Lennox SPBH4 Unit Information

Page 1
Page 1
©2006 Lennox Industries Inc.
Corp. 0629−L5
Revised 07−2010
SPB*H4
Service Literature
SCLASSt SPB*H4 Commercial Heat Pump
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
TABLE OF CONTENTS
Specifications / Electrical Page 2. . . . . . . . . . . . .
I Unit Information Page 5. . . . . . . . . . . . . . . . . . . .
II Unit Components Page 6. . . . . . . . . . . . . . . . . .
III Refrigerant System Page 16. . . . . . . . . . . . . . . .
IV Charging Page 19. . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery Page 26. . . . . . . . . . . . .
VI Maintenance Page 27. . . . . . . . . . . . . . . . . . . . .
VII Brazing Procedure Page 27. . . . . . . . . . . . . . .
VIII Wiring Diagram Page 28. . . . . . . . . . . . . . . . . .
MODEL NUMBER IDENTIFICATION
SPB Y5036 H 44 S
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Brand/Family
S = T−Class Product Line
Unit Type
P = Heat Pump Outdoor Unit
Nominal Cooling Capacity − Tons
036 = 3 Tons 048 = 4 Tons 060 = 5 Tons
Cooling Efficiency
H = High Efficiency
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Vol ta ge
Y = 208/230V-3 phase-60hz
Refrigerant Type
4 = HFC−410A
Part Load Capability
S = Part load capabilities with multi−stage operation
Coil type
4 = Four−sided
Page 2
Page 2
SPECIFICATIONS  SPBXXXH4S41Y and SPBXXXH4S42Y
General Data
Model No. SPB036H4
SPB048H4 SPB060H4
Nominal Tonnage 3 4 5
Connections (sweat)
Liquid line (o.d.) − in. 3/8 3/8 3/8
Vapor line (o.d.) − in. 7/8 1−1/8 1−1/8
Refrigerant
1
HFC−410A charge furnished 12 lb. 8 oz. 15 lb. 7 oz. 13 lb. 8 oz.
Outdoor Coil
Net face area − sq. ft. Outer coil 18.67 24.5 24.93
Inner coil 18.00 23.64 24.14
Tube diameter − in. 5/16 5/16 5/16
No. of rows 2 2 2
Fins per inch 22 22 22
Outdoor Fan
Diameter − in. 22 22 26
No. of blades 4 4 3
Motor hp 1/6 1/4 1/3
Cfm 3150 3980 4380
Rpm 844 836 850
Watts 215 305 280
Shipping Data − lbs. 1 pkg. 252 294 331
ELECTRICAL DATA
Line voltage data − 60hz 208/230V−3ph 208/230V−3ph 208/230V−3ph
2
Maximum overcurrent protection (amps) 25 30 40
3
Minimum circuit ampacity 15.04 18.53 23.83
Compressor
Rated load amps 11.15 13.46 17.62
Locked rotor amps 58 88 135
Power factor 0.99 0.99 0.99
Outdoor Coil Fan Motor
Full load amps 1.1 1.7 1.8
Locked rotor amps 2.1 3.1 2.9
Page 3
Page 3
SPECIFICATIONS  SPBXXXH4S43Y and SPBXXXH4S44Y
General Data
Model No. SPB036H4
SPB048H4 SPB060H4
Nominal Tonnage 3 4 5
Connections (sweat)
Liquid line (o.d.) − in. 3/8 3/8 3/8
Vapor line (o.d.) − in. 7/8 1−1/8 1−1/8
Refrigerant
1
HFC−410A charge furnished 10 lb. 4 oz. 15 lb. 7 oz. 11 lb. 7 oz.
Outdoor Coil
Net face area − sq. ft. Outer coil 18.67 24.5 24.93
Inner coil 18.00 23.64 24.14
Tube diameter − in. 5/16 5/16 5/16
No. of rows 2 2 2
Fins per inch 22 22 22
Outdoor Fan
Diameter − in. 22 22 26
No. of blades 4 4 3
Motor hp 1/6 1/4 1/3
Cfm 3150 3980 4380
Rpm 844 836 850
Watts 215 305 280
Shipping Data − lbs. 1 pkg. 252 294 331
ELECTRICAL DATA
Line voltage data − 60hz 208/230V−3ph 208/230V−3ph 208/230V−3ph
2
Maximum overcurrent protection (amps) 25 30 40
3
Minimum circuit ampacity 15.04 18.53 23.83
Compressor
Rated load amps 11.15 13.46 17.62
Locked rotor amps 58 88 135
Power factor 0.99 0.99 0.99
Outdoor Coil Fan Motor
Full load amps 1.1 1.7 1.8
Locked rotor amps 2.1 3.1 2.9
Page 4
Page 4
SPECIFICATIONS  SPBXXXH4S45Y
General Data
Model No. SPB036H4
SPB048H4 SPB060H4
Nominal Tonnage 3 4 5
Connections (sweat)
Liquid line (o.d.) − in. 3/8 3/8 3/8
Vapor line (o.d.) − in. 7/8 1−1/8 1−1/8
Refrigerant
1
HFC−410A charge furnished 10 lb. 9 oz. 11 lb. 12 oz. 12 lb. 15 oz.
Outdoor Coil
Net face area − sq. ft. Outer coil 21.0 22.17 29.09
Inner coil 20.27 21.51 28.16
Tube diameter − in. 5/16 5/16 5/16
No. of rows 2 2 2
Fins per inch 22 22 22
Outdoor Fan
Diameter − in. 22 26 26
No. of blades 4 3 3
Motor hp 1/4 1/3 1/3
Cfm 3900 4100 4350
Rpm 830 855 820
Watts 2195 265 195
Shipping Data − lbs. 1 pkg. 273 294 353
ELECTRICAL DATA
Line voltage data − 60hz 208/230V−3ph 208/230V−3ph 208/230V−3ph
2
Maximum overcurrent protection (amps) 25 30 40
3
Minimum circuit ampacity 15.6 18.6 24.8
Compressor
Rated load amps 11.15 13.46 17.62
Locked rotor amps 58 88 135
Power factor 0.99 0.99 0.99
Outdoor Coil Fan Motor
Full load amps 1.7 1.8 2.8
WARNING
Warranty will be voided if covered equipment is re­moved from original installation site. Warranty will not cover damage or defect resulting from: Flood, wind, lightning, or installation and operation in a corrosive atmosphere (chlorine, fluorine, salt, recycled waste water, urine, fertilizers, or other damaging chemicals).
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non−compliance.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox SPB036H4 Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
Page 5
Page 5
I − UNIT INFORMATION
All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the En­gineering Handbook for approved system matchups. A misapplied system will cause erratic operation and can re­sult in early compressor failure.
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and bat­tered.
Remove the louvered panels as follows:
1. Remove 2 screws, allowing the panel to swing open slightly (see figure 1).
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinge corner post until lower 3 tabs clear the slots (see figure 1, De­tail B).
3. Move panel down until lip of upper tab clears the top slot in corner post (see figure 1, Detail A).
Position and Install Panel  Position the panel almost parallel with the unit (figure 1, Detail D) with the screw side" as close to the unit as possible. Then, in a continuous mo­tion:
Slightly rotate and guide the lip of top tab inward (figure
1, Details A and C); then upward into the top slot of the hinge corner post.
Rotate panel to vertical to fully engage all tabs.
Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw holes.
When panel is correctly positioned and aligned, insert the screws and tighten.
Detail
A
Detail C
Detail
B
FIGURE 1
Removing/Installing Louvered Panels
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
PREFERRED ANGLE FOR INSTALLATION
Detail D
ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL
SCREW HOLES
ANGLE MAY BE TOO EXTREME
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
LIP
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or installing) panel.
Page 6
Page 6
II − UNIT COMPONENTS
Unit components are illustrated in figure 2.
SPB*H4 UNIT COMPONENTS
FIGURE 2
OUTDOOR FAN
COMPRESSOR
HIGH PRESSURE
SWITCH
REVERSING
VALV E
FILTER
DRIER
CONTROL
BOX
EXPANSION
VALV E
VAPOR LINE
SERVICE
VALV E
LIQUID LINE
SERVICE
VALV E
LOW PRESSURE
SWITCH
A − Control Box (Figure 3)
SPB*H4 units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
FIGURE 3
DUAL CAPACITOR
(C12)
COMPRESSOR
CONTACTOR
(K1)
UNIT CONTROL BOX
GROUNDING
LUG
DEFROST
CONTROL
(A108)
Electrical openings are provided under the control box cov­er. Field thermostat wiring is made to a 24V terminal strip located on the defrost control board located in the control box. See figure 4.
FIGURE 4
CRW1OY1L
24V THERMOSTAT TERMINAL STRIP
Y2
1 − Compressor Contactor K1
The compressor is energized by a contactor located in the control box. See figure 3. Three−pole contactors are used in all SPB*H4 series units. K1 is energized through the de­frost control board by the indoor thermostat demand.
DANGER
Electric Shock Hazard. May cause injury or death.
Disconnect all remote electrical power supplies before opening unit panel. Unit may have multiple power supplies.
2 − Dual Capacitor C12
The compressor and fan in SPB*H4 series units use perma­nent split capacitor motors. The capacitor is located inside the unit control box (see figure 3). A single dual" capacitor (C12) is used for both the fan motor and the compressor (see unit wir­ing diagram). The fan side and the compressor side of the ca­pacitor have different MFD ratings. See side of capacitor for ratings.
3 − Defrost Control
The demand defrost controller measures differential tem­peratures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates" when the defrost system starts and after each system defrost cycle. The defrost control board com­ponents are shown in figure 5.
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a de­frost cycle is required. The coil temperature probe is de­signed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE  The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
Page 7
Page 7
Defrost Control Board
24V TERMINAL STRIP CONNECTIONS
DIAGNOSTIC LEDS
PRESSURE
SWITCH
CIRCUIT
CONNECTIONS
TEST PINS
Note − Component Locations Vary by Board Manufacturer.
SENSOR PLUG IN
(COIL, AMBIENT,
AND DISCHARGE
SENSORS)
FIGURE 5
REVERSING
VALV E
DELAY
PINS
LOW AMBIENT THERMOSTAT PINS
DEFROST
TERMINATION
PIN SETTINGS
Diagnostic LEDs
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 2.
Defrost Board Pressure Switch Connections
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the defrost board on the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS)  When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following condi­tions:
during the defrost cycle and 90 seconds after the ter-
mination of defrost
when the average ambient sensor temperature is be-
low 15° F (−9°C)
for 90 seconds following the start up of the compressor
during "test" mode
High Pressure Switch (HI−PS)When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike.
5−Strike Lockout Feature
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pres­sure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the con­trol will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins between 1 and 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
Defrost System Sensors
Sensors connect to the defrost board through a field-re­placeable harness assembly that plugs into the board. Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the de­tected temperature changes, the resistance across the sensor changes. Sensor resistance values can be checked by ohming across pins shown in table 1. The graph in figure 6 shows sensor temperature to resistance range.
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 1, may be performing as de­signed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
TABLE 1
Sensor Temperature / Resistance Range
Sensor
Temperature Range °F (°C)
Resistance values range (ohms)
Pins/Wire Color
Outdoor −35 (−37) to 120
(48)
280,000 to 3750 3 and 4
(Black)
Coil −35 (−37) to 120
(48)
280,000 to 3750 5 and 6
(Brown)
Discharge (if applicable)
24 (−4) to 350 (176)
41,000 to 103 1 and 2
(Yellow)
Note: Sensor resistance increases as sensed temperature decreases.
FIGURE 6
Ambient and Coil Sensor
RESISTANCE (OHMS)
TEMPERATURE (ºF)
5750
7450
9275
11775
15425
19975
26200
34375
46275
62700
100
90
80
70
60
50
40
30
20
10
0
10000 30000 50000 70000 90000
85300
Discharge Sensor
RESISTANCE (OHMS)
TEMPERATURE (ºF)
200
325
250
425
600
825
1175
1700
2500
3750
5825
300
280
260
240
220
200
180
160
140
120
100
1000 2000 50004000 60003000
4650
3000
2025
1400
1000
700
225
275
375
500
Page 8
Page 8
FIGURE 7
CLIP COIL TEMPERATURE SENSOR FROM THE DEFROST BOARD ON THE RETURN BEND SHOWN.
COIL SENSOR − APPLY GREASE BETWEEN RETURN BEND AND SENSOR
SPB036H4−0 36
COIL SENSOR 17 tubes up from bottom (17−1/2")
SPB036H4−04 8
COIL SENSOR 13 tubes up from bottom (12−1/2")
SPB036H4−060
COIL SENSOR 12 tubes up from bottom (11−1/2")
Sensor Locations
AMBIENT SENSOR
DISCHARGE LINE SENSOR
DEFROST BOARD
DEFROST SENSOR HARNESS
Ambient Sensor  The ambient sensor (shown in detail A, figure 7) considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a problem. If the ambient sensor is detected as being open, shorted or out of the tem­perature range of the sensor, the board will not perform de­mand defrost operation. The board will revert to time/tem­perature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Coil Sensor  The coil temperature sensor (shown in de­tail B, figure 7) considers outdoor temperatures below
−35°F (−37°C) or above 120°F (48°C) as a problem. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Discharge Line Sensor  If the discharge line tempera­ture (shown in figure 7) exceeds a temperature of 300°F (148°C) during compressor operation, the board will de−en­ergize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti−short cycle delay has been satisfied. This sensor has two fault and lockout codes:
4. If the board recognizes five high discharge line temper­ature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropri­ate code. This code detects shorted sensor or high dis­charge temperatures. (Code on board is Discharge Line Temperature Fault and Lockout").
5. If the board recognizes five temperature sensor range faults during a single (Y1) compressor demand, it re­verts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-temper­ature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout. (Code on board is Dis­charge Sensor Fault and Lockout").
The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" re- frigerant discharge line.
Page 9
Page 9
Second−Stage Operation  If the board receives a call for second−stage compressor operation Y2" in heating or cooling mode and the first-stage compressor output is ac­tive, the second-stage compressor solenoid output will be energized.
If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage com­pressor solenoid output will be energized without the Y2" room thermostat input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used.
The board de−energizes the second-stage compressor so­lenoid output immediately when the Y2" signal is removed or the outdoor ambient temperature is 5°F above the se­lected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason.
Defrost Temperature Termination Shunt (Jumper) Pins
 The defrost board selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
Delay Mode
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when the TEST pins are jumpered.
Operational Description
The defrost control board has three basic operational modes: normal, calibration, and defrost.
Normal Mode  The demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
Calibration Mode  The board is considered uncalibrated when power is applied to the board, after cool mode opera­tion, or if the coil temperature exceeds the termination tem­perature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to en­sure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
Defrost Mode  The following paragraphs provide a de­tailed description of the defrost system operation.
Detailed Defrost System Operation
Defrost Cycles  The demand defrost control board initi-
ates a defrost cycle based on either frost detection or time.
Frost Detection  If the compressor runs longer than
34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maxi-
mum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT  The demand defrost control board will al­low a greater accumulation of frost and will initiate fewer de­frost cycles than a time/temperature defrost system.
Time  If 6 hours of heating mode compressor run
time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the de­mand defrost control will initiate a defrost cycle.
Actuation  When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is be­low 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system tempera­tures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 45 minutes (90 minutes −1 to −4 boards) of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference be­tween the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
NOTE  If ambient or coil fault is detected, the board will not execute the TEST" mode.
Termination  The defrost cycle ends when the coil tem­perature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.
Test Mode  When Y1 is energized and 24V power is be­ing applied to the board, a test cycle can be initiated by plac­ing the termination temperature jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper will ini­tiate one cycle per test.
Enter the TEST" mode by placing a shunt (jumper) across the TEST" pins on the board after power−up. (The TEST" pins are ignored and the test function is locked out if the shunt is applied on the TEST" pins before power−up). Board timings are reduced, the low−pressure switch and loss of charge detection fault is ignored and the board will clear any active lockout condition.
Each test pin shorting will result in one test event. For each TEST" the shunt (jumper) must be removed for at least 1 second and reapplied. Refer to flow chart (figure 8) for TEST" operation.
NOTE  The Y1 input must be active (ON) and the O" room thermostat terminal into board must be inactive.
Defrost Board Diagnostics
See table 2 to determine defrost board operational condi­tions and to diagnose cause and solution to problems.
Page 10
Page 10
TEST
Placing the jumper on the test pins allows the technician to:
Clear short cycle lockout Clear five−strike fault lockout Cycle the unit in and out of defrost mode Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Demand Defrost Control, a test cycle can be initiated by placing a jumper on the Demand Defrost Control’s TEST pins for 2 to 5 sec­onds. If the jumper remains on the TEST pins for longer than five seconds, the Demand Defrost Control will ignore the jumpered TEST pins and revert to normal operation.
The control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
DEMAND DEFROST CONTROL (UPPER LEFT−HAND CORNER)
JUMPER
NOTE  Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Demand Defrost Control.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
If in HEATING Mode
If in DEFROST Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
If no ambient or coil sensor fault ex­ist, unit will go into DEFROST MODE. If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 30 minute test.
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 30 minutes.
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
O Line Status
INACTIVE
ACTIVE
If in COOLING Mode
FIGURE 8
Page 11
Page 11
TABLE 2
Defrost Control Board Diagnostic LEDs
DS2 Green
DS1 Red
Condition/Code Possible Cause(s) Solution
OFF OFF Power problem No power (24V) to board termi-
nals R and C or board failure.
1
Check control transformer power (24V).
2
If power is available to board and LED(s) do not light, replace board.
Simultaneous SLOW Flash
Normal operation Unit operating normally or in
standby mode.
None required.
Alternating SLOW Flash
5−minute anti−short cycle delay
Initial power up, safety trip, end of room thermostat demand.
None required (Jumper TEST pins to override)
Simultaneous FAST Flash
Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will re-
vert to time/temperature defrost operation. (System will still heat or cool).
Alternating FAST Flash
Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not
perform demand or time/temperature defrost operation. (System will still heat or cool).
ON ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24 volt power to board. If
code does not clear, replace board.
FAULT and LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
OFF SLOW
Flash
Low Pressure Fault
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or incorrect operation of metering device.
4
Incorrect or improper sensor location or connection to sys­tem.
1
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and subcooling temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.
OFF ON Low Pressure LOCKOUT
SLOW Flash
OFF High Pressure Fault
ON OFF High Pressure LOCKOUT
SLOW Flash
ON Discharge Line Tempera-
ture Fault
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300ºF (148ºC) during compressor op­eration, the board will de−energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).
FAST Flash
ON Discharge Line Tempera-
ture LOCKOUT
OFF Fast
Flash
Discharge Sensor Fault The board detects open sensor or out of temperature sensor range. This fault is
detected by allowing the unit to run for 90 seconds before checking sensor resist­ance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout.
Fast Flash
OFF Discharge Sensor
LOCKOUT
Page 12
Page 12
B − Two−Stage Scroll Compressor (B1)
FIGURE 9
TWO−STAGE MODULATED SCROLL
solenoid actuator coil
slider ring
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 10 shows the basic scroll form. Two iden­tical scrolls are mated together forming concentric spiral shapes (figure 11). One scroll remains stationary, while the other is allowed to orbit" (figure 12). Note that the orbiting scroll does not rotate or turn but merely orbits" the station­ary scroll.
FIGURE 10
SCROLL FORM
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (fig­ure 4 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4 −3). When the compressed gas reaches the center, it is dis­charged vertically into a chamber and discharge port in the top of the compressor (figure9). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 11). During a single orbit, several pockets of gas are compressed simultaneous­ly providing smooth continuous compression.
FIGURE 11
STATIONARY
SCROLL
ORBITING SCROLL
DISCHARGE
SUCTION
CROSS−SECTION OF SCROLLS
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE PRESSURE
The scroll compressor is tolerant to the effects of liquid re­turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com­pressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. This type of damage can be detected and will result in denial of warranty claims. The scroll com­pressor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig.
NOTE  During operation, the head of a scroll compres­sor may be hot since it is in constant contact with dis­charge gas.
The scroll compressors in all SPB*H4 model units are de­signed for use with HFC−410A refrigerant and operation at high pressures. Compressors are shipped from the factory with 3MA (32MMMA) P.O.E. oil. See electrical section in this manual for compressor specifications.
TWO−STAGE OPERATION
The two−stage scroll compressor operates like any stan­dard scroll compressor with the exception the two−stage compressor modulates between first stage (low capacity approximately 67%) and second stage (high capacity). Modulation occurs when gas is bypassed through bypass ports (figure 13 bypass ports open) in the first suction pock­et. This bypassing of gas allows the compressor to operate on first stage (low capacity) if thermostat demand allows. Indoor thermostat setting will determine first or second stage operation. The compressor will operate on first−stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second−stage.
Second−stage (high capacity) is achieved by blocking the bypass ports (figure 13 bypass ports closed) with a slider ring. The slider ring begins in the open position and is con­trolled by a 24VDC internal solenoid. On a Y2 call the inter- nal solenoid closes the slider ring, blocking the bypass ports and bringing the compressor to high capacity. Two− stage modulation can occur during a single thermostat de­mand as the motor runs continuously while the compressor modulates from first−stage to second− stage.
Page 13
Page 13
FIGURE 12
SCROLL
HOW A SCROLL WORKS
SUCTION
SUCTION
SUCTION
MOVEMENT OF ORBIT
STATIONARY SCROLL
ORBITING
CRESCENT
SHAPED GAS
POCKET
HIGH
PRESSURE
GAS
DISCHARGE
POCKET
FLANKS
SEALED BY
CENTRIFUGAL
FORCE
12
3
4
SUCTION
INTERMEDIATE
PRESSURE
GAS
SUCTION
POCKET
FIGURE 13
Bypass Ports
Closed
High Capacity
Bypass Ports
Open
Low Capacity
TWO−STAGE MODULATION
INTERNAL SOLENOID (L34)
The internal unloader solenoid controls the two−stage op­eration of the compressor by shifting a slide ring mecha­nism to open two by−pass ports in the first compression pocket of the scrolls in the compressor. The internal sole­noid is activated by a 24 volt direct current solenoid coil. The coil power requires 20VAC. The internal wires from the solenoid in the compressor are routed to a 2 pin fusite con-
nection on the side of the compressor shell. The external electrical connection is made to the compressor with a molded plug assembly. This plug contains a full wave rectifi­er that converts 24 volt AC into 24 volt DC power to power the unloader solenoid. Refer to unit diagram for internal cir­cuitry view of plug.
If it is suspect the unloader is not operating properly, check the following
Page 14
Page 14
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper air­flow over coils, and correct system refrigerant charge. All components in the system must be func­tioning proper to correctly perform compressor mod­ulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).
STEP 1 Confirm low to high capacity compressor op­eration
Tools required
Refrigeration gauge set
Digital volt/amp meter
Electronic temperature thermometer
On-off toggle switch
Procedure
1. Turn main power "OFF" to outdoor unit.
2. Adjust room thermostat set point above (heating op­eration on heat pump) or below (cooling operation) the room temperature 5ºF.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach
thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch "OFF" and install switch in series with Y2 wire from room thermostat.
5. Cycle main power "ON."
6. Allow pressures and temperatures to stabilize before taking any measured reading (may take up to 10 min­utes).
NOTE  Block outdoor coil to maintain a minimum of 375 psig during testing).
7. Record all of the readings for the Y1 demand on table
3.
8. Close switch to energize Y2 demand.
9. Allow pressures and temperatures to stabilize before taking any measured reading (this may take up to 10 minutes).
10. Record all of the readings of Y2 demand on table 3.
NOTE  On new installations or installations that have shut down for an extended period of time, if the compressor does not cycle from low stage to high stage on the first at­tempt, it may be necessary to recycle the compressor back down to low stage and back up to high stage a few times in order to get the bypass seals to properly seat
Compare Y1 readings with Y2 readings in table 3. Some readings should be higher, lower or the same. If the read­ings follow what table 3 specifies, the compressor is operat­ing and shifting to high capacity as designed. If the readings do not follow what table 3 specifies, continue to step 2 to de­termine if problem is with external solenoid plug power.
TABLE 3
Unit Readings
Compressor Operation
Y1 −
1st-Stage
Expected Results
Y2 −
2nd-Stage
Compressor
Voltage Same Amperage Higher
Condenser Fan motor
Amperage Same or Higher
Temperature
Ambient Same Outdoor Coil Discharge Air Higher in Cooling
Lower in Heating
Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower in Cooling
Higher in Heating
Pressures
Suction (Vapor) Lower Liquid Higher
Page 15
Page 15
STEP 2 Confirm DC voltage output on compressor solenoid plug
A − Compressor solenoid plug WITH built in full wave−
rectifier (LSOM I) that converts 24 volt AC into 24 volt DC power. See Table 1 for units equipped with the LSOM I.
1. Shut power off to outdoor unit.
2. Supply 24 volts AC control voltage to the wire ends of the full wave rectifier plug. Listen for a click" as the so­lenoid is energized. See figure 14.
compressor
solenoid fusite
terminals
compressor
fusite
terminals
meter
rectifier plug leads
apply 24vac
FIGURE 14
3. Unplug the full wave rectifier plug from the fusite con­nection on the compressor.
4. Turn the low voltage power back onto the unit. Supply 24VAC to the wires of the full wave rectifier plug. Set volt meter to DC volts and measure the DC voltage at the female connector end of the full wave rectifier plug. The DC voltage reading should be 1.5 to 3 volts lower than the input voltage to the plug wire leads. (EX: Input voltage is 24VAC output voltage is 22VDC). See figure 15.
meter
rectifier plug leads
compressor
fusite
terminals
solenoid
fusite
terminals
compressor
apply 24vac
FIGURE 15
If the above checks verify that the solenoid plug is pro­viding power to cycle into high capacity operation, contin­ue to step 3 to determine if problem is with solenoid coil in compressor
STEP 3 Confirm internal unloader solenoid has prop­er resistance
1. Shut all power off to unit (main and low voltage)
2. Unplug the molded plug from the compressor solenoid 2−pin fusite.
3. Using a volt meter set on the 200 ohm scale
Replace the Compressor under these conditions:
Bad Solenoid
a. Measure the resistance at the 2−pin fusite. The resist­ance should be 32 to 60 ohms depending on compressor temperature. If no resist ancereplace compressor.
b. Measure the resistance from each fusite pin to ground. There should not be continuity to ground. If solenoid coil is grounded, replace compressor.
Good Solenoid
a. Seals not shifting, replace compressor b. Slider ring not shifting, replace compressor.
C − Outdoor Fan Motor
All units use single−phase PSC fan motors which require a run capacitor. In all units, the condenser fan is controlled by the compressor contactor.
ELECTRICAL DATA tables in this manual show specifi­cations for condenser fans used in SPB*H4’s.
Access to the condenser fan motor on all units is gained by removing the four screws securing the fan assembly. See figure 16. The grill fan assembly can be removed from the cabinet as one piece. See figure 17. The con­denser fan motor is removed from the fan guard by re­moving the four nuts found on top of the grill. See figure 17 if condenser fan motor replacement is necessary.
Make sure all power is disconnected before beginning electrical service procedures.
DANGER
FIGURE 16
Remove
screws
Remove
screws
ALIGN FAN HUB FLUSH WITH END OF SHAFT
FIGURE 17
NUTS (4)
Page 16
Page 16
D − Reversing Valve L1 and Solenoid
A refrigerant reversing valve with electro−mechanical so­lenoid is used to reverse refrigerant flow during unit op­eration. The reversing valve requires no maintenance. It is not repairable. If the reversing valve has failed, it must be replaced.
E − Crankcase Heater (HR1) and Thermostat (S40)
The compressor in the unit is equipped with a 70 watt, belly band type crankcase heater. HR1 prevents liquid from accu­mulating in the compressor. HR1 is controlled by a thermo­stat located on the liquid line. When liquid line temperature drops below 50° F the thermostat closes energizing HR1. The thermostat will open, de−energizing HR1 once liquid line temperature reaches 70° F .
F − Drier
A filter drier designed for all SPB*H4 model units is factory installed in the liquid line. The filter drier is designed to re­move moisture and foreign matter, which can lead to com­pressor failure.
Moisture and / or Acid Check
Because POE oils absorb moisture, the dryness of the system must be verified any time the refrigerant sys­tem is exposed to open air. A compressor oil sample must
be taken to determine if excessive moisture has been introduced to the oil. Table 4 lists kits available from Lennox to check POE oils.
If oil sample taken from a system that has been exposed to open air does not test in the dry color range, the filter drier MUST be replace.
IMPORTANT
Replacement filter drier MUST be approved for HFC−410A refrigerant and POE application.
Foreign Matter Check
It is recommended that a liquid line filter drier be replaced
when the pressure drop across the filter drier is greater than 4 psig. To safeguard against moisture entering the system follow the steps in section IV − sub section B − "Evacuating the System" when replacing the drier.
G − High/Low Pressure Switch
IMPORTANT
Pressure switch settings for HFC−410A refrigerant will be significantly higher than units with HCFC−22.
An auto-reset, single-pole/single-throw high pressure switch is located in the liquid line. This switch shuts off the compres­sor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 590 +
15 psi.
An auto-reset, single-pole/single-throw low pressure switch is located in the suction line. This switch shuts off the compressor when suction pressure drops below the factory setting. The switch is closed during normal operating pres­sure conditions and is permanently adjusted to trip (open) at 25 +
5 psi. The switch automatically resets when suction
line pressure rises above 40 +
5 psi. Under certain condi­tions the low pressure switch is ignored. See Pressure Switch Circuit in the Defrost Control description.
TABLE 4
KIT CONTENTS TUBE SHELF LIFE
10N46 − Refriger­ant Analysis
Checkmate−RT700
10N45 − Acid Test Tubes
Checkmate−RT750A (three pack)
2 − 3 years @ room temperature. 3+ years refrigerated
10N44 − Moisture Test Tubes
Checkmate − RT751 Tubes (three pack)
6 − 12 months @ room temperature. 2 years refrigerated
74N40 − Easy Oil Test Tubes
Checkmate − RT752C Tubes (three pack)
2 − 3 years @ room temperature. 3+ years refrigerated
74N39 − Acid Test Kit
Sporlan One Shot − TA−1
III − REFRIGERANT SYSTEM
Refer to figure 18 and 19 for refrigerant flow in the heating and cooling modes. The reversing valve is energized during cooling demand and during defrost.
Page 17
Page 17
FIGURE 18
SPB*H4 COOLING CYCLE (SHOWING MANIFOLD GAUGE CONNECTIONS)
OUTDOOR
COIL
EXPANSION/CHECK
VALV E
BI−FLOW
FILTER / DRIER
TO
HFC−410A
DRUM
LOW
PRESSURE
HIGH
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR
LINE
VALV E
MUFFLER
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
SERVICE
PORT
SUCTION
EXPANSION/CHECK
VALV E
INDOOR UNIT
OUTDOOR UNIT
LIQUID LINE
SERVICE
PORT
GAUGE MANIFOLD
INTERNAL
COMPRESSOR
LIMIT
DISTRIBUTOR
INDOOR
COIL
COIL SENSOR
FIGURE 19
SPB*H4 HEATING CYCLE (SHOWING MANIFOLD GAUGE CONNECTIONS)
OUTDOOR
COIL
EXPANSION/CHECK
VALV E
BI−FLOW
FILTER / DRIER
TO
HFC−410A
DRUM
LOW
PRESSURE
HIGH
PRESSURE
COMPRESSOR
REVERSING VALVE
VAPOR
LINE
VALV E
MUFFLER
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
SERVICE
PORT
SUCTION
EXPANSION/CHECK
VALV E
INDOOR UNIT
OUTDOOR UNIT
LIQUID LINE
SERVICE
PORT
GAUGE MANIFOLD
INTERNAL
COMPRESSOR
LIMIT
DISTRIBUTOR
INDOOR
COIL
COIL SENSOR
A − Plumbing
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections). Use Lennox L15 (sweat) series line sets as shown in table 1.
Page 18
Page 18
TABLE 1
Unit
Liquid
Line
Suction
Line
L15 Line Sets
−036,
−048
3/8 in.
(10 mm)
7/8 in.
(22 mm)
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
−060
3/8 in.
(10 mm)
1−1/8 in.
(29 mm)
Field
Fabricated
B − Service Valves
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale min). Fully in­sert the wrench into the valve stem recess. Service valve stems are factory torqued (from 9 ft lbs for small valves, to 25 ft lbs for large valves) to prevent refrigerant loss during ship­ping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
Service valves (figures 20 and 21) and gauge ports are ac­cessible from the outside of the unit. Use the service ports for leak testing, evacuating, charging and checking charge.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench. 2 − Connect gauge to the service port. 3 − When testing is complete, replace service port cap. Tight-
en finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as it will go.
NOTE  Use a 3/16" hex head extension for 3/8" line sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to turn
the stem clockwise to seat the valve. Tighten the stem firmly.
NOTE  Use a 3/16" hex head extension for 3/8" line sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Service Valve
(Valve Closed)
Schrader valve open
to line set when valve is
closed (front seated)
service
port
service
port cap
stem cap
insert hex
wrench here
(valve front seated)
to outdoor coil
to indoor coil
Service Valve
(Valve Open)
Schrader
valve
service
port
service port
cap
insert hex
wrench here
to indoor coil
to outdoor coil
stem cap
FIGURE 20
Vapor Line Ball Valve – 4 and 5 Ton Only
Vapor line service valves function the same way as the oth­er valves, the difference is in the construction. If a valve has failed, you must replace it. A ball valve is illustrated in figure
21. The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak−free seal.
Page 19
Page 19
Ball Valve (Valve Open)
Schrader valve
service port
service port
cap
stem cap
stem
Use Adjustable Wrench
To open: rotate Stem Clockwise 90°.
To close: rotate Stem Counter-clockwise 90°.
ball
(shown open)
to outdoor coil
to indoor coil
FIGURE 21
IV − CHARGING A − Leak Testing
After the line set has been connected to the indoor and out­door units, check the line set connections and indoor unit for leaks.
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could re­sult in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in per­sonal injury or death.
Using an Electronic Leak Detector or Halide
1 − Connect a cylinder of HFC−410A to the center port of
the manifold gauge set.
2 − With both manifold valves closed, open the valve on the
HFC−410A cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow the
HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a maxi­mum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the R−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and HFC−410A mixture. Correct any leaks and recheck.
B − Evacuating the System
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
NOTE  This evacuation process is adequate for a new installation with clean and dry lines. If excessive moisture is present, the evacuation process may be required more than once.
Page 20
Page 20
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 10,000 microns.
1 − Connect manifold gauge set to the service valve ports :
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to deter­mine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total ac­tual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
CAUTION
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compres­sors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off theHFC−410A cylinder and remove the manifold gauge set.
Page 21
Page 21
C − Charging  SSB*H4S41Y through
SSB*H4S43Y
Charge Using the Weigh-in MethodOutdoor
Temperature < 65ºF (18ºC)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit.
1. Recover the refrigerant from the unit.
2. Conduct leak check; evacuate as previously outlined.
3. Weigh in the unit nameplate charge. If weighing facili­ties are not available or if charging the unit during warm weather, use one of the following procedures.
Charge Using the Subcooling MethodOutdoor
Temperature <
65ºF (18ºC)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. If necessary, restrict the air flow through the outdoor coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 325−375 psig (2240−2585 kPa) range. See figure 22.
Blocking Outdoor Coil
BLOCK OUTDOOR COIL ONE SIDE AT A TIME WITH CARDBOARD OR PLASTIC SHEET UNTIL PROPER TESTING PRESSURES ARE REACHED.
CARDBOARD OR PLASTIC SHEET
FIGURE 22
1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital ther­mometer to check the liquid line temperature and re­cord in table 2.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for HFC−410A (table
9) to determine the saturation temperature for the liquid line pressure reading; record in table 2.
4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine the subcooling value.
5. Compare the subcooling value with those in table 2. If subcooling value is greater than shown, recover some refrigerant; if less, add some refrigerant.
TABLE 2
SPB036H4 Subcooling Values for Charging
Second Stage (High-Capacity)
SSB*H4S41Y through SSB*H4S43Y
Saturation Temperature
Liquid Line Temperature
=
Subcooling Value
Model SPB036H4S41 SPB048H4S41 SPB060H4S41
°F (°C)* 7 (3.9) 9 (5) 8 (4.4)
*F: +/−1.0°; C: +/−0.5°
Charge Using the Approach MethodOutdoor
Temperature >
65ºF (18ºC)
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Check the outdoor ambient temperature using a digital thermometer and record in table 3.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in tables 4 and 5, Normal Operating Pressures." Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the sys­tem. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Contin­ue to check adjusted charge using approach values.
4. Use the same digital thermometer used to check out­door ambient temperature to check liquid line tempera­ture and record in table 3. Verify the unit charge using the approach method. The difference between the am­bient and liquid temperatures should match values giv­en in table 3. Add refrigerant to lower the approach tem­perature and remove it to increase the approach tem­perature. Loss of charge results in low capacity and ef­ficiency.
5. If the values do not agree with those in table 3, add re­frigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Page 22
Page 22
TABLE 3
SPB036H4 Approach Values for Charging
Second Stage (High-Capacity)
SSB*H4S41Y through SSB*H4S43Y
Liquid Line Temperature
Outdoor Temperature
=
Approach Temperature
Model SPB036H4S41 SPB048H4S41 SPB060H4S41
°F (°C)* 9 (5) 8 (4.4) 8 (4.4)
*F: +/−1.0°; C: +/−0.5°
TABLE 4
Normal Operating Pressures − Cooling
1
SSB*H4S41Y through SSB*H4S43Y
Model SPB036H4S41 SPB048H4S41 SPB060H4S41
°F (°C)
2
Liquid Vapor Liquid Vapor Liquid Vapor
First Stage (Low Capacity) Pressure
3
65 (18.3) 225 144 235 144 225 138
75 (23.9) 261 147 268 145 264 141
85 (29.4) 302 149 310 147 305 142
95 (35.0) 349 151 356 148 352 146
105 (40.6)
397 153 407 150 405 148
115 (46.1)
461 157 466 152 459 150
Second Stage (High Capacity) Pressure
3
65 (18.3) 239 139 244 140 241 134
75 (23.9) 278 141 283 141 280 136
85 (29.4) 322 143 326 144 324 137
95 (35.0) 367 146 374 147 373 138
105 (40.6)
426 148 427 148 425 142
115 (46.1)
489 151 491 151 486 146
1 These are most−popular−match−up pressures. Indoor match up,
indoor air quality, and indoor load cause pressures to vary. 2 Temperature of the air entering the outdoor coil. 3 Liquid ±10 and Vapor ±5 psig.
TABLE 5
Normal Operating Pressures − Heating
1
SSB*H4S41Y through SSB*H4S43Y
Model SPB036H4S41 SPB048H4S41 SPB060H4S41
°F (°C)
2
Liquid Vapor Liquid Vapor Liquid Vapor
First Stage (Low Capacity) Pressure
3
40 (4.4) 328 98 369 75 351 63
50 (10) 333 11 8 366 114 335 92
Second Stage (High Capacity) Pressure
3
20 (−7.0) 296 62 311 58 308 59
30 (−1.0) 309 75 334 72 323 70
40 (4.4) 322 92 354 89 318 69
50 (10) 336 11 3 381 108 329 82
1 These are most−popular−match−up pressures. Indoor match up,
indoor air quality, and indoor load cause pressures to vary. 2 Temperature of the air entering the outdoor coil. 3 Liquid ±10 and Vapor ±5 psig.
C − Charging  SSB*H4S44Y
TESTING AND CHARGING SYSTEM
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (
DT) process using the il-
lustration in figure 23.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing elec­tric heat and measuring:
Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
Measuring voltage supplied to the unit, Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount specified on nameplate
Adjust amount. for variation in line set length listed on table in figure 24.
Additional charge specified per indoor unit match−up listed in tables 6 through 8.
To ta l charge
+ + =
Page 23
Page 23
Step 1. Determine the desired DTMeasure entering air tempera- ture using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
Step 2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
Drop
) = A minus C.
Step 3. Determine if fan needs adjustmentIf the difference be- tween the measured T
Drop
and the desired DT (T
Drop
DT) is within
+
3º, no adjustment is needed. See examples: Assume DT = 15 and
A temp. = 72º, these C temperatures would necessitate stated ac­tions:
Cº T
Drop
DT = ºF ACTION
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +
3º range) no change
62º 10 15 = −5 Decrease the airflow
Step 4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +
3º.
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp. of air entering indoor coil ºF
INDOOR COIL
DRY BULBDRY
BULB
WET
BULB
B
T
Drop
19º
A
Dry−bulb
Wet−bulb ºF
A
72º
B
64º
C
53º
air flowair flow
All temperatures are expressed in ºF
Figure 23. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
WEIGH IN
1. Check Liquid and suction line pressures
2. Compare unit pressures with tables 4 and 10, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
Liquid Line
Set Diameter
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm)
3 ounce per 5’ (85 g per 1.5 m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Refrigerant Charge per Line Set Length
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Figure 24. Using HFC−410A Weigh In Method
1 Check the airflow as illustrated in figure 23 to be sure the indoor airflow is as required. (Make any air
flow adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to
check charge. 3 Connect gauge set. 4 Check liquid and vapor line pressures. Compare pressures with either heat or cooling mode normal
operating pressures in tables 4 and 10 (second stage − high capacity),
NOTE − The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values (second stage − high capacity) in tables 4 are based on 70 to 80°F (21−27°C) indoor
return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat
to cooling mode setpoint to 68ºF (20ºC) which should call for second stage (high capacity) cooling. When
pressures have stabilized, continue with step 6.
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target
subcooling values (second stage − high capacity) in tables 4 and 10 are based on 65−75°F (18−24°C) indoor
return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat
to heating mode setpoint to 77ºF (25ºC) which should call for second stage (high capacity) heating. When
pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart
listed in table 15 and record it in the SATº space.
8 Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space.
9 Compare SCº results with tables 6 through 8, being sure to note any additional charge for line set and/or
match−up.
10 If subcooling value is greater than shown in tables 6 through 8 for the applicable unit, remove refrigerant;
if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 4 through 10 to verify charge.
12 Disconnect gauge set and re−install both the liquid and suction service valve caps.
USE COOLING
MODE
USE HEATING
MODE
60ºF (15º)
SATº LIQº – SCº =
SUBCOOLING
Figure 25. Using HFC−410A Subcooling Method  Second Stage (High Capacity)
Page 24
Page 24
Indoor Unit Matchups  SSB*H4S44Y
Table 6. SSB024H4S44Y
INDOOR HEAT MATCHUP PUMP
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
SPB036H4–036
lb oz
CH23–51 17 7 0 13
CH23–65 12 8 1 10
CBX26UH–030 25 8 1 14
CBX26UH–036 25 8 1 14
CB27UH−036 17 8 2 4
CB27UH−042 17 8 2 4
CB30U–31 17 6 0 0
CB30U–41/46 17 8 2 4
CBX32M–030 17 6 0 0
CBX32M–036 17 8 2 4
CBX32MV–024/030 17 6 0 0
CBX32MV–036 17 8 2 4
C33–44C 17 8 1 14
CH33–42B–2F 17 7 0 13
CH33–44/48B–2F 12 8 1 8
CH33–48C–2F 10 8 1 6
CH33–43B 9 10 1 6
CH33–49C 9 10 1 6
CR33–48B/C–F 25 8 2 0
CR33–50/60C–F 25 9 0 14
CX34–38A/B–6F Serial No# before 6007K 31 7 1 5
CX34–38A/B–6F Serial No# 6007K and after 10 8 1 12
CX34–43B/C–6F 10 8 1 6
CX34–60D 9 9 0 14
**Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)
Table 7. SSB036H4S44Y
INDOOR HEAT MATCHUP PUMP
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
SPB036H4–048
lb oz
CH23–68 15 13 0 7
CB27UH−048 17 7 0 0
CB27UH−060 17 7 0 0
CB30U–51, –65 17 7 0 0
CBX32M–048, –060 17 7 0 0
CBX32MV–048, –060 17 7 0 0
CBX32MV–068 16 10 0 3
CH33–60D–2F 18 4 0 2
CH33–62D–2F 15 10 0 4
CR33–60 40 4 0 2
CX34–60D–6F 18 4 0 2
CX34–62D–6F 16 8 0 2
Table 8. SSB060H4S44Y
INDOOR HEAT MATCHUP PUMP
Target Subcooling HeatCool
(+
5ºF)(+1ºF)
**Add
charge
SPB036H4SPB036H4–060
lb oz
CH23–68 13 14 3 3
CH23–65 18 2 0 0
CBX26UH–060 13 14 3 5
CB27UH−060 13 10 2 1
CBX32M–060 13 10 2 1
CBX32MV–060 13 10 2 1
CBX32MV–068 13 12 2 9
CH33–60D–2F 15 6 1 3
CH33–62D–2F 13 12 2 10
CR33–50/60C–F 30 6 1 3
CR33–60D–F 30 6 1 3
CX34–49C–6F 13 9 1 14
CX34–60D–6F 15 6 1 3
CX34–62C–6F 13 11 2 6
CX34–62D–6F 13 11 2 5
Table 9. HFC−410A Normal Operating Pressures −
Cooling
1
SSB*H4S44Y
SPB036
H4
−024 −036 −048 −060
°F (°C)2Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity) Pressure
3
65 (18.3) 232 146 225 144 235 144 225 138
75 (23.9) 264 148 261 147 268 145 264 141
85 (29.4) 307 149 302 149 310 147 305 142
95 (35.0) 353 151 349 151 356 148 352 146
105 (40.6) 403 153 397 153 407 150 405 148
115 (46.1) 460 155 461 157 466 152 459 150
Second Stage (High Capacity) Pressure
3
65 (18.3) 240 143 239 139 244 140 241 134
75 (23.9) 279 145 278 141 283 141 280 136
85 (29.4) 322 147 322 143 326 144 324 137
95 (35.0) 371 149 367 146 374 147 373 138
105 (40.6) 423 151 426 148 427 148 425 142
115 (46.1) 485 154 489 151 491 151 486 146
Page 25
Page 25
Table 10. HFC−410A Normal Operating Pressures −
Heating
1
SSB*H4S44Y
XP16 −024 −036 −048 −060
°F (°C)2Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity) Pressure
3
40 (4.4) 314 88 304 89 324 92 341 89
50 (10) 333 11 6 318 11 6 354 11 5 365 11 3
Second Stage (High Capacity) Pressure
3
20 (−7.0) 286 59 289 63 306 61 318 59
30 (−1.0) 303 74 303 77 322 70 335 73
40 (4.4) 321 89 314 88 345 92 348 86
50 (10) 346 109 333 11 0 370 11 0 369 107
1 Most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary. 2 Temperature of the air entering the outdoor coil. 3 Liquid ±10 and Vapor ±5 psig.
1
Use tables 9 and 10 to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the sys­tem is not properly charged or that a problem exists with some component in the system.
Indoor Unit Matchups  SSB*H4S45Y
Table 11. SPB036H4S45Y
Indoor Unit Match− up
Heating
+
5ºF
Cooling
+
1ºF
*Add
Charge
Subcooling lbs. oz.
CBX26UH−036 50 5 0 0
CBX27UH−036−230 22 7 0 9
CBX27UH−042−230 24 11 3 0
CBX32M−036 22 7 0 9
CBX32MV−036 22 7 0 9
CBX32MV−048 24 11 3 0
CBX40UHV−030 22 7 0 9
CBX40UHV−036 22 7 0 9
CBX40UHV−042 24 11 3 0
CBX40UHV−048 24 11 3 0
CH33−43B 13 10 2 7
CH33−48C 37 11 2 11
CH33−43C 37 11 2 11
CR33−48B/C 49 7 0 9
CX34−43B/C 29 9 2 11
CX34−50/60C 29 9 2 11
Table 12. SPB048H4S45Y
Indoor Unit Match− up
Heating
+
5ºF
Cooling
+
1ºF
*Add Charge
Subcooling lbs. oz.
CBX26UH−048−230 10 8 1 4
CBX27UH−048−230 19 9 1 4
CBX27UH−060−230 13 14 3 3
CBX32M−048 19 9 1 4
CBX32M−060 14 9 1 11
CBX32MV−048 19 9 1 4
CBX32MV−060 14 9 1 11
CBX32MV−068 9 8 1 11
CBX40UHV−048 19 9 1 4
CBX40UHV−060 14 9 1 11
CH23−68 24 10 1 12
CH33−49C 19 9 2 5
CH33−50/60C 19 9 2 5
CH33−60D 13 8 0 0
CH33−62D 11 9 1 4
CR33−50/60C 15 7 0 10
CR33−60D 15 7 0 10
CX34−60D 14 8 1 0
CX34−62D 9 9 1 6
CX34−62C 8 9 1 9
Table 13. SPB060H4S45Y
Indoor Unit Match− up
Subcooling lbs. oz.
CBX26UH−060 20 9 4 13
CBX27UH−060−230 10 6 2 3
CBX32M−060 17 6 1 12
CBX32MV−060 17 6 1 12
CBX32MV−068 15 7 2 1
CBX40UHV−060 17 6 1 12
CH33−50/60C 33 8 1 0
CH33−62D 15 7 1 4
CH23−68 37 9 2 10
CR33−50/60C 24 7 0 0
CR33−60D 24 7 0 0
CX34−62C 21 9 2 16
CX34−62D 13 7 1 4
*Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)
Page 26
Page 26
Table 14. Normal Operating Pressures* SPB*H4S45Y
1
Use tables to perform maintenance checks; it is not a pro­cedure for charging the system. Minor variations in these pressures may be due to differences in installations. Signifi­cant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Normal Operating Pressures − Cooling
SPB*
H4
−036 −048 −060
°F
(°C)**
Liq Va p Liq Vap Liq Vap
First Stage (Low Capacity) Pressure
65
(18.3)
220 141 224 143 230 137
75
(23.9)
254 144 259 143 267 139
85
(29.4)
295 148 302 147 311 141
95
(35.0)
340 150 346 149 357 144
105
(40.6)
389 153 396 152 398 147
115
(46.1)
444 156 450 155 453 149
Second Stage (High Capacity) Pressure
65
(18.3)
232 129 238 138 232 131
75
(23.9)
269 136 278 140 276 133
85
(29.4)
312 140 321 142 320 136
95
(35.0)
346 142 372 144 367 138
105
(40.6)
409 145 424 147 421 141
115
(46.1)
465 148 481 149 479 144
Normal Operating Pressures − Heating
First Stage (Low Capacity) Pressure
50
(10)
350 115 336 114 385 108
60
(15.5)
372 136 363 135 414 126
Second Stage (High Capacity) Pressure
20
(−7.0)
321 61 289 57 332 59
30
(−1.0)
347 74 294 69 349 67
40
(4.4)
367 90 321 80 361 75
50
(10)
387 110 341 110 383 85
60
(15.5)
395 131 361 128 425 122
* Typical pressures only, expressed in psig (liquid +/− 10 and va-
por+/− 5 psig); indoor match up, indoor air quality, and indoor load will cause the pressures to vary. These operating pressures are also listed on the unit charging sticker (580005−01) located on the access panel.
** Temperature of air entering outdoor coil.
Table 15. HFC−410A Temp. (°F) − Pressure (Psig)
°F
Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6 39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 11 0 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 50 142.2 81 239.0 11 2 375.1 143 559.1 51 144.8 82 242.7 11 3 380.2 144 565.9 52 147.4 83 246.5 11 4 385.4 145 572.8 53 150.1 84 250.3 11 5 390.7 146 579.8 54 152.8 85 254.1 11 6 396.0 147 586.8 55 155.5 86 258.0 11 7 401.3 148 593.8 56 158.2 87 262.0 11 8 406.7 149 601.0 57 161.0 88 266.0 11 9 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 175.4 93 286.5 124 440.2 155 645.0
V − SERVICE AND RECOVERY
WARNING
Polyol ester (POE) oils used with HFC−410A refriger­ant absorb moisture very quickly. It is very impor­tant that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
IMPORTANT
Use recovery machine rated for HFC−410A refrig­erant.
If the SPB*H4 system must be opened for any kind of ser­vice, such as compressor or drier replacement, you must take extra precautions to prevent moisture from entering the system. The following steps will help to minimize the amount of moisture that enters the system during recovery of HFC−410A. 1 − Use a regulator−equipped nitrogen cylinder to break
the system vacuum. Do not exceed 5 psi. The dry nitro­gen will fill the system, and will help purge any mois­ture.
2 − Remove the faulty component and quickly seal the sys-
tem (using tape or some other means) to prevent addi­tional moisture from entering the system.
Page 27
Page 27
3 − Do not remove the tape until you are ready to install
new component. Quickly install the replacement com­ponent.
4 − Evacuate the system to remove any moisture and other
non−condensables.
The SPB*H4 system MUST be checked for moisture any time the sealed system is opened.
Any moisture not absorbed by the polyol ester oil can be re­moved by triple evacuation. Moisture that has been ab­sorbed by the compressor oil can be removed by replacing the drier.
IMPORTANT
Evacuation of system only will not remove mois­ture from oil. Drier must be replaced to eliminate moisture from POE oil.
VI − MAINTENANCE
In order to maintain the warranty on this equipment, the SPB*H4 system must be serviced annually and a record of service maintained. The following should be checked be­tween annual maintenance:
A − Outdoor Unit
1 − Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned off before you clean the coil.
2 − Condenser fan motor is pre−lubricated and sealed. No
further lubrication is needed.
3 − Visually inspect connecting lines and coils for evidence
of oil leaks. 4 − Check wiring for loose connections. 5 − Check for correct voltage at unit (unit operating). 6 − Check amp−draw condenser fan motor.
Unit nameplate _________ Actual ____________ .
NOTE  If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
1 − Clean and inspect condenser coil. (Coil may be flushed
with a water hose after disconnecting power). 2 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
B − Indoor Coil
1 − Clean coil, if necessary.
2 − Check connecting lines and coils for evidence of oil
leaks.
3 − Check the condensate line and clean it if necessary.
C − Indoor Unit
1 − Clean or change filters. 2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper ten-
sion. 4 − Check all wiring for loose connections 5 − Check for correct voltage at unit (blower operating). 6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.
VII − BRAZING
Before brazing remove access panels and any piping pan­els to avoid burning off paint. Be aware of any components ie, service valves, reversing valve, pressure switches that may be damaged due to brazing heat.
When making line set connections, use 1 to 2 psig dry nitro­gen to purge the refrigerant piping. This will help to prevent oxidation into the system.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
1 − .Cut ends of copper square (free from nicks or dents).
Debur the ends. The pipe must remain round, do not
pinch end of line. 2 − Wrap wet rag around any components that may be da-
maged. 3 − Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper to copper brazing or 45 percent
silver alloy for copper to brass or copper to steel braz-
ing) which are rated for use with HCFC−22 and
HFC−410A refrigerant. 4 − After brazing quench the joints with a wet rag to prevent
possible heat damage to any components.
Page 28
Page 28
VIII − WIRING DIAGRAM AND SEQUENCE OF OPERATION
Page 29
Page 29
Figure 26. Unit Wiring Diagram (−036 and −048 Sizes)  SPB*H4S45Y
Page 30
Page 30
Figure 27. Unit Wiring Diagram (−060 Size Only)  SPB*H4S45Y
Page 31
Page 31
Sequence of Operation
Cooling
A – First Stage Low Capacity
Transformer from indoor unit supplies 24VAC power to the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling de­mand initiates at Y1 in the thermostat.
2 − The defrost board checks for open low or high−pres-
sure switches and proper coil, ambient and discharge sensor readings. If checks show no issues, the defrost board sends 24 volts through Y1 OUT signal to the K1 compressor contactor coil.
3− K1−1 N.O. closes energizing compressor B1 and out-
door fan motor B4.
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
B – Second Stage High Capacity
5− Second stage thermostat demand goes through Y2 on
the defrost board and energizes rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34 unloader solenoid. L34 then closes the slider ring, allowing the compressor to operate at high capacity.
Heating
A – Low Capacity
1− Internal wiring de−energizes terminal O by heating
mode selection, de−energizing the reversing valve. Heating demand initiates at Y1 in the thermostat.
2 − The defrost board checks for open low or high−pres-
sure switches and proper coil, ambient and discharge sensor readings. If checks show no issues, the defrost board sends 24 volts through Y1 OUT signal to the K1 compressor contactor coil.
3− K1−1 closes, energizing the compressor and outdoor
fan motor.
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
B – High Capacity (Ambient temperature above
defrost board Y2 lock−in temperature)
1− Room thermostat in heating mode. Room thermostat
outputs Y1 and Y2 (if applicable to that room thermo­stat) signal to the defrost board in the heat pump and to the indoor unit.
2− The defrost board checks for open low or high−pres-
sure switches and proper coil, ambient and discharge sensor readings. If checks show no issues, the defrost board sends 24 volts through Y1 OUT signal to the K1 compressor contactor coil.
3 − The defrost board sends 24 volts through Y2 OUT to
the L34 compressor solenoid plug. The 2− wire com-
pressor solenoid plug converts the 24volt AC outputs to
a 24volt DC signal input to the L34 internal high capac-
ity solenoid valve in the compressor. 4 − K1−1 closes, energizing the compressor and outdoor
fan motor through the normally closed fan relay con-
tacts on the defrost board. The compressor runs high
capacity.
B – High Capacity (Ambient temperature below
defrost board Y2 lock−in temperature)
1 − Room thermostat in heating mode. Room thermostat
outputs Y1 signal to the defrost board in the heat pump
and to the indoor unit. 2 − The defrost board checks for open low or high−pres-
sure switches and proper coil, ambient and discharge
sensor readings. If checks show no issues, the defrost
board sends 24 volts through Y1 OUT signal to the K1
compressor contactor coil. 3 − The defrost board Y2 locks in
sends 24 volts through Y2 OUT to the L34 compressor solenoid plug. The plug converts the 24volt AC outputs to a 24volt DC signal in­put to the L34 internal high capacity solenoid valve in the compressor.
4 − K1−1 closes, energizing the compressor and outdoor
fan motor through the normally closed fan relay con­tacts on the defrost board. The compressor runs on high capacity.
Defrost Mode
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1" (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination tempera­ture, the defrost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default ter­mination temperature will be 90°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by time and the coil temper­ature did not remain above 35°F (2°C) for 4 minutes the control will go to the 34−minute Time/Temperature mode.
Loading...