Lennox THN 105, THN 073, THN056, THN 090, THN 120 Installation And Operating Manual

...
Page 1
INSTALLATION AND OPERATING MAINTENANCE MANUAL
TELECOOL THN
English January 2004
Page 2
CONTENTS
GENERAL DESCRIPTION 2
BASIC COOLANT CIRCUIT ....................................................................................... 3
INSTALLATION WARNINGS ...................................................................................... 4
INSPECTION 5
TRANSPORT .............................................................................................................. 5
UNPACKING............................................................................................................... 5
POSITIONING ............................................................................................................ 5
INSTALLATION 7
ELECTRICAL CONNECTIONS ................................................................................ 10
STARTING UP 11
PRELIMINARY CHECKS........................................................................................... 11
STARTING UP INSTRUCTIONS .............................................................................. 12
SETTING OPERATING PARAMETERS 15
GENERALITIES ........................................................................................................ 15
MAXIMUM PRESSURE SWITCH ............................................................................ 16
MINIMUM PRESSURE SWITCH .............................................................................. 16
ROUTINE MAINTENANCE AND CHECKS 17
WARNINGS .............................................................................................................. 17
GENERALITIES ........................................................................................................ 18
REPAIRING THE COOLING CIRCUIT ..................................................................... 20
TIGHTNESS TEST ................................................................................................... 21
HARD VACUUM AND DRYING OF COOLING CIRCUIT ......................................... 21
CHARGING WITH R407C REFRIGERANT ............................................................. 22
ENVIRONMENTAL PROTECTION ........................................................................... 22
TROUBLESHOOTING 23
TECHNICAL DATA 25
CONTENTS
Page 3
Page 2 - IOM / TELECOOL THN - 0104 - E
GENERAL DESCRIPTION
Structure
All THN units have a galvanised sheet steel supporting base, and enclosing panels made galvanised sheet steel coated with epoxy polyester powder paint oven cured at 180°C (RALxxxx). The unit features an exclusive design which, combined with a rational layout of components and extremely compact dimensions, lends it an attractive appearance.
Field of Application:
Model
Power supply
Minimum outdoor temperature T Maximum outdoor temperature T Minimum indoor temp./humidity conditions Maximum indoor temp./humidity conditions
Storage conditions
Cooling circuit
The entire cooling circuit is built in the HiRef factory using only components of the finest quality brands and processes conforming to the specifications of Directive 97/23 for brazing and testing.
Compressors: only scroll-type compressors of leading international manufacturers are used in the THN units. Today scroll compressors represent the best solution in terms of reliability, efficiency and MTBF.
Cooling components:
o Molecular mesh activated-alumina filter dryer o Flow indicator with humidity indicator.
Indications are provided directly on the sight glass.
o Thermostatic valve with external equalization
and integrated MOP function. o High and low pressure switches o Schrader valves for checks and/or
maintenance
Electric control board: The electric control board is constructed and wired in accordance with Directives 73/23/EEC and 89/336/EEC and related standards. The board may be accessed through a door after the main switch has been put off. All the remote controls use 24 V signals powered by an insulating transformer situated on the electric control board.
NOTE: the mechanical safety devices such as the high pressure switch are of the kind that trigger directly; their efficiency will not be affected by any faults occurring in the microprocessor control circuit, in compliance with 97/ 23 PED.
Control microprocessor: the microprocessor built into the unit allows the different operating parameters to be controlled from a set of pushbuttons situated on the electric control board;
o Switching on/off of compressor to maintain the
temperature set point T inside the shelter
o Alarm management
High / low pressure
Dirty filters alarmAir flow alarm
o Alarm signalling o Display of operating parameters o RS232, RS485 serial output management
(optional)
o Phase sequence error [Not displayed by the
mP, but prevents the compressor from starting up]
[see microprocessor control manual for further details, also in relation to particular customer specifications]
GENERAL DESCRIPTION
THN “HiRef Telecom units” are air conditioners for low- and medium-powered telephone exchanges. They are designed to be mounted inside shelter. THN air conditioners are direct expansion package units with an air-cooled condenser system. They are distinguished by an innovative air circulation system which significantly enhances performance in all operating conditions.
THN THN THN 045 056 073
230Vac+/-10%
24 Vdc +/- 16% - 48 Vdc +/- 16%
- 20 °C
45 °C 45 °C 45 °C
19 °C - 30 % r.h.
35 °C - 50 % r.h.
-10 / 90 % r.h.
+ 55 / 90 % r.h.
THN THN THN THN THN 090 105 120 150 170
400Vac+/-10% /3/50 + N
24 Vdc +/- 16% - 48 Vdc +/- 16%
- 20 °C
46 °C 45 °C 46 °C 46 °C 45 °C
19 °C - 30 % r.h.
35 °C - 50 % r.h.
-10 / 90 % r.h.
+ 55 / 90 % r.h.
THN units are to be used within the operating limits stated in this manual; failure to comply with said limits will invalidate the warranties provided in the contract of sale.
Page 4
GENERAL DESCRIPTION
BASIC COOLING CIRCUIT
ENGLISH
1 COMPRESSOR 2 CONDENSER 3 THERMOSTATIC 4 EVAPORATOR 5 FILTER DRYER 6 SIGHT GLASS 7 LOW PRESSURE SWITCH 8 HIGH PRESSURE SWITCH 9 CONDENSING PRESSURE PROBE
Page 5
Page 4 - IOM / TELECOOL THN - 0104 - E
INSTALLATION WARNINGS
GENERAL RULES
-
When installing or servicing the unit, you must strictly follow the rules provided in this manual, comply with the directions on
the units themselves and take all such precautions as are necessary.
- The fluids under pressure in the cooling circuit and the presence of electrical components may cause hazardous situations during installation and maintenance work.
All work on the unit must be carried out by qualified personnel only, trained to do their job in accordance with current laws and regulations.
- Failure to comply with the rules provided in this manual or any modification made to the unit without prior authorisation will result in the immediate invalidation of the warranty.
Warning: Before performing any kind of work on the unit, make sure it has been disconnected from the power supply.
GENERAL DESCRIPTION
Page 6
LIFTING AND TRANSPORT
While the unit is being unloaded and positioned, utmost care must be taken to avoid abrupt or violent manoeuvres. The unit must be handled carefully and gently; avoid using machine components as anchorages or holds and always keep it in an upright position. The unit should be lifted using the pallet it is packed on; a transpallet or similar conveyance means should be used.
Warning: In all lifting operations make sure that the unit is securely anchored in order to prevent accidental falls or overturning.
UNPACKING
The packing must be carefully removed to avoid the risk of damaging the unit. Different packing materials are order to minimise their environmental impact.
POSITIONING
Bear in mind the following aspects when choosing the best site for installing the unit and the relative connections:
- positioning and dimensions of the coupling flanges;
- location of power supply;
It is recommended to first prepare holes in the wall for the air intake and outlet flanges. The dimensions of the air outlet/intake flanges are shown below:
THN*D045...170 (rear view)
INSPECTION
INSPECTION
INSPECTION ON RECEIPT
On receiving the unit, check that it is perfectly intact: the unit left the factory in perfect conditions; immediately report any signs of damage to the carrier and note them on the Delivery Slip before signing it. HiRef S.p.A. or its Agent must be promptly notified of the entity of the damage. The Customer must submit a written report describing every significant sign of damage.
Page 7
Page 6 - IOM / TELECOOL THN - 0104 - E
THN*U045..073 – 150-170
INSPECTION
THN*U090..120 (rear view)
Page 8
INSTALLATION
The THN package air-conditioning unit is suitable for all environments except aggressive ones. Do not place any obstacles near the units and make sure that the air flow is not impeded by obstacles and/or situations causing back suction.
The following steps should be carried out to ensure proper installation:
- Apply a vibration-damping rubber lining between the unit and wall
- Position the unit on the wall, fitting the air outlet and intake flanges correctly into place
- carefully seal the entire perimeter of the unit on the interior wall of the shelter and the air intake and outlet flanges on the inside.
INSTALLATION
- In order to obtain stable indoor conditions, make sure that the shelter interior is insulated from the outside; any openings should be sealed closed.
The recommended sizes for the power cables and emergency line are shown in the table below:
Unit model
THN045 THN056 THN073
THN090 THN105
THN120 THN150 THN170
Mains power supply
230V/1Ph/50Hz
400V/3Ph+N/50Hz
Cable type
2 x 6mm2 + T 6mm2
4 x 6 mm2 +
T x 6 mm2
UPS emergency line
48 Vdc/230Vac
48 Vdc/230Vac
Cable Type
2 x 2.5 mm2
2 x 4 mm2
Page 9
Page 8 - IOM / TELECOOL THN - 0104 - E
INSTALLATION
Evacuation and charging operations for THN-type units
This type of work must be carried out by qualified personnel only trained to do their job in accordance with current laws and regulations
1.
Introduction
The simultaneous presence of liquid and vapour makes it necessary for both to be in a state of saturation [ Gibbs law ], as shown in fig. 1). In conditions of thermal equilibrium, the pressure in the tank corresponds to the T of the surrounding environment; a withdrawal of refrigerant charge will cause pressure drops, which will be associated with
- withdrawal of refrigerant charge Ö pressure drop in tank
- pressure drop in tank Ö T drop change of state
- T drop change of state Ö evaporation of part of the liquid, causing the liquid itself to cool
- cooling of liquid Ö thermal exchange with ambient air, further evaporation of remaining liquid; the original pressure is restored in the tank after a certain amount of time
Fig. 1
T tank/ambient
Saturated gas
Saturated liquid
Page 10
INSTALLATION
2. Vacuum and charging machine
3.
Vacuum cycle
In general it is preferable to apply a “long” rather than “hard” vacuum: reaching low pressures too abruptly may in fact cause any trapped humidity to evaporate instantaneously, thereby freezing part of it.
Fig. 3
Time
The figure represents a vacuum cycle and an optimal subsequent pressure rise for the refrigeration devices we manufacture.
As a rule, if there is suspicion of an extensive presence of humidity throughout the circuit or system as a whole, the vacuum must be “broken” with anhydrous nitrogen and then the steps must be repeated as described; this operation facilitates the removal of trapped and/or frozen humidity during the evacuation process.
4.
Evacuating a circuit “contaminated” with refrigerant
The first step is to remove the refrigerant from the circuit using a specific machine with a dry compressor for recovering the refrigerant.
Refrigerants
all tend to dissolve in oil [compressor sump] in percentages that are directly proportional to increases in pressure and decreases in the T of the oil itself - Charles’ Law -
Pressure
Oil T
T 3
T 2
T 1
% R... in oil
The release of refrigerant tends to cool the oil and thus actually serves to oppose the release itself: for this reason, it is advisable to switch on the crankcase heating elements, if available, during the evacuation process.
Page 11
Page 10 - IOM / TELECOOL THN - 0104 - E
INSTALLATION
If a high % of refrigerant gets into contact with the Pirani gauge (vacuum sensor), it may “drug” the sensitive element of the latter, rendering it inefficient for a certain period of time. For this reason, if no machine for recovering refrigerant is available, it is nonetheless advisable to switch on the crankcase heating elements and avoid applying a vacuum until the circuit has been adequately purged of refrigerant: the refrigerant may in fact solubilize in the oil of the vacuum pump, undermining its performance for a long time (hours).
5.
Charging positions [single point]
The best position for charging the air conditioners is the section between the thermostatic valve and the evaporator; care should be taken to avoid fixing the thermostat bulb until the operation is complete: this is important to ensure that the valve orifice
remains open so as to allow the passage of refrigerant also toward the condenser/receiver.
Air-condensed water chillers should be charged with refrigerant in the section between the condenser and thermostatic valve: this favours flow into the larger-sized exchanger.
If possible, avoid the inflow of refrigerant into the compressor as this may cause excessive dilution of the lubricant; in any case, first check the compatibility between the crankcase capacity and the required charge volumes.
ELECTRICAL CONNECTIONS
GENERALITIES
Before carrying out any job on electrical parts, make sure the power supply is disconnected.
Check that the mains electricity supply is compatible with the specifications (voltage, number of phases, frequency) shown on the unit rating plate.
The power connection for single-phase loads is to be made with a three-pole cable and “N” wire at the centre of the star [optional: power supply w/o neutral]
The size of the cable and line protections must conform to the specifications provided in the wiring diagram.
The supply voltage may not undergo fluctuations exceeding ±5% and the unbalance between phases must always be below 2%.
The above operating conditions must always be complied with: failure to ensure said conditions will result in the immediate invalidation of the warranty.
The electrical connections must be made in accordance with the information shown in the wiring diagram provided with the unit and with current and local regulations.
An earth connection is
mandatory. The installer must connect the earthing wire using the earthing terminal situated on the electric control board (yellow and green wire).
The power supply to the control circuit is taken from the power line through an insulating transformer situated on the electric control board.
The control circuit is protected by suitable fuses or automatic breakers depending on the unit size.
Page 12
IOM / TELECOOL THN - 0104 - E Page 11
STARTING UP
STARTING UP
PRELIMINARY CHECKS
- Check that the electrical connections have been made properly and that all the terminals are securely tightened. This check should also be included in a periodic six-month inspection.
- Check that the voltage at the RST terminals is 400 V ± 5% and make sure the yellow indicator light of the phase sequence relay is on. The phase sequence relay is positioned on the electric control board; if the sequence is not duly observed, it will not enable the machine to start.
- Make sure there are no refrigerant leaks that may have been caused by accidental impacts during transport and/ or installation.
- Check the power supply to the crankcase heating elements, where present.
The heating elements must be turned on at least 12 hours before the unit is started. They are automatically activated when the main switch is put on. Their function is to raise the T of the oil in the sump and limit the quantity of refrigerant dissolved in it.
To verify whether the heating elements are working properly, check the lower part of the compressors: it should be warm or in any case at a temperature 10 - 15 °C higher than the ambient temperature.
The diagram above illustrates a specific property of gases [Charles’ Law], which are more soluble in liquids as the pressure increases but less soluble as the temperature increases: if the oil in the sump is held at a constant pressure,
an increase in temperature will significantly reduce the amount of refrigerant dissolved in it, thus ensuring that the desired lubricating function is maintained.
Pressure
Oil T
% R407C in oil
Page 13
Page 12 - IOM / TELECOOL THN - 0104 - E
STARTING UP
STARTING UP FOR THE FIRST TIME
Installation:
Attention: the unit is filled with HFC R407C refrigerant.
This refrigerant belongs to group I ( no toxic - no dangerous) according to EN Norm 378 and according the specification contained into CEE law n° 2037/00.
Install the unit in the computer room. Make sure that
the air inlet grilles have more than 0,3 m free space around. [ left - right side ]
The condensate discharge lines can suitably pass in
pre-sheared holes on the unit basament.
Electrical connections:
Open electrical panel.
Disconnect the main switch.
Inlet cables holes are positioned on the bottom side
of the unit
Connect the power supply and the earth connection
to the main switch and to the main earth connection.
3 phase versions only. In case of wrong phase
sequence, the compressor will start in the opposite direction: scroll compressors have to turn in one only direction. The phase sequence relay is connected in series with the air flow switch, so that if wrong R-S-T occurs an “FL” alarm on mP will appear. In this case disconnect the power supply, reverse two phases before the main switch and restart. NB: the R-S-T phase sequence device is positioned in the left part of the E-Panel: green light means power presence and the yellow light means correct phase sequence; if the yellow light doesn’t shine, switch of the main switch and reverse two cables before the main switch.
Close the panel.
Press button “ON” on the microprocessor keyboard.
Start Up
Make sure that the air flows normally and the flow
switch alarm is not present.
Press the “ON” button on the mP keyboard:
o The indoor fan will start immediately o After 20 second and if no alarm are
present, the compressor will start up. NB: the compressor will start if the indoor conditions are according the set point presetted in the mP.
Check the air Delta T: it has to be between 7 and
10 °C.
Check for refrigerant leakage.
Operation
Use the microprocessor and the unit manuals
Page 14
IOM / TELECOOL THN - 0104 - E Page 13
STARTING UP
STARTING OPERATION
Before starting the unit, turn the main switch on, select the operating mode desired from the control panel and press the “ON” button on the control panel.
If the unit fails to start up, check if the service thermostat has been set according to the nominal values provided
You should not disconnect the unit from the power supply during periods when it is inoperative but only when it is to be taken out of service for a prolonged period (e.g. at the end of the season). To turn off the unit temporarily follow the directions provided in the section 4.5.
CHECKS DURING OPERATION
- Check the phase sequence relay on the control board to verify whether the phases occur in the correct sequence: if they do not, disconnect the unit from power supply and invert two phases of the incoming three-pole cable. Never attempt to modify internal electrical connections: any undue modifications will immediately invalidate the warranty.
- Check that the temperature of the water entering the
evaporator is close to the value set on the service thermostat.
Page 15
Page 14 - IOM / TELECOOL THN - 0104 - E
STARTING UP
CHECKING THE REFRIGERANT LEVEL
-
After a few hours of operation, check whether the liquid level indicator has a green ring: a yellow colour indicates the presence of humidity in the circuit. In such a case the circuit must be dehumidified by qualified personnel.
- Large quantities of bubbles should not appear through the
liquid level indicator. A constant passage of numerous bubbles may indicate that the refrigerant level is low and needs to be topped up. The presence of a few bubbles is however allowed, especially in the case of high-glide ternary mixtures such as HFC R407C
- Also check that the end-of-evaporation temperature shown
on the pressure gauge (refer to the pressure gauge scale for the refrigerant R407C, marked with the initials D.P. - Dew Point) is about 4 °C lower than the temperature of the water leaving the evaporator.
- Make sure the overheating of the cooling fluid is limited to
between 5 and 8 °C: to this end:
1) read the temperature indicated by a contact thermometer
placed on the compressor intake pipe;
2) read the temperature indicated on the scale of a pressure
gauge likewise connected to the intake side; refer to the pressure gauge scale for the refrigerant R407C, marked with the initials D.P. (Dew Point). The degree of overheating is given by the difference between the temperatures thus determined.
- Make sure that the Sub-cooling of the cooling fluid is
limited to between 3 and 5°C: to this end:
1) read the temperature indicated by a contact
thermometer placed on the compressor intake pipe;
2) read the temperature indicated on the scale of a
pressure gauge connected to the liquid inlet at the condenser outlet; refer to the pressure gauge scale for the refrigerant R407C, marked with the initials B.P. (Bubble Point). The degree of Sub-cooling is given by the difference between the temperatures thus determined.
Warning: all THN units are charged with R407C. Any top-ups must be made using the same type of refrigerant. This operation is to be considered extraordinary maintenance work and must be performed by qualified personnel only.
Warning: the refrigerant R407C requires “POE” polyolester oil of the type and viscosity indicated on the compressor rating plate. For no reason should oil of a different type be introduced into the oil circuit.
Real P compressor outlet
Average T (T1+T2)/2
T1 (start of condensation) DEW POINT
T2 (end of condensation) BUBBLE POINT
Heat content h
- The difference between the Dew Point and Bubble Point is known as “GLIDE” and this is a characteristic property of refrigerant mixtures. If pure fluids are used, the phase change occurs at a constant T and thus the glide is equal to zero.
Page 16
IOM / TELECOOL THN - 0104 - E Page 15
SETTING OPERATING PARAMETERS
SETTING OPERATING PARAMETERS
GENERALITIES
All the control devices are set and tested in the factory before the unit is dispatched. However, after the unit has been in service for a reasonable period of time you can perform a check on the operating and safety devices. The settings are shown in Tables II and III.
All servicing of the equipment is to be considered extraordinary maintenance and may be carried out BY QUALIFIED TECHNICIANS ONLY: incorrect settings may cause serious damage to the unit and injuries to persons.
The operating parameters and control system settings configurable by means of the microprocessor control are password protected if they have a potential impact on the integrity of the unit.
TABLE II - SETTING OF CONTROL DEVICES
CONTROL DEVICE
Differential air pressure switch (outlet air flow)
Differential air pressure switch (dirty filter)
Pa
Pa
SET POINT
50
50
DIFFERENTIAL
30
20
CONTROL DEVICE
Maximum pressure switch
Minimum pressure switch
Modulating condensation control device
Time lapse between two compressor starts
Bars-r
Bars-r
Bars-r
s
ACTIVATION
28.0
2
14
480
DIFFERENTIAL
4
1.5
7
-
RESETTING
Manual
Automatic
-
Page 17
Page 16 - IOM / TELECOOL THN - 0104 - E
SETTING OPERATING PARAMETERS
MAXIMUM PRESSURE SWITCH
The high pressure switch stops the compressor when the outlet pressure exceeds the set value.
Warning: do not attempt to change the setting of the maximum pressure switch: Should the latter fail to trip in the event of a pressure increase, the pressure relief valve will open.
The high pressure switch must be manually reset; this is possible only when the pressure falls below the set differential (see Table III).
MINIMUM PRESSURE SWITCH
The low pressure switch stops the compressor when the inlet pressure falls below the set value for more than 120 seconds.
The switch is automatically reset when the pressure rises above the set differential (see Table III);
Page 18
IOM / TELECOOL THN - 0104 - E Page 17
ROUTINE MAINTENANCE AND CHECKS
ROUTINE MAINTENANCE AND CHECKS
The only operations to be performed by the user are to switch the unit on and off. All other operations are to be considered maintenance work and must thus be carried out by qualified personnel trained to do their job in accordance with current laws and regulations.
WARNINGS
All the operations described in this chapter MUST ALWAYS BE PERFORMED BY QUALIFIED PERSONNEL ONLY.
Before carrying out any work on the unit or accessing internal parts, make sure you have disconnected it from the mains electricity supply.
The upper part and the outlet pipe of the compressor reach high temperatures. Be especially careful when working in the surrounding area with the panels off.
Be especially careful when working in proximity to finned coils since the 0.11 mm-thick aluminium fins can cause superficial injuries due to cuts.
After completing maintenance jobs, always replace the panels enclosing the units and secure them with the fastening screws provided.
Page 19
Page 18 - IOM / TELECOOL THN - 0104 - E
ROUTINE MAINTENANCE AND CHECKS
GENERALITIES
To guarantee a constantly satisfactory performance over time, it is advisable to carry out routine maintenance and checks as described below. The indications below are related to standard tear and wear.
Operation
Check the efficiency of all the control and safety devices
Check the terminals on the electric control board and compressor terminal boards to ensure that they are securely tightened. The movable and fixed contacts of the circuit breakers must be periodically cleaned and replaced whenever they show signs of deterioration
Check the refrigerant level by means of the liquid level indicator
Check the efficiency of the differential air pressure switch and dirty filter differential pressure switch
Check the condition of the air filter and replace it if necessary
Check the humidity indicator (green=dry, yellow=humid) on the liquid level indicator; if the indicator is not green as shown on the indicator sticker, replace the filter
Frequency
Once a year Once a year
Every 6 mos. Every 6 mos.
Every 6 mos. Every 6 mos.
INSPECTING THE AIR FILTER
Remove the panel above the condenser fan to access the damper and air filter compartment. – Pull out the air filter. – Check the condition of the filter and replace it if necessary
Page 20
IOM / TELECOOL THN - 0104 - E Page 19
ROUTINE MAINTENANCE AND CHECKS
INSPECTING THE DAMPER SERVOMOTOR
Remove the panel above the condenser fan – Remove the damper fastening screws (see fig. below)
Pull out the entire damper section to access the servomotor
Page 21
Page 20 - IOM / TELECOOL THN - 0104 - E
ROUTINE MAINTENANCE AND CHECKS
REPAIRING THE COOLING CIRCUIT
Warning: while performing repairs on the cooling circuit or maintenance work on the compressors, make sure the circuit is left open for as little time as possible. Even if briefly exposed to air, ester oils tend to absorb large amounts of humidity, which results in the formation of weak acids.
If the cooling circuit has undergone any repairs, the following operations must be carried out:
- tightness test;
- evacuation and drying of the cooling circuit;
- charging with refrigerant.
If the system has to be drained, always recover the refrigerant present in the circuit using suitable equipment; the refrigerant should be handled exclusively in the liquid phase.
Page 22
IOM / TELECOOL THN - 0104 - E Page 21
ROUTINE MAINTENANCE AND CHECKS
TIGHTNESS TEST
Fill the circuit with anhydrous nitrogen supplied from a tank with a pressure-reducing valve until the pressure rises to 22 bars.
During the pressurisation phase, do not exceed a pressure of 22 bars on the compressor low pressure side.
The presence of any leaks must be determined using special leak detectors. Should any leaks be detected during the test, empty out the circuit before repairing the leaks with suitable alloys.
Do not use oxygen in the place of nitrogen as a test agent, since this would cause a risk of explosion.
HARD VACUUM AND DRYING OF COOLING CIR­CUIT
To achieve a hard vacuum in the cooling circuit it is necessary to use a pump capable of generating a high degree of vacuum, i.e. 150 Pa of absolute pressure with a capacity of approximately 10 m
3
/h. If such a pump is available, one evacuation will normally suffice to achieve an absolute pressure of 150 Pa.
If there is no such vacuum pump available, or whenever the circuit has remained open for long periods of time, you are strongly recommended to adopt the triple evacuation method. This method is also recommended when there is a presence of humidity within the circuit.
The vacuum pump should be connected to the inlets.
The procedure to be carried out is as follows:
- Evacuate the circuit until you reach an absolute pressure of
at least 350 Pa: at this point inject nitrogen into the circuit until you reach a relative pressure of about 1 bar.
- Repeat the step described above.
- Carry out the step described above for the third time, but in
this case attempting to reach the hardest vacuum possible.
Using this procedure you can easily remove up to 99% of pollutants.
Page 23
Page 22 - IOM / TELECOOL THN - 0104 - E
ROUTINE MAINTENANCE AND CHECKS
RECHARGING WITH REFRIGERANT R407C
-
Connect the tank of refrigerant gas to the male 1/4 SAE inlet situated on the liquid line after discharging a little gas to eliminate air in the connection pipe.
- Fill with refrigerant in liquid form until you reach 75% of the total charge.
- Then connect to the inlet on the pipe between the thermostatic valve and evaporator and complete the charging process with the refrigerant in liquid form until no more bubbles can be seen on the liquid level indicator and the operating parameters specified in section 4.4 have been reached.
Since R407C is a ternary mixture, charging must take place exclusively with liquid refrigerant to ensure the correct percentages of the three constituents. Introduce refrigerant through the inlet in the liquid line.
A unit that was originally charged with R407C in the factory must not be charged with R22 or other refrigerants without the written authorisation of HiRef S.p.A.
ENVIRONMENTAL PROTECTION
The law implementing the regulations [reg. EEC 2037/00] which govern the use of ozone-depleting substances and greenhouse gases bans the dispersal of refrigerant gases in the environment and requires whoever is in their possession to recover them and, at the end of their useful life, either to return them to the dealer or take them to a suitable waste disposal facility.
The refrigerant HFC R407C is not harmful to the ozone layer but is included among the substances responsible for the greenhouse effect and thus falls within the scope of the aforesaid regulations.
Therefore, special care should be taken when carrying out maintenance work to minimise refrigerant leaks.
Page 24
IOM / TELECOOL THN - 0104 - E Page 23
TROUBLESHOOTING
TROUBLESHOOTING
On the next pages you will find a list of the most common causes that may cause the package unit to fail or malfunction. These causes are broken down according to easily identifiable symptoms.
You should be extremely careful when attempting to implement any of the possible remedies suggested: overconfidence can result in injuries, even serious ones, to inexpert individuals. Therefore, once the cause has been identified, you are advised to contact the manufacturer or a qualified technician for help.
FAULT
The unit does not start
The compressor is noisy
Presence of abnormally high pressure
Possible causes
No power supply
The electronic card is cut off from the power supply Alarms have been triggered
The phase sequence is wrong
The compressor is rotating in the wrong direction
Insufficient flow of air to the condenser
Presence of air in the refrigerant circuit, as revealed by the presence of bubbles in the flow indicator also with undercooling values exceeding 5 °C
Corrective actions
Check that power is being supplied both to the primary and auxiliary circuits.
Check the fuses
Check whether any alarms are signalled on the microprocessor control panel, eliminate the causes and restart the unit. Invert two phases in the primary power line after disconnecting them upstream from the unit
Check the phase sequence relay. Invert the phases on the terminal board after disconnecting the unit and contact the manufacturer.
Check for the presence of obstructions in the condenser section ventilation circuit Check whether the condenser coil surface is obstructed Check the condensation control device [optional]
Drain and pressurise the circuit and check for leaks. Evacuate slowly [for more than 3 hours] until reaching a pressure of 0.1 Pa and then recharge in the liquid phase
Page 25
Page 24 - IOM / TELECOOL THN - 0104 - E
TROUBLESHOOTING
FAULT
Presence of abnormally high pressure
Low condensation pressure
Low evaporation pressure
The compressor does not start
Possible causes
Unit overcharged, as revealed by an Sub-cooling of more than 8 °C
Thermostatic valve and/or filter obstructed. These symptoms may also occur in the presence of an abnormally low pressure
Transducer fault
Malfunctioning of thermostatic valve
Filter dryer clogged
Low condensation T
Low level of refrigerant
The internal thermal protection device has tripped
The circuit breakers or line fuses have been tripped by a short circuit
One of the high or low pressure switches has tripped
The phases have been inverted in the distribution compartment
Corrective actions
Drain the circuit
Check the temperatures upstream and downstream from the valve and filter and replace them if necessary.
Check the efficiency of the condensation control device [optional]
Warming the bulb with your hand, check whether the valve opens and adjust it if necessary. If it does not respond, replace it.
Pressure drops upstream and downstream from the filter should not exceed 2°C. If they do, replace the filter.
Check the efficiency of the condensation control device [where present]
Check the refrigerant level by measuring the degree of Sub-cooling; if it is below 2°C replenish the charge
In the case of compressors equipped with a protection module, check the thermal contact. Identify the causes after restarting.
Pinpoint the cause by measuring the resistance of the individual windings and the insulation from the casing before restoring power.
Check on the microprocessor, eliminate the causes.
Check the phase sequence relay.
Page 26
IOM / TELECOOL THN - 0104 - E Page 25
Technical data
TECHNICAL DATA
Model
Refrigerant
Cooling Capacity @27°/40%-35°
Standard Power Supply
Power Supply (Option 2)
Power Supply (Option 3)
Power Supply (Option 4)
Power Supply (Option 5)
Total Absorbed Power
Total Absorbed Current
FLA
LRA
Indoor Fan(s) absorbed Power in 230/1/50 execution
Indoor Fan(s) absorbed Power in 48 V DC execution (optional)
Indoor Air Flow
Indoor Air Flow during Free Cooling Operations @ 40 Pa
Full Free Cooling Temperature
Filtration
Sound Power Level
Outdoor Noise Level: SPL @ 2m FF
Type of compressor
Number of refrigerating circuits
Number of compressors
Oil charge per compressor
Indoor Coil Front Surface
Outdoor Coil Front Surface
Condenser Air Flow
Number of condenser’s fan
Overall dimensions: height H
Overall dimensions: lenght L
Overall dimensions: depth D
Weight
[Ashrae]
[W]
[V-n-f]
[V-n-f]
[V-n-f]
[V-n-f]
[V-n-f]
[W]
[A]
[A]
[A]
[W]
[W]
[m3/h]
[m3/h]
[°C]
[-]
[dB-A]
[dB-A]
[-]
[-]
[-]
[dm3]
[m2]
[m2]
[m3/h]
[-]
[mm]
[mm]
[mm]
kg
THN 045
R407C
4500
230/1/50
-
230/1/50+ 230/1/50
230/1/50+ 48 VDC
-
1810
8.3
15.1
30
108
100
1450
1320
17,8
EU3
69
58
Rotary
1
1
0.44
0.30
0.33
2250
1
800
1850
550
120
THN 056
R407C
5600
230/1/50
400/3/50
400/3/50+ 230/1/50
230/1/50+ 48 VDC
400/3/50+ 48 VDC
2330
14.3
16
47
108
100
1450
1320
15,5
EU3
69
58
Scroll
1
1
1
0.30
0.33
2250
1
800
1850
550
128
THN 073
R407C
7100
230/1/50
400/3/50
400/3/50+ 230/1/50
230/1/50+ 48 VDC
400/3/50+ 48 VDC
2990
13.6
19.6
61
310
260
2100
1980
17.0
EU3
69
58
Scroll
1
1
1
0.30
0.33
2250
1
800
1850
550
135
THN 090
R407C
8970
400/3/50
230/1/50
400/3/50+ 230/1/50
400/3/50+ 48 VDC
230/1/50+ 48 VDC
3950
11.8
17.5
40
470
350
3020
2850
18.2
EU3
72
61
Scroll
1
1
1.1
0.38
0.45
3750
1 (THN) 2 (THN*D)
1010
1850
550
195
THN 105
R407C
10850
400/3/50
230/1/50
400/3/50+ 230/1/50
400/3/50+ 48 VDC
230/1/50+ 48 VDC
4400
12.5
17.5
46
470
350
3020
2810
16.3
EU3
72
61
Scroll
1
1
1.1
0.38
0.45
3750
1 (THN) 2 (THN*D)
1010
1850
550
200
THN 120
R407C
11850
400/3/50
230/1/50
400/3/50+ 230/1/50
400/3/50+ 48 VDC
230/1/50+ 48 VDC
5000
13.6
19.5
50
470
350
3020
2810
15.4
EU3
72
61
Scroll
1
1
1.1
0.38
0.45
3750
1 (THN) 2 (THN*D)
1010
1850
550
210
THN 150
R407C
14980
400/3/50
-
400/3/50+ 230/1/50
400/3/50+ 48 VDC
-
6040
17.8
21.7
65
520
450
3800
3550
15.3
EU3
72
61
Scroll
1
1
1.36
0.42
0.52
4700
2
1160
1850
550
245
THN 170
R407C
17200
400/3/50
-
400/3/50+ 230/1/50
400/3/50+ 48 VDC
-
7030
18.6
25.7
74
520
450
3800
3550
13.6
EU3
72
61
Scroll
1
1
1.65
0.42
0.52
4700
2
1160
1850
550
250
Page 27
www.lennoxeurope.com
IOM-TELE-THN-0104-E
Due to Lennox's ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
LENNOX BENELUX N.V./S.A.
tel. : + 32 3 633 30 45 fax : + 32 3 633 00 89 e-mail : info.be@lennoxbenelux.com
JANKA LENNOX a.s.
tel. : + 420 2 510 88 111 fax : + 420 2 579 10 393 e-mail : janka@janka.cz
LENNOX FRANCE
tel. : + 33 1 64 76 23 23 fax : + 33 1 64 76 35 75 e-mail : marketing.france@lennoxfrance.com
LENNOX DEUTSCHLAND GmbH
tel. : + 49 69 42 09790 fax : + 49 69 42 09 79 40 e-mail :info.de@lennoxdeutschland.com
LENNOX BENELUX B.V.
tel. : + 31 33 2471 800 fax : + 31 33 2459 220 e-mail : info@lennoxbenelux.com
LENNOX POLSKA Sp. z o.o.
tel. : + 48 22 832 26 61 fax : + 48 22 832 26 62 e-mail : info@lennoxpolska.pl
LENNOX PORTUGAL Lda.
tel. : +351 22 998 33 70 fax : +351 22 998 33 79 e-mail : info@lennoxportugal.com
LENNOX DISTRIBUTION MOSCOW
tel. : + 7 095 233 29 55 fax : + 7 095 926 56 50 e-mail : lennox.dist.moscow@co.ru
LENNOX SLOVENSKO s.r.o.
tel. : + 421 2 44 87 19 27 fax : + 421 2 44 88 64 72 e-mail : lennox.slovensko@lennox.sk
LENNOX REFAC S.A.
tel. : + 34 915 40 18 10 fax : + 34 915 42 84 04 e-mail : marketing@lennox-refac.com
LENNOX DISTRIBUTION KIEV
tel. : + 380 44 213 14 21 fax : + 380 44 213 14 21 e-mail : jankauk@uct.kiev.ua
LENNOX INDUSTRIES LTD
tél. : + 44 1604 669100 fax : + 44 1604 669150 e-mail : ukmarketing@lennoxind.com
LENNOX DISTRIBUTION
tel. : + 33 4 72 23 20 14 fax : + 33 4 72 23 20 28 e-mail : marketing@lennoxdist.com
BELGIUM,
LUXEMBOURG :
CZECH REPUBLIC :
FRANCE :
GERMANY :
NETHERLANDS :
POLAND :
PORTUGAL :
RUSSIA :
SLOVAKIA :
SPAIN :
UKRAINE :
UNITED KINGDOM,
IRELAND :
OTHER EUROPEAN COUNTRIES,
AFRICA,
MIDDLE-EAST :
Loading...