Lennox T?CLASS TAA SERIES, TAA072, TAA090, TAA120, TAA150 Installation Instructions Manual

...
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTALLATION INSTRUCTIONS
T−CLASSE TAA SERIES
AIR HANDLERS 6 TO 20 TONS
506149−01 04/11 Supersedes 8/09
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
TAA072 and TAA090 Unit Dimensions 2. . . . . . . . . . .
TAA120 and TAA150 Unit Dimensions 3. . . . . . . . . . .
TAA180 and TAA240 Unit Dimensions 4. . . . . . . . . . .
Unit Parts Arrangement 5. . . . . . . . . . . . . . . . . . . . . . . .
Unit Control Box Components Arrangement 6. . . . . . .
Typical Installation Support Method 6. . . . . . . . . . . . . .
Requirements 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping Connections 7. . . . . . . . . . . . . . . . . .
Installing Condensate Drain 8. . . . . . . . . . . . . . . . . . . . .
Duct Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sealing the Unit 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Belt Tensioning Adjustment 12. . . . . . . . .
Pulley Alignment 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Volume Adjustment 13. . . . . . . . . . . . . . . . . . . . . . . . .
Blower Data 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Drive Components 15. . . . . . . . . . . . . . . . . . . . . .
Blower Performance 16. . . . . . . . . . . . . . . . . . . . . . . . . . .
Repairing or Replacing Cabinet Insulation 20. . . . . . . . .
Optional Accessories 20. . . . . . . . . . . . . . . . . . . . . . . . . .
General
The TAA Series air handler units are designed for installation with a matched remote outdoor unit that is charged with HFC−410A refrigerant and optional field−installed electric heat. The air handler units are for indoor installation only and are designed for upflow or horizontal applications.
Litho U.S.A.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Foil-faced insulation has conductive characteristics sim­ilar to metal. Be sure there are no electrical connections within a ½" of the insulation. If the foil-faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause person­al injury or death.
08/ 506149−01
*2P08* *P506149-01*
Shipping and Packing List
Package contains the following: 1  Assembled blower coil unit 8  Supply and return air flanges which are stored inside
unit and are listed in table 2, on page 9. 1  Bag assembly that consists of the following:
S One installation instruction S Two wiring diagrams (unit wiring and thermostat
connections)
S Six plastic grommets (various sizes) for line set
knockouts.
Check package contents for shipping damage; if found, immediately report damage to the last carrier.
Page 1
TAA072 and TAA090 Unit Dimensions − Inches (mm)
CORNER WEIGHTS CENTER OF GRAVITY
Model No.
TAA072 88 40 88 40 88 40 88 40 25−1/2 648 25−1/2 648 TAA090 88 40 88 40 88 40 88 40 25−1/2 648 25−1/2 648
P−FLOW POSITION SHOWN
29−1/2
(749)
AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
51−1/4 (1302)
SUPPLY AIR
OPENING
CONTROL BOX
(Alternate Location)
18−5/8
(473)
POWER
ENTRY HOLES
NOTE:
072 models only use one Suction and Liquid Line. Cabinet has knockouts for two. Either opening may be used.
BB
AA
SUPPLY END VIEW
51−1/4 (1302)
1 (25)
TYP.
25−3/4
(654)
EE
FF
(762)
SIDE RETURN
AIR OPENING
1 (25)
RETURN AIR FLANGES
TYP.
(Furnished with Unit,
Field Installed)
30 (762)
RETURN AIR OPENING
(Bottom or Horizontal Applications)
INLET VIEW DRIVE END VIEW
CENTER OF
GRAVITY
30
1−3/8
(35)
20−5/8
(524)
16−7/8
(429)
CONTROL
10−3/4
(267)
2
(51)
BOX
SUPPLY AIR FLANGES
(Furnished with Unit,
Field Installed)
CC
54−3/4 (1391)
26−1/4
(667)
DD
RETURN AIR FLANGES
(Furnished with Unit,
Field Installed)
1−3/8
(35)
CONTROL
BOX
2
(51)
CONDENSATE
DRAIN
(Horizontal)
20−5/8
(524)
1−5/8
(41)
29−1/2
(749)
18−5/8
(473)
AIR FLOW
BLOWER
INDOOR
COIL
AIR FLOW
AIR FILTERS
AIR FLOW
20−5/8 (524)
RETURN AIR
(Bottom or Horizontal Applications)
OPENING
3
(76)
CONTROL BOX (Alternate Location)
3
(76)
SUCTION (VAPOR) LINE INLETS / KNOCKOUTS (2)
LIQUID LINE INLETS / KNOCKOUTS (2)
16−1/2
14
(419)
(356)
11−7/8
(302)
1−7/8
(48)
CONDENSATE
DRAIN (Up−flow)
18−5/8
(473)
506149−01 04/11
Page 2
TAA120 and TAA150 Dimensions − Inches (mm)
CENTER OF GRAVITY
Model No.
CORNER WEIGHTS
AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
TAA120−150 126 57 101 46 101 46 126 57 33−1/2 851 24−1/2 622
UP−FLOW POSITION
SHOWN
67−1/4
29−1/2
(749)
(1708)
SUPPLY AIR
OPENING
CONTROL BOX
(Alternate Location)
18−5/8
(473)
1−3/8
(35)
POWER
ENTRY HOLES
CONTROL
BOX
SUPPLY END VIEW
BB
AA
FF
1 (25)
TYP.
67−1/4
(1708)
1 (25)
TYP.
EE
RETURN AIR FLANGES
(Furnished with Unit, Field Installed)
(Bottom or Horizontal Applications)
25−3/4
(654)
CENTER OF
GRAVITY
45
(1143)
SIDE RETURN
AIR OPENING
45 (1143)
RETURN AIR OPENING
20−5/8
(524)
24−7/8
(429)
SUPPLY AIR FLANGES
(Furnished with Unit,
Field Installed)
CC
54−3/4 (1391)
11−1/8
(283)
DD
RETURN AIR FLANGES
2
(Furnished with Unit,
(51)
Field Installed)
CONTROL
CONDENSATE
DRAIN
(Horizontal)
20−5/8
(524)
26−1/4
(667)
1−3/8
(35)
BOX
2
(51)
AIR FLOW
1−5/8
(41)
(Bottom or Horizontal Applications)
29−1/2
(749)
18−5/8
(473)
AIR FLOW
BLOWER
INDOOR
COIL
AIR FILTERS
AIR FLOW
20−5/8 (524)
RETURN AIR
OPENING
(76)
3
(76)
CONTROL BOX (Alternate Location)
3
SUCTION (VAPOR) LINE INLETS/KNOCKOUTS (2)
LIQUID LINE INLETS/KNOCKOUTS (2)
18−5/8
(473)
11−7/8
(302)
1−7/8
(48)
CONDENSATE
DRAIN (Up−Flow)
16−1/2
(419)
14
(356)
INLET VIEW DRIVE END VIEW
Page 3
TAA SERIES
TAA 180 and TAA 240 Unit Dimensions − Inches (mm)
CENTER OF GRAVITY
Model No.
CORNER WEIGHTS
AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
TAA180−240 110 50 99 45 116 53 130 59 52 1321 25−3/4 654
UP−FLOW POSITION SHOWN
96−1/4
29−1/2
(749)
(2445)
SUPPLY AIR
OPENING
CONTROL BOX
(Alternate Location)
18−5/8
(473)
1−3/8
(35)
POWER
ENTRY
HOLES
CONTROL
BOX
SUPPLY END VIEW
AA
BB
1 (25)
TYP.
1 (25)
TYP.
FF
96−1/4 (2445)
51−5/8 (1311)
CENTER OF
EE
SIDE RETURN
AIR OPENING
RETURN AIR FLANGES
(Furnished with Unit, Field Installed)
59−1/4 (1505)
RETURN AIR OPENING
(Bottom or Horizontal Applications)
GRAVITY
59−1/4 (1505)
20−5/8
(524)
27−1/2
(699)
(Furnished with
CC
18−1/2
(470)
DD
2
RETURN AIR FLANGES
(51)
(Furnished with Unit,
Field Installed)
SUPPLY AIR
FLANGES
Unit, Field
Installed)
CONTROL
54−3/4 (1391)
CONDENSATE
(Horizontal)
26−1/4
(667)
1−3/8
(35)
BOX
2
(51)
DRAIN
20−5/8
(524)
AIR FLOW
1−5/8
(41)
(Bottom or Horizontal Applications)
29−1/2
(749)
18−5/8
(473)
AIR FLOW
BLOWER
INDOOR
COIL
AIR FILTERS
AIR FLOW
20−5/8 (524)
RETURN AIR
OPENING
CONTROL BOX (Alternate Location)
3
(76)
SUCTION (VAPOR) LINE INLETS/KNOCKOUTS (2)
LIQUID LINE INLETS/ KNOCKOUTS (2)
11−7/8
(302)
1−7/8
(48)
3
(76)
CONDENSATE
DRAIN (Up−Flow)
16−1/2
(419)
14
(356)
18−5/8
(473)
INLET VIEW DRIVE END VIEW
506149−01 04/11
Page 4
Unit Parts Arrangement
All TAA Series
HORIZONTAL POSITION SHOWN
BLOWER
BLOWER BELT
CONTROL BOX
072−090−120−150 MODELS
HORIZONTAL POSITION SHOWN
CONDENSATE DRAIN
COIL
BELT TENSIONER
COIL
BLOWER MOTOR
BLOWER MOTOR
ADJUSTABLE PULLEY
LIQUID LINES
VAPOR LINES
CONDENSATE
DRAIN POSITION
FOR UPFLOW))
ADJUSTABLE PULLEY
BLOWERS
BLOWER BELT
CONTROL BOX
180−240 MODELS
BELT TENSIONER
CONDENSATE DRAIN (HORIZONTAL)
LIQUID LINES
VAPOR LINES
CONDENSATE DRAIN
POSITION FOR
UPFLOW))
Page 5
TAA SERIES
Unit Control Box Components Arrangement
All TAA Series
RELAY (K43)
TERMINAL
STRIP (TB1)
BLOWER
CONTACTOR
(K3−1)
Y, G, AND J VOLTAGE WIRING
GROUND
LUG
Typical Installation Support Method
CONTROL PANEL
THREE−PHASE THERMAL
OVERLOAD RELAY (S42)
M VOLTAGE OVERLOAD WIRING
4 (102) TAA072, 090, 120, 150
10 (254) TAA180, 240
RECOMMENDED SUPPORT RAILS
TAA AIR HANDLER
(HORIZONTAL POSITION)
4 (102) TAA072, 090, 120,150
10 (254) TAA180, 240
ELECTRIC or HOT
WATER SECTION
NOTES:
1. Ensure support rails do not interfere with ducting, plumbing or electrical connections.
2. When hot water or electric heat section is installed, additional support underneath these accessories will be required.
3. Support rods and rails are field supplied.
SUPPORT RODS (4)
506149−01 04/11
Page 6