Compressor − limited warranty for five years in
non-residential installations.
All other covered components − one year in
non-residential installations.
Refer to Lennox Equipment Limited Warranty certificate
included with unit for specific details.
Approvals
Certified in accordance with USE certification program
which is based on ARI Standard 210/240−2005.
Sound rated in Lennox reverberant sound test room in
accordance with test conditions included in ARI Standard
270−95.
Tested in the Lennox Research Laboratory environmental
test room.
Rated according to U.S. Department of Energy (DOE) test
procedures.
Heat pumps and components within bonded for
grounding to meet safety standards for servicing required
by UL and CEC.
Units are UL and ULC listed.
ISO 9001 Registered Manufacturing Quality System.
E
NERGY STAR® certified units are designed to use less
energy, help save money on utility bills, and help protect
the environment.
ApplicationS
SEER up to 16.0.
Heating COP up to 3.52.
HSPF (region IV) up to 8.70.
3 through 5 ton.
Three−phase power supply.
Sound levels as low as 76 dB.
Vertical air discharge allows concealment behind shrubs
at grade level or out of sight on a roof.
Designed for applications with remotely located indoor air
handlers or add−on indoor coils with FM21
furnace control. See FM21
Also see Indoor Coils and Air Handlers sections for indoor
unit data.
Units shipped completely factory assembled, piped, and
wired. Each unit is test operated at the factory insuring
proper operation.
Installer must set heat pump, connect refrigerant lines,
and make electrical connections to complete job.
For expanded ratings, see www.lennoxcommercial.com.
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 2
®
bulletin, Controls section.
®
dual fuel
B
J
C
I
D
H
G
F
E
L
M
REFRIGERATION SYSTEM
Refrigerant
Non−chlorine, ozone friendly, R−410A.
Unit pre−charged with refrigerant.
See Specification table.
Outdoor Coil Fan
B
Direct drive fan moves large air volumes uniformly
through entire condenser coil for high refrigerant cooling
capacity.
Vertical air discharge minimizes operating sounds and
eliminates damage to lawn and shrubs.
Fan motor has sleeve bearings and is inherently
protected.
Motor totally enclosed for maximum protection from
weather, dust and corrosion
Fan guard constructed of corrosion−resistant PVC
(polyvinyl chloride) coated steel.
Fan service access accomplished by removal of fan
guard.
Copper Tube/Enhanced Fin Coil
C
Lennox designed and fabricated coil.
Ripple−edged aluminum fins.
Copper tube construction.
Lanced fins provide maximum exposure of fin surface to
air stream resulting in excellent heat transfer.
Fin collars grip tubing for maximum contact area.
Inverted coil circuiting prevents ice buildup at coil base in
low ambients. Discharge gas enters bottom of coil during
defrost and heat of refrigerant flows counter to water
drainage resulting in extremely clean and unobstructed
fins and tubes.
Fin spacing allows rapid and complete water drainage.
Flared shoulder tubing connections/silver soldering
construction.
Coil is factory tested under high pressure to insure
leakproof construction.
Entire coil is accessible for cleaning.
K
Page 3
FEATURES
REFRIGERATION SYSTEM (CONTINUED)
Expansion Valve − Outdoor Unit
D
Designed and sized specifically for use in heat pump
system.
Sensing bulb is located on the line between reversing valve
and the coil thus sensing suction temperature in any cycle.
Factory installed and piped.
Discharge Temperature Switch
Shuts off unit if operating conditions cause the
compressor discharge line temperature to rise above
setpoint.
Protects compressor from excessive pressure /
temperature.
Automatic reset when temperature drops below setpoint.
High Pressure Switch
E
Shuts off unit if abnormal operating conditions cause the
discharge pressure to rise above setting.
Protects compressor from excessive condensing
pressure.
Automatic reset.
Low Pressure Switch
F
Shuts off unit if suction pressure falls below setting.
Provides loss of charge and freeze-up protection.
Automatic reset.
Hi-Capacity Liquid Line Drier
G
Factory installed in the liquid line, the drier traps moisture
or dirt that could contaminate the refrigerant system.
100% molecular−sieve bead type drier.
Reversing Valve
H
4-way interchange reversing valve effects a rapid change
in direction of refrigerant flow resulting in quick
changeover from cooling to heating and vice versa.
Valve operates on pressure differential between outdoor
unit and indoor unit of the system. Factory installed.
OPTIONS
Expansion Valve Kits
Must be ordered extra and field installed on certain indoor
units. See ARI Ratings tables.
Chatleff style fitting.
Freezestat
Installs on or near the discharge line of the evaporator or
on the suction line.
Senses suction line temperature and cycles the
compressor off when suction line temperature falls below
it’s setpoint.
Opens at 29°F and closes at 58°F.
Refrigerant Line Sets
Refrigerant lines (suction & liquid) are shipped
refrigeration clean. Lines are cleaned, dried, pressurized,
and sealed at factory.
Suction line fully insulated.
L15 lines are stubbed at both ends.
See Specifications table for selection.
Not available for −060 model and must be field fabricated.
COMPRESSOR
Copeland Scroll Ultra Techt Two−Stage Compressor
I
Compressor features high
efficiency with uniform
suction flow, constant
discharge flow and high
volumetric efficiency and
quiet operation.
Compressor consists of
two involute spiral scrolls
matched together to
generate a series of
crescent shaped gas
pockets between them.
During compression, one
scroll remains stationary
while the other scroll orbits
around it.
Gas is drawn into the outer
pocket, the pocket is sealed as the scroll rotates.
As the spiral movement continues, gas pockets are
pushed to the center of the scrolls. Volume between the
pockets is simultaneously reduced.
When pocket reaches the center, gas is now at high
pressure and is forced out of a port located in the center
Slider Ring
Fixed scroll
efficiency.
Scroll compressor is tolerant to the effects of slugging
and contaminants. If this occurs, scrolls separate,
allowing liquid or contaminants to to be worked toward
the center and discharged.
On the fixed scroll there are two bypass ports in the first
suction pocket. On the outside of the fixed scroll there is a
slider ring" that is controlled by an internal solenoid that
will rotate and cover the bypass ports. When the
thermostat calls for first−stage cooling, the bypass ports
are open and the compressor operates at 67% capacity,
creating more cost−effective and efficient compressor
operation. The bypassed refrigerant is returned to the
compressor housing through the bypass ports. When
the thermostat calls for second−stage cooling, the
internal solenoid is energized, the slider ring rotates and
covers the bypass ports, and the compressor operates
at full capacity.
Low gas pulses during compression reduces
operational sound levels.
Compressor motor is internally protected from
excessive current and temperature.
Compressor is installed in the unit on specially
formulated, resilient rubber mounts for better sound
dampening and vibration free operation.
Internal solenoid
Slider
Ring
Internal
solenoid
of the fixed scrolls. During
compression, several
pockets are compressed
simultaneously resulting in
a smooth continuous
compression cycle.
Continuous flank contact,
maintained by centrifugal
force, minimizes gas
leakage and maximizes
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 3
Page 4
FEATURES
COMPRESSOR (CONTINUED)
Crankcase Heater
Crankcase heater prevents migration of liquid refrigerant
into compressor and ensures proper compressor
lubrication.
Outdoor Thermostat Kit
An outdoor thermostat can be used to lock out some of the
electric heating elements on indoor units where two−stage
control is applicable.
Outdoor thermostat maintains the heating load on the low
power input as long as possible before allowing the full
power load to come on the line.
Thermostat kit and mounting box must be ordered extra.
Cabinet
J
Heavy−gauge steel construction
Pre−painted cabinet finish.
Pre−painted base section.
Compressor and control box located in a separate
compartment, insulated with thick fiberglass insulation.
Compartment provides protection from the weather and
keeps sound transmission at a minimum.
Control box is conveniently located with all controls
factory wired.
Large removable panel provides service access.
Drainage holes are provided in base section for moisture
removal.
High density polyethylene unit support feet raise the unit off
of the mounting surface, away from damaging moisture.
SmartHinget Louvered Coil Protection
K
Steel louvered panels
provides complete coil
protection.
Panels are hinged to
allow easy cleaning
and servicing of coils.
Panels may be
completely removed.
Interlocking tabs and
slots assure tight fit on
cabinet.
Refrigerant Line Connections, Electrical Inlets and
Service Valves
Vapor and liquid lines are located on corner of unit cabinet
and are made with sweat connections. See dimension
drawing.
Fully serviceable brass service valves prevent corrosion
L
and provide access to refrigerant system. Vapor valve can
be fully shut off, while liquid valve may be front seated to
manage refrigerant charge while servicing system.
Vapor and liquid line service valves and gauge ports are
located inside the cabinet.
Refrigerant line connections and field wiring inlets are
located in one central area of the cabinet. See dimension
drawing.
CONTROLS
Defrost Control
M
Solid-state control furnished as standard.
Gives a demand defrost cycle whenever system heating
performance falls below optimum levels. The sensing
element on coil determines when defrost cycle is required
and when to terminate cycle.
Anti−short cycle (5 minutes) incorporated into the board.
Diagnostic LED’s furnished as an aid in troubleshooting.
Conveniently located in control box.
OPTIONS
Indoor Blower Speed Relay Kit
Relay kit provides optimum humidity control conditions by
automatically reducing indoor blower speed during
continuous fan or first−stage compressor operation.
®
L Connection
Complete building automation control system for single or
multi−zone applications. Options include local interface,
software for local or remote communication, and
hardware for networking other control functions. See L
Connection Network Engineering Handbook Bulletin for
details.
Low Ambient Control Options
Air conditioners operate satisfactorily down to 45°F
outdoor air temperature without any additional controls.
Two low ambient control options are available for field
installation:
Low Ambient Control Kit (30°F)
Allows unit operation down to 30°F. See Optional
Accessories, page 7, for ordering information.
Low Ambient Control Kit (0°F)
Allows unit operation down to 0°F. This option requires
that the outdoor fan motor and capacitor be changed. See
Low Ambient Control Option table, page 7, for ordering
information.
A Freezestat should be installed on compressors
equipped with a low ambient kit.
A Compressor Low Ambient Cut−off should be added to
terminate compressor operation below recommended
operation conditions (on/off operation, 30°F or modulating
operation, 0°F).
Indoor Blower Off Delay Relay
Delays the indoor blower−off time during the cooling cycle.
See ARI Rating Tables for usage.
Monitor Kit − Service Light
Contains ambient compensating thermistor and service
light thermostat.
For use with thermostats requiring input for indicator
lights.
Network
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 4
Page 5
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or
Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1)
C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4)
C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.
DIGITAL NON−PROGRAMMABLE THERMOSTATS
Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control
Low Ambient Control Option (down to 0°F)See table, page 7See table, page 7See table, page 7
Monitor Kit − Service Light76F53SSS
Outdoor
Thermostat
Kit
SignatureStatt Home Comfort Control81M28SSS
Refrigerant
Line Sets
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
3/8 in. tubing93G35SSS
5/8 in. tubing50A93SSS
Thermostat56A87SSS
Mounting Box31461S
L15−65−30L15−65−40
Model No.SPB036H4SPB048H4SPB060H4
Nominal Tonnage3
45
1−1/81−1/8
Inner coil18.00
23.6424.14
No. of rows222
Fins per inch222222
Diameter − in.222226
No. of blades4
43
Motor hp1/61/41/3
Cfm315039804380
Rpm844836850
Watts215305280
208/230V−3ph208/230V−3ph
Rated load amps11.1513.4617.62
Power factor0.990.990.99
Full load amps1.11.71.8
3.12.9
SS
S
L15−65−50
Field FabricateSS
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 6
Page 7
LOW AMBIENT CONTROL Option (Down to 0°F)
Model No
Number
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No.SPB036H4
SPB048H4SPB060H4
Speed Control KitX5867SSS
Weatherproof Kit56N41SSS
Motor1/2 HP − 230V69H75SSS
Capacitorwith mounting bracket53H06SSS
OUTDOOR SOUND DATA
1
Unit
Octave Band Sound Power Levels dBA, re 10
.
63
1252505001000200040008000
Center Frequency − HZ
−12
Watts
SPB036H480.570.571.571.068.563.558.553.576
SPB048H481.072.571.573.070.566.060.558.576
SPB060H480.572.573.577.572.567.062.558.578
NOTE − the octave sound power data does not include tonal correction.
1
Tested according to ARI Standard 270-95 test conditions.
1
Rating
Sound
(dB)
INSTALLATION CLEARANCES
See NOTES
See
NOTES
See NOTES
NOTES
Control
Box
See
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one
of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm).
Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two
units.
48 in. (1219 mm) clearance required on top of unit.
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 7
Page 8
DIMENSIONS − INCHES (MM)
Model N
TOP VIEW
DISCHARGE AIR
VAPOR LINE
CONNECTION
LIQUID LINE
CONNECTION
BC
LIQUID LINE
CONNECTION
4−1/4(108)
SIDE VIEW
UNIT SUPPORT
FEET
8−1/2
(216)
8−3/4
(222)
5−1/2
(140)
13−1/2
(343)
SPB036H4 T0 SPB048H4 BASE SECTION
ELECTRICAL
INLETS
VAPOR LINE
CONNECTION
4−3/4
(121)
9−1/2
(241)
8−1/4
(210)
A
2 (51)
UNIT SUPPORT
FEET
16−7/8
(429)
8−3/4
(222)
3−1/8
(79)
1 (25)
END VIEW
30−3/4
(781)
SPB060H4 BASE SECTION
26−7/8
(683)
3−3/4
(95)
4−5/8
(117)
o.
SPB036H4
SPB048H445114330−1/277535889
SPB060H43999135−1/290239−1/21003
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 8
ABC
in.
mmin.mmin.mm
3588930−1/277535889
Page 9
ARI RATINGS − INDOOR COIL / AIR HANDLER SUBSTITUTION
Substituting Coils in the ARI Tables
Most R−22 and R−410A indoor coils and air handlers are
the same except for the factory installed expansion
device. C33 coils can be used in place of the CX34 coils,
CB26UH−R, CB30M and CB31MV air handlers can be
used in place of the CB26XUH, CBX32M and CBX32MV,
respectively.
The expansion device is based on the size of the outdoor
unit. The factory installed RFC or TXV on the
C33/CB26UH−R/CB31MV/CB30M must be replaced to
correspond to the outdoor unit. The correct TXV’s are:
3 ton heat pumps49L24
4−5 ton heat pumps91M02
Example:
A four−ton heat pump is being installed. The ARI table
shows that CBX32MV−048 is a matching air handler. A
CB31MV−51 with a 91M02 TXV can be used in its place.
UP−FLOW COILS
CX34−18/24A−6F
CX34−18/24B−6F=
CX34−18/24C−6F=
CX34−44/48B−6F
CX34−44/48C−6F
R−410AR−22
=
C33−24A−2
C33−24B−2
C33−24C−2
CX34−19A−6F
CX34−25A−6F
CX34−25B−6F
CX34−30A−6F
CX34−30B−6F
CX34−30C−6F
CX34−31A−6F
CX34−31B−6F
CX34−36A−6F
CX34−36B−6F
CX34−36C−6F
CX34−38A−6F
CX34−38B−6F
CX34−42B−6F=C33−42B−2
CX34−43B−6F=C33−43B−2
CX34−43C−6F=C33−43C−2
no equivalent
CX34−49C−6F
CX34−50/60C−6F
CX34−60D−6F
CX34−62C−6F
CX34−62D−6F
=
C33−19A−2
=
C33−25A−2
=
C33−25B−2
=
C33−30A−2
=
C33−30B−2
=
C33−30C−2
=
C33−31A−2
=
C33−31B−2
=
C33−36A−2
=
C33−36B−2
=
C33−36C−2
=
C33−38A−2
=
C33−38B−2
C33−44C−2
=
C33−48B−2
=
C33−48C−2
=
C33−49C−2
=
C33−50/60C−2
=
C33−60D−2
=
C33−62C−2
=
C33−62D−2
AIR HANDLERS
CBX32M−018/024=CB30M−21/26
CBX32MV−018/024no equivalent
CBX32MV−024/030no equivalent
R−410AR−22
CBX26UH−018
CBX26UH−024=CB26UH−024−R
CBX26UH−030=CB26UH−030−R
CBX26UH−036
CBX26UH−042=CB26UH−042−R
CBX26UH−048=CB26UH−048
CBX26UH−060
CBX32M−030=CB30M−31
CBX32M−036
CBX32M−042=CB30M−46
CBX32M−048=CB30M−51
CBX32M−060
CBX32MV−036
CBX32MV−048=CB31MV−51
CBX32MV−060=CB31MV−65
CBX32MV−068
=CB26UH−018−R
=CB26UH−036−R
=CB26UH−060−R
=CB30M−41
=CB30M−65
=CB31MV−41
no equivalent
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 9
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air.
High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air.
Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Indoor Unit Model No.
3
CBX32M−030 (Multi−Position)Factory TXV
3
CB30U−31 (Up−Flow)
4
CBX32MV−024/030 (Multi−Position)Factory TXV
3
CBX32M−036 (Multi−Position)Factory TXV
3
CB30U−41/46 (Up−Flow)
4,5
CBX32MV−036 (Multi−Position)Factory TXV
4
CBX27UH−036 (Up−Flow/Horizontal)
4
CBX27UH−042 (Up−Flow/Horizontal)
3
CX34−38A/B−6FFactory TXV
4
G60UHV−36A−070Factory TXV
4
G61MPV−36B−045Factory TXV
4
G61MPV−36B−070Factory TXV
4
G60UHV−36B−090Factory TXV
4
G61MPV−36C−090
4
G61MPV−36C−090
4
G60UHV−36B−090
3
CR33−48B/C−F
3
CR33−50/60C−F
4
G61MPV−36B−070
4
G61MPV−36B−045
4
G61MPV−36C−090
4
G60DFV−36B−090
4
G61MPV−36C−090
3
CH23−51
3
CH23−65
4
G60UHV−36B−090
4
G61MPV−36C−090
4
G60UHV−36B−090
Device
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
2
49L24
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 10
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air.
High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air.
Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
Indoor Unit Model No.
3
CB30U−51 (Up−Flow)
4
CBX32MV−048 (Multi−Position)Factory TXV
4
CBX27UH−060 (Up−Flow/Horizontal) Factory TXV
3
CBX32M−048 (Multi−Position)Factory TXV
4
CBX27UH−048 (Up−Flow/Horizontal) Factory TXV
4
CBX32MV−068 (Multi−Position)Factory TXV
4,5
CBX32MV−060 (Multi−Position)Factory TXV
3
CBX32M−060 (Multi−Position)Factory TXV
3
CB30U−65 (Up−Flow)
4
G60UHV−60D−135Factory TXV
4
G60UHV−60D−135Factory TXV
4
G61MPV−60D−135 Factory TXV
4
G61MPV−60D−135 Factory TXV
3
CH33−62D−2F
3
CH23−68
4
G60UHV−60D−135
4
G60UHV−60D−135
4
G61MPV−60D−135
Device
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 11
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. of connecting refrigerant lines;
Cooling Ratings − 95_F outdoor air temperature and 80_F db/67_F wb entering indoor coil air.
High Temperature Heating Ratings − 47_F db/43_F wb outdoor air temperature and 70_F db entering indoor coil air.
Low Temperature Heating Ratings − 17_F db/15_F wb outdoor air temperature and 70_F db entering indoor coil air.
2
Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).
3
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommend for field installation.
4
Blower control must be set for a time−off blower delay.
5
Most popular air handler combination.
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 12
Indoor Unit Model No.
4
CBX32MV−068 (Multi−Position)Factory TXV
4,5
CBX32MV−060 (Multi−Position)Factory TXV
3
CBX32M−060 (Multi−Position)Factory TXV
4
CBX27UH−060 (Up−Flow/Horizontal) Factory TXV
3
CX34−60D−6FFactory TXV
3
CX34−49C−6FFactory TXV
3
CX34−62D−6FFactory TXV
3
CX34−62C−6FFactory TXV
4
G61MPV−60D−135Factory TXV
4
G61MPV−60C−110Factory TXV
4
G60UHV−60C−090Factory TXV
4
G60UHV−60C−110Factory TXV
4
G60UHV−60D−135Factory TXV
4
G61MPV−60D−135 Factory TXV
4
G61MPV−60C−090 Factory TXV
4
G60UHV−60C−110Factory TXV
4
G60UHV−60C−090Factory TXV
4
G61MPV−60C−110Factory TXV
4
G60UHV−60D−135Factory TXV
4
G61MPV−60C−090 Factory TXV
4
G61MPV−60D−135
4
G61MPV−60C−110
4
G61MPV−60C−090
4
G60DFV−60D−135
4
G60DFV−60C−110
4
G60DFV−60C−090
3
CH33−60D−2F
3
CH33−62D−2F
3
CH23−68
4
G61MPV−60D−135
4
G61MPV−60D−135
4
G60UHV−60D−135
4
G60UHV−60D−135
Device
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
2
91M02
Page 13
GUIDE SPECIFICATIONS
This specification specifies [Lennox SPB S−Class®] split system heat pumps. These products are manufactured
by Lennox Industries. Revise section number and title below to suit project requirements, specification practices
and section content. Refer to CSI MasterFormat for other section numbers and titles.
Optional text and text that requires a decision are indicated by bold brackets [ ] and proprietary information is
indicated by bold italic brackets[ ]; delete text that is not needed in final copy of specification. Specifier Notes
typically precede specification text; delete notes in final copy of specification. Trade/brand names with appropriate
symbols typically are used in Specifier Notes; symbols are not used in specification text. Metric conversion, where
used, is soft metric conversion.
AIR−SOURCE UNITARY HEAT PUMPS
PART 1 GENERAL
PART 1.01SUMMARY
A.Section Includes: Split System Air Conditioners, including:
1.Cabinet
2.Compressor
3.Refrigerant system
4.Controls
5.Refrigerant line connectors, electrical inlets and service valves.
SECTION 23 81 43
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI MasterFormat
and specifier’s practice.
Specifier Note: Article below may be omitted when specifying manufacturer’s proprietary products and recommended
installation. Retain Reference Article when specifying products and installation by an industry reference standard. If
retained, list standard(s) referenced in this section. Indicate issuing authority name, acronym, standard designation and
title. Establish policy for indicating edition date of standard referenced. Conditions of the Contract or Division 01
References Section may establish the edition date of standards. This article does not require compliance with standard, but
is merely a listing of references used. Article below should list only those industry standards referenced in this section.
Retain only those reference standards to be used within the text of this Section. Add and delete as required for specific
project.
PART 1.02REFERENCES
A.Air−Conditioning and Refrigeration Institute (ARI):
2.ARI 270 – 1995, Sound Rating of Outdoor Unitary Equipment.
B.Servicing Standards:
1.Underwriters Laboratories, Inc.® (UL)
2.Canadian Electric Code (CEC)
3.Underwriters Laboratories of Canada® (ULC)
C.Department of Energy (DOE), units rated to
D.ISO 9001 registered manufacturing quality system
E.Units to Be Energy Star® compliant
Specifier Note: Article below should be restricted to statements describing design or performance requirements and
functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and operational properties
required to link components of a system together and to interface with other systems.
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 13
Page 14
GUIDE SPECIFICATIONS
PART 1.03SYSTEM DESCRIPTION
A.Performance Requirements:
Specifier Note: Refer to Lennox Engineering Handbook for specific heating and cooling capacities. Units are available in 3, 4
and 5 ton models. Cooling capacities vary from 33,400 to 58,500 Btuh, and heating capacities vary from 32,000 to 54, 000
Btuh.
1.3, 4 and 5 ton capacity
2.Electrical Characteristics:
a.60 Hz
b.3−phase
c.208/230 V
Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or after
construction. Coordinate this article with Architect’s and Contractor’s duties and responsibilities in Conditions of the
Contract and Division 01 Submittal Procedures Section.
PART 1.04SUBMITTALS
A.General: Submit listed submittals in accordance with Conditions of the Contract and Division 01 Submittal Procedures.
B.Product Data: Submit product data for specified products.
C.Shop Drawings:
1.Submit shop drawings in accordance with Section [01 33 00 − Submittal Procedures] [_____].
2.Indicate:
a.Equipment, piping and connections, together with valves, strainers, control assemblies, thermostatic controls,
auxiliaries and hardware, and recommended ancillaries that are mounted, wired and piped ready for final
connection to building system, its size and recommended bypass connections.
b.Piping, valves and fittings shipped loose showing final location in assembly.
c.Control equipment shipped loose, showing final location in assembly.
d.Field wiring diagrams.
e.Dimensions, internal and external construction details, installation clearances, recommended method of
installation, sizes and location of mounting boltholes.
f.Detailed composite wiring diagrams for control systems showing factory installed wiring and equipment on split
systems or required for controlling devices or ancillaries, accessories, controllers.
D.Quality Assurance:
1.Test Reports: Certified test reports showing compliance with specified performance characteristics and physical
properties.
2.Certificates: Product certificates signed by manufacturer certifying materials comply with specified performance
characteristics and criteria and physical requirements.
Specifier Note: Coordinate paragraph below with Part 3 Field Quality Requirements Article. Retain or delete as applicable.
E.Manufacturer’s Field Reports: Manufacturer’s field reports specified.
F.Closeout Submittals: Submit the following:
1.Warranty: Warranty documents specified.
2.Operation and Maintenance Data: Operation and maintenance data for installed products in accordance with
Division 01 Closeout Submittals (Maintenance Data and Operation Data) Section. Include methods for maintaining
installed products, and precautions against cleaning materials and methods detrimental to finishes and performance.
Include names and addresses of spare part suppliers.
3.Provide brief description of unit, with details of function, operation, control and component service.
4.Commissioning Report: Submit commissioning reports, report forms and schematics in accordance with Section
[01 91 00 − Commissioning] [______].
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 14
Page 15
GUIDE SPECIFICATIONS
PART 1.05QUALITY ASSURANCE
A.Qualifications:
1.Installer experienced in performing work of this section who has specialized in installation of work similar to that
required for this project.
2.Manufacturer Qualifications: Manufacturer capable of providing field service representation during construction and
approving application method.
instructions and manufacturer’s warranty requirements. Comply with Division 01 Project Management and Coordination
(Project Meetings).
PART 1.06DELIVERY, STORAGE & HANDLING
A.General: Comply with [01 61 00 − Common Product Requirements] [_____].
B.Ordering: Comply with manufacturer’s ordering instructions and lead−time requirements to avoid construction delays.
C.Packing, Shipping, Handling and Delivery:
1.Deliver materials in manufacturer’s original, unopened, undamaged containers with identification labels intact.
2.Ship, handle and unload units according to manufacturer’s instructions.
D.Storage and Protection:
1.Store materials protected from exposure to harmful weather conditions.
2.Factory shipping covers to remain in place until installation.
Specifier Note: Include or remove following section as project dictates.
E.Waste Management and Disposal:
Specifier Note: ENVIRONMENT: The disposal of packaging waste into landfill site demonstrates an inefficient use of natural
resources and consumes valuable landfill space.
1.Separate waste materials for [Reuse] [And] [Recycling] [_____] in accordance with Section [01 74 19 −
Construction Waste Management and Disposal] [_____].
2.Remove from site and dispose of packaging materials at appropriate recycling facilities.
3.Collect and separate for disposal [Paper] [Plastic] [Polystyrene] [Corrugated cardboard] [_____] packaging
material [In appropriate onsite bins] [_____] for recycling.
Specifier Note: Coordinate article below with Conditions of the Contract and with Division 01 Closeout Submittals
(Warranty).
PART 1.07WARRANTY
A.Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B.Manufacturer’s Warranty: Submit, for Owner’s acceptance, manufacturer’s standard warranty document executed by
authorized company official. Manufacturer’s warranty is in addition to, and not a limitation of, other rights Owner may have
under Contract Documents.
Specifier Note: Coordinate paragraph below with manufacturer’s warranty requirements.
C.Warranty: Commencing on Date of Installation.
1.Compressor: Five years (limited) (non−residential)
2.Other Covered Components: One year (limited) (non−residential)
SPB − 3 to 5 Ton R−410A Heat PumpOutdoor Units / Page 15
Page 16
GUIDE SPECIFICATIONS
PART 2 PRODUCTS
Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance
characteristics, material standards, and descriptions as applicable. Use of such phrases as or equal" or or approved
equal" or similar phrases may cause ambiguity in specifications. Such phrases require verification (procedural, legal and
regulatory) and assignment of responsibility for determining or equal" products.
PART 2.01AIR CONDITIONERS/SPLIT SYSTEM UNITS
A.Manufacturer: [Lennox Industries]
1.[Contact: 2100 Lake Park Blvd., Richardson, TX 75080; Telephone: (800) 453−6669; website: www.lennox.com]
B.[Proprietary] Products/Systems: [SPB, S−Class®] Heat Pump Units, including the following equipment:
1.All units to be factory assembled, wired and piped
2.All units to be assembled in the USA
3.All units to be factory tested prior to shipping
4.Cabinet:
a.Heavy−gauge steel construction
b.Corrosion free pre−painted cabinet finish
c.Corrosion free pre−painted base section
d.Compressor and control box
1)Located in separate compartment inside unit
2)Insulated with thick fiberglass insulation
e.Control box with controls factory wired
f.Large removable service access panel
g.Base drainage holes for moisture removal
h.High density polyurethane unit support feet
i.Coil protection panels
1)[SmartHinget]
2)Steel construction
3)Hinged
4)Louvered
5)May be completely removable
j.Refrigerant Line Connections, Electrical Inlets, Service Valves:
1)Sweat connection vapor and liquid lines located on cabinet corner
2)Fully serviceable brass service valves
3)Full shutoff vapor valve
4)Liquid valve can be front seated to manage refrigerant charge while servicing system
5)Vapor and liquid line service valve to be located inside unit
6)Suction and liquid line gauge ports to be located inside unit
7)Refrigerant line connections and field wiring inlets to be located in one central area
5.Controls:
a.Defrost Control
b.[Options:]
1)[Indoor Blower Speed Relay Kit]
2)[Time Delay Relay Kit]
3)[Low Ambient Kit (down to 30° F)]
4)[Low Ambient Control Option (down to 0° F)]
5)[Compressor Low Ambient Cutoff]
6)[Compressor Lock−out thermostat]
7)[Monitor Kit – Service Light]
8)[Commercial Touchscreen Thermostat by Lennox]
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 16
Page 17
GUIDE SPECIFICATIONS
6.Compressor:
a.Two Stage
b.Scroll type
c.Resiliently mounted on rubber mounts for vibration isolation
d.Internal excessive current and temperature protection
e.Crankcase heater
f.[Outdoor Thermostat Kit – Field installed]
7.Refrigerant System:
a.Refrigerant: R410−a
b.Units to come pre−charged
c.Outdoor Coil Fan:
1)Direct drive fan
2)Vertical air discharge
3)Totally enclosed fan motor with sleeve bearings
4)Inherently protected fan motor
5)Corrosion resistant PVC coated steel fan guard
6)Removable fan guard for fan service access
d.Copper Tube/Fin Coil:
1)Copper tube
2)Flared shoulder connections
3)Silver solder construction
4)Lanced, ripple−edged aluminum fins
5)Coil is leak tested at factory
e.Entire coil to be accessible for cleaning Standard factory installed features:
1)Expansion valve to be factory piped
2)Discharge temperature switch
3)High pressure switch
4)Low pressure switch
5)Hi−capacity liquid line drier
6)Four (4) – way reversing valve
f.[Options]:
1)[Field installed expansion valve kits]
2)[Freezestat that opens at 29°F and closes at 58°F]
3)[Refrigerant Line Kit]
8.See manufacturers documentation for matching add−ons:
a.Air handlers
b.Furnaces:
1)Dual fuel applications
2)[FM21® dual fuel furnace control]
9.Installer must:
a.Set heat pump
1)Connect refrigerant lines
2)Make electrical connections
Specifier Note: Edit article below to suit project requirements. If substitutions are permitted, edit text below. Add text to
refer to Division 01 Project Requirements (Product Substitutions Procedures) Section.
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 17
Page 18
GUIDE SPECIFICATIONS
PART 2.02PRODUCT SUBSTITUTIONS
A.Substitutions: No substitutions permitted.
PART 3 EXECUTION
PART 3.01MANUFACTURER’S INSTRUCTIONS
Specifier Note: Revise article below to suit project requirements and specifier’s practice.
A.Compliance: Comply with manufacturer’s written data, including product technical bulletins, product catalog installation
instructions and product carton installation instructions.
PART 3.02EXAMINATION
A.Site Verification of Conditions: Verify that substrate conditions, which have been previously installed under other sections,
are acceptable for product installation in accordance with manufacturer’s instructions.
PART 3.03INSTALLATION
A.Install heat pump in accordance with manufacturer’s instructions and regulations of authorities having jurisdiction.
END OF SECTION
SPB − 3 to 5 Ton R−410A Heat Pump Outdoor Units / Page 18
Page 19
REVISIONS
SectionsDescription of Change
DimensionsAdded new base section view.
Specifications TableRefrigerant charge changed on SPB036H4 and SPB060H4 models.
Guide SpecificationsAdded Guide Specifications.
Page 20
Visit us at www.lennox.com
For the latest technical information, www.lennoxdavenet.com
Contact us at 1−800−4−LENNOX
NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.