Lennox SLP98UHV SERIES, SLP98UH070V36B, SLP98UH090V36C, SLP98UH090V48C, SLP98UH090V60C, SLP98UH110V60C, SLP98UH135V60D Unit Information
Specifications and Main Features
Frequently Asked Questions
User Manual
Service Literature
Corp. 1029−L7
SLP98UHV SERIES UNITS
SLP98UHV series units are high−efficiency upflow, horizontal right and left) gas furnaces equipped with variable capacity gas valve, variable speed combustion air inducer and
variable speed indoor blower motor. All models are designed only for direct vent (dual pipe) venting system.
SLP98UHV units are available in heating capacities from
66,000 to 132,000 Btuh (19.3 to 38.6 kW) and cooling applications from 2 to 5 tons (7.0 kW to 17.5 kW). Refer to Engineering Handbook for proper sizing.
Units are factory−equipped for use with natural gas. Kits are
available for conversion to LPG operation. SLP98UHV mod-
®
els include a SureLight
that can be used with Lennox icomfort Touch thermostat as
part of a communicating comfort system. All SLP98UHV
units meet the California Nitrogen Oxides (NOx) Standards
and California Seasonal Efficiency requirements.
variable capacity integrated control
SLP98UHV
All specifications in this manual are subject to change. Procedures outlined in this manual are presented as recommendations only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommendations only and do not constitute code.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect switch(es). Unit may have multiple
power supplies.
WARNING
Sharp edges.
Be careful when servicing unit to avoid sharp edges
which may result in personal injury.
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.SLP98UH070V36BSLP98UH090V36CSLP98UH090V48C
1
AFUE97.0%98.0%97.5%
Output - Btuh64,00085,00085,000
3.5 / 10.03.5 / 10.03.5 / 10.0
Output - Btuh22,00030,00030,000
0.5 / 1.50.5 / 1.50.5 / 1.5
Motor output - hp1/21/23/4
SPECIFICATIONS
Gas
Heating
Performance
MaximumInput - Btuh88,000110,000132,000
Temperature rise range - °F50 - 8050 - 8055 - 85
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
MinimumInput - Btuh31,00039,00046,000
Temperature rise range - °F35 - 6535 - 6535 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g.0.80.80.8
Connections
in.
Condensate Drain Trap (PVC pipe) - i.d.1/21/21/2
Intake / Exhaust Pipe (PVC)2 / 22 / 22 / 2
with eld supplied (PVC coupling) - o.d.1/2 slip x 1/2 NPT1/2 slip x 1/2 NPT1/2 slip x 1/2 NPT
hose with hose clamp - i.d. x o.d.1 x 1-1/41 x 1-1/41 x 1-1/4
Gas pipe size IPS1/21/21/2
Indoor
Wheel nominal diameter x width - in.11 x 1111 x 1111 x 11
Blower
Tons of add-on cooling3 - 53 - 53.5 - 5
Air Volume Range - cfm375 - 2195554 - 2125634 - 2190
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.SLP98UH090V60CSLP98UH110V60CSLP98UH135V60D
1
AFUE98.2%97.5%97.5%
Output - Btuh85,000106,000126,000
3.5 / 10.03.5 / 10.03.5 / 10.0
Output - Btuh30,00038,00045,000
0.5 / 1.50.5 / 1.50.5 / 1.5
Motor output - hp111
Page 2
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
“B” Width
Models
CABINET ACCESSORIES
Horizontal Suspension Kit - Horizontal only51W1051W1051W10
Return Air Base - Upow only50W9850W9951W00
CONDENSATE DRAIN KITS
Condensate Drain Heat Cable6 ft. 26K6826K6826K68
24 ft.26K6926K6926K69
50 ft.26K7026K7026K70
Heat Cable TapeFiberglass - 1/2 in. x 66 ft.36G5336G5336G53
Remote Outdoor Sensor may be used with an icomfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a
conventional outdoor unit.
2
Optional for service diagnostics.
3
Remote Outdoor Temperature Sensor for ComfortSense 7000 Thermostat must be connected directly to the thermostat, Do not connect it to the icomfort™ control board.
4
Cleanable polyurethane frame type lter.
NOTE - Termination Kits 44W92, 44W93, 30G28, 81J20 are certied to ULC S636 standard for use in Canada only.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
Page 4
BLOWER DATA
SLP98UH070V36B BLOWER PERFORMANCE (less lter)
RIGHT SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm.
Page 7
BLOWER DATA
SLP98UH090V48C BLOWER PERFORMANCE (less lter)
RIGHT SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm (SLP98UH090V48C) and 450 cfm (SLP98UH090V60C).
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
Page 10
BLOWER DATA
SLP98UH110V60C BLOWER PERFORMANCE (less lter)
RIGHT SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
Page 12
BURNER BOX ASSEMBLY
SLP98UHV PARTS ARRANGEMENT
PRESSURE SWITCHES
VARIABLE
CAPACITY
GAS VALVE
VARIABLE SPEED
COMBUSTION AIR
INDUCER
HEAT EXCHANGER
PRIMARY LIMIT
BAG ASSEMBLIES
(shipping location)
COLD END HEADER
BOX
ACCESS PANEL
SIGHT GLASS
INNER BLOWER
ACCESS PANEL
VARIABLE SPEED BLOWER MOTOR
CONTROL BOX
(includes variable capacity integrated control
transformer circuit breaker and door switch)
FIGURE 1
Page 13
I−UNIT COMPONENTS
SLP98UHV unit components are shown in figure 1. The gas
valve, combustion air inducer and burners can be accessed
by removing the access panel. Electrical components are in
the control box (figure 2) found in the blower compartment.
SLP98UHV units are factory−equipped with a bottom return air
panel in place. The panel is designed to be field removed as
required for bottom air return. Markings are provided for side
return air and may be cut out in the field.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the trans-
former (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit opera-
tion will shut down. The breaker can be manually reset by
pressing the button on the face. See figure 3.
CIRCUIT BREAKER CB8
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting
the furnace, the control and the technician at the
same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an
unpainted unit surface, such as the gas valve or
blower deck, before performing any service procedure.
A−Control Box 1
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V secondary.
2. Interlock Switch (S51)
An interlock switch rated 14A at 125VAC is wired in series
with line voltage. When the inner blower access panel is removed the unit will shut down.
CONTROL BOX SLP98UHV
TRANSFORMER
CIRCUIT
BREAKER
INTERLOCK
SWITCH
SURELIGHT®
INTEGRATED
CONTROL
FIGURE 2
PRESS TO RESET
FIGURE 3
WARNING
Shock hazard.
Disconnect power before servicing.
Integrated control is not field repairable. If control
is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
4. Integrated Control (A92)
SLP98UHV units are equipped with the Lennox SureLight
variable−capacity integrated control. This control can be
used with the icomfort Touch thermostat as part of a com-
municating comfort system. The control can also operate
with a conventional single or two−stage thermostat. The
system consists of an ignition / blower control (figures 4 and
5) with control pin designations in tables 1 and 2, and ignitor.
The control provides gas ignition, safety checks and indoor
blower control with variable capacity rate gas heating. The
furnace combustion air inducer, gas valve and indoor blow-
er are controlled in response to various system inputs such
as thermostat signal, pressure and limit switch signal and
flame signal. The control features a seven−segment LED
display, indicating furnace status (including indoor blower)
and error codes. The LED flashes in single digits. For exam-
ple using table 14 under LIMIT CODE, an E" followed by 2"
followed by 5" followed by 0", the limit switch circuit is
open. The control also has two 120 volt accessory terminals
(used for a humidifier and electronic air cleaner) rated at (1)
one amp each.
®
Page 14
Electronic Ignition
At the beginning of the heat cycle the SureLight® integrated
control monitors the low fire combustion air inducer pressure switch. The control will not begin the heating cycle if the
low fire pressure switch is closed (by−passed). Likewise the
control will not begin the high fire heating cycle if the high fire
pressure switch is closed, and will remain in low fire heat.
However, if the high fire pressure switch closes during the
low fire heat pre−purge, the control will allow high fire heat.
Once the low fire pressure switch is determined to be open,
the combustion air inducer is energized on ignition speed.
When the differential in the pressure switch is great enough,
the pressure switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the inducer is de−energized and the control will initiate vent calibration. If the vent calibration is unsuccessful the control
goes into a 5 minute delay. The control will attempt vent calibration 3 more times before going into a 1 hour soft lockout.
After the 15 second pre−purge period the SureLight ignitor
warms up for 20 seconds. The gas valve then opens for a
4−second trial for ignition. The ignitor stays energized during
this trial until flame is sensed. If ignition is not proven during
the 4−second trial for ignition, the control will try four more
times with an inter purge and warm−up time between trials of
35 seconds. After a total of five trials for ignition (including
the initial trial), the control goes into Watchguard−Flame
Failure mode. After a 60−minute reset period, the control will
begin the ignition sequence again.
Thermostat Selection Modes
See table 3 for DIP switch settings
The control can be made to operate in three modes: variable capacity, three−stage timed or two−stage. The variable
capacity and two−stage modes are only operational with a
two−stage thermostat. The thermostat selection is made using dip switches one and / or two (figure 4) and must be
positioned for the particular application.
Three−Stage Timed Operation
Using a single−stage thermostat the system will operate in a
three stage timed mode. Upon a call for heat and a successful ignition, the combustion air inducer will operate at 35%
and the indoor blower will adjust to the appropriate cfm. After a field selectable 7 or 12 minute delay period, the inducer RPM will increase and the unit will operate at 70%. The
indoor blower will adjust to the appropriate cfm. After a factory set non−adjustable 10 minute delay expires the furnace
will increase rate to 100%. The indoor blower will adjust to
the appropriate cfm.
Two−Stage Operation
The system will also operate in conventional two−stage
mode. While in two−stage mode, the furnace will fire on low
fire (70% rate). The combustion air inducer will operate at
70% and the indoor blower will adjust to the appropriate
cfm. The unit will switch to high fire on a W2 call from the
thermostat. After a 30 second recognition period (during
which the integrated control will receive a continuous W2
call) expires the furnace will increase to 100% rate. The inducer will increase to 100% speed and the indoor blower will
adjust to appropriate cfm. If there is a simultaneous call for
first and second stage heat, the unit will fire on first stage
heat and switch to second stage heat after 30 seconds of
operation.
TABLE 1
SureLight
®
Control 6 Pin Terminal Designation
PIN #Function
1Data Input From Motor
2Common
3Not Used
4Data Output To Motor
55 Volt Bias Supply
6Not Used
Variable Capacity
Using a two−stage thermostat the system will operate in a
variable capacity sequence mode. In this mode, the control
will vary the firing rate anywhere between 35% and 100% of
full capacity. The indoor blower will be automatically adjusted accordingly to provide the appropriate airflow at any
rate. On the initial call for low fire, the furnace will operate at
35% and will remain there until the heat call is satisfied or a
call for high fire is initiated. If there is a call for high fire the
rate will increase by 10% if the current rate is above 60%.
However, if the current rate is below 60% the rate will increase to 70%. After this initial rate increase to 70% capacity, the furnace will increase rate by 10% every 5 minutes
while a high fire heat call is present. If the high fire heat call is
satisfied but the low fire heat call is still present, the furnace
will remain at the current firing rate until the demand is satisfied or another call for high fire is initiated.
TABLE 2
SureLight Control 12 Pin Terminal Designation
PIN #Function
1Not used
2High Fire Pressure Switch
3Rollout In
4Ground
524V Hot
6Primary Limit In
7Gas Valve
8Gas Valve Common
924V Neutral
10Ground
11Primary Limit Switch Out
12Low Fire Pressure Switch
Page 15
COMBUSTION
AIR INDUCER
CONNECTOR
FLAME
SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
NEUTRAL
TERMINALS
IGNITOR
CONNECTOR
LINE VOLTAGE
+
HUM
EAC
TERMINALS
ON−BOARD
LINKS
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
FACTORY TEST
HEADER PINS.
FACTORY USE ONLY.
TB83 OUTDOOR
TERMINALS
TB84 INDOOR
RS−BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION
I − = DATA LOW CONNECTION
RS−BUS OUTDOOR (TB83)
R = 24VAC
I + = DATA HIGH CONNECTION
I − = DATA LOW CONNECTION
C = 24VAXC COMMON
RS−BUS INDOOR (TB84)
R = 24VAC
I + = DATA HIGH CONNECTION
I − = DATA LOW CONNECTION
C = 24VAXC COMMON
7−SEGMENT
DIAGNOSTIC LED
INDOOR
BLOWER
CONNECTOR
W915 Y1 TO Y2
W951 R TO O
W915
W951
W914
W914 R TO DS
L − use only with
communicating T’stat and
non−communicating outdoor
unit.
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T’STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED
TO TRANSFORMER GRD (TR) & CHASIS GROUND
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
(GRD)
1/4" QUICK CONNECT TERMINALS
HUM = 120 VAC OUTPUT TO HUMIDIFIER
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
CIRC = 120 VAC OUTPUT TO CIRCULATING BLOWER
EAC = 120 VAC OUTPUT TO ELECTRICAL AIR CLEANER
NEUTRALS = 120 VAC NEUTRAL
FIGURE 4
Page 16
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
REVERSING VALVE
H = 24V HUMIDIFIER OUTPUT. DO NOT CONNECT
TO COMFORTSENSE
®
THERMOSTAT
L = USE ONLY WITH A COMMUNICATING
THERMOSTAT AND A NON−COMMU-
NOTE − When the SLP98UHV is used with an icomfort
Toucht communicating thermostat, all indoor blower
speed selections and DIP switch settings are made by
the communicating thermostat.
Heating Operation DIP Switch Settings −− Figure 4
Switch 1 −− Thermostat Selection −− This unit may be used
with either a single−stage or two−stage thermostat. The thermostat selection is made using a DIP switch which must be
properly positioned for the particular application. The DIP
switch is factory−positioned for use with a two−stage thermostat. If a single−stage thermostat is to be used, the DIP
switch must be repositioned. See table 3.
NOTE − All DIP switches are factory shipped in the
OFF" position.
Switch 2 −− Operating Mode with Two−Stage Thermostat
−− If a two−stage thermostat is used, the furnace can operate
in either variable−capacity or conventional two−stage mode.
When variable−capacity mode is selected, the firing rate of
the unit is varied to maximize comfort. Conventional two−
stage mode is the factory default setting. See table 3.
Switch 3 −− Second−Stage Heat On Delay −− If a single−
stage thermostat is used, the integrated control can be used
to energize second−stage heat after either 7 minutes or 12
minutes of first−stage heat operation. See table 3.
Switches 4 and 5 −− Blower−Off Delay −− The blower−on
delay of 45 seconds is not adjustable. The blower−off delay
(time that the blower operates after the heating demand has
been satisfied) can be adjusted by moving switches 4 and 5
on the integrated control. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the blower off delay to achieve a supply
air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures. Table 4 provides the blower off timings that will result from different
switch settings.
Blower Off Delay Switch Settings
TABLE 4
Blower Off Delay
(Seconds)
Switch 4Switch 5
60OffOn
90 (factory)OffOff
120OnOff
180OnOn
Indoor Blower Operation DIP Switch Settings
Switches 6 and 7 −− Continuous Indoor Fan Operation −−
Blower Speed − Switches 6 and 7 are used to select blower
motor speeds during continuous indoor blower operation.
The unit is shipped from the factory with DIP switches positioned for medium low (2) speed during continuous indoor
blower operation. The table below provides the continuous
blower speeds that will result from various switch settings.
Refer to blower tables at the front of this manual for corresponding cfm values.
TABLE 5
Continuous Indoor Fan
SpeedSwitch 6Switch 7
1 − Low (28%)OffOn
2 − Medium Low
(38%)
OffOff
(Factory)
3 − Medium High
(70%)
OnOff
4 − High (100%)OnOn
Switches 8 and 9 −− Cooling Mode Blower Speed −−
Switches 8 and 9 are used to select cooling blower motor
speed. The unit is shipped from the factory with the DIP
switches positioned for high speed (4) indoor blower motor
operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from
different switch settings. Refer to blower tables at the front
of this manual for corresponding cfm values.
TABLE 6
Cooling Mode Blower Speeds
SpeedSwitch 8Switch 9
1 − LowOnOn
2 − Medium LowOffOn
3 − Medium HighOnOff
4 − High (Factory)OffOff
Page 18
Switches 10 and 11 −− Cooling Mode Blower Speed Adjustment −− Switches 10 and 11 are used to select blower
speed adjustment settings. The unit is shipped from the factory with the DIP switches positioned for NORMAL (no) adjustment. The DIP switches may be positioned to adjust the
blower speed by +10% or −10% to better suit the application.
The table below provides blower speed adjustments that
will result from different switch settings. Refer to blower
tables at the front of this manual for corresponding cfm values. With switches 10 and 11 set to ON, motor will bypass
ramping profiles and all delays and immediately upon a call
for cool, run at COOLING speed selected. LED will continue
to operate as normal. This mode is used to check motor operation.
TABLE 7
Blower Speed Adjustment
AdjustmentSwitch 10Switch 11
+10% (approx.)OnOff
NORMAL (Factory)OffOff
−10% (approx.)OffOn
MOTOR TESTOnOn
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds.
Motor then runs at 82% for approximately 7−1/2 min-
utes.
If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Switches 12 and 13 −− Cooling Mode Blower Speed
Ramping −− Switches 12 and 13 are used to select cooling
mode blower speed ramping options. Blower speed ramping may be used to enhance dehumidification performance.
The switches are factory set at option A which has the greatest effect on blower motor performance. Table 8 provides
the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower
speed ramping options are detailed below.
TABLE 8
Cooling Mode Blower Speed Ramping
Ramping OptionSwitch 12Switch 13
A (Factory)OffOff
BOnOff
COffOn
DOnOn
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec-
Switches 14 through 19 are used to select heating mode
blower motor speeds. These switches are factory set at the
OFF position which provides 100 % of normal speed during
HIGH HEAT demand, 70% of normal speed during MID−
RANGE HEAT demand and 40% of normal speed during
LOW HEAT demand. Switches 14, 15 and 16 are used to
adjust the LOW FIRE blower motor speed. Switches 17, 18
and 19 are used to adjust the HIGH FIRE blower motor
speed. Figure 6 and tables 9 and 10 provides the heating
mode blower speeds that will result from different switch
settings. Figure 6 indicates the effect the DIP switch settings (tables 20 &21 above) have upon the heating airflow at
various furnace firing rates.
Refer to blower tables at the front of this manual for corresponding cfm values.
Thermostat
Demand
High Heat
(R to
W1 & W2)
High Heat Blower Speeds
TABLE 10
Blower
Speed
Adjust-
ments
DIP SWITCH SETTINGS
171819
+15%OnOffOn
+7.5%OnOffOff
Normal
OffOffOff
−7.5%OnOnOff
−15%OnOnOn
Increasing
Airflow
+15%
+7.5%
Nominal
−7.5%
−15%
Airflow Determination
Identify blower speed adjustment points at low and high fire
Airflow will lie on straight line between these two points and will fall within
the shaded area as shown
EXAMPLE −7.5% at low fire +7.5% at high fire
Low Fire
Dip Switches
14, 15, 16
35%
50%
60%
70%
RATE (%)
FIGURE 6
80%
90%
High Fire
Dip Switches
17, 18, 19
+15%
+7.5%
Nominal
−7.5%
−15%
100%
Page 20
On−Board Link W914 DS to R (Figure 4)
On−board link W914, is a clippable connection between terminals DS and R on the integrated control. W914 must be
cut when the furnace is installed with either the Harmony
III zone control or a thermostat which features humidity
control. If the link is left intact the PWM signal from the Harmony III control will be blocked and also lead to control damage. Refer to table 15 for operation sequence in applications including SLP98UHV, a thermostat which features humidity control and a single−speed outdoor unit. Table 16
gives the operation sequence in applications with a two−
speed outdoor unit.
On−Board Link W951 R to O (Figure 4)
On−board link W951 is a clippable connection between terminals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal O" will remain energized eliminating the HEAT MODE in the heat pump.
On−Board Link W915 Y1 to Y2 (Figure 4)
On−board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control. W915 must be
cut if two−stage cooling will be used. If the link is not cut the
outdoor unit will operate in second−stage cooling only.
Diagnostic LED (Figure 4)
The seven−segment diagnostic LED displays operating status, target airflow, error codes and other information. Table
14 lists diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the seven−
segment diagnostic LED. This button is used to enable the
Error Code Recall mode and the Field Test mode. Press the
button and hold it to cycle through a menu of options. Every
five seconds a new menu item will be displayed. When the
button is released, the displayed item will be selected. Once
all items in the menu have been displayed, the menu resumes from the beginning until the button is released.
Error Code Recall Mode
Select "E" from the menu to access the most recent 10 error
codes. Select c" from the Error Code Recall menu to clear
all error codes. Button must be pressed a second time while
c" is flashing to confirm command to delete codes. Press
the button until a solid ≡" is displayed to exit the Error Code
Recall mode.
Field Test Mode
Use the diagnostic push button to scroll through the menu
as described above. Release the button when the LED
flashes −" to select the Field Test mode.
While in the Field Test mode the technician can:
Initiate furnace ignition and move to and hold low−fire
rate by applying a R to W1 jumper.
Initiate furnace ignition sequence and move to and hold
high−fire rate by applying a jumper from R to W1 and
W2.
Initiate furnace ignition sequence and move to and hold
mid−fire rate by applying a jumper to R and W2.
Apply then remove the jumper from R to W1 and W2 to
change the firing rate from low fire to mid fire and high
fire.
A vent calibration sequence can be initiated even if a
thermostat signal is not present. Press and hold the
push button until a solid C" is displayed. Release the
button and calibration will begin. The furnace will perform the high−fire and low−fire pressure switch calibrations and display CAL". After calibration, the LED will
return to the flashing −" display.
During Field Test mode operation, all safety switches are
still in the circuit (they are not by−passed) and indoor blower
performance and timings will match DIP switch selections.
Current furnace firing rate, indoor blower CFM and flame
signal will be displayed. To exit the Field Test mode, press
and hold the button. The menu will resume from the beginning. Also, cycle the main power to exit the Field Test mode.
The integrated control will automatically exit the Field Test
mode after 45 minutes of operation.
Page 21
Loading...
+ 48 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.