Lennox THS105, THS035, THS045, THS090, THS056 Installation, Operating And Maintenance Manual

...
Page 1
Providing IT Climate Technology
@DNOVA_THS-IOM-0508-E
Installation, operating and maintenance
@DNOVA THS Telecom split unit
Page 2
Page 3
IOM / @DNOVA_THS-0508 1
CONTENTS
INDEX
Page
GENERAL DESCRIPTION 2 Basic cooling circuit 3 Installation warnings 5
INSPECTION / TRANSPORT 6 Inspection on receipt 6 Lifting and transport 6
Unpacking 6
INSTALLATION 7 Positioning 7
ELECTRICAL CONNECTIONS 12
STARTING UP 13 Preliminary checks 13 Starting up for the first time 13 Starting operation 15 Checks during operation 15 Checking the refrigerant level 15
SETTING OPERATING PARAMETERS 17 Generalities 17 Maximum pressure switch 17 Minimum pressure switch 17
MAINTENANCE 18 Warnings 18 Generalities 18 Inspecting the air filter 19 Inspecting the damper servomotor 19 Repairin g the cooling circuit 20 Tightness test 20 Hard vacuum and drying of cooling circuit 20 Recharging with R407C refrigerant 21 Environmental protection 21
TROUBLESHOOTING
22
OVERALL DIMENSIONS 24 TECHNICAL DATA SHEET 25
Page 4
2 IOM / @DNOVA_THS-0508
1. GENERAL DESCRIPTION
THS “LENNOX Telecom Splitunits composed by an evaporating indoor unit THI for ceiling or wall installation and a motor-condensing outdoor unit THC, mainly for electronic equipped shelters, process centres, telecomunications sites from 4.5 to 14.5 kW of nominalcooling capacity. The system provides air filtration, indoor ventilation, cooling, heating, freecooling with outdoor fresh air to assure the useful climate in the site.
Structure
All THS units have a galvanised sheet steel supporting base and enclosing panels are painted with epoxy polyester powder coating cured at 180°C, or, on request, painted galvanised sheet steel (RALxxxx).
Field of Application:
THS units are to be used within the operating limits stated in this manual; failure to comply with said limi ts will invalidate the warranties provided in the contract of sale.
Cooling circuit
The entire cooling circuit is built in the LENNOX factory using only components of the finest quality brands and processes conform ing to the specifications of Directive 97/23 for brazing and testing.
Compresso rs
: only scroll-type compressors of leading international manufacturers are used in the THS units. Today scroll compressors represent the best solution in terms of reliability, efficiency and MTBF.
Cooling components:
o Molecular mesh activated-alumina filter dryer o Flow indicator with humidity indicator. Indications are provided directly on the sight
glass.
o Thermostatic valve with external equaliz ation and integrated MOP function. o High and low pressure switches o Schrader valves for checks and/or maintenance
Electric control board
: The electric control board i s constructed and wired in accordance with Directives 73/23/EEC and 89/336/EEC and rel ated standards. All the remote controls use 24 V signals powered by an insulating transformer. NOTE: the mechanical safety devices such as the high pressure switch are of the kind that trigger directly; their efficiency will not be affected by any faults occurring in the microprocessor control circuit, in compliance with 97/23 PED.
Control microproce ssor
: the microprocessor built into the unit allows the different operating
parameters to be controlled from a set of pushbuttons situated on the electric control board;
o Switching on/off of compressor to maintain the temperature set point T inside the
shelter
o Alarm management
High / low pressure
MODEL
THS025 THS035 THS045 THS056 THS073 THS090 THS105 THS120 THS145
230Vac ± 10%/1Ph/50Hz 400Vac ± 10%/3Ph+N /50Hz
24± 16% Vdc emergency cooling 24± 16% Vdc emergency cooling
Power supply
48± 16% Vdc emergency cooling 48± 16% Vdc emergency cooling
Min -20°C
Temperature Outdoor
Max. 48°C 46,5°C 45°C 47°C 45°C 44°C Min. 19 °C - 30 % r .h.
Temp./humidi ty conditions
Max. 35 °C - 50 % r.h. Min. + 10° C / 90 % r.h.
Storage conditions
Max. + 55°C / 90 % r.h.
Page 5
IOM / @DNOVA_THS-0508 3
Dirty filters alarm Air flow alarm
o Alarm signalling o Display of operatin g parameters o RS232, RS485 serial outp ut management (optional) o Phase sequence error [Not displayed by the mP, but prevents the compressor from
starting up]
[see microprocessor control manual for further details, also in relation to particular customer specifications]
a. Basic cooling circuit
THI 025-035 VTE
Page 6
4 IOM / @DNOVA_THS-0508
THI 025-035 VTM
THI 045-145
Page 7
IOM / @DNOVA_THS-0508 5
b. Installation warnings
General rules
- When installing or servicing the unit, you must strictly follow the rules provided in this manual, comply with the directions on the units themselves and take all such precautions as are necessary.
- The fluids under pressure in the cooling circuit and the presence of electrical components may cause hazardous situations during installation and m aintenance work.
All work on the unit must be carried out by qualified personnel only, trained to do
their job in accordance with current laws and regulations
- Failure to comply with the rules provided in this manual or any modification made to the unit without prior authorisation will result in the imm ediate invalidation of the warranty.
Warning: Before performing any kind of work on the unit, make sure it has been disconnected from the power supply.
Page 8
6 IOM / @DNOVA_THS-0508
2. INSPECTION/TRANSPORT
a. Inspection on receipt
On receiving the unit, check that it is perf ectly intact: the unit left the factory in perfect conditions; immediately report any signs of damage to the carrier and note them on the Delivery Slip before signing it. LENNOX or its Agent must be promptly notified of the entity of the damage. The Customer must submit a written report describing every significant sign of damage.
b. Lifting and transport
While the unit is being unloaded and positioned, utmost care must be taken to avoid abrupt or violent manoeuvres. The unit must be handled carefully and gently; avoid using machine components as anchorages or holds and always keep it in an upright position. The unit should be lifted using the pallet it is packed on; a transpallet or similar conveyance means should be used.
Warning: In all lifting operations make sure that the unit is securely anchored in order to prevent accidental falls or ov erturning.
c. Unpacking
The packing m ust be carefully rem oved to avoid the risk of damaging the unit. Different packing materials are used: wood, cardboard, nylon etc. It is recommended to keep them separately and deliver them to suitable waste disposal or recycling facilities in order to minimise their environmental impact.
Page 9
IOM / @DNOVA_THS-0508 7
3. INSTALLATION
The THS package air-conditioning unit is suitable for all environments except aggressive ones. Do not place any obstacles near the units and make sure that the air flow is not impeded by obstacles and/or situations causing back suction.
Positioning indoor unit
Bear in mind the following aspects when choosing the best site for installing the unit and the relative connections:
- position of the indoor unit next to the main heat source;
- location of power supply;
- solidity of the supporting ceiling/wall;
It is recommended to first prepare holes in the ceiling/wall for the screw anchors. The dimensions and the positions of the holes for the screw anchors are shown below:
Page 10
8 IOM / @DNOVA_THS-0508
Freecooling duct connections (optional)
The air conditioner may be supplied with an integrated Freecooling device (optional), which uses fresh air from outside to cool the ambient without starting up the compressor. The device supplies the correct cooling capacity required, through a modulating m otor damper. In this case, the back side of the unit is equipped with connections collect the outside air, as follows:
Standard: double circular hole for 252mm diameter flexible ducts.
Option: single rectangular hole with flange for 789x252 m m duct
In both cases, the holes in the ceiling/wall have to be protected by r ainp roof g rilles with prefilter to avoid water or foreign bodies get in the conditioner.
Outside air, taken into the room by the fan, gets out throug h an overpressure damper, which is installed on the ceiling/wall of the room and is protected also by external rainproof grille.
Positioning outdoor unit
The condensing unit must be positioned outside to enable its cooling. It is connected to the air conditioner through the refrigerant lines. Keep refrigerant lines as short as possible (do not use lines longer than 15m for R22 and 10m for R407C).
Page 11
IOM / @DNOVA_THS-0508 9
Refrigerant connections
THIS OPERATION MUST BE CARRIED OUT BY AN EXPERT TECHNICIAN
1. Lines positioning
Connect th e air conditioner to the condensing unit b y using refrigerant lines in hard or soft copper.
Limit the number of preshaped bends; if this is not possible, every bend must have a
radius of at least 100mm
The gas line must be insulated The liquid line must be kept far from heat sources; if this is not possible it has to be
insulated
If the condensing unit is placed above the evaporating unit, the last se gment o f the
intake tube (insulated tube) must lean towards the condensing unit.
If, on the other hand, the condensing unit is placed under the conditioner it is advisable
to create a trap on the intake tube.
The recomm ended sizes for the power cables and emergency line are shown in the table below:
Models Main power supply Cable type
Emergency
power UPS
Cable type
THI025 THI035 THI045 THI056 THI073 THI090 THI105 THI120 THI145
230V/1Ph/50Hz 2 x 6 mm2 + T x 6 mm2 48 Vdc 2 x 2,5 mm2
Unità
modello
Main power supply Cable type
Emergency
power UPS
Cable type
THC025 THC035 THC045 THC056 THC073
230V/1Ph/50Hz 2 x 6mm2 + T x 6 mm2 48 Vdc 2 x 2,5 mm2
THC090 THC105 THC120 THC145
400V/3Ph+N/50Hz 4 x 6 mm2 + T x 6 mm2 48 Vdc 2 x 4 mm2
Evacuation and charging operations for THS-type units
This type of work must be carried out by qualified personnel only trained to do
their job in accordance with current laws and regulations
Page 12
10 IOM / @DNOVA_THS-0508
1. Introduction
:
The simultaneous presence of liquid and vapour makes it necessary for both to be in a state of saturation [ Gibbs law ], as shown in fig. 1). In conditions of thermal equilibrium, the pressure in the tank corresponds to the T of the surrounding environment; a withdrawal of refrigerant charge will cause pressure drops, which will be associated with
- withdrawal of refrigeran t charge pressure drop in tank
- pressure drop in tank T drop change of state
- T drop change of state evaporation of part of the liquid, causing the liquid itself to cool
- cooling of liquid thermal exchange with ambient air, further evaporation of remaining liquid; the original pressure is restored in the tank after a certain amount of time
2. Vacuum and charging machine
3. Vacuum cycle In general it is preferable to apply a “long” rather than “hard” vacuum: reaching low pressures too abruptly may in
fact cause any trapped humidity to evaporate instantaneously, thereby freezing part of it.
The figure represents a vacuum cycle and an optimal subsequent pressure rise for the refrigeration devices we manufacture.
As a rule, if there is suspicion of an extensive presence of humidity throughout the circuit or system as a whole,
the vacuum must be “broken” with anhydrous nitrogen and then the steps must be repeated as described; this
operation facilitates the removal of trapped and/or frozen humidity during the evacuation process.
P
Heat content
h
T tank/ambient
Saturated gas
Saturated
liquid
Fig. 1
P
[Pa]
Time
200 s
6
150
Fig. 3
Page 13
IOM / @DNOVA_THS-0508 11
4. Evacuating a circuit “contaminated” with refrigerant The f irst step is to remove the refrigerant from the circuit using a specific machine with a dry compressor for
recovering the refrigerant. Refrigerants all
tend to dissolve in oil [compressor sump] in percentages that are directly proportional to increases
in pressure and decreases in the T of the oil itself - Charles' Law -
The release of refrigerant tends to cool the oil and thus actually serves to oppose the release itself: for this reason, it is advisable to switch on the crankcase heating elements, if available, during the evacuation process.
If a high % of r e frigerant gets into contact with the Pirani gauge (vacuum sensor), it may “drug” the sensitive element of the latter, rendering it inefficient for a certain period of time. For this reason, if no machine f or recovering refrigerant is available, it is nonetheless advisa ble to switch on the crankcase heating elements and avoid applying a vacuum until the circuit has been adequately purged of refrigerant: the refrigerant may in fact solubilize in the oil of the vacuum pump, undermining its performance for a long time (hours).
5. Charging positions
[single point]
The best position for charging the air conditioners is the section between the thermostatic valve and the evaporator; care should be taken to avoid f ixing the thermostat bulb until the operation is complete: this is important to ensure that the valve orifice remains open so as to allow the passage of refrigerant also toward the condenser/receiver.
If possibl e, avoid the inflow of refrigerant into the compressor as this may cause excessive dilution of the lubricant; in any case, first che ck the compatibility between the crankcase capacity and the required charge volumes.
Oil T
Pressure
% R.... in oil
T1
T2
T3
Page 14
12 IOM / @DNOVA_THS-0508
4. ELECTRICAL CONNECTIONS
Before carrying out any job on electrical parts, make sure the power supply is disconnected.
Check that the mains electricity supply is com patib le with th e specifications (voltage, number of phases, frequency) shown on the unit rating plate. The power connection for single-phase loads is to be made with a three-pole cable and “N” wire at the centre of the star [optional: power supply w/o neutral]
The siz e of the cable and line protections must conform to the specifications provided in the wiring diagram.
The supply voltage may not undergo fluctuations exceeding ±5% and the unbalance between phases must always be below 2%.
The above operating conditions must always be complied with: failure to ensure said conditions will result in the immediate invalidation of the warranty.
The electrical connections must be made in accordance with the information shown in the wiring diagram provided with the unit and with current and local regulations. An earth connection is mandatory. The installer must connect the earthing wire using the earthing terminal situated on the electric control board (yellow and green wire). The power supply to the control circuit is taken from the power line through an insulating transformer situated on the electric control board. The control circuit is protected by suitable fuses or automatic breakers depending on the unit size.
Legend: 1-Power supply for internal unit; 2-Power supply for external unit; 3-Auxiliary cables
MAIN ELECTRICAL
PANEL
3
2
1
Page 15
IOM / @DNOVA_THS-0508 13
5. STARTING UP
a. Preliminary checks
- Check that th e electrical con nections have been made properly an d that al l the terminals are
securely tightened. This check should also be included in a periodic six-month inspection.
- Check that the voltage at the RST terminals is 400 V ± 5% and make sure the yellow indicator light
of the phase s equence relay is on. The phase sequence relay is positioned on the electric control board; if the sequence is not duly observed, it will not enable the machine to start.
- Make sure there are no refrigerant leaks that may have been caused by accidental impacts during
transport and/or installation.
- Check the power supply to the crankcase heating elements, where present.
The heating elem ents must be turned on at least 12 hours before the unit is started. They are automatically activated when the main switch is put on. Their function is to raise the T of the oil in the sump and limit the quantity of refrigerant dissolved in it.
To verify whether the heating elements are working properly, check the lower part of the compressors: it should be warm or in any case at a temperature 10 - 15 °C higher than the ambient temperature.
The diagram above illustrates a specific property of gases [Charles’ Law], which are more soluble in liquids as the pressure increases but less soluble as the temperature increases: if the oil in the sump is held at a constant pressure, an increase in temperature will significantly reduce the amount of refrigerant dissolved in it, thus ensuring that the desired lubricating function is maintained.
b. Starting up for the first time Start-up instructions for THI 025-073 AN D THC 025-073 units Refrig erant connection between the two units.
THI 025-0473 and THC 025-073 units are both pre-charged with R407C refrigerant. Following here-attached refrigeration diagram instructions (pay attention in particular to IN/OUT)
start refrigeration connections between THI and THC units.
Make the vacuum in refrigerant line between in/out of the two units.
Electrical connection
Open the frontal panel of the two un its. Turn THI unit QS main switch OFF. Switch OFF THC unit Q01 automatic switch. Insert 230/1/50 (main power) power supply cable using one of the special holes you can find on
THI unit sides and connect it to QS main switch.
Pressure
% R407C in oil
Oil T
Page 16
14 IOM / @DNOVA_THS-0508
Following wiring diagram instructions make electrical connections between THI and THC units
230/1/50 power supply and power supply and auxiliary circuit cables.
Connect user interface to microprocessor J10 connector (you can find it in THS wiring diagram)
using a telephone cable.
Turn THI unit QS main switch ON. Turn THC unit Q01 automatic switch ON.
THI Unit THC Unit
Charge the circuit with R407C refrigerant. Close the panels with the matching screws.
Start up When you give power to microprocessor, you can see the first mask of main menu where you can see the
following information:
Indoor air T (Tint); Supply air T (Tsup); External air T (Text) [only Free-Cooling version]; Compresso rs and fan s state; Counter for evaporator fans and compressors.
In next mask (m_on_off), that you can see pushing Down
, it i s possibile to turn the unit on or off
pushing Enter
, Down and then again Enter . It is also shown if the unit is a master or a slave unit (this is a fundamental information for LAN operations) and configuration of local net address (Unit 1, Unit 2 o Stand Alone).
In THI unit there is a RED coloured LED to show that alarm is present.
Usage
always consult the USER manual and control system manual provided with t he unit when
undertaking maintenance and/or advanced set-ups.
N.B.
: In THI unit there is not condensing pressure gouge so the value is not reliable.
m_on_off
╔════════════════════╗ ║UNIT ON: ║ ║ No ║ ║Master ║ ║STAND ALONE UNIT ║ ╚════════════════════╝
main
╔════════════════════╗ ║Comp OFF Tint 00.0°C║ ║Evap OFF Tsup 00.0°C║ ║Cond OFF Text 00.0°C║ ║Ev 00000 Comp 00000h║
╚════════════════════╝
Page 17
IOM / @DNOVA_THS-0508 15
c. Starting operation
Before starting the unit, turn the main switch on, select the operating mode desired from the control panel and press the "ON" button on the control panel.
If the unit fa i ls to start up, check if the service thermostat has been set according to the nominal values
provided
You should not disconnect the unit from the power supply during periods when it is inoperative but only when it is to be taken out of service for a prolonged period (e.g. at the end o f the season). To turn off the unit temporarily follow the directions provided in the section 4.5.
d. Checks during operation
Check the phase sequence relay on the con trol board to verify whether the phases occur in the correct sequence: if they do not, disconnect the unit from power supply and invert two phases of the incoming three-pole cable. Never attempt to modify internal electrical connections: any undue modifications will immediately invalidate the warranty.
e. Checking the refrigerant level
- After a few hours of operation, check whether the liquid level indicator has a green ring: a yellow colour
indicates the presence of humidity in the circuit. In such a case the circuit must be dehumidified by qualified personnel.
-Large quantities of bubbles should not appear through the liquid level indicator. A constant passage of
numerous bubbles may indicate that the refrigerant level is low and needs to be topped up. The presence of a few bubbles is however allowed, especially in the case of high-glide ternary mixtures such as HFC R407C
- Make sure the overheating of the cooling fluid is lim ited to between 5 and 8 °C: to this end:
1) read the temperature indicated by a contact thermometer placed on the compressor intake pipe;
2) read the temperature indicated on the scale of a pressure gauge likewise connected to the intake side; refer to the pressure gauge scale for the refrigerant R407C, marked with the initials D.P. (Dew Point). The degree of overheating is given by the difference between the temperatures thus determined.
- Make sure that the Sub-cooling of the cooling fluid is limited to between 3 and 5°C: to this end:
1) read the temperature indicated by a contact thermometer placed on the condenser outlet pipe;
2) read the temperature indicated on the scale of a pressure gauge connected to the liquid inlet at the condenser outlet; refer to the pressure gauge scale for the refrigerant R407C, marked with the initials B.P. (Bubble Point). The degree of Sub-cooling is given by the difference between the temperatures thus determined.
Warning: all THS units are precharged with R407C. Any top-ups must be made using the same type of refrigerant. This operation is to be considered extraordinary maintenance work and must be performed by qualified personnel only.
Warning: the refrigerant R407C requires “POE” polyolester oil of the type and viscosity
indicated on the compressor rating plate. For no reason should oil of a different type be introduced into the oil circuit.
Page 18
16 IOM / @DNOVA_THS-0508
- The difference betwee n the De w Point and Bubble Point is known as “GLIDE” and this is a characteristic property of refrigerant mixtures. If pure fluids are used, the phase change occurs at a constant T and thus the glide is equal to z ero.
Averag e T
(T1+T2)/2
T1 (start of condensation)
DEW POINT
T2 (end of condensation)
BUBBLE POINT
Heat content h
P
Real P
compressor outlet
R407C
Page 19
IOM / @DNOVA_THS-0508 17
6. SETTING OPERATING PARAMETERS
a. Generalities
All the control devices are set and tested in the factory before the unit is dispatched. However, after the unit has been in service for a reasonable period of time you can perform a check on the operating and safety devices. The settings are shown in Tables II and III.
All ser vicing of the equipment is to be considered extraordinary maintenance and may be carried out BY QUALIFIED TECHNICIANS ONLY: incorrect settings may cause serious damage to the unit and injuries to persons.
The operating parameters and control system settings configurable by means of the microprocessor control are password protected if they have a potential impact on the integrity of the unit.
TABLE II - SETTING OF CONTROL DEVICES
CONTROL DEVICE
SET POINT DIFFERENTIAL
Differential air pressure switch (outlet air flow)
Pa
50 30
Differential air pressure switch (di rty filter)
Pa
50 20
CONTROL DEVICE
ACTIVATION DIFFERENTIAL RESETTING
Maximum pressure switch Bars-r
28.0 4 Manual
Minimum pressure switch Bars-r
2 1.5 Automatic
Modulating condensation control device
Bars-r
14 7 -
Time lapse between two compressor starts
s
480 - -
b. Maximum pressure swithc
The high pressure switch stops the compressor when the outlet pressure exceeds the set value.
Warning: do not attempt to change the setting of the maximum pressure switch: Should the latter fail to trip in the event of a pressure increase, the pressure relief valve will open.
The high pressure switch m ust be manually reset; this is possible only when the pressure falls below the set differential (see Table III).
c. Minimum pressure switch
The low pressure switch stops the compressor when the inlet pressure falls below the set va lue for more than 120 seconds.
The switch is automatically reset when the pressure rises above the set differential (see Table III);
Page 20
18 IOM / @DNOVA_THS-0508
7. MAINTENANCE
The only operations to be performed by the user are to switch the unit on and off. All other operations are to be considered maintenance work and must thus be carried out by qualified personnel trained to do their job in accordance with current laws and regulations.
a. Warnings
All the operations described in this chapter MUST ALWAYS BE PERFORMED BY QUALIFIED PERSONNEL ONLY.
Before carrying out any work on the unit or accessing internal parts, make sure you have disconnected it from the mains electricity supply.
The upper part and the outlet pipe of the compressor reach high temperatures. Be especially careful when w orking in the surrounding area w ith the panels off.
Be especially careful when working in proximity to finned coi ls since the 0.11 mm­thick aluminium fins can cause superficial injuries due to cuts.
After completing m aintenance jobs, always replace the panels enclosing the units and secure them with the fastening screws provided.
b. Generalities
To guarantee a constantly satisfactory performance over time, it is advisable to carry out routine maintenance and checks as described below. The indications below are related to standard tear and wear.
Operation
Frequency
Check the efficiency of all the control an d saf et y devices
Once a year
Check the terminals on the electric control board and comp ressor terminal boards
to ensure that they are securely tightened. The movable and fixed contacts of the circuit breakers must be periodically cleaned and replaced whenever they show signs of deterioration.
Once a year
Check the refrigerant level by means of the liquid level indicator
Every 6 months.
Check the efficiency of the differential air pressure switch and dirty filter differential
pressure switch
Every 6 months.
Check the condition of the air filter and replace it if necessary
Every 6 months.
Check the humidity indicator (green=dry, yellow=humid) on the liquid level indicator;
if the indicator is not green as shown on the indicator sticker, replace the filter
Every 6 months..
Page 21
IOM / @DNOVA_THS-0508 19
c. Inspecting the air filter
Remove the grilled panel to access the dam per and air filter compartment.
Pull out the air filter.
Check the cond ition of the filter and replace it if necessary.
d. Inspecting the damper servomotor
Remove the grilled panel to access the damper and air filter compartment. Remove the damper fastening screws placed at the side Pull out the entire damper section to access the servomotor
Page 22
20 IOM / @DNOVA_THS-0508
e. Rep airing the cooling circuit
Warning: while performing repairs on the cooling circuit or maintenance work on the compressors, make sure the circuit is left open for as little time as possible. Even if briefly exposed to air, ester oils tend to absorb large amounts of humidity, which results in the formation of weak acids.
If the cooling circuit has undergone any repairs, the following operations must be carried out:
- tightness test;
- evacuation and drying of the cooling circuit;
- charging with refrigerant.
If the system has to be drained, always recover the refrigerant present in the circuit using suitable equipment; the refrigerant should be handled exclusively in the liquid phase.
f. Tightness test
Fill the circ uit with anhydrous nitrogen supplied from a tank with a pressure-reducing valve until the pressure rises to 22 bars.
During the pres surisation phase, do not exceed a pressure of 22 bars on the compressor low pressure side
The presence of any leaks must be determ ined using special leak detectors. Should any leaks be detected during the test, em pty out the circuit before repairing the leaks with suitable alloys.
Do not use oxygen in the place of nitrogen as a test agent, since this would cause a risk of explosion.
g. Hard vacuum and drying of cooling circuit
To achieve a hard vacuum in the cooling circuit it is necessary to use a pump capable of generating a high degree of vacuum, i.e. 150 Pa of absolute pressure with a capacity of approximately 10 m3/h. If such a pump is available, one evacuation will normally suffice to achieve an absolute pressure of 150 Pa. If there is no such vacuum pump available, or whenever the circuit has remained open for long periods of time, you are strongly recommended to a dopt the triple evacuation method. This method is also recommended when there is a presence of humidity within the circuit. The vacuum pump should be connected to the inlets. The procedure to be carried out is as follows:
- Evacuate the circuit until you reach an absolute pressure of at least 350 Pa: at this point inject nitrogen
into the circuit until you reach a relative pressure of about 1 bar.
- Repeat th e step described above.
- Carry out the step described above for the third time, but in this case attempting to reach the hardest
vacuum possible.
Using this procedure you can easily remove up to 99% of pollutants.
Page 23
IOM / @DNOVA_THS-0508 21
h. Recharging with refrigerant R407C
- Connect the tank of refrigerant gas to the male 1/4 SAE inlet situated on the liquid line after discharging
a little gas to eliminate air in the connection pipe.
- Fill with refrigerant in liquid form until you reach 75% of the total charge.
- Then connect to the inlet on the pipe between the thermostatic valve and ev a porator and complete the
charging process with the refrigerant in liquid form until no more bubbles can be seen on the liquid level indicator and the operating param eters specified in section 4.4 have been reached.
Since R407C is a ternary mixture, charging must take place exclusively with liquid refrigerant to ensure the correct percentages of the three constituents. Introduce refrigerant through the inlet in the liquid line.
A unit that was originally charged with R407C in the factory must not be charged with R22 or other refri gerants without the written authorisation of LENNOX
i. Environmental protection
The law implementing the regulations [reg. EEC 2037/00] which govern the use of ozone-depleting substances and greenhouse gases bans the dispersal of refrigerant gases in the environment and requires whoever is in their possession to recover them and, at the end of their useful life, either to return them to the dealer or take them to a suitable waste disposal facility. The refrigerant HFC R407C is not harmful to the ozone layer but is included among the substances responsible for the greenhouse effect and thus falls within the scope of the aforesaid regulations.
Therefore, special care should be taken when carrying out maintenance work to minimise refrigerant leaks.
Page 24
22 IOM / @DNOVA_THS-0508
8. TROUBLESHOOTING
On the next pages you will find a list of the m ost common causes that m ay cause the package unit to fail or malfunction. These causes are broken down according to easily identifiable symptom s.
You should be extremely careful when attempting to implement any of the possible remedies suggested: overconfidence ca n result in injuries, even serious ones, to inexpert individuals. Therefore, once the cause has be en identified, you are advised to contact the manufacturer or a qualified technician for help.
FAULT
Possible causes Corrective actions
The unit does not start No power supply Check that p ower is b eing supplied
both to the primary and auxiliary circuits.
The electronic card is cut off from
the power supply
Check the fu ses
Alarms have been triggered Check whether any alarms are
signalled on the microprocessor control panel, eliminate the causes and restart the unit.
The phase sequence is wrong Invert two phases in the primary
power line after disconnecting them upstream from the unit
The compressor is noisy The compressor is rotating in the
wrong direction
Check the phase sequence relay.
Invert the phases on the terminal board after disconnecting the unit and contact the manufacturer.
Presence of abnormally high pressure
Insufficient flow of ai r to the condenser
Check for the presence of obstructions in the condenser section ventilation circuit
Check whether the condenser coil
surface is obstructed
Check the condensation control
device [optional]
Presence of air in the refrigerant
circuit, as revealed by the presence of bubbles in the flow indicator also with undercooling values exceeding 5 °C
Drain an d pressurise the circuit and check for leaks. Evacuate slowly [for more than 3 hours] until reaching a pressure of 0.1 Pa and then recharge in the liquid phase
Page 25
IOM / @DNOVA_THS-0508 23
FAULT
Possible causes Corrective actions
Presence of abnormally high pressure
Unit overch arged, as revealed by an Sub-cooling of more than 8 °C
Drain the circuit
Thermostatic valve and/or filter
obstructed. These symptoms may also occur in the presence of an abnormally low pressure.
Check the temperatures upstream and downstream from the valve and filter and replace them if necessary.
Low condensation pressure Transducer fault Check the efficiency of the
condensation control device [optional]
Low evaporation pressure Malfunctioning of thermostatic
valve
Warming the bulb with your hand, check whether the valve opens and adjust it if necessary. If it does not respond, replace it.
Filter dryer clogged Pressure drops upstream and
downstream from the filter should not exceed 2°C. If they do, replace the filter.
Low condensation T Check the efficiency of the
condensation control device [where present]
Low level of refrigerant Check the refrigerant level by
measuring the degree of Sub­cooling; if it is below 2°C replenish the charge
The internal thermal protection
device has tripped
In the case of compressors equipped with a protection module, check the thermal contact. Identify the causes after restarting.
The compressor does not start The circuit breakers or line fuses
have been tripped by a short circuit
Pinpoint the cause by measuring the resistance of the individual windings and the insulation from the casing before restoring power.
One of the high or low pressure
switches has tripped
Check on the microprocessor, eliminate the causes.
The phases have been inverted in
the distribution compartment
Check the phase sequence relay.
Page 26
24 IOM / @DNOVA_THS-0508
9. OVERALL DIMENSIONS
A B C D
THI 025-145
0 200 200 200
Page 27
IOM / @DNOVA_THS-0508 25
10. TECHNICAL DATA SHEET
THS
Technical Data internal unit
Model THI025 THI035 THI045 THI056 THI073 THI090 THI105 THI120 THI145
Refrigerant
[Ashrae]
R407C R407C R407C R407C R407C R407C R407C R407C R407C
Cooling capacity @27°/40%, 35°
[kW]
2,60 3,60 4,50 5,60 7,30 9,00 10,40 12,00 14,50
Standard power supply
[V-n-f]
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Number of fans
[m3/h]
1 1 2 2 2 2 2 2 2
Number of refrigeration circuits
[-]
1 1 1 1 1 1 1 1 1
Fan absorbed power
[W]
185 185 245 245 470 470 470 690 690
Evaporator air flow
[m3/h]
950 930 1.400 1.400 2.200 2.200 2.200 3.200 3.200
Indoor coil frontal surface
[m2]
0,16 0,16 0,29 0,29 0,29 0,29 0,29 0,37 0,37
Filter
[-]
EU3 EU3 EU3 EU3 EU3 EU3 EU3 EU3 EU3
Air flow during Free­Cooling
[m3/h]
810 790 1.190 1.190 1.870 1.870 1.870 2.720 2.720
Full Free­Cooling Temperature
[°C]
17,5 13,5 15,8 13,0 15,5 12,7 10,5 14,0 11,2
Dimensions internal unit: height H
[mm]
350 350 350 350 350 350 350 400 400
length L
[mm]
1.040 1.040 1.040 1.040 1.040 1.040 1.040 1.140 1.140
depth D
[mm]
590 590 990 990 990 990 990 1.090 1.090
Weight
kg
64 64 83 83 87 94 94 105 106
Page 28
26 IOM / @DNOVA_THS-0508
Technical Data external unit
Model THC025 THC035 THC045 THC056 THC073 THC090 THC105 THC120 THC145
Refrigerant
[Ashrae]
R407C R407C R407C R407C R407C R407C R407C R407C R407C
Power supply (standard)
[V-n-f]
230/1/50 230/1/50 230/1/50 230/1/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Total absorbed power
[W]
940 1.180 1.320 1.760 2.210 2.560 3.070 3.720 4.720
Absorbed current (total)
[A]
3,4 4,6 4,9 7,4 9,6 4,5 5,1 6,2 8,2
FLA
[A]
6,3 8,8 9,5 12 15 7 7 10 13
LRA
[A]
18,3 28 34 47 61 40 46 50 66
Type of compressor
[-]
Rotary Rotary Rotary* Scroll Scroll Scroll Scroll Scroll Scroll
Number of refrigeration circuits
[-]
1 1 1 1 1 1 1 1 1
Number of com pressors
[-]
1 1 1 1 1 1 1 1 1
External coil frontal surface
[m2]
0,25 0,25 0,54 0,54 0,54 0,54 0,54 0,67 0,67
Condenser air flow
[m3/h]
2.250 2.050 3.450 3.350 3.350 5.100 5.100 5.580 5.450
Sound power level
[dB-A]
68 68 69 69 70 70 73 71 71
Sound pressure level
[dB-A]
41 41 42 42 43 43 46 44 44
@ 10 m in free field Nr. of condenser fans
[-]
1 1 1 1 1 1 1 2 2
Dimensions external unit: height H
[mm]
580 580 630 630 630 630 630 1.128 1.128
length L
[mm]
600 600 990 990 990 990 990 1.120 1.120
depth D
[mm]
350 350 360 360 360 360 360 578 578
Weight
[kg]
77 78 86 88 92 98 106 130 133
* scroll compressor optional For other power supplies please contact
Page 29
Page 30
www.lennoxeurope.com
www.lennoxbelgium.com
www.lennoxczech.com
www.lennoxfrance.com
www.lennoxdeutschland.com
www.lennoxnederland.com
www.lennoxpolska.com
www.lennoxportugal.com
www.lennoxrussia.com
www.lennoxdistribution.com
www.lennoxspain.com
www.lennoxukraine.com
www.lennoxuk.com
www.lennoxdistribution.com
@DNOVA_THS-IOM-0508-E
BELGIUM, LUXEMBOURG
CZECH REPUBLIC
FRANCE
GERMANY
NETHERLANDS
POLAND
PORTUGAL
RUSSIA
SLOVAKIA
SPAIN
UKRAINE
UNITED KINGDOM AND IRELAND
OTHER COUNTRIES
Due to Lennox’s ongoing commitment to quality,
the Specifications, Ratings and Dimensions are
subject to change without notice and without
incurring liability.
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage or personal injury.
Installation and service must be performed by a
qualified installer and servicing agency.
Loading...