SLP98DFV series units are high-efficiency downflow gas
furnaces equipped with variable capacity gas valve, vari
able speed combustion air inducer and variable speed in
door blower motor. All models are designed for direct vent
(dual pipe) venting system only. SLP98DFV units are avail
able in heating capacities from 66,000 to 132,000 Btuh
(19.3 to 38.6 kW) and cooling applications from 2 to 5 tons
(7.0 kW to 17.5 kW). Refer to Engineering Handbook for
proper sizing.
Units are factory-equipped for use with natural gas. Kits are
available for conversion to LPG operation. SLP98DFV mod
els include a SureLight
that can be used with Lennox icomfort Wi-Fi
part of a communicating comfort system. All SLP98DFV
units meet the California Nitrogen Oxides (NO
and California Seasonal Efficiency requirements.
®
variable capacity integrated control
®
thermostat as
) Standards
x
SLP98DFV
All specifications in this manual are subject to change. Pro
cedures outlined in this manual are presented as recom
mendations only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommendations only and do not consti
tute code.
TABLE OF CONTENTS
SpecificationsPage 2.............................
Optional AccessoriesPage 3......................
Blower DataPage 4..............................
I Unit ComponentsPage 8........................
II icomfort Wi-Fi
III Placement and InstallationPage 35..............
IV Start UpPage 53..............................
V Heating System Service ChecksPage 54..........
VI Typical Operating CharacteristicsPage 57........
VII MaintenancePage 57..........................
VIII Wiring and Sequence of Operation Page 60.....
IX Field WiringPage 68...........................
®
ThermostatPage 33..............
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a licensed professional HVAC in
staller (or equivalent), service agency or the gas sup
plier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal injury.
Take care while handling this equipment and wear
gloves and protective clothing.
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SLP98DF070XV36BSLP98DF090XV36CSLP98DF090XV48C
1
AFUE97.5%97.5%97.5%
Output - Btuh64,00084,00085,000
3.5 / 10.03.5 / 10.03.5 / 10.0
Output - Btuh22,00030,00030,000
0.5 / 1.50.5 / 1.50.5 / 1.5
Motor output - hp1/21/23/4
SPECIFICATIONS
Gas
Heating
Performance
MaximumInput - Btuh88,000110,000
Temperature rise range - °F50 - 8050 - 80
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
MinimumInput - Btuh31,00039,000
Temperature rise range - °F35 - 6535 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g.0.80.8
Connections
in.
Intake / Exhaust Pipe (PVC)2 / 22 / 2
Gas pipe size IPS1/21/2
Condensate Drain Trap (PVC pipe) - i.d.3/43/4
with furnished 90° street elbow3/4 slip x 3/4 Mipt3/4 slip x 3/4 Mipt
with eld supplied (PVC coupling) - o.d.3/4 slip x 3/4 MPT3/4 slip x 3/4 MPT
Indoor
Wheel nominal diameter x width - in.11 x 1111 x 11
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.SLP98DF090XV60CSLP98DF110XV60C
1
AFUE97.5%97.5%
Output - Btuh85,000107,000
3.5 / 10.03.5 / 10.0
Output - Btuh30,00038,000
0.5 / 1.50.5 / 1.5
Motor output - hp11
Page 2
OPTIONAL ACCESSORIES - ORDER SEPARATELY
NOTE - FURNACES CANNOT BE TWINNED!
“B” Width Models“C” Width Models
CABINET ACCESSORIES
Downow Combustible Flooring Base11M6011M61
CONDENSATE DRAIN KITS
Condensate Drain Heat Cable6 ft. 26K6826K68
24 ft.26K6926K69
50 ft.26K7026K70
Heat Cable TapeFiberglass - 1/2 in. x 66 ft.36G5336G53
Crawl Space Vent Drain Kit USA (Canada)51W18 (15Z70)51W18 (15Z70)
CONTROLS
iComfort Wi-Fi® Thermostat10F8110F81
1
Remote Outdoor Air Sensor (for dual fuel and Humiditrol®)X2658X2658
2
Discharge Air Temperature Sensor88K3888K38
®
ComfortSense
3
Remote Outdoor Temperature Sensor
(for dual fuel and Humiditrol)
DOWNFLOW FILTER KITS
Downow Air Filter and Rack Kit51W0751W08
NIGHT SERVICE KITS
Night Service Kit10U3710U37
Universal Service Kit - Switches 89W2089W20
TERMINATION KITS
Direct Vent Applications Only. See Installation Instructions for specic venting information.
Remote Outdoor Sensor may be used with an iComfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conven-
tional outdoor unit.
2
Optional for service diagnostics.
3
Remote Outdoor Temperature Sensor for ComfortSense® 7000 Thermostat must be connected directly to the thermostat, Do not connect it to the SureLight® control.
4
NOTE - The curved exhaust pipe furnished with the Left Side Vent Kit counts as one additional 2 in. diameter 90° elbow. When using 3 in. diameter pipe, the furnished
NOTE - Termination Kits 44W92, 44W93, 30G28, 51W12, 81J20 and Crawl Space Vent Drain Kit 15Z70 are certied to ULC S636 standard for use in Canada only.
7000 ThermostatY0349Y0349
X2658X2658
No. and Size of lter - in.(2) 16 x 20 x 1(2) 16 x 20 x 1
3 in.- - -60L46
Canada - 2 in.44W9244W92
3 in.- - -44W93
Flush-MountUS - 2, 2-1/2 or 3 in.51W1151W11
Canada - 2, 2-1/2 or 3 in.51W1251W12
Wall - Close
Couple
Wall - Close
Couple WTK
US - 2 in.22G44- - -
3 in.44J4044J40
Canada - 2 in.30G28- - -
3 in.81J2081J20
Roof2 in.15F7515F75
Wall Ring Kit2 in.15F7415F74
curved exhaust pipe and eld provided ttings to transition from 2 in. to 3 in. count as 20 feet of equivalent pipe on all units.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 250 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 450 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm (SLP98DF090V48C) and 450 cfm (SLP98DF090V60C).
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 450 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
Heating Input Range and Blower Volume - CFM
Blower Speed Selections
Medium
High
High
(Default)
LowMedium-
Low
Medium
High
High
(Default)
Page 6
CONTROL BOX
(includes variable capacity
integrated control,
transformer, circuit breaker
and door switch)
BLOWER
ACCESS
PANEL
SLP98DFV PARTS ARRANGEMENT
BLOWER ASSEMBLY
(Variable Speed Blower
Motor Is Hidden)
BAG ASSEMBLY
ACCESS PANEL
COMBUSTION AIR INDUCER
GAS VALVE
PRIMARY LIMIT
BURNER BOX ASSEMBLY
FIGURE 1
Page 7
I-UNIT COMPONENTS
SLP98DFV unit components are shown in figure 1. The gas
valve, combustion air inducer and burners can be accessed
by removing the access panel. Electrical components are in
the control box (figure 2) found in the blower compartment.
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions to
neutralize electrostatic charge by touch
ing your hand and tools to metal prior to
handling the control.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the trans
former (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit opera
tion will shut down. The breaker can be manually reset by
pressing the button on the face. See figure 3.
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
A-Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all mod
els are rated 40VA with a 120V primary and a 24V secon
dary.
2. Interlock Switch (S51)
An interlock switch rated 14A at 125VAC is wired in series
with line voltage. When the inner blower access panel is re
moved the unit will shut down.
CONTROL BOX SLP98DFV
SURELIGHT®
DOOR
INTERLOCK
SWITCH
INTEGRATED
CONTROL
CIRCUIT
BREAKER
FIGURE 2
TRANSFORMER
WARNING
Shock hazard.
Disconnect power before servicing.
Integrated control is not field repairable. If control
is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will re
sult if repair is attempted.
4. Integrated Control (A92)
SLP98DFV units are equipped with the Lennox SureLight
variable-capacity integrated control. This control can be
used with the icomfort Wi-Fi
municating comfort system. The control can also operate
with a conventional single or two-stage thermostat. The
system consists of an ignition / blower control (figures 4 and
5) with control pin designations in tables 1, 2 and ignitor. The
control provides gas ignition, safety checks and indoor
blower control with variable capacity rate gas heating. The
furnace combustion air inducer, gas valve and indoor blow
er are controlled in response to various system inputs such
as thermostat signal, pressure and limit switch signal and
flame signal. The control features a seven-segment LED
display, indicating furnace status (including indoor blower)
and error codes. The LED flashes in single digits. For exam
ple using table 14 under LIMIT CODE, an “E” followed by
“2” followed by “5” followed by “0”, the limit switch circuit is
open. The control also has two 120 volt accessory terminals
(used for a humidifier and electronic air cleaner) rated at (1)
one amp each.
®
thermostat as part of a com
®
Page 8
Electronic Ignition
At the beginning of the heat cycle the SureLight
®
integrated
control monitors the low fire combustion air inducer pres
sure switch. The control will not begin the heating cycle if the
low fire pressure switch is closed (by-passed). Likewise the
control will not begin the high fire heating cycle if the high fire
pressure switch is closed, and will remain in low fire heat.
However, if the high fire pressure switch closes during the
low fire heat pre-purge, the control will allow high fire heat.
Once the low fire pressure switch is determined to be open,
the combustion air inducer is energized on ignition speed.
When the differential in the pressure switch is great enough,
the pressure switch closes and a 15-second pre-purge be
gins. If the switch is not proven within 2-1/2 minutes, the in
ducer is de-energized and the control will initiate vent cal
ibration. If the vent calibration is unsuccessful the control
goes into a 5 minute delay. The control will attempt vent cal
ibration 3 more times before going into a 1 hour soft lockout.
After the 15 second pre-purge period the SureLight ignitor
warms up for 20 seconds. The gas valve then opens for a
4-second trial for ignition. The ignitor stays energized dur
ing this trial until flame is sensed. If ignition is not proven
during the 4-second trial for ignition, the control will try four
more times with an inter purge and warm-up time between
trials of 35 seconds. After a total of five trials for ignition (in
cluding the initial trial), the control goes into WatchguardFlame Failure mode. After a 60-minute reset period, the
control will begin the ignition sequence again.
Thermostat Selection Modes
See table 3 for DIP switch settings
The control can be made to operate in three modes: vari
able capacity, three-stage timed or two-stage. The variable
capacity and two-stage modes are only operational with a
two-stage thermostat. The thermostat selection is made us
ing DIP switches one and / or two (figure 4) and must be
positioned for the particular application.
Three- Stage Timed Operation
Using a single-stage thermostat the system will operate in a
three stage timed mode. Upon a call for heat and a success
ful ignition, the combustion air inducer will operate at 35%
and the indoor blower will adjust to the appropriate cfm. Af
ter a field selectable 7 or 12 minute delay period, the induc
er RPM will increase and the unit will operate at 70%. The
indoor blower will adjust to the appropriate cfm. After a fac
tory set non-adjustable 10 minute delay expires the furnace
will increase rate to 100%. The indoor blower will adjust to
the appropriate cfm.
Two-Stage Operation
The system will also operate in conventional two-stage
mode. While in two-stage mode, the furnace will fire on low
fire (70% rate). The combustion air inducer will operate at
70% and the indoor blower will adjust to the appropriate
cfm. The unit will switch to high fire on a W2 call from the
thermostat. After a 30 second recognition period (during
which the integrated control will receive a continuous W2
call) expires the furnace will increase to 100% rate. The in
ducer will increase to 100% speed and the indoor blower will
adjust to appropriate cfm. If there is a simultaneous call for
first and second stage heat, the unit will fire on first stage
heat and switch to second stage heat after 30 seconds of
operation.
TABLE 1
®
Control 6 Pin Terminal Designation
SureLight
PIN #Function
1Data Input From Motor
2Common
3Not Used
4Data Output To Motor
55 Volt Bias Supply
6Not Used
Variable Capacity
Using a two-stage thermostat the system will operate in a
variable capacity sequence mode. In this mode, the control
will vary the firing rate anywhere between 35% and 100% of
full capacity. The indoor blower will be automatically ad
justed accordingly to provide the appropriate airflow at any
rate. On the initial call for low fire, the furnace will operate at
35% and will remain there until the heat call is satisfied or a
call for high fire is initiated. If there is a call for high fire the
rate will increase by 10% if the current rate is above 60%.
However if the current rate is below 60% the rate will in
crease to 70%. After this initial rate increase to 70% capac
ity, the furnace will increase rate by 10% every 5 minutes
while a high fire heat call is present. If the high fire heat call is
satisfied but the low fire heat call is still present, the furnace
will remain at the current firing rate until the demand is satis
fied or another call for high fire is initiated.
Page 9
TABLE 2
SureLight Control 12 Pin Terminal Designation
PIN #Function
1Not used
2High Fire Pressure Switch
3Rollout In
4Ground
524V Hot
6Primary Limit In
7Gas Valve
8Gas Valve Common
924V Neutral
10Ground
11Primary Limit Switch Out
12Low Fire Pressure Switch
COMBUSTION
AIR INDUCER
CONNECTOR
FLAME
SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
NEUTRAL
TERMINALS
IGNITOR
CONNECTOR
LINE VOLTAGE
+
HUM
EAC
TERMINALS
ON-BOARD
LINKS
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
FACTORY TEST
HEADER PINS.
FACTORY USE ONLY.
TB83 OUTDOOR
TB84 INDOOR
TERMINALS
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
7-SEGMENT
DIAGNOSTIC LED
INDOOR
BLOWER
CONNECTOR
W915 Y1 TO Y2
W951 R TO O
W915
W951
W914
W914 R TO DS
L - use only with
communicating T'stat and
non-communicating outdoor
unit.
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
REVERSING VALVE
1/4” QUICK CONNECT TERMINALS
HUM = 120 VAC OUTPUT TO HUMIDIFIER
XMFR = 120 VAC OUTPUT TO TRANSFORMER
Wi-Fi
speed selections and DIP switch settings are made by
the communicating thermostat.
Heating Operation DIP Switch Settings -- Figure 4
Switch 1 -- Thermostat Selection -- This unit may be used
with either a single-stage or two-stage thermostat. The ther
mostat selection is made using a DIP switch which must be
properly positioned for the particular application. The DIP
switch is factory-positioned for use with a two-stage thermo
stat. If a single-stage thermostat is to be used, the DIP
switch must be repositioned. See table 3.
NOTE - All DIP switches are factory shipped in the
“OFF” position.
Switch 2 -- Operating Mode with Two-Stage Thermostat
-- If a two-stage thermostat is used, the furnace can operate
in either variable-capacity or conventional two-stage mode.
When variable-capacity mode is selected, the firing rate of
the unit is varied to maximize comfort. Conventional twostage mode is the factory default setting. See table 3.
Switch 3 -- Second-Stage Heat On Delay -- If a singlestage thermostat is used, the integrated control can be used
to energize second-stage heat after either 7 minutes or 12
minutes of first-stage heat operation. See table 3.
Switches 4 and 5 -- Blower-Off Delay -- The blower-on
delay of 45 seconds is not adjustable. The blower-off delay
(time that the blower operates after the heating demand has
been satisfied) can be adjusted by moving switches 4 and 5
on the integrated control. The unit is shipped from the facto
ry with a blower-off delay of 90 seconds. The blower off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the blower off delay to achieve a supply
air temperature between 90° and 110°F at the exact mo
ment that the blower is de-energized. Longer off delay set
tings provide lower supply air temperatures; shorter set
tings provide higher supply air temperatures. Table 4 pro
vides the blower off timings that will result from different
switch settings.
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
60OffOn
90 (factory)OffOff
120OnOff
180OnOn
Indoor Blower Operation DIP Switch Settings
Switches 6 and 7 -- Continuous Indoor Fan Operation -Blower Speed - Switches 6 and 7 are used to select blower
motor speeds during continuous indoor blower operation.
The unit is shipped from the factory with DIP switches posi
tioned for medium low (2) speed during continuous indoor
blower operation. The table below provides the continuous
blower speeds that will result from various switch settings.
Refer to blower tables at the front of this manual for corre
sponding cfm values.
Continuous Indoor Fan
Speed
1 - Low (28%)OffOn
2 - Medium Low
(38%)
(Factory)
3 - Medium High
(70%)
4 - High (100%)OnOn
Switches 8 and 9 -- Cooling Mode Blower Speed --
Switches 8 and 9 are used to select cooling blower motor
speed. The unit is shipped from the factory with the DIP
switches positioned for high speed (4) indoor blower motor
operation during the cooling mode. The table below pro
vides the cooling mode blower speeds that will result from
different switch settings. Refer to blower tables at the front
of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
Speed
1 - LowOnOn
2 - Medium LowOffOn
3 - Medium HighOnOff
4 - High (Factory)OffOff
TABLE 4
Switch 4Switch 5
TABLE 5
Switch 6Switch 7
OffOff
OnOff
TABLE 6
Switch 8Switch 9
Page 12
Switches 10 and 11 -- Cooling Mode Blower Speed Ad
justment -- Switches 10 and 11 are used to select blower
speed adjustment settings. The unit is shipped from the fac
tory with the DIP switches positioned for NORMAL (no) ad
justment. The DIP switches may be positioned to adjust the
blower speed by +10% or -10% to better suit the application.
The table below provides blower speed adjustments that
will result from different switch settings. Refer to blower
tables at the front of this manual for corresponding cfm val
ues. With switches 10 and 11 set to ON, motor will bypass
ramping profiles and all delays and immediately upon a call
for cool, run at COOLING speed selected. LED will continue
to operate as normal. This mode is used to check motor op
eration.
TABLE 7
Blower Speed Adjustment
Adjustment
Switch 10Switch 11
+10% (approx.)OnOff
NORMAL (Factory)OffOff
-10% (approx.)OffOn
MOTOR TESTOnOn
Ramping Option A (Factory Selection)
D Motor runs at 50% for 30 seconds.
D Motor then runs at 82% for approximately 7-1/2 min
utes.
D If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes, mo
tor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Switches 12 and 13 -- Cooling Mode Blower Speed
Ramping -- Switches 12 and 13 are used to select cooling
mode blower speed ramping options. Blower speed ramp
ing may be used to enhance dehumidification performance.
The switches are factory set at option A which has the great
est effect on blower motor performance. Table 8 provides
the cooling mode blower speed ramping options that will re
sult from different switch settings. The cooling mode blower
speed ramping options are detailed below.
TABLE 8
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 12Switch 13
A (Factory)OffOff
BOnOff
COffOn
DOnOn
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec
-- Switches 14 through 19 are used to select heating mode
blower motor speeds. These switches are factory set at the
OFF position which provides 100 % of normal speed during
HIGH HEAT demand, 70% of normal speed during MIDRANGE HEAT demand and 35% of normal speed during
LOW HEAT demand. Switches 14, 15 and 16 are used to
adjust the LOW FIRE blower motor speed. Switches 17, 18
and 19 are used to adjust the HIGH FIRE blower motor
speed. Figure 6 and tables 9 and 10 provides the heating
mode blower speeds that will result from different switch
settings. Figure 6 indicates the effect the DIP switch set
tings (tables 20 &21 above) have upon the heating airflow at
various furnace firing rates.
Refer to blower tables at the front of this manual for corre
sponding cfm values.
Thermostat
Demand
High Heat
(R to
W1 & W2)
High Heat Blower Speeds
TABLE 10
Blower
Speed
Adjust
ments
DIP SWITCH SETTINGS
171819
+15%OnOffOn
+7.5%OnOffOff
Normal
OffOffOff
-7.5%OnOnOff
-15%OnOnOn
Increasing
Airflow
+15%
+7.5%
Nominal
-7.5%
-15%
Airflow Determination
S Identify blower speed adjustment points at low and high fire
S Airflow will lie on straight line between these two points and will fall within
the shaded area as shown
EXAMPLE -7.5% at low fire +7.5% at high fire
Low Fire
Dip Switches
14, 15, 16
35%
50%
60%
70%
RATE (%)
FIGURE 6
80%
Dip Switches
90%
High Fire
17, 18, 19
+15%
+7.5%
Nominal
-7.5%
-15%
100%
Page 14
On-Board Link W914 DS to R (Figure 4)
On-board link W914, is a clippable connection between ter
minals DS and R on the integrated control. W914 must be
cut when the furnace is installed with either the Harmony
IIIt zone control or a thermostat which features humidity
control. If the link is left intact the PWM signal from the Har
mony III control will be blocked and also lead to control dam
age. Refer to table 15 for operation sequence in applica
tions including SLP98DFV, a thermostat which features hu
midity control and a single-speed outdoor unit. Table 16
gives the operation sequence in applications with a twospeed outdoor unit.
On-Board Link W951 R to O (Figure 4)
On-board link W951 is a clippable connection between ter
minals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal “O” will remain ener
gized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 Y1 to Y2 (Figure 4)
On-board link W915 is a clippable connection between ter
minals Y1 and Y2 on the integrated control. W915 must be
cut if two-stage cooling will be used. If the link is not cut the
outdoor unit will operate in second-stage cooling only.
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating sta
tus, target airflow, error codes and other information. Table
14 lists diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the sevensegment diagnostic LED. This button is used to enable the
Error Code Recall mode and the Field Test mode. Press the
button and hold it to cycle through a menu of options. Every
five seconds a new menu item will be displayed. When the
button is released, the displayed item will be selected. Once
all items in the menu have been displayed, the menu re
sumes from the beginning until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error
codes. Select “c” from the Error Code Recall menu to clear
all error codes. Button must be pressed a second time while
“c” is flashing to confirm command to delete codes. Press
the button until a solid “≡” is displayed to exit the Error Code
Recall mode.
Field Test Mode
Use the diagnostic push button to scroll through the menu
as described above. Release the button when the LED
flashes “-” to select the Field Test mode.
While in the Field Test mode the technician can:
D Initiate furnace ignition and move to and hold low-fire
rate by applying a R to W1 jumper.
D Initiate furnace ignition sequence and move to and hold
high-fire rate by applying a jumper from R to W1 and
W2.
D Initiate furnace ignition sequence and move to and hold
mid-fire rate by applying a jumper to R and W2.
D Apply then remove the jumper from R to W1 and W2 to
change the firing rate from low fire to mid fire and high
fire.
D A vent calibration sequence can be initiated even if a
thermostat signal is not present. Press and hold the
push button until a solid “C” is displayed. Release the
button and calibration will begin. The furnace will per
form the high-fire and low-fire pressure switch calibra
tions and display “CAL”. After calibration, the LED will
return to the flashing “-” display.
During Field Test mode operation, all safety switches are
still in the circuit (they are not by-passed) and indoor blower
performance and timings will match DIP switch selections.
Current furnace firing rate, indoor blower CFM and flame
signal will be displayed. To exit the Field Test mode, press
and hold the button. The menu will resume from the begin
ning. A
The integrated control will automatically exit the Field Test
mode after 45 minutes of operation.
Soft Disable
Soft disabling is when thermostat finds a device on the BUS
that it does not recognize and the thermostat sends a the
device a message to be in soft disabling mode until properly
configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
ls
o, cycle the main power to exit the Field Test mode.
1- Confirm proper wiring between all devices (thermo
stat, damper control module, indoor and outdoor).
2- Cycle power to the control that is displaying the soft
disable code.
3- Put the room thermostat through set up.
4- Go to setup / system devices / thermostat / edit /
then push reset.
5- Go to setup / system devices / thermostat / edit /
then push resetAll.
Page 15
TABLE 11
Idle Menu Options
These options are displayed on the menu when the button is pressed during normal operation
DISPLAY
No change (idle)remain in idle mode
Solid “E”enter diagnostic mode
Solid “-”enter field test mode
NOTE - No change implies the display will continue to show whatever is currently being displayed for normal operation
Field Test Menu Options
These options are displayed when the button is used in Field Test Mode
DISPLAY
No change (blinking “-”)remain in field test mode
Solid “-”exit field test mode
Solid “c”start pressure switch calibration
Field Test Menu Options
These options are displayed when the button is used in diagnostic recall mode
ACTION (when button released)
TABLE 12
ACTION (when button released)
TABLE 13
DISPLAY
No change (displaying error history) remain in diagnostic recall mode
Once the button is released to clear the error history a blinking “c” will be shown on the display for up to 10 seconds. During this
time the user must press and release the button one additional time to confirm the action of deleting the error history. Once the
error history is deleted it cannot be recovered.
ACTION (when button released)
Page 16
Configuring Unit Size Codes
Power-Up - Number displayed represents by integrated control unit size code (furnace model
and capacity). If three horizontal bars are displayed followed by continuous E203, furnace
control does not recognize unit size code. Configure per the following:
To enter Field TestMode: push and hold
button next to
7-segment LED display
until solid dash symbol
appears. Release
button.
If alarm is present, furnace
control will display error
code. If alarm is not
present solid dash starts
blinking on 7-segment
LED display.
Yes
−
−
−
Furnace control in IDLE mode
No heating, cooling or indoor fan
operation)
No
_
Turn room thermostat to OFF
UNIT SIZE
CODE
FURNACE MODEL
H
_
SLP98DFV070-36B
J
SLP98DFV-090-36C
L
SLP98DFV-090-48C
n
SLP98DFV-090-60C
o
SLP98DFV-110-60C
Push and hold button until the solid P
symbol is displayed on the 7-segment
LED. Release button. This mode allows
the user to select a unit size code number
that matches the furnace model size and
capacity.
IMPORTANT: Field replacement controls may
need to be manually configured to validate
furnace unit size code.
Solid P starts
blinking on
7-Segment LED
Push and hold button. Integrated control will
display unit size code number for each
furnace model for five seconds.
P
P
When the correct unit size code is displayed, release
button. Selected code will flash for 10-second period.
During that period, hold push button until code stops
blinking (disappear for 2 seconds). Integrated control
will store code in memory and will automatically exit
Field Test Mode and reset. (If second period expires
or push button is held less than five seconds, control
will automatically exit Field Test Mode and go into
IDLE mode without storing unit size code. If this
happens, programming function must be repeated).
−
. If
−
−
Verify that the selected unit size code is correct
and stored in non-volatile memory by cycling
the 24 volt power to the furnace control. (At 24
volt power-up of the furnace control, the
7-segment LED will display a unit size code
three horizontal bars display, board does not
recognize unit size code
function must be repeated)
. Programming
FINISHED
Page 17
TABLE 14
LED 7 Segment Status / Error Code
Press the diagnostic push button and hold it to cycle through a menu of options. Every five seconds a new menu item will be displayed.
Release the button when the desired mode is displayed.
When a solid ”P” is displayed, the furnace capacity/ size is programmed.
When the solid “E” is displayed, the control enters the Error Code Recall mode. Error Code Recall mode menu options: No change (display
ing error history) remains in Error Code Recall mode; solid “b” exits Error Code Recall mode; and solid “c” clears the error history. Must press
button while flashing “c” is displayed to clear error codes.
When the solid “-” is displayed, the control enters the Field Test mode. Field Test mode menu options: Solid “C” starts pressure switch
calibration; blinking “-” exits Field Test mode.
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
.
Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF).
A
Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5 second
OFF) / cfm setting for current mode displayed.
C
Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm
setting displayed / Pause / Repeat codes).
d
Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting displayed /
Pause / Repeat Codes).
h
Variable Capacity Heat (1 second ON, 0.5 second OFF) / % of input rate displayed
/ Pause/ cfm setting / Pause/ Repeat codes.
H
Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm set
ting displayed / Pause / Repeat codes.
df
Defrost mode.
U
Discharge air temperature
Soft disable - Soft disabling is when thermostat finds a device on the BUS that it
does not recognize and the thermostat sends a the device a message to be in soft
disabling mode until properly configured. Two horizontal bars will display.
E 105
Device communication problem - No other devices on BUS (Communication
system).
E 110
Low line voltage.Line Voltage low (Voltage lower than nameplate rating)
E 113
High line voltage.Line Voltage High (Voltage higher than nameplate rating)
E 114
Line voltage frequency out-of-range.No 60 hertz power (Check voltage and frequency).
E 115
Low 24V - Control will restart if the error recovers.24 voltage low (Range is 18 to 30 volts) Check voltage.
E 120
Unresponsive device.Usually caused by delay in outdoor unit responding to
E 124
Active communicating thermostat signal missing for more than 3 minutes.Equipment lost communication with the thermostat. Check
E 125
Control failed self-check, internal error, failed hardware. Will restart if error
recovers. Integrated furnace control not communicating. Covers hardware errors
(flame sense circuit faults, pin shorts, etc.).
E 126
Failed internal control communication between microcontrollers.Hardware problem on the control board. Cycle power on
E 131
Corrupted control parameters (Verify configuration of system).Reconfigure the system. Replace board if service (heating
E 180
Outdoor air sensor failure - NO error if disconnected. Only shown if shorted or
out-of-range.
E 200
Hard lockout - Rollout circuit open or previously open.Correct unit cause of rollout trip or replace flame rollout
E 201
Indoor blower communication failure - Unable to communicate with blower motor.Indoor blower communication failure including power
Steps to follow if the damper control module is displaying
the soft disable code.
1- Confirm proper wiring between all devices
(thermostat, damper control module, indoor and
outdoor).
2- Cycle power to the control that is displaying
the soft disable code.
3- Put the room thermostat through set up.
4- Go to setup / system devices / thermostat /edit / then push reset.
5- Go to setup / system devices / thermostat /edit / then push resetAll.
Equipment is unable to communicate. Check for mis wire
and loose connections and check for a high voltage
source of noise close to the system. (welder etc.).
Check voltage.
Check voltage.
indoor unit poling recycle power, check wiring.
connections and cycle power on the thermostat.
Hardware problem on the control board. Cycle power on
control. Replace if problem prevents service and is
persistent.
control. Replace if problem prevents service and is
persistent.
/cooling) is unavailable.
Compare outdoor sensor resistance to temperature
resistance charts in installation instructions. Replace if
necessary.
switch and test furnace operation.
outage.
Page 18
Integrated Control Diagnostic Codes (continued)
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 202
E 203
E 204
E 205
E 207
E 223
E 224
E 225
E 226
E 227
E 228
E 240
E 241
E 250
E 252
E 270
E 271
E 272
E 273
E 274
E 275
E 276
E 290
E 291
Indoor blower motor mis-match - Indoor motor horsepower does not match unit
capacity.
Appliance capacity / size is NOT programmed. Invalid unit codes refer to
configuration flow chart in installation instructions.
Gas valve mis-wired.Check operation of gas valve.
Gas valve control relay contact shorted.Check operation of gas valve.
Hot surface ignitor sensed open - Refer to troubleshooting in installation
instruction.
Low pressure switch failed open - Refer to troubleshooting in installation
instruction.
Low pressure switch failed closed - Refer to troubleshooting in installation
instruction.
High pressure switch failed open - Refer to troubleshooting in installation
instruction.
High pressure switch failed closed - Refer to troubleshooting in installation
instruction.
Low pressure switch open during trial for ignition or run mode. Refer to trouble
shooting in installation instruction.
Unable to perform successful pressure switch calibration.Retry after 300 seconds. Error counter cleared when exit
Low flame current - Run mode - Refer to troubleshooting in
installation instruction.
Flame sensed out of sequence - Flame still present.Shut off gas, check for gas valve leak.
Limit switch circuit open - Refer to troubleshooting in installation instruction.Check why limit is tripping, overfired, low air flow.
Discharge air temperature too high (gas heat only).Check temperature rise, air flow and input rate.
Soft lockout - Exceeded maximum number of retries. No flame current sensed. Check for gas flow, ignitor lighting burner, flame sensor
Soft lockout - Exceeded maximum number of retries. Last retry failed due to
the pressure switch opening.
Soft lockout - Exceeded maximum number of recycles. Last recycle due to the
pressure switch opening.
Soft lockout - Exceeded maximum number of recycles. Last recycle due to
flame failure.
Soft lockout - Exceeded maximum number of recycles. Last recycle failed due
to the limit circuit opening or limit remained open longer than 3 minutes.
Soft lockout - Flame sensed out of sequence from code 241 fault. Flame signal
is gone.
Soft lockout - Exceeded maximum number of calibration retries.See E 228.
Ignitor circuit fault - Failed ignitor or triggering circuitry.See E 207.
Restricted air flow - Cubic feet per minute is lower than what is needed for
minimum firing rate.
Incorrect furnace size code selected. Check unit size
codes on configuration guide or in installation instructions.
No furnace size code selected. Check unit size codes on
configuration guide or in installation instructions.
Measure resistance of Hot Surface Ignitor, replace if open
or not within specification.
Check inches of water column pressure during operation
of low pressure switch on heat call, measure inches of
water column of operating pressure, inspect vent and
combustion air inducer for correct operation and restric
tion.
Check low pressure switch for closed contacts, measure
inches of water column of operating pressure, inspect vent
and combustion air inducer for correct operation and re
striction.
Check inches of water column pressure of high pressure
switch on heat call, measure inches of water column of
operating pressure, inspect vent and combustion air
inducer for correct operation and restriction.
Check high pressure switch for closed contacts, measure
inches of water column of operating pressure, inspect vent
and combustion air inducer for correct operation and
restriction.
Check inches of water column pressure during operation
of low pressure switch on heat call, measure inches of
water column of operating pressure, inspect vent and
combustion air inducer for correct operation and restric
tion.
ing lockout, unable to perform pressure switch calibration.
Check vent system and pressure switch wiring
connections.
Check micro amperes of flame sensor, clean or replace
sensor. Measure voltage of neutral to ground for good unit
ground.
current.
See E 223.
See E 223 and E 225.
See E 240.
See E 250.
See E 241.
Check for dirty filter, unit air flow restriction, blower
performance.
Page 19
Integrated Control Diagnostic Codes (continued)
CodeDiagnostic Codes/Status of EquipmentAction Required to Clear and Recover
E 292
E 294
E 295
E 310
E 311
E 312
E 313
E 331
E 347
E 348
E 349
E 401
E 402
E 403
E 404
E 405
E 406
E 407
E 408
E 409
Indoor blower motor unable to start - Seized bearings, stuck wheel, etc.Indoor blower motor unable to start (seized
Combustion air inducer motor amp draw is too high.Check combustion blower bearings, wiring , amperes,
bearing, stuck wheel, etc), replace motor or wheel if
assembly does not operate or meet performance.
replace if it does not operate or meet performance.
Indoor blower motor temperature is too high.Indoor blower motor over temperature (motor
tripped on internal protector), Check motor bear
ings, amperes. Replace if necessary.
Discharge error sensor failure - No error if disconnected. Only shown if
shorted or out-of-range.
Heat rate reduced to match indoor blower air flow. Replace filter or repair
duct restriction.
Discharge air temperature(DATS) out of range,
code is activated during ”Field test mode”.
Furnace blower in cutback mode due to restricted
airflow. Check filter and ductwork. To clear replace
filter if needed or repair/ add ductwork.
Restricted air flow in cooling or continuous fan mode is lower than cfm
setting.
Restricted airflow - Indoor blower is running at a
reduced cubic feet per minute (Cutback Mode) The variable speed motor has pre-set speed and
torque limiters to protect the motor from damage
caused by operating out of its designed parameters
(0 to 0.8 inches water column total external static
pressure). Check filter and ductwork. To clear re
place filter if needed or repair/ add ductwork.
Indoor or outdoor unit capacity mismatch.Incorrect Indoor /outdoor capacity code selected.
Check for proper configuration in installation instruc
tions. Alarm is just a warning. The system operation
is not impacted at all and alarm would clear when
Commissioning is exited.
Global network connection - Communication link problem.For Future Use.
No 24 Volt output on Y1 to C with non-communicating outdoor unit.Y1 relay / Stage 1 failed (Pilot relay contacts did not
close or the relay coil did not energize).
No 24 Volt output on Y2 to C with non-communicating outdoor unit.Y2 relay / Stage 2 failed (Pilot relay contacts did not
close or the relay coil did not energize).
No 24 Volts between R & O with non-communicating outdoor unit (Dual
fuel module required for heat pump application).
Configuration link R to O needs to be cut on control
board.
LSOM - Compressor ran more than 18 hours in air conditioning mode. Compressor protector is open. Check for high head
pressure, check compressor supply voltage. Out
door unit power disconnect is open , compressor
circuit breaker or fuse(s) is open, broken wire or
connector is not making contact. Low or high pres
sure switch open if present in the system. Compres
sor contactor has failed to close.
LSOM - Outdoor unit system pressure trip.Compressor ran over 18 hours in air conditioning
mode.
LSOM - Compressor short-cycling (Running less than 4 minutes).Outdoor unit pressure trip. Check dirty coil, fan mo
tor, refrigerant charge.
LSOM - Compressor rotor locked.Compressor short cycling (Running less than 4 min
utes).
LSOM - Compressor open circuit.Check capacitor, wiring, hard start kit , replace com
pressor.
LSOM - Compressor open start circuit.Check compressor for hot (cool down) , check pres
LSOM - Compressor open run circuit.
sures, fan motor etc. Replace compressor if unable
to get circuit to close and compressor to operate.
LSOM - Compressor contactor is welded.
LSOM - Compressor low voltage.Replace contactor.
Page 20
TABLE 15
OPERATING SEQUENCE
SLP98DFV and Single-Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMANDSYSTEM RESPONSE
DemandRelative Humidity
System
Condition
Step
1st
stage
OGStatusD*
NO CALL FOR DEHUMIDIFICATION
Normal Operation1OnOnOnAcceptable
24
VAC
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1OnOnOnAcceptable
Dehumidification
Call
2OnOnOnDemand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOnOnAcceptable
Dehumidification
call
Dehumidification
call ONLY
2OnOnOnDemand
1OnOnOnDemand
24
VAC
0
VAC
0
VAC
On-board links at indoor unit with a single-stage outdoor unit:
With Condensing unit - Cut W914 (R to DS) on SureLight
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
control.
*ComfortSense
®
7000 thermostat ony
Compressor
High100%
High100%
High70%
High100%
High70%
High70%
®
control;
Blower
CFM
(COOL)
®
Comments
Compressor and indoor
blower follow thermostat
demand
Thermostat energizes Y1
and de-energizes D on a
call for de-humidification
Dehumidification mode
begins when humidity is
greater than set point
Thermostat will keep out
door unit energized after
cooling temperature set
point has been reached in
order to maintain room
humidity setpoint.
Page 21
TABLE 16
OPERATING SEQUENCE
SLP98DFV and Two-Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMANDSYSTEM RESPONSE
DemandRelative Humidity
System
Condition
Step
1st
stage
2nd
stage
G
O
StatusD*
NO CALL FOR DEHUMIDIFICATION
Normal Operation -
Y1
Normal Operation -
Y2
1OnOn
2On
On
On
On
On
Acceptable
Acceptable
24
VAC
24
VAC
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1OnOn
Dehumidification
Call
2On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOn
Dehumidification
call
Dehumidification
call ONLY
2On
1On
On
On
On
On
On
On
On
Acceptable
Demand
Demand
24
VAC
0
VAC
0
VAC
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1On
Dehumidification
Call
2On
On
On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOn
Dehumidification
call
2On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
Compressor
Low70%
High100%
Low70%
High70%
Low70%
High70%
High70%
High100%
High70%
Low70%
High70%
Blower
CFM
(COOL)
Comments
Compressor and indoor
blower follow thermostat
demand
Thermostat energizes
2nd stage and de-ener
gizes D on a call for dehumidification
Dehumidification mode
begins when humidity is
greater than set point
Thermostat will keep out
door unit energized after
cooling temperature set
point has been reached
in order to maintain room
humidity setpoint.*
Thermostat energizes
2nd stage and de-ener
gizes D on a call for dehumidification
Dehumidification mode
begins when humidity is
greater than set point
Dehumidification
call ONLY
1On
On
On
On
Demand
On-board links at indoor unit with a two-stage outdoor unit:
Cut factory link from Y1 to Y2 or cut W915 (Y1 to Y2) on SureLight
grated control.
With Condensing unit - Cut W914 (R to DS) on SureLight
0
VAC
High70%
®
®
integrated control;
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
integrated control.
*ComfortSense
®
7000 thermostat only
Page 22
inte
®
Thermostat will keep out
door unit energized after
cooling temperature set
point has been reached
in order to maintain room
humidity setpoint.
Loading...
+ 49 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.