Lennox T?CLASS TPA S4 Information Manual

Page 1
© 2006 Lennox Industries Inc.
Corp. 0632−L6
TPA*S4
Service Literature
3, 3.5, 4 and 5 ton
10.5, 12.3, 14 and 17.6 kW
T−CLASStTPA*S4 COMMERCIAL SERIES UNITS
The TPA*S4 is a HFC−410A commercial split-system heat pump. The series is designed for use with expansion valves (TXV). All TPA*S4 units utilize scroll compressors.
TPA*S4 series units are available in 3, 3.5, 4 and 5 ton capacities. All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the Engineering Handbook for approved system matchups.
This manual is divided into sections which discuss the major components, refrigerant system, charging procedure, maintenance and operation sequence.
Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
Table of Contents
Specifications / Electrical Data Page 2. . . . . . . . .
Optional Accessories Page 3. . . . . . . . . . . . . . . . .
I Unit Components Page 4. . . . . . . . . . . . . . . . . . .
II Refrigerant System Page 8. . . . . . . . . . . . . . . . .
III Charging Page 10. . . . . . . . . . . . . . . . . . . . . . . . .
IV Maintenance Page 16. . . . . . . . . . . . . . . . . . . . . .
V Diagrams Page 17. . . . . . . . . . . . . . . . . . . . . . . . .
MODEL NUMBER IDENTIFICATION
TPA Y1036 S 44 n
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Brand/Family
T = T−Classt Product Line
Unit Type
P = Heat Pump Outdoor Unit
Nominal Cooling Capacity − Tons
036 = 3 Tons
042 = 3.5 Tons
048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
S = Standard Efficiency
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Vol ta ge
Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz
Refrigerant Type
4 = R−410A
Part Load Capability
N = No part load, single stage compressor
Coil type
4 = Four−sided
Page 2
Revised 05−2009TPA*S4
SPECIFICATIONS
General Data
Model No. TPA036S4 TPA042S4 TPA048S4 TPA060S4
Nominal Tonnage 3 3.5 4 5
Connections (sweat)
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
Vapor line o.d. − in. 7/8 7/8 7/8 1-1/8
1
Refrigerant HFC−410A charge furnished 8 lbs. 12 oz. 10 lbs. 10 oz. 13 lbs. 2 oz. 15 lbs. 3 oz.
Outdoor Coil
Net face area
sq. ft.
Outer coil 15.21 18.66 21.11 29.09
Inner coil 14.50 17.95 20.31 28.16
Tube diameter 5/16 5/16 5/16 5/16
Number of rows 2 2 2 2
Fins per inch 22 22 22 22
Outdoor Fan
Diameter − in. − No. of Blades 18 − 4 22 − 4 22 − 4 22 − 4
Motor hp 208/230V − 1/5
460V − 1/6
1/3 1/3 1/4
Cfm 2450 3890 3890 3830
Rpm 1100 1080 1085 830
Watts 190 400 375 330
Shipping Data − lbs. 1 package 180 220 250 255
ELECTRICAL DATA
Line voltage data − 60 hz − 3ph 208/230V 460V 208/230V 460V 208/230V 460V 208/230V 460V
2
Maximum overcurrent protection (amps) 20 15 30 15 30 15 35 15
3
Minimum circuit ampacity 14.2 7.8 18.6 8.3 18.8 8.6 21.3 10.7
Compressor Rated Load Amps
10.4 5.8 13.5 6.0 13.7 6.2 15.6 7.8
Locked Rotor Amps
88 38 88 44 83.1 41 110 52
Power Factor
.85 .84 .83 .81 .90 .92 .90 .91
Outdoor Fan Motor
Full Load Amps
1.1 .55 1.7 1.0 1.7 1.0 1.7 1.0
Locked Rotor Amps
1.9 1.1 4.1 2.2 4.1 2.2 3.1 2.3
Page 3
Revised 05−2009TPA*S4
OPTIONAL ACCESSORIES − must be ordered extra
Model No. TPA036S4 TPA042S4 TPA048S4 TPA060S4
Compressor Low Ambient Cut−Off 45F08 S S S S
Compressor Sound Cover 69J03 S S S S
Freezestat 3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
Hail Guards 92M89 S
92M90 S S
12W21 S
92M94 S
4
Low Ambient Kit 54M89 S S S S
Low Ambient Control Option (down to 30°F) See table below See table below See table below See table below
Mild Weather Kit 33M07 S S S S
Monitor Kit − Service Light 76F53 S S S S
Mounting Base 69J06 S
69J07 S S S
Outdoor Thermostat Kit
Thermostat 56A87 S S S S
Mtg. Box 31461 S S S S
Refrigerant Line Sets
L15−65−30, L15−65−40, or L15−65−50 S S S
Field Fabricate S
Time Delay Relay Kit 58M51 S S S S
Unit Stand−Off Kit 94J45 S S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Freezestat is recommended with Low Ambient Kit.
LOW AMBIENT CONTROL Option (Down to 0°F)
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No. TPA036S2
TPA048S2 TPA060S2 Speed Control Kit X5867 S S S
Weatherproof Kit 56N41 S S S Outdoor
Fan Motor
1/2 HP − 230V 69H75 S S S
460V 69H76 S S S
Capacitor with mounting bracket 53H06 S S S
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Page 4
Revised 05−2009TPA*S4
I − UNIT COMPONENTS
Unit components are illustrated in figure 1.
TPA*S4 UNIT COMPONENTS
FIGURE 1
control box
service valves
compressor
reversing valve
condenser fan
drier
muffler
FIGURE 2
CAPACITOR
(C1)
COMPRESSOR
CONTACTOR
(K1)
TPA*S4 UNIT CONTROL BOX
GROUNDING
LUG
DEFROST
CONTROL
(CMC1)
DANGER
Electric Shock Hazard. May cause injury or death.
Disconnect all remote electrical power supplies before opening unit panel. Unit may have multiple power supplies.
A − Control Box (Figure 2)
TPA*S4 units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
Electrical openings are provided under the control box cover. Field thermostat wiring is made to a 24V terminal strip located on the defrost control board located in the control box. See figure 3.
24V THERMOSTAT TERMINAL STRIP
FIGURE 3
W1 C L R O Y1
1 − Compressor Contactor K1
The compressor is energized by a contactor located in the control box. See figure 2. Three−pole contactors are used in TPA*S4 series units. K1 is energized through the control board by the indoor thermostat terminal Y1 (24V) when thermostat demand is present.
2 − Capacitor C1
All units use single−phase PSC outdoor fan motors which require a run c a p a c i t o r. Ra t i n g s for c a p a c i t o r will be on fan motor nameplate. C1 aids in the start up of outdoor fan B4.
3 − Defrost System
The TPA036S4 defrost system includes two components: a defrost thermostat and a defrost control.
Defrost Thermostat
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When defrost thermostat senses 42°F (5.5°C) or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
Page 5
Revised 05−2009TPA*S4
Defrost Control
The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections. See figure 4.
The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (call for defrost), the control accumulates compressor run times at 30-, 60-, or 90-minute field−adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
TPA036S4 Outdoor Unit Defrost Control
Board
FIGURE 4
LEDs
24v terminal
strip
Timing
Pins
Test Pins
Compressor
Delay Pins
Reversing
Valve
Low Pressure Switch (S87)
High Pressure Switch (S4)
Defrost
Thermostat
Defrost Control Timing Pins
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 4). The defrost timing jumper is factory−installed to provide a 90−minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90−minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at
power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5−second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5−second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re−applied.
Compressor Delay
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.
NOTE − The 30-second off" cycle is not functional when jumpering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Pressure Switch Circuit
The defrost control incorporates two pressure switch circuits. The optional high pressure switch (S4) connects to the board’s HI PS terminals. The board also includes connections for an optional low pressure, or loss-of-charge-pressure, switch (S87). See figure 4 for switch terminal location.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch (see Table 1). The unit will remain locked out until power to the board is interrupted, then re-established or until the jumper is applied to the TEST pins for 0.5 seconds.
NOTE  The defrost control board ignores input from the low-pressure switch terminals as follows:
S during the TEST mode,
S during the defrost cycle,
S during the 90-second start-up period,
S and for the first 90 seconds each time the reversing
valve switches heat/cool modes. If the TEST pins are jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.
Page 6
Revised 05−2009TPA*S4
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
TABLE 1
Defrost Control Board Diagnostic LED
Mode Green LED (DS2)
Red LED (DS1)
No power to control OFF OFF
Normal operation / power to control
Simultaneous Slow FLASH
Anti-short cycle lock­out
Alternating Slow FLASH
Low pressure switch fault (Optional)
OFF Slow FLASH
Low pressure switch lockout (Optional)
OFF ON
High pressure switch fault (Optional)
Slow FLASH OFF
High pressure switch lockout (Optional)
ON OFF
B − Compressor
All TPA*S4 units utilize a scroll compressor. The scroll compressor design is simple, efficient and requires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 5. The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 6 shows the basic scroll form. Two identical scrolls are mated together forming concentric spiral shapes (figure 7). One scroll remains stationary, while the other is allowed to "orbit" (figure 8). Note that the orbiting scroll does not rotate or turn but merely orbits the stationary scroll.
FIGURE 5
SCROLL COMPRESSOR
DISCHARGE
SUCTION
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
FIGURE 6
SCROLL FORM
FIGURE 7
STATIONARY SCROLL
ORBITING SCROLL
DISCHARGE
SUCTION
CROSS−SECTION OF SCROLLS
TIPS SEALED BY DISCHARGE PRESSURE
DISCHARGE PRESSURE
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (figure 8 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 8 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 8 − 3). When the compressed gas reaches the center, it is discharged vertically into a chamber and discharge port in the top of the compressor (figure 7). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 7). During a single orbit, several pockets of gas are compressed simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. If the compressor is replaced, conventional Lennox cleanup practices must be used.
Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating compressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. Never use a scroll compressor for evacuating or pumping−down" the system. This type of damage can be detected and will result in denial of warranty claims.
The scroll compressor is quieter than a reciprocating compressor, however, the two compressors have much different sound characteristics. The sounds made by a scroll compressor do not affect system reliability, performance, or indicate damage.
See compressor nameplate and ELECTRICAL DATA table on page 2 for compressor specifications.
Page 7
Revised 05−2009TPA*S4
1
2
3
4
SUCTION
POCKET
SUCTION
ORBITING SCROLL
STATIONARY SCROLL
SUCTION
SUCTION
DISCHARGE
POCKET
SUCTION
INTERMEDIATE PRESSURE
GAS
CRESCENT
SHAPED
GAS POCKET
HIGH PRESSURE GAS
FLANKS SEALED
BY CENTRIFUGAL
FORCE
MOVEMENT OF ORBIT
FIGURE 8
Make sure all power is disconnected before beginning electrical service procedures.
DANGER
C − Outdoor Fan Motor B4
All units use single−phase PSC fan motors . In a l l units, t h e condenser fan is controlled by the compressor contactor (and defrost control during defrost cycles).
ELECTRICAL DATA tables in this manual show specifications for condenser fans used in TPA*S4s.
Access to the condenser fan motor on all units is gained by removing the seven screws securing the fan assembly. See figure 9. The outdoor fan motor is removed from the fan guard by removing the four nuts found on the top panel. If outdoor fan motor must be replaced, align fan hub flush with motor shaft. Drip loops should be used in wiring when servicing motor.
FAN
CONDENSER FAN MOTOR
AND COMPRESSOR ACCESS
Remove (7) screws
REMOVE (7) SCREWS
SECURING FAN GUARD.
REMOVE FAN GUARD/FAN
ASSEMBLY.
FAN GUARD
WIRING
FIGURE 9
Remove (4) nuts
ALIGN FAN HUB
FLUSH WITH
MOTOR SHAFT
D − Reversing Valve L1 and Solenoid
A refrigerant reversing valve with electro−mechanical solenoid is used to reverse refrigerant flow during unit operation. The reversing valve requires no maintenance. The only replaceable part is the solenoid. If the reversing valve itself has failed, it must be replaced.
If replacement is necessary, access reversing valve by removing the outdoor fan motor. Refer to figure 9.
E − Crankcase Heater HR1 and Optional
Thermostat S40
Crankcase heater HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by crankcase heater thermostat S40, located on the liquid line. When liquid line temperature drops below 50° F, S40 closes energizing HR1. S40 opens when liquid line temperature reaches 70°.
F − High Pressure Switch S4
S4 is a manual re−set switch located on the liquid line. When liquid line pressure rises above the factory setting of 590 + 10 psi, the switch opens and shuts off the compressor.
G − Low Pressure Switch S87
S87 is an auto−reset low pressure switch located on the suction line. The switch shuts of the compressor when suction pressure drops below the factory setting. The switch is ignored during the first 90 seconds of compressor start up, during defrost operation,90 seconds after defrost operation and during test mode. The switch is factory set to open at 25 +
5 psig and close at 40 + 5 psig. These settings
are not adjustable.
Page 8
Revised 05−2009TPA*S4
II − REFRIGERANT SYSTEM
FIGURE 10
TPA*S4 COOLING CYCLE (SHOWING MANIFOLD GAUGE CONNECTIONS)
OUTDOOR
COIL
DEFROST THERMOSTAT
EXPANSION/CHECK
VALV E
BI−FLOW
FILTER / DRIER
TO
LOW
PRESSURE
HIGH
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR
LINE
VALV E
MUFFLER
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
SERVICE
PORT
SUCTION
EXPANSION/CHECK
VALV E
INDOOR UNIT
OUTDOOR UNIT
LIQUID LINE
SERVICE
PORT
GAUGE MANIFOLD
DISTRIBUTOR
INDOOR
COIL
TO
HFC−410A
DRUM
FIGURE 11
TPA*S4 HEATING CYCLE (SHOWING MANIFOLD GAUGE CONNECTIONS)
OUTDOOR
COIL
DEFROST THERMOSTAT
EXPANSION/CHECK
VALV E
BI−FLOW
FILTER / DRIER
LOW
PRESSURE
HIGH
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR
LINE
VALV E
MUFFLER
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
SERVICE
PORT
SUCTION
EXPANSION/CHECK
VALV E
INDOOR UNIT
OUTDOOR UNIT
LIQUID LINE
SERVICE
PORT
GAUGE MANIFOLD
DISTRIBUTOR
INDOOR
COIL
TO
HFC−410A
DRUM
Page 9
Revised 05−2009TPA*S4
A − Plumbing
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections). Use Lennox L15 (sweat) series line sets as shown in table 2.
TABLE 2
Refrigerant Line Sets
Model
Field Connections
Recommended Line Set
Liquid Line
Vapor Line
Liquid Line
Vapor Line
L15 Line Sets
−036
−048
3/8 in. (10 mm)
7/8 in (22 mm)
3/8 in. (10 mm)
7/8 in (22 mm)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
−060
3/8 in. (10 mm)
1−1/8 in. (29 mm)
3/8 in. (10 mm)
1−1/8 in. (29 mm)
Field Fabricated
B − Service Valves
The liquid and vapor line service valves (figures 12 and 13) and gauge ports are accessible from outside the unit.
Each valve is equipped with a service port. The service ports are used for leak testing, evacuating, charging and checking charge. A Schrader
®
valve is factory installed. A service port
cap is supplied to protect the Schrader
®
valve from
contamination and serve as the primary leak seal.
NOTE-Always keep valve stem caps clean.
To Access Schrader® Port:
1 − Remove service port cap with an adjustable wrench.
2 − Connect gauge to the service port.
3 − When testing is completed, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Liquid or Vapor Line Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Using service wrench and hex head extension (5/16 for
vapor line and 3/16 for liquid line), back the stem out counterclockwise until the valve stem just touches the retaining ring.
3 − Replace stem cap and tighten finger tight, then tighten an
additional 1/6 turn.
Do not attempt to backseat this valve. Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result.
DANGER
To Close Liquid or Vapor Line Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Using service wrench and hex head extension (5/16 for
vapor line and 3/16 for liquid line), turn stem clockwise to seat the valve. Tighten firmly.
3 − Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
FIGURE 12
LIQUID LINE SERVICE VALVE (VALVE OPEN)
SCHRADER
®
VALV E
SERVICE
PORT
SERVICE
PORT
CAP
INSERT HEX
WRENCH HERE
TO INDOOR COIL
TO COMPRESSOR
STEM CAP
SCHRADER® VALVE OPEN
TO LINE SET WHEN VALVE IS
CLOSED (FRONT SEATED)
SERVICE
PORT
SERVICE
PORT CAP
RETAINING RING
STEM CAP
TO
COMPRESSOR
INSERT HEX
WRENCH HERE
LIQUID LINE SERVICE VALVE (VALVE CLOSED)
VALVE FRONT
SEATED
TO INDOOR COIL
SUCTION LINE (BALL TYPE) SERVICE VALVE
(VALVE OPEN)
FIGURE 13
SCHRADER® CORE
SERVICE PORT
SERVICE
PORT
CAP
STEM CAP
FROM INDOOR COIL
TO COMPRESSOR
STEM
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90_ TO CLOSE
ROTATE STEM COUNTER-CLOCKWISE 90_ TO OPEN
BALL
(SHOWN OPEN)
Page 10
Revised 05−2009TPA*S4
Vapor Line (Ball Type) Service Valve 5 ton unit only
A ball-type full service valve is used on TPA060S4N4xY units only. Va l v e s are not re−buildable. If a valve has failed it must be replaced. A ball valve is illustrated in figure 13.
The ball valve is equipped with a service port. A Schrader
®
valve is factory installed. A service port cap is supplied to protect the Schrader
®
valve from contamination and
assure a leak free seal.
III − CHARGING
A − Pumping Down System
CAUTION
Deep vacuum operation (operating compressor at 0 psig or lower) can cause internal fusite arcing resulting in a damaged or failed compressor. This type of damage will result in denial of warranty claim.
The system may be pumped down when leak checking the line set and indoor coil or making repairs to the line set or indoor coil.
1− Attach gauge manifold.
2− Front seat (close) liquid line valve.
3− Start outdoor unit.
4− Monitor suction gauge. Stop unit when 0 psig is reached.
5− Front seat (close) suction line valve.
B − Leak Testing (To Be Done Before
Evacuating)
1− Attach gauge manifold and connect a drum of dry
nitrogen to center port of gauge manifold.
2− Open high pressure valve on gauge manifold and
pressurize line set and indoor coil to 150 psig (1034 kPa).
3− Check lines and connections for leaks.
NOTE  The preferred method is to use an electronic leak or Halide detector. Add a small amount of HCFC−22 (3 to 5 psig [20kPa to 34kPa]) then pressurize with nitrogen to 150 psig.
4− Release nitrogen pressure from the system, correct any
leaks and recheck.
DANGER
When using dry nitrogen, a pressure reducing regu­lator must be used to prevent excessive pressure in gauge manifold, connecting hoses, and within the system. Regulator setting must not exceed 150 psig (1034 kpa). Failure to use a regulator can cause equipment failure resulting in injury or death.
C − Evacuating the System
1− Attach gauge manifold. Connect vacuum pump (with
vacuum gauge) to center port of gauge manifold. With both manifold service valves open, start pump and evacuate indoor coil and refrigerant lines.
IMPORTANT
A temperature vacuum gauge, mercury vacuum (U− tube), or thermocouple gauge should be used. The usual Bourdon tube gauges are not accurate enough in the vacuum range.
IMPORTANT
The compressor should never be used to evacu­ate a refrigeration or air conditioning system.
2− Evacuate the system to 29 inches (737mm) vacuum.
During the early stages of evacuation, it is desirable to stop the vacuum pump at least once to determine if there is a rapid loss of vacuum. A rapid loss of vacuum would indicate a leak in the system and a repeat of the leak testing section would be necessary.
3− After system has been evacuated to 29 inches
(737mm), close gauge manifold valves to center port, stop vacuum pump and disconnect from gauge manifold. Attach an upright nitrogen drum to center port of gauge manifold and open drum valve slightly to purge line at manifold. Break vacuum in system with nitrogen pressure by opening manifold high pressure valve. Close manifold high pressure valve to center port.
4− Close nitrogen drum valve and disconnect from
gauge manifold center port. Release nitrogen pressure from system.
5− Connect vacuum pump to gauge manifold center
port. Evacuate system through manifold service valves until vacuum in system does not rise above .5mm of mercury absolute pressure or 500 microns within a 20−minute period after stopping vacuum pump.
6− After evacuation is complete, close manifold center port ,
and connect refrigerant drum. Pressurize system slightly with refrigerant to break vacuum.
Page 11
Revised 05−2009TPA*S4
D − Charging  TPA*S4N41Y through
TPA*S4N42Y
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is
determined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1.. Close manifold gauge set valves. Connect the manifold gauge set to the service valves.
D low pressure gauge to vapor valve service port D high pressure gauge to liquid valve service port
2.. Connect the center manifold hose to an upright cylinder of HFC−410A.
3.. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
4.. Use a digital thermometer to record the outdoor ambient temperature.
5.. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68_F (20_C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
6.. The outdoor temperature will determine which charging method to use. Proceed with the appropriate charging procedure.
Charge using the Weigh−In Method − Outdoor Temperature < 65_F (18_C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit.
1.. Recover the refrigerant from the unit.
2.. Conduct leak check; evacuate as previously outlined.
3.. Weigh in the unit nameplate charge. If weighing facilities are not available or if charging the unit during warm weather, use one of the following procedures.
Charge using the Subcooling Method − Outdoor Temperature < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 200−250 psig (1379−1724 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 200−250 psig (1379−1724 kPa) range. See figure 14.
Blocking Outdoor Coil
*Outdoor coil should be blocked one side at a time with cardboard or plastic sheet until proper testing pressures are reached.
cardboard or plastic sheet
*Four−sided unit shown.
FIGURE 14
1.. With the manifold gauge hose still on the liquid service port and the unit’s pressure stabilized, use a digital thermometer to record the liquid line temperature.
2.. At the same time, record the liquid line pressure reading.
3.. Use a temperature/pressure chart for HFC−410A to determine the saturation temperature for the liquid line pressure reading.
4.. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling.
5.. Compare the subcooling value results with those in table 3. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant.
TABLE 3
TPA*S4N41Y through TPA*S4N42Y
TPA036S4 Subcooling Values for Charging
_ Saturation Temperature
_ Liquid Line Temperature
=
_ Subcooling Value
Model −036 −042 −048 −060
°F (°C)* 8 (4.4) 6 (3.3) 11 (6. 1 ) 11 (6. 1)
*F: +/−1.0°; C: +/−0.5°
Charge using the Approach Method − Outdoor Temperature >
65_F (18_C)
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1.. Record outdoor ambient temperature using a digital thermometer.
2.. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3.. Compare stabilized pressures with those provided in table 4, Normal Operating Pressures." Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
Page 12
Revised 05−2009TPA*S4
IMPORTANT
Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
4.. Use the same digital thermometer used to check outdoor ambient temperature to check liquid line temperature. Verify the unit charge using the approach method.
5.. The difference between the ambient and liquid temperatures should match the approach values given in table 5. If the values do not agree with the those in table 5, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
TABLE 4
TPA*S4N41Y through TPA*S4N42Y
Normal Operating Pressures
1
MODEL
TPA036S4N41TPA042S4N41TPA048S4N41TPA060S4N4
1
5F(5C)2Liquid/Vapor Liquid/Vapor Liquid/Vapor Liquid/Vapor
Cooling Pressures
3
65 (18)
260 / 136 231 / 135 246 / 134 256 / 116
75 (24)
303 / 140 267 / 138 286 / 136 298 / 123
85 (29)
348 / 143 314 / 140 330 / 138 345 / 131
95 (35)
398 / 145 367 / 143 379 / 140 395 / 135
105 (41)
452 / 148 414 / 146 432 / 143 450 / 138
115 (45)
512 / 151 473 / 148 492 / 146 512 / 141
Heating Pressures
3
60 (15)
350 / 131 360 / 135 361 / 130 370 / 127
50 (10)
331 / 107 340 / 110 334 / 100 350 / 102
40 (4)
314 / 88 324 / 91 302 / 92 331 / 81
30 (−1)
290 / 74 307 / 73 300 / 73 309 / 62
20 (−7)
283 / 58 298 / 61 286 / 60 300 / 56
1 These are most−popular−match−up pressures. Indoor match up,
indoor air quality, and indoor load cause pressures to vary. 2 Temperature of the air entering the outdoor coil. 3 Liquid ±10 and Vapor ±5 psig.
TABLE 5
TPA*S4N41Y through TPA*S4N42Y
TPA036S4 Approach Values for Charging
_ Liquid Line Temperature
_ Outdoor Temperature
=
_ Approach Temperature
Model −036 −042 −048 −060
°F (°C)* 13 (7.2) 9 (5) 6 (3.3) 9 (5)
NOTE − For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures.
*F: +/−1.0°; C: +/−0.5°
D − Charging  TPA*S4N43Y
This system is charged with HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The recommended check expansion valve is approved for use with HFC−410A. Do not replace it with a valve that is designed to be used with HCFC−22. This unit is NOT approved for use with coils that include metering orifices or capillary tubes.
The unit is factory−charged with the amount of HFC−410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6 m) line set. For varying line set lengths and for
various indoor unit matchups, the refrigerant charge must be adjusted per tables 6 (Page 14) and 8 (Page 15). A blank space is provided on the unit rating
plate to list the actual field charge.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a polyol ester oil.
Check Indoor Airflow before Charging
IMPORTANT
CHECK AIRFLOW BEFORE CHARGING!
NOTE − Be sure that filters and indoor and outdoor coils are clean before testing.
Page 13
Revised 05−2009TPA*S4
Step 1. Determine the desired DTMeasure entering air tempera- ture using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
Step 2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
Drop
) = A minus C.
Step 3. Determine if fan needs adjustmentIf the difference be- tween the measured T
Drop
and the desired DT (T
Drop
DT) is within
+
3º, no adjustment is needed. See examples: Assume DT = 15 and
A temp. = 72º, these C temperatures would necessitate stated ac­tions:
Cº T
Drop
DT = ºF ACTION
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +
3º range) no change
62º 10 15 = −5 Decrease the airflow
Step 4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +
3º.
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp. of air entering indoor coil ºF
INDOOR COIL
DRY BULBDRY
BULB
WET
BULB
B
T
Drop
19º
A
Dry−bulb
Wet−bulb ºF
A
72º
B
64º
C
53º
air flowair flow
All temperatures are expressed in ºF
Figure 15. Checking Indoor Airflow over Evaporator Coil using Delta−T (DT) Chart
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
OUTDOOR
COIL
CHECK
EXPANSION VALVE
BI−FLOW FILTER / DRIER
TO
HFC−410A
DRUM
LOW
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR LINE VALV E
MUFFLE
R
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
CHECK EXPANSION VALVE
INDOOR UNIT
OUTDOOR
UNIT
LIQUID
SERVICE
PORT
GAUGE
MANIFOLD
DISTRIBUTOR
INDOOR
COIL
VAPOR SERVICE PORT
HUGH
PRESSURE
LIQUID LINE VALV E
Figure 16. TPA*S4N43Y Cooling Cycle (Showing Gauge Manifold Connections)
Page 14
Revised 05−2009TPA*S4
Cooling mode indoor airflow check
Check airflow using the Delta−T (DT) process (figure 15).
Heating mode indoor airflow check
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
S temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
S measuring voltage supplied to the unit, S measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Setup for Charging
Connect the manifold gauge set to the unit’s service ports (see figure 16):
S low pressure gauge to vapor service port
S high pressure gauge to liquid service port
Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
Calculating charge
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount specified on nameplate
Adjust amt. for variation in line set length (table 6)
Additional charge specified per indoor unit matchup (table 8)
To ta l charge
+ + =
Weigh−in Charging Method
Weigh−in:
1.. Recover the refrigerant from the unit.
2.. Conduct leak check; evacuate as previously outlined.
3.. Weigh in the unit nameplate charge plus any charge required for line set differences from 15 feet and any extra indoor unit matchup amount per table 8. (If weighing facilities are not available, use the subcooling method.)
Table 6. Charge per Line Set Lengths
Liquid Line Set Diameter
Oz. per 5 ft. (g per 1.5m) adjust from 15 ft. (4.6m) line set*
3/8 in. (9.5mm) 3 ounce per 5 ft. (85g per 1.5m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Subcooling Charging Method
Requirementsthese items are required for charging:
S Manifold gauge set connected to unit. S Thermometers for measuring outdoor ambient, liquid
line, and vapor line temperatures.
When to use cooling modeWhen outdoor temperature is 60°F (15°C) and above, use cooling mode to adjust charge.
When to use heating modeWhen the outdoor temperature is below 60°F (15°C), use the heating mode to adjust the charge.
Adding Charge for Indoor MatchupsTable 8 lists all the Lennox recommended indoor unit matchups along with the charge levels for the various sizes of outdoor units.
Table 7. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
TPA*S4N43Y
Mode
5F (5C)**
TPA036S4 TPA036S4 TPA036S4 TPA036S4
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
Cooling
65 (18) 260 / 136 231 / 135 246 / 134 256 / 116 75 (24) 303 / 140 267 / 138 286 / 136 298 / 123 85 (29) 348 / 143 314 / 140 330 / 138 345 / 131 95 (35) 398 / 145 367 / 143 379 / 140 395 / 135 105 (41) 452 / 148 414 / 146 432 / 143 450 / 138 115 (45) 512 / 151 473 / 148 492 / 146 512 / 141
Heating
60 (15) 350 / 131 366 / 129 348 / 119 379 / 127 50(10) 331 / 111 348 / 110 334 / 105 361 / 109 40 (4) 314 / 91 333 / 91 312 / 84 341 / 89 30 (−1) 303 / 74 317 / 70 300 / 73 323 / 71 20 (−7) 290 / 62 298 / 58 286 / 60 310 / 60
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
Page 15
Revised 05−2009TPA*S4
Table 8. Adding Charge per Indoor Unit Matchup using Subcooling Method
Use cooling mode
Use heating mode
1. Check the airflow (figure 15, Page 13) to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following procedure.)
2. Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge.
3. Connect gauge set.
4. Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 4, (Table 4 is a general guide. Expect minor pressures variations. Significant differences may mean improper charge or other system problem.)
5. Set thermostat for heat/cool demand, depending on mode being used: Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values in table below are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6..
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target subcooling values in table below are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6..
6. Read the liquid line temperature; record in the LIQº space.
7. Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure table 13 and record it in the SATº space.
8. Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9. Compare SCº results with table below, being sure to note any additional charge for line set and/or matchup.
10. If subcooling value is greater than shown in table, remove refrigerant; if less than shown, add refrigerant.
11. If refrigerant is added or removed, repeat steps 5. through 10. to verify charge.
60ºF (15ºC)
SATº LIQº – SCº =
D − Indoor Unit Matchups  TPA*S4N43Y
Table 9. TPA036S4N43Y
INDOOR MATCHUPS
Target
Subcooling
*Add
charge
g
Heat Cool
(+
5ºF)(+1ºF)
lb oz
CBX26UH−036 17 10 2 7
CBX27UH−036−230 10 5 2 7
CBX27UH−042−230 10 10 2 13
CBX32M−036, −042 10 5 2 7
CBX32MV−036−230 10 5 2 7
CBX40UHV−036 10 5 2 7
CH33−31A, −31B 10 5 2 8
CH33−36B 10 5 0 0
CH33−36C 10 5 0 5
CH33−42 10 5 2 8
CH33−44/48B 10 5 2 10
CH33−48C 10 5 2 10
CR33−30/36 25 5 0 6
CR33−48 25 5 2 8
CR33−50/60 10 5 2 10
CX34−36B 10 5 0 1
CX34−38 SN# 6007 and after 5 5 2 7
CX34−38 before SN# 6007 10 5 2 7
CX34−42B 10 5 0 1
CX34−44/48B 10 5 2 7
Table 10. TPA042S4N43Y
INDOOR MATCHUPS
Target
Subcooling
*Add
charge
g
Heat Cool
(+
5ºF)(+1ºF)
lb oz
CBX26UH−042 26 5 1 1
CBX26UH−048 10 12 4 5
CBX27UH−042−230 10 6 4 5
CBX27UH−048−230 10 6 4 5
CBX32M−036, −042 15 5 0 0
CBX32MV−036 15 5 0 0
CBX32MV−048−230 10 6 4 5
CBX40UHV−036 15 5 0 0
CBX40UHV−042, −048 10 6 4 5
CH33−43C, −48C 10 6 1 1
CH33−49C, −50/60C 10 6 4 5
CH33−60D 10 6 2 6
CR33−48 32 5 0 5
CR33−50/60 32 9 2 6
CR33−60 32 9 2 6
CX34−43C 10 6 1 1
CX34−49 10 6 3 7
CX34−50/60C 10 6 1 1
Page 16
Revised 05−2009TPA*S4
Table 11. TPA048S4N43Y
INDOOR MATCHUPS
Target
Subcooling
*Add
charge
g
Heat Cool
(+
5ºF)(+1ºF)
lb oz
CBX26UH−048 9 11 1 7
CBX26UH−060 24 18 2 7
CBX27UH−048−230 11 11 1 3
CBX27UH−060−230 24 18 2 7
CBX32M−048 11 11 1 3
CBX32M−060 11 11 1 3
CBX32MV−048 11 11 1 3
CBX32MV−060−230 11 11 1 3
CBX40UHV−048 11 11 1 3
CBX40UHV−060 11 11 1 3
CH33−43C 18 7 0 0
CH33−49C, −50/60C 11 11 1 3
CH33−60D 11 11 0 9
CH33−62D 11 11 1 10
CR33−50/60 25 7 0 9
CR33−60 25 7 0 9
CX34−49 11 11 1 1
CX34−60D 11 11 0 9
Table 12. TPA060S4N43Y
INDOOR MATCHUPS
Target
Subcooling
*Add
charge
g
Heat Cool
(+
5ºF)(+1ºF)
lb oz
CBX26UH−060 10 11 1 7
CBX27UH−060−230 10 9 0 13
CBX32MV−060 10 9 0 0
CBX32MV−068 10 9 0 9
CBX40UHV−060 10 9 0 0
CH33−60D 10 9 0 0
CH33−62D 10 9 0 11
CX34−62D 10 9 0 6
*Amount of charge required in additional to charge shown on unit
nameplate. (Remember to consider line set length difference.)
Table 13. HFC−410A Temp. (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
−40 10.1 21 80.5 56 158.2 91 278.2
−35 13.5 22 82.3 57 161 92 282.3
−30 17.2 23 84.1 58 163.9 93 286.5
−25 21.4 24 85.9 59 166.7
94 290.8
−20 25.9 25 87.8 60 169.6 95 295.1
−18 27.8 26 89.7 61 172.6 96 299.4
−16 29.7 27 91.6 62 175.4 97 303.8
−14 31.8 28 93.5
63 178.5
98 308.2
−12 33.9 29 95.5 64 181.6 99 312.7
−10 36.1 30 97.5 65 184.3 100 317.2
−8 38.4 31 99.5 66 187.7 101 321.8
−6 40.7
32 100.8
67 190.9 102 326.4
−4 43.1 33 102.9 68 194.1 103 331
−2 45.6 34 105 69 197.3 104 335.7 0 48.2 35 107.1 70 200.6 105 340.5 1 49.5
36 109.2 71 203.9 106 345.3 2 50.9 37 111.4 72 207.2 107 350.1 3 52.2 38 113.6 73 210.6 108 355 4 53.6 39 115.8 74 214 109 360 5 55 40 118 75 217.4 110 365 6 56.4 41 120.3 76 220.9 111 370 7 57.9 42 122.6 77 224.4 112 375.1 8 59.3 43 125 78 228 113 380.2 9 60.8 44 127.3 79 231.6 114 385.4
10 62.3 45 129.7 80 235.3 11 5 390.7
11 63.9 46 132.2 81 239 116 396 12 65.4 47 134.6 82 242.7 11 7 401.3 13 67 48 137.1 83 246.5 118 406.7 14 68.6 49 139.6 84 250.3 11 9 412.2 15 70.2 50 142.2 85 254.1 120 417.7 16 71.9 51 144.8 86 258 121 423.2 17 73.5 52 147.4 87 262 122 428.8 18 75.2 53 150.1 88 266 123 434.5 19 77 54 152.8 89 270 124 440.2 20 78.7 55 155.5 90 274.1
125 445.9
IV − MAINTENANCE
At the beginning of each heating or cooling season, the system should be cleaned as follows:
A − Outdoor Unit
1 − Clean and inspect condenser coil. (Coil may be
flushed with a water hose).
NOTE − Make sure all power is disconnected before flushing coil with water.
2 − Visually inspect all connecting lines, joints and
coils for evidence of oil leaks.
NOTE-Outdoor fan motors are permanently
lubricated.
B − Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines and coil for evidence of oil
leaks.
3 − Check condensate line and clean if necessary.
C − Indoor Unit
1 − Clean or change filters. 2 − Bearings are pre-lubricated and need no further
oiling. 3 − Check all wiring for loose connections. 4 − Check for correct voltage at unit. 5 − Check amp−draw on blower motor.
Page 17
Revised 05−2009TPA*S4
V − WIRING DIAGRAM AND SEQUENCE OF OPERATION
TPA*S4 230 VOLT UNIT DIAGRAM
5
1
2
4
3
6
COOLING:
Internal thermostat wiring energizes terminal O by cooling mode selection, energizing the reversing valve L1.
1− Demand initiates at Y1 in the thermostat.
2− Assuming high pressure switch S4 and low pressure
switch S87 are closed, 24VAC energizes compressor contactor K1.
3− K1-1 N.O. closes, energizing compressor (B1) and
outdoor fan motor (B4).
END OF COOLING DEMAND:
4− Demand is satisfied. Terminal Y1 is de-energized.
5− Compressor contactor K1 is de-energized.
6− K1-1 opens and compressor (B1) and outdoor fan motor
(B4) are de-energized and stop immediately.
FIRST STAGE HEAT:
Internal thermostat wiring de−energizes terminal O by heat­ing mode selection, de−energizing the reversing valve L1.
See steps 1, 2 and 3.
End of FIRST STAGE HEAT:
See steps 4, 5 and 6.
DEFROST MODE:
During heating operation when outdoor coil temperature drops below
35°F (2°C) or 42°F (5.5°C)defrost switch (thermostat) S6 closes.
Defrost control CMC1 begins timing. If defrost thermostat (S6) remains closed at the end of the 30,60 or 90 minute period, defrost relay ener­gizes and defrost begins.
During defrost CMC1 energizes the reversing valve and W1 on the ter-
minal strip (operating indoor unit on the first stage heat mode), while de-energizing outdoor fan motor B4.
Defrost continues 14 + 1 minutes or until thermostat switch (S6) opens. When defrost thermostat opens, defrost control timer loses power and resets.
When CMC1 resets, the reversing valve and W1 on the terminal strip are de-energized, while the outdoor fan motor B4 is energized.
When CMC1 resets, the reversing valve and W1 on the terminal strip are de-energized, while the outdoor fan motor B4 is energized.
Page 18
Revised 05−2009TPA*S4
TPA*S4 460 VOLT UNIT DIAGRAM
5
1
2
4
3
6
COOLING:
Internal thermostat wiring energizes terminal O by cooling mode selection, energizing the reversing valve L1.
1− Demand initiates at Y1 in the thermostat.
2− Assuming high pressure switch S4 and low pressure
switch S87 are closed, 24VAC energizes compressor contactor K1.
3− K1-1 N.O. closes, energizing compressor (B1) and
outdoor fan motor (B4).
END OF COOLING DEMAND:
4− Demand is satisfied. Terminal Y1 is de-energized.
5− Compressor contactor K1 is de-energized.
6− K1-1 opens and compressor (B1) and outdoor fan motor
(B4) are de-energized and stop immediately.
FIRST STAGE HEAT:
Internal thermostat wiring de−energizes terminal O by heat­ing mode selection, de−energizing the reversing valve L1.
See steps 1, 2 and 3.
End of FIRST STAGE HEAT:
See steps 4, 5 and 6.
DEFROST MODE:
During heating operation when outdoor coil temperature drops below
35°F (2°C) or 42°F (5.5°C)defrost switch (thermostat) S6 closes.
Defrost control CMC1 begins timing. If defrost thermostat (S6) remains closed at the end of the 30,60 or 90 minute period, defrost relay ener­gizes and defrost begins.
During defrost CMC1 energizes the reversing valve and W1 on the ter-
minal strip (operating indoor unit on the first stage heat mode), while de­energizing outdoor fan motor B4.
Defrost continues 14 +
1 minutes or until thermostat switch (S6) opens. When defrost thermostat opens, defrost control timer loses power and resets.
When CMC1 resets, the reversing valve and W1 on the terminal strip are de-energized, while the outdoor fan motor B4 is energized.
When CMC1 resets, the reversing valve and W1 on the terminal strip are de-energized, while the outdoor fan motor B4 is energized.
Loading...