Lennox T-Class TPA090S4S, T-Class TPA120S4S Installation Instructions Manual

RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets.
INSTALLATION INSTRUCTIONS
T-CLASSt TPA Series
7.5 AND 10 TON
HEAT PUMPS
7.5 TO 10 TONS
506148-01 12/2015 Supersedes 10/2011
Table of Contents
Shipping and Packing List 1......................
Outdoor Unit 1..................................
Unit Dimensions, Corner Weights and Center of
Gravities 2.....................................
Unit Plumbing Parts Arrangement 3...............
Unit Control Box Components Arrangement 4.......
Model Number Identification 4....................
Rigging the Unit for Lifting 4......................
Installation Clearances 5.........................
Line Set 5......................................
Refrigerant Charge and Check 8..................
System Operation 11.............................
Defrost System 11...............................
Defrost Control Board 11..........................
Maintenance 12..................................
Start-up and Performance Checklist 13.............
Shipping and Packing List
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1 — Assembled outdoor unit
1 — Installation instruction
Outdoor Unit
Litho U.S.A.
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
TPA series heat pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the TP Engineering Handbook.
This outdoor unit is designed for use in thermal expansion valve (TXV) systems only.
Unit Dimensions, Corner Weights and Center of Gravities
Corner Weights
Model No.
TPA090S4S 105 48 105 48 112 51 112 51
TPA120S4S 129 59 11 0 50 123 56 145 66
5
(127)
AA BB CC DD
lbs. kg lbs. kg lbs. kg lbs. kg
91/8 (232)
11/8
(29)
11/8
(29)
LIQUID LINE
SUCTION LINE
Model No.
TPA090S4S 21.75 552 29.0 737
TPA120S4S 20.0 508 28.25 718
OUTDOOR
FAN GUARDS
CENTER OF
GRAVITY
FF
Center of Gravities
EE FF
inch mm inch mm
OPTIONAL HAIL GUARD
(Field Installed All Coil Sides)
(Not used with Coil Guard)
INLET AIR
BBAA
EE
INLET AIR
21/2
(54)
REFRIGERANT LINE
CONNECTIONS DETAIL
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
577/8 (1470)
DISCHARGE
COMPRESSOR
FORKLIFT SLOTS (Both Sides)
FRONT VIEW
AIR
601/8 (1527)
BASE
ELECTRICAL INLETS (Above Refrigerant Lines)
OPTIONAL HAIL GUARD (Field Installed All Coil Sides) (Not used with Coil Guard)
CONTROL BOX ACCESS
REFRIGERANT
LINE CONNECTIONS
SEE DETAIL
ELECTRICAL INLETS (Above Refrigerant Lines)
DD
TOP VIEW
DISCHARGE
AIR
LIFTING HOLES (For Rigging)
SIDE VIEW
413/8
(1051)
435/8
(1108)
CC
OPTIONAL
INLET AIR
BASE
(Field Installed All Coil Sides)
(Not used with Hail Guard)
COIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Hail Guard)
(286)
2 (51)
OPTIONAL
COIL GUARD
12
483/4 (1238)
451/4 (1149)
31/2
(89)
Page 2
Unit Plumbing Parts Arrangement
TPA090S4S
REVERSING
VALV E
HIGH PRESSURE
SWITCH (S4)
CHECK EXPANSIVE VALVE
(CTXV)
LOSS-OF-CHARGE
SWITCH (S24)
COIL
DEFROST SWITCH LOCATION (S6)
TPA120S4S
DEFROST SWITCH
LOCATION (S9)
COMPRESSOR
LIQUID LINE BI-FLOW DRIER
HIGH PRESSURE
SWITCH (S4)
REVERSING VALV E
SUCTION LINE SERVICE VALV E
LIQUID LINE SERVICE VALV E
CTXV SENSING BULB
DEFROST SWITCH LOCATION (S6)
CTXV SENSING BULB
COMPRESSOR
LIQUID LINE BI-FLOW DRIER
Page 3
LIQUID LINE SERVICE VALV E
COIL
CTXV SENSING BULB
LOSS OF CHARGE SWITCH (S24)
SUCTION LINE SERVICE VALV E
TP SERIES
Unit Control Box Components Arrangement
TPA090S4S AND TPA120S4S
TRANSFORMER
CONTACTOR (K1)
RUN CAPACITORS
Model Number Identification
T = T-Class Product Line
Brand/Family
P = Split System Heat Pump
Major Design Sequence
Unit Type
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity -
(T1)
(C1, C2,)
TPA Y1120 S N4 S
Tons
090 = 7.5 Tons
120 = 10 Tons
DEFROST CONTROL BOARD
RELAY (K149)
TERMINAL STRIP (TB14)
RELAY (K10)
GROUND LUG
Vol t ag e
Y = 208/230V‐3 phase‐60hz G = 460V‐3 phase‐60hz J = 575V‐3 phase‐60hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Part Load Capability
N = Single Stage Compressor
Refrigerant Circuits
S = Single Circuit
Rigging the Unit for Lifting
Rig the unit for lifting by attaching four cables to the holes in the base rail of the unit as illustrated in figure 5.
1. Remove protective packaging before rigging the unit for lifting.
Page 4
Refrigerant Type
4 = R-410A
Cooling Efficiency
S = Standard Efficiency
2. Connect the rigging to the holes in each corner of the unit's base.
3. All panels must be in place for rigging.
4. Place a field‐provided H‐style frame just above the top edge of the unit. The frame must be of adequate strength and length. (An H‐style frame will prevent the top of the unit from being damaged.)
Lifting point should be directly above the center of gravity.
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
ППППППППППППППП
Line Set
Caution - do not
walk on unit.
Important - all panels
must be in place for
rigging.
Figure 1. TPA 090S4S and TPA 120S4S
Installation Clearances
See Unit Dimensions on page to sizing mounting slab, platforms or supports. Refer to figure 2 for mandatory installation clearance requirements.
NOTES:
Field refrigerant piping consists of liquid and suction lines connecting the condensing unit and the indoor unit. Liquid and suction service valves are located in a compartment at the corner of the unit below the control box. Piping can be routed directly from the service valves or field supplied elbows can be added to divert the piping as required
Refer to table 1 for field-fabricated refrigerant line sizes for runs up to 50 linear feet (15 m).
Table 1. Refrigerant Line Sizes for Runs
Up to 50 Linear Feet
Unit Liquid Line Suction Line
TPA 090 5/8” (16 mm) 1-3/8” (35 mm)
TPA 120 5/8” (16 mm) 1-3/8” (35 mm)
Refrigerant Line Limitations
You may install the unit in applications that have line set lengths of up to 50 linear feet (15 m) with refrigerant line sizes as outlined in table 1 (excluding equivalent length of fittings). Size refrigerant lines greater than 50 linear feet (15m or greater) according to the Lennox Refrigerant Piping Design and Fabrication Guidelines (Corp. 9351-L9) or latest version.
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained
between two units.
48 in. (1219 mm) clearance required on top of unit.
SEE
NOTES
SEE
NOTES
*One of these clearance distances may be reduced to 18 inches (457 mm).
**This clearance may be reduced to 12 inches (305 mm).
Note- 48 in. (1219 mm) clearance required above top of unit.
Figure 2. TPA 090S4S and TPA 120S4S
Installation Clearances
36 (914)
30
(762)
Electrical Connections
Electric Shock Hazard. Can cause injury or death.
Line voltage is present at all components on units with single‐pole contactors, even when unit is not in operation!
Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel.
Unit must be grounded in accordance with national and local codes.
In the United States, wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
TRANSFORMER - 24VAC, 70VA - PROVIDED
NOTE — The addition of accessories to the system could exceed the 70VA power requirement of the factory‐provided transformer. Measure the system's current and voltage after installation is complete to determine transformer loading. If loading exceeds the factory‐provided transformer capacity, a larger field‐provided transformer will need to be installed in the system.
Page 5
TP SERIES
CIRCUIT SIZING AND DISCONNECT SWITCH
1
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
TYPICAL HIGH VOLTAGE POWER SUPPLY
2
CONNECTIONS
CONTROL BOX
USE THE LEFT CUTOUT TO ROUTE HIGH VOLTAGE WIRING TO THE K1 CONTACTOR ON THE TPA 090S AND 120S MODELS.
K1 CONTACTOR
GROUND LUG
LEFT CUTOUT
NOTE — ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING.
Refer to the unit nameplate for minimum circuit ampacity amperage minimum, and maximum fuse or circuit breaker fusible (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE — UNITS ARE APPROVED FOR USE ONLY WITH COPPER CONDUCTORS. GROUND UNIT AT DISCONNECT SWITCH OR TO AN EARTH GROUND.
INSTALL THERMOSTAT
3
THERMOSTAT
5 FEET
(1.5M)
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
HIGH VOLTAGE WIRING
CONNECT EARTH GROUND TO GROUND LUG
TYPICAL CONTROL WIRING
4
TPA HEAT
PUMP
R
C1
W1
W2
C
TAA AIR
HANDER
RO
C1
W1
W2
C
A2
THERMOSTAT
R
S1
S2
Y1
W
W2
C
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
RT2 REMOTE
SENSOR
TYPICAL UNIT LOW VOLTAGE CONNECTIONS
5
K1 CONTACTOR
HIGH VOLTAGE WIRING
EARTH GROUND CONNECTION
CONTROL BOX
ROUTE THROUGH WIRE TIES
B
TIGHTEN WIRE TIES
D
RIGHT CUTOUT
A
WIRE NUTS
LOW VOLTAGE CONTROL
C
WIRING
Page 6
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
A Run control wires through right cutout. B Run control wires through wire ties. C Make control wire connections using field
provided wire nuts. See figure 3 for connections requirements.
D Tighten wire tie to secure 24V low voltage
control wiring.
NOTE — FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.
NOTE — WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE — DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
Figure 3. TPA090S4S and TPA120S4S G, J, M, and Y Voltages) Typical Wiring Diagram
Page 7
TP SERIES
Refrigerant Charge and Check
TPA units have a factory holding charge of 1 pound of HFC-410A. Additional refrigerant will need to be added during installation (table 2).
Table 2. Adding Refrigerant
Models
TPA090 /
TAA090
TPA120 /
TAA120
(2) TPA090 /
TAA240
1
Total amount of charge necessary to accommodate 25
25 Feet
(pounds)
17 5/8 1-3/8 1.8
23 5/8 1-3/8 1.8
3
23
Line
Diameter
(inches)
5/8 1-3/8 1.8
Liquid
1
Vapor
Line
Diameter
(inches)
feet of line set.
2
If line set length is greater than 25 feet, add this amount to each circuit. If line set is less than 25 feet, subtract this amount from each circuit. Refer to Lennox Refrigerant Piping Design and Fabrication Guidelines for more information.
3
Charge amount per outdoor unit. NOTE - Refrigerant line sets longer than 200 feet (60 meters)
are not recommended. For assistance contact Lennox Application Department.
To charge the system, use either of the following procedures:
CHARGE PROCEDURE — NORMAL OPERATING PRESSURES
1. Connect a manifold gauge set to the service valves:
A Low pressure gauge to vapor service port. B High pressure gauge to liquid valve service port
2. Operate system in cooling mode until pressures and temperatures stabilize (5 minutes minimum).
3. Use a thermometer to measure the outdoor ambient temperature. The outdoor temperature will determine which charging procedure to use.
Outdoor Temp > 65ºF (18ºC)
1. Apply the outdoor ambient temperature to tables 4 or 5 to determine normal operating pressures. Compare the normal operating pressures to the pressures obtained from the connected gauges. If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refrigerant to the system.
A Add or remove charge in increments. B Allow the system to stabilize at least 5 minutes
each time refrigerant is added or removed
2. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
3. Switch to heating mode to confirm normal operating pressures. Let the system stabilize at least 10 minutes
Adjustment
per foot of
2
Line
(Ounces)
then compare the pressure obtained from the connected gauges to the normal operating pressures (heating mode) in table 5.
4. Verify the charge, as described in the approach method section.
Outdoor Temp < 65ºF (18ºC)
1. When the outdoor ambient temperature is below 65F (18C) it may be necessary to restrict the air flow through the outdoor coil to achieve liquid pressures in the 325-375 psig (2240-2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of the outdoor coil on all coil sides until the liquid pressure is in the 325-375 psig range (figure 4).
2. Charge the system as described in the approach method section.
3. Switch to heating mode and let the system stabilize at least 10 minutes. Then confirm that the pressures obtained from the connected gauges match the normal operating pressures (heating mode) in table 5
4. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
CARDBOARD OR PLASTIC SHEET
OUTDOOR COIL SHOULD BE BLOCKED ONE SIDE AT A TIME WITH CARDBOARD OR PLASTIC SHEET UNTIL PROPER TESTING PRESSURES ARE REACHED.
Figure 4. Blocking Outdoor Coil
PROCEDURE — APPROACH METHOD
Use the following approach method along with the normal operating pressures in cooling mode to confirm readings.
1. Using the same thermometer, compare liquid temperature at service valve to outdoor ambient temperature.
Approach Temperature = Liquid temperature
minus ambient temperature
2. Approach temperature should be as indicated in table 3 for each stage. An approach temperature greater then this value indicates an undercharge. An approach temperature less than this value indicates an overcharge.
A Add or remove charge in increments. B Allow the system to stabilize at least 5 minutes
each time refrigerant is added or removed
Page 8
Table 3. HFC-410A Approach Temperatures
TPA090 / TAA090
TPA120 / TAA120
TPA090 / TAA090
TPA120 / TAA120
Approach
Models
TPA090S4S /
TAA090
TPA120S4S /
TAA120
(2) TPA090S4S
/ TAA240
Stage
1, 2 8.0 4.4
Temperature (F)
(+/- 1)
1 7.0 3.8
1 8.0 4.4
Approach
Temperature (C)
(+/- 0.5)
3. Do not use the approach method if system pressures do not match pressures in tables 4 or 5 except when the outdoor ambient temperature is below 65
(18ºC).
The approach method is not valid for grossly
over or undercharged systems.
Table 4. HFC-410A Normal Operating Pressures — Cooling Mode (Liquid +10 and Suction +5 psig)
(2) TPA090 / TAA240
Temp*
Liquid Suction Liquid Suction Liquid Suction Liquid Suction
65 F (18 C)
75 F (24 C)
85 F (29 C)
95 F (35 C)
105 F (41 C)
115  F (46 C)
125 F (52 C)
231 128 243 130 239 132 239 132
265 130 281 133 289 135 289 135
310 131 325 136 322 137 322 137
358 134 372 139 370 140 370 140
410 137 427 140 422 142 422 142
467 140 478 142 480 145 480 145
551 146 548 142 541 148 541 148
*Temperature of air entering outdoor Coil
Stage 1 Stage 2
ºF
Table 5. HFC-410A Normal Operating Pressures — Heating Mode (Liquid +10 and Suction +5 psig)
(2) TPA090 / TAA240
Temp*
Liquid Suction Liquid Suction Liquid Suction Liquid Suction
60 F (15 C)
50 F (10 C)
47 F (8 C)
40 F (4 C)
30 F (-1 C)
20 F (-6 C)
17 F (-8 C)
384 116 367 120 394 117 394 117
366 101 350 105 376 102 376 102
361 96 345 101 370 97 370 97
348 85 333 91 357 87 357 87
330 70 316 76 338 72 338 72
312 55 299 61 320 57 320 57
307 50 294 57 314 52 314 52
*Temperature of air entering outdoor Coil
Stage 1 Stage 2
Page 9
TP SERIES
Table 6. HFC-410A Temperature (°F) - Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 11 9 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Page 10
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
HIGH PRESSURE SWITCHES (S4 AND S7)
These units are equipped with a auto‐reset high pressure switch (single-pole, single-throw) which is located on the discharge line. The switch shuts off the compressor when discharge pressure rises above the factory setting. High
Pressure (auto reset) - trip at 640 psig, reset at 512 psig.
LOSS-OF-CHARGE SWITCH (S24)
These units are equipped with a loss-of-charge switch that is located on the liquid line. The switch is a SPST, auto-reset switch that is normally closed. The switch opens at 40 psi and closes at 90 psi.
Defrost System
The defrost system includes a defrost thermostat and a defrost control.
DEFROST THERMOSTAT
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor on each coil. When the defrost thermostat senses 42°F (5.5°C) or cooler, its contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
DEFROST CONTROL
The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, time delay, diagnostic LEDs, and a terminal strip for field wiring connections.
The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (defrost thermostat is closed, calling for defrost), the control accumulates compressor run times at 30, 60, or 90 minute field adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. The maximum defrost period is 14 minutes and cannot be adjusted.
NOTE — Defrost control part number is listed near the P1 timing pins.
Units with defrost control 100269-02: The factory
default defrost interval is 60 minutes.
Units with defrost control 100269-04 or higher: The
factory default defrost interval is 90 minutes.
If the timing selector jumper is missing, the defrost control defaults to a 90-minute defrost interval.
Defrost Control Board
DEFROST CONTROL TIMING PINS
FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S24
LOSS-OF-CHARGE
HIGH PRESSURE
SWITCH
DEFROST
THERMOSTAT
S4
SWITCH
Figure 5. Outdoor Unit Defrost Control Board
A TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is operating in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at
power‐up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied.
COMPRESSOR DELAY
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When the compressor delay jumper is removed, the compressor will be cycled off for 30 seconds going in and out of the defrost mode.
NOTE — The 30‐second compressor feature is ignored when the TEST pins have been jumpered.
TIME DELAY
The timed-off delay is five minutes long. The delay helps protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
NOTE — The board must have a thermostat demand for the bypass function.
LEDS
24V TERMINAL STRIP CONNECTIONS
SERVICE LIGHT CONNECTIONS
Page 11
TP SERIES
PRESSURE SWITCH CIRCUITS
The defrost control includes two pressure switch circuits. The factory-installed high pressure switch (S4) wires are connected to the board's HI PS terminals (figure 5). The board also includes LO PS terminals to accommodate the factory installed loss-of-charge switch.
During a single thermostat cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch that is wired to the control board. In addition, the diagnostic LEDs will indicate a pressure switch lockout after the fifth occurrence of an open pressure switch (table 7). The unit will remain locked out until power is broken then remade to the control or until the jumper is applied to the TEST pins for 0.5 seconds.
NOTE — The defrost control board ignores input from the loss-of-charge switch terminals during the TEST mode, during the defrost cycle, during the 90-second start-up period, and for the first 90 seconds each time the reversing valve switches heat/cool modes. If the TEST pins are
jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.
SERVICE LIGHT CONNECTION
The defrost control board includes terminal connections for a service light which provides a signal that activates the room thermostat service light during periods of inefficient operation.
IMPORTANT
After testing has been completed, properly reposition test jumper across desired timing pins.
DIAGNOSTIC LEDS
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the diagnosis (table 7).
Table 7. Defrost Control Board Diagnostic LEDs
DS2 Green DS1 Red Condition
OFF OFF Power problem
Simultaneous Slow Flash Normal operation
Alternating Slow Flash 5-min. anti-short cycle delay
Fault and Lockout Codes
OFF Slow Flash Loss-of-Charge Fault
OFF ON Loss-of-Charge Lockout
Slow Flash OFF High Pressure Fault
ON OFF High Pressure Lockout
Maintenance
At the beginning of each cooling season, the system should be checked as follows:
OUTDOOR UNIT
1. Clean and inspect the condenser coil. You can flush the coil with a water hose.
2. The outdoor fan motor is prelubricated and sealed. No further lubrication is necessary.
3. Visually inspect connecting lines and coils for evidence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at the unit while the unit is operating and while it is off.
6. Check amp-draw of the outdoor fan motor.
Unit Nameplate _________ Actual ____________
7. Check amp-draw of the compressor.
Unit Nameplate _________ Actual ____________
NOTE - If the owner complains of insufficient cooling, gauge the unit and check the refrigerant charge. Refer to section on refrigerant charging in this instruction.
INDOOR COIL
1. If necessary, clean the coil.
2. Check connecting lines and coils for evidence of oil leaks.
3. If necessary, check the condensate line and clean it.
INDOOR UNIT
1. Clean or change filters.
2. Adjust the blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. On belt drive blowers, check the belt for wear and proper tension.
4. Check all wiring for loose connections.
5. Check for correct voltage at the unit (blower operating).
6. Check amp-draw on blower motor.
Unit Nameplate _________ Actual ____________
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Page 12
Start-Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Vapor Pressure;
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?
THERMOSTAT
Properly Set?  Level? 
Page 13
TP SERIES
Loading...