Lennox SSBH4, SSB036H4, SSB048H4, SSB060H4 User Manual

Corp. 0628−L5
Revised 02−2007
Service Literature
SSB*H4 Commercial Air Conditioner
The SSB*H4 is a high efficiency commercial split−system condensing unit, which features a two stage scroll compres­sor and R−410A refrigerant. SSB*H4 units are available in 3, 4and 5 ton capacities.. The series is designed for use with an expansion valve (approved for use with R−410A) in the indoor unit. This manual is divided into sections which dis­cuss the major components, refrigerant system, charging procedure, maintenance and operation sequence. Information contained in this manual is intended for use by qualified service technicians only. All specifications are sub­ject to change.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
SSB*H4
WARNING
Warranty will be voided if covered equipment is re­moved from original installation site. Warranty will not cover damage or defect resulting from: Flood, wind, lightning, or installation and operation in a corrosive atmosphere (chlorine, fluorine, salt, recycled waste water, urine, fertilizers, or other dam­aging chemicals).
DANGER
Shock Hazard Remove all power at disconnect
before removing access panel. Single phase SSB*H4 units use single-pole contactors. Potential exists for electrical shock resulting in injury or death. Line voltage exist at all components (even when unit is not in operation).
IMPORTANT
Operating pressures of this R−410A unit are higher than pressures in R−22 units. Always use service equipment rated for R410A.
TABLE OF CONTENTS
General Page 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical Data Page 2. . . . . . . .
I Application Page 4. . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components Page 4. . . . . . . . . . . . . . . . . .
III Refrigeration System Page 12. . . . . . . . . . . . . .
IV Charging Page 13. . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery Page 17. . . . . . . . . . . . .
VI Maintenance Page 17. . . . . . . . . . . . . . . . . . . . .
VII Wiring and Sequence of Operation Page 18.
Page 1
©2006 Lennox Industries Inc.
SPECIFICATIONS
General Data
Connections (sweat)
Refrigerant
Outdoor Coil
Model No. SSB036H4 SSB048H4 SSB060H4
Nominal Tonnage 3
4 5
Liquid line (o.d.) − in. 3/8 3/8 3/8
Suction line (o.d.) − in. 7/8
1
R−410A charge furnished 8 lb. 9 oz. 11 lb. 4 oz. 14 lb. 2 oz.
Net face area − sq. ft.
Outer coil 16.33 21.00 24.93
Inner coil 15.76
7/8 1−1/8
20.27 24.14
Tube diameter − in. 5/16 5/16 5/16
No. of rows 2 2 2
Fins per inch 22 22 22
Outdoor Fan
Diameter − in. 22 22 26
No. of blades 4
4 3
Motor hp 1/6 1/4 1/3
Cfm 3060 3955 4380
Rpm 845 835 850
Watts 215 320 280
Shipping Data − lbs. 1 pkg. 229 257 309
ELECTRICAL DATA
Line voltage data − 60hz 208/230V−3ph 460V−3ph 208/230V−3ph 460V−3ph 208/230V−3ph 460V−3ph
2
Maximum overcurrent protection (amps) 25 10 30 15 40 20
3
Minimum circuit ampacity 15.04 6.20 18.53 8.91 23.83 12.21
Compressor
Rated load amps 11.15 4.48 13.46 6.41 17.62 8.97
Outdoor Fan Motor
Locked rotor amps 58 29 88 41 135 62
Power factor 0.99 0.99 0.99 0.99 0.99 0.99
Full load amps 1.1 0.6 1.7 0.9 1.8 1.0
Locked Rotor amps 2.1 1.1 3.1 2.1 2.9 2.0
Page 2
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Low Ambient Cut−Off 45F08
Compressor Time−Off Control 47J27
Freezestat
3/8 in. tubing 93G35
5/8 in. tubing 50A93
Indoor Blower Relay 40K58
Low Ambient Kit (down to 30°F) 34M72
Low Ambient Control Option (down to 0°F) See table below See table below See table below
Refrigerant Line Sets
L15−65−30 L15−65−40
L15−65−50
Field Fabricate
Time Delay Relay 58M81
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
LOW AMBIENT CONTROL Option (Down to 0°F)
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No. SSB036H4
Speed Control Kit X5867
Weatherproof Kit 56N41
Outdoor Fan Motor
1/2 HP − 208/230V 69H75
460V 69H76
Capacitor with bracket 53H06
SSB048H4 SSB060H4
Page 3
I − APPLICATION
SSB*H4 condensing units are available in 3, 4 and 5 ton ca­pacities. All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the Engi­neering Handbook for approved system matchups.
II − UNIT COMPONENTS
Unit components are illustrated in figure 1.
SSB*H4 PARTS ARRANGEMENT
Removing/Installing Louvered Panels
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or installing) panel.
SCREW HOLES
LIP
Detail
A
DUAL CAPACITOR
CONTACTOR
FILTER DRIER
OUTDOOR FAN
COMPRESSOR
HIGH
PRESSURE
SWITCH
LOW
PRESSURE
SWITCH
FIGURE 1
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
Remove the louvered panels as follows: 1 − Remove 2 screws, allowing the panel to swing open
slightly (see figure 2).
Detail
B
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
Detail C
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail D
FIGURE 2
2 − Hold the panel firmly throughout this procedure. Ro-
tate bottom corner of panel away from hinge corner post until lower 3 tabs clear the slots (see figure 2, Detail B).
3 − Move panel down until lip of upper tab clears the top slot
in corner post (see figure 2, Detail A).
Page 4
Position and Install PanelPosition the panel almost par­allel with the unit (figure 2, Detail D) with the screw side" as close to the unit as possible. Then, in a continuous motion:
Slightly rotate and guide the lip of top tab inward (figure 2,
Details A and C); then upward into the top slot of the
hinge corner post. Rotate panel to vertical to fully engage all tabs. Holding the panel’s hinged side firmly in place, close the
right−hand side of the panel, aligning the screw holes. When panel is correctly positioned and aligned, insert the
screws and tighten.
A − Control Box (Figure 3)
SSB*H4 units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
Electrical openings are provided under the control box cov­er. Field thermostat wiring is made to color-coded pigtail connections.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the con­trol and the technician at the same electrostatic po­tential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface be­fore performing any service procedure.
1 − Compressor Contactor K1
The compressor is energized by a single−pole contactor lo­cated in the control box. See figure 3. K1 is energized by the indoor thermostat terminal Y1 (24V) when thermostat de­mand is present.
2 − Dual Capacitor C12
The compressor and fan in SSB*H4 series units use per­manent split capacitor motors. The capacitor is located inside the unit control box (see figure 3). A single dual" capacitor (C12) is used for both the fan motor and the compressor (see unit wiring diagram). The fan side and the compressor side of the capacitor have different MFD ratings. See side of capacitor for ratings.
CAUTION
In order to avoid injury, take precaution when lifting heavy objects.
B − Two−Stage Scroll Compressor (B1)
TWO−STAGE MODULATED SCROLL
slider ring
COMPRESSOR
CONTACTOR
(K1)
GROUNDING
LUG
CONTROL BOX
FIGURE 3
DUAL CAPACITOR
(C12)
solenoid actuator coil
FIGURE 1
The scroll compressor design is simple, efficient and re­quires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 1.The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent proper­ties. Figure 2 shows the basic scroll form. Two identical scrolls are mated together forming concentric spiral shapes (figure 3 ). One scroll remains stationary, while the other is allowed to orbit" (figure 4). Note that the orbiting scroll does not rotate or turn but merely orbits" the stationary scroll.
Page 5
SCROLL FORM
FIGURE 2
CROSS−SECTION OF SCROLLS
DISCHARGE PRESSURE
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (figure 4 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 − 2). As the orbiting motion con­tinues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4 −3). When the compressed gas reaches the center, it is discharged vertical­ly into a chamber and discharge port in the top of the com­pressor (figure1). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 3 ). During a single orbit, several pockets of gas are compressed simultaneously providing smooth con­tinuous compression.
The scroll compressor is tolerant to the effects of liquid re­turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. If the com­pressor is replaced, conventional Lennox cleanup practices must be used.
Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com­pressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. This type of damage can be detected and will result in denial of warranty claims. The scroll com­pressor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
The scroll compressors in all HSXA19 model units are de­signed for use with R410A refrigerant and operation at high pressures. Compressors are shipped from the factory with 3MA (32MMMA) P.O.E. oil. See electrical section in this manual for compressor specifications.
TWO−STAGE OPERATION
The two−stage scroll compressor operates like any standard scroll compressor with the exception the two−stage com­pressor modulates between first stage (low capacity approximately 67%) and second stage (high capacity). Modulation occurs when gas is bypassed through bypass ports (figure 5 bypass ports open) in the first suction pocket. This bypassing of gas allows the compressor to operate on first stage (low capacity) if thermostat demand allows. In­door thermostat setting will determine first or second stage operation. The compressor will operate on first−stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second−stage.
Second−stage (high capacity) is achieved by blocking the bypass ports (figure 5 bypass ports closed) with a slider ring. The slider ring begins in the open position and is controlled by a 24VDC internal solenoid. On a Y2 call the internal sole- noid closes the slider ring, blocking the bypass ports and bringing the compressor to high capacity. Two−stage modu­lation can occur during a single thermostat demand as the motor runs continuously while the compressor modulates from first−stage to second− stage.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
Page 6
Loading...
+ 13 hidden pages