Lennox TPA036S2, TPA048S2, TPA060S2 User Manual

E N G I N E E R I N G D A T A
H E A T P U M P O U T D O O R U N I T S
TP
T−CLASSt SPLIT SYSTEM UNITS
R−22 − 60 HZ
Bulletin No. 210438
November 2007
Supersedes October 2007

MODEL NUMBER IDENTIFICATION

TPA Y1036 S 42 n
T = T−Classt Product Line
Brand/Family
P = Heat Pump Outdoor Unit
Major Design Sequence
Nominal Cooling Capacity − Tons
Unit Type
A = 1st Generation
B = 2nd Generation
036 = 3 Tons 048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
S = Standard Efficiency
3 to 5 Tons
Cooling Capacity − 34,000 to 57,500 Btuh
Heating Capacity − 33,600 to 55,500 Btuh
Vol ta ge
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Coil type
4 = Four−sided
Part Load Capability
N = No part load, single stage compressor
Refrigerant Type
2 = R−22

FEATURES

CONTENTS
ARI Rating Tables Pages 10 − 12. . . . . . . . . . . . . . . . . . . . .
Dimensions Page 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Data Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features Page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Coil / Air Handler Substitutions Page 9. . . . . . . . . .
Installation Clearances Page 7. . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification Page 1. . . . . . . . . . . . . . . . . .
Optional Accessories Page 6. . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
J
B
C
I
Warranty
Compressor − limited warranty for five years. All other covered components − one year.
Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.
Approvals
Certified in Accordance with the USE certification program, which is based on ARI Standard 210/240−2005. Sound rated in Lennox reverberant sound test room in Accordance with test conditions included in ARI Standard 270-95. Tested in the Lennox Research Laboratory environmental test room. Rated According to U.S. Department of Energy (DOE) test procedures. Units and components within bonded for grounding to meet safety standards for servicing required by UL, NEC and CEC. Units are UL and ULC listed. ISO 9001 Registered Manufacturing Quality System.
Applications
SEER up to 13.0. Heating COP up to 3.68. HSPF (Region IV) up to 7.70. 3 through 5 tons. Three−phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Designed for applications with remotely located indoor air handler units. See Air Handlers tab section for unit data. Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory insuring proper operation. Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job.
For expanded ratings, see www.lennoxdavenet.com.
H
D
E
G
F
REFRIGERANT SYSTEM
Outdoor Coil Fan
B
Direct drive fan moves large air volumes uniformly through entire outdoor coil for high refrigerant cooling and heating capacity. Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. Fan motor has sleeve bearings and is inherently protected. Motor totally enclosed for maximum protection from weather, dust and corrosion. Rain shield on motor provides additional protection from moisture. Louvered steel top fan guard furnished as standard. Fan service access accomplished by removal of top panel.
Copper Tube/Enhanced Fin Coil
C
Lennox designed and fabricated coil. Ripple-edged aluminum fins. Copper tube construction. Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer. Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction. Coil is factory tested under high pressure to ensure leakproof construction. Entire coil is accessible for cleaning. PVC coated steel wire coil guard furnished as standard.
D
K
TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units / Page 2
FEATURES
REFRIGERANT SYSTEM (CONTINUED)
Expansion Valve − Outdoor Unit
E
Designed and sized specifically for use in heat pump system. Sensing bulb is located on the suction line between the reversing valve and the compressor to sense evaporator suction temperature in any cycle. Factory installed and piped.
High Capacity Liquid Line Drier
F
Factory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system. 100% molecular−sieve, bead type bi−flow drier.
Reversing Valve
G
4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa. Valve operates on pressure differential between outdoor unit and indoor unit of the system. Factory installed.
OPTIONS
Check/Expansion Valve Kits
Must be ordered extra and field installed on certain indoor units. See ARI Ratings tables. Chatleff−style fitting.
High Pressure Switch Kit
Protects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil. Manual reset.
Loss of Charge Kit
Helps protect the compressor from damage due low refrigerant charge conditions. SPST, normally−closed switch, automatic reset switch mounted on suction line.
Refrigerant Line Kits
Refrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory. Suction line fully insulated. Lines are stubbed at both ends. Not available for −060 models and must be field fabricated.
Compressor
H
Copeland Scrollt Compressor
Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. Muffler in discharge line reduces operating sound levels. Compressor is installed in the unit on resilient rubber mounts for vibration free operation.
Compressor Crankcase Heater
Protects against refrigerant migration that can occur during low ambient operation.
OPTIONS
Compressor Low Ambient Cut−Off
Non-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F.
Compressor Sound Cover
A reinforced vinyl compressor cover containing a 1−1/2 inch thick batt of fiberglass insulation. All open edges are sealed with a one−inch wide hook and loop fastening tape.
TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units / Page 3
FEATURES
CONTROLS
Defrost Control
I
Solid-state time/temperature defrost control is furnished as standard equipment. Control initiates a defrost cycle every 30, 60 or 90 minutes of compressor on" time at outdoor coil temperatures below 42°F (factory setting 90 minutes). Anti−short cycle, timed−off control incorporated into the board. High and low pressure switch monitoring with five−trip lockout. Diagnostic LED’s furnished as an aid in troubleshooting. Conveniently located in control box.
OPTIONS
Freezestat
Installs on or near the vapor line of the indoor coil or on the suction line. Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint. Opens at 29°F and closes at 58°F.
L Connection
See L Connection Engineering Handbook Bulletin in Controls section for details.
Low Ambient Control
Air conditioners operate satisfactorily down to 45°F outdoor air temperature without any additional controls. Two low ambient control options are available for field installation. The Low Ambient Control Kit allows unit operation down to 30°F. The second control option allows unit operation down to 0°F. This option requires that the outdoor fan motor and capacitor be changed. See Low Ambient Control Option table, page 7, for ordering information. Freezestat should be installed on compressors equipped with a low ambient kit. A compressor lock−out thermostat should be added to terminate compressor operation below recommended operation conditions (on/off operation, 30°F or modulating operation, 0°F).
Mild Weather Kit
Heat pump units operate satisfactorily in the heating mode at outdoor air temperatures up to 75_F. Mild Weather Kit can be field installed, allowing heating operation above 75_F.
Monitor Kit − Service Light
Contains ambient compensating thermistor and service light thermostat. For use with thermostats requiring input for indicator lights.
Outdoor Thermostat Kit
An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable. Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line. Thermostat kit and mounting box must be ordered extra.
Thermostat
Thermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book.
®
Network
Time Delay Relay Kit
Delays the indoor blower−off time during the cooling cycle. See ARI Rating Tables for usage.
Cabinet
J
Heavy gauge steel cabinet with five station metal wash process. Powder paint finish provides superior rust and corrosion protection. Painted base section. Control box is conveniently located with all controls factory wired. Corner patch plate allows access to compressor components. Drainage holes are provided in base section for moisture removal.
Refrigerant Line Connections, Electrical Inlets,
K
Service Valves
Sweat connection vapor and liquid lines are located on corner of unit cabinet. Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.
OPTIONS
Hail Guards
Constructed of louvered heavy gauge steel painted to match cabinet. Surrounds unit on all four sides to prevent damage to the coil.
Mounting Base
Provides permanent foundation for outdoor units. High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot. Can be shipped singly or in packages of 6 to a carton.
Unit Stand-Off Kit
Black high density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture. Four feet are furnished per order number.
TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units / Page 4
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Compliant − E
NERGY STAR
Sensors For Touchscreen Thermostat
1
Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1
Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . . . . . . . . . . . . C0SNZN73AE1−
1
Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR03AE1−
Accessories For Touchscreen Thermostat
Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−
1
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4) C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.
DIGITAL NON−PROGRAMMABLE THERMOSTATS
Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control
Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L
Sensor For Digital Non−Programmable Thermostats Above
®
Qualified − Backlit Display − Automatic Changeover
C0STAT02AE1L
Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−
Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down Temperature Control
One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L
Sensor For Digital Non−Programmable Thermostats Above
Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR04AE1−
Accessories For Digital Non−Programmable Thermostats Above
Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC17AE1−
TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units / Page 5