Lennox THS105, THS035, THS045, THS090, THS056 Installation, Operating And Maintenance Manual

...
Providing IT Climate Technology
@DNOVA_THS-IOM-0508-E
Installation, operating and maintenance
@DNOVA THS Telecom split unit
IOM / @DNOVA_THS-0508 1
CONTENTS
INDEX
Page
GENERAL DESCRIPTION 2 Basic cooling circuit 3 Installation warnings 5
INSPECTION / TRANSPORT 6 Inspection on receipt 6 Lifting and transport 6
Unpacking 6
INSTALLATION 7 Positioning 7
ELECTRICAL CONNECTIONS 12
STARTING UP 13 Preliminary checks 13 Starting up for the first time 13 Starting operation 15 Checks during operation 15 Checking the refrigerant level 15
SETTING OPERATING PARAMETERS 17 Generalities 17 Maximum pressure switch 17 Minimum pressure switch 17
MAINTENANCE 18 Warnings 18 Generalities 18 Inspecting the air filter 19 Inspecting the damper servomotor 19 Repairin g the cooling circuit 20 Tightness test 20 Hard vacuum and drying of cooling circuit 20 Recharging with R407C refrigerant 21 Environmental protection 21
TROUBLESHOOTING
22
OVERALL DIMENSIONS 24 TECHNICAL DATA SHEET 25
2 IOM / @DNOVA_THS-0508
1. GENERAL DESCRIPTION
THS “LENNOX Telecom Splitunits composed by an evaporating indoor unit THI for ceiling or wall installation and a motor-condensing outdoor unit THC, mainly for electronic equipped shelters, process centres, telecomunications sites from 4.5 to 14.5 kW of nominalcooling capacity. The system provides air filtration, indoor ventilation, cooling, heating, freecooling with outdoor fresh air to assure the useful climate in the site.
Structure
All THS units have a galvanised sheet steel supporting base and enclosing panels are painted with epoxy polyester powder coating cured at 180°C, or, on request, painted galvanised sheet steel (RALxxxx).
Field of Application:
THS units are to be used within the operating limits stated in this manual; failure to comply with said limi ts will invalidate the warranties provided in the contract of sale.
Cooling circuit
The entire cooling circuit is built in the LENNOX factory using only components of the finest quality brands and processes conform ing to the specifications of Directive 97/23 for brazing and testing.
Compresso rs
: only scroll-type compressors of leading international manufacturers are used in the THS units. Today scroll compressors represent the best solution in terms of reliability, efficiency and MTBF.
Cooling components:
o Molecular mesh activated-alumina filter dryer o Flow indicator with humidity indicator. Indications are provided directly on the sight
glass.
o Thermostatic valve with external equaliz ation and integrated MOP function. o High and low pressure switches o Schrader valves for checks and/or maintenance
Electric control board
: The electric control board i s constructed and wired in accordance with Directives 73/23/EEC and 89/336/EEC and rel ated standards. All the remote controls use 24 V signals powered by an insulating transformer. NOTE: the mechanical safety devices such as the high pressure switch are of the kind that trigger directly; their efficiency will not be affected by any faults occurring in the microprocessor control circuit, in compliance with 97/23 PED.
Control microproce ssor
: the microprocessor built into the unit allows the different operating
parameters to be controlled from a set of pushbuttons situated on the electric control board;
o Switching on/off of compressor to maintain the temperature set point T inside the
shelter
o Alarm management
High / low pressure
MODEL
THS025 THS035 THS045 THS056 THS073 THS090 THS105 THS120 THS145
230Vac ± 10%/1Ph/50Hz 400Vac ± 10%/3Ph+N /50Hz
24± 16% Vdc emergency cooling 24± 16% Vdc emergency cooling
Power supply
48± 16% Vdc emergency cooling 48± 16% Vdc emergency cooling
Min -20°C
Temperature Outdoor
Max. 48°C 46,5°C 45°C 47°C 45°C 44°C Min. 19 °C - 30 % r .h.
Temp./humidi ty conditions
Max. 35 °C - 50 % r.h. Min. + 10° C / 90 % r.h.
Storage conditions
Max. + 55°C / 90 % r.h.
IOM / @DNOVA_THS-0508 3
Dirty filters alarm Air flow alarm
o Alarm signalling o Display of operatin g parameters o RS232, RS485 serial outp ut management (optional) o Phase sequence error [Not displayed by the mP, but prevents the compressor from
starting up]
[see microprocessor control manual for further details, also in relation to particular customer specifications]
a. Basic cooling circuit
THI 025-035 VTE
4 IOM / @DNOVA_THS-0508
THI 025-035 VTM
THI 045-145
IOM / @DNOVA_THS-0508 5
b. Installation warnings
General rules
- When installing or servicing the unit, you must strictly follow the rules provided in this manual, comply with the directions on the units themselves and take all such precautions as are necessary.
- The fluids under pressure in the cooling circuit and the presence of electrical components may cause hazardous situations during installation and m aintenance work.
All work on the unit must be carried out by qualified personnel only, trained to do
their job in accordance with current laws and regulations
- Failure to comply with the rules provided in this manual or any modification made to the unit without prior authorisation will result in the imm ediate invalidation of the warranty.
Warning: Before performing any kind of work on the unit, make sure it has been disconnected from the power supply.
6 IOM / @DNOVA_THS-0508
2. INSPECTION/TRANSPORT
a. Inspection on receipt
On receiving the unit, check that it is perf ectly intact: the unit left the factory in perfect conditions; immediately report any signs of damage to the carrier and note them on the Delivery Slip before signing it. LENNOX or its Agent must be promptly notified of the entity of the damage. The Customer must submit a written report describing every significant sign of damage.
b. Lifting and transport
While the unit is being unloaded and positioned, utmost care must be taken to avoid abrupt or violent manoeuvres. The unit must be handled carefully and gently; avoid using machine components as anchorages or holds and always keep it in an upright position. The unit should be lifted using the pallet it is packed on; a transpallet or similar conveyance means should be used.
Warning: In all lifting operations make sure that the unit is securely anchored in order to prevent accidental falls or ov erturning.
c. Unpacking
The packing m ust be carefully rem oved to avoid the risk of damaging the unit. Different packing materials are used: wood, cardboard, nylon etc. It is recommended to keep them separately and deliver them to suitable waste disposal or recycling facilities in order to minimise their environmental impact.
IOM / @DNOVA_THS-0508 7
3. INSTALLATION
The THS package air-conditioning unit is suitable for all environments except aggressive ones. Do not place any obstacles near the units and make sure that the air flow is not impeded by obstacles and/or situations causing back suction.
Positioning indoor unit
Bear in mind the following aspects when choosing the best site for installing the unit and the relative connections:
- position of the indoor unit next to the main heat source;
- location of power supply;
- solidity of the supporting ceiling/wall;
It is recommended to first prepare holes in the ceiling/wall for the screw anchors. The dimensions and the positions of the holes for the screw anchors are shown below: