These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HFCs, and HCFCs) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook. Coils
previously charged with HCFC−22 must be flushed.
NOTICE TO INSTALLER
UNIT PLACEMENT
It is critical for proper unit operation to place outdoor unit on an
elevated surface as described in Unit Placement section on page 8.
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on
page 11 to avoid damaging the service valve’s internal seals.
06/11506648−01
*2P0611**P506648-01*
Shipping and Packing List
Check the unit components for shipping damage. If you
find any damage, immediately contact the last carrier.
1 Assembled outdoor unit
1 Liquid line bi−flow filter drier
General
The T−Class TPA*S4 outdoor units use HFC−410A HFC
refrigerant. This unit must be installed with a matching
indoor blower coil and line set as outlined in the Lennox
Engineering Handbook. TPA*S4 outdoor units are
designed for use in expansion valve systems only. They
are not designed to be used with other refrigerant flow
control devices. An expansion valve approved for use with
HFC−410A must be ordered separately and must be
installed prior to operating the unit.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air
conditioning components, ensure the fasteners are
appropriately tightened. Table 1 lists torque values for
fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc −
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for
small valves, to 25 ft−lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes #C−08−1
for further details and information.
IMPORTANT
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 provides
torque values for fasteners.
Table 1. Torque Requirements
PartsRecommended Torque
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 psig on the high side and a low
side of 30" vacuum to 250 psig with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a
factory−installed valve stem. Figure 2 provides information
on how to access and operating both angle and ball service
valves.
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
Page 4
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
CLOSED) INSERT HEX
WRENCH HERE
SERVICE PORT
CORE
TO OUTDOOR UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
When service valve is OPEN, the service port is
open to linE set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
rotate stem counterclockwise 90°. To close rotate stem
clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN
CLOSED)
VALV E
STEM
STEM CAP
STEM CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
WHENSERVICEVALVE ISCLOSED,THESERVICEPORTISOPEN
TO
THELINE SETANDINDOORUNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and
serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
With torque wrench: Finger tighten and
torque cap per table 1.
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
9
10
8
11
12
7
6
With Torque Wrench: Finger tighten and
then torque cap per table 1.
Without Torque Wrench: Finger tight-
en and use an appropriately sized
wrench to turn an additional 1/12 turn
clockwise.
9
10
8
11
12
7
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
3
4
5
NOTE A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 5
TPA*S4 SERIES
Recovering Refrigerant from Existing System
RECOVERING
REFRIGERANT FROM SYSTEM
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the service
1
disconnect switch or main fuse box/breaker panel.
SERVICE
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing refrigerant using one of the following procedures:
3
IMPORTANT Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the
instructions provided with the recovery machine to make the
connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY
CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing to
flush the system.
Remove all refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.
Compressor can stop pumping due to tripped internal pressure relief valve.
Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.
Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and
internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the
main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
AStart the existing system in the cooling mode and close the liquid line valve.
BUse the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
CWhen the low side system pressures reach 0 psig, close the vapor line valve.
DCheck gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Page 6
CLEARANCE ON ALL SIDES INCHES (MILLIMETERS)
MINIMUM CLEARANCE
ABOVE UNIT
6 (152)
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
DETAIL A
Install unit away
from windows .
DETAIL C
If unit coil cannot be
mounted away from prevailing winter winds, a wind barrier should be constructed.
Size barrier at least the
same height and width as
outdoor unit. Mount barrier
24 inches (610 mm) from the
sides of the unit in the direction of prevailing winds as illustrated.
30 (762)
LINE SET
CONNECTIONS
TWO UNITS
24 (610)
PREVAILING WINTER WINDS
INLET AIR
Figure 4. Placement, Slab Mounting and Wind Barrier
ACCESS PANEL
NOTES:
Clearance to one of the other three
Clearance to one of the remaining
Figure 3. Installation Clearances
Two 90° elbows
installed in line set will
reduce line set vibration.
WIND BARRIER
INLET AIR
INLET AIR
sides must be 36 inches (914mm).
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
DETAIL B
These units operate under a wide range of weather conditions;
therefore, several factors must be considered when positioning the
outdoor unit. The unit must be positioned to give adequate clearances
for sufficient airflow and servicing.
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
Install the unit high enough above the ground or roof to allow
adequate drainage of defrost water and prevent ice or snow
build−up.
In heavy snow areas, do not locate the unit where drifting will
occur. The unit base should be elevated above the depth of
average snows. Stand−off kits are available for ordering using
either catalog numbers 94J45 (4 each) or 30K79 (20 each).
When installed in areas where low ambient temperatures exist,
locate unit so winter prevailing winds do not blow directly onto
outdoor unit.
Locate unit away from overhanging roof lines which would allow
water or ice to drop on, or in front of, coil or unto unit.
INLET AIR
MOUNTING SLAB MUST SLOPE
AWAY FROM BUILDING.
STRUCTURE
48 (1219)
DISCHARGE AIR
GROUND LEVEL
Page 7
TPA*S4 SERIES
New Unit Placement
See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to figure 3 for mandatory
installation clearance requirements.
POSITIONING CONSIDERATIONS
CAUTION
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the
rubber to swell when it comes into contact with oil. The
rubber will then bubble and could cause leaks. Protect
the roof surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow this
notice could result in damage to roof surface.
In order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 4.
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground would not collect around the unit as
illustrated in figure 4.
Slab may be level or have a slope tolerance away from the
building of not more than two degrees, or 2 inches per 5
feet (51 mm per 1524 mm) as illustrated in figure 4.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above
the surface of the roof. Ensure the weight of the unit is
properly distributed over roof joists and rafters. Redwood
or steel supports are recommended. Refer to figure 4,
detail c, for rooftop wind barrier considerations.
Table 2. Refrigerant Line Set Inches (mm)
Model
TPA036S4N4
TPA042S4N4
TPA048S4N4
TPA060S4N43/8 in. (10 mm)1−1/8 in. (29 mm)3/8 in. (10 mm)1−1/8 in. (29 mm)Field Fabricated
NOTE Some applications may required a field provided 7/8" to 1−1/8" adapter
Liquid LineVapor LineLiquid LineVapor LineL15 Line Sets
3/8 in. (10 mm)7/8 in. (22 mm)3/8 in. (10 mm)7/8 in. (22 mm)L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field ConnectionsRecommended Line Set
New or Replacement Line Set
This section provides information on new installation or
replacement of existing line set. If a new or replacement
line set is not required, then proceed to BrazingConnections on page 11.
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds.
Also, consider the following when placing and installing a
high−efficiency air conditioner:
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or braze connections). Use Lennox L15 (braze,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed in table 2.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol ester oil.
The compressor is charged with sufficient Polyol ester oil
for line set lengths up to 50 feet. Recommend adding oil to
system based on the amount of refrigerant charge in the
system. No need to add oil in system with 20 pounds of
refrigerant or less. For systems over 20 pounds − add one
ounce of every five pounds of refrigerant.
Page 8
Recommended topping−off POE oils are Mobil EAL
ARCTIC 22 CC or ICI EMKARATE RL32CF.
NOTE When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351−L9, or contact
Lennox Technical Support Product Applications for
assistance.
To obtain the correct information from Lennox, be sure to
communicate the following points:
Model (TPA*S4) and size of unit (e.g. −060).
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.
If the TPA*S4 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served
as a metering device (RFCI), the liquid line must be
replaced prior to the installation of the TPA*S4 unit.
Typically a liquid line used to meter flow is 1/4" in diameter
and copper.
IMPORTANT
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
Page 9
TPA*S4 SERIES
LINE SET
INSTALLATION
Line Set Isolation The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
AUTOMOTIVE
MUFFLER-TYPE HANGER
IMPORTANT Refrigerant lines must not contact structure.
REFRIGERANT LINE SET INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater
than 20 psig.
IMPORTANT Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL
STUD
STRAP LIQUID LINE TO
VAPOR LINE
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED
IN ARMAFLEX
REFRIGERANT LINE SET INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
WIRE TIE (AROUND
VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE
METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST
OR RAFTER AT 8 FEET (2.43 METERS)
INTERVALS THEN STRAP THE LIQUID
LINE TO THE VAPOR LINE.
TAPE OR
WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
STRAP
NON−CORROSIVE
METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID
LINE
NOTE Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
WARNING Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT
remove line set caps or service valve stub caps until you are ready
to make connections.
Figure 5. Line Set Installation
Page 10
Brazing Connections
Use the procedures outline in figures 6 and 7 for brazing
line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture − Check the high and low
pressures before applying heat.
IMPORTANT
Connect gauge set low pressure side to vapor line
service valve and repeat procedure starting at
paragraph 4 for brazing the liquid line to service port
valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well−ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver
alloy for copper−to−copper brazing. Use 45% minimum
alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an explosion, that could result in property
damage, personal injury or death.
Page 11
TPA*S4 SERIES
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the
2
vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT
CORE
LIQUID LINE SERVICE
VALV E
SUCTION / VAPOR LINE
SERVICE VALVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
AConnect gauge set low pressure side to
liquid line service valve (service port).
BConnect gauge set center port to bottle of
nitrogen with regulator.
CRemove Schrader valve in suction / vapor
line service port to allow nitrogen to escape.
ATTACH
GAUGES
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
SERVICE
PORT
CORE
SERVICE
PORT CAP
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
B
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 6. Brazing Procedures
OUTDOOR
UNIT
NITROGEN
Page 12
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use another
4
saturated cloth underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
BRAZE LINE SET
Wrap both service valves with a saturated cloth as illustrated here before brazing to line set.
6
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT Allow braze joint to cool. Apply
additional saturated cloths to help cool brazed joint.
Do not remove wet rag until piping has cooled.
Temperatures above 250ºF will damage valve seals.
LIQUID LINE
SATURATED CLOTH
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY
DAMAGE will result if you do not wrap a wet cloth
around both liquid and suction line service valve
bodies and copper tube stub while brazing in the line
set! The braze, when complete, must be quenched
with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and
indoor coil have been leak−tested and evacuated.
Refer to procedures provided in this supplement.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
7
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply saturated rags to both services valves to cool
piping. Once piping is cool, remove all wet cloths. Refer to the unit installation instructions for the next step in preparing the unit.
SUCTION / VAPOR LINE
SERVICE VALVE
SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 7. Brazing Procedures (continued)
Page 13
TPA*S4 SERIES
Flushing Line Set and Indoor Coil
Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering
Device on page 15.
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps holding the liquid line and distributor as-
sembly.
CUsing two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this process.
DRemove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
EUse a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
REMOVAL PROCEDURE
(UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON® RING
FIXED ORIFICE
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
2
INVERTED CYLINDER
CONTAINS CLEAN TO
BE USED FOR
FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
VAPOR
LIQUID
D
RECOVERY
CYLINDER
AInverted cylinder with clean refrigerant to the vapor service valve.
B gauge set (low side) to the liquid line valve.
C gauge set center port to inlet on the recovery machine with an empty
recovery tank to the gauge set.
DConnect recovery tank to recovery machines per machine instructions.
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps holding the liquid line and distributor
assembly.
CDisconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
DRemove the vapor line sensing bulb.
EDisconnect the liquid line from the check expansion valve at the liquid
line assembly.
FDisconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
GRemove and discard check expansion valve and the two Teflon® rings.
HUse a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
ORIFICE
HOUSING
EQUALIZER
LINE
STUB END
TEFLON
RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
LINE
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.
ASet the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.
B
BInvert the cylinder of clean and open its valve to allow liquid
refrigerant to flow into the system through the vapor line valve.
Allow the refrigerant to pass from the cylinder and through the
line set and the indoor unit coil before it enters the recovery
machine.
CAfter all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the vapor is
recovered. Allow the recovery machine to pull down to 0 the
system.
DClose the valve on the inverted drum and the gauge set valves.
Pump the remaining refrigerant out of the recovery machine and
turn the machine off.
Figure 8. Removing Metering Device and Flushing
Page 14
Installing Indoor Metering Device
This outdoor unit is designed for use in systems that use
expansion valve metering device (purchased separately)
at the indoor coil.
See the Lennox TPA*S4 Engineering Handbook for
approved expansion valve kit match ups. The expansion
valve unit can be installed internal or external to the indoor
coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the expansion
valve in a manner that will provide access for field servicing
of the expansion valve. Refer to below illustration for
reference during installation of expansion valve unit. .
After installation of the indoor coil metering device,
proceed to Leak Test Line Set and Indoor Coil on page 16.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
VAPOR
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
SENSING
LIQUID LINE
Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
ARemove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure to the right.
BRemove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on
the vapor line as illustrated in the figure to the right.
®
LINE
ARemove the field−provided fitting that temporary
reconnected the liquid line to the indoor unit’s distributor
assembly.
BInstall one of the provided Teflon® rings around the
stubbed end of the expansion valve and lightly lubricate
the connector threads and expose surface of the Teflon
ring with refrigerant oil.
CAttach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft−lb.
DPlace the remaining Teflon® washer around the other
end of the expansion valve. Lightly lubricate connector
threads and expose surface of the Teflon® ring with
refrigerant oil.
EAttach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to
turn an additional 1/2 turn clockwise as illustrated in the
figure above or 20 ft−lb.
SENSING BULB INSTALLATION
AAttach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE Confirm proper thermal contact between vapor line
and expansion bulb before insulating the sensing bulb once
installed.
BConnect the equalizer line from the expansion valve to
the equalizer vapor port on the vapor line. Finger tighten
the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
VAPOR LINE
VAPOR LINE
12
BULB
NOTE NEVER MOUNT ON BOTTOM OF LINE.
Figure 9. Installing Indoor Expansion Valve
Page 15
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT ON
BOTTOM OF LINE.
BULB
TPA*S4 SERIES
IMPORTANT
Leak Test Line Set and Indoor Coil
The Environmental Protection Agency (EPA) prohibits
the intentional venting of HFC refrigerants during
maintenance, service, repair and disposal of appliance.
Approved methods of recovery, recycling or reclaiming
must be followed.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
CONNECT GAUGE
SET
AConnect an HFC−410A manifold gauge set high pressure
1
hose to the vapor valve service port.
NOTE Normally, the high pressure hose is connected to
the liquid line port. However, connecting it to the vapor port
better protects the manifold gauge set from high pressure
damage.
BWith both manifold valves closed, connect the cylinder of
HFC−410A refrigerant to the center port of the manifold gauge
set.
NOTE Later in the procedure,
the HFC−410A container will be
replaced by the nitrogen
container.
IMPORTANT
Leak detector must be capable of sensing HFC
refrigerant.
After completing the leak testing the line set and indoor coil
as outlined in figure 10, proceed to Evacuating Line Setand Indoor Coil on page 17.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
A
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the
2
following procedure to test for leaks:
AWith both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve
on the HFC−410A cylinder (vapor only).
BOpen the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder
and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
CConnect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
DAdjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
and the indoor unit.
EAfter a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak
detector.
FAfter leak testing disconnect gauges from service ports.
NITROGEN
HFC−410A
Figure 10. Leak Test
Page 16
TO VAPOR
SERVICE VALVE
Evacuating Line Set and Indoor Coil
CONNECT GAUGE SET
NOTE Remove cores from service valves (if not already done).
1
AConnect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line
service valve
BConnect high side of manifold gauge
set to liquid line service valve
CConnect micron gauge available
connector on the 1/4 SAE in−line tee.
DConnect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC−410A and nitrogen containers.
NITROGEN
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
C
MICRON
GAUGE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
LOW
D
EVACUATE THE SYSTEM
AOpen both manifold valves and start the vacuum pump.
2
BEvacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
CWhen the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves
Close valve on vacuum pump
Turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
DShut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
EReconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
FWhen the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.
GPerform the following:
Close manifold gauge valves.
Shut off HFC−410A cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
RECOMMEND
MINIMUM 3/8" HOSE
10
9
8
1/6 TURN
12
11
7
HIGH
1
2
3
4
5
6
Figure 11. Evacuating System
Page 17
TPA*S4 SERIES
WARNING
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are
defined as any gas that will not condense under
temperatures and pressures present during operation of
an air conditioning system. Non−condensables and water
suction combine with refrigerant to produce substances
that corrode copper piping and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air
handler for low-voltage control power (24VAC − 40 VA
minimum)
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker (HACR per NEC). Install power wiring and properly
sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
NOTE Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m) from
the floor. It should not be installed on an outside wall or where it can be
affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE 24VAC, Class II circuit connections are made in the control
panel.
Page 18
WARNING
Electric Shock Hazard. Can cause injury
or death.
Line voltage is present at all components
on units with single-pole contactors, even
when unit is not in operation!
Unit may have multiple power supplies.
Disconnect all remote electric power supplies before opening access panel.
Unit must be grounded in accordance
with national and local codes.
Figures 14 and 15 show typical outdoor unit wiring
diagrams for the TPA*S4 heat pumps.
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
1. Install line voltage power supply to unit from a properly
sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box
using a proper conduit fitting.
NOTE − Units are approved for use only with copper
conductors. 24V, Class II circuit connections are
made in the low voltage junction box (see figs. 14 and
15).
NOTE − A complete unit wiring diagram is located
inside the unit control box cover.
NOTE − For proper voltages, select thermostat wire
gauge per the following chart:
Wire run lengthAWG #Insulation type
less than 100’ (30m)18
more than 100’ (30m)16
3. Install room thermostat (ordered separately) on an
inside wall approximately in the center of the
conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it
can be effected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit (see figs. 12 and
13).
color−coded, temperature
rating 35ºC minimum
ThermostatIndoor Unit
R
C
W1
G
O
Y1
power
common
1st. stage aux. heat
indoor blower
reversing valve
compressor
(SOME CONNECTIONS MAY NOT APPLY. REFER
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
R
C
W1
W2
W3
G
1st. stage aux. heat
power
common
Outdoor Unit
R
C
W1
O
Y1
Figure 12. Low Voltage Wiring
ThermostatIndoor UnitOutdoor Unit
R
C
E
W1
G
O
Y1
power
common
emergency heat
1st. stage aux. heat
indoor blower
reversing valve
compressor
(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)
W1
W2
W3
R
C
emer.
heat
relay
G
power
common
outdoor t’stat
1st. stage aux. heat
R
C
W1
O
Y1
Figure 13. Low Voltage Wiring (with aux. heat)
Three-Phase Scroll Voltage Phasing
Three-phase scroll compressors must be phased
sequentially to ensure correct compressor rotation and
operation. Incorrect line voltage phasing may cause
compressor damage and abnormal unit operation. Power
wires are color-coded as follows: Line 1 − red, line 2 − yellow,
line 3 − blue. To test for proper rotation and operation:
1. Install refrigeration gauges on system. Cycle
compressor On" and observe that suction pressure
decreases and discharge pressure increases.
2. If pressures do not follow the above conditions,
disconnect all power to unit. Reverse any two
field−installed main power wires to the line side of the
compressor contactor. Make sure connections are tight.
Repeat pressure test with system.
Page 19
TPA*S4 SERIES
Figure 14. Typical Unit Wiring Diagram (Y Voltage)
Figure 15. Typical Unit Wiring Diagram (G Voltage)
If the outdoor unit is void of refrigerant, clean the system
using the procedure described below.
1. Leak check system using procedure outlined on page
16.
2. Evacuate the system using procedure outlined on
page 17.
3. Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again using procedure outlined
on page 17.
5. Weigh in refrigerant using procedure outlined in figure
20.
Start−Up
IMPORTANT
Crankcase heater (if applicable) should be energized 24
hours before unit start−up to prevent compressor damage as a result of slugging.
1. Check that fan rotates freely.
2. Inspect all factory and field-installed wiring for loose
connections.
3. Open the liquid line and vapor line service valves
(counterclockwise) to release refrigerant charge
(contained in outdoor unit) into the system.
4. Replace the stem caps and tighten as specified in
Operating Service Valves on page 4.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
power company has been consulted and the voltage
condition has been corrected.
6. Set the thermostat for a cooling demand, turn on
power to indoor blower unit and close the outdoor unit
disconnect to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the
procedures listed under System Refrigerant.
System Charge
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
CHARGE IN
LIQUID PHASE
D
TEMPERATURE
SENSOR
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for
liquid phase charging.
INSIDE OUTDOOR UNIT
BConnect the manifold gauge set’s low pressure side to the true suction port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port.
REFRIGERANT TANK
DIGITAL SCALE
TO LIQUID
LINE SERVICE
MANIFOLD GAUGE SET
LOW
HIGH
A
C
VALV E
TEMPERATURE SENSOR
(LIQUID LINE)
OUTDOOR UNIT
LIQUID LINE
SERVICE
PORT
Figure 18. Gauge Set Connections
Page 23
TPA*S4 SERIES
ADDING OR REMOVING REFRIGERANT
Check airflow using the Delta−T (DT) process using the illustration in figure 19.
1. Determine the desired DTMeasure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between
B
A
72º
B
64º
WET
BULB
DRY
BULB
the measured T
+
3º, no adjustment is needed. See examples: Assume DT =
15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
53º 19–15 =4Increase the airflow
58º14–15=−1 (within +3º range) no change
62º10–15=−5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
–DT=ºF ACTION
Drop
and the desired DT (T
Drop
) = A minus C.
Drop
–DT) is within
Drop
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within
3º.
+
Figure 19. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for
verifying refrigerant charge.
WEIGH IN
OUTDOOR UNIT VOID OF CHARGE
CHARGING METHOD
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the
CALCULATING SYSTEM CHARGE FOR
unit. To calculate the total refrigerant charge:
Amount specified on
nameplate
NOTE Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Adjust amount. for variation
in line set length listed on
line set length table below.
+
Additional charge specified
per indoor unit match−ups
starting on page 25.
+
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Total charge
=
Figure 20. Weigh In Method
Page 24
SUBCOOLING
g
g
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
1 Check the airflow as illustrated in figure 19 to be sure the indoor airflow is as
required. (Make any air flow adjustments before continuing with the following
procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode
or heating mode to check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal
Operating Pressures table 7, (The reference table is a general guide. Expect
minor pressure variations. Significant differences may mean improper charge or
other system problem.)
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and
above. Target subcooling values in table below are based on 70 to 80°F (21−27°C)
indoor return air temperature; if necessary, operate heating to reach that
temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC).
When pressures have stabilized, continue with step 6.
SATº
LIQº –
SCº=
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C).
Target subcooling values in table below are based on 65−75°F (18−24°C) indoor
return air temperature; if necessary, operate cooling to reach that temperature range;
then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have
stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the
temperature/ pressure chart listed in table 8 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with table below, being sure to note any additional charge for
line set and/or match−up.
10 If subcooling value is greater than shown in tables 3 through 6 for the applicable unit,
remove refrigerant; if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
Figure 21. Using Subcooling Method
Table 3. TPA*S4−036
Target
INDOOR MATCHUPS
CBX26UH−036171027
CBX27UH−036−23010527
CBX27UH−042−23010102 13
CBX32M−036, −04210527
CBX32MV−036−23010527
CBX40UHV−03610527
CH33−31A, −31B10528
CH33−36B10500
CH33−36C10505
CH33−4210528
CH33−44/48B105210
CH33−48C1052 10
CR33−30/3625506
CR33−4825528
CR33−50/601052 10
CX34−36B10501
CX34−38 SN# 6007 and after5527
CX34−38 before SN# 600710527
CX34−42B10501
CX34−44/48B10527
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lboz
Table 4. TPA*S4−042
Target
INDOOR MATCHUPS
CBX26UH−04226511
CBX26UH−048101245
CBX27UH−042−23010645
CBX27UH−048−23010645
CBX32M−036, −04215500
CBX32MV−03615500
CBX32MV−048−23010645
CBX40UHV−03615500
CBX40UHV−042, −04810645
CH33−43C, −48C10611
CH33−49C, −50/60C10645
CH33−60D10626
CR33−4832505
CR33−50/6032926
CR33−6032926
CX34−43C10611
CX34−4910637
CX34−50/60C10611
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lboz
Page 25
TPA*S4 SERIES
Table 5. TPA*S4−048
g
g
Target
INDOOR MATCHUPS
CBX26UH−04891117
CBX26UH−060241827
CBX27UH−048−230111113
CBX27UH−060−230241827
CBX32M−048111113
CBX32M−060111113
CBX32MV−048111113
CBX32MV−060−230111113
CBX40UHV−048111113
CBX40UHV−060111113
CH33−43C18700
CH33−49C, −50/60C111113
CH33−60D111109
CH33−62D11111 10
CR33−50/6025709
CR33−6025709
CX34−49111111
CX34−60D111109
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lboz
Table 7. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Table 6. TPA*S4−060
Target
INDOOR MATCHUPS
CBX26UH−060101117
CBX27UH−060−2301090 13
CBX32MV−06010900
CBX32MV−06810909
CBX40UHV−06010900
CH33−60D10900
CH33−62D1090 11
CX34−62D10906
*Amount of charge required in additional to charge shown on unit
nameplate. (Remember to consider line set length difference.)
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lboz
Use table 7 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer
to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some
component in the system.
The unit is equipped with a large−capacity bi−flow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of the same design and capacity.
The replacement filter drier must be suitable for use with
HFC−410A refrigerant.
Low Pressure Switch (S87)
The TPA*S4 is equipped with an auto−reset low pressure
switch which is located on the vapor line. The switch shuts
off the compressor when the vapor pressure falls below the
factory setting. This switch, which is ignored during defrost
operation, closes at pressures at or above 40 psig and
opens at 25 psig. It is not adjustable.
High Pressure Switch (S4)
The TPA*S4 is equipped with a manual-reset high
pressure switch (single−pole, single−throw) which is
located on the liquid line. The switch shuts off the
compressor when discharge pressure rises above the
factory setting. The switch is normally closed and is
permanently adjusted to trip (open) at 590 + 10 psig (4412
+ 69 kPa).
NOTE − A Schrader core is under the pressure switches.
MANUAL RESET
BUTTON
System Operation
IMPORTANT
Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.
The outdoor unit and indoor blower cycle on demand from
the room thermostat. If the thermostat blower switch is in
the ON position, the indoor blower operates continuously.
Figure 22. High Pressure Switch (S4) Manual Reset
Crankcase Heater (HR1) and Thermostat Switch
(S40)
Compressor in models listed below are equipped with a 40
watt belly band type crankcase heater. HR1 prevents liquid
from accumulating in the compressor. HR1 is controlled by
a single pole, single throw thermostat switch (S40) located
on the liquid line (see figure 1 for location).
When liquid line temperature drops below 50°F the
thermostat closes energizing HR1. The thermostat will
open, de−energizing HR1 once liquid line temperature
reaches 70° F.
Page 27
TPA*S4 SERIES
Defrost System
The TPA*S4 defrost system includes two components: a
defrost thermostat (S6) and a defrost control (CMC1).
FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT
S4
HIGH PRESSURE
SWITCH
Figure 23. Defrost Control (CMC1)
Defrost Thermostat (S6)
The defrost thermostat is located on the liquid line between
the check/expansion valve and the distributor. When
defrost thermostat senses 42°F (5.5°C) or cooler, the
thermostat contacts close and send a signal to the defrost
control to start the defrost timing. It also terminates defrost
when the liquid line warms up to 70°F (21°C).
Defrost Control (CMC1)
The defrost control includes the combined functions of a
time/temperature defrost control, defrost relay, diagnostic
LEDs and terminal strip for field wiring connections. See
figure 23.
The defrost control provides automatic switching from
normal heating operation to defrost mode and back. When
the defrost thermostat is closed, the control accumulates
compressor run time at 30, 60 or 90 minute field adjustable
intervals. When the selected compressor run time interval
is reached, the defrost relay is energized and defrost
begins.
Defrost Control Timing Pins (P1)
Each timing pin selection provides a different
accumulated compressor run time period for one defrost
cycle. This time period must occur before a defrost cycle
is initiated. The defrost interval can be adjusted to 30
(T1), 60 (T2), or 90 (T3) minutes (see figure 23). The
maximum defrost period is 14 minutes and cannot be
adjusted.
NOTE Defrost control part number is listed near the P1
timing pins.
Units with defrost control 100269−02: Factory default
is 60 minutes
LEDS
24V TERMINAL
STRIP
CONNECTIONS
Units with defrost control 100269−04: Factory default
is 90 minutes
If the timing selector jumper is missing, the defrost
control defaults to a 90−minute defrost interval.
Compressor Delay (P5)
The defrost control has a field−selectable function to
reduce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode.
Units with defrost control 100269−02: The compressor
will be cycled off for 30 seconds going in and out of the
defrost mode when the compressor delay jumper is
removed.
Units with defrost control 100269−04: The compressor
will be cycled off for 30 seconds going in and out of the
defrost mode when the compressor delay jumper is
installed.
NOTE The 30-second compressor feature is ignored
when jumpering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps to
protect the compressor from short-cycling in case the
power to the unit is interrupted or a pressure switch opens.
The delay is bypassed by placing the timer select jumper
across the TEST pins for 0.5 seconds.
Test Mode (P1)
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or
jumpered. If the jumper is in the TEST position at
power-up, the defrost control will ignore the test pins.
When the jumper is placed across the TEST pins for two
seconds, the defrost control will enter the defrost mode. If
the jumper is removed before an additional 5−second
period has elapsed (7 seconds total), the unit will remain in
defrost mode until the defrost thermostat opens or 14
minutes have passed. If the jumper is not removed until
after the additional 5−second period has elapsed, the
defrost will terminate and the test option will not function
again until the jumper is removed and re−applied.
Defrost Control Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition.
Table 9. Defrost Control (CMC1) Diagnostic LEDs
ModeGreen LED (DS2)Red LED (DS1)
No power to control
Normal operation /
power to control
Anti-short cycle
lockout
High pressure
switch fault
High pressure
switch lockout
OFFOFF
Simultaneous Slow FLASH
Alternating Slow FLASH
Slow FLASHOFF
ONOFF
Page 28
Maintenance
Outdoor Unit
1. Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed.
No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
MotorNameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and
clean if necessary.
OWNER
Cleaning of the outdoor unit’s coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit. The
following maintenance may be performed by the
homeowner.
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure of the
unit to treated water (i.e., sprinkler systems, soakers,
waste water, etc.) will corrode the surface of steel and
aluminum parts and diminish performance and longevity
of the unit.
NOTE - If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge should be
checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more
frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)
Outdoor Coil The outdoor coil may be flushed with
a water hose.
Outdoor Coil (Sea Coast) Moist air in ocean
locations can carry salt, which is corrosive to most
metal. Units that are located near the ocean require
frequent inspections and maintenance. These
inspections will determine the necessary need to wash
the unit including the outdoor coil. Consult your
installing contractor for proper intervals/procedures
for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and
permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper
tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of
oil leaks.
3. Check condensate line and clean if necessary.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its
proper operation.
Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
Make sure no obstructions restrict airflow to the
outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more
energy.
Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the
unit.
Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air Filter Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either
at the indoor unit (installed internal or external to the
cabinet) or behind a return air grille in the wall or
ceiling. Check the filter monthly and clean or replace
it as needed.
2. Disposable Filter Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.
3. Reusable Filter Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
NOTE The filter and all access panels must be in place
any time the unit is in operation.
4. Indoor Unit The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
Page 29
TPA*S4 SERIES
Thermostat Operation
See the thermostat homeowner manual for instructions on
how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45F (7C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
EMERGENCY HEAT setting to obtain temporary heat
without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is locked
out. After a six-hour compressor crankcase warm-up
period, the thermostat can be switched to the HEAT setting
and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before
calling for service:
Verify room thermostat settings are correct.
Verify that all electrical disconnect switches are ON.
Check for any blown fuses or tripped circuit breakers.
Verify unit access panels are in place.
Verify air filter is clean.
If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update−to−date information, see any of the following
publications:
Lennox TPA*S4 Engineering Handbook
Lennox Product Catalog
Lennox Price Book
Cleaning Outdoor Coil
1. Make sure power is off before cleaning. Clean and
inspect outdoor coil. The coil may be flushed with a
water hose.
2. The outdoor coil is protected by an inner mesh screen
and a wire cage (see figure 24). If debris has collected
between the mesh screen and the coil and cannot be
dislodged by spraying unpressurized water from
inside coil surface to the outside, the mesh may be
removed by first removing the top of the unit which will
allow for removal of the wire cage.
3. Then, using pliers to grip the head of the push pins, pull
straight out to extract the push pins along one side of
the coil. If necessary, remove the push pins along the
back of the unit; it is usually unnecessary to fully
remove the inner mesh screen.
4. Drape the mesh screen back and wash the coil. When
all the debris has been removed from the coil, reinstall
the mesh screen by positioning it in its original position
and reinserting the push pin. No tool is required to
push the pin back into the same slot in the fins.
5. If the push pin is loose and tends not to stay in place,
brush the fins with a fin brush (22 fins/in). Line up the
push pin a couple fins to the right or left of the original
hole and re−insert the pin.
9 PINS USED ON −048
AND −060; 6 PINS ALL
OTHERS
PUSH PIN
MESH SCREEN
Figure 24. Cleaning Debris from Mesh
Page 30
TPA*S4 Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.