler. A CB30M−51 with a 91M02 TXV can be used in its place.
UP−FLOW COILS
R−410A R−22
CX34−31A−6F
=
C33−31A−2
CX34−31B−6F
=
C33−31B−2
CX34−36A−6F
=
C33−36A−2
CX34−36B−6F
=
C33−36B−2
CX34−36C−6F
=
C33−36C−2
CX34−38A−6F
=
C33−38A−2
CX34−38B−6F
=
C33−38B−2 CX34−42B−6F = C33−42B−2 CX34−43B−6F = C33−43B−2 CX34−43C−6F = C33−43C−2
no equivalent
C33−44C−2
CX34−44/48B−6F
=
C33−48B−2
CX34−44/48C−6F
=
C33−48C−2 CX34−49C−6F
=
C33−49C−2
CX34−50/60C−6F
=
C33−50/60C−2 CX34−60D−6F
=
C33−60D−2 CX34−62C−6F
=
C33−62C−2 CX34−62D−6F
=
C33−62D−2
AIR HANDLERS
R−410A R−22
CBX26UH−036
= CB26UH−036−R
CBX26UH−042 = CB26UH−042−R
CBX26UH−048 = CB26UH−048
CBX26UH−060
= CB26UH−060−R
CBX27UH−036 = CB27UH−036
CBX27UH−042 = CB27UH−042
CBX27UH−048
= CB27UH−048
CBX27UH−060 = CB27UH−060
CBX32M−036 = CB30M−41
CBX32M−042
= CB30M−46
CBX32M−048 = CB30M−51
CBX32M−060 = CB30M−65
CBX32MV all
no equivalent
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA036H4 3 TON
Air Handlers Air Handlers
34,400 35,400 21,400 14.00 12.00 8.20 7.20 2865 2790 2570 3.72 2.44
4
CBX32M−042 (Multi−Position)
2
49L25
34,400 35,600 21,400 14.00 12.00 8.20 7.20 2865 2785 2575 3.74 2.44
4
CBX32M−036 (Multi−Position) Factory TXV
34,600 35,200 21,400 14.00 12.00 8.20 7.20 2885 2830 2595 3.64 2.42
5
CBX26UH−037 (Up−Flow / Horizontal) Factory TXV
34,600 35,400 21,400 14.00 12.00 8.20 7.20 2885 2760 2550 3.76 2.46
4
CBX32MV−036 (Multi−Position) Factory TXV
34,800 35,000 21,000 15.00 12.50 8.50 7.20 2785 2670 2450 3.84 2.50
4
CBX27UH−036 (Up−Flow / Horizontal) Factory TXV
35,800 35,200 21,200 15.00 12.50 8.50 7.20 2865 2685 2485 3.84 2.50
4
CBX32MV−048 (Multi−Position)
2
49L25
Up−Flow Indoor Coils Up−Flow Coils
34,400 35,400 21,600 13.00 11 .0 0 7.70 6.70 3125 2950 2705 3.52 2.34
3
CX34−38A/B−6F
2
49L25
34,600 34,800 21,200 13.00 11 .0 0 7.70 6.70 3145 3130 2855 3.26 2.18
3
CX34−44/48B/C−6F Factory TXV
35,000 35,000 21,200 13.00 11 .0 0 7.70 6.70 3180 3065 2820 3.34 2.20
3
CX34−50/60C−6F
2
49L25
35,200 35,000 21,200 13.00 11 .0 0 7.70 6.70 3200 3055 2815 3.36 2.20
3
CX34−43B/C−6F Factory TXV
35,400 35,000 21,200 13.00 11 .0 0 7.70 6.70 3220 3045 2805 3.36 2.22
3
CX34−49C−6F
2
49L25
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Page 10
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 10
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA036H4 3 TON
Up−Flow Indoor Coils + Furnaces Up−Flow Coils + Furnaces
34,600 35,000 21,200 14.00 12.00 8.20 7.20 2885 2825 2575 3.64 2.42 CX34−38B−6F
4
G61MPV−36B−070
2
49L25
34,600 35,000 21,200 14.00 12.00 8.20 7.20 2885 2825 2575 3.64 2.42 CX34−38B−6F
4
G71MPP−36B−0702 49L25
34,600 35,000 21,200 14.00 12.00 8.20 7.20 2885 2825 2575 3.64 2.42 CX34−38B−6F
4
G61MPV−36B−071
2
49L25
34,800 34,400 20,800 14.00 12.00 7.70 6.70 2900 3010 2735 3.34 2.22 CX34−44/48B−6F
4
G61MPV−36B−045 Factory TXV
34,800 35,200 21,200 14.00 12.00 8.20 7.20 2900 2835 2595 3.64 2.40 CX34−38A−6F
4
G60UHV−36A−070
2
49L25
34,800 35,200 21,400 14.00 12.00 8.20 7.20 2900 2850 2610 3.62 2.40 CX34−38B−6F
4
G61MPV−36B−045
2
49L25
35,000 34,200 20,600 15.00 12.50 8.00 6.70 2800 2930 2655 3.42 2.28 CX34−44/48C−6F
4
G61MPV−36C−090 Factory TXV
35,000 34,200 20,600 15.00 12.50 8.00 6.70 2800 2930 2655 3.42 2.28 CX34−44/48C−6F
4
G71MPP−36C−090 Factory TXV
35,000 34,400 20,800 14.50 12.00 8.00 6.70 2915 3005 2725 3.36 2.24 CX34−44/48B−6F
4
G61MPV−36B−070 Factory TXV
35,000 34,400 20,800 14.50 12.00 8.00 6.70 2915 3005 2725 3.36 2.24 CX34−44/48B−6F
4
G71MPP−36B−070 Factory TXV
35,000 34,400 20,800 14.50 12.00 8.00 6.70 2915 3005 2725 3.36 2.24 CX34−44/48B−6F
4
G61MPV−36B−071 Factory TXV
35,000 34,800 21,000 15.00 12.50 8.50 7.20 2800 2735 2495 3.72 2.46 CX34−38B−6F
4
G60UHV−36B−090
2
49L25
35,200 34,000 20,400 15.00 12.50 8.00 6.70 2815 2875 2595 3.46 2.30 CX34−43B−6F
4
G60UHV−36B−090 Factory TXV
35,200 34,200 20,600 15.00 12.50 8.00 6.70 2815 2910 2645 3.44 2.28 CX34−44/48B−6F
4
G60UHV−36B−090 Factory TXV
35,400 34,400 20,600 15.00 12.50 8.20 6.70 2830 2865 2620 3.52 2.30 CX34−50/60C−6F
4
G61MPV−36C−090 Factory TXV
35,400 34,400 20,600 15.00 12.50 8.20 6.70 2830 2865 2620 3.52 2.30 CX34−50/60C−6F
4
G71MPP−36C−090 Factory TXV
35,400 34,400 20,800 15.00 12.50 8.00 6.70 2830 2910 2655 3.46 2.30 CX34−44/48C−6F
4
G61MPV−60C−090 Factory TXV
35,400 34,400 20,800 15.00 12.50 8.00 6.70 2830 2910 2655 3.46 2.30 CX34−44/48C−6F
4
G71MPP−60C−090 Factory TXV
35,400 34,600 20,800 14.50 12.50 8.00 6.70 2830 2935 2695 3.46 2.26 CX34−43B−6F
4
G61MPV−36B−045 Factory TXV
35,400 34,600 20,800 14.50 12.50 8.00 6.70 2830 2925 2685 3.46 2.26 CX34−43B−6F
4
G61MPV−36B−070 Factory TXV
35,400 34,600 20,800 14.50 12.50 8.00 6.70 2830 2925 2685 3.46 2.26 CX34−43B−6F
4
G71MPP−36B−070 Factory TXV
35,400 34,600 20,800 14.50 12.50 8.00 6.70 2830 2925 2685 3.46 2.26 CX34−43B−6F
4
G61MPV−36B−071 Factory TXV
35,600 34,400 20,600 15.00 12.50 8.00 6.70 2850 2855 2610 3.54 2.32 CX34−43C−6F
4
G61MPV−36C−090 Factory TXV
35,600 34,400 20,600 15.00 12.50 8.00 6.70 2850 2855 2610 3.54 2.32 CX34−43C−6F
4
G71MPP−36C−090 Factory TXV
35,800 34,600 20,800 15.00 12.50 8.00 7.00 2865 2845 2620 3.56 2.32 CX34−50/60C−6F
4
G61MPV−60C−090
2
49L25
35,800 34,600 20,800 15.00 12.50 8.00 7.00 2865 2845 2620 3.56 2.32 CX34−50/60C−6F
4
G71MPP−60C−0902 49L25
36,000 34,400 20,600 15.00 12.50 8.20 7.00 2880 2845 2605 3.54 2.32 CX34−49C−6F
4
G61MPV−36C−090
2
49L25
36,000 34,400 20,600 15.00 12.50 8.20 7.00 2880 2845 2605 3.54 2.32 CX34−49C−6F
4
G71MPP−36C−0902 49L25
36,000 34,600 20,800 15.00 12.50 8.20 7.00 2880 2845 2615 3.56 2.32 CX34−43C−6F
4
G61MPV−60C−090 Factory TXV
36,000 34,600 20,800 15.00 12.50 8.20 7.00 2880 2845 2615 3.56 2.32 CX34−43C−6F
4
G71MPP−60C−090 Factory TXV
36,400 34,600 20,800 15.00 12.50 8.20 7.00 2910 2825 2610 3.58 2.34 CX34−49C−6F
4
G61MPV−60C−090
2
49L25
36,400 34,600 20,800 15.00 12.50 8.20 7.00 2910 2825 2610 3.58 2.34 CX34−49C−6F
4
G71MPP−60C−0902 49L25
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
Page 11
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 11
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA036H4 3 TON
Down−Flow Indoor Coils Down−Flow Coils
33,800 35,200 21,400 13.00 11 .0 0 7.70 6.70 3075 2980 2730 3.46 2.30
3
CR33−48B/C−F
2
49L25
34,800 35,600 21,600 13.00 11 .0 0 7.70 6.70 3165 2875 2655 3.62 2.38
3
CR33−50/60C−F
2
49L25
Down−Flow Indoor Coils + Furnaces Down−Flow Coils + Furnaces
34,200 34,800 21,000 14.00 12.00 8.20 7.00 2850 2860 2605 3.56 2.36 CR33−48B−F
4
G61MPV−36B−045
2
49L25
34,200 34,800 21,000 14.00 12.00 8.20 7.00 2850 2855 2600 3.58 2.36 CR33−48B−F
4
G61MPV−36B−070
2
49L25
34,200 34,800 21,000 14.00 12.00 8.20 7.00 2850 2855 2600 3.58 2.36 CR33−48B−F
4
G71MPP−36B−0702 49L25
34,200 34,800 21,000 14.00 12.00 8.20 7.00 2850 2855 2600 3.58 2.36 CR33−48B−F
4
G61MPV−36B−071
2
49L25
34,400 34,600 20,800 14.50 12.00 8.20 7.00 2865 2780 2525 3.64 2.42 CR33−48C−F
4
G61MPV−36C−090
2
49L25
34,400 34,600 20,800 14.50 12.00 8.20 7.00 2865 2780 2525 3.64 2.42 CR33−48C−F
4
G71MPP−36C−0902 49L25
34,400 34,600 20,800 14.50 12.50 8.20 7.00 2750 2765 2515 3.66 2.42 CR33−48B−F
4
G60DFV−36B−090
2
49L25
34,600 34,800 21,000 14.50 12.00 8.20 7.20 2885 2770 2535 3.68 2.42 CR33−48C−F
4
G61MPV−60C−090
2
49L25
34,600 34,800 21,000 14.50 12.00 8.20 7.20 2885 2770 2535 3.68 2.42 CR33−48C−F
4
G71MPP−60C−0902 49L25
35,600 34,600 20,600 15.00 13.00 9.00 7.50 2850 2545 2330 3.98 2.58 CR33−50/60C−F
4
G61MPV−36C−090
2
49L25
35,600 34,600 20,600 15.00 13.00 9.00 7.50 2850 2545 2330 3.98 2.58 CR33−50/60C−F
4
G71MPP−36C−0902 49L25
36,000 35,000 20,800 15.00 13.00 9.00 7.50 2880 2545 2340 4.04 2.60 CR33−50/60C−F
4
G61MPV−60C−090
2
49L25
36,000 35,000 20,800 15.00 13.00 9.00 7.50 2880 2545 2340 4.04 2.60 CR33−50/60C−F
4
G71MPP−60C−0902 49L25
Horizontal Indoor Coils Horizontal Coils
35,000 35,200 21,400 13.00 11 .0 0 7.70 6.70 3180 3015 2795 3.42 2.24
3
CH33−44/48B−2F
2
49L25
35,200 35,000 21,200 13.00 11 .0 0 7.70 6.70 3200 3050 2815 3.36 2.20
3
CH33−43C−2F
2
49L25
35,400 35,200 21,400 13.00 11 .0 0 7.70 6.70 3220 3020 2800 3.42 2.24
3
CH33−50/60C−2F
2
49L25
35,600 35,200 21,400 13.00 11 .0 0 7.70 6.70 3235 2995 2770 3.44 2.26
3
CH33−43B−2F
2
49L25
35,600 35,200 21,400 13.00 11 .0 0 7.70 6.70 3235 3020 2800 3.42 2.24
3
CH33−49C−2F
2
49L25
Horizontal Indoor Coils + Furnaces Horizontal Coils + Furnaces
35,200 34,800 21,000 14.00 12.00 8.20 6.70 2935 2930 2705 3.48 2.28 CH33−44/48B−2F
4
G61MPV−36B−045
2
49L25
35,200 34,800 21,000 14.00 12.00 8.20 6.70 2935 2920 2700 3.50 2.28 CH33−44/48B−2F
4
G61MPV−36B−070
2
49L25
35,200 34,800 21,000 14.00 12.00 8.20 6.70 2935 2920 2700 3.50 2.28 CH33−44/48B−2F
4
G71MPP−36B−0702 49L25
35,200 34,800 21,000 14.00 12.00 8.20 6.70 2935 2920 2700 3.50 2.28 CH33−44/48B−2F
4
G61MPV−36B−071
2
49L25
35,400 34,600 20,800 15.00 12.50 8.20 7.00 2830 2835 2625 3.58 2.32 CH33−44/48B−2F
4
G60UHV−36B−090
2
49L25
35,600 34,600 20,800 14.50 12.50 8.00 6.70 2850 2925 2685 3.46 2.26 CH33−43C−2F
4
G61MPV−36B−071
2
49L25
35,800 35,000 21,200 14.50 12.00 8.20 6.70 2985 2910 2680 3.52 2.32 CH33−43B−2F
4
G61MPV−36B−045
2
49L25
36,000 34,400 20,600 15.00 12.50 8.20 7.00 2880 2820 2595 3.58 2.32 CH33−50/60C−2F
4
G61MPV−36C−090
2
49L25
36,000 34,400 20,600 15.00 12.50 8.20 7.00 2880 2820 2595 3.58 2.32 CH33−50/60C−2F
4
G71MPP−36C−0902 49L25
36,000 34,600 20,600 15.00 12.50 8.20 7.00 2880 2820 2600 3.60 2.32 CH33−49C−2F
4
G61MPV−36C−090
2
49L25
36,000 34,600 20,600 15.00 12.50 8.20 7.00 2880 2820 2600 3.60 2.32 CH33−49C−2F
4
G71MPP−36C−0902 49L25
36,000 35,000 21,000 14.50 12.50 8.20 7.00 2880 2900 2670 3.54 2.30 CH33−43B−2F
4
G61MPV−36B−070
2
49L25
36,000 35,000 21,000 14.50 12.50 8.20 7.00 2880 2900 2670 3.54 2.30 CH33−43B−2F
4
G71MPP−36B−0702 49L25
36,200 34,800 20,800 15.00 12.50 8.20 7.00 2895 2805 2600 3.64 2.34 CH33−50/60C−2F
4
G61MPV−60C−090
2
49L25
36,200 34,800 20,800 15.00 12.50 8.20 7.00 2895 2805 2600 3.64 2.34 CH33−50/60C−2F
4
G71MPP−60C−0902 49L25
36,200 34,800 21,000 15.00 12.50 8.20 7.00 2895 2815 2595 3.62 2.36 CH33−43B−2F
4
G60UHV−36B−090
2
49L25
36,400 34,800 20,800 15.00 12.50 8.20 7.00 2910 2800 2600 3.64 2.34 CH33−49C−2F
4
G61MPV−60C−090
2
49L25
36,400 34,800 20,800 15.00 12.50 8.20 7.00 2910 2800 2600 3.64 2.34 CH33−49C−2F
4
G71MPP−60C−0902 49L25
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
Page 12
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 12
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA042H4 3.5 TON
Air Handlers Air Handlers
42,500 45,000 27,800 14.00 12.00 8.00 7.20 3540 3890 3540 3.40 2.30
4
CBX32M−048 (Multi−Position)
2
49L25
42,500 45,500 28,200 14.00 12.00 8.20 7.20 3540 3650 3320 3.66 2.48
5
CBX26UH−042 (Up−Flow / Horizontal) Factory TXV
43,500 44,500 27,400 15.00 12.50 8.20 7.20 3480 3735 3405 3.50 2.36
4
CBX27UH−042 (Up−Flow / Horizontal) Factory TXV
43,500 44,500 27,600 14.50 12.50 8.20 7.20 3480 3785 3465 3.44 2.34
4
CBX32MV−048 (Multi−Position)
2
49L25
Up−Flow Indoor Coils Up−Flow Coils
41,500 42,000 27,000 13.00 11 .0 0 7.70 6.70 3775 3440 3145 3.58 2.52
3
CX34−60D−6F
2
49L25
42,000 42,000 26,800 13.00 11 .0 0 7.70 6.70 3820 3475 3165 3.54 2.48
3
CX34−49C−6F
2
49L25
42,000 42,000 27,000 13.00 11 .0 0 7.70 6.70 3820 3435 3120 3.58 2.54
3
CX34−62D−6F
2
49L25
42,500 42,500 27,200 13.00 11 .0 0 7.70 6.70 3865 3350 3060 3.72 2.60
3
CX34−62C−6F
2
49L25
Up−Flow Indoor Coils + Furnaces Up−Flow Coils + Furnaces
42,000 41,000 26,000 15.00 12.50 8.50 7.70 3360 3230 2915 3.72 2.62 CX34−49C−6F
4
G60UHV−60C−090
2
49L25
42,000 41,000 26,000 15.00 13.00 9.00 7.70 3360 3165 2865 3.80 2.66 CX34−60D−6F
4
G60UHV−60D−135
2
49L25
42,000 41,000 26,200 14.50 12.00 8.20 7.50 3500 3310 2990 3.64 2.56 CX34−49C−6F
4
G61MPV−60C−091
2
49L25
42,000 41,500 26,200 14.50 12.00 8.20 7.50 3500 3285 2975 3.70 2.58 CX34−49C−6F
4
G61MPV−60C−090
2
49L25
42,000 41,500 26,200 14.50 12.00 8.20 7.50 3500 3285 2975 3.70 2.58 CX34−49C−6F
4
G71MPP−60C−0902 49L25
42,000 41,500 26,400 14.00 12.00 8.20 7.50 3500 3315 3010 3.66 2.56 CX34−49C−6F
4
G61MPV−36C−090
2
49L25
42,000 41,500 26,400 14.00 12.00 8.20 7.50 3500 3315 3010 3.66 2.56 CX34−49C−6F
4
G71MPP−36C−0902 49L25
42,500 41,000 26,200 14.50 12.00 8.50 7.70 3540 3250 2945 3.70 2.60 CX34−49C−6F
4
G60UHV−60C−110
2
49L25
42,500 41,000 26,200 15.00 13.00 9.00 7.70 3400 3160 2875 3.80 2.66 CX34−62D−6F
4
G60UHV−60D−135
2
49L25
42,500 41,500 26,200 14.50 12.00 8.50 7.70 3540 3195 2920 3.80 2.62 CX34−60D−6F
4
G61MPV−60D−135
2
49L25
42,500 41,500 26,200 14.50 12.00 8.50 7.70 3540 3195 2920 3.80 2.62 CX34−60D−6F
4
G71MPP−60D−1352 49L25
42,500 41,500 26,200 15.00 13.00 9.00 7.70 3400 3190 2915 3.82 2.64 CX34−62D−6F
4
G61MPV−60D−135
2
49L25
42,500 41,500 26,200 15.00 13.00 9.00 7.70 3400 3190 2915 3.82 2.64 CX34−62D−6F
4
G71MPP−60D−1352 49L25
42,500 41,500 26,200 14.50 12.00 8.20 7.50 3540 3265 2960 3.72 2.60 CX34−49C−6F
4
G61MPV−60C−110
2
49L25
42,500 41,500 26,200 14.50 12.00 8.20 7.50 3540 3265 2960 3.72 2.60 CX34−49C−6F
4
G71MPP−60C−1102 49L25
42,500 41,500 26,200 14.50 12.00 8.20 7.50 3540 3275 2970 3.72 2.58 CX34−49C−6F
4
G61MPV−60C−111
2
49L25
42,500 41,500 26,400 14.50 12.00 8.50 7.70 3540 3180 2885 3.82 2.68 CX34−62C−6F
4
G61MPV−60C−091
2
49L25
43,000 41,500 26,200 15.00 13.00 9.00 8.00 3440 3105 2810 3.92 2.74 CX34−62C−6F
4
G60UHV−60C−090
2
49L25
43,000 41,500 26,400 15.00 13.00 9.00 7.70 3440 3130 2840 3.88 2.72 CX34−62C−6F
4
G60UHV−60C−110
2
49L25
43,000 42,000 26,600 15.00 12.50 8.50 8.00 3440 3150 2895 3.90 2.70 CX34−62C−6F
4
G61MPV−60C−111
2
49L25
43,000 42,000 26,600 15.00 12.50 8.50 8.00 3440 3140 2880 3.92 2.70 CX34−62C−6F
4
G61MPV−60C−110
2
49L25
43,000 42,000 26,600 15.00 12.50 8.50 8.00 3440 3140 2880 3.92 2.70 CX34−62C−6F
4
G71MPP−60C−1102 49L25
43,000 42,000 26,600 14.50 12.00 8.50 7.70 3585 3190 2905 3.86 2.68 CX34−62C−6F
4
G61MPV−36C−090
2
49L25
43,000 42,000 26,600 14.50 12.00 8.50 7.70 3585 3190 2905 3.86 2.68 CX34−62C−6F
4
G71MPP−36C−0902 49L25
43,000 42,000 26,400 14.50 12.00 8.50 7.70 3585 3160 2870 3.90 2.70 CX34−62C−6F
4
G61MPV−60C−090
2
49L25
43,000 42,000 26,400 14.50 12.00 8.50 7.70 3585 3160 2870 3.90 2.70 CX34−62C−6F
4
G71MPP−60C−0902 49L25
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Page 13
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 13
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA042H4 3.5 TON
Down−Flow Indoor Coils Down−Flow Coils
41,500 42,500 27,200 13.00 11 .0 0 7.70 6.70 3775 3340 3055 3.72 2.60
3
CR33−50/60C−F
2
49L25
41,500 42,500 27,200 13.00 11 .0 0 7.70 6.70 3775 3340 3055 3.72 2.60
3
CR33−60D−F
2
49L25
Down−Flow Indoor Coils + Furnaces Down−Flow Coils + Furnaces
41,500 41,500 26,200 14.50 12.00 8.50 8.00 3460 3100 2805 3.92 2.74 CR33−50/60C−F
4
G60DFV−60C−110
2
49L25
41,500 41,500 26,200 14.50 12.00 8.50 8.00 3460 3085 2790 3.94 2.74 CR33−60D−F
4
G60DFV−60D−135
2
49L25
41,500 41,500 26,400 14.00 12.00 8.50 7.70 3460 3170 2875 3.84 2.68 CR33−50/60C−F
4
G61MPV−60C−091
2
49L25
41,500 42,000 26,400 14.50 12.00 8.50 7.70 3460 3150 2860 3.90 2.70 CR33−50/60C−F
4
G61MPV−60C−090
2
49L25
41,500 42,000 26,400 14.50 12.00 8.50 7.70 3460 3150 2860 3.90 2.70 CR33−50/60C−F
4
G71MPP−60C−0902 49L25
41,500 42,000 26,600 14.00 12.00 8.50 7.70 3460 3180 2895 3.88 2.70 CR33−50/60C−F
4
G61MPV−36C−090
2
49L25
41,500 42,000 26,600 14.00 12.00 8.50 7.70 3460 3180 2895 3.88 2.70 CR33−50/60C−F
4
G71MPP−36C−0902 49L25
42,000 41,500 26,200 14.50 12.00 8.50 8.00 3500 3080 2795 3.94 2.74 CR33−50/60C−F
4
G60DFV−60C−090
2
49L25
42,000 41,500 26,400 14.50 12.00 8.50 8.00 3500 3095 2815 3.92 2.74 CR33−60D−F
4
G61MPV−60D−135
2
49L25
42,000 41,500 26,400 14.50 12.00 8.50 8.00 3500 3095 2815 3.92 2.74 CR33−60D−F
4
G71MPP−60D−1352 49L25
42,000 42,000 26,400 14.50 12.00 8.50 8.00 3500 3125 2845 3.94 2.72 CR33−50/60C−F
4
G61MPV−60C−110
2
49L25
42,000 42,000 26,400 14.50 12.00 8.50 8.00 3500 3125 2845 3.94 2.72 CR33−50/60C−F
4
G71MPP−60C−1102 49L25
42,000 42,000 26,600 14.50 12.00 8.50 8.00 3500 3140 2860 3.92 2.72 CR33−50/60C−F
4
G61MPV−60C−111
2
49L25
Horizontal Indoor Coils Horizontal Coils
41,500 42,000 26,800 13.00 11 .0 0 7.70 6.70 3775 3485 3165 3.54 2.48
3
CH33−43C−2F
2
49L25
41,500 42,000 26,800 13.00 11 .0 0 7.70 6.70 3775 3460 3145 3.56 2.50
3
CH33−60D−2F
2
49L25
41,500 42,000 27,000 13.00 11 .0 0 7.70 6.70 3775 3470 3145 3.54 2.52
3
CH33−62D−2F
2
49L25
42,000 42,000 27,000 13.00 11 .0 0 7.70 6.70 3820 3420 3120 3.60 2.54
3
CH33−50/60C−2F
2
49L25
42,000 42,500 27,200 13.00 11 .0 0 7.70 6.70 3820 3275 3025 3.80 2.64
3
CH23−68
2
49L25
42,000 42,500 27,000 13.00 11 .0 0 7.70 6.70 3820 3395 3095 3.66 2.56
3
CH33−43B−2F
2
49L25
Horizontal Indoor Coils + Furnaces Horizontal Coils + Furnaces
42,000 41,000 25,800 15.00 13.00 9.00 7.70 3360 3185 2865 3.78 2.64 CH33−60D−2F
4
G60UHV−60D−135
2
49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3215 2905 3.74 2.62 CH33−60D−2F
4
G61MPV−60D−135
2
49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3215 2905 3.74 2.62 CH33−60D−2F
4
G71MPP−60D−1352 49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3230 2905 3.72 2.62 CH33−62D−2F
4
G61MPV−60D−135
2
49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3230 2905 3.72 2.62 CH33−62D−2F
4
G71MPP−60D−1352 49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3240 2910 3.70 2.62 CH33−43C−2F
4
G60UHV−60C−090
2
49L25
42,000 41,000 26,000 14.50 12.00 8.20 7.50 3500 3260 2950 3.68 2.58 CH33−43C−2F
4
G60UHV−60C−110
2
49L25
42,000 41,000 26,000 15.00 13.00 9.00 7.70 3360 3200 2870 3.76 2.66 CH33−62D−2F
4
G60UHV−60D−135
2
49L25
42,000 41,000 26,200 14.50 12.00 8.20 7.50 3500 3300 2970 3.64 2.58 CH33−43C−2F
4
G61MPV−60C−090
2
49L25
42,000 41,000 26,200 14.50 12.00 8.20 7.50 3500 3300 2970 3.64 2.58 CH33−43C−2F
4
G71MPP−60C−0902 49L25
42,000 41,000 26,200 14.50 12.00 8.20 7.50 3500 3320 2980 3.62 2.58 CH33−43C−2F
4
G61MPV−60C−091
2
49L25
42,000 41,500 26,200 14.00 12.00 8.20 7.50 3500 3325 3000 3.66 2.56 CH33−43C−2F
4
G61MPV−36C−090
2
49L25
42,000 41,500 26,200 14.00 12.00 8.20 7.50 3500 3325 3000 3.66 2.56 CH33−43C−2F
4
G71MPP−36C−0902 49L25
42,000 41,500 26,200 14.00 12.00 8.20 7.50 3500 3330 3010 3.66 2.54 CH33−48C−2F
4
G61MPV−60C−110
2
49L25
Horizontal Indoor Coils + Furnaces Continued on Next Page
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
Page 14
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 14
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA042H4 3.5 TON
Horizontal Indoor Coils + Furnaces Continued from Previous Page
42,000 41,500 26,200 14.00 12.00 8.20 7.50 3500 3330 3010 3.66 2.54 CH33−48C−2F
4
G71MPP−60C−1102 49L25
42,000 41,500 26,200 14.50 12.00 8.20 7.50 3500 3285 2965 3.70 2.58 CH33−43C−2F
4
G61MPV−60C−111
2
49L25
42,000 41,500 26,200 14.50 12.00 8.20 7.50 3500 3210 2905 3.78 2.64 CH33−50/60C−2F
4
G60UHV−60C−090
2
49L25
42,000 41,500 26,400 14.00 12.00 8.20 7.50 3500 3285 2970 3.70 2.60 CH33−50/60C−2F
4
G61MPV−60C−091
2
49L25
42,000 41,500 26,400 14.50 12.00 8.20 7.50 3500 3260 2960 3.74 2.62 CH33−50/60C−2F
4
G61MPV−60C−090
2
49L25
42,000 41,500 26,400 14.50 12.00 8.20 7.50 3500 3260 2960 3.74 2.62 CH33−50/60C−2F
4
G71MPP−60C−0902 49L25
42,000 41,500 26,600 14.00 12.00 8.20 7.50 3500 3305 2995 3.68 2.60 CH33−50/60C−2F
4
G61MPV−36C−090
2
49L25
42,000 41,500 26,600 14.00 12.00 8.20 7.50 3500 3305 2995 3.68 2.60 CH33−50/60C−2F
4
G71MPP−36C−0902 49L25
42,000 42,000 26,600 14.50 12.00 8.50 8.00 3500 3105 2845 3.96 2.74 CH23−68
4
G61MPV−60C−091
2
49L25
42,000 42,000 26,800 14.00 11 .5 0 8.20 7.50 3650 3385 3065 3.64 2.56 CH33−43B−2F
4
G61MPV−36B−045
2
49L25
42,500 41,500 26,400 14.50 12.00 8.50 7.70 3540 3225 2925 3.78 2.64 CH33−43B−2F
4
G60UHV−36B−090
2
49L25
42,500 41,500 26,400 14.50 12.00 8.20 7.50 3540 3245 2930 3.74 2.64 CH33−50/60C−2F
4
G60UHV−60C−110
2
49L25
42,500 41,500 26,400 14.50 12.00 8.20 7.50 3540 3255 2945 3.74 2.62 CH33−50/60C−2F
4
G61MPV−60C−110
2
49L25
42,500 41,500 26,400 14.50 12.00 8.20 7.50 3540 3255 2945 3.74 2.62 CH33−50/60C−2F
4
G71MPP−60C−1102 49L25
42,500 41,500 26,400 14.50 12.00 8.20 7.50 3540 3265 2955 3.72 2.62 CH33−50/60C−2F
4
G61MPV−60C−111
2
49L25
42,500 42,000 26,400 14.50 12.00 8.50 8.00 3540 3050 2800 4.04 2.76 CH23−68
4
G60UHV−60C−110
2
49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3115 2865 3.96 2.72 CH23−68
4
G61MPV−36C−090
2
49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3115 2865 3.96 2.72 CH23−68
4
G71MPP−36C−0902 49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3085 2830 4.00 2.76 CH23−68
4
G61MPV−60C−090
2
49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3085 2830 4.00 2.76 CH23−68
4
G71MPP−60C−0902 49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3065 2815 4.02 2.76 CH23−68
4
G61MPV−60C−110
2
49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3065 2815 4.02 2.76 CH23−68
4
G71MPP−60C−1102 49L25
42,500 42,000 26,600 14.50 12.00 8.50 8.00 3540 3075 2825 4.00 2.76 CH23−68
4
G61MPV−60C−111
2
49L25
42,500 42,000 27,000 14.00 11 .5 0 8.20 7.50 3695 3365 3065 3.66 2.58 CH33−43B−2F
4
G61MPV−36B−070
2
49L25
42,500 42,000 27,000 14.00 11.5 0 8.20 7.50 3695 3365 3065 3.66 2.58 CH33−43B−2F
4
G71MPP−36B−0702 49L25
42,500 42,000 27,000 14.00 11 .5 0 8.20 7.50 3695 3365 3065 3.66 2.58 CH33−43B−2F
4
G61MPV−36B−071
2
49L25
TPA048H4 4 TON
Air Handlers Air Handlers
48,500 46,500 30,000 14.00 12.00 8.50 7.20 4040 3765 3465 3.62 2.54
4
CBX32MV−060 (Multi−Position) Factory TXV
48,500 46,500 29,800 14.50 12.00 8.50 7.20 4040 3830 3505 3.56 2.48
4
CBX32MV−068 (Multi−Position) Factory TXV
48,500 47,000 29,200 15.00 12.50 8.50 7.20 3880 3930 3540 3.50 2.42
4
CBX27UH−048 (Up−Flow / Horizontal) Factory TXV
49,000 47,000 30,200 14.00 12.00 8.20 7.20 4085 3820 3505 3.60 2.52
5
CBX26UH−048 (Up−Flow / Horizontal) Factory TXV
Up−Flow Indoor Coils Up−Flow Coils
48,500 47,000 30,400 13.00 11 .0 0 7.70 6.70 4410 3995 3675 3.44 2.42
3
CX34−49C−6F Factory TXV
48,500 47,000 30,400 13.00 11 .0 0 7.70 6.70 4410 3975 3660 3.46 2.44
3
CX34−60D−6F Factory TXV
48,500 47,000 30,400 13.00 11 .0 0 7.70 6.70 4410 3945 3625 3.50 2.46
3
CX34−62D−6F Factory TXV
49,500 47,500 30,600 13.00 11 .0 0 7.70 6.70 4500 3850 3555 3.62 2.52
3
CX34−62C−6F Factory TXV
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Page 15
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 15
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA048H4 4 TON
Up−Flow Indoor Coils + Furnaces Up−Flow Coils + Furnaces
49,000 46,000 29,600 14.50 12.00 8.20 7.20 4085 3805 3475 3.54 2.50 CX34−60D−6F
4
G60UHV−60D−135 Factory TXV
49,000 46,000 29,800 14.50 12.00 8.20 7.20 4085 3835 3520 3.52 2.48 CX34−60D−6F
4
G61MPV−60D−135 Factory TXV
49,000 46,000 29,800 14.50 12.00 8.20 7.20 4085 3835 3520 3.52 2.48 CX34−60D−6F
4
G71MPP−60D−135 Factory TXV
49,000 46,500 29,800 14.00 12.00 8.20 7.20 4085 3835 3520 3.56 2.48 CX34−49C−6F
4
G60UHV−60C−110 Factory TXV
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CX34−49C−6F
4
G61MPV−60C−090 Factory TXV
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CX34−49C−6F
4
G71MPP−60C−090 Factory TXV
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CX34−49C−6F
4
G61MPV−60C−110 Factory TXV
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CX34−49C−6F
4
G71MPP−60C−110 Factory TXV
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.46 CX34−49C−6F
4
G61MPV−60C−111 Factory TXV
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3920 3610 3.48 2.44 CX34−49C−6F
4
G61MPV−60C−091 Factory TXV
49,500 46,000 29,600 14.50 12.00 8.20 7.20 4125 3765 3440 3.58 2.52 CX34−62D−6F
4
G60UHV−60D−135 Factory TXV
49,500 46,500 29,800 14.50 12.00 8.20 7.20 4125 3820 3510 3.56 2.48 CX34−49C−6F
4
G60UHV−60C−090 Factory TXV
49,500 46,500 29,800 14.50 12.00 8.20 7.20 4125 3805 3485 3.58 2.50 CX34−62D−6F
4
G61MPV−60D−135 Factory TXV
49,500 46,500 29,800 14.50 12.00 8.20 7.20 4125 3805 3485 3.58 2.50 CX34−62D−6F
4
G71MPP−60D−135 Factory TXV
50,000 47,000 30,000 14.50 12.00 8.20 7.20 4165 3690 3395 3.74 2.58 CX34−62C−6F
4
G60UHV−60C−110 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3690 3400 3.74 2.60 CX34−62C−6F
4
G60UHV−60C−090 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3735 3445 3.68 2.56 CX34−62C−6F
4
G61MPV−60C−090 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3735 3445 3.68 2.56 CX34−62C−6F
4
G71MPP−60C−090 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3725 3435 3.70 2.58 CX34−62C−6F
4
G61MPV−60C−110 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3725 3435 3.70 2.58 CX34−62C−6F
4
G71MPP−60C−110 Factory TXV
50,000 47,000 30,200 14.50 12.00 8.20 7.20 4165 3730 3440 3.70 2.58 CX34−62C−6F
4
G61MPV−60C−111 Factory TXV
50,000 47,500 30,400 14.00 12.00 8.20 7.20 4165 3775 3490 3.68 2.56 CX34−62C−6F
4
G61MPV−60C−091 Factory TXV
Down−Flow Indoor Coils Down−Flow Coils
47,500 47,500 30,600 13.00 11 .0 0 7.70 6.70 4320 3855 3555 3.62 2.52
3
CR33−50/60C−F
2
91M02
47,500 47,500 30,600 13.00 11 .0 0 7.70 6.70 4320 3855 3555 3.62 2.52
3
CR33−60D−F
2
91M02
Down−Flow Indoor Coils + Furnaces Down−Flow Coils + Furnaces
48,000 46,500 29,800 14.50 12.00 8.20 7.20 4000 3665 3345 3.72 2.60 CR33−60D−F
4
G60DFV−60D−135
2
91M02
48,000 46,500 30,000 14.00 12.00 8.20 7.20 4000 3665 3355 3.72 2.62 CR33−50/60C−F
4
G60DFV−60C−090
2
91M02
48,000 47,000 30,200 14.00 12.00 8.20 7.20 4000 3745 3445 3.68 2.56 CR33−50/60C−F
4
G61MPV−60C−090
2
91M02
48,000 47,000 30,200 14.00 12.00 8.20 7.20 4000 3745 3445 3.68 2.56 CR33−50/60C−F
4
G71MPP−60C−0902 91M02
48,000 47,000 30,200 14.00 12.00 8.20 7.20 4000 3735 3435 3.68 2.58 CR33−50/60C−F
4
G61MPV−60C−110
2
91M02
48,000 47,000 30,200 14.00 12.00 8.20 7.20 4000 3735 3435 3.68 2.58 CR33−50/60C−F
4
G71MPP−60C−1102 91M02
48,000 47,000 30,200 14.00 12.00 8.20 7.20 4000 3740 3440 3.68 2.58 CR33−50/60C−F
4
G61MPV−60C−111
2
91M02
48,000 47,000 30,400 13.00 11 .0 0 7.70 7.00 4365 3785 3490 3.64 2.56 CR33−50/60C−F
4
G61MPV−60C−091
2
91M02
48,500 47,000 30,200 14.00 12.00 8.20 7.20 4040 3680 3385 3.74 2.62 CR33−50/60C−F
4
G60DFV−60C−110
2
91M02
48,500 47,000 30,000 14.00 12.00 8.20 7.20 4040 3690 3385 3.74 2.60 CR33−60D−F
4
G61MPV−60D−135
2
91M02
48,500 47,000 30,000 14.00 12.00 8.20 7.20 4040 3690 3385 3.74 2.60 CR33−60D−F
4
G71MPP−60D−1352 91M02
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
Page 16
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 16
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA048H4 4 TON
Horizontal Indoor Coils Horizontal Coils
48,000 46,500 30,400 13.00 11 .0 0 7.70 6.70 4365 4005 3675 3.40 2.42
3
CH33−60D−2F
2
91M02
48,500 47,000 30,400 13.00 11 .0 0 7.70 6.70 4410 3995 3655 3.44 2.44
3
CH33−62D−2F
2
91M02
48,500 47,000 30,400 13.00 11 .0 0 7.70 6.70 4410 3965 3645 3.48 2.44
3
CH33−50/60C−2F
2
91M02
49,000 48,000 30,800 13.00 11 .0 0 7.70 6.70 4455 3775 3510 3.72 2.56
3
CH23−68
2
91M02
Horizontal Indoor Coils + Furnaces Horizontal Coils + Furnaces
48,500 46,000 29,600 14.50 12.00 8.20 7.20 4040 3800 3465 3.54 2.50 CH33−60D−2F
4
G60UHV−60D−135
2
91M02
48,500 46,000 29,800 14.00 12.00 8.20 7.20 4040 3835 3505 3.52 2.48 CH33−60D−2F
4
G61MPV−60D−135
2
91M02
48,500 46,000 29,800 14.00 12.00 8.20 7.20 4040 3835 3505 3.52 2.48 CH33−60D−2F
4
G71MPP−60D−1352 91M02
49,000 46,000 29,600 14.50 12.00 8.20 7.20 4085 3790 3445 3.56 2.52 CH33−62D−2F
4
G60UHV−60D−135
2
91M02
49,000 46,000 29,800 14.00 12.00 8.20 7.20 4085 3825 3485 3.52 2.50 CH33−62D−2F
4
G61MPV−60D−135
2
91M02
49,000 46,000 29,800 14.00 12.00 8.20 7.20 4085 3825 3485 3.52 2.50 CH33−62D−2F
4
G71MPP−60D−1352 91M02
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3820 3505 3.56 2.50 CH33−50/60C−2F
4
G60UHV−60C−090
2
91M02
49,000 46,500 30,000 14.00 12.00 8.20 7.20 4085 3840 3520 3.54 2.50 CH33−50/60C−2F
4
G60UHV−60C−110
2
91M02
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F
4
G61MPV−60C−090
2
91M02
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F
4
G71MPP−60C−0902 91M02
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CH33−50/60C−2F
4
G61MPV−60C−110
2
91M02
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3875 3555 3.52 2.48 CH33−50/60C−2F
4
G71MPP−60C−1102 91M02
49,000 46,500 30,200 14.00 12.00 8.20 7.20 4085 3880 3560 3.52 2.48 CH33−50/60C−2F
4
G61MPV−60C−111
2
91M02
49,000 47,000 30,400 14.00 12.00 8.20 7.20 4085 3915 3600 3.52 2.48 CH33−50/60C−2F
4
G61MPV−60C−091
2
91M02
49,500 47,000 30,000 14.50 12.00 8.20 7.20 4125 3565 3315 3.86 2.66 CH23−68
4
G60UHV−60C−090
2
91M02
49,500 47,000 30,000 14.50 12.00 8.20 7.20 4125 3585 3320 3.84 2.64 CH23−68
4
G60UHV−60C−110
2
91M02
49,500 47,000 30,000 14.50 12.00 8.20 7.20 4125 3575 3310 3.86 2.66 CH23−68
4
G61MPV−60D−135
2
91M02
49,500 47,000 30,000 14.50 12.00 8.20 7.20 4125 3575 3310 3.86 2.66 CH23−68
4
G71MPP−60D−1352 91M02
49,500 47,000 30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.80 2.64 CH23−68
4
G61MPV−60C−090
2
91M02
49,500 47,000 30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.80 2.64 CH23−68
4
G71MPP−60C−0902 91M02
49,500 47,000 30,200 14.50 12.00 8.20 7.20 4125 3610 3345 3.82 2.64 CH23−68
4
G61MPV−60C−110
2
91M02
49,500 47,000 30,200 14.50 12.00 8.20 7.20 4125 3610 3345 3.82 2.64 CH23−68
4
G71MPP−60C−1102 91M02
49,500 47,500 30,200 14.50 12.00 8.20 7.20 4125 3625 3360 3.84 2.64 CH23−68
4
G61MPV−60C−111
2
91M02
49,500 47,500 30,400 14.00 12.00 8.20 7.20 4125 3665 3410 3.80 2.62 CH23−68
4
G61MPV−60C−091
2
91M02
50,000 47,000 29,800 15.00 13.00 9.00 7.50 3845 3530 3290 3.90 2.66 CH23−68
4
G60UHV−60D−135
2
91M02
TPA060H4 5 TON
Air Handlers Air Handlers
56,000 55,000 35,600 14.00 11 .5 0 8.20 7.50 4870 4640 4135 3.48 2.52
4
CBX32MV−048 (Multi−Position) Factory TXV
56,500 54,500 35,400 14.00 11 .5 0 8.20 7.20 4915 4840 4305 3.30 2.40
4
CBX32MV−068 (Multi−Position) Factory TXV
56,500 55,000 35,800 14.00 11 .5 0 8.20 7.50 4915 4665 4195 3.46 2.50
4
CBX32M−060 (Multi−Position) Factory TXV
56,500 55,000 35,800 14.00 11 .5 0 8.20 7.50 4915 4680 4215 3.44 2.48
4
CBX32MV−060 (Multi−Position) Factory TXV
58,500 55,000 35,800 14.00 12.00 8.20 7.50 4875 4610 4120 3.50 2.545 CBX26UH−060 (Up−Flow / Horizontal) Factory TXV
59,000 55,500 36,000 15.00 12.50 8.50 7.70 4720 4585 4055 3.54 2.60
4
CBX27UH−060 (Up−Flow / Horizontal) Factory TXV
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Page 17
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 17
ARI RATINGS
1
ARI Standard 210/240 Ratings
Capacity − Btuh Efficiency Tota l Wat ts COP
High
Low
HSPF
High Low High Low
Indoor Unit Model No.
Expansion
Device
Cooli
ng
Tem p.
Heating
Tem p.
Heating
SEER EER IV V
Cool
High
Heat
Low
Heat
High
Heat
Low
Heat
TPA060H4 5 TON
Up−Flow Indoor Coils Up−Flow Coils
57,000 54,500 35,800 13.00 11 .0 0 7.70 6.70 5180 4955 4415 3.22 2.38
3
CX34−62D−6F Factory TXV
58,500 55,000 36,000 13.00 11 .0 0 7.70 6.70 5320 4850 4325 3.32 2.44
3
CX34−62C−6F Factory TXV
Up−Flow Indoor Coils + Furnaces Up−Flow Coils + Furnaces
57,500 54,000 35,200 14.00 11 .5 0 8.20 7.20 5000 4820 4270 3.28 2.42 CX34−62D−6F
4
G61MPV−60D−135 Factory TXV
57,500 54,000 35,200 14.00 11.5 0 8.20 7.20 5000 4820 4270 3.28 2.42 CX34−62D−6F
4
G71MPP−60D−135 Factory TXV
58,000 54,500 35,800 14.00 11 .5 0 8.20 7.50 5045 4835 4295 3.30 2.44 CX34−62C−6F
4
G61MPV−60C−090 Factory TXV
58,000 54,500 35,800 14.00 11.5 0 8.20 7.50 5045 4835 4295 3.30 2.44 CX34−62C−6F
4
G71MPP−60C−090 Factory TXV
58,000 55,000 36,000 14.00 11 .5 0 8.20 7.20 5045 4885 4355 3.30 2.42 CX34−62C−6F
4
G61MPV−60C−091 Factory TXV
58,500 54,500 35,400 14.50 12.00 8.20 7.20 4875 4725 4240 3.38 2.44 CX34−62D−6F
4
G60UHV−60D−135 Factory TXV
58,500 54,500 35,600 14.00 11 .5 0 8.20 7.50 5085 4750 4220 3.36 2.48 CX34−62C−6F
4
G60UHV−60C−090 Factory TXV
58,500 54,500 35,600 14.00 11 .5 0 8.20 7.50 5085 4765 4235 3.36 2.46 CX34−62C−6F
4
G60UHV−60C−110 Factory TXV
58,500 54,500 35,800 14.00 11 .5 0 8.20 7.50 5085 4800 4270 3.32 2.46 CX34−62C−6F
4
G61MPV−60C−110 Factory TXV
58,500 54,500 35,800 14.00 11.5 0 8.20 7.50 5085 4800 4270 3.32 2.46 CX34−62C−6F
4
G71MPP−60C−110 Factory TXV
58,500 55,000 35,800 14.00 11 .5 0 8.20 7.50 5085 4815 4290 3.34 2.44 CX34−62C−6F
4
G61MPV−60C−111 Factory TXV
Horizontal Indoor Coils Horizontal Coils
56,500 54,500 35,600 13.00 11 .0 0 7.70 6.70 5135 5005 4465 3.20 2.34
3
CH33−62D−2F
2
91M02
57,000 54,500 35,800 13.00 11 .0 0 7.70 6.70 5180 4965 4405 3.22 2.38
3
CH33−50/60C−2F
2
91M02
57,500 55,500 36,200 13.00 11 .0 0 7.70 6.70 5225 4615 4180 3.52 2.54
3
CH23−68
2
91M02
Horizontal Indoor Coils + Furnaces Horizontal Coils + Furnaces
56,500 54,500 35,800 13.50 11 .0 0 8.20 7.20 5135 4985 4405 3.20 2.38 CH33−50/60C−2F
4
G61MPV−60C−090
2
91M02
56,500 54,500 35,800 13.50 11.0 0 8.20 7.20 5135 4985 4405 3.20 2.38 CH33−50/60C−2F
4
G71MPP−60C−0902 91M02
57,000 54,500 35,600 14.00 11 .5 0 8.20 7.20 4955 4900 4340 3.26 2.40 CH33−50/60C−2F
4
G60UHV−60C−090
2
91M02
57,000 54,500 35,600 14.00 11 .5 0 8.20 7.20 4955 4920 4350 3.24 2.40 CH33−50/60C−2F
4
G60UHV−60C−110
2
91M02
57,000 54,500 35,800 13.50 11 .0 0 8.20 7.20 5180 4950 4385 3.22 2.40 CH33−50/60C−2F
4
G61MPV−60C−110
2
91M02
57,000 54,500 35,800 13.50 11.0 0 8.20 7.20 5180 4950 4385 3.22 2.40 CH33−50/60C−2F
4
G71MPP−60C−1102 91M02
57,000 54,500 35,800 13.50 11 .0 0 8.20 7.20 5180 4960 4400 3.22 2.38 CH33−50/60C−2F
4
G61MPV−60C−111
2
91M02
57,500 54,500 35,800 14.00 11 .5 0 8.20 7.20 5000 4875 4375 3.28 2.40 CH33−62D−2F
4
G61MPV−60D−135
2
91M02
57,500 54,500 35,800 14.00 11.5 0 8.20 7.20 5000 4875 4375 3.28 2.40 CH33−62D−2F
4
G71MPP−60D−1352 91M02
57,000 54,500 36,000 13.50 11 .0 0 8.20 7.20 5180 5030 4465 3.18 2.36 CH33−50/60C−2F
4
G61MPV−60C−091
2
91M02
57,500 55,500 35,800 14.00 11 .5 0 8.20 7.50 5000 4560 4115 3.56 2.54 CH23−68
4
G61MPV−60C−090
2
91M02
57,500 55,500 35,800 14.00 11.5 0 8.20 7.50 5000 4560 4115 3.56 2.54 CH23−68
4
G71MPP−60C−0902 91M02
57,500 55,500 35,800 14.00 11 .5 0 8.20 7.50 5000 4535 4100 3.58 2.56 CH23−68
4
G61MPV−60C−110
2
91M02
57,500 55,500 35,800 14.00 11.5 0 8.20 7.50 5000 4535 4100 3.58 2.56 CH23−68
4
G71MPP−60C−1102 91M02
57,500 55,500 36,000 14.00 11 .5 0 8.20 7.50 5000 4620 4185 3.52 2.52 CH23−68
4
G61MPV−60C−091
2
91M02
57,500 55,500 36,000 14.00 11 .5 0 8.20 7.50 5000 4550 4115 3.58 2.56 CH23−68
4
G61MPV−60C−111
2
91M02
58,000 54,000 35,400 14.00 12.00 8.20 7.20 4835 4760 4265 3.32 2.44 CH33−62D−2F
4
G60UHV−60D−135
2
91M02
58,000 55,000 35,600 14.00 11 .5 0 8.20 7.70 5045 4475 4045 3.60 2.58 CH23−68
4
G60UHV−60C−090
2
91M02
58,000 55,000 35,600 14.00 12.00 8.20 7.50 4835 4475 4040 3.60 2.58 CH23−68
4
G61MPV−60D−135
2
91M02
58,000 55,000 35,600 14.00 12.00 8.20 7.50 4835 4475 4040 3.60 2.58 CH23−68
4
G71MPP−60D−1352 91M02
58,500 55,500 35,800 14.50 12.00 8.20 7.50 4875 4405 3995 3.70 2.62 CH23−68
4
G60UHV−60D−135
2
91M02
58,500 56,000 36,200 14.00 11 .5 0 8.20 7.50 5085 4525 4130 3.62 2.56 CH23−68
4
G60UHV−60C−110
2
91M02
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air. High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air. Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
Page 18
GUIDE SPECIFICATIONS
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 18
This specification specifies Lennox Industries TP outdoor heat pumps. Revise section number and title below to suit project requirements, specification practices and section content. Refer to CSI MasterFormat for other section numbers and titles.
Optional text and text that requires a decision are indicated by bold brackets [ ]; delete text not needed in final copy of specification. Specifier Notes typically precede specification text; delete notes in final copy of specification. Trade/brand names with appropriate symbols typically are used in Specifier Notes; symbols are not used in specification text. Metric conversion, where used, is soft metric conversion.
SECTION 23 81 43
AIR−SOURCE UNITARY HEAT PUMPS
PART 1 GENERAL
PART 1.01 SUMMARY
A. Section Includes: Outdoor Heat Pumps, including:
1. Cabinets.
2. Compressors.
3. Refrigerant systems.
4. Controls.
5. Refrigerant line connectors, electrical inlets and service valves.
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI MasterFormat and specifier’s practice.
Specifier Note: Article below may be omitted when specifying manufacturer’s proprietary products and recommended installation. Retain Reference Article when specifying products and installation by an industry reference standard. If retained, list standard(s) referenced in this section. Indicate issuing authority name, acronym, standard designation and title. Establish policy for indicating edition date of standard referenced. Conditions of the Contract or Division 01 References Section may establish the edition date of standards. This article does not require compliance with standard, but is merely a listing of references used. Article below should list only those industry standards referenced in this section. Retain only those reference standards to be used within the text of this Section. Add and delete as required for specific project.
PART 1.02 REFERENCES
A. Air−Conditioning and Refrigeration Institute (ARI):
1. ARI 210/240 – 1994, Unitary Air−Conditioning and Air−Source Heat Pump Equipment.
2. ARI 270 – 1995, Sound Rating of Outdoor Unitary Equipment.
B. Servicing Standards:
1. National Electric Code (NEC).
2. Underwriter’s Laboratories (UL)
3. Canadian Electric Code(CEC)
C. Department of Energy (DOE), units rated to
D. ISO 9001, units manufactured to quality standard.
Specifier Note: Article below should be restricted to statements describing design or performance requirements and functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and operational properties required to link components of a system together and to interface with other systems.
Page 19
GUIDE SPECIFICATIONS
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 19
PART 1.03 SYSTEM DESCRIPTION
A. Performance Requirements:
Specifier Note: Refer to Lennox Engineering Handbook for specific heating and cooling capacities. Units using R22 refrigerant are available in 3, 4 and 5 ton models. Units using R410−a refrigerant are available in 3, 3.5, 4 and 5 ton models. Cooling capacities vary from 34,400 to 57,500 Btuh.
1. 3, [3.5], 4 and 5 ton capacity.
2. Electrical Characteristics:
a. 60 hz.
b. 3−phase.
c. [208/230 V] [460 V].
Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or after construction. Coordinate this article with Architect’s and Contractor’s duties and responsibilities in Conditions of the Contract and Division 01 Submittal Procedures Section.
PART 1.04 SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of the Contract and Division 01 Submittal Procedures.
B. Product Data: Submit product data for specified products.
C. Shop Drawings:
1. Submit shop drawings in accordance with Section [01 33 00 − Submittal Procedures] [______].
2. Indicate:
a. Equipment, piping and connections, together with valves, strainers, control assemblies, thermostatic controls,
auxiliaries and hardware, and recommended ancillaries that are mounted, wired and piped ready for final connection to building system, its size and recommended bypass connections.
b. Piping, valves and fittings shipped loose showing final location in assembly.
c. Control equipment shipped loose, showing final location in assembly.
d. Field wiring diagrams.
e. Dimensions, internal and external construction details, installation clearances, recommended method of
installation, sizes and location of mounting bolt holes.
f. Detailed composite wiring diagrams for control systems showing factory installed wiring and equipment on split
systems or required for controlling devices or ancillaries, accessories, controllers.
D. Quality Assurance:
1. Test Reports: Certified test reports showing compliance with specified performance characteristics and physical properties.
2. Certificates: Product certificates signed by manufacturer certifying materials comply with specified performance characteristics and criteria and physical requirements.
3. Manufacturer’s Instructions: Manufacturer’s installation instructions.
Specifier Note: Coordinate paragraph below with Part 3 Field Quality Requirements Article. Retain or delete as applicable.
E. Manufacturer’s Field Reports: Manufacturer’s field reports specified.
F. Closeout Submittals: Submit the following:
1. Warranty: Warranty documents specified.
2. Operation and Maintenance Data: Operation and maintenance data for installed products in accordance with Division 01 Closeout Submittals (Maintenance Data and Operation Data) Section. Include methods for maintaining installed products and precautions against cleaning materials and methods detrimental to finishes and performance. Include names and addresses of spare part suppliers.
3. Provide brief description of unit, with details of function, operation, control and component service.
4. Commissioning Report: Submit commissioning reports, report forms and schematics in accordance with Section [01 91 00 − Commissioning] [______].
Page 20
GUIDE SPECIFICATIONS
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 20
PART 1.05 QUALITY ASSURANCE
A. Qualifications:
1. Installer experienced in performing work of this section who has specialized in installation of work similar to that required for this project.
2. Manufacturer Qualifications: Manufacturer capable of providing field service representation during construction and approving application method.
B. Preinstallation Meetings: Conduct preinstallation meeting to verify project requirements, manufacturer’s installation
instructions and manufacturer’s warranty requirements. Comply with Division 01 Project Management and Coordination (Project Meetings).
PART 1.06 DELIVERY, STORAGE & HANDLING
A. General: Comply with Section [01 61 00 − Common Product Requirements] [______].
B. Ordering: Comply with manufacturer’s ordering instructions and lead time requirements to avoid construction delays.
C. Packing, Shipping, Handling and Delivery:
1. Deliver materials in manufacturer’s original, unopened, undamaged containers with identification labels intact.
2. Ship, handle and unload units according to manufacturer’s instructions.
D. Storage and Protection:
1. Store materials protected from exposure to harmful weather conditions.
2. Factory shipping covers to remain in place until installation.
Specifier Note: Include or remove following section as project dictates.
E. Waste Management and Disposal:
Specifier Note: ENVIRONMENT: The disposal of packaging waste into landfill site demonstrates an inefficient use of natural resources and consumes valuable landfill space.
1. Separate waste materials for [Reuse] [And] [Recycling] [_____] in accordance with Section [01 74 19 − Construction Waste Management and Disposal] [_____].
2. Remove from site and dispose of packaging materials at appropriate recycling facilities.
3. Collect and separate for disposal [Paper] [Plastic] [Polystyrene] [Corrugated cardboard] [_____] packaging
material [In appropriate onsite bins] [_____] for recycling.
Specifier Note: Coordinate article below with Conditions of the Contract and with Division 01 Closeout Submittals (Warranty).
PART 1.07 WARRANTY
A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B. Manufacturer’s Warranty: Submit, for Owner’s acceptance, manufacturer’s standard warranty document executed by
authorized company official. Manufacturer’s warranty is in addition to, and not a limitation of, other rights Owner may have under Contract Documents.
Specifier Note: Coordinate paragraph below with manufacturer’s warranty requirements.
C. Warranty: Commencing on Date of Installation.
1. Compressor: Five years (limited).
2. Other Covered Components: One year (limited).
PART 2 PRODUCTS
Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance characteristics, material standards and descriptions as applicable. Use of such phrases as or equal" or or approved equal" or similar phrases may cause ambiguity in specifications. Such phrases require verification (procedural, legal and regulatory) and assignment of responsibility for determining or equal" products.
Page 21
GUIDE SPECIFICATIONS
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 21
PART 2.01 HEAT PUMP OUTDOOR UNITS/SPLIT SYSTEM UNITS
A. Manufacturer: Lennox Industries.
1. Contact: 2100 Lake Park Blvd., Richardson, TX 75080; Telephone: (800) 453−6669; website: www.lennox.com
.
B. Proprietary Products/Systems: TP, T−Class Split System Units, including the following equipment:
1. Cabinet:
a. Heavy gauge steel with 5 station metal wash preparation and powder paint finish.
b. Control box with controls factory wired.
c. Corner patch plate access to compressor components.
d. Base drainage holes for moisture removal.
e. [Accessories]:
1) [Hail Guards: Four−sided of louvered heavy gauge steel painted to match cabinet.]
2) [Mounting Base of high−density polyethylene structural material for permanent foundation of outdoor units.]
3) [Unit Stand−Off Kit consisting of 4 black polyethylene feet to raise unit off mounting surface.]
2. Compressor:
a. Scroll type.
b. Resiliently mounted on rubber mounts for vibration isolation.
c. Internal excessive current and temperature protection.
d. Crankcase heater.
e. [Accessories:]
1) [Low Ambient Cut−Off: nonadjustable switch to prevent compressor operation at outdoor temperatures below 35 degrees F (2 degrees C).]
2) [Compressor Sound Cover: Reinforced vinyl cover containing 1 1/2 inches (38 mm) thick fiberglass insulation batt.]
3) [Compressor Timed−Off Control: kit prevents short cycling.]
Specifier Note: Units using R22 refrigerant are available in 3, 4 and 5 ton models. Units using R410−a refrigerant are available in 3, 3.5, 4 and 5 ton models.
3. Refrigerant System:
a. Refrigerant: [R22] [R410−a]
b. Outdoor Coil Fan:
1) Direct drive fan.
2) Vertical discharge.
3) Totally enclosed fan motor with sleeve bearings.
4) Rain shield
5) Louvered steel top fan guard.
c. Copper Tube/Fin Coil:
1) Copper tube with flared shoulder connections and silver solder construction.
2) Lanced, ripple−edged aluminum fins.
3) PVC coated steel wire coil guard.
4) Coil is leak tested at factory.
5) Entire coil is accessible for cleaning.
d. Factory installed and piped outdoor unit expansion valve.
e. High Capacity Liquid Line Drier.
1) 100% molecular−sieve, bead type, bi−flow drier, factory installed in liquid line.
f. Factory installed, 4−way interchange reversing valve.
Page 22
GUIDE SPECIFICATIONS
TP − 3 to 5 Ton High−Efficiency, R−410A Heat Pump / Page 22
g. [Accessories:]
1) [High Pressure Switch Kit: manual reset for system protection from high pressure conditions resulting from fan failure or blocked/dirty coil.]
2) [Loss of Charge Kit : SPST, normally closed switch and automatic reset switch mounted on suction line.]
3) [Refrigerant Line Kits: Factory cleaned, dried, pressurized and sealed for field fabrication.]
4. Controls:
a. Defrost Control:
1) Solid−state temperature/time control.
2) Initiates defrost cycle every 30, 60 or 90 minutes of compressor on" time at temperatures below 42 degrees F (6 degrees C).
3) Anti−short cycle, timed−off control.
4) High and low pressure switch monitoring with 5 trip lockout.
b. [Accessories:]
1) [Freezestat: senses suction line temperature and cycles compressor off when suction line temperature falls below 29 degrees F (−2 degrees C) and cycles back on at 58 degrees F (14 degrees C).]
2) [Low Ambient Control: Available in 2 options based on ambient temperature; for field installation.]
3) [Mild Weather Kit for field installation to allow heating operation above 75 degrees F (24 degrees C).]
4) [Monitor Kit with ambient compensating thermistor and service light thermostat.]
5) [Outdoor Thermostat Kit to lock out some electric heating elements on indoor units where 2−stage control is applicable.]
6) [Thermostat.]
7) [Time Delay Relay Kit delays indoor blower−off time during cooling cycle.]
5. Refrigerant Line Connections, Electrical Inlets, Service Valves:
a. Sweat connection vapor and liquid lines located on cabinet corner.
b. Fully serviceable and accessible brass service valves.
c. Full shutoff Vapor valve.
d. Liquid valve can be front seated to manage refrigerant charge while servicing system.
PART 2.02 PRODUCT SUBSTITUTIONS
A. Substitutions: No substitutions permitted.
PART 3 EXECUTION
PART 3.01 MANUFACTURER’S INSTRUCTIONS
Specifier Note: Revise article below to suit project requirements and specifier’s practice.
A. Compliance: Comply with manufacturer’s written data, including product technical bulletins, product catalog installation
instructions and product carton installation instructions.
PART 3.02 EXAMINATION
A. Site Verification of Conditions: Verify that substrate conditions, which have been previously installed under other sections,
are acceptable for product installation in accordance with manufacturer’s instructions.
PART 3.03 INSTALLATION
A. Install heat pump in accordance with manufacturer’s instructions and regulations of authorities having jurisdiction.
END OF SECTION
Page 23
Page 24
Visit us at www.lennox.com For the latest technical information, www.lennoxcommercial.com Contact us at 1−800−4−LENNOX
NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
©2008 Lennox Industries Inc.