Lennox SLP98DF090XV60C, SLP98DF110XV60C, SLP98DF090XV36C, SLP98DF090XV48C, SLP98DF070XV36B Handbook

Page 1
Corp. 1030-L7
Service Literature
Revised 05-2016
SLP98DFV SERIES UNITS
SLP98DFV series units are high-efficiency downflow gas furnaces equipped with variable capacity gas valve, vari able speed combustion air inducer and variable speed in door blower motor. All models are designed for direct vent (dual pipe) venting system only. SLP98DFV units are avail able in heating capacities from 66,000 to 132,000 Btuh (19.3 to 38.6 kW) and cooling applications from 2 to 5 tons (7.0 kW to 17.5 kW). Refer to Engineering Handbook for proper sizing.
Units are factory-equipped for use with natural gas. Kits are
available for conversion to LPG operation. SLP98DFV mod
els include a SureLight
that can be used with Lennox icomfort Wi-Fi
part of a communicating comfort system. All SLP98DFV
units meet the California Nitrogen Oxides (NO
and California Seasonal Efficiency requirements.
®
variable capacity integrated control
®
thermostat as
) Standards
x
SLP98DFV
All specifications in this manual are subject to change. Pro cedures outlined in this manual are presented as recom mendations only and do not supersede or replace local or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (except where noted) are recommendations only and do not consti tute code.
TABLE OF CONTENTS
Specifications Page 2.............................
Optional Accessories Page 3......................
Blower Data Page 4..............................
I Unit Components Page 8........................
II icomfort Wi-Fi
III Placement and Installation Page 35..............
IV Start Up Page 53..............................
V Heating System Service Checks Page 54..........
VI Typical Operating Characteristics Page 57........
VII Maintenance Page 57..........................
VIII Wiring and Sequence of Operation Page 60.....
IX Field Wiring Page 68...........................
®
Thermostat Page 33..............
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person al injury or loss of life. Installation and service must be performed by a licensed professional HVAC in staller (or equivalent), service agency or the gas sup plier.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Page 1
© 2016 Lennox Industries Inc.
Page 2

SPECIFICATIONS

Gas Heating Performance
Maximum Input - Btuh 66,000 88,000 88,000
Temperature rise range - °F 50 - 80 60 - 90 50 - 80
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
Minimum Input - Btuh 23,000 31,000 31,000
Temperature rise range - °F 35 - 65 35 - 65 35 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g. 0.8 0.8 0.8
Connections in.
Intake / Exhaust Pipe (PVC) 2 / 2 2 / 2 2 / 2
Gas pipe size IPS 1/2 1/2 1/2
Condensate Drain Trap (PVC pipe) - i.d. 3/4 3/4 3/4
with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt
with eld supplied (PVC coupling) - o.d. 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT
Indoor
Wheel nominal diameter x width - in. 10 x 9 10 x 9 11 x 11
Blower
Tons of add-on cooling 2 - 3 2 - 3 3 - 4
Air Volume Range - cfm 410 - 1365 488 - 1385 545 - 1745
Electrical Data Voltage (Maximum Amps) 120 volts - 60 hertz - 1 phase
Blower motor full load amps 7.7 7.7 10.1
Maximum overcurrent protection 15 15 15
Shipping Data lbs. - 1 package 140 155 165
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SLP98DF070XV36B SLP98DF090XV36C SLP98DF090XV48C
1
AFUE 97.5% 97.5% 97.5%
Output - Btuh 64,000 84,000 85,000
3.5 / 10.0 3.5 / 10.0 3.5 / 10.0
Output - Btuh 22,000 30,000 30,000
0.5 / 1.5 0.5 / 1.5 0.5 / 1.5
Motor output - hp 1/2 1/2 3/4
SPECIFICATIONS
Gas Heating Performance
Maximum Input - Btuh 88,000 110,000
Temperature rise range - °F 50 - 80 50 - 80
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
Minimum Input - Btuh 31,000 39,000
Temperature rise range - °F 35 - 65 35 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g. 0.8 0.8
Connections in.
Intake / Exhaust Pipe (PVC) 2 / 2 2 / 2
Gas pipe size IPS 1/2 1/2
Condensate Drain Trap (PVC pipe) - i.d. 3/4 3/4
with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt
with eld supplied (PVC coupling) - o.d. 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT
Indoor
Wheel nominal diameter x width - in. 11 x 11 11 x 11
Blower
Tons of add-on cooling 3.5 - 5 3.5 - 5
Air Volume Range - cfm 467 - 2130 575 - 2180
Electrical Data Voltage (Maximum Amps) 120 volts - 60 hertz - 1 phase
Blower motor full load amps 12.8 12.8
Maximum overcurrent protection 20 20
Shipping Data lbs. - 1 package 165 174
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. SLP98DF090XV60C SLP98DF110XV60C
1
AFUE 97.5% 97.5%
Output - Btuh 85,000 107,000
3.5 / 10.0 3.5 / 10.0
Output - Btuh 30,000 38,000
0.5 / 1.5 0.5 / 1.5
Motor output - hp 1 1
Page 2
Page 3
OPTIONAL ACCESSORIES - ORDER SEPARATELY
NOTE - FURNACES CANNOT BE TWINNED!
“B” Width Models “C” Width Models
CABINET ACCESSORIES
Downow Combustible Flooring Base 11M60 11M61
CONDENSATE DRAIN KITS
Condensate Drain Heat Cable 6 ft. 26K68 26K68
24 ft. 26K69 26K69
50 ft. 26K70 26K70
Heat Cable Tape Fiberglass - 1/2 in. x 66 ft. 36G53 36G53
Crawl Space Vent Drain Kit USA (Canada) 51W18 (15Z70) 51W18 (15Z70)
CONTROLS
iComfort Wi-Fi® Thermostat 10F81 10F81
1
Remote Outdoor Air Sensor (for dual fuel and Humiditrol®) X2658 X2658
2
Discharge Air Temperature Sensor 88K38 88K38
®
ComfortSense
3
Remote Outdoor Temperature Sensor
(for dual fuel and Humiditrol)
DOWNFLOW FILTER KITS
Downow Air Filter and Rack Kit 51W07 51W08
NIGHT SERVICE KITS
Night Service Kit 10U37 10U37
Universal Service Kit - Switches 89W20 89W20
TERMINATION KITS
Direct Vent Applications Only. See Installation Instructions for specic venting information.
Termination Kits Concentric US - 2 in. 71M80 69M29
Roof Termination Flashing Kit (2 ashings) 3 in. 44J41 44J41
VENTING
4
Left Side Vent Kit 2 or 3 in. 87W73 87W73
1
Remote Outdoor Sensor may be used with an iComfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conven-
tional outdoor unit.
2
Optional for service diagnostics.
3
Remote Outdoor Temperature Sensor for ComfortSense® 7000 Thermostat must be connected directly to the thermostat, Do not connect it to the SureLight® control.
4
NOTE - The curved exhaust pipe furnished with the Left Side Vent Kit counts as one additional 2 in. diameter 90° elbow. When using 3 in. diameter pipe, the furnished
NOTE - Termination Kits 44W92, 44W93, 30G28, 51W12, 81J20 and Crawl Space Vent Drain Kit 15Z70 are certied to ULC S636 standard for use in Canada only.
7000 Thermostat Y0349 Y0349
X2658 X2658
No. and Size of lter - in. (2) 16 x 20 x 1 (2) 16 x 20 x 1
3 in. - - - 60L46
Canada - 2 in. 44W92 44W92
3 in. - - - 44W93
Flush-Mount US - 2, 2-1/2 or 3 in. 51W11 51W11
Canada - 2, 2-1/2 or 3 in. 51W12 51W12
Wall - Close
Couple
Wall - Close
Couple WTK
US - 2 in. 22G44 - - -
3 in. 44J40 44J40
Canada - 2 in. 30G28 - - -
3 in. 81J20 81J20
Roof 2 in. 15F75 15F75
Wall Ring Kit 2 in. 15F74 15F74
curved exhaust pipe and eld provided ttings to transition from 2 in. to 3 in. count as 20 feet of equivalent pipe on all units.
GAS HEAT ACCESSORIES
Input High Altitude
Pressure Switch Kit
7501 - 10,000 ft. 0 - 10,000 ft. 0 - 10,000 ft.
All Models 93W75 65W77 70W87
Natural Gas to
LPG/Propane Kit
Page 3
LPG/Propane to
Natural Gas Kit
Page 4

BLOWER DATA

SLP98DF070V36B BLOWER PERFORMANCE (less lter)
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 495 543 639 735 830 926 1022 1118
Increase (+7.5%) Heat CFM 473 516 604 691 778 866 953 1041
Default Heat CFM 450 489 568 647 726 805 884 963
Decrease (-7.5% ) Heat CFM 430 467 540 614 687 761 834 908
Decrease (-15% ) Heat CFM 410 444 512 580 649 717 785 853
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Increase (+10%) Cool CFM 625 785 890 995 910 1075 1230 1365
Default Cool CFM 575 710 830 890 845 960 1125 1265
Decrease (-10%) Cool CFM 520 615 710 820 755 885 985 1150
Heating Input Range and Blower Volume - CFM
Blower Speed Selections
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
SLP98DF090V36C BLOWER PERFORMANCE (less lter)
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
35% 40% 50% 60% 70% 80% 90% 100%
Heating Input Range and Blower Volume - CFM
Increase (+15%) Heat CFM 710 756 848 940 1033 1125 1217 1309
Increase (+7.5%) Heat CFM 670 713 799 885 971 1057 1143 1230
Default Heat CFM 629 669 749 829 910 990 1070 1150
Decrease (-7.5% ) Heat CFM 559 599 681 763 845 927 1009 1091
Decrease (-15% ) Heat CFM 488 530 614 697 781 865 948 1032
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
Blower Speed Selections
High
Low Medium-
(Default)
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 610 770 900 1035 920 1080 1215 1385
Default Cool CFM 545 690 805 920 835 1000 1135 1255
Decrease (-10%) Cool CFM 465 620 720 810 750 890 1025 1145
The effect of static pressure is included in air volumes shown. The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position minimum 250 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
Page 4
Page 5
BLOWER DATA
SLP98DF090V48C BLOWER PERFORMANCE (less lter)
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 723 790 925 1060 1195 1329 1464 1599
Increase (+7.5%) Heat CFM 690 752 878 1004 1129 1255 1381 1507
Default Heat CFM 656 714 831 948 1064 1181 1297 1414
Decrease (-7.5% ) Heat CFM 601 654 761 867 974 1081 1188 1295
Decrease (-15% ) Heat CFM 545 593 690 787 884 981 1078 1175
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Increase (+10%) Cool CFM 775 940 1100 1255 1120 1340 1535 1745
Default Cool CFM 690 875 975 1135 1000 1220 1425 1625
Decrease (-10%) Cool CFM 635 755 915 1025 920 1100 1270 1470
Heating Input Range and Blower Volume - CFM
Blower Speed Selections
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
SLP98DF090V60C BLOWER PERFORMANCE (less lter)
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
35% 40% 50% 60% 70% 80% 90% 100%
Heating Input Range and Blower Volume - CFM
Increase (+15%) Heat CFM 653 728 877 1027 1176 1326 1475 1625
Increase (+7.5%) Heat CFM 603 673 813 953 1092 1232 1372 1512
Default Heat CFM 553 618 748 878 1009 1139 1269 1399
Decrease (-7.5% ) Heat CFM 510 570 690 811 931 1051 1171 1292
Decrease (-15% ) Heat CFM 467 522 632 743 853 963 1074 1184
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
Blower Speed Selections
High
Low Medium-
(Default)
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 1110 1265 1395 1600 1600 1750 1965 2130
Default Cool CFM 1000 1145 1275 1445 1445 1625 1805 1975
Decrease (-10%) Cool CFM 885 1060 1145 1265 1265 1445 1645 1805
The effect of static pressure is included in air volumes shown. The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position minimum 450 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm (SLP98DF090V48C) and 450 cfm (SLP98DF090V60C).
Page 5
Page 6
BLOWER DATA
SLP98DF110V60C BLOWER PERFORMANCE (less lter)
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 811 906 1096 1286 1475 1665 1855 2045
Increase (+7.5%) Heat CFM 744 835 1017 1199 1380 1562 1744 1926
Default Heat CFM 677 764 938 1112 1285 1459 1633 1807
Decrease (-7.5% ) Heat CFM 626 707 869 1031 1193 1355 1517 1679
Decrease (-15% ) Heat CFM 575 650 800 950 1101 1251 1401 1551
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Increase (+10%) Cool CFM 1090 1260 1395 1580 1580 1790 1990 2180
Default Cool CFM 965 1125 1285 1440 1440 1625 1845 2000
Decrease (-10%) Cool CFM 860 1030 1125 1270 1270 1470 1655 1845
The effect of static pressure is included in air volumes shown. The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position minimum 450 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.
Heating Input Range and Blower Volume - CFM
Blower Speed Selections
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Page 6
Page 7
CONTROL BOX
(includes variable capacity
integrated control,
transformer, circuit breaker
and door switch)
BLOWER
ACCESS
PANEL
SLP98DFV PARTS ARRANGEMENT
BLOWER ASSEMBLY
(Variable Speed Blower
Motor Is Hidden)
BAG ASSEMBLY
ACCESS PANEL
COMBUSTION AIR INDUCER
GAS VALVE
PRIMARY LIMIT
BURNER BOX ASSEMBLY
FIGURE 1
Page 7
Page 8
I-UNIT COMPONENTS
SLP98DFV unit components are shown in figure 1. The gas valve, combustion air inducer and burners can be accessed by removing the access panel. Electrical components are in the control box (figure 2) found in the blower compartment.
CAUTION
Electrostatic discharge can affect elec tronic components. Take precautions to neutralize electrostatic charge by touch ing your hand and tools to metal prior to handling the control.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the trans former (T1). The breaker is rated 3A at 32V. If the current exceeds this limit the breaker will trip and all unit opera tion will shut down. The breaker can be manually reset by pressing the button on the face. See figure 3.
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
A-Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage section of the unit. Transformers on all mod els are rated 40VA with a 120V primary and a 24V secon dary.
2. Interlock Switch (S51)
An interlock switch rated 14A at 125VAC is wired in series with line voltage. When the inner blower access panel is re moved the unit will shut down.
CONTROL BOX SLP98DFV
SURELIGHT®
DOOR
INTERLOCK
SWITCH
INTEGRATED
CONTROL
CIRCUIT BREAKER
FIGURE 2
TRANSFORMER
WARNING
Shock hazard. Disconnect power before servicing.
Integrated control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will re sult if repair is attempted.
4. Integrated Control (A92)
SLP98DFV units are equipped with the Lennox SureLight variable-capacity integrated control. This control can be used with the icomfort Wi-Fi municating comfort system. The control can also operate with a conventional single or two-stage thermostat. The system consists of an ignition / blower control (figures 4 and
5) with control pin designations in tables 1, 2 and ignitor. The control provides gas ignition, safety checks and indoor blower control with variable capacity rate gas heating. The furnace combustion air inducer, gas valve and indoor blow er are controlled in response to various system inputs such as thermostat signal, pressure and limit switch signal and flame signal. The control features a seven-segment LED display, indicating furnace status (including indoor blower) and error codes. The LED flashes in single digits. For exam ple using table 14 under LIMIT CODE, an “E” followed by “2” followed by “5” followed by “0”, the limit switch circuit is open. The control also has two 120 volt accessory terminals (used for a humidifier and electronic air cleaner) rated at (1) one amp each.
®
thermostat as part of a com
®
Page 8
Page 9
Electronic Ignition
At the beginning of the heat cycle the SureLight
®
integrated control monitors the low fire combustion air inducer pres sure switch. The control will not begin the heating cycle if the low fire pressure switch is closed (by-passed). Likewise the control will not begin the high fire heating cycle if the high fire pressure switch is closed, and will remain in low fire heat. However, if the high fire pressure switch closes during the low fire heat pre-purge, the control will allow high fire heat. Once the low fire pressure switch is determined to be open, the combustion air inducer is energized on ignition speed. When the differential in the pressure switch is great enough, the pressure switch closes and a 15-second pre-purge be gins. If the switch is not proven within 2-1/2 minutes, the in ducer is de-energized and the control will initiate vent cal ibration. If the vent calibration is unsuccessful the control goes into a 5 minute delay. The control will attempt vent cal ibration 3 more times before going into a 1 hour soft lockout. After the 15 second pre-purge period the SureLight ignitor warms up for 20 seconds. The gas valve then opens for a 4-second trial for ignition. The ignitor stays energized dur ing this trial until flame is sensed. If ignition is not proven during the 4-second trial for ignition, the control will try four more times with an inter purge and warm-up time between trials of 35 seconds. After a total of five trials for ignition (in cluding the initial trial), the control goes into Watchguard­Flame Failure mode. After a 60-minute reset period, the control will begin the ignition sequence again.
Thermostat Selection Modes
See table 3 for DIP switch settings
The control can be made to operate in three modes: vari able capacity, three-stage timed or two-stage. The variable capacity and two-stage modes are only operational with a two-stage thermostat. The thermostat selection is made us ing DIP switches one and / or two (figure 4) and must be positioned for the particular application.
Three- Stage Timed Operation
Using a single-stage thermostat the system will operate in a three stage timed mode. Upon a call for heat and a success ful ignition, the combustion air inducer will operate at 35% and the indoor blower will adjust to the appropriate cfm. Af ter a field selectable 7 or 12 minute delay period, the induc er RPM will increase and the unit will operate at 70%. The indoor blower will adjust to the appropriate cfm. After a fac tory set non-adjustable 10 minute delay expires the furnace will increase rate to 100%. The indoor blower will adjust to the appropriate cfm.
Two-Stage Operation
The system will also operate in conventional two-stage mode. While in two-stage mode, the furnace will fire on low fire (70% rate). The combustion air inducer will operate at 70% and the indoor blower will adjust to the appropriate cfm. The unit will switch to high fire on a W2 call from the thermostat. After a 30 second recognition period (during which the integrated control will receive a continuous W2 call) expires the furnace will increase to 100% rate. The in ducer will increase to 100% speed and the indoor blower will adjust to appropriate cfm. If there is a simultaneous call for first and second stage heat, the unit will fire on first stage heat and switch to second stage heat after 30 seconds of operation.
TABLE 1
®
Control 6 Pin Terminal Designation
SureLight
PIN # Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6 Not Used
Variable Capacity
Using a two-stage thermostat the system will operate in a variable capacity sequence mode. In this mode, the control will vary the firing rate anywhere between 35% and 100% of full capacity. The indoor blower will be automatically ad justed accordingly to provide the appropriate airflow at any rate. On the initial call for low fire, the furnace will operate at 35% and will remain there until the heat call is satisfied or a call for high fire is initiated. If there is a call for high fire the rate will increase by 10% if the current rate is above 60%. However if the current rate is below 60% the rate will in crease to 70%. After this initial rate increase to 70% capac ity, the furnace will increase rate by 10% every 5 minutes while a high fire heat call is present. If the high fire heat call is satisfied but the low fire heat call is still present, the furnace will remain at the current firing rate until the demand is satis fied or another call for high fire is initiated.
Page 9
TABLE 2
SureLight Control 12 Pin Terminal Designation
PIN # Function
1 Not used
2 High Fire Pressure Switch
3 Rollout In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Switch Out
12 Low Fire Pressure Switch
Page 10
COMBUSTION
AIR INDUCER
CONNECTOR
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
NEUTRAL
TERMINALS
IGNITOR
CONNECTOR
LINE VOLTAGE
+
HUM
EAC
TERMINALS
ON-BOARD
LINKS
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
FACTORY TEST
HEADER PINS.
FACTORY USE ONLY.
TB83 OUTDOOR
TB84 INDOOR
TERMINALS
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
7-SEGMENT
DIAGNOSTIC LED
INDOOR
BLOWER
CONNECTOR
W915 Y1 TO Y2
W951 R TO O
W915
W951
W914
W914 R TO DS
L - use only with
communicating T'stat and
non-communicating outdoor
unit.
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
REVERSING VALVE
1/4” QUICK CONNECT TERMINALS
HUM = 120 VAC OUTPUT TO HUMIDIFIER XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
CIRC = 120 VAC OUTPUT TO CIRCULATING BLOWER
EAC = 120 VAC OUTPUT TO ELECTRICAL AIR CLEANER
NEUTRALS = 120 VAC NEUTRAL
H = 24V HUMIDIFIER OUTPUT. DO NOT CONNECT TO COM
FORTSENSE
L = USE ONLY WITH A COMMUNICATING THERMOSTAT AND
A NON-COMMUNICATING OUTDOOR UNIT
DH = DEHUMIDIFICATION OUTPUT
COMMUNICATING THERMOSTAT ONLY
FIGURE 4
Page 10
®
THERMOSTAT
Page 11
SLP98DFV INTEGRATED CONTROL CONFIGURATION GUIDE
FIGURE 5
Page 11
Page 12
Thermostat Selection Switch Settings
TABLE 3
Operation
Variable Capacity Heat
Thermostat Switch 1 Switch 2 Switch 3
Two-Stage Off On Off
(35% to 100%)
Three-Stage Heat (35%, 70%, 100%)
Single-Stage On Off 2nd stage delay
OFF = 7 minutes
ON = 12 minutes
3rd stage delay
10 minutes fixed
Two-Stage Heat (W1 70%, W2 100%) Two-Stage Off Off Off
NOTE - When the SLP98DFV is used with an icomfort
®
communicating thermostat, all indoor blower
Wi-Fi speed selections and DIP switch settings are made by the communicating thermostat.
Heating Operation DIP Switch Settings -- Figure 4
Switch 1 -- Thermostat Selection -- This unit may be used
with either a single-stage or two-stage thermostat. The ther mostat selection is made using a DIP switch which must be properly positioned for the particular application. The DIP switch is factory-positioned for use with a two-stage thermo stat. If a single-stage thermostat is to be used, the DIP switch must be repositioned. See table 3.
NOTE - All DIP switches are factory shipped in the “OFF” position.
Switch 2 -- Operating Mode with Two-Stage Thermostat
-- If a two-stage thermostat is used, the furnace can operate
in either variable-capacity or conventional two-stage mode. When variable-capacity mode is selected, the firing rate of the unit is varied to maximize comfort. Conventional two­stage mode is the factory default setting. See table 3.
Switch 3 -- Second-Stage Heat On Delay -- If a single­stage thermostat is used, the integrated control can be used to energize second-stage heat after either 7 minutes or 12 minutes of first-stage heat operation. See table 3.
Switches 4 and 5 -- Blower-Off Delay -- The blower-on delay of 45 seconds is not adjustable. The blower-off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 4 and 5 on the integrated control. The unit is shipped from the facto ry with a blower-off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact mo ment that the blower is de-energized. Longer off delay set tings provide lower supply air temperatures; shorter set tings provide higher supply air temperatures. Table 4 pro vides the blower off timings that will result from different switch settings.
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
60 Off On
90 (factory) Off Off
120 On Off 180 On On
Indoor Blower Operation DIP Switch Settings Switches 6 and 7 -- Continuous Indoor Fan Operation -­Blower Speed - Switches 6 and 7 are used to select blower
motor speeds during continuous indoor blower operation. The unit is shipped from the factory with DIP switches posi tioned for medium low (2) speed during continuous indoor blower operation. The table below provides the continuous blower speeds that will result from various switch settings. Refer to blower tables at the front of this manual for corre sponding cfm values.
Continuous Indoor Fan
Speed
1 - Low (28%) Off On
2 - Medium Low
(38%)
(Factory)
3 - Medium High
(70%)
4 - High (100%) On On
Switches 8 and 9 -- Cooling Mode Blower Speed --
Switches 8 and 9 are used to select cooling blower motor speed. The unit is shipped from the factory with the DIP switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro vides the cooling mode blower speeds that will result from different switch settings. Refer to blower tables at the front of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
Speed
1 - Low On On
2 - Medium Low Off On
3 - Medium High On Off
4 - High (Factory) Off Off
TABLE 4
Switch 4 Switch 5
TABLE 5
Switch 6 Switch 7
Off Off
On Off
TABLE 6
Switch 8 Switch 9
Page 12
Page 13
Switches 10 and 11 -- Cooling Mode Blower Speed Ad justment -- Switches 10 and 11 are used to select blower
speed adjustment settings. The unit is shipped from the fac tory with the DIP switches positioned for NORMAL (no) ad justment. The DIP switches may be positioned to adjust the blower speed by +10% or -10% to better suit the application. The table below provides blower speed adjustments that will result from different switch settings. Refer to blower tables at the front of this manual for corresponding cfm val ues. With switches 10 and 11 set to ON, motor will bypass ramping profiles and all delays and immediately upon a call for cool, run at COOLING speed selected. LED will continue to operate as normal. This mode is used to check motor op eration.
TABLE 7
Blower Speed Adjustment
Adjustment
Switch 10 Switch 11
+10% (approx.) On Off
NORMAL (Factory) Off Off
-10% (approx.) Off On MOTOR TEST On On
Ramping Option A (Factory Selection)
D Motor runs at 50% for 30 seconds. D Motor then runs at 82% for approximately 7-1/2 min
utes.
D If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes, mo tor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Switches 12 and 13 -- Cooling Mode Blower Speed Ramping -- Switches 12 and 13 are used to select cooling
mode blower speed ramping options. Blower speed ramp ing may be used to enhance dehumidification performance. The switches are factory set at option A which has the great est effect on blower motor performance. Table 8 provides the cooling mode blower speed ramping options that will re sult from different switch settings. The cooling mode blower speed ramping options are detailed below.
TABLE 8
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 12 Switch 13
A (Factory) Off Off
B On Off C Off On D On On
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec
onds then ramps down to stop.
OFF
100% CFM
DEMAND
100% CFM
45 SEC.
OFF
Ramping Option D
Motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
100% CFM
COOLING DEMAND
OFFOFF
Page 13
Page 14
Low Heat Blower Speeds
TABLE 9
Thermostat
Demand
Blower
Speed
Adjust
ments
DIP SWITCH SETTINGS
14 15 16
+15% On Off On
Low Heat (R to W1)
+7.5% On Off Off
Normal Off Off Off
-7.5% On On Off
-15% On On On
Switches 14 through19 -- Heating Mode Blower Speed
-- Switches 14 through 19 are used to select heating mode
blower motor speeds. These switches are factory set at the OFF position which provides 100 % of normal speed during HIGH HEAT demand, 70% of normal speed during MID­RANGE HEAT demand and 35% of normal speed during LOW HEAT demand. Switches 14, 15 and 16 are used to adjust the LOW FIRE blower motor speed. Switches 17, 18 and 19 are used to adjust the HIGH FIRE blower motor speed. Figure 6 and tables 9 and 10 provides the heating mode blower speeds that will result from different switch settings. Figure 6 indicates the effect the DIP switch set tings (tables 20 &21 above) have upon the heating airflow at various furnace firing rates. Refer to blower tables at the front of this manual for corre sponding cfm values.
Thermostat
Demand
High Heat
(R to
W1 & W2)
High Heat Blower Speeds
TABLE 10
Blower
Speed
Adjust
ments
DIP SWITCH SETTINGS
17 18 19
+15% On Off On
+7.5% On Off Off
Normal
Off Off Off
-7.5% On On Off
-15% On On On
Increasing
Airflow
+15% +7.5%
Nominal
-7.5%
-15%
Airflow Determination
S Identify blower speed adjustment points at low and high fire S Airflow will lie on straight line between these two points and will fall within
the shaded area as shown EXAMPLE -7.5% at low fire +7.5% at high fire
Low Fire
Dip Switches
14, 15, 16
35%
50%
60%
70%
RATE (%)
FIGURE 6
80%
Dip Switches
90%
High Fire
17, 18, 19
+15%
+7.5%
Nominal
-7.5%
-15%
100%
Page 14
Page 15
On-Board Link W914 DS to R (Figure 4)
On-board link W914, is a clippable connection between ter minals DS and R on the integrated control. W914 must be cut when the furnace is installed with either the Harmony IIIt zone control or a thermostat which features humidity control. If the link is left intact the PWM signal from the Har mony III control will be blocked and also lead to control dam age. Refer to table 15 for operation sequence in applica tions including SLP98DFV, a thermostat which features hu midity control and a single-speed outdoor unit. Table 16 gives the operation sequence in applications with a two­speed outdoor unit.
On-Board Link W951 R to O (Figure 4)
On-board link W951 is a clippable connection between ter minals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal “O” will remain ener gized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 Y1 to Y2 (Figure 4)
On-board link W915 is a clippable connection between ter minals Y1 and Y2 on the integrated control. W915 must be cut if two-stage cooling will be used. If the link is not cut the outdoor unit will operate in second-stage cooling only.
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating sta tus, target airflow, error codes and other information. Table 14 lists diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the seven­segment diagnostic LED. This button is used to enable the Error Code Recall mode and the Field Test mode. Press the button and hold it to cycle through a menu of options. Every five seconds a new menu item will be displayed. When the button is released, the displayed item will be selected. Once all items in the menu have been displayed, the menu re sumes from the beginning until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error codes. Select “c” from the Error Code Recall menu to clear all error codes. Button must be pressed a second time while “c” is flashing to confirm command to delete codes. Press the button until a solid “” is displayed to exit the Error Code Recall mode.
Field Test Mode
Use the diagnostic push button to scroll through the menu as described above. Release the button when the LED flashes “-” to select the Field Test mode.
While in the Field Test mode the technician can: D Initiate furnace ignition and move to and hold low-fire
rate by applying a R to W1 jumper.
D Initiate furnace ignition sequence and move to and hold
high-fire rate by applying a jumper from R to W1 and W2.
D Initiate furnace ignition sequence and move to and hold
mid-fire rate by applying a jumper to R and W2.
D Apply then remove the jumper from R to W1 and W2 to
change the firing rate from low fire to mid fire and high fire.
D A vent calibration sequence can be initiated even if a
thermostat signal is not present. Press and hold the push button until a solid “C” is displayed. Release the button and calibration will begin. The furnace will per form the high-fire and low-fire pressure switch calibra tions and display “CAL”. After calibration, the LED will return to the flashing “-” display.
During Field Test mode operation, all safety switches are still in the circuit (they are not by-passed) and indoor blower performance and timings will match DIP switch selections. Current furnace firing rate, indoor blower CFM and flame signal will be displayed. To exit the Field Test mode, press and hold the button. The menu will resume from the begin ning. A The integrated control will automatically exit the Field Test mode after 45 minutes of operation.
Soft Disable
Soft disabling is when thermostat finds a device on the BUS that it does not recognize and the thermostat sends a the device a message to be in soft disabling mode until properly configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying the soft disable code.
ls
o, cycle the main power to exit the Field Test mode.
1- Confirm proper wiring between all devices (thermo stat, damper control module, indoor and outdoor).
2- Cycle power to the control that is displaying the soft disable code.
3- Put the room thermostat through set up.
4- Go to setup / system devices / thermostat / edit / then push reset.
5- Go to setup / system devices / thermostat / edit / then push resetAll.
Page 15
Page 16
TABLE 11
Idle Menu Options
These options are displayed on the menu when the button is pressed during normal operation
DISPLAY
No change (idle) remain in idle mode
Solid “E” enter diagnostic mode
Solid “-” enter field test mode
NOTE - No change implies the display will continue to show whatever is currently being displayed for normal operation
Field Test Menu Options
These options are displayed when the button is used in Field Test Mode
DISPLAY
No change (blinking “-”) remain in field test mode
Solid “-” exit field test mode
Solid “c” start pressure switch calibration
Field Test Menu Options
These options are displayed when the button is used in diagnostic recall mode
ACTION (when button released)
TABLE 12
ACTION (when button released)
TABLE 13
DISPLAY
No change (displaying error history) remain in diagnostic recall mode
Solid (3 horizontal bars) exit diagnostic recall mode
Solid “c” clear error history
Once the button is released to clear the error history a blinking “c” will be shown on the display for up to 10 seconds. During this time the user must press and release the button one additional time to confirm the action of deleting the error history. Once the error history is deleted it cannot be recovered.
ACTION (when button released)
Page 16
Page 17

Configuring Unit Size Codes

Power-Up - Number displayed represents by integrated control unit size code (furnace model
and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following:
To enter Field Test Mode: push and hold button next to 7-segment LED display until solid dash symbol appears. Release button.
If alarm is present, furnace control will display error code. If alarm is not present solid dash starts blinking on 7-segment LED display.
Yes
Furnace control in IDLE mode
No heating, cooling or indoor fan
operation)
No
_
Turn room thermostat to OFF
UNIT SIZE
CODE
FURNACE MODEL
H
_
SLP98DFV070-36B
J
SLP98DFV-090-36C
L
SLP98DFV-090-48C
n
SLP98DFV-090-60C
o
SLP98DFV-110-60C
Push and hold button until the solid P symbol is displayed on the 7-segment LED. Release button. This mode allows the user to select a unit size code number that matches the furnace model size and capacity.
IMPORTANT: Field replacement controls may need to be manually configured to validate furnace unit size code.
Solid P starts blinking on 7-Segment LED
Push and hold button. Integrated control will display unit size code number for each furnace model for five seconds.
P
P
When the correct unit size code is displayed, release button. Selected code will flash for 10-second period. During that period, hold push button until code stops blinking (disappear for 2 seconds). Integrated control will store code in memory and will automatically exit Field Test Mode and reset. (If second period expires or push button is held less than five seconds, control will automatically exit Field Test Mode and go into IDLE mode without storing unit size code. If this happens, programming function must be repeated).
. If
Verify that the selected unit size code is correct and stored in non-volatile memory by cycling the 24 volt power to the furnace control. (At 24 volt power-up of the furnace control, the 7-segment LED will display a unit size code three horizontal bars display, board does not recognize unit size code function must be repeated)
. Programming
FINISHED
Page 17
Page 18
TABLE 14
LED 7 Segment Status / Error Code
Press the diagnostic push button and hold it to cycle through a menu of options. Every five seconds a new menu item will be displayed. Release the button when the desired mode is displayed. When a solid ”P” is displayed, the furnace capacity/ size is programmed. When the solid “E” is displayed, the control enters the Error Code Recall mode. Error Code Recall mode menu options: No change (display ing error history) remains in Error Code Recall mode; solid “b” exits Error Code Recall mode; and solid “c” clears the error history. Must press button while flashing “c” is displayed to clear error codes. When the solid “-” is displayed, the control enters the Field Test mode. Field Test mode menu options: Solid “C” starts pressure switch calibration; blinking “-” exits Field Test mode.
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
.
Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF).
A
Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5 second OFF) / cfm setting for current mode displayed.
C
Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes).
d
Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting displayed / Pause / Repeat Codes).
h
Variable Capacity Heat (1 second ON, 0.5 second OFF) / % of input rate displayed / Pause/ cfm setting / Pause/ Repeat codes.
H
Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm set ting displayed / Pause / Repeat codes.
df
Defrost mode.
U
Discharge air temperature
Soft disable - Soft disabling is when thermostat finds a device on the BUS that it does not recognize and the thermostat sends a the device a message to be in soft disabling mode until properly configured. Two horizontal bars will display.
E 105
Device communication problem - No other devices on BUS (Communication system).
E 110
Low line voltage. Line Voltage low (Voltage lower than nameplate rating)
E 113
High line voltage. Line Voltage High (Voltage higher than nameplate rating)
E 114
Line voltage frequency out-of-range. No 60 hertz power (Check voltage and frequency).
E 115
Low 24V - Control will restart if the error recovers. 24 voltage low (Range is 18 to 30 volts) Check voltage.
E 120
Unresponsive device. Usually caused by delay in outdoor unit responding to
E 124
Active communicating thermostat signal missing for more than 3 minutes. Equipment lost communication with the thermostat. Check
E 125
Control failed self-check, internal error, failed hardware. Will restart if error recovers. Integrated furnace control not communicating. Covers hardware errors (flame sense circuit faults, pin shorts, etc.).
E 126
Failed internal control communication between microcontrollers. Hardware problem on the control board. Cycle power on
E 131
Corrupted control parameters (Verify configuration of system). Reconfigure the system. Replace board if service (heating
E 180
Outdoor air sensor failure - NO error if disconnected. Only shown if shorted or out-of-range.
E 200
Hard lockout - Rollout circuit open or previously open. Correct unit cause of rollout trip or replace flame rollout
E 201
Indoor blower communication failure - Unable to communicate with blower motor. Indoor blower communication failure including power
Steps to follow if the damper control module is displaying the soft disable code.
1- Confirm proper wiring between all devices (thermostat, damper control module, indoor and outdoor). 2- Cycle power to the control that is displaying the soft disable code. 3- Put the room thermostat through set up. 4- Go to setup / system devices / thermostat / edit / then push reset. 5- Go to setup / system devices / thermostat / edit / then push resetAll.
Equipment is unable to communicate. Check for mis wire and loose connections and check for a high voltage source of noise close to the system. (welder etc.).
Check voltage.
Check voltage.
indoor unit poling recycle power, check wiring.
connections and cycle power on the thermostat.
Hardware problem on the control board. Cycle power on control. Replace if problem prevents service and is persistent.
control. Replace if problem prevents service and is persistent.
/cooling) is unavailable.
Compare outdoor sensor resistance to temperature resistance charts in installation instructions. Replace if necessary.
switch and test furnace operation.
outage.
Page 18
Page 19
Integrated Control Diagnostic Codes (continued)
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 202
E 203
E 204
E 205
E 207
E 223
E 224
E 225
E 226
E 227
E 228
E 240
E 241
E 250
E 252
E 270
E 271
E 272
E 273
E 274
E 275
E 276
E 290
E 291
Indoor blower motor mis-match - Indoor motor horsepower does not match unit capacity.
Appliance capacity / size is NOT programmed. Invalid unit codes refer to configuration flow chart in installation instructions.
Gas valve mis-wired. Check operation of gas valve.
Gas valve control relay contact shorted. Check operation of gas valve.
Hot surface ignitor sensed open - Refer to troubleshooting in installation instruction.
Low pressure switch failed open - Refer to troubleshooting in installation instruction.
Low pressure switch failed closed - Refer to troubleshooting in installation instruction.
High pressure switch failed open - Refer to troubleshooting in installation instruction.
High pressure switch failed closed - Refer to troubleshooting in installation instruction.
Low pressure switch open during trial for ignition or run mode. Refer to trouble shooting in installation instruction.
Unable to perform successful pressure switch calibration. Retry after 300 seconds. Error counter cleared when exit
Low flame current - Run mode - Refer to troubleshooting in installation instruction.
Flame sensed out of sequence - Flame still present. Shut off gas, check for gas valve leak.
Limit switch circuit open - Refer to troubleshooting in installation instruction. Check why limit is tripping, overfired, low air flow.
Discharge air temperature too high (gas heat only). Check temperature rise, air flow and input rate.
Soft lockout - Exceeded maximum number of retries. No flame current sensed. Check for gas flow, ignitor lighting burner, flame sensor
Soft lockout - Exceeded maximum number of retries. Last retry failed due to the pressure switch opening.
Soft lockout - Exceeded maximum number of recycles. Last recycle due to the pressure switch opening.
Soft lockout - Exceeded maximum number of recycles. Last recycle due to flame failure.
Soft lockout - Exceeded maximum number of recycles. Last recycle failed due to the limit circuit opening or limit remained open longer than 3 minutes.
Soft lockout - Flame sensed out of sequence from code 241 fault. Flame signal is gone.
Soft lockout - Exceeded maximum number of calibration retries. See E 228.
Ignitor circuit fault - Failed ignitor or triggering circuitry. See E 207.
Restricted air flow - Cubic feet per minute is lower than what is needed for minimum firing rate.
Incorrect furnace size code selected. Check unit size codes on configuration guide or in installation instructions.
No furnace size code selected. Check unit size codes on configuration guide or in installation instructions.
Measure resistance of Hot Surface Ignitor, replace if open or not within specification.
Check inches of water column pressure during operation of low pressure switch on heat call, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restric tion.
Check low pressure switch for closed contacts, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and re striction.
Check inches of water column pressure of high pressure switch on heat call, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check high pressure switch for closed contacts, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check inches of water column pressure during operation of low pressure switch on heat call, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restric tion.
ing lockout, unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
Check micro amperes of flame sensor, clean or replace sensor. Measure voltage of neutral to ground for good unit ground.
current.
See E 223.
See E 223 and E 225.
See E 240.
See E 250.
See E 241.
Check for dirty filter, unit air flow restriction, blower performance.
Page 19
Page 20
Integrated Control Diagnostic Codes (continued)
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 292
E 294
E 295
E 310
E 311
E 312
E 313
E 331
E 347
E 348
E 349
E 401
E 402
E 403
E 404
E 405
E 406
E 407
E 408
E 409
Indoor blower motor unable to start - Seized bearings, stuck wheel, etc. Indoor blower motor unable to start (seized
Combustion air inducer motor amp draw is too high. Check combustion blower bearings, wiring , amperes,
bearing, stuck wheel, etc), replace motor or wheel if assembly does not operate or meet performance.
replace if it does not operate or meet performance.
Indoor blower motor temperature is too high. Indoor blower motor over temperature (motor
tripped on internal protector), Check motor bear ings, amperes. Replace if necessary.
Discharge error sensor failure - No error if disconnected. Only shown if shorted or out-of-range.
Heat rate reduced to match indoor blower air flow. Replace filter or repair duct restriction.
Discharge air temperature(DATS) out of range, code is activated during ”Field test mode”.
Furnace blower in cutback mode due to restricted airflow. Check filter and ductwork. To clear replace filter if needed or repair/ add ductwork.
Restricted air flow in cooling or continuous fan mode is lower than cfm setting.
Restricted airflow - Indoor blower is running at a reduced cubic feet per minute (Cutback Mode) ­The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating out of its designed parameters (0 to 0.8 inches water column total external static pressure). Check filter and ductwork. To clear re place filter if needed or repair/ add ductwork.
Indoor or outdoor unit capacity mismatch. Incorrect Indoor /outdoor capacity code selected.
Check for proper configuration in installation instruc tions. Alarm is just a warning. The system operation is not impacted at all and alarm would clear when Commissioning is exited.
Global network connection - Communication link problem. For Future Use.
No 24 Volt output on Y1 to C with non-communicating outdoor unit. Y1 relay / Stage 1 failed (Pilot relay contacts did not
close or the relay coil did not energize).
No 24 Volt output on Y2 to C with non-communicating outdoor unit. Y2 relay / Stage 2 failed (Pilot relay contacts did not
close or the relay coil did not energize).
No 24 Volts between R & O with non-communicating outdoor unit (Dual fuel module required for heat pump application).
Configuration link R to O needs to be cut on control board.
LSOM - Compressor ran more than 18 hours in air conditioning mode. Compressor protector is open. Check for high head
pressure, check compressor supply voltage. Out door unit power disconnect is open , compressor circuit breaker or fuse(s) is open, broken wire or connector is not making contact. Low or high pres sure switch open if present in the system. Compres sor contactor has failed to close.
LSOM - Outdoor unit system pressure trip. Compressor ran over 18 hours in air conditioning
mode.
LSOM - Compressor short-cycling (Running less than 4 minutes). Outdoor unit pressure trip. Check dirty coil, fan mo
tor, refrigerant charge.
LSOM - Compressor rotor locked. Compressor short cycling (Running less than 4 min
utes).
LSOM - Compressor open circuit. Check capacitor, wiring, hard start kit , replace com
pressor.
LSOM - Compressor open start circuit. Check compressor for hot (cool down) , check pres
LSOM - Compressor open run circuit.
sures, fan motor etc. Replace compressor if unable to get circuit to close and compressor to operate.
LSOM - Compressor contactor is welded.
LSOM - Compressor low voltage. Replace contactor.
Page 20
Page 21
TABLE 15
OPERATING SEQUENCE
SLP98DFV and Single-Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
Demand Relative Humidity
System
Condition
Step
1st
stage
O G Status D*
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
24
VAC
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidification
Call
2 On On On Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidification
call
Dehumidification
call ONLY
2 On On On Demand
1 On On On Demand
24
VAC
0
VAC
0
VAC
On-board links at indoor unit with a single-stage outdoor unit: With Condensing unit - Cut W914 (R to DS) on SureLight With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight control. *ComfortSense
®
7000 thermostat ony
Compressor
High 100%
High 100%
High 70%
High 100%
High 70%
High 70%
®
control;
Blower
CFM
(COOL)
®
Comments
Compressor and indoor blower follow thermostat demand
Thermostat energizes Y1 and de-energizes D on a call for de-humidification
Dehumidification mode begins when humidity is greater than set point
Thermostat will keep out door unit energized after cooling temperature set point has been reached in order to maintain room humidity setpoint.
Page 21
Page 22
TABLE 16
OPERATING SEQUENCE
SLP98DFV and Two-Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
Demand Relative Humidity
System
Condition
Step
1st
stage
2nd
stage
G
O
Status D*
NO CALL FOR DEHUMIDIFICATION
Normal Operation -
Y1
Normal Operation -
Y2
1 On On
2 On
On
On
On
On
Acceptable
Acceptable
24
VAC
24
VAC
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On
Dehumidification
Call
2 On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On
Dehumidification
call
Dehumidification
call ONLY
2 On
1 On
On
On
On
On
On
On
On
Acceptable
Demand
Demand
24
VAC
0
VAC
0
VAC
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On
Dehumidification
Call
2 On
On
On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On
Dehumidification
call
2 On
On
On
On
On
Acceptable
Demand
24
VAC
0
VAC
Compressor
Low 70%
High 100%
Low 70%
High 70%
Low 70%
High 70%
High 70%
High 100%
High 70%
Low 70%
High 70%
Blower
CFM
(COOL)
Comments
Compressor and indoor blower follow thermostat demand
Thermostat energizes 2nd stage and de-ener gizes D on a call for de­humidification
Dehumidification mode begins when humidity is greater than set point
Thermostat will keep out door unit energized after cooling temperature set point has been reached in order to maintain room humidity setpoint.*
Thermostat energizes 2nd stage and de-ener gizes D on a call for de­humidification
Dehumidification mode begins when humidity is greater than set point
Dehumidification
call ONLY
1 On
On
On
On
Demand
On-board links at indoor unit with a two-stage outdoor unit: Cut factory link from Y1 to Y2 or cut W915 (Y1 to Y2) on SureLight grated control. With Condensing unit - Cut W914 (R to DS) on SureLight
0
VAC
High 70%
®
®
integrated control; With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight integrated control. *ComfortSense
®
7000 thermostat only
Page 22
inte
®
Thermostat will keep out door unit energized after cooling temperature set point has been reached in order to maintain room humidity setpoint.
Page 23
B-Blower Compartment (Figure 7)
To Remove Blower From Unit:
1. Disconnect Power, 2. Remove access panels. 3. Remove Control Box 4. Remove Bolts. 5. Unplug Motor Wires From
Control Board (070 unit remove exhaust and air intake pipe)
Then Slide Out Front of Unit.
FIGURE 7
1. Blower Motor (B3)
A solid‐state controller is permanently attached to the motor. The controller is primarily an A.C. to D.C. convert er. Converted D.C. power is used to drive the motor. The controller contains a microprocessor which monitors varying conditions inside the motor (such as motor work load).
SLP98DFV BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
FIGURE 8
The controller uses sensing devices to sense what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in se quence, the rotor shaft turns the blower.
WARNING
During blower operation, the ECM motor emits ener gy that may interfere with pacemaker operation. Inter ference is reduced by both the sheet metal cabinet and distance.
The SLP98DFV line uses three different motor sizes, a 1/2 hp, 3/4 hp and 1 hp. The motor communicates with the integrated control via a 2-way serial connection. The motor receives all necessary functional parameters from the integrated control and does not rely on a factory program like traditional variable speed motors. SLP98DFV units use a three‐phase, electroni cally controlled D.C. brushless motor (controller converts single phase a.c. to three phase D.C.), with a permanent‐ magnet‐type rotor (figure 8). Because this motor has a perma nent magnet rotor it does not need brushes like conventional D.C. motors. Internal components are shown in figure 8. The stator wind ings are split into three poles which are electrically connected to the controller. This arrangement al l o w s m o t o r wi n d i ngs t o turn on and off in sequence by the controller.
IMPORTANT
Earlier ECM motors used on other Lennox furnace models are not interchangeable with motors used on the SLP98DFV furnace line.
All SLP98DFV blower motors use single phase power. An external run capacitor is not used. The motor uses permanently lubricated ball‐type bearings.
Internal Operation
The motor is controlled via serial communication between the integrated control on the furnace and the controller at tached to the motor shell. The messages sent back and forth between the two controls serve to communicate rota tional direction, demand, motor size, current draw, torque, and rpm, among other variables.
Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel. The controller moni tors the static work load on the motor and motor amp‐draw to determine the amount of rpm adjustment. Blower rpm may be adjusted any amount in order to maintain a constant cfm as shown in Blower Ratings Tables. The cfm remains relatively stable over a broad range of static pressure. Since the blower constantly adjusts rpm to maintain a specified cfm, motor rpm is not rated. Hence, the terms “cool speed”, “heat speed ” or “speed tap” in this manual, on the unit wiring diagram and on blower B3, refer to blower cfm regardless of motor rpm.
Initial Power Up
When line voltage is applied to B3, there will be a large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC filter capacitors inside the controller. If the discon nect switch is bounced when the disconnect is closed, the dis connect contacts may become welded. Try not to bounce the disconnect switch when applying power to the unit.
Page 23
Page 24
Motor Start‐Up
When B3 begins start‐up, the motor gently vibrates back and forth for a moment. This is normal. During this time the elec tronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called “soft‐start”). The motor may take as long as 10‐15 seconds to reach full speed. If the motor does not reach 200 rpm within 13 seconds, the motor shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a frozen bear ing or blocked blower wheel. The motor may attempt to start eight times. If the motor does not start after the eighth try, the controller locks out. Reset controller by momentarily turning off power to unit.
BLOWER B3 HARNESS CONNECTORS
P48 5 Pin
SHAFT
P49 4 Pin
MOTOR with INTEGRATED
CONTROLLER
J48 5 Pin
The DC filter capacitors inside the controller are connected electrically to the motor supply wires. The capacitors take approximately 5 minutes to discharge when the disconnect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempt ing to service motor.
DANGER
Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before at tempting to service motor. Failure to wait may cause personal injury or death.
Power Choke (L13)
A choke coil is used on SLP98DFV 5 ton 3/4 hp and 1 hp un its. Th e choke is located on the blower housing and is used to supress transient current spikes.
J49 4 Pin
J49 4 Pin Control Connector
J48 5 Pin Line Voltage Connector
FIGURE 9
Page 24
Page 25
Troubleshooting Motor Operation (figure 10)
To verify motor operation see steps below:
1- Remove J48 (5 pin power plug) from P48 on the mo tor.
2- With the power on at the furnace and door switch de pressed, use a test meter to verify 120V between pins 4 and 5 on J48.
3- Reconnect J48 to P48 on the motor.
4- Remove J49 (4 pin low voltage connector) from P49 on the motor.
5- Using test jumpers, apply 24V to pins 3 and 4 on P49 on the motor.
Note: Do not apply 24V to pins 2 and 4 on P49. Doing so will cause permanent damage to the motor.
6- Motor should run at 75%.
7- Test is complete. Remove jumpers and reconnect plugs.
Another option is to use the TECMate PRO motor tester with the 16 to 4 pin adaptor. The use of the TECMate PRO isolates the motor from the integrated control. Follow the instructions provided with the kit. If the motor runs do not replace.
BLOWER B3 HARNESS CONNECTORS
P48 5 Pin
P49 4 Pin
SHAFT
MOTOR with INTEGRATED
CONTROLLER
P48 5 Pin
P49 4 Pin
J48 Connector installed on motor
P49 4 Pin
1
2
3
4
5
120v
0
J48 Connector
240v
Page 25
24v Transformer
J49 Connector
FIGURE 10
Page 26
Troubleshooting Motor Windings
Ensure that motor windings are not damaged by performing the following tests:
NOTE - If your ohm meter is not an auto-ranging type, set it to the highest ohm scale (100k ohms or greater) before per forming tests.
TABLE 17
Ohm Meter Range
Scale
2M
200k
20k
2k
200 two hundred ohm 0-200
Measurement Range
in words ohms
two megohm -- two million ohms
two hundred kilohm -­two hundred thou sand ohms
twenty kilohm -­twenty thousand ohms
two kilohm -- two thousand ohms
0-2,000,000
0-200,000
0-20,000
0-2,000
FIGURE 11
TEST A
Measure the resistance between each of the three motor leads (3-pin plug) and the unpainted part of the end shield.
If the winding resistance to ground is <100k ohms, replace the motor and control module. If the resistance to ground is >100k, the motor windings are fine. Proceed to Test B.
Test A
FIGURE 12
TEST B
Use an ohmmeter to measure the motor phase-to-phase re sistance by checking these combinations of the the 3-pin motor plug. For the purpose of this test, start at either end of the connector as lead 1.
1 - The lead-to-lead resistance across any two leads
should be less than 20 ohms.
2 - Each lead-to-lead resistance should be the same. If the measured resistance is greater than 20 ohms, replace
the motor and control module.
Test B
Page 26
FIGURE 13
Page 27
C-Heating Components
1. Ignitor (Figure 14)
The SureLight nitor longevity is enhanced by controlling voltage to the igni tor. The integrated control provides a regulated 120 volts to the ignitor for a consistent ignition and long ignitor life. Due to this feature of the control, voltage measured with a digital meter will be slightly lower. To measure correct voltage use a true RMS meter or ignitor can be ohmed. Ohm value should be 39 to 70.
2. Flame Sensor (Figure 14)
A flame sensor is located on the left side of the burner sup port. The sensor is mounted on the flame rollout plate and the tip protrudes into the flame envelope of the left-most burner. The sensor can be removed for service without re moving any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to re main open as long as flame signal is sensed. To check flame sense signal use the push-button found on the integrated control and go to Field Test Mode. The menu will display the flame signal. Table 18 shows the flame signal for the SLP98DFV unit.
Normal
2.6 or greater 2.5 or less 1.1
NOTE - A much higher than normal micro amp reading (15 for example) may appear when checking flame signal.
3. Flame Rollout Switches (Figure 14)
Flame rollout switch S47 is a high temperature limit located inside the burner box. Each furnace is equipped with two identical switches. The limit is a N.C. SPST manual‐reset limit connected in series with the primary limit S10. When
®
ignitor is made of durable silicon nitride. Ig
TABLE 18
Flame Signal in Microamps
Low Drop Out
S47 senses rollout, the circuit breaks and the integrated control immediately stops ignition and closes the gas valve. If unit is running and flame rollout is detected, the gas valve will close and integrated control will be disabled. Rollout can be caused by a blocked heat exchanger, flue or lack of com bustion air. The switch is factory set to trip (open) at 210°F and cannot be adjusted. The switch can be manually reset. To manually reset a tripped switch, push the reset button located on the center of the switch.
4. Burners (Figure 14)
All units use inshot burners. Burners are factory set and re quire no adjustment. Always operate the unit with the burner box front panel in place. Each burner uses an orifice that is precisely matched to the burner input. Burners can be re moved as a one piece assembly for service. If burner assem bly has been removed, it is critical to align center of each burn er to the center of the clamshell when re-installing. See more detail in Section VII- MAINTENANCE..
5. Duralock Plus Heat Exchanger (Figure 15)
SLP98DFV units use an aluminized steel primary and stainless steel secondary heat exchanger assembly. Heat is transferred to the air stream from all surfaces of the heat exchanger. The shape of the heat exchanger en sures maximum efficiency.
The combustion air inducer pulls fresh air through the burn er box. This air is mixed with gas in the burner venturi and at the corbel orifices. The gas / air mixture is then burned at the en t rance of eac h clamsh e l l . Combustion gases are then pulled through the primary and secondary heat exchangers and exhausted out the exhaust vent pipe.
Page 27
Page 28
Ignitor
Rollout Switch
Burner Box Assembly
Burner Assembly
Intake Air Collar
Flame Sensor
Burner Box Front Cover
(remove screw to open cover)
Gas Valve
Sight Glass
FIGURE 14
Page 28
Page 29
6. Primary Limit Control (S10)
Figure 15 shows the primary limit (S10) used on SLP98DFV units located in the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. Once the limit opens, the furnace control energizes the supply air blower and de-energizes the gas valve. The limit automati cally resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. In the event of restricted air flow, the integrated control will reduce firing rate and indoor blower airflow in 10% increments until a sus tainable air flow is reached. If the furnace reaches 35% fir ing rate, and adequate air flow is not available, the furnace will shutdown and enter one hour watchguard. For limit re placement remove wires from limit terminals and rotate limit switch 90 degrees. Slowly remove from the vestibule panel.
Primary Limit Location and Heat Exchanger
A 24VAC 2-pin plug and gas control switch are located on the valve. 24V applied to the pins enables valve operation.
Inlet and outlet pressure taps are located on the valve.
LPG change over kits are available from Lennox. Kits include burner orifices and an LP gas valve.
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
The burner box is sealed and operates under a negative pressure. A pressure hose is connected from the burner box to the gas valve. The gas valve senses the pressure in the burner box and uses that to set the maximum manifold pres sure while the pressure switch with pressure conditioning device adjusts the gas flow. This will compensate for differ ent vent configurations which can greatly affect the rate of the unit.
install limit face down
FIGURE 15
7. Gas Valve (GV1)
The SLP98DFV uses a variable capacity gas valve (figure
46) and is applicable for two-stage, three-stage or variable capacity settings. See “Thermostat selection modes” in the integrated control section (section A- subsection 4.) for more details The valve is internally redundant to assure safety shut-off. If the gas valve must be replaced, the same type valve must be used.
NEGATIVE AIR
PRESSURE PORT
INLET
SUPPLY
PRESSURE
TAP
GAS VALVE SHOWN IN THE ON POSITION
GAS VALVE
POSITIVE AIR
PRESSURE PORT
OUTLET
MANIFOLD
PRESSURE TAP
FIGURE 16
Page 29
Page 30
8. Combustion Air Inducer (B6) & Pressure Switch (S18)
All SLP98DFV units are equipped with a combustion air in ducer (B6) and dual pressure switch assembly (high fire and low fire). The pressure switch (figure 17) serves four func tions. First it establishes calibration points for the vent cal ibration routine. The combustion air inducer's speed at a giv en firing rate is a function of the vent system resistance. The calibration routine establishes the inducer speed required to make low and high fire switches for a given vent pipe installa tion and interpolates the speeds required to achieve all inter mediate rates between these two points. The setting for low­fire switch on the assembly is such that it does not normally enter into the vent calibration routine.
Second, the switch proves combustion air inducer operation by sensing a vacuum energizing the control circuit and allow ing ignition. The low fire pressure switch provides this func tion. Third, the switch interrupts the combustion process in the event vent outlet or combustion air intake blockage. Finally, the switch interrupts the combustion process if the condensate drainage system becomes blocked to the point the condensate level builds up in the cold end header box/ secondary coil or vent system.
If the switch assembly is to be replaced, replace the entire assembly. Individual switch components can not be re placed.
WARNING
The pressure switch is a safety shut-down control in the furnace and must not be jumpered for any rea son other than troubleshooting.
To troubleshoot the pressure switch, add a temporary jumper. The unit will not fire with the switch jumpered. Therefore, the pressure switch must be bypassed after the combustion air in ducer is activated. This will determine if the pressure switch and furnace are operating properly. However, this may not indi cate if the sealed combustion system is operating properly.
Vent Calibration
The vent calibration sequence establishes furnace operat ing parameters in a specific installation. The integrated con trol runs the calibration and may be repeated as necessary to maintain proper furnace operation. Prior to calibration, all duct work (and returns) vent pipe and condensate trap (primed) must be connected.
If calibration is successful the data is stored in memory and will be used to determine furnace operation and maintain parameters during heat call. If calibration is not successful, the integrated control will proceed to a 5 minute delay and signal the appropriate code. After the 5 minute delay the cal ibration will be repeated 4 more times with a 5 minute delay in between. If still unsuccessful after the 4 trials (total 5) the integrated control will go into a 1 hour soft lockout.
Calibration may be initiated by:
S Initial call for heat
S Cycling main power off / on and then call for heat
S Venting conditions change (affecting high and low
pressure switch operation)
S Ramp down low fire switch check failed (calibration will follow next call for heat)
S The service technician (by pressing the push button found on the integrated control until the control cycles through to “Field Test Mode”)
The integrated control will do the following during calibration:
1- Verify both low pressure switch and high pressure switch are open. If either are closed log error and end calibration.
2- Start inducer at a predetermined low RPM (1600). Wait 7.5 seconds.
3- Check low pressure switch, if open, increase RPM by 250, wait 5 seconds. Repeat this step until low pressure switch is closed.
4- Decrease RPM by 50, wait 5 seconds and look for the low pressure switch to open. Repeat this step until it is open.
low fire
Pressure Switch (S18)
FIGURE 17
bracket
high fire
5- Keep this RPM as RPM1.
6- Increase RPM by 1250. Wait 5 seconds.
7- Check high pressure switch, if open, increase RPM by 250, wait 5 seconds. Repeat this step until high pres sure switch is closed.
8- Decrease RPM by 50, check after 5 seconds. Repeat this step until switch is open.
9- Keep this RPM as RPM2.
10- Calibration complete.
NOTE - If after a successful calibration and a heat call is present the integrated control will by-pass the prepurge state and go straight into ignitor warm up.
Page 30
Page 31
After calibration, the integrated control stores the RPM1 and RPM2 values. The low fire (35%) and high fire (100%) RPM points are calculated by adding margin values to the RPM1 and RPM2 values.
The integrated control also initiates a low fire switch check at the end of a normal heating cycle described below. If this check fails the pressure switch calibration will follow on the next call for heat.
1- The inducer runs 15 seconds at the last firing rate before the heat call ended.
2- Inducer runs at 35% firing rate RPM (RPM1 + low pressure switch open RPM margin value).
3- If low pressure switch is open, set flag for calibration on next call for heat. Turn inducer off until next call for heat.
4- If low pressure switch is closed move inducer speed to RPM1. Allow 5 seconds for stabilization.
5- If low pressure switch opens turn off inducer. No fur ther action.
Measuring Pressure Differential
Field Installed
6- If low pressure switch is still closed, decrease induc er speed 1/2 of the low pressure switch open RPM mar gin. Allow 5 seconds to stabilize.
7- If low pressure switch is open turn off inducer. No fur ther action.
8- If low pressure switch is still closed, set flag for cal ibration on next call for heat and turn off inducer.
Measuring pressure differential (Figure 18)
Checks of pressure differential can aid in troubleshooting. Len nox provides a kit (10L34) if necessary. When measuring the pressure differential, readings should be taken at the pressure switch. Lack of differential usually indicates problems in the in take or exhaust piping, but may i n d i cate p roblems in t h e heat exchanger, condensing coil, header boxes, com bustion inducer or other components.
The differential pressure is the difference in pressure mea sured across the cold end header box orifice.
BLACK TUBING
POSITIVE
To Cold End Header Box
RED and BLACK TUBING
or RED TUBING NEGATIVE
Red
1 - Remove thermostat demand and allow unit to cycle off.
2 - Install a tee in the negative (-) line (red and black tubing or red
tubing) and a tee in the positive (+) line (black tubing) running from the pressure switch to the cold end header box.
3 - Install a measuring device with hose from the negative (-)
side of the measuring device to the tee installed in the neg ative (-) line and with hose from the positive (+) side of the measuring device to the tee in the positive (+) line.
NOTE - Both sides of the cold end header box are negative. However the (+) port reads less negative pressure than the (-) port.
Measuring Device
4 - Operate unit and observe measuring device reading.
Readings will change as heat exchanger warms.
a. Take one reading immediately after start‐up. b. Take a second reading after unit has reached steady state (approximately 5 minutes). This will be the pressure differential.
The pressure differential should be greater than those listed in table 20.
5 - Remove thermostat demand and allow to cycle off.
6 - Remove measuring device and tee's. Reinstall combustion
air sensing hoses to the pressure switch.
FIGURE 18
Page 31
Page 32
The CAI is installed on the cold end header box (see figure
16). The cold end header box is a single piece made of
hard plastic. The box has an internal channel where the combustion air inducer creates negative pressure at unit start up. The channel contains an orifice used to regulate flow created by the CAI. The box has pressure taps for the CAI pressure switch hoses.
The pressure switch measures the pressure differential across the CAI orifice (difference in the channel and cold end header box). See table 19 for orifice size per unit. If
replacement is necessary the gaskets used to seal the box to the vestibule panel and the CAI to the box, must also be replaced.
TABLE 19
SLP98DFV Unit
-070-1 / -5
-070-6 / -9
-070-10 and later
-090-1 / -9
-090-10 and later
-110-1 / -9
-110-10 and later
C.A.I. Orifice Size
0.780
0.833
0.775
0.920
0.890
1.030
1.000
TABLE 20
Pressure Switch 0' to 7500'
SLP98DFV Unit
Set Point
High Fire
Set Point
Low Fire
-070
-090
1.00 + 0.05 0.25 + 0.05
-110
*Units over 7500 ft will require a conversion kit. See table 32.
Page 32
Page 33
Combustion Air Inducer / Cold End Header Box / Vent Pipe Assembly
Intake Air Pipe
Exhaust Pipe
Cold End Header Box
Drain Cap
Combustion Air Inducer (CAI)
Exhaust Connector
with Alignment Tabs
Pipe Clamp
Blower Deck Seal
Exhaust Coupling
Exhaust Elbow
Tubing
Clamp
CAI Embossment
FIGURE 19
Page 33
Intake Air Coupling
Page 34
II-icomfort Wi-Fi
G
®
thermostat (if applicable)
In communicating applications the Lennox icomfort Wi-Fi thermostat must be used. In these applications the icomfort Toucht thermostat overrides the DIP switch settings on the
integrated control. Refer to the illustrations provided with the thermostat for installation, set-up and operation.
®
®
thermostat wiring
See figures 20 and 21 for icomfort Wi-Fi in communicating applications.
icomfort Wi-Fi
®
Thermostat with SLP98DFV
and Non-Communicating Outdoor Unit
icomfort Wi-Fi® Thermostat icomfortt-Enabled SLP98DFV Indoor Furnace Non-Communicating Outdoor Air Conditioner
icomfortt­ENABLED
SLP98DFV
OPTIONAL DISCHARGE AIR SENSOR
icomfort Wi-Fi THERMOSTAT
®
FURNACE
OPTIONAL OUTDOOR
AIR SENSOR
NON-COMMUNICATING
OUTDOOR AIR
CONDITIONING UNIT -
1 OR 2 STAGE
icomfort Wi-Fi® Thermostat with SLP98DFV
and icomfort-ENABLED Outdoor Unit
icomfort Wi-Fi® Thermostat icomfortt-Enabled SLP98DFV Indoor Furnace icomfortt-Enabled Outdoor Air Conditioner or Heat Pump
icomfortt-
ENABLED SLP98DFV FURNACE
OPTIONAL
DISCHARGE
AIR SENSOR
OPTIONAL OUTDOOR
AIR SENSOR
icomfort Wi-Fi THERMOSTAT
®
icomfortt- ENABLED
OUTDOOR AIR CONDITIONIN
OR HEAT PUMP UNIT
CLIP Y1 TO Y2 FOR
TWO-STAGE OPERATION
Outdoor Unit
Indoor Unit Controller
Single wire to terminal C
Unused wires
Single wire to terminal C
Unused wires
IcomfortWi-Fi thermostat
Communicating systems using the IcomfortWi-Fi® thermostat require four ther mostat wires between the thermostat and the furnace/air handler control and four wires between the outdoor unit and the furnace/air handler control. When a ther mostat cable with more than four wires is used, the extra wires must be properly connected to avoid electrical noise. The wires must not be left disconnected.
Use wire nuts to bundle the four unused wires at each end of the cable. A single wire should then be connected to the indoor unit end of the wire bundle and attached to the “C” terminals as shown in the diagram above.
FIGURE 20
®
Page 34
Page 35
Optional Accessories for use with any icomfort Touch System
DISCHARGE AIR SENSOR
icomfort Toucht
THERMOSTAT
NOTE: 24V UV LIGHT APPLICATIONS
Furnace transformer will not have ad equate va to power 24v UV light ap plications. An additional transformer for UV light applications is required.
icomfortt­ENABLED
SLP98DFV
FURNACE
NOTE: icomfortt THERMOSTAT SENSES HUMIDITY & CONTROLS 24V “H” OUTPUT (& 120V “H” OUTPUT) TO CYCLE HUMIDIFIER BASED ON DEMAND. NO OTHER CONTROL OR HUMIDISTAT REQUIRED.
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH HU MIDIFIER (IF NOT ALREADY IN THE SYSTEM FOR OTHER FUNCTIONS. BUILT INTO ALL icomfortt OUTDOOR UNITS).
icomfortt­ENABLED
SLP98DFV
FURNACE
icomfortt-
ENABLED SLP98DFV FURNACE
HEPA BYPASS FILTER
X2680 HEPA
INTERLOCK KIT
LVCS VENTILATION CONTROL SYSTEM
SEE LVCS VENTILATION INSTRUCTIONS FOR DAMPER & SENSOR WIRING
PASS INDOOR BLOWER MOTOR COMMON WIRE THROUGH CURRENT LOOP.
SEE HEPA INTERLOCK KIT FOR INSTALLATION DE TAILS
icomfortt-
ENABLED SLP98DFV FURNACE
icomfortt­ENABLED
SLP98DFV
FURNACE
(C)
icomfortt- ENABLED
OUTDOOR AIR
CONDITIONING OR
HEAT PUMP UNIT
NON-COMMUNICATING
1 OR 2 STAGE AC OR HP UNIT
(C)
(disables out
door unit only)
FIGURE 21
Page 35
Page 36
III-PLACEMENT AND INSTALLATION
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri can Society for Testing and Materials (ANSI/ASTM) stan dards. The solvent shall be free-flowing and contain no lumps, undissolved particles or any foreign matter that ad versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica tion, or separation that cannot be removed by stirring. Re fer to table 21 for approved piping and fitting materials.
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADIAN PIPE, FITTINGS &
SOLVENT CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM ULC-S636 PolyPro® by Duravent ULC-S636 InnoFlue® by Centrotherm ULC-S636
TABLE 21
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3138
MARKING
ULCS636
CAUTION
Solvent cements for plastic pipe are flammable liq uids and should be kept away from all sources of igni tion. Do not use excessive amounts of solvent ce ment when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
IMPORTANT
SLP98DFV exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when us ing PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 21. As an alter nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi als. Use transition solvent cement when bonding ABS to ei ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni formly apply a liberal coat of PVC primer for PVC
Canadian Applications Only - Pipe, fittings, primer and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (exhaust) sys tem. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 22 lists the available exhaust termination kits.
Page 36
Page 37
OUTDOOR TERMINATION KITS USAGE*
TABLE 22
STANDARD KITS CONCENTRIC KITS
Flush
Vent
Input Size
070
090
110
* Kits must be properly installed according to kit instructions. NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calcula
tions. See vent length tables.
1
Requires field-provided outdoor 1-1/2” exhaust accelerator.
2
Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3
Flush mount kits 51W11 and 51W12 include 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4
Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.
5
See table 27 for vent accelerator requirements.
Pipe
Dia. in.
2
2-1/2
3
2
2-1/2
3
2 YES YES YES
2-1/2 YES YES
3 YES YES
Mount
Kit
51W11
(US)
51W12
(CA)
3
YES YES
3
YES YES
3
YES YES
3
YES YES YES
3
YES YES YES
3
YES YES YES
2 inch 3 inch 2 inch
22G44 (US)
4
30G28 (CA)
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
NOTE - A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.
Wall Kit Wall Ring Kit
44J40
(US)
4
81J20 (CA)
1
YES
1
YES
1
YES
15F74
1
YES
1
YES
1
YES
5 - Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket sur face of fitting and male end of pipe to depth of fitting socket.
6 - Promptly apply solvent cement to end of pipe and in
side socket surface of fitting. Cement should be ap plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second
1-1/2 inch 2 inch 3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
coat to end of pipe.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
NOTE - Time is critical at this stage. Do not allow prim er to dry before applying cement.
7 - Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur ing assembly (but not after pipe is fully inserted) to dis
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges or
rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leak ing joint.
3 - Clean and dry surfaces to be joined.
NOTE - Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.
4 - Test fit joint and mark depth of fitting on outside of pipe.
tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE - Assembly should be completed within 20 sec onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indicate a defective assembly due to insufficient solvent.
9 - Handle joints carefully until completely set.
Page 37
Page 38
Venting Practices
Piping Suspension Guidelines
SCHEDULE 40 PVC --
Support every 5 feet.
all other pipe* --
Support every 3 feet.
* See table 21 for allowable pipe.
NOTE - Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24” maximum 3/4” minimum
1. In areas where piping penetrates joists or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2. When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.
Exhaust Piping (Figure 25)
Route piping to outside of structure. Continue with installa tion following instructions given in piping termination sec tion.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti cal discharge through an existing unused stack is re quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
inside outside
Wall
FIGURE 22
REPLACING FURNACE THAT WAS PART OF A
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE (Replaced by SLP98)
If an SLP98 furnace replaces a furnace which was com monly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
COMMON VENT SYSTEM
WATER
HEATER
OPENINGS (To Adjacent
Room)
FIGURE 23
CAUTION
The exhaust vent pipe operates under positive pres sure and must be completely sealed to prevent leak age of combustion products into the living space.
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent Centrotherm manufactured vent pipe and terminations as
®
an option to PVC. When using the PolyPro InnoFlue
®
by Centrotherm venting system the vent pipe re
by DuraVent or
quirements stated in the unit installation instruction – minim um & maximum vent lengths, termination clearances, etc. – apply and must be followed. Follow the instructions provided with PoyPro by DuraVent and InnoFlue trotherm venting system for assembly or if requirements are more restrictive. The PolyPro by Duravent and InnoFlue by Centrotherm venting system must also follow the uninsu lated and unconditioned space criteria listed in table 26.
The SLP98DFV is installed only as a Direct Vent gas cen tral furnace.
NOTE - In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 23 and 24. Count all elbows inside and outside the home. Table 23 lists the minimum vent pipe lengths per mitted. Table 24 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 27.
In some applications which permit the use of several differ ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox' Application Department for assistance in sizing vent pipe in these applications.
®
®
by Cen
and
Page 38
Page 39
MINIMUM VENT PIPE LENGTHS
TABLE 23
SLP98DF
MODEL
070, 090, 110
*Any approved termination may be added to the minimum equivalent length listed.
MIN. EQUIV.
VENT LENGTH
15 ft.*
EXAMPLE
5 ft. plus 2 elbows of 2”, 2-1/2” or
3” diameter pipe
NOTE - It is acceptable to use any pipe size which fits within the guidelines allowed in table 24.
NOTE - The exhaust collar on all models is sized to ac commodate 2” Schedule 40 vent pipe. Contact the Ap plication Department for more information concerning sizing of vent systems which include multiple pipe sizes.
NOTE -
All horizontal runs of exhaust pipe must slope back
toward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm) of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make sure there are no sags or low spots.
Use the following steps to correctly size vent pipe diameter.
Piping Size Process
What is the
furnace capacity?
1
070, 090, 110?
Which style termination
2
being used?
Standard or concentric?
See table 22.
Which needs
3
most elbows?
Intake or
exhaust?
How many elbows? Count all elbows inside
4
and outside house.
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.
Desired pipe size?
5
6
2”, 2-1/2”, 3”
What is the altitude of the furnace installation?
Use table 24 to find max intake or exhaust pipe
7
length. Includes all vent pipe and elbows inside and outside the house.
FIGURE 24
Page 39
Page 40
Maximum Allowable Intake or Exhaust Vent Length in Feet
TABLE 24
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500'
Number Of
90° Elbows
Used
1 91 69 14 140 93 43 162 143 11 8
2 86 64 9 135 88 38 157 138 113 3 81 59 4 76 54 125 78 28 147 128 103 5 71 49 120 73 23 142 123 98 6 66 44 115 68 18 137 118 93 7 61 39 110 63 13 132 113 88 8 56 34 105 58 9 51 29 100 53 122 103 78
10 46 24 95 48 117 98 73
Number Of
90° Elbows
Used
1 66 69 14 115 93 43 137 143 11 8
2 61 64 9 110 88 38 132 138 11 3 3 56 59 4 51 54 100 78 28 122 128 103 5 46 49 95 73 23 117 123 98 6 41 44 90 68 18 112 118 93 7 36 39 85 63 13 107 113 88 8 31 34 80 58 9 26 29 75 53 97 103 78
10 21 24 70 48 92 98 73
Number Of
90° Elbows
Used
1 41 44 2 36 39 85 63 107 113 88 3 31 34 80 58 102 108 83 4 26 29 75 53 97 103 78 5 21 24 70 48 92 98 73 6 16 19 65 43 87 93 68 7 11 14 60 38 82 88 63
8
9 50 28 72 78 53
10 45 23 67 73 48
070 090 110 070 090 11 0 070 090 110
070 090 110 070 090 11 0 070 090 110
070 090 110 070 090 11 0 070 090 110
n/a
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
130 83 33 152 133 108
n/a
127 108 83
n/a
Standard Termination Elevation 4501' - 7500'
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
105 83 33 127 133 108
n/a
102 108 83
n/a
Standard Terminating at Elevation 7501' - 10,000''
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
n/a
n/a
90 68
n/a
55 33 77 83 58
112 118 93
NOTE - Table 23 continued on next page with concentric terminations.
Page 40
Page 41
TABLE 25
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 - 4500'
Number Of
90° Elbows
Used
1 83 67 12 130 89 39 146 139 11 4
2 78 62 7 125 84 34 141 134 109 3 73 57 4 68 52 115 74 24 131 124 99 5 63 47 110 69 19 126 119 94 6 58 42 105 64 14 121 114 89 7 53 37 100 59 8 48 32 95 54 111 104 79 9 43 27 90 49 106 99 74
10 38 22 85 44 101 94 69
Number Of
90° Elbows
Used
1 58 67 12 105 89 39 121 114 114
2 53 62 7 100 84 34 116 109 109 3 48 57 4 43 52 90 74 24 106 99 99 5 38 47 85 69 19 101 94 94 6 33 42 80 64 14 96 89 89 7 28 37 75 59 8 23 32 70 54 86 79 79 9 18 27 65 49 81 74 74
10 13 22 60 44 76 69 69
Number Of
90° Elbows
Used
1 33 42 2 28 37 75 59 91 109 84 3 23 32 70 54 86 104 79 4 18 27 65 49 81 99 74 5 13 22 60 44 76 94 69 6 7 12 50 34 66 84 59
8
9 40 24 56 74 49
10 35 19 51 69 44
070 090 110 070 090 110 070 090 110
070 090 110 070 090 110 070 090 110
070 090 110 070 090 11 0 070 090 110
n/a
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
120 79 29 136 129 104
n/a
n/a
Concentric Termination Elevation 4501' - 7500'
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
95 79 29 111 104 104
n/a
n/a
Concentric Terminating at Elevation 7501' - 10,000''
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
80 64
17 55 39 71 89 64
n/a
n/a
45 29 61 79 54
n/a
116 109 84
91 84 84
96 114 89
Page 41
Page 42
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
TRAP
2”
2”
2”
DO NOT transition from smaller to larger pipe size in horizontal
3”
TRANSITION
*2“
Use only the factory−supplied
trap. Trap can be installed on
either side of cabinet within 5 ft.
of the furnace.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE Exhaust pipe and intake pipe must be the same diameter.
runs of exhaust pipe.
Air Intake
FIGURE 25
TYPICAL AIR INTAKE PIPE CONNECTIONS
2”
2”
2”
Exhaust
TOP VIEW
TRAP
TRANSITION
*2”
*2”
Use only the factory−supplied
trap. Trap can be installed on
either side of cabinet within 5 ft.
of the furnace.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE Intake pipe and exhaust pipe must be the same diameter.
3”
3”
TRANSITION
*2”
Air Intake
FIGURE 26
Exhaust
TOP VIEW
Page 42
Page 43
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap
pliances > 50,000 Btuh (15kw)
C =
Clearance to permanently
* 12”
closed window
D =
Vertical clearance to ventilated soffit
located above the terminal within a
* Equal to or greater than soffit depth
horizontal distance of 2 feet (610mm)
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
supply inlet to building or the com
bustion air inlet to any other ap
pliance
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap
pliances > 50,000 Btuh (15kw)
K =
Clearance to mechanical air sup
ply inlet
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
H
B
Fixed
Closed
A
J
I
M
K
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”
FIGURE 27
Page 43
Page 44
General Guidelines for Vent Terminations
In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the out doors. The SLP98DFV is classified as a direct vent, Cate gory IV gas furnace.
In Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current CSA-B149 Natural Gas and Pro pane Installation Codes in Canada for details.
Position termination according to location given in figure 27. In addition, position termination so it is free from any ob structions and 12” above the average snow accumulation.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating.
NOTE - See table 26 for maximum allowed exhaust pipe length without insulation in unconditioned space during winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2” (13mm) Arma flex or equivalent. In extreme cold climate areas, 3/4” (19mm) Armaflex or equivalent may be necessary. Insula tion must be protected from deterioration. Armaflex with UV protection is permissable. Basements or other en closed areas that are not exposed to the outdoor ambient temperature and are above 32 degrees F (0°C) are to be considered conditioned spaces.
IMPORTANT
Do not use screens or perforated metal in exhaust ter minations. Doing so will cause freeze-ups and may block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
Maximum Allowable Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
TABLE 26
Winter Design Temperatures Modulating High Efficiency Furnace
Winter Design
Temperatures
32 to 21
(0 to -6)
1
°F (°C)
Vent Pipe
Diameter
PVC
070 090 110
2
PP PVC
2 in. 11 9 14 12 18 15
2-1/2 in. 7 N/A 10 N/A 12 N/A
Unit Input Size
2
PP PVC
2
PP
3 in. N/A N/A 6 6 8 8
2 in N/A N/A 6 4 8 6
20 to 1
(-7 to -17)
2-1/2 in. N/A N/A N/A N/A N/A N/A
3 in. N/A N/A N/A N/A N/A N/A
2 in. N/A N/A N/A N/A N/A N/A
0 to -20
(-18 to -29)
2-1/2 in. N/A N/A N/A N/A N/A N/A
3 in. N/A N/A N/A N/A N/A N/A
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP) by Duravent and Centrotherm. NOTE - Concentric terminations are the equivalent of 5' and should be considered when measuring pipe length. NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
maximum allowable intake or exhaust vent length listed in table 24 which ever is less. NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure28.
Page 44
Page 45
Conditioned
Space
Pipe Insulation
Exhaust
Pipe
Conditioned
Space
FIGURE 28
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
NOTE - Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building mate rial, a corrosion-resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the op tional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropri ate sealant. See figure 32.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 29 through 36 show typical termina tions.
1. Intake and exhaust terminations are not required to be in the same pressure zone. You may exit the intake on one side of the structure and the exhaust on another side (figure 30). You may exit the exhaust out the roof and the intake out the side of the structure (figure 31).
2. Intake and exhaust pipes should be placed as close to gether as possible at termination end (refer to illustra tions). Maximum separation is 3” (76mm) on roof ter minations and 6” (152mm) on side wall terminations.
Intake
Unconditioned
Space
Pipe
NOTE - When venting in different pressure zones, the maximum separation requirement of intake and ex haust pipe DOES NOT apply.
3. On roof terminations, the intake piping should termi nate straight down using two 90° elbows (See figure
29).
4. Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust pip ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 27.
NOTE - Care must be taken to avoid recirculation of ex haust back into intake pipe.
TABLE 27
EXHAUST PIPE TERMINATION SIZE REDUCTION
SLP98DFV
MODEL
*070 2”, 2-1/2” or 3” 1-1/2” *090 2”, 2-1/2” or 3” 2”
110 2”, 2-1/2” or 3” 2”
Exhaust Pipe Size Termination Pipe Size
*SLP98DF -070 and -090 units with the flush-mount termina tion must use the 1-1/2” accelerator supplied with the kit.
5. On field-supplied terminations for side wall exit, ex haust piping may extend a maximum of 12 inches (305mm) for 2” PVC and 20 inches (508mm) for 3” (76mm) PVC beyond the outside wall. Intake piping should be as short as possible. See figure 32.
Page 45
Page 46
6. On field-supplied terminations, a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow. See figure 32.
Inches(mm)
8” (203mm) MIN
12” (305mm) ABOVE
AVERAGE SNOW ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
3”(76mm) MAX.
(15F75 or 44J41)
SIZE TERMINATION
PIPE PER TABLE 27.
UNCONDITIONED
ATTIC SPACE
1/2” (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
FIGURE 29
Exiting Exhaust and Intake Vent
(different pressure zones)
Exiting Exhaust and Intake Vent
(different pressure zones)
Roof T
erminated
Exhaust Pipe
Inlet Air
Furnace
(Minimum 12 in. 305 MM) above
grade or snow
accumulation
FIGURE 31
7. If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob
structions, piping must be supported. At least one
bracket must be used within 6” from the top of the el
bow and then every 24” (610mm) as shown in figure
32, to prevent any movement in any direction. When
exhaust and intake piping must be run up an outside
wall, the exhaust piping must be terminated with pipe
sized per table 27.The intake piping may be equipped
with a 90° elbow turndown. Using turndown will add 5
feet (1.5m) to the equivalent length of the pipe.
Exhaust
Pipe
Furnace
FIGURE 30
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
8. Based on the recommendation of the manufacturer, a
multiple-furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 34.
Page 46
Page 47
NOTE FIELDPROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
C1
REDUCER MAY BE
TO TERMINATION
C1
A
E
D
B
STRAIGHT
APPPLICATION
D
B
A
EXTENDED
APPLICATION
FIELD FABRICATED WALL TERMINATION
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
D
B
See venting table 24 for maximum venting lengths with this arrangement.
* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than 24” (610 mm) but less than 48” (1219 mm). NOTE One wall support must be within 6” (152 mm) from top of each pipe (intake and exhaust) to prevent movement in any direction.
Intake Elbow
C2
D
B
C2
A
E
A
2” (51mm)
Vent Pipe
12” (305 mm)
12” (305 mm)
6” (152 mm)
3” (76mm)
Vent Pipe
12” (305 mm)
6” (152 mm)6” (152 mm)
8” (203 mm)8” (203 mm)
6” (152 mm)6” (152 mm)
20” (508 mm)
6” (152 mm)
ALTERNATE TERMINATIONS (TEE & FORTYFIVE DEGREE ELBOWS ONLY)
2” (51MM)
B
D
1
C
2
A
D
E
B
C
2
A
1
12”
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
3
B
C
Intake Elbow
Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
termination is used and flue gases will impinge on the building materials, a corrosionresistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant. Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
A
Front View of
Intake and Exhaust
Intake
Exhaust
D
3
Exhaust
A− Clearance above
grade or average snow
accumulation
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
D Exhaust pipe length
E Wall support distance
from top of each pipe
(intake/exhaust)
Vent Pipe
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 16” (405 mm) Max.
6” (152 mm) Max.
3” (76MM)
Vent Pipe
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 20” (508 mm) Max.
6” (152 mm) Max.
FIGURE 32
Page 47
Page 48
FIELD-PROVIDED
REDUCER MAY BE RE
QUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION.
EXHAUST
AIR
INTAKE
AIR
(Not Furnished)
OUTSIDE
WALL
CLAMP
1-1/2” (38mm) accelerator
provided on 71M80 &
44W92 kits for
SL98DF070V36B
INTAKE
AIR
INTAKE
AIR
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 33
EXHAUST
AIR
12” (305mm) Min.
above grade or
average snow
accumulation.
GRADE
12” (305mm)
Minimum
Above Average
Snow
Accumulation
CLAMP
1-1/2” (38mm) accelerator
provided on 71M80 &
44W92 kits for
SLP98DFV-36B-070
INTAKE
FLASHING
(Not Furnished)
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
VENT
5”
(127mm)
5-1/2”
(140mm)
12”
(305mm)
INTAKE
AIR
18” MAX.
(457mm)
Front View
EXHAUST VENT
12” (305mm) Min.
above grade or
Inches (mm)
INTAKE
average snow ac
cumulation.
AIR
optional intake elbow
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 34
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
FIGURE 35
2” EXTENSION FOR 2” PVC PIPE 1” EXTENSION FOR 3” PVC PIPE
FURNACE
INTAKE
PIPE
FLUSH-MOUNT SIDE WALL TERMINATION KIT
4''
51W11 (US) or 51W12 (Canada)
FURNACE EXHAUST
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
1-1/2” ACCELERATOR (all -070 and -090 units)
FIGURE 36
Page 48
Page 49
SLP98 DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
3” - 8”
8” - 12”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
*SIZE TERMINATION PIPE PER TABLE 27.
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus trated. In any exterior portion of chimney, the exhaust vent must be insulated.
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE TO FORM
SEAL
(76mm­203mm)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2” (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8” (76mm­203mm)
ALTERNATE INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 37
Condensate Piping
This unit is designed for either right‐ or left‐side exit of con densate piping. Refer to figures 38 and 40 for condensate trap locations.
CONDENSATE TRAP AND PLUG LOCATION
(shown with left side exit of condensation)
2 - For furnaces with a 1/2” drain connection use a 3/8 allen
wrench and remove plug (figure 38) from the cold end header box at the appropriate location on the side of the unit. Install field-provided 1/2 NPT male fitting into cold end header box. For furnaces with a 3/4” drain connec tion use a large flat head screw driver or a 1/2” drive socket extension and remove plug. Install provided 3/4 NPT street elbow fitting into cold end header box. Use Teflon tape or appropriate pipe dope.
3 - Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 44 (3/4” drain connection) or 45 (1/2” drain connection).
4 - Install drain trap using appropriate PVC fittings, glue all
joints. Glue the provided drain trap as shown in figure 44 or 45. Route the condensate line to an open drain.
5 - Figure 41 shows the furnace and evaporator coil using
a separate drain. If necessary, the condensate line from the furnace and evaporator coil can drain togeth er. See figures 42 and 43. The field provided vent must be a minimum 1” to a maximum 2” length above the condensate drain outlet connection.
NOTE - If necessary the condensate trap may be installed up to 5 feet away from the furnace. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.
NOTE - Appropriately sized tubing and barbed fitting may be used for condensate drain. Attach to the drain on the trap using a hose clamp. See figure 39.
1-1/2 in.
Trap
(same other right side)
Plug
(same on left side)
FIGURE 38
1 - Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length of PVC pipe required to reach available drain.
Field Provided Drain Components
Elbow
Barbed Fitting
Tubing
Hose Clamp
FIGURE 39
6 - If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start-Up section.
Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heat cable kit is avail able from Lennox in various lengths; 6 ft. (1.8m) - kit no. 26K68 and 24 ft. (7.3m) - kit no. 26K69.
Page 49
Page 50
CONDENSATE TRAP LOCATION
(shown with right side exit of condensation)
Trap can be installed a maximum of 5ft. from furnace (*PVC only)
Field Provided Vent
1” min. 2” max. above
condensate drain.
1” min.
2” max.
5’ max.
to drain
*Piping from furnace must slope down a
minimum 1/4” per ft. toward trap
FIGURE 40
SLP98DFV with Evaporator Coil Using a Common Drain
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate Drain
Connection
Evaporator Drain Line
(vent required)
FIGURE 42
SLP98DFV with Evaporator Coil
Using a Separate Drain
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate Drain
Connection
Evaporator Drain Line
(vent required)
FIGURE 41
IMPORTANT
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in order for the furnace pressure switch to operate properly.
Drain
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
Optional
Field Provided Vent
1” min. 2” max. above
condensate drain.
FurnaceCondensate
Drain
Connection
FIGURE 43
CAUTION
Do not use copper tubing or existing copper con densate lines for drain line.
Page 50
Page 51
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
COLD END HEADER BOX WITH 3/4” DRAIN CONNECTION
Optional Condensate Drain Connection
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow 3/4 inch PVC (not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow 3/4 inch PVC ( furnished)
To
Trap
Optional Drain Piping FromTrap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
Elbow 3/4 inch PVC
90°
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
V
ent
5 Feet
Maximum
3/4 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
(Not Furnished)
Drain Trap
Assembly
(Furnished)
Condensate Drain
Connection In Unit
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
DrainTrap Assembly
(Furnished)
7
(178)
Drain Trap Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
T
o
Coupling 3/4 inch slip X slip
Drain
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain
Connection In Unit
To
Drain
DrainTrap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain Connection In Unit
To
Drain
FIGURE 44
Page 51
Page 52
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
COLD END HEADER BOX WITH 1/2” DRAIN CONNECTION
Optional Condensate Drain Connection
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
90° Street Elbow
1/2 inch PVC
(Not Furnished)
Condensate Drain
Connection In Unit
90° Street Elbow
1/2 inch PVC
(Furnished)
To
Trap
Optional Drain Piping From Trap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
90° Elbow 1/2 inch PVC
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Vent
5 Feet
Maximum
1/2 inch PVC Pipe
(Not Furnished)
Coupling 1/2 inch slip X slip
(Not Furnished)
Drain Trap
Assembly
(Furnished)
Condensate Drain
Connection In Unit
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
Drain Trap Assembly
(Furnished)
7
(178)
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Coupling 3/4 inch slip X slip
Drain
Drain Trap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain Connection In Unit
To
Drain
Drain Trap Clean Out
Drain Trap Assembly with 3/4 inch Piping
Drain Trap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain
Connection In Unit
To
Drain
FIGURE 45
Page 52
Page 53
IV-START‐UP
A-Preliminary and Seasonal Checks
1 - Inspect electrical wiring, both field and factory installed for
loose connections. Tighten as required.
2 - Check voltage at disconnect switch. Voltage must be
within range listed on the nameplate. If not, consult the power company and have voltage condition corrected before starting unit.
B-Heating Start‐Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwa ter. A flood-damaged furnace is extremely danger ous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified service tech nician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
BEFORE PLACING THE UNIT INTO OPERATION, the
unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
The gas valve on the SLP98DFV is equipped with a gas control switch. Use only your hand to move the control switch. Never use tools. If the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
SLP98DFV units are equipped with an automatic ignition system. Do not furnace. Each time the thermostat calls for heat, the burn ers will automatically light. The ignitor does not get hot when there is no call for heat on units with this ignition sys tem.
attempt to manually light burners on this
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
CAUTION
Before attempting to perform any service or mainte nance, turn the electrical power to unit OFF at discon nect switch.
Priming Condensate Trap
The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:
1 - Follow the lighting instructions to place the unit into op
eration.
2 - Set the thermostat to initiate a heating demand.
3 - Allow the burners to fire for approximately 3 minutes.
4 - Adjust the thermostat to deactivate the heating de
mand.
5 - Wait for the combustion air inducer to stop. Set the ther
mostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.
6 - Adjust the thermostat to deactivate the heating demand
and again wait for the combustion air inducer to stop. At this point, the trap should be primed with sufficient wa ter to ensure proper condensate drain operation.
Gas Valve Operation (Figure 46)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit. 4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the burners by hand.
5 - Remove the upper access panel. 6 - Move the gas valve switch to the OFF position. See
figure 46.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instruc tions. If you do not smell gas go to next step.
NEGATIVE AIR
PRESSURE PORT
INLET
SUPPLY
PRESSURE
TAP
GAS VALVE SHOWN IN THE ON POSITION
FIGURE 46
8 - Move gas valve switch to the ON position. See figure 46.
Do not force.
9 - Replace the upper access panel.
POSITIVE AIR
PRESSURE PORT
OUTLET
MANIFOLD
PRESSURE TAP
Page 53
Page 54
10- Turn on all electrical power to to the unit.
11- Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service techni cian or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the upper access panel. 4 - Move the gas valve switch to the OFF position. 5 - Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following: 1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse? 5 - Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut‐off valve open? 8 - Is the gas valve turned on? 9 - Is the unit ignition system in lock out? If the unit locks out
again, inspect the unit for blockages. 10 - Is blower harness connected to integrated control? Fur
nace will not operate unless harness is connected.
C-Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D-Extended Period Shutdown
Turn off thermostat or set to “UNOCCUPIED” mode. Close all gas valves (both internal and external to unit) to guaran tee no gas leak into combustion chamber. Turn off power to unit. All access panels and covers must be in place and se cured.
V-HEATING SYSTEM SERVICE CHECKS
A-CSA Certification
All units are CSA design certified without modifications. Re fer to the SLP98DFV Installation Instruction.
B-Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.
WARNING
Do not over torque (800 in-lbs) or under torque (350 in-lbs) when attaching the gas piping to the gas valve.
Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefied petroleum gases.
C-Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off the main shut‐off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
When pressure testing gas lines, the gas valve must be dis connected and isolated. Gas valves can be damaged if sub jected to more than 0.5psig (14” W.C.). See figure 47.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8” N.P.T. PLUGGED TAP
CAP
FIGURE 47
When checking piping connections for gas leaks, use pre ferred means. Kitchen detergents can cause harmful corro sion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is available through Lennox under part number 31B2001. See Corp. 8411-L10, for further details.
Do not use matches, candles, flame or any other source of ignition to check for gas leaks.
D- Proper Gas Flow (Approximate)
TABLE 28
GAS METER CLOCKING CHART
Seconds for One Revolution
SLP98
Unit
-70 55 110 136 272
-90 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Natural LP
1 cu ft
Dial
2 cu ft
Dial
FURNACE
ISOLATE
GAS VALVE
1 cu ft
Dial
2 cu ft
DIAL
Page 54
Page 55
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in
table 28. If manifold pressure matches table 33 and rate is
incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
E-Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
supply pressure tap on the gas valve. See figure 46. Check
gas line pressure with unit firing at maximum rate. Low pres
sure may result in erratic operation or underfire. High pres
sure can result in permanent damage to gas valve or over
fire. See table 29 for operating pressure at unit gas connec
tion (line).
On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pres
sure must fall within range listed in table 29.
TABLE 29
All SLP98DFV Units
Line Pressure WC” 4.5 - 10.5 11.0 - 13.0
Manifold Pressure Measurement (Figure 48)
To correctly measure manifold pressure, the differential
pressure between the positive gas manifold and the nega
tive burner box must be considered. Use pressure test
adapter kit (available as Lennox part 10L34) to assist in
measurement.
1 - Remove the threaded plug from the outlet side of the
gas valve and install a field-provided barbed fitting. Connect measuring device “+” connection to barbed fitting to measure manifold pressure.
2 - Tee into the gas valve regulator vent hose and connect
measuring device “-” connection.
3 - Start unit on low heat (35% rate) and allow 5 minutes
for unit to reach steady state.
Natural LP
4 - While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue.
5 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
33.
6 - Repeat steps 3, 4 and 5 on high heat.
7 - Shut unit off and remove manometer as soon as an ac
curate reading has been obtained. Take care to re move barbed fitting and replace threaded plug.
8 - Start unit and perform leak check. Seal leaks if found.
Operating Pressure Signal (Delta P) Measurement (Figure 49)
Operating pressure signal can be taken while the manifold pressure pressure check is taken (using two measuring de vices). Or, taken after the manifold pressure measurement is complete.
1 - Tee into the negative line between the gas valve and
pressure switch and connect to measuring device neg ative “-”.
2 - Tee into the positive line between the gas valve and
pressure switch and connect to measuring device posi tive “+”.
3 - Start unit on low heat (35% rate) and allow 5 minutes
for unit to reach steady state.
4 - After allowing unit to stabilize for 5 minutes, record op
erating pressure signal and compare to value given in table 33.
5 - Repeat steps 3 on 4 high heat.
CAUTION
Do not attempt to make adjustments to the gas valve.
Page 55
Page 56
Manifold Pressure Measurement
Gas Valve
Field Installed
FIGURE 48
Operating Signal (Delta P) Measurement
Red and Black Tubing or Red Tubing -
Field Installed
FIGURE 49
F- Proper Combustion
Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com bustion. Take combustion sample beyond the flue outlet and compare to the tables below.
Negative Port
Positive Port
Black Tubing +
Gas Valve
Measuring Device
TABLE 30
High Fire
SLP98DFV Unit
CO2%
For Nat
CO2%
070
090
6.5 - 9.0 7.7 - 10.2
110
The maximum carbon monoxide reading should not exceed 100 ppm.
For L.P.
Page 56
Page 57
TABLE 31
Low Fire
SLP98DFV Unit
CO2%
For Nat
CO2%
For L.P.
070
090
4.7 - 7.2 5.7 - 8.2
110
The maximum carbon monoxide reading should not exceed 100 ppm.
Manifold and Operating Signal Pressures in inches 0 - 7500 ft (0 - 2286 m)
G- High Altitude
NOTE - In Canada, certification for installations at eleva tions over 4500 feet (1372 m) is the jurisdiction of local au thorities.
SLP98DFV units require no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048m) above sea level. However, units installed at altitude of 7,501 to 10,000 feet (2287 to 3048m) require a pressure switch change per table 32. Table 32 also lists conversion kit re quirements at all altitudes.
The combustion air pressure switch is factory-set and re quires no adjustment.
TABLE 33
Model
Input
Size
-070
-090
-110
TABLE 32
Conversion Kit Requirements
LP/Propane
Kit
0 - 10,000
(0 - 3048 m)
65W77 Not required 14T67
High Altitude Pressure Switch Kit
0 - 7,500
(0 - 2286 m)
7,501 - 10,000
(2287 - 3048m)
SLP98
Manifold Pressure Nat Gas Manifold Pressure LP/Propane
Operating Pressure Signal
(Delta P)
Firing Rate
Min Max Min Max Min Max
Low 0.4 0.95 1.2 2.8 0.20 0.40
High 3.0 3.8 9.1 10.5 0.95 1.25
NOTE - The values given in table are measurements only. The gas valve should NOT be adjusted.
NOTE - A natural to LP/propane gas changeover kit (table 32) is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Page 57
Page 58
VI-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat subbase
fan switch. With fan switch in ON position, blower oper
ates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.
3 - Depending on the type of indoor thermostat, blower and
entire unit will be off when the system switch is in OFF
position.
B-Temperature Rise
Temperature rise for SLP98DFV units depends on unit in put, blower speed, blower horsepower and static pressure as marked on the unit rating plate. The blower speed must be set for unit operation within the range of “TEMP. RISE °F” listed on the unit rating plate.
To Measure Temperature Rise:
1 - Place plenum thermometers in the supply and return air
plenums. Locate supply air thermometer in the first hori
zontal run of the plenum where it will not pick up radiant
heat from the heat exchanger.
2 - Set thermostat for heat call. Unit must operate on sec
ond-stage heat. If using a single-stage thermostat fur
nace must fire at least 10 minutes before switching to
second-stage heat.
3 - After plenum thermometers have reached their highest
and steadiest readings, subtract the two readings. The
difference should be in the range listed on the unit rating
plate. If the temperature is too low, decrease blower
speed. If temperature is too high, first check the firing
rate. Provided the firing rate is acceptable, increase
blower speed to reduce temperature.
C-External Static Pressure
1 - Tap locations shown in figure 50.
2 - Punch a 1/4” diameter hole in
supply and return air ple
nums. Insert manometer
hose flush with inside edge of
hole or insulation. Seal
around the hose with perma
gum. Connect the zero end of
the manometer to the dis
charge (supply) side of the system. On ducted systems,
connect the other end of manometer to the return duct
as above.
3 - With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blower
motor speed to deliver the air desired according to the
job requirements.
4 - External static pressure drop must not be more than
0.8” W.C. in the heating mode and must not exceed 1.0”
W.C in the cooling mode.
5 - Seal the hole when the check is complete.
STATIC PRESSURE TEST
filter
coil
FIGURE 50
VII-MAINTENANCE
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or prop erty damage. Improper servicing could result in dangerous opera tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Filters
All SLP98DFV filters are installed external to the unit. Fil ters should be inspected monthly. Clean or replace the fil ters when necessary to ensure proper furnace operation. All SLP98DFV units use a 16 x 25 x1 filter.
IMPORTANT
If a highefficiency filter is being installed as part of this system to ensure better indoor air quality, the fil ter must be properly sized. Highefficiency filters have a higher static pressure drop than standardeffi ciency glass/foam filters. If the pressure drop is too great, system capacity and performance may be re duced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.
Before using any filter with this system, check the specifications provided by the filter manufacturer against the data given in the appropriate Lennox Product Specifications bulletin. Additional informa tion is provided in Service and Application Note ACC002 (August 2000).
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.
Page 58
Page 59
NOTE - After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product may result in a fire, causing property damage, severe injury or death. Use copper wire only with this product.
CAUTION
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specifications bulletin (EHB) and unit rating plate.
1 - Check all wiring for loose connections. 2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 - Turn off power to the unit.
2 - Have a shallow pan ready to empty condensate water.
3 - Remove the drain plug from the condensate trap and
empty water. Inspect the trap then reinstall the drain plug and refill trap with water.
Condensate Hose Screen (Figure 51)
Check the condensate hose screen for blockage and clean
if necessary.
1 - Turn off power to the unit. 2 - Remove hose from cold end header box. Twist and pull
screen to remove. 3 - Inspect screen and rinse with tap water if needed. 4 - Reinstall screen and turn on power to unit.
Condensate Hose Screen
Hose
FIGURE 51
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem bling unit. Use papers or protective covering in front of fur nace while removing heat exchanger assembly.
1 - Turn off electrical and gas supplies to the furnace. 2 - Remove the furnace access panels. 3 - Disconnect the 2-pin plug from the gas valve. 4 - Remove gas supply line connected to gas valve. Re
move the burner box cover and remove gas valve/ manifold assembly.
5 - Remove sensor wire from sensor. Disconnect 2‐pin
plug from the ignitor. 6 - Disconnect wires from flame roll-out switches. 7 - Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE - If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
8 - Loosen the clamps to the flexible exhaust coupling. 9 - Disconnect condensate drain line from the cold end
header box. 10 - Disconnect condensate drain tubing from flue collar.
Remove screws that secures the flue collar into place.
Remove flue collar. It may be necessary to cut the exit
ing exhaust pipe for removal of the fitting. 11 - Mark and disconnect all combustion air pressure tub
ing from cold end header collector box. 12 - Mark and remove wires from pressure switches. Re
move pressure switches. Keep tubing attached to
pressure switches. 13 - Disconnect the 4‐pin plug from the combustion air in
ducer. Remove two screws which secure combustion
air inducer to collector box. Remove combustion air in
ducer assembly. Remove ground wire from vest panel. 14 - Remove electrical junction box from the side of the fur
nace. 15 - Remove cold end header box. 16 - Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck. 17 - Remove the primary limit from the vestibule panel. 18 - Remove two screws from the front cabinet flange at the
blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger. 19 - Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as
sembly to cabinet. Remove two screws from blower rail
which secure bottom heat exchanger flange. Remove
heat exchanger from furnace cabinet. 20 - Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
21 - Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire as
sembly.
Page 59
Page 60
22 - Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are resting on the support located at the rear of the cabinet. Remove the indoor blower to view this area through the blower opening.
23 - Re‐secure the supporting screws along the vestibule
sides and bottom to the cabinet. 24 - Reinstall cabinet screws on front flange at blower deck. 25 - Reinstall the primary limit on the vestibule panel. 26 - Route heating component wiring through hole in blow
er deck and reinsert strain relief bushing. 27 - Reinstall electrical junction box. 28 - Reinstall the cold end header box. 29 - Reinstall the combustion air inducer. Reconnect the
4-pin plug to the wire harness. 30 - Reinstall pressure switches and reconnect pressure
switch wiring. 31 - Carefully connect combustion air pressure switch
hosing from pressure switches to proper stubs on
cold end header collector box. 32 - Reinstall condensate trap. 33 - Use securing screws to reinstall flue collar to the top
cap on the furnace. Reconnect exhaust piping and ex
haust drain tubing. 34 - Replace flexible exhaust adapter tee on combustion air
inducer and flue collar. Secure using two existing hose
clamps. 35 - Reinstall burner box assembly in vestibule area. 36 - Reconnect flame roll-out switch wires. 37 - Reconnect sensor wire and reconnect 2-pin plug from
ignitor. 38 - Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
39 - Reinstall gas valve manifold assembly. Reconnect gas
supply line to gas valve. 40 - Reinstall burner box cover. 41 - Reconnect 2-pin plug to gas valve.
42 - Replace the blower compartment access panel. 43 - Refer to instruction on verifying gas and electrical con
nections when re-establishing supplies.
44 - Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly.
45 - Replace heating compartment access panel.
Cleaning the Burner Assembly
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels. 2 - Disconnect the 2-pin plug from the gas valve. 3 - Remove the burner box cover. 4 - Disconnect the gas supply line from the gas valve. Re
move gas valve/manifold assembly. 5 - Mark and disconnect sensor wire from the sensor. Dis
connect 2‐pin plug from the ignitor at the burner box. 6 - Remove four screws which secure burner box assem
bly to vest panel. Remove burner box from the unit. 7 - Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block
age caused by foreign matter. Remove any blockage. 8 - Reconnect the sensor wire and reconnect the 2-pin
plug to the ignitor wiring harness. 9 - Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports. 10 - Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn
er box cover. 11 - Reconnect 2-pin plug to gas valve. 12 - Replace the blower compartment access panel. 13 - Refer to instruction on verifying gas and electrical con
nections when re-establishing supplies. 14 - Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean
and dry and that furnace is operating properly. 15 - Replace heating compartment access panel.
Page 60
Page 61
VIII- Wiring and Sequence of Operation
NOTE - The thermostat selection DIP switch on the control is factory-set in the “TWO-STAGE” position.
Applications Using a Two-Stage Thermostat
A - Heating Sequence -- Control Thermostat Selection DIP switch in “Variable Capacity” Position
1. On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The inte grated control runs a self‐diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener gized at ignition speed, which is approximately the same as the inducer speed at 70 percent firing rate.
Page 61
2. Once the control receives a signal that the low-fire pressure switch has closed, the combustion air inducer begins a 15-second pre-purge in ignition speed.
3. After the pre-purge is complete, a 20-second initial ig nitor warm-up period begins. The combustion air in ducer continues to operate at the ignition speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized and ignition occurs. At the same time, the control module begins an indoor blower 45-second ON-delay. When the delay ends, the indoor blower mo tor is energized at a speed that matches the firing rate. After the 10-second ignition stabilization delay expires, the inducer speed is adjusted to the
Page 62
appropriate target rate. If the furnace is operating in the initial heating cycle after power-up, the initial firing rate will be approximately 35 percent. The firing rate on subsequent cycles will be automatically adjusted by the integrated control based on thermostat cycles. The firing rate will vary and will range from 40 percent to 90 percent. The furnace will continue this operation as long as the thermostat has a first-stage heating de mand.
5 - If second-stage heat is required, the thermostat sec
ond-stage heat contacts close and send a signal to the integrated control. The integrated control either in creases the firing rate to 70 percent (if the current rate is at or below 60 percent) or increases the firing rate by 10 percent (if the current rate is above 60 percent). If the call for heat continues 5 minutes beyond this initial upstage, the rate will be increased by 10 percent every 5 minutes until the call for heat is satisfied or the furnace reaches 100 percent rate. As the firing rate in creases, the indoor blower motor is adjusted to a speed which is appropriate for the target rate.
6 - If second-stage heat demand is satisfied, but first stage
is still present, the furnace will continue to operate at the present firing rate until the heat cycle ends.
7 - When the demand for first- and second-stage heat is
satisfied, the gas valve is de-energized and the field­selected indoor blower off delay begins. The combus tion air inducer begins a 20-second post-purge period.
8 - When the combustion air post-purge period is com
plete, the inducer is de-energized. The indoor blower is de-energized at the end of the off delay.
Applications Using A Single-Stage Thermostat
B - Heating Sequence -- Control Thermostat Selection DIP switch in “Single-Stage” Position
1. On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The inte grated control runs a self‐diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener gized at the ignition speed, which is approximately the same as the inducer speed at 70 percent firing rate.
2. Once the control receives a signal that the low-fire pressure switch has closed, the combustion air inducer begins a 15-second pre-purge at the ignition speed.
3. After the pre-purge is complete, a 20-second initial ig nitor warm-up period begins. The combustion air in ducer continues to operate at the ignition speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized and ignition occurs, which initiates a 10-second ignition stabilization delay. At the same time, the control module sends a signal to begin an indoor blower 45-second ON-delay. When the delay ends, the indoor blower motor is energized at a speed which is appropriate for the firing rate. After the 10-second igni tion stabilization delay expires, the inducer speed is adjusted to 40 percent speed. The integrated control also initiates a second-stage on delay (factory-set at 7 minutes; adjustable to 12 minutes).
5 - If the heating demand continues beyond the second-
stage on delay, the integrated control energizes the combustion air inducer at 70 percent speed. The in door blower motor is adjusted to a speed which matches the target rate. A fixed, 10-minute third-stage on delay is initiated.
6 - If the heating demand continues beyond the third-
stage on delay, the integrated control energizes the in ducer at high speed. The indoor blower motor is ad justed to a speed which is appropriate for the target rate.
7 -When the thermostat heating demand is satisfied, the
gas valve is de-energized and the combustion air in ducer begins a 20-second post-purge. The field-se lected indoor blower off delay begins.
8 - When the combustion air post-purge period is com
plete, the inducer is de-energized. The indoor blower is de-energized at the end of the off delay.
Applications Using a Two-Stage Thermostat
C - Heating Sequence -- Control Thermostat Selection DIP switch in “Two-Stage” Position (Factory Setting)
1. On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The inte grated control runs a self‐diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener gized at ignition speed, which is approximately the same as the inducer speed at 70 percent firing rate.
2. Once the control receives a signal that the low-fire pressure s begins a 15-second pre-purge at the ignition speed.
3. After the pre-purge is complete, a 20-second initial ig nitor warm-up period begins. The combustion air in ducer continues to operate at the ignition speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 45-second ON-delay. When the delay ends, the indoor blower motor is energized at a speed that matches the firing rate. After the 10-second ignition stabilization delay expires, the inducer speed is ad justed to the appropriate target rate. The inducer will remain at the 70 percent speed as long as the thermo stat has a first-stage heating demand.
5 - If second-stage heat is required, the thermostat sec
ond-stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30-second second-stage recognition delay.
6 - At the end of the recognition delay and on all subse
quent calls for heat in the same heating cycle, the inte grated control energizes the combustion air inducer at high speed. The control also checks the high-fire pres sure switch to make sure it is closed. As the inducer speed is increased to high, the indoor blower motor is adjusted to a speed which is appropriate for the target rate.
7 - When the demand for high-fire (second stage) heat is
satisfied, the gas valve is de-energized and the field­selected indoor blower off delay begins. The combus tion air inducer begins a 20-second post-purge period.
8 - When the combustion air post-purge period is com
plete, the inducer is de-energized. The indoor blower is de-energized at the end of the off delay.
witch has closed, the combustion air inducer
Page 62
Page 63
A - Sequence of Operation and Troubleshooting Flow Chart
IGNITION AND CALL FOR LOW FIRE WITH TWO-STAGE THERMOSTAT
1
Safety Check
Verify There
Is No Main Burner
Flame
Limit
Switch
Closed?
YES
Rollout
Circuit
L I G H T
O F F
Closed?
YES
Low
Pressure
Switch
Open?
YES
NO
NO
NO
DeEnergize
Gas Valve
DeEnergize
Gas Valve
Error Code Flashes
After 5 Seconds
Low Pressure Switch Opens
Combustion Air
(100% rate speed)
Combustion
On (100% rate
Indoor Blower
Inducer On
Air Inducer
speed)
ON (70%)
Pressure
Switch
Open?
YES
Indoor blower OFF
Heat OFF Delay (Low Heat Speed)
Error Code
Error Code
High
Flashes
Flashes
NO
After
Indoor Blower
ON (100%)
NO
Error Code Flashes
After 5 Seconds
High Pressure Switch Opens
Rollout
Circuit
Closes?
YES
Limit
Closes Within 3
Minutes?
YES
Combustion Air
Inducer OFF
After PostPurge
Indoor Blower OFF After
Heat OFF Delay
Hard Lockout:
Error Code
Flashes
flashes
NO
Indoor Blower OFF After Heat OFF Delay (High Heat Speed)
Soft Lockout:
Error Code
Flashes
2
2
1
C A L L
Ignition Trial Begins
F O R
1 S T
S T A G E
H E A T
Combustion Air Inducer
ON at 70% Rate Speed
Pressure Switch
Closed Within 150
Seconds?
PrePurge
15 Seconds
Ignitor ON 20 Seconds
Gas Valve Energized
(Ignitor ON)
Flame
Sensed Within
4 seconds?
Ignitor OFF
Wait For Ignition
Stabilization Delay
Set Target Firing Rate
Based on Thermostat
Signals Present
Low
YES
Indoor Blower Delay
YES
NO
Timer Started
NO
Pressure Switch
Calibration
Gas Valve
Deenergized
Ignitor OFF
Call
For
NO
YES
Calibration
Successful?
Wait
5 minutes
Interpurge
(15 Seconds)
1
2
NO
NO
5th
Unsuccessful
Trial?
SOF T LOCKOU T IS RESE T AUTOMATICALLY AFTER ONE HOUR WITH A CALL FOR HE AT ACTIVE, OR B Y CYCLING THE CAL L FOR HE AT, OR B Y CYCLING POWER TO THE CONTROL.
HARD LOCKOU T IS RESE T B Y CYCLING POWER TO THE CONTROL.
Calibrations
Attempted?
YES
4
NO
PostPurge
(20Seconds)
YES
Soft Lockout:
Error Code
Flashes
Combustion Air
Inducer OFF
Heat?
YES
Soft Lockout:
Error Code
Flashes
Call For
Indoor blower OFF After Heat OFF Delay
1
NO
Heat
Ends?
YES
Indoor
Blower
ON?
YES NO
1
OR
Call For 2nd Stage Heat Call For Heat Satisfied
3A2
Page 63
Page 64
CALL FOR HIGH FIRE WITH TWO-STAGE THERMOSTAT
1
2
2 Stage
Thermostat
1st Call
for High
Fire?
YES
2nd Stage
Recognition Delay
(30 Seconds)
Combustion Air Inducer ON
(100% Rate Speed)
High
Pressure Switch
Closes Within 10 Seconds?
YES
Adjust Indoor
Blower to
Appropiate speed
Wait for Call for Heat Satisfied
3A
NO
NO
Increase Combustion
Air Inducer Speed
if Not at 100%
Rate Speed
Error Code
Flashes
Wait 5
Minutes
1
System will always light at 70% even if 2nd stage call for heat is in place
If the high pressure switch does not close within 5 attempts, the system
2
will operate at low fire for the remainder of the call for heat at request
Page 64
Page 65
CALL FOR HEAT SATISFIED
RUN MODE (2 STAGE THEREMOSTAT) 1ST OR 2ND STAGE CALL FOR HEAT ALL INPUTS MONITORED (LIMIT, PRESSURE, CALL FOR HEAT / COOL, FLAME LEVEL)
2nd Stage Heat
1st Stage Heat
3A 3B
NO
2nd Stage
Call for Heat
satisfied?
YES
Combustion Air Inducer
switched to 70% rate speed
Adjust Indoor Blower
to appropiate speed
NO
RUN MODE (SINGLE STAGE THERMOSTAT) ALL INPUTS MONITORED (LIMIT, PRESSURE, CALL FOR HEAT / COOL, FLAME LEVEL)
1st Stage
Call for Heat
satisfied?
Gas valve
DeEnergized
Combustion Air Inducer OFF
after 20Second Post Purge
Indoor Blower OFF
after OFF Delay
1 4
Wait for Call
2StageThermostat
YES
OR
Wait for Call
Single StageThermostat
Page 65
Page 66
L I G H T
O F F
4
Safety Check
Verify There
Is No Main Burner
Flame
Limit
Switch
Closed?
YES
Rollout
Circuit
Closed?
YES
Low
Pressure
Switch Open?
YES
IGNITION AND CALL FOR LOW FIRE WITH SINGLE-STAGE THERMOSTAT
Indoor Blower OFF After
NO
NO
NO
DeEnergize
Gas Valve
DeEnergize
Gas Valve
Error Code Flashes
After 5 Seconds
Low Pressure Switch Opens
Heat OFF Delay (Low Heat Speed)
Combustion Air
Inducer ON
(100%)
Combustion Air
Inducer ON
(100%)
Indoor Blower
ON
(70%)
High
Pressure
Switch Open?
YES
Error Code
Flashes
Error Code
Flashes
NO
Indoor Blower
ON
(100% Speed)
NO
Error Code Flashes
After 5 Seconds
High Pressure
Switch Opens
YES
Rollout
Circuit
Closes?
Combustion Air Inducer
OFF After PostPurge
Indoor Blower OFF After
Limit
Closes Within 3
Minutes?
YES
Heat OFF Delay
Hard Lockout:
Error Code
Flashes
flashes
NO
Indoor Blower OFF
After Heat OFF Delay
(High Heat Speed)
Soft Lockout:
Error Code
Flashes
2
1
Ignition Trial Begins
C A L L
F O R
H E A T
Combustion Air Inducer ON at
Ignition at 70% rate speed
Low
Pressure Switch
Closed Within 150
Seconds?
YES
PrePurge
15 Seconds
Ignitor ON 20 Seconds
Gas Valve Energized
Ignitor ON
Wait For Ignition
Stabilization Delay
Low Firing Rate
Indoor Blower On
Delay Timer Started
Flame
Sensed Within
4 seconds?
YES
Ignitor OFF
Set to
NO
NO
Pressure Switch
Calibration
Gas Valve
Deenergized
Ignitor OFF
YES
Calibration
Successful?
Wait
5 minutes
Interpurge
(15 Seconds)
Unsuccessful
Call
For
NO
Heat?
4
Calibrations
NO
Attempted?
NO
NO
5th
Trial?
1
SOFT LOCKOUT IS RESE T AUTOMATICALLYAFTER ONE HOUR WITH A CALL FOR HEATACTIVE, OR BY CYCLINGTHE CALL FOR HEAT, OR BY CYCLING POWER TO THE CONTROL.
HARD LOCKOUT IS RESE T BY CYCLING POWER TO THE CONTROL.
2
YES
PostPurge
(20 Seconds)
YES
Soft Lockout:
Error Code
Flashes
Combustion Air
Inducer OFF
YES
Soft Lockout:
Error Code
Flashes
NO
Call For
Heat
Ends?
YES
Indoor
Blower On?
YES NO
Indoor Blower OFF
After Heat OFF Delay
1
1
Move to Mid Firing Rate and High Firing Rate after 2nd and 3rd Stage Delays
(based on DI P Switch selections)
Call For Heat Satisfied
3B
Page 66
Page 67
CALL FOR COOLING
5
1st Stage Cooling Request Received
Energize 1st Stage
Cooling Contactor
(Compressor & Fan)
Indoor Blower On
After 2second delay
Energize Indoor Blower
(Per Ramping Profile)
1
2nd Stage
Cooling
Request?
2
1
YES
1st Stage
NO
Cooling Request
Still Active?
YES
Energize 2nd Stage
Cooling Contactor
(Compressor & Fan)
Cooling Request
DeEnergize 2nd
(Compressor & Fan)
Cooling Request
DeEnergize 1st
(Compressor & Fan)
DeEnergize Indoor Blower
Per Ramping Profile
Energize Indoor Blower
2nd Stage
Still Active?
NO
Stage Cooling
Contactor
1st Stage
Still Active?
NO
Stage Cooling
Contactor
YES
(High Cooling mode)
YES
YES
2
2
Maintain Indoor Blower
(High Cooling mode)
Energize and
Maintain Indoor Blower at
Low Cooling mode
NO
2nd stage cooling operation requires a 2stage thermostat, a 2stage cooling system and jumpers
1
W915 must be be cut. The control will not respond to a 2nd stage cooling request unless a 1st stage cooling request is active
Indoor blower cooling mode and high cooling mode have a specific ON, OFF and speed ramping
2
profiles. The specific profile is selected using the DIP switches on the control.
Page 67
Page 68
CONTINUOUS LOW SPEED INDOOR BLOWER SEQUENCE OF OPERATION
6
Call for
Continuous Blower
Indoor Blower On
(Speed Determined by
Dip Switch settings)
Request for Cooling Received?
NO
Request
for Heat
Received?
NO
Call for Fan
Removed?
YES
DeEnergize
Indoor Blower Per
Ramping Profile
Indoor blower low cooling mode and high cooling mode, have specific ON OFF and speed ramping
1
YES
YES
NO
profiles. The specific profile is selected using the dip switches on the control.
Blower at set speed
Blower at set speed
Blower at set speed
1
Maintain Indoor
Maintain Indoor
Maintain Indoor
Go to Call for Cooling
5
Go to Call for Heat 2 Stage
1
OR
Go to Call for Heat Single Stage
4
Thermostat
Thermostat
Page 68
Page 69
IX- Field Wiring
Thermostat
TABLE 34
Field Wiring for Non-Communicating Thermostat Applications
DIP Switch Settings and On-Board Links (figure 4)
DIP Switch 1
W915
(Y1 to Y2)
Two-Stage
Cooling
W914
(DS to R)
Dehumidifi
cation or
Harmony III
W951
(O to R)
Heat Pumps
Wiring Connections
1Heat / 1 Cool
NOTE - Use DIP switch 3 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
1 Heat / 2 Cool
NOTE - Use DIP switch 3 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
ON Intact Intact Intact
ON Cut Intact Intact
S1
T'STAT
S1
T'STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
*
OUTDOOR
UNIT
*
1 Heat / 2 Cool
ON Cut Cut Intact with t'stat with dehumidification mode
NOTE - Use DIP switch 3 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
* “R” required on some units.
S1
T'STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
*
Page 69
Page 70
TABLE 44
Field Wiring for Non-Communicating Thermostat Applications
DIP Switch Settings and On-Board Links (figure 4)
W914
(DS to R)
Dehumidifi
cation or Harmony
W951
(O to R)
Heat Pumps
Thermostat
DIP Switch 1
W915
(Y1 to Y2)
Two-Stage
Cooling
III
2 Heat / 2 Cool OFF Cut Intact Intact
Wiring Connections
S1
T'STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
*
2 Heat / 2 Cool
OFF Cut Cut Intact with t'stat with dehumidifica tion mode
2 Heat / 1 Cool OFF Intact Intact Intact
S1
T'STAT
S1
T'STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
*
OUTDOOR
UNIT
*
* “R” required on some units.
Page 70
Page 71
Thermostat
Dual Fuel Single Stage Heat Pump
ComfortSense 7000 L7742U thermostat w/ dual fuel capa bilities Capable of 2 stage gas heat control
TABLE 34
Field Wiring for Non-Communicating Thermostat Applications (Continued)
DIP Switch Settings and On-Board Link (figure 4)
W914
DIP Switch
W915
(Y1 to Y2)
Two-Stage
Cooling
(DS to R)
Dehumidifi
cation or
Harmony
W951
(O to R)
Heat Pumps
Wiring Connections
III
DIP Switch 1
OFF
Intact Intact Cut
L7742U T'STAT
H
L
Y2
D
B
CONTROL
TERM. STRIP
HEAT PUMP
67M41*
L
Y
Y2
Dual Fuel Two Stage
DIP Switch 1
OFF
Cut Intact Cut
Heat Pump
ComfortSense 7000 L7742U thermostat w/ dual fuel capa bilities Capable of 2 stage gas heat control
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
T
T
L7742U T'STAT
H
L
Y2
D
B
T
T
CONTROL TERM.
STRIP
67M41*
outdoor
sensor
HEAT PUMP
L
Y2
out blue
outdoor sensor
Page 71
Loading...