Lennox SLO183UFV Installation Instructions Manual

Page 1
INSTALLATION
E2012 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
SLO183UFV SERIES UNITS ARE NOT FOR USE IN ZONING APPLICATIONS!
WARNING
Improper installation, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes­sional installer, or equivalent, or service agency.
WARNING
Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other appliance.
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
INSTRUCTIONS
SLO183UFV Series Units
OIL UNITS
506904−01
04/2012
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
SLO183UFV Unit Dimensions 2. . . . . . . . . . . . . . . . . . .
SLO183UFV Unit Parts Arrangement 3. . . . . . . . . . . .
SLO183UFV Oil Burner Parts Arrangement 3. . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion & Ventilation Air 5. . . . . . . . . . . . . . . . . . . .
Locate & Level the Unit 6. . . . . . . . . . . . . . . . . . . . . . . .
Adjustments 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue Connections 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Air Plenums 10. . . . . . . . . . . . . . . . . . .
Oil Supply Line Sizing 10. . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Supply Line & Filter Connections 11. . . . . . . . . . . . .
Leak Check 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Control 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up & Adjustments 19. . . . . . . . . . . . . . . . . . . .
Service 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Burner Control 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro­fessional technicians, or equivalent, can install and service the Dave Lennox Signaturet Collection SLO183UFV oil furnaces. In Canada, refer to CSA B139 for recommended installation procedures. Consult authorities who have juris­diction before installation.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
Shipping & Packing List
1 − Assembled oil furnace
1 − Barometric draft control
1 − Oil nozzle (used with SLO183UF86, −114 and −150
only)
Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
Litho U.S.A.
04/12
*2P0412*
Page 1
506904−01
*P506904-01*
Page 2
SLO183UFV Unit Dimensions − Inches (mm)
3/4 (19)
3/4 (19)
SIDE FLUE OUTLET
CENTERING HOLE
(Field Fabricate Either Side)
ELECTRICAL INLET
(Right Side Only)
OIL PIPING INLET
(Left Side Only)
OPT. OUTDOOR COMBUSTION
AIR INLET CENTERING HOLE
(Field Fabricate Right Side only)
RETURN AIR OPENING
(Either Side)
1-1/2 (38)
D
C
SUPPLY
AIR
OPENING
TOP VIEW
22
(559)
14
(356)
TOP FLUE OUTLET
FLUE
CONNECTION
(On Heat
Exchanger)
54
(1372)
1-1/2
(38)
23-1/2
(597)
AB
AIR FLOW
2 (51)
1-1/4 (32)
RETURN AIR SIDE VIEW
SLO183UFV Unit Dimensions − Inches (mm)
SLO183UFV Model
68/86V36 101/114V42
135/150V60
A B C D E
19−1/2
(495)
22−1/2
(572)
30−5/8
(778)18(457)
33−1/8
(841)21(533)
19−5/8
(498)16(406)
22−1/8
(562)18(457)
22
(559)
Figure 1
E
RETURN AIR FRONT VIEW
Page 2
Page 3
SLO183UFV Unit Parts Arrangement
FLUE
COLLAR
HEAT
EXCHANGER
CLEAN−
OUT PORT
LIMIT SWITCH
BECKETT
AFG BURNER
CLEAN−
OUT PORT
OBSERVATION
PORT
VARIABLE
SPEED BLOWER
MOTOR
CAPACITORBLOWER CONTROL
INDOOR BLOWER
Figure 2
SLO183UFV AFG Burner Parts Arrangement
MAIN
HEAT
SHIELD
AIR TUBE WITH
ELECTRODE
ASSEMBLY AND
NOZZLE INSIDE
COPPER OIL
TUBE
HOUSING
ESCUTCHEON
PLATE
OIL DELAY
VALV E
FUEL PUMP
Figure 3
AIR BAND AND
AIR SHUTTER
IGNITER
BLOWER WHEEL
WITH AIR GUIDE
(Inside housing)
BURNER CONTROL
(with Reset Button)
BLOWER
MOTOR
Page 3
Page 4
Requirements
Table 1
Combustion Air Opening Dimensions
WARNING
This product contains fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Installation of Lennox oil−fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA−B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recom­mendations of the National Environmental Systems Con­tractors Association and any state or provincial laws or lo­cal ordinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan­dards outlined in section 140 of NFPA No. 31 or, in Cana­da, CSA Standard B139. When installing SLO183UFV units in confined spaces such as utility rooms, two com­bustion air openings are required. Dimensions of combus­tion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6" (152 mm) from the room’s ceiling.
The combustion air opening should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area containing the furnace below the level of the furnace burner.
Model No. (2 openings required)
SLO183UFV−68/86 & 101/114
SLO183UFV−135/150 11" X 22" (279 mm X 559 mm)
This unit is approved for use on combustible flooring and for clearances to combustible material as listed on unit rating plate and in table 2. Unit service and accessibility clearances take precedence over fire protection clearances.
10" X 20" (254 mm X 508 mm)
Table 2
SLO183UFV Installation Clearances
Clearances inches (mm)
top of plenum & duct 2 (51) plenum sides 3 (76) sides 0 (0) rear 0 (0) front 4 (120) flue pipe 6 (152)
NOTE − When service clearances are greater than fire protection clearances, service clearances take prece­dence.
Obtain a temperature rise within the range listed in table 8 in the Start-Up section of this manual.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/ NFPA No. 70, or Canadian Electric Code (CEC) if an exter­nal electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
If installing a programmable thermostat, use a type which retains its memory in event of a power loss.When the fur­nace is used in conjunction with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating element. With a parallel flow arrangement, a damper (or other means to con­trol the flow of air) shall be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit, un­less damper is in the full heat" or cool" position.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 1 or the unit rating plate for specific combustion air opening dimensions.
WARNING
When an air conditioning unit is used in conjunc­tion with the furnace, the evaporator coil must be installed in the discharge (supply) air. Do not install an evaporator coil in the return air; excessive con­densation will occur within the furnace.
Page 4
Page 5
Notice to Home Owner
This furnace is equipped with safety devices that protect you and your property. If one or more of these devices is activated, furnace operation will stop. If your home is left unattended for an extended period of time, equipment op­eration must be checked periodically. If this is not possible, the water supply to the house should be shut off and the pipes should be drained. This will prevent problems associated with a NO HEAT condition (frozen pipes, etc.)
Combustion and Ventilation Air
Homes built with energy conservation in mind use tight construction practices. These houses are sealed so well that it becomes necessary to provide a means of bringing in air from outside for combustion. Also, exhaust fans, ap­pliance vents, chimneys and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the home for combustion, nega­tive pressure (pressure outside is greater than inside pres­sure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation. Ne­gative pressure may also interfere with proper combus­tion, causing sooting within the heat exchanger.
The importance of the previous paragraph cannot be over­stated. Users may inadvertently block fresh air intakes af­ter installation.
In the absence of local codes concerning air for combus­tion and ventilation, the following section outlines guide­lines and recommends procedures for operating oil fur­naces in a manner that ensures efficient and safe operation. Special consideration must be given to combus­tion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. It can also cause property damage.
All oil-fired appliances require air to be used for the com­bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will oper­ate in an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel-burning ap­pliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans,
or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down-draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which termi­nate outside the space containing the furnace. This is es­pecially important when the furnace is mounted on a plat­form in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condi­tion. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid­ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel-fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centimeters). One opening shall be within 12" (305 mm) of the top of the enclosure and one opening within 12" (305 mm) of the bottom (See figure 1).
Page 5
Page 6
Equipment In Confined Space
All Air From Inside
Chimney or
t
Oil Ven
Oil
Furnace
NOTE−Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (614.5 square centimeters).
Water
Heater
Openings
(To Adjacent Room)
Figure 1
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305 mm) of the top of the enclosure and one within 12" (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure. (See figure 2.) When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 3).
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3" (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cover­ing is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera­tion.
Equipment In Confined Space
All Air From Outside
Chimney
Or Oil
Vent
Oil
Furnace
NOTE−Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equipment in the enclosure.
Water
Heate
r
Outlet Air
Inlet Air
Figure 3
Equipment In Confined Space
All Air From Outside
(Inlet Air from Crawl Space and Outlet Air to
Ventilated Attic)
Chimney or
Oil Vent
Ventilation Louvers (Each End Of Attic)
Oil
Furnace
Ventilation
Louvers
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
Outlet
Ai
r
Water
Heater
Inlet
Air
Figure 2
CAUTION
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re­sult in a fire hazard or injury.
CAUTION
The barometric draft control shall be in the same at­mospheric pressure zone as the combustion air in­let to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard or injury.
Locate & Level the Unit
Set the unit in desired location keeping in mind the clear­ances listed in table 2. Also keep in mind oil supply connec­tions, electrical supply, flue connections and sufficient clear­ance for installing and servicing unit.
Page 6
Page 7
Level the unit from side to side and from front to rear. If the furnace is not level, place fireproof wedges or shims be­tween the low side of the furnace and the floor. Make sure the weight of the furnace is distributed evenly on all four corners. Strain on sides of cabinet causing cracking and popping noises may occur if weight of furnace is not evenly distributed.
Adjustments
Neither the nozzle setting nor the air adjustments are fac­tory set. The furnace is fire−tested and the limit control is checked to make sure it functions properly; no factory set­tings are made. During installation, the furnace must be set up." The installing dealer/contractor must have and use proper test equipment in order to correctly set up the oil furnace. Proper testing equipment is required to ensure correct operation of the unit. The use of test equipment is now more critical than ever due to tighter tolerances need­ed to keep the furnace operating efficiently.
Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
S Draft gauge S CO
or O2 analyzer
2
S Smoke tester S Pressure gauge S High temperature thermometer S Beckett T−501 or Z−2000 nozzle gauge S Oil vacuum gauge S Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow­ing section for correct adjustment procedures.
Adjusting the Nozzle
Proper adjustment of the nozzle assembly is critical. Before the flue pipe and oil lines are installed, the nozzle assembly must be checked for proper depth and alignment. You must remove the entire burner assembly (not just the nozzle) from the furnace to check the nozzle depth and alignment. The smaller sized firing nozzle has been factory−installed. This should be verified by the installer. A larger nozzle has been provided in the bag assembly for use with SLO183UFV86, 114 and 150 units. Inspect the spark transformer leads also to ensure they are still attached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re­moving the burner assembly from the vestibule. Loosen the nuts and turn the whole burner assembly clockwise (figure 4) to remove the entire burner assembly from the furnace. There is adequate wire to remove the burner with­out disconnecting wires. Once removed, turn the burner around in the vest panel area.
SLO183UFV Series Burner Removal
First, loosen three nuts which
attach burner to vest panel.
Next, rotate burner clockwise on slots then pull toward you.
Figure 4
To correctly check and adjust the nozzle depth and align­ment, use the Beckett T−501 or Z−2000 gauge.
To check the oil nozzle depth, insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the face of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. If necessary, loosen the escutcheon plate se­curing screw and slide the entire nozzle assembly forward or backward within the air tube (figure 5). Re−secure es­cutcheon plate screw when adjustment is completed.
To check nozzle alignment, again insert the small end of gauge into the end cone and measure the nozzle and electrode alignment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not centered, but found to be too far left or right, a new nozzle assembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line.
Take care to properly re−install burner assembly when nozzle adjustment has been completed.
Beckett Oil Burner Nozzle Adjustment
Burner must be removed from
furnace for this procedure.
T−501 Gauge
To Adjust Nozzle
1−Loosen escutcheon plate screw.
2−Slide entire nozzle/electrode assembly back and forth inside air tube until nozzle just touches gauge.
2
1
Escutcheon Plate
Figure 5
Page 7
Page 8
Indoor Coil Placement
In cooling / heat pump applications, Lennox recommends that the indoor coil be installed at least 4 inches above the top of the furnace cabinet to allow proper airflow. If coil cabinet does not provide proper clearance, use field−fabricated tran­sition.
Venting
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re­sult in a fire hazard.
WARNING
The barometric draft control shall be in the same at­mospheric pressure zone as the combustion air in­let to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
3 − The vent connector should not be smaller than the
outlet diameter of the vent outlet of the furnace.
4 − Pipe should be at least 24 gauge galvanized.
5 − Single wall vent pipe should not run outside or through
any unconditioned space.
6 − Chimney should extend 3 feet (0.9 m) above highest
point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7 − The vent must not pass through a floor or ceiling.
Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.
8 − The vent may pass through a wall where provisions
have been made for a thimble as specified in the Stan­dards of the National Board of Fire Underwriters. See figure 4.
Wall Thimble
Thimble
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo­tor oil, gasoline, paint thinner, etc.) may ignite by spontaneous combustion creating a fire hazard.
WARNING
This furnace is certified for use with type L" vent. B" vent must not be used with oil furnaces.
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized ac­cording to the requirements of the National Fire Protection Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is re­quired during burner operation.
1 − Local building codes may have more stringent instal-
lation requirements and should be consulted before installation of unit.
2 − The vent connector should be as short as possible to
do the job.
Combustible
Wall
Vent Pipe
Figure 4
9 − The vent pipe should slope upward toward the chim-
ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers.
10 − Extend the vent pipe into the chimney so that it is flush
with the inside of the chimney liner. Seal the joint be­tween the pipe and the liner.
11 − The furnace shall be connected to either a factory−
built chimney or vent which complies with a recog­nized standard, or to a masonry or concrete chimney which has been lined with a material acceptable to the authority having jurisdiction.
12 − When two or more appliances vent into a common
vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent con­nection. Chimney must be able to sufficiently vent all appliances operating at the same time.
Page 8
Page 9
Factory−Built Chimney
Barometric Draft
Control*
(in either location)
*Barometric draft control may be installed in either vertical or hor­izontal section of flue pipe no less than 12" and no more than 18" from furnace flue outlet.
Factory−
Built
Chimney
Condensate
Drain
Figure 5
Masonry Chimney
Barometric
Draft
Control* (in either location)
Clean Out
*Barometric draft control may be installed in either vertical or hor­izontal section of flue pipe no less than 12" and no more than 18" from furnace flue outlet.
Liner
Masonry
Chimney
Figure 6
13 − The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical draft system.
14 − All unused chimney openings should be closed.
15 − All vent pipe run through unconditioned areas or out-
side shall be constructed of factory−built chimney sec­tions. See figure 5.
16 − Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con­densation in the vent is unacceptable.
17 − Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys­tems operating under positive pressure.
18 − Keep the area around the vent terminal free of snow,
ice and debris.
NOTE − If vent pipe needs to exit from side of cabinet, use the pilot hole (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the other appliances not in operation remain con­nected to the common venting system. If venting system has been installed improperly, the system must be cor­rected as outlined in the previous section.
1 − Seal any unused openings in the common venting
system.
2 − Visually inspect venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3 − Insofar as is practical, close all building doors and win-
dows and all doors between the space in which the ap­pliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not con­nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom ex­hausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust ther­mostat so appliance will operate continuously.
5 − Test for spillage using a draft gauge.
6 − After it has been determined that each appliance re-
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to its previous condi­tion of use.
7 − If improper venting is observed during any of the
above tests, the common venting system must be cor­rected.
Flue Connections
IMPORTANT
When flue pipe is installed at less than minimum clearance listed in table 2, radiation shields must be installed. See figure 6.
Use 24 gauge or heavier galvanized smoke pipe and fit­tings to connect the furnace to the vent. Connect flue pipe to chimney using the least number of elbows and angles possible. Flue pipe or vent connector must be inserted into but not beyond the inside surface of the chimney flue. No reduction in diameter of flue pipe is acceptable. It is best to
Page 9
Page 10
have flue pipe as short and direct as possible. Where two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue or vent connector, plus 50% of the area of any additional flues or vent connectors. Install a barometric draft control (provided) and flue pipe according to instruc­tions packed with control.
Inspect flue pipe annually. Clean soot or ash from flue pipe, if necessary. If pipe is rusted, replace.
Barometric Draft Control Installation
Install the provided barometric draft control in the flue pipe at least 12 inches beyond the furnace flue outlet to pro­vide space for flue gas sampling. The barometric draft con­trol may be installed in either vertical or horizontal sections of the flue pipe; however, it should be positioned no more than 18" beyond the furnace flue outlet. Follow the instruc­tions packed with the barometric draft control.
Alternate Side Flue Connections
The vent pipe may exit the top or sides of the cabinet. A hole is provided in the top cap for top exit. For side exit, lo­cate the center hole punched in the side of the cabinet. See unit dimensions on page 2. Using it as the center point, cut a 6 inch (152 mm) round hole in the cabinet’s side.
Install the barometric draft control within 18 inches of the furnace flue outlet. Attach the provided finishing
plate to cover rough edges.
Radiation Shield Installation
COMBUSTIBLE
MATERIAL
UNIT
CABINET
SLO183UFV UNIT
(TOP)
RADIATION
SHIELDS
1" (25 mm) min
12" (305 mm) min
7" (178
mm) min
Supply & Return Air Plenums
Secure return air plenum to unit using sheet metal screws.
NOTE − The following are suggested procedures that should be followed when installing the supply air plenum.
1. Use sealing strips of fiberglass.
2. In all cases, the plenum should be secured to furnace or evaporator cabinet with sheet metal screws.
3. Install supply and return air ducts as desired.
Oil Supply Line Sizing
Ensure that the restrictions of the piping system, plus any lift involved, do not exceed the capability of the oil pump. Use the following guidelines when determining whether to use a single−or two−stage oil pump.
One−Pipe System
When using a one−pipe system (see figure 7), even with the oil tank that is above the burner and a vacuum of 6" (152 mm) Hg or less, a single−stage fuel pump with a sup­ply line and no return line should be adequate.
Manual bleeding of the fuel pump is required on initial start up. Failure to bleed air from the oil pump could result in an air lock/oil starvation condition.
NOTE − As an extra precaution, cycle heating on and off ten times after bleeding air from the oil pump. This will elim­inate air in the gun assembly.
Oil Piping − One-Pipe System
AIR VENT
FILL PIPE
FUEL PUMP
OIL
TANK
SHUT−OFF VALV E
AUX FILTER
8 ft (2.4 m)
Maximum
One Pipe Lift
NON−
COMBUSTIBLE
SPACERS
NOTE 1−Radiation shields must be constructed of 24 gauge sheet metal minimum.
NOTE 2−Radiation shields required when A is less than 9" (229 mm). NOTE 3−Radiation shields should extend from the top of the unit to
the top of the flue pipe.
SEE
A
NOTE 2
RADIATION SHIELDS (SEE NOTE 1)
FLUE
PIPE
SLO183UFV UNIT
(FRONT)
A
Figure 6
B
SEE
NOTE
3
Figure 7
To determine the correct tubing size for piping, refer to table 3 .
Table 3
One−Pipe Oil Line Sizing
Line Length Pipe Diameter (OD Tubing)
0−50’ (15 m) 3/8" (10 mm)
51−100’ (15 m) 1/2" (12 mm)
Two−Pipe System
When using a two−pipe system (see figure 8) with the oil tank below the level of the burner, use a single−stage fuel pump in lift conditions of up to 10 feet (3 m) and/or a vacu­um of 10" (254 mm) Hg or less. Use a two−stage fuel pump
Page 10
Page 11
when lift exceeds 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg to 15" (381 mm) Hg. Both conditions require the use of a two−pipe system, which consists of a return line
Fuel Pump Usage
Pump Piping Application Maximum Lift (vacuum)
Single−Stage Pump
Two−Stage Pump Two−Pipe System
One−Pipe System 8 ft. (6" Hg vacuum)
Two−Pipe System 10 ft. (12" Hg vacuum)
that purges the fuel pump of air by returning it to the tank. To determine the run and lift for piping, refer to table 5 .
Table 4
10 ft. or greater
(12" to 17" Hg vacuum)
Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe. Install oil supply pipe under floor or near walls to protect it from damage. Avoid running pipes along joists or reverberating surfaces. Always use flare fittings. All fittings must be accessible. Do not use compression fittings.
Oil Piping − Two-Pipe System
AIR VENT
FILL PIPE
RETURN PIPE
OIL
TANK
3"−4"
RETURN
PIPE
outside tank fuel pump above bottom of tank.
(76 mm −102 mm)
R
FUEL PUMP
AUX FILTER
INLET
H
Figure 8
IMPORTANT
Both oil supply and return pipes must be sub­merged in oil in the supply tank.
Table 5
Two−Pipe Maximum Pipe Length (H + R)
3450 RPM − 3 GPH (11.4 LPH)
Single− Stage
Lift H" ft (m)
0’ (0.0) 84 (25.6) 93 (28.3) 100 (30.5) 100 (30.5)
2’ (0.6) 73 (22.3) 85 (25.9) 100 (30.5) 100 (30.5)
4’ (1.2) 63 (19.2) 77 (23.5) 100 (30.5) 100 (30.5)
6 ’ (1.8) 52 (15.8) 69 (21.0) 100 (30.5) 100 (30.5)
8’ (2.4) 42 (12.8) 60 (18.3) 100 (30.5) 100 (30.5)
10’ (3.0) 31 (9.4) 52 (15.9) 100 (30.5) 100 (30.5)
12’ (3.7) 21 (6.4) 44 (13.4) 83 (25.3) 100 (30.5)
14’ (4.3) −−− 36 (11.0) 41 (12.5) 100 (30.5)
16’ (4.9) −−− 27 (8.2) −−− 100 (30.5)
18’ (5.5) −−− −−− −−− 76 (23.2)
3/8" (10 mm) OD Tubing − ft (m)
Two− Stage
Single− Stage
1/2" (12 mm) OD Tubing
Two− Stage
Oil Supply Line & Filter Connections
One−Pipe Systems
CAUTION
Do not install the bypass plug into the pump on one− pipe systems.
The burner is shipped with a single−stage fuel pump set for one−pipe operation. For one−pipe systems, the oil supply pipe is connected to the inlet tap on the pump. A one−pipe system should only be used where there is gravity oil flow to the pump or there is no more than 8 ft. of vertical lift (or 6 in. Hg) from the oil tank to the fuel pump. 1 − Connect the inlet pipe to the pump inlet. Start the burner. 2 − Turn the bleed valve one turn counterclockwise. 3 − Bleed the unit until all air bubbles disappear.
NOTE − Hurried bleeding will prevent the unit from op­erating properly.
4 − If necessary, put GeniSyst primary control into its
4−minute pump priming mode. Refer to table 10.
5 − Tighten the bleed valve securely.
Two−Pipe Systems
If the installation requires a two−pipe operation, install the bypass plug included in the bag which is attached to the pump. To convert the pump, install the bypass plug accord­ing to the provided pump instructions. Notice in the two-
Page 11
Page 12
pipe system the return pipe must terminate in the tank 3" (76 mm) to 4" (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system. This could result in loss of prime.
NOTE− If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.
1. Remove 1/4" plug from return port.
2. Insert bypass plug and tighten it (see figure 8).
3. Attach the return and inlet pipes. Start the burner. Air bleeding is automatic.
NOTE − If a faster bleed is necessary, open the bleed valve.
4. The return pipe must terminate 3" to 4" above the sup­ply pipe inlet (see figure 8).
NOTE − If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.
An oil filter is required for all models. Install filter inside the building between the tank shut-off valve and the burn­er. Locate filter close to burner for easy maintenance. Table 6 lists the filters for the SLO183UFV furnace.
Table 6
Oil Filters Cat. No.
10 micron filter (no mounting bracket)
10 micron filter (mounting bracket) 53P92
10 micron replacement cartridge for filter, 45 gph
Filter restriction indicator gauge
81P89
53P93
53P90
Electrical
All wiring must conform to the National Electric Code (NEC), or Canadian Electric Code (CEC) and any local codes. Refer to figure 7 for typical unit wiring diagram. See figures and for field wiring. Refer to figure 11 for terminal designations on blower control.
1 − Refer to appliance rating plate for proper fuse size. 2 − Install room thermostat and make wire connections to
the fan control board. Avoid installing thermostat on an outside wall or where it can be affected by radiant heat. Set the adjustable heat anticipator on thermostat ac­cording to the wiring diagram sticker provided on unit.
3 − Install a separate fused disconnect switch near unit so
power can be shut off for servicing.
4 − Complete line voltage wiring from disconnect switch
near unit to make-up box.
NOTE − An equipment ground screw is provided. Refer to unit wiring diagram. Ground unit using a suitable ground wire.
5 − A 24V dehumidistat or ComfortSense® 7000 input
(from terminal D) can be connected to the reverse−act­ing HUM terminal on the A54 blower control. See fig­ure 11.
WARNING
Run 24V Class II wiring only through specified low voltage opening. Run line voltage wiring only through specified high voltage opening. Do not combine voltage in one opening.
Consult burner manufacturer’s instructions packaged with unit for further details concerning oil supply pipe connec­tions.
Leak Check
After oil piping is completed, carefully check all piping con­nections (factory and field) for oil leaks.
Oil Pipe Heater (Optional)
A heater for the oil pipe is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial start−up.
CAUTION
USE COPPER CONDUCTORS ONLY.
IMPORTANT
If using a programmable thermostat, be sure to use a type of thermostat that retains its memory in event of a power loss.
Page 12
Page 13
Typical SLO183UFV Wiring Diagram
9
1
ST9103A
A15
OIL DELAY
Figure 7
Page 13
A54
Page 14
Field Wiring Diagrams
1 Heat / 1 Cool
ComfortSense
®
7000 L7724U
1 Heat / 2 Cool
ComfortSense® 7000 L7724U
1 Heat / 1 Cool
ComfortSense
with Thermostat Dehumidification Mode
®
7000 L7724U
1 Heat / 2 Cool
ComfortSense® 7000 L7724U
with Thermostat Dehumidification Mode
Figure 8
Page 14
Page 15
Field Wiring Diagrams (Continued)
Dual Fuel Single−Stage Heat Pump
ComfortSense® 7000 L7724U
with Dual Fuel Control Mode
Dual Fuel Two−Stage Heat Pump
ComfortSense® 7000 L7724U
with Dual Fuel Control Mode
Dual Fuel Two−Stage Heat Pump
ComfortSense® 7000 L7724U
with Dual Fuel Control Mode
and Thermostat Dehumidification Mode
Figure 9
Page 15
Page 16
Blower Control (A54)
When the demand for cool is met, the blower ramps down to 82% CFM for 60 seconds, then turns off.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
SLO183UFV units are equipped with a variable speed blower motor which is capable of maintaining a specified CFM throughout the external static range. Harmony zone controls cannot be used with this furnace since the ECM motor is not programmed for variable speed operation. The blower motor is controlled by jumper selections made on the A54 blower control. Jumpers are available to select both heating and cooling blower speeds, as well as adjust­ment rates for cooling blower speeds and a test mode. Blower control settings and operation are described in this section.
The units are factory−set for nominal airflow for each mod­el. Figure 11 shows the blower control. Use table 7 to deter­mine the correct air volume for operation in heat and cool mode. Read this section thoroughly before adjusting the jumpers to obtain the appropriate blower speed. To change jumper positions, gently pull the jumper off the pins and re−position it across the pins that will give the desired blower speed. The following section outlines the different jumper selections available and conditions associated with each one (see figure 11).
COOL (two-stage systems)
This unit is factory−wired for single−stage cooling. For two−stage cooling operation, you must cut the jumper wire from Y1 to Y2 on the A54 blower control. Cut the
jumper close to the Y1 terminal to allow a pigtail connection with the remaining wire from the Y2 terminal and a wire connected to the Y2 terminal of the two−stage thermostat. Refer to field wiring diagrams.
A thermostat call for first-stage cooling closes the R to Y1 circuit on the A54 blower control. The blower motor runs at 57% CFM for the first 7−1/2 minutes of the 1st−stage cool­ing demand. After 7−1/2 minutes, the blower motor runs at 70% CFM until the first−stage demand is satisfied.
Y1
7−1/2 minutes
57%
Y1 − 1st−stage COOL Demand Present y1 − 1st−stage COOL Demand Satisfied Y2 − 2nd−stage COOL Demand Present y2 − 2nd−stage COOL Demand Satisfied
Y1/Y2
y1
60 sec
100%
70%
OFF
y2/Y1
70%
y1
60 sec
57%
OFFCALL
IMPORTANT
The unit is not designed for and will not work with the Harmony zone control system.
COOL (single-stage systems)
The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized. A factory−installed jumper from Y1 to Y2 allows single−stage cooling.
The blower motor runs at 82% CFM for the first 7−1/2 min­utes of each cooling demand to allow for greater humidity removal and to conserve energy. If, after 7−1/2 minutes, the Y demand is not met, 100% CFM is supplied until the demand is satisfied.
Y
7.5 minutes
82%
Y − Cool Demand Present
y − Cool Demand Satisfied
100%
y
60 sec
82%
OFFCALL
If first−stage cooling does not satisfy the demand, the ther­mostat calls for 2nd-stage cooling, closing the R to Y2 cir­cuit on the A54 blower control. The blower motor ramps up to 100% CFM.
When the Y2 demand is met, the blower ramps down to Y1 at 70% CFM until Y1 is met, and ramps down to 57% CFM for 1 minute, then turns off.
Heat Pump
IMPORTANT
For heat pump operation, cut the jumper between R and O near the R terminal of A54 and connect the pigtail to the thermostat O wire (A54 board O" to thermostat O"). See figure 10.
In heat pump mode, a call for heat pump operation follows the same sequence as a call for cooling, with the exception that there is a 30−second blower ramp−up to blower CFM.
Page 16
Page 17
Heat Pump Applications
A15
To blower
motor
A54
Make pigtail connection and run wire from terminal O to O terminal on thermostat.
Clip red jumper from R to O close to R terminal.
Figure 10
ADJUST
The ADJUST pins affect blower motor speed during cool­ing operation only. The ADJUST feature allows the motor to run at normal speed, approximately 15% higher than normal speed, or 15% lower than normal speed during the cooling mode. Table 7 gives three rowsNORM, (+), and (–) with their respective CFM volumes. Notice that the nor­mal NORM" adjustment setting for cool speed position C in table 7 is 800 CFM. The (+)" adjustment setting for that position is 920 CFM (115% of 800 CFM) and the (–)" ad­justment setting is 680 CFM (85% of 800 CFM). After the adjustment setting has been determined, choose the re­maining speed settings from those offered in the table in that row.
HEAT
The unit is factory−set to run at the middle of heating rise range as shown on the unit rating plate. The jumper on the tap marked HEAT must remain in the position given in table
7. The HEAT jumper is used to determine CFM during heat-
ing operation only. These jumper selections are activated only when W1 is energized.
During the heat ON delay, the blower runs at 13% CFM for the first minute, 50% CFM for the second minute, and full CFM after two minutes.
W
60 sec60sec
13%
50%
100%
W − Heat Demand Present
w − Heat Demand Satisfied
w
210 seconds
82%
OFFCALL
When the demand for heat is met, the blower ramps down to 82% CFM for 3−1/2 minutes, then turns off.
TEST
The TEST pin is available to bypass the blower control and run the motor at approximately 70% to make sure that the motor is operational. This is used mainly in troubleshoot­ing. The G terminal must be energized for the motor to run.
CFM LED
The CFM LED located on the blower control flashes one time per 100 cfm to indicate selected blower speed. For example, if the unit is operating at 1000 CFM, the CFM LED will flash 10 times.
At times, the light may appear to flicker or glow. This takes place when the control is communicating with the motor between cycles. This is normal operation.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in table 7. From the table, determine which row most close­ly matches the desired CFM. Once a specific row has been chosen (+, NORMal, or −), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections.
The variable speed motor slowly ramps up to and down from the selected air flow during both cooling and heating demand. This minimizes noise and eliminates the initial blast of air when the blower is initially energized.
Continuous Fan
When the thermostat is set for Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50% of the COOL CFM selected.
G
50%
G − Fan switch ON
g − Fan switch OFF
g
OFFCALL
NOTE − With the proper thermostat and subbase, continu­ous blower operation is possible by closing the R to G cir­cuit.
Dehumidification
The A54 blower control (see figure 11) includes a HUM ter­minal which provides for connection of a humidistat. The JW1 jumper on the blower control must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the selected air flow rate by 18% when humidity levels are high. An LED (D1) lights when the blower is operating in the dehumidification mode.
Humidification
Terminals are provided on the A15 control for 120 volt out­put to operate a humidifier. The HUM" terminal is ener­gized when there is a call for heat. See figure 13.
Indoor Air Quality (IAQ) Accessory
An EAC terminal is provided on the A15 control for 120 volt output to an indoor air quality accessory. The EAC terminal is energized when there is a call for heat, cool, or continu­ous blower. See figure 13.
Page 17
Page 18
Blower Performance {0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range}
ADJUST"
Jumper Setting
(+)
NORM
(–)
(+)
NORM
(–)
(+)
NORM
(–)
Table 7
HEAT" Jumper Speed Position [kBtuh heat input] COOL" Jumper Speed Position
A B C D A B C D
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Model SLO183UFV68/86 Units
Do not use Do not use [−86] [−68]
N/A N/A N/A N/A Same as NORM 1380 650 1150 545 920 435 690 325
N/A N/A N/A N/A 1000 470 750 355 1200 565 1000 470 800 380 600 285
N/A N/A N/A N/A Same as NORM 1020 480 850 400 680 320 510 240
Model SLO183UFV101/114 Units
Do not use Do not use [−120] [−105]
N/A N/A N/A N/A Same as NORM 1610 760 1380 650 1150 540 920 435
N/A N/A N/A N/A 1300 615 1200 565 1400 660 1200 565 1000 470 800 380
N/A N/A N/A N/A Same as NORM 1190 560 1020 480 850 400 680 320
Model SLO183UFV135/150 Units
Do not use [−150] Do not use [−135]
N/A N/A
N/A N/A 1730 816 N/A N/A 1400 660 2000 945 1800 850 1600 755 1200 565
N/A N/A
Same as
NORM
Same as
NORM
N/A N/A
N/A N/A
NOTE − Continuous Fan air volume is 50% of COOL speed.
Same as
NORM
Same as
NORM
2300 1085 2070 975 1840 870 1380 650
1700 800 1530 720 1360 640 1020 480
Blower Control Board (A54)
16−PIN PLUG
(BOARD TO MOTOR)
Figure 11
DIAGNOSTIC LED
ADJUST SELECTOR PINS (Setting affect cooling only)
HEATING SPEED SELECTOR PINS (SEE TABLE)
COOLING SPEED SELECTOR PINS
NOTE − The JW1 resistor must be cut to activate the HUM terminal.
SLO183UFV−86 SLO183UFV−114
SLO183UFV−68 SLO183UFV−101
SLO183UFV−135 SLO183UFV−150
HEAT SPEED SELECTOR PINS (JUMPERS)
Page 18
Page 19
Unit Start−Up & Adjustments
Before starting unit, make sure the oil tank is adequately filled with clean No. 1 or No. 2 furnace oil.
NOTE − Water, rust or other contaminants in oil supply sys­tem will cause malfunction and failure of the internal parts of the fuel pump.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
CAUTION
Blower access door must be in place before start-up.
Burner Start−Up
1 − Set thermostat for heating demand and turn on electri-
cal supply to unit.
2 − Open all shut−off valves in the oil supply line to the
burner.
3 − While the ignition is on, press and release the reset
button on the burner control (hold 1/2 second or less).
4 − Bleed the pump until all froth and bubbles are purged.
The bleed port is located on the bottom of the fuel pump. To bleed, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all the air has been purged.
NOTE − A two−line fuel system will normally bleed itself by forcing air back to the tank through the return line. This type of bleeding procedure is not necessary.
5 − If burner fails to start within the set time, the burner
control will lock out operation. Press the reset button to reset the control as in step 3. See figure on page 3 for burner parts arrangement.
CAUTION
Do not push the reset button on the primary control more than one time.
6 − Repeat steps 4 and 5, if necessary, until pump is fully
primed and oil is free of bubbles. Then, terminate the call for heat. The burner control will resume normal operation
Fuel Pump Pressure Adjustment
Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet. Turn unit on and check pressure and compare to table 9. Adjust if necessary.
Temperature Rise Adjustment
To measure temperature rise, place plenum thermometers in warm air and return air plenums. Locate thermometer in warm air plenum where thermometer will not see" the heat exchanger to prevent it from picking up radiant heat. Set
thermostat to its highest setting to start unit. After plenum thermometers have reached their highest and steadiest readings, subtract the readings. The difference in temper­atures in the supply and return air plenums should approxi­mate the temperatures listed in table 8 and on the ap­pliance rating plate.
If the temperature rise is not within the range listed, check the following items:
D Make sure that properly sized nozzle has been
used (table 9).
D Make sure that fuel pump pressure is correct. D If furnace is in cutback mode, check for:
Dirty filters, Dirty indoor coil, Restricted ducts, closed registers, etc.
Table 8
Temperature Rise
Unit Temperature Rise °F
SLO183UFV68 50 − 80
SLO183UFV86 50 − 80
SLO183UFV101 65 − 75
SLO183UFV114 70 − 80
SLO183UFV135 65 − 75
SLO183UFV150 70 − 80
Limit Control
Limit Control  Do not adjust from factory setting.
Burner Adjustment
The following instructions are essential to the proper op­eration of SLO183UFV series oil furnaces. To prevent sooting, these instructions must be followed in sequence:
1. DraftThis test should be taken at the breach be-
tween the outlet of the vent connector and the baro­metric draft control. Generally a 1/4" hole will need to be drilled for the draft gauge to be inserted into the vent connector.
A minimum of 0.03 draft must be established without the burner in operation. With the burner in operation, the draft should be 0.04 to 0.05. This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good shape and can ac­commodate the products of combustion. The temper­ature in the unconditioned space will also affect the draft if long vent connectors are allowed to get too cold.
2. Overfire DraftThis test should be taken with the
burner in operation. Remove the plug from the center of the inspection port. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02 less than the reading found in the vent connector. If a positive reading is seen at this point, the combustion fan is pumping too much air into the heat exchanger. Make the necessary adjustments with the air shutter or air band.
Page 19
Page 20
Unit
SLO183UFV−68/86 100591−04 ARM−2007
Burner
Number
Beckett
Spec. No.
Table 9
Burner Specifications
Beckett
Air Tube
Part No.
AF46XZT
HS
Input
Rating
BTU/HR
68,000 0.50 gph x 80° B 100 F0 4−3/4 2−3/4
Nozzle Size,
Spray, Angle, &
Pattern
Pump
Pressure
Head
Insertion
Length
Static
Plate
Diameter
SLO183UFV−68/86 100591−04 ARM−2007
SLO183UFV−101/114 100591−05 ARM2008
SLO183UFV−101/114 100591−05 ARM2008
SLO183UFV−135/150 100591−06 ARM2009
SLO183UFV−135/150 100591−06 ARM2009
*Nozzle must be field−installed for conversion to higher heating input. NOTE − All nozzles are Delavan brand.
AF46XTH
S
AF46XNH
S
AF46XNH
S
AF46WPH
S
AF46WPH
S
Air Shutter / Band Adjustment
Loosen this screw to adjust air band.
Air Shutter
Air Band
(Secondary)
Air Band
Figure 12
3. Smoke TestThe smoke test should be taken at the hole drilled in step 1.
Using a smoke test gun, adjust the air so that you will have just a trace (between 0 and #1) of smoke. If the burner is producing more than #1 smoke, adjust the air shutter (primary) and air band (secondary) to reduce the smoke. See figure 12. To adjust the air shutter, loosen the top screw on the air shutter (and lower screw, if necessary). Then, rotate the shutter until the desired smoke level is achieved. If smoke cannot be reduced to the desired level by moving the air shutter, adjust the air band to increase the air. To adjust the air band, loosen the air band screw and rotate the band.This is the starting point. Do not stop here.
4. CO2 TestAgain, take this sample at the vent pipe.
86,000 0.50 gph x 80° B 100 F0 4−3/4 2−3/4
101,000 0.65gph X 80° B 140 F3 4−3/4 2−3/4
114,000 *0.65gph X 80° B 140 F3 4−3/4 2−3/4
135,000 1.00gph x 80° 140 F4 4−3/4 3−3/8
150,000 *1.00gph X 80° B 140 F4 4−3/4 3−3/8
With the unit firing at a trace of smoke, take a sample of the CO2. From the results of this test, a window of op­eration" will be determined. This window of operation establishes some tolerance. The tolerance the install­er builds in provides room within the set-up for those things which might affect combustion. Those things which might affect combustion can then do so without causing the unit to start sooting/smoking. Things which might affect combustion include a nozzle going bad, draft that changes during different climatic condi­tions, dirty oil, dirt obstructing the air inlet, etc.
To build in a window of operation," set up the burner to be 2% less in CO2. For example, if you find a reading of 12% CO2, adjust the air shutter (and air band, if neces­sary) to increase the air and drop the CO2 to 10%.
5. Retest the SmokeWith a drop in the CO2 and in-
crease in the air you should see that the smoke has re­turned to 0.
6. Retest the Overfire DraftThis test serves to con-
firm that you have not increased the air too much. Again you do not want a positive pressure at the test port. It should still be 0.02 less than the draft pressure reading taken at the breach. You may need to increase the stack draft by adjusting the barometric draft con­trol.
7. Stack TemperatureTake a stack temperature read-
ing in the vent pipe. Subtract the room air temperature from the stack temperature. This will give you the net stack temperature. Use the efficiency charts provided in most CO2 analyzers to determine furnace efficiency.
8. When the proper combustion and smoke readings have been achieved, re−tighten the air shutter screw(s) and air band screw.
Page 20
Page 21
Service
CAUTION
NOTE − A heat exchanger clean-out kit ABRSH380 (35K09) is available from Lennox. The Kit includes one radiator brush (which consists of a tapered brush with a 36" spiral wire handle).
Do not tamper with unit controls. Call your qualified service technician.
Servicing the Air Filter
NOTE − Under no circumstances should the access panels to the blower compartment be left off or left partially open.
Throw-Away Type FiltersCheck filters monthly and re­place when necessary to assure proper furnace operation. Replace filters with like kind and size filters.
Reusable Type FiltersFilters should be checked monthly and cleaned when necessary to assure proper fur­nace operation. Use warm water and a mild detergent. Re­place filter when dry. Permanent filters supplied with SLO183UFV furnaces do not require oiling after cleaning. Examine filter label for any for special instructions that may apply.
Servicing the Blower
Blower motor is prelubricated and sealed for extended op­eration. No further lubrication is required. Disconnect pow­er to unit before cleaning blower wheel for debris.
Inspecting the Flue Pipe
The flue pipe should be inspected annually by a qualified service technician. Remove and clean any soot or ash found in the flue pipe. Inspect pipe for holes or rusted areas. If replacement is necessary, replace with the same size and type as required by code. Inspect the flue draft control device and replace if found defective.
Cleaning the Heat Exchanger
1. Remove the vent pipe from the furnace.
2. Remove the locking screws and the caps from the clean out tubes. Remove flue access elbow.
3. Using a long spiral wire brush, sweep down the outer drum of the heat exchanger. Then using the hose at­tachment, vacuum out loose debris.
4. Remove the locking screw and cap from the observa­tion tube and with the spiral wire brush, reach upward toward the rear of the heat exchanger to clean out the crossover tube.
GeniSyst Primary Burner Control
SLO183UFV units are equipped with the Beckett GeniSys­t 7505B primary burner control. The control is positioned on the upper right−hand side of the Beckett AFG burner as­sembly. The control includes a reset button and three sta­tus lights. See figure 13 for location of reset buttons and status lights. Table 10 details reset button operation. Table 11 details status light function.
Additional information on the GeniSyst 7505B primary burner control is provided with this furnace.
Beckett GeniSyst 7505B Primary Burner Control
Reset Button
with Red Status Light
FRONT VIEW
Yellow Pump Prime
Status Light
Green Flame
Status Light
Wiring
Connections
REAR VIEW
CAUTION
Do not attempt to clean the combustion chamber. It can be easily damaged.
5. Replace the three clean out caps and flue access el­bow. Make sure locking screws are secure.
6. Brush out and vacuum the vent outlet area of the outer drum and replace vent pipe.
7. Clean around the burner, blower deck and vestibule area.
Cad Cell
Connections
Figure 13
Page 21
Page 22
Table 10
Reset Button Operation
If the burner is in the
below state:
Valve−on Delay, Trial for Ignition, Ignition Carryover
Run (igniter is shut off) No action
Pump Prime No action Exit Pump Prime mode and return to Standby
Button Click
(press < 1 second)
Go to pump prime (see Priming the Pump" above)
No action
Status Light Function
R
Green Flame Sensed during normal operation (Could be stray
Yellow Control is in pump prime mode or N/A
light during standby)
Reset button currently held for 15+ seconds.
Heating Sequence − Actions & Responses
1. Action: Thermostat calls for heat (W terminal is en-
ergized)
Response:
D ST9103A control (A15) closes oil primary control
TR−TW contacts.
D After 15−second prepurge, power is sent to the oil
delay valve, ignition occurs and flame is established.
D Igition sequence continues for 10 seconds after
flame is sensed. Oil will continue to flow as long as cad cell senses flame.
D Heat fan on ramp timing begins. When timing is
complete, the indoor blower is at heat speed and warm air is delivered to the controlled space.
2. Action: Thermostat ends call for heat (W terminal
is de−energized)
Response:
D After the thermostat is satisfied, the thermostat
circuit opens. The oil delay valve and burner are de−energized.
D Burner is de−energized. D Heat fan off ramp timing begins. When timing is
complete, indoor blower is de−energized.
D Blower control returns to standby mode (oil prima-
ry control and indoor blower are off).
3. Action: Burner fails to light
Response:
D Oil primary control enters soft lockout after ignition
failure (15 seconds without flame being sensed). Push reset button on primary control for one sec­ond to reset soft lockout.
Pushing the reset button will:
Button Hold
(press > 1 second)
tuokcoLtfoSmorfteseRtuokcoL
Disable the Burner: Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.
Table 11
D After soft lockout reset, oil primary control allows
second ignition attempt. Primary control enters hard lockout after second ignition failure (15 sec­onds without flame being sensed). Push reset but­ton on primary control for 15 seconds until light on control turns yellow to reset hard lockout.
D Burner motor is de−energized.
4. Action: Established flame fails
Response:
D Burner motor is de−energized and oil primary con-
trol goes into recycle mode.
D If the fan off delay is longer than the recycle timing,
the indoor blower continues to run on heating speed through the next trial for ignition.
5. Action: Limit Switch Opens
Response:
D Oil primary control de−energizes burner. D Indoor blower is energized immediately at cool
speed.
D A15 control opens oil primary control TR−TW con-
tacts.
D Indoor blower runs as long as limit stays open.
6. Action: Limit Switch Closes
Response: If there is a heating demand, A15 control energizes oil primary control and ignition sequence begins.
Troubleshooting
Burner failure or improper operation can result from a num­ber of different causes. Often the cause can be pinpointed by observing the different types of failure or by the process of elimination. The following troubleshooting charts list some failures, causes and a sequence of steps to isolate the point of failure. Check the simplest and most obvious items before progressing to other items.
Page 22
Button Hold
(press 15+ seconds)
Reset from Restricted (Hard) Lockout
Enables pump priming After the reset button has been held for 15 seconds. The button can then be clicked during the next ignition sequence to enter pump prime mode.
gnihsalFylsuounitnoCnOroloCthgiL
tuokcoLtfoStuokcoL)draH(detcirtseRde
Recycle
Page 23
Troubleshooting: Blower Control Operating Sequence
Action System Response
Thermostat calls for heat. (W terminal is energized.)
Thermostat ends call for heat. (W terminal is de−energized.)
Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control).
Established flame fails. Burner motor is de−energized and oil primary control goes into recycle mode.
Thermostat begins call for cool. (G and Y terminals are energized.)
Thermostat ends call for cool. (G and Y terminals are de−energized.)
Thermostat begins call for fan. (G terminal is energized.)
Thermostat ends call for fan. (G terminal is de−energized.)
ST9103A closes oil primary control TR−TW contacts.
Ignition system and oil primary control start the furnace. Oil flows as long as cad cell senses flame.
Call for heat energizes burner motor and blower ramping begins for heating mode. When ramping is complete, the indoor blower is energized at heat speed and warm air is delivered to the controlled space.
Oil primary control is de−energized, terminating the burner cycle.
Heat fan off delay timing begins. When timing is complete, the indoor blower is de−ener­gized.
ST9103A returns to standby mode (oil primary control and circulating fan are off).
Burner motor is de−energized.
If heat fan has started, it continues through the selected delay off period.
If selected heat fan off delay is longer than the recycle delay timing, the heat fan continues to run through the next trial for ignition.
Indoor blower is energized at the cool speed.
Cooling compressor turns on immediately.
Cooling compressor turns off immediately and indoor blower speed ramps down. Circulat­ing fan shuts off after 60 seconds.
Indoor blower is energized immediately at 50% of cool speed.
ST9103A may be factory−configured to operate heat speed in this mode.
Indoor blower is de−energized.
Limit switch string opens. Oil primary control shuts off the burner.
Indoor blower is energized immediately at heat speed.
ST9103A opens oil primary control TR−TW contacts.
Indoor blower runs as long as limit string stays open.
If there is a call for cooling or fan, the indoor blower switches from heat speed to cool speed.
Limit switch string closes. ST9103A begins heat fan off delay sequence.
Indoor blower turns off after the selected heat fan off delay timing.
ST9103A closes oil primary control TR−TW contacts.
Oil primary control is energized, initiating burner ignition.
Continuous circulating fan is connected. (Optional connectors are available for separate circulat­ing fan speed tap.)
IAQ accessory is connected. (Optional connectors are available for 120 Vac acces­sories.)
Humidity control is connected. (Optional connectors are available for 120 Vac humidifi­er.)
Indoor blower is energized at 50% of cool speed when there is no call for heat, cool or fan.
If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the continuous fan speed tap before energizing the other fan speed.
EAC terminals (for IAQ accessories) are energized when the indoor blower is energized in either the heat or cool speed. EAC terminals are not energized when the optional continu­ous fan terminal is energized.
Humidifier connections are energized when the burner motor is energized.
Page 23
Page 24
Troubleshooting: Burner fails to start.
Source Procedure Causes Correction
Thermostat in OFF or COOL Switch to HEAT.
Thermostat Check thermostat settings.
Check burner motor, primary
Safety Overloads
Power
Thermostat
Cad Cell
Primary Control
Burner
safety control, & auxiliary limit switch.
Check furnace disconnect switch & main disconnect.
Touch jumper wire across TR− TW terminals on primary control. If burner starts, then fault is in the thermostat circuit.
Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit.
Place trouble light between the orange and white leads. No light indicates that no power is going to the control.
Place trouble light between the orange and white leads. No light indicates faulty control.
Place the trouble light between the orange and white leads to the burner motor. No light indi­cates that no power is getting to the motor.
Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault.
Thermostat is set too low
Burner motor overload tripped Push reset button pump motor.
Primary control tripped on safe­ty
Auxiliary limit switch tripped on safety
Open switch Close switch.
Blown fuse or tripped circuit breaker
Broken or loose thermostat wires
Loose thermostat screw con­nection
Dirty thermostat contacts Clean contacts.
Thermostat not level Level thermostat.
Faulty thermostat Replace thermostat.
Open circuit in wiring between ST9103A and oil primary con­trol.
Flame detector leads are shorted
Flame detector exposed to light Seal off false source of light.
short circuit in the flame detec­tor
Primary or auxiliary control switch is open
Open circuit between discon­nect switch and limit control
Low line voltage or power fail­ure
Failed internal control circuit Replace the control.
Blown fuse Replace the fuse.
Binding burner blower wheel
Seized fuel pump
Failed burner motor Replace the motor.
Turn thermostat to higher tem­perature.
Reset primary control.
Reset auxiliary limit.
Replace fuse or reset circuit breaker.
Repair or replace wires.
Tighten connection.
Check wiring between ST9103A and oil primary con­trol.
Separate leads.
Replace detector.
Check adjustment. Set the maximum setting.
Jumper terminals; if burner starts, switch is faulty, replace control.
Trace wiring and repair or re­place it.
Call the power company.
Turn off power and rotate the blower wheel by hand. If seized, free the wheel or re­place the fuel pump.
Page 24
Page 25
Troubleshooting: Burner starts, but no flame is established.
Source Procedure Causes Correction
Oil Supply
Oil Filters & Oil Line
Oil Pump
Nozzle
Ignition Electrodes
Ignition
Transformer
Burner Motor
Check tank gauge or use dip stick.
Coat dip stick with litmus paste and insert into bottom of tank.
Listen for pump whine. Tank shut−off valve closed Open valve.
Listen for pump whine.
Open bleed valve or gauge port. Start the burner. No oil or milky oil indicates loss or prime.
Install pressure gauge on pump and read pressure. Should not be less than 140 psi.
Observe the oil spray (gun as­sembly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build− up around orifice.
Remove gun assembly and in­spect electrodes.
Start burner and observe spark. Check line voltage to transform­er primary.
Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for bind­ing or excessive drag.
No oil in tank Fill tank.
Water in oil tank
Oil line filter is plugged Replace filter cartridges.
Kinks or restriction in oil line Repair or replace oil line.
Plugged fuel pump strainer Clean strainer or replace pump.
Air leak in oil supply line
Pump is partially or completely frozen. No pressure and the motor locks out on overload.
Coupling disengaged or broken
− no pressure
Fuel pressure too low Adjust to 140 psi.
Nozzle orifice plugged
Nozzle strainer plugged
Poor or off center spray
Fouled or shorted electrodes
Dirty electrodes
Eroded electrode tips
Improper electrode gap spacing
Improper position of electrode tips
Bad buss bar connection Retension and realign.
Cracked or chipped insulators Replace electrode.
Low line voltage
Burned out transformer wind­ings.
No spark or weak spark
Low line voltage
Pump or blower overloading motor
Faulty motor Replace motor.
If water depth exceeds 1 inch, pump or drain water.
Locate and correct leak.
Tighten all connections.
Replace pump.
Re−engage or replace coupling.
Replace nozzle with the same size, spray angle, and spray pattern.
Clean or replace electrodes.
Clean electrode tips and use T−501 gauge to reset the gap to 5/32 inches and correctly posi­tion tips.
Check voltage at power source. Correct cause of voltage drop or call the power company.
Replace the transformer.
Properly ground the transformer case.
Check voltage at power source. Correct cause of voltage drop or the call power company.
Correct cause of overloading.
Page 25
Page 26
Troubleshooting: Burner starts and fires, but lock out on safety.
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Reduce combustion air − check combustion.
Increase combustion air − check combustion.
Adjust barometric draft control for correct draft.
Correct draft or remove restric­tion.
Secure connections or replace cad cell holder and wire leads.
Check cad cell for proper align­ment. Check cad cell face and clean, if necessary.
Poor Fire
Flame Detector
Primary Control
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
If burner con­tinues to run, this may be due to poor fire. Inspect fire.
If fire is good, fault is in the flame detector. Check detec­tor circuit.
If burner locks out on safety, fault is in the primary con­trol.
Too much air − −lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Cad cell cannot sense flame
Primary control circuit failed Replace primary control.
Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Poor Fire
Flame Detector
Oil Supply
After burner fires, immedi­ately jumper across flame detector termi­nals at the pri­mary control.
Listen for pump whine
If burner con­tinues to run (does not lock out of safety), fault may be due to poor fire. Inspect fire.
If fire is good, fault is in the flame detector. Check detec­tor circuit.
If burner loses flame (does not lock out on safety), fault is in the fuel sys­tem.
Too much air − − lean short fire
Too little air − − long dirty fire
Excessive draft
Too little draft or restriction
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Cad cell cannot sense flame
Pump loses prime − air slug Prime pump at bleed port
Pump loses prime − air leak in supply line
Water slug in line Check oil tank for water (over 1
Partially plugged nozzle or nozzle strainer
Restriction in oil line Clear restriction.
Plugged fuel pump strainer Clean strainer or replace pump.
Cold oil − outdoor tank Change to number 1 oil.
Reduce combustion air − check combustion.
Increase combustion air − check combustion.
Adjust barometric draft control for correct draft.
Correct draft or remove restric­tion.
Secure connections or replace cad cell holder and wire leads.
Check cad cell for proper align­ment. Check cad cell face and clean, if necessary.
Check supply line for loose con­nections and tighten fittings.
inch) pump or drain out water. Replace nozzle.
Page 26
Page 27
Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Source Procedure Causes Correction
Heat anticipator set too low Correct heat anticipator setting.
Thermostat Check thermostat.
Connect voltmeter between line voltage connections to primary
Limit Control
control (black & white leads). If burner cycles due to power inter­ruption, it is cycling on limit.
Vibration at thermostat Correct source of vibration.
Thermostat in the path of a warm air draft
Dirty furnace air filters Clean or replace filter.
Temperature rise too high
Blower motor seized or burned out
Blower wheel dirty Clean blower wheel.
Wrong motor rotation Replace motor.
Restrictions in return or supply air system
Shield thermostat from draft or relocate.
Check fo proper nozzle size. Replace nozzle, if necessary. Check for restrictions and re­move, if necessary. Check speed tap jumper and make sure it is still in factory position.
Replace motor.
Correct cause of restriction.
Power
If voltage fluctuates, fault is in the power source. Recheck voltage at the power source.
Loose wiring connection Locate and secure connection.
Low or fluctuating line voltage Call power company.
Troubleshooting: Burner runs continuously (too much heat).
Source Procedure Causes Correction
Thermostat
Primary control
Disconnect thermostat wires at the pri­mary control.
If burner turns off, fault is in the thermostat circuit.
If burner does not turn off, fault is in the primary control.
Shorted or welded thermostat contacts
Stuck thermostat bimetal
Thermostat not level Level thermostat.
Shorted thermostat wires Repair short or replace wires.
Thermostat out of calibration Replace thermostat.
Thermostat in cold draft
Failed primary control Replace the primary control.
Repair or replace the thermo­stat.
Clear obstruction or replace thermostat.
Correct draft or relocate the thermostat.
Page 27
Page 28
Troubleshooting: Burner runs continuously (too little heat).
Source Procedure Causes Correction
Too much combustion air Reduce combustion air.
Combustion
Oil Pressure
Check burner combustion for CO2, stack tem­perature, and smoke
Inspect fire and check
oil pressure.
Low CO
2
less
than 10%.
High smoke reading more than a trace.
High stack tem­perature is more than 550
_F Net.
Air leaks into heat exchanger around inspection door, etc.
Excessive overfire draft
Incorrect nozzle assembly depth
Dirty or plugged heat exchanger
Insufficient overfire draft Increase draft.
Incorrect nozzle assembly depth
Too little combustion air Increase combustion air.
Low volume indoor blower air
Dirty heat exchanger Clean heat exchanger.
Dirty burner blower wheel Clean burner blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or dampers
Partially plugged or bad nozzle Replace nozzle.
Oil pressure is too low (less than 140 psi.)
Correct cause of air leak.
Adjust barometric draft control for correct draft.
Set to 1.13.
Clean heat exchanger.
Readjust burner.
Set to 1.13.
Check pump coupling for wear / slippage.
Readjust registers or damp­ers.
Increase oil pressure to 140 psi.
Page 28
Loading...