
INSTALLATION
,t_2006 Lennox industries Inc,
Dallas, Texas, USA
WARNING
A IMPORTANT
CAUTION
INSTRUCTIONS
SPA Units
SPA036H4 (3 Ton)
SPA048H4 (4 Ton)
SPA060H4 (5 Ton)
S-CLASS " HEAT PUMP UNITS
504,867M
06/06
Supersedes 03/06
SPA Outdoor Unit ............................. 1
Shipping and Packing List ...................... 1
General Information ........................... 1
Unit Dimensions ............................... 2
Parts Arrangement ............................ 2
Setting the Unit ............................... 3
Electrical ..................................... 4
Refrigerant Piping ............................. 6
Refrigerant Metering Device .................... 8
Flushing Existing Line Set & Indoor Coil .......... 8
Manifold Gauge Set ........................... 10
Service Valves ................................ 10
Leak Testing .................................. 11
Evacuation ................................... 12
Start-Up ...................................... 12
Refrigerant Charging ........................... 13
System Operation ............................. 16
Defrost System ............................... 17
Maintenance .................................. 18
Optional Accessories .......................... 18
Start-Up and Performance Check List ............ 20
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
)puTeChnical
blications
Litho U.S.A.
The S-Class '" SPA outdoor units use R-410A HFC refrig-
erant. This unit must be installed with a matching indoor
coil and line set as outlined in the Lennox Engineering
Handbook. SPA outdoor units are designed for use in ex-
pansion valve (TXV) systems only. They are not designed
to be used with other refrigerant flow control devices. The
Lennox Engineering Handbook lists indoor TXV kits that
must be ordered separately.
06/06
IIIIIIIIIIIIIIIIIIIIIIIIIIIIHIIIIIIII
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
Assembled SPA outdoor unit
Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Page 1
504,867M
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

Dimen-
Model
sion SPA036 SPA048/060
Inches mm Inches mm
A 30-7/8 784 44-7/8 1140
B 32-1/8 816 32-1/8 816
C 34-1/16 865 34-1/16 865
D 12-3/4 324 14-1/4 362
E 26-5/8 676 26-5/8 676
F 18-5/8 473 18-5/8 473
G 28-1/8 718 28-1/8 718
H 17-1/4 438 18-3/4 476
J 3-7/8 98 3-7/8 98
K 7-1/2 191 7-1/2 191
VAPOR
INLET
TOP INLET
VIEW AIR
COMPRESSOR
ELECTRICAL
INLETS
X _ C r
INLETAIR
INLETAIR
DISCHARGEd&.
AIR BB
COIL DRAIN OUTLETS
(Around perimeter of base)
A
2 (51) -- G 2 (51)
RUN
CAPACITOR
DEFROST
CONTROL
DISCHARGE
LINE
COMPRESSOR
TERMINAL PLUG
TXV/CHECK
VALVE
VAPORLINE
DISCHARGE
TEMPERATURE
THERMOSTAT
LIQUID
LINE
INLET
4-
_" 1/2(114) 1: .......................................................................................................................................
n
T_
:: :__::_:;;................................................................
A 1102). I I I
2-3/4(70) F ----'1_"_ b
1-3/8 (35) _ _ 16-1/161
I:: "Yl (154)
INDEPENDENT
MOTOR MOUNT
CONTACTOR
TWO-STAGE
COMPRESSOR
VAPOR VALVE AND
GAUGE PORT
LOW PRESSURE
SWITCH
FILTER DRIER
CRANKCASE
HEATER
HIGH PRESSURE
SWITCH
SIDE
VIEW
504867M 06/06
Page 2

WARNING
CAUTION
These units operate under a wide range of weather condi-
tions; therefore, several factors must be considered when
positioning the outdoor unit. The unit must be positioned to
give adequate clearances for sufficient airflow and servic-
ing, Refer to figure 1 for installation clearances.
Installation Clearances
I AS NOTED TM
(762 _ AS NOTED
mm)
36" _}
I AS NOTEDj
NOTE - A service access clearance of 30" (762 mm)
must be maintained in front of the service access panel.
Clearance to one side must be 36" (914 mm). Clearance
to one of the remaining two sides may be 12" (305 mm)
and the final side may be 6" (152 mm).
NO TE - A clearance of 24" (610 mm) must be maintained
between two units.
NOTE - 48" (1219 mm) clearance required on top of unit.
Maximum soffit overhang is 36" (914 mm).
Figure 1
1, Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or posi-
tion that will transmit sound or vibration to the to the
conditioned space.
2, Mount unit high enough above ground or roof to allow
adequate drainage of defrost water and prevent ice
build-up,
3, In heavy snow areas, do not locate unit where drifting
will occur. The unit base should be elevated above the
depth of average snows,
NOTE - Elevation of the unit may be accomplished by
constructing a frame using suitable materials. If a sup-
port frame is constructed, it must not block drain holes
in unit base.
4, When installed in areas where low ambient tempera-
tures exist, locate unit so winter prevailing winds do
not blow directly into outdoor coil.
5, Locate unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil
or into unit,
Slab Mounting
When installing unit at grade level, top of slab should be
high enough above the grade so that water from higher
ground will not collect around unit, See figure 2. Slab
should have a slope tolerance away from the building of 2
degrees or 2 inches per 5 feet (51 mm per 1,5 m), This will
prevent ice build-up under unit during a defrost cycle. Re-
fer to roof mounting section for barrier construction if unit
must face prevailing winter winds,
Slab Mounting
2 degrees or
2 in. per 5 foot DISCHARGE
(51 mm per 1.5 m) AIR
slope tolerance away A
from building structure
-L[
BUILDING
STRUCTURE
:21-
ZZ-
CL
CZ-
GROUND
LEVEL
Figure 2
Roof Mounting
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build-up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit, Consult local codes for
rooftop applications.
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. See figure 3.
Size barrier at least the same height and width as outdoor
unit, Mount barrier 24 inches (610 mm) from the sides of
the unit in the direction of prevailing winds,
Page 3
SPA SERIES

Rooftop Application with Wind Barrier
prevailir_Rer winds
wind barrier inlet
air
©
1
(610 ram)
24"
I
1
/r',
k_J
I
I •
©
inlet air
Figure 3
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
WARNING l,
O inlet air
Refer to figure 4 for high voltage field wiring diagram.
NOTE -A complete unit wiring diagram is located in-
side the unit's access door.
NOTE - For proper voltages, select thermostat wire
gauge per the following chart:
Wire run length AWG # Insulation type
less than 100' (30m) 18 color-coded, temperature
more than 100' (30m) 16 rating 35°C minimum
3. Install room thermostat (ordered separately) on an inside
wall approximately in the center of the conditioned area
and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figure 7.
NOTE - 24V, Class II circuit connections are made in
the low voltage junction box.
Three-Phase Scroll Voltage Phasing
Three-phase scroll compressors must be phased sequential-
ly to ensure correct compressor rotation and operation. In-
correct linevoltage phasing may cause compressor damage
and abnormal unit operation. Power wires are color-coded as
follows: Line 1 - red, line 2 - yellow, line 3 - blue.
To test for proper rotation and operation:
1. Install refrigeration gauges on system. Cycle compres-
sor "On" and observe that suction pressure decreases
and discharge pressure increases.
2. If pressures do not follow the above conditions, discon-
nect all power to unit. Reverse any two field-installed
main power wires to the lineside of the compressor con-
tactor. Make sure connections are tight. Repeat pres-
sure test with system.
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
1. Install line voltage power supply to unit from a properly
sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth
ground.
NOTE - Connect conduit to the unit using a proper
conduit fitting.
NO TE - Units are approved for use only with copper
conductors.
Typical Field Wiring Diagram
A 108 BROUND
_ DEFROST CONTROL LU6 _ "_C FAN
OUT _ sz_ "
OUTDOOR L LI
rAN
/ I _ ORAN6E-COM_ON _-PS Y2
PURPLE =
\_'_ C_]TOR ?[L _ Yl 2081
A ARNING! ELECTRIC SHOCK HAZARD! Can cause
cI o 230/
CAPACITOR =RV_---L o 3/60
For use with copper conductors only Refer to Unit rating
plate for minimum circuit ampacity and maximum overcur-
rent protection size.
injury or death. Unit must be grounded in accordance with
national and local codes.
C COMPRESSOR
-0UT K' A
K 195 SPEED
CONTACTOR
Figure 4
LZ
504867M 06/06
Page 4

Outdoor Unit, Blower Unit,
Thermostat Designations
SPA TB1 A2 Thermostat
(Some connections
may not apply.
Refer to specific
thermostat and in-
door unit,)
@--
©--
©--
@--
©--
$4 SZ3
HiGH $5 LOW
PRESSURE DISCH TEMP AMBIENT
SWITCH LIMIT
THERMOSTAT If¢7_,#_,/_%_I PLATE FOR MINIMUM CIRCUIT
©©
$87 LOW LI
PRESSURE REVERSING
SWITCH VALVE
RTIS
AMBIENT COIL ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY
SENSOR SENSOR OR DEATH,UNIT MUST BE GROUNDED IN
©@
L_ ,C_
HR I CONTACT0 I A
_ _TA6rl _ L
)"L _
Indoor Unit
©E
GE ©1
@E @1
Figure 5
Typical SPA Wiring
DI_ z_ MOTE-
COMPRESSOR ONLY,REFER TO UNIT RATING
z:_ Z_ REFER TO COMPRESSOR IN UNIT
RT21 A FOR ACTUAL TERMINAL ARRANGEMENT.
DEFROST _ WARNING-
/_ ACCORDANCE WITH NATIONAL AND LOCAL CODES,
CE
CAPACITOR
FOR USE WITH COPPER CONDUCTORS
AMPACITY AND MAXIMUM OVER-
CURRENT PROTECTION SIZE
-,,e-_DENOTES OPTIONAL COMPONENTS
-- LINE VOLTAGE FIELD INSTALLED
-- -- -- CLASS II VOLTAGE FIELD INSTALLED
Be
FAN
LE
W
(I y KI
C K2 AN
Outdoor Unit, CB31MV/CB32MV,
Thermostat Designations
(Some connections may not apply,
Refer to specific thermostat and indoor unit.)
SPA T7300G
_ Thermostat
CB31MV
CBX32MV
TB1
®1
@-
@1
@1
@1
©1
I _>
I @-
©1
Figure 6
Z_ REMOVE JUMPER FOR TWO STAGE COOL
Z_ RTI4 SENSOR,OUTDOOR TEMP (OPTIONAL}
Z_ $25 CLOSES AT LOW AMBIENT TEMPERATURES
TO OPERATE SECOND STAGE COMPRESSOR
ON HEATING
z_ SII AND K58 ARE OPTIONAL LOW AMBIENT CONTROLS
Z_ L34,SECOND STAGE, SOLENOID IS LOCATED IN
COMPRESSOR. COIL IS 24VOC, DO NOT CONNECT
24VAO TO COIL TERMINALS.
CB31MV
CBXS2MV
TBI
F --
]
]
@-- -- __
_ y;i
A2
]
I
THERMOSTAT
T7300F
60L59
82N52
A_._
--{G>I
-{cYqs
-@ [
(B)
BE_
_ 8
EQUIPMENT c_
GROUND
KI-I
L_ _
+________] RV AMB
rIo£
c......................................I1 ?
z_ RTI3
Figure 7
Page 5
SPA SERIES

If the SPA unit is being installed with a new indoor coil and
line set, the refrigerant connections should be made as
outlined in this section. If an existing line set and/or indoor
coil is going to be used to complete the SPA system, refer
to the following section which includes flushing proce-
dures,
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-
flare) series line sets as shown in table 1 or use field-fabri-
cated refrigerant lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Sets
Valve Field Size
Model
036
048
060
Connections
Liquid Vapor
Line Line
3t8 in. 7/8 in.
10 mm 22 mm
3t8 in. 7/8 in.
10 mm 22 mm
3t8in. 1-1/8in.
10 mm 29 mm
Recommended Line Set
Liquid Vapor
Line Line
3/8 in. 7/8 in.
10 mm 22 mm
3/8 in. 7/8 in.
10 mm 22 mm
3/8 in. 1-1/8 in.
10 mm 29 mm
L15
Line Sets
L15-65
15-50 ft.
4.6-15m
Field
Fabricated
necessary vibration. Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound, As a result, more
energy or vibration can be expected, Closer attention to
line set isolation must be observed,
Following are some points to consider when placing and
installing a high-efficiency outdoor unit:
1. Placement - Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans-
mission,
2. Line Set Isolation - The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 8 shows how to place the outdoor
unit and line set. Figure 9 shows how to install line sets
on horizontal runs. Figure 10 shows how to make a
transition from horizontal to vertical. Figure 11 shows
how to install line sets on vertical runs.
Outside Unit Placement and Installation
INSTALL UNIT AWAY _
FROM WINDOWS.
J
Refrigerant Line Set Connections - SPA
Matched with New Indoor Coil and Line Set
If an existing indoor coil which was equipped with an RFCI
metering device is being replaced, the liquid line must also
be replaced prior to the installation of the SPA unit,
"2 ,,
NOTE - Units are designed for line sets of up to 50 feet
(15 m).
Installing Refrigerant Line
During the installation of any heat pump system, it is impor-
tant to properly isolate the refrigerant lines to prevent un-
Refrigerant Line Sets: Installing Horizontal Runs
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties. WIRE TIE
8 feet (Around vapor line only)
STRAPPING MATERIAL
(Around vapor line only),
FLOOR JOIST OR
ROOF RAFTER
8 feet WIRE TIE
TAPE OR
TWO 90 ° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
Figure 8
Strap the vapor line to the joist or
rafter at 8 ft. intervals then strap
the liquid line to the vapor line.
TAPE OR WIRE TIE N
504867M 06/06
METAL FLOOR JOIST OR ,
SLEEVE ROOF RAFTER
Figure 9
Page 6